10-80 kW
400 V
Installation Manual
Symme
Qui
tra® PX
ck-Start
User
Guide
Contents
Installation Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Wiring through bottom . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Interconnect schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
EPO switch wiring (if required) . . . . . . . . . . . . . . . . . . . . . . . . 10
Input/output wiring - dual mains installation . . . . . . . . . . . . . . 10
Input/output wiring - single mains installation . . . . . . . . . . . . . 12
Communication wiring to optional equipment . . . . . . . . . . . . . 14
Connection of Maintenance Bypass Panel . . . . . . . . . . . . . . . . 15
Wiring verification procedure . . . . . . . . . . . . . . . . . . . . . . . . . 16
Connecting communication cables . . . . . . . . . . . . . . . . . . . . . 17
Installation site information . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
This guide contains important instructions that should be followed when handling the UPS, Battery
Enclosures, and Batteries.
WARNING!
Risk of electric shock.
CAUTION!
Read this information.
Note
Indicates that more information is available on this subject in a different section of this
manual.
Indicates that more information is available on the same subject in a different manual.
See also
Operating Conditions
Installation safety
WARNING!
• After the UPS has been electrically wired, do not start it up. Start-up is
commisioned to APC-authorized personnel only.
• All electrical power and control wiring must be installed by a qualified
electrician and comply with local and national codes.
• When connected, the UPS contains energy from both AC and DC sources.
Hazardous voltage from batteries may be present even when the unit is
disconnected from the power source. Follow Total Power Off Procedure to
completely de-energize the system (see Total Power Off procedure section).
• Remove all conductive jewelry such as chains, watches, and rings before
handling Battery Units and Power Modules.
• Battery Units and Power Modules do not contain serviceable parts. Only APC
authorized personnel may open Battery Units and Power Modules.
• Do not dispose of batteries in a fire, as they may explode. Do not mutilate
batteries, as released electrolyte is harmful to the skin and eyes and may be
toxic.
• For configurations including customer-supplied external batteries, refer to
manufacturer’s battery installation and maintenance instructions.
• When handling batteries, use tools with insulated handles, and wear insulated
gloves and boots. Do not lay tools or metal objects on top of batteries.
• When replacing batteries, replace with the same number and type as installed.
WARNING!
Before electrical installation begins, verify that the UPS is in the Total Power Off
mode by following this procedure.
UPS
INTELLIG
ENCE
MODULE
INTELLIG
ENCE
MODULE
?
SE
YN
SA
TB
EL
ME
XR Communic
ations
ide
er , PX
GuV
DOCUM
on 0
Op kW a®
ati 20
sic - 40 etr
ENT
Ba 10 mm
STO
Sy
RAG
E
Battery Enclosure
BATTERY UNIT
BATTER
Y UNIT
ON Mains
UPS supply
OFF
Set the DC Disconnect on all Battery Enclosures in the configuration to the OFF position.
Disconnect all Battery Units by removing or pulling out to red disconnect line.
Set the upstream Mains Power to the OFF or LOCKED OUT position. If the UPS has dual
mains supply, set both supplies to the OFF or LOCKED OUT position.
CAUTION!
To ensure solid stability, do not pull Battery Units out beyond the red disconnect line
unless completely removing them from the enclosure.
Input
Output
Notes
Recommended source connections.
1. Input electricity to be provided from a dedicated, grounded 4-wire star (Wye) power supply
source with a grounded neutral.
2. If a grounded 3- wire power supply source is present, a Delta to star (Wye) isolation transformer
on UPS input is required.
3. Ensure clockwise voltage phase rotation (L1, L2, L3 or RST).
Recommended current protection.
4. Mains input: 200 Amp 3-pole AC circuit breaker or a 200 Amp gL fuse with a withstand short-
circuit current rating of 30 kA.
5. Bypass input: 125 Amp gL fuse.
Recommended current protection (single mains configurations).
6. Mains input: 200 Amp gL fuse.
Recoomended output (single and dual mains).
7. 125 Amp 3-pole AC circuit breaker or a 125 Amp gL fuse with a withstand short-circuit current
of 30 kA.
8. Neutral wires: rate for 173% output phase current if feeding all switch mode power supply loads
without power factor corrections.
Recommended wiring for 30oC temperature environments (single and dual mains
systems)
All cables must comply with IEC/EN 60364-4-4-41 and local electrical regulations.
Neutral Wires: rate for 173% of output phase current if feeding all switch mode power supply loads without
input power factor corrections.
WARNING!
This is a Class A UPS product. In a domestic environment, this product may cause
radio interference, in which case, the user may be required to take additional
measures.
WARNING!
The UPS system has no built-in disconnection devices for AC output and DC input.
When installing the UPS system, ensure that disconnection devices are provided as
separate parts.
CAUTION!
For customer-supplied external batteries, overcurrent protection and disconnecting
device for the battery circuits must be provided by the customer.
Make sure the UPS is in its location of use before wiring begins.
Note
CAUTION!
Do not move the UPS after the stabilizing feet have been lowered, or equipment
damage may occur.
Punch holes as required and reinstall panel before mounting wiring hardware.
Interconnect schematic
UPS
L1 L2L3 N DC Input L1 L2 L3 N L1 L2 L3 N
Batt +
Maintenance Bypass
4 3 2 1 8 7 6 5 Batt. –
Interface
EPO / Ancillary
14 13 12 11 10 9 8 7 6 5 4 3 2 1 Batt. CT 1 2 3 4 5 6 7 8 9 10 11 12 13 14
PE PE
UPS
L1 L2L3 N L1 L2 L3 N L1 L2 L3 N
DC Input
Batt +
Maintenance Bypass
4 3 2 1 8 7 6 5 Batt. –
Interface
EPO / Ancillary 3 copper
14 13 12 11 10 9 8 7 6 5 4 3 2 1 Batt. CT 1 2 3 4 5 6 7 8 9 10 11 12 13 14
PE PE brackets
between
mains input
and bypass
input
terminals
Output Mains Input
Power Power
As the neutral from AC mains input and AC bypass input is hardwired internally in the
UPS, it is not necessary to install a jumper between the 2 neutral connections in single
mains installations.
Note
The UPS must be connected to either a dry contact or an external 24 VDC source.
The Emergency Power Off (EPO) circuit is considered a Safety Extra Low Voltage (SELV) circuit. A
SELV circuit is isolated from primary circuits through an isolating transformer and designed so that
under normal conditions, the voltage is limited to 42.4 VAC peak or 60 VDC. SELV circuits must be
isolated from all primary circuits. Do not connect any circuit to the EPO terminal block unless it can
be confirmed that the circuit is a SELV circuit. If an external 24 VDC source is used, this source must
comply with the SELV requirements.
EPO switch wiring must comply with local and national codes.
Note
The UPS is designed for both dual and single mains installations. Follow the instructions below to
install the UPS in a dual mains installation:
CAUTION!
Power terminal lug diameter is 10 mm, torque value: 25 Nm.
CAUTION!
Ensure clockwise phase rotation and neutral location.
Route all power input wires (Mains and bypass) through the supplied choke and attach choke
with strips.
Connect power input and output wiring to terminals as shown. Connect either one cable lug on
each busbar or two on each - one from the front and one from the rear of each busbar (see wire
Proceed with ground connections as shown. Feed ground wire through provided ferrite beads.
Feed DC cables through the chase nipple in the left side of the UPS and into the Battery
Enclosure.
Connect the provided EPO cable to the EPO port in the UPS. Feed the cable through the chase
nipple into the Battery Enclosure and attach it to the EPO port as illustrated.
N
N
L3
L1
L2 L3
L2 +
L2
–
L1
L3
AC Output L1
N CT AC Mains Input
AC Bypass Input
DC
input
The UPS is designed for both single and dual mains installations. Follow the instructions below for a
single mains installation:
CAUTION!
Power terminal lug diameter is 10 mm; torque value: 25 Nm.
CAUTION!
Ensure clockwise phase rotation and neutral location.
Remove brackets on the L1, L2, L3 Mains Input and on L1, L2, L3 Bypass Input. Save brackets
for later conversion to dual mains if applicable.
Route input wires through the supplied choke and secure the choke with the 4 strips (one in each
corner).
Attach the 3 copper brackets L1, L2. and L3 (shipped in plastic bag in the cable-land area of the
UPS), using the provided bolts and nuts as illustrated.
Connect cables to the AC mains input busbars, using the provided bolts and nuts.
Proceed with ground connections as shown. Feed ground wire through provided ferrite beads.
Feed DC cables through the chase nipple in the left side of the UPS and into the Battery
Enclosure.
Connect provided EPO cable to the EPO port in the UPS. Feed the cable through the chase
nipple into the Battery Enclosure and attach it to the EPO port as illustrated.
L3 N
L2
L1 L3
L2
L1
C
Battery Enclosure UPS
As the neutral from AC mains input and AC bypass input is hardwired internally in the
UPS, it is not necessary to install a jumber between the 2 neutral connections in single
Note
mains installations.
CAUTION!
Connect the EPO as shown in the interconnect schematic.
4 Ground 8 Ground
3/2 Relay Coil 1 7/6 Relay Coil 2
1 Internal Power 5 Internal Power
J6: For use only with ISX
+24V Supply +24V Supply
J3
AC AC
Blue
Output Input
J3
J1
AC AC
Output Input
CAUTION!
Do not install modules in the UPS.
Use following procedure to verify that the UPS has been wired properly:
Measured voltage must be between 200 and 250. If not, stop! Verify correct wiring
(correct location of N) from the power source to the input wiring connections. Repeat
Note
this step.
Record voltages between:
Mains Input:
L1 and N: _________ L2 and N: ________ L3 and N: _______
5 4. Verify clockwise phase rotation (L1, L2, L3 or RST) using a phase rotation meter.
5 5. Turn on the System Enable Switch. Wait 1 minute for the system to self test. Ignore
display warning (fault light will be on).
5 6. Test the EPO operation (applicable to installations with EPO switches only). The
System Enable Switch should trip to the Stand-By position, and the system should
shut down completely. If not, check the connections and the EPO switch to ensure
that they are installed and functioning correctly. For installations with Battery
Enclosures, the DC disconnect should trip to the OFF position at the EPO test.
5 7. Successful completion of steps 1 through 6 indicates that the UPS wiring is
correctly installed and functioning correctly. Turn off breakers and switches and
shut down utility power to the system input. See Total Power Off Procedure.
If a problem occurs, note UPS serial# (to the left of the XR Communication Card) and
date purchased before calling Customer Support.
Note
WARNING!
Ensure Total Power Off before removing side panel (see Total power OFF
procedure).
Use 5-m standard Cat 5 Data cable (supplied). If cable length is inadequate, a longer
Cat 5 cable, or couplers, can be used (not supplied). Maximum length of standard CAT
5 data cable: 50 m.
Note
INTELL
IGENCE
MODUL
E
INTELL
IGENCE
MODUL
E
?
de
n 0V
ra , 20PX
ui
G
pe ¤
O kWra
tio
ic 40 et
as - m
B 10 m
DOCU
Sy
MENT
STOR
AGE
puter
ote Com ce
Rem ew Interfa 10/100
Bas e-T
r Vi Status
Powe
lay X/TX
Disp Link-R /100
10
ce Reset nt
me
te r Interfa k Ma
nage
mpu twor
17 Ne
lay / Co AP96
Disp 2
Port
1
Port
ations
unic
omm
XR C
Card
itor
r Mon
h Gea
Switc
Remove right terminator from Port 2. Save for reinstallation in Battery Enclosure. Connect
Battery Communication cable to port 2.
Depress latches.
Route cables through front holes of UPS. Exit UPS from bottom or top as required.
If your UPS has been installed between devices, and side panels are inaccessible,
remove the Bypass Static Switch Module to gain access.
Note
This section should be completed by the electrician after the wiring installation:
Installed at (company):_____________________________________________________
Telephone/country:______________------______________________________________
Location of
protection devices: Room _______________ Breaker ID ______________________
Ground connection
method and location:____________________________________________________
Leave this guide in the Documentation Storage Tray located at the bottom of the UPS.
Note
Hospital-grade wiring devices and leakage current protection may be ordered as options on many
APC UPS systems. APC does not claim that units with these modifications are certified or listed as
hospital-grade by APC or any other organization. Therefore these units do not meet the requirements
for use in direct patient care.
The limited warranty provided by American Power Conversion Corporation (“APC”) in this
Statement of Limited Factory Warranty applies only to Products you purchase for your commercial or
industrial use in the ordinary course of your business.
Symmetra PX UPS
Terms of warranty
APC warrants that the Product shall be free from defects in materials and workmanship, for a period
of two (2) years from the date of start-up when APC authorized service personnel has performed the
start-up of the Product. In the event that the Product fails to meet the foregoing warranty, APC shall
repair or replace any defective parts. Any parts furnished under this warranty may be new or factory
remanufactured.
This Warranty is extended to the first person, firm, association or corporation for whom the APC
Product specified herein (herein referred to as “You or Your”.) This Warranty is not transferable or
assignable without the prior written permission of APC.
Assignment of warranties
APC will assign to you any warranties which are made by manufacturers and suppliers of
components of the APC Product and which are assignable. Any such warranties are assigned “as is”
and APC makes no representations as to the effectiveness or extent of such warranties, assumes no
responsibility for any matters which may be warranted by such manufacturers or suppliers and
extends no coverage under this Warranty to such components.
Drawings, descriptions
APC warrants for the Warranty Period and on the terms of the Warranty set forth herein that the APC
Product will substantially conform to the descriptions contained in APC's Official Published
Specifications or any the drawings certified and agreed to by an authorized APC representative, if
applicable thereto (“Specifications”). It is understood that the Specifications are not warranties of
performance and not warranties of fitness for a particular purpose.
EXCLUSIONS
APC SHALL NOT BE LIABLE UNDER THE WARRANTY IF ITS TESTING AND
EXAMINATION DISCLOSES THAT THE ALLEGED DEFECT IN THE PRODUCT DOES
NOT EXIST OR WAS CAUSED BY YOUR OR ANY THIRD PERSON’S MISUSE,
NEGLIGENCE, IMPROPER INSTALLATION OR TESTING, UNAUTHORIZED
ATTEMPTS TO REPAIR OR MODIFY, OR ANY OTHER CAUSE BEYOND THE RANGE
OF THE INTENDED USE, OR BY ACCIDENT, FIRE, LIGHTNING OR OTHER HAZARD.
Parts
• APC warrants the parts of their systems for 2 years. This warranty only covers the cost of the
part and not the labor for installation.
• Calls for warranty parts requests need to have specific unit information (serial number, model
number, job number) to allow proper identification and processing of the warranty part
transaction.
• A purchase order may be required to issue a warranty part(s). An invoice will be sent once the
part(s) are shipped to the field. You have 30 days to return the part back to APC. After 30 days,
the warranty invoice will be outstanding and payment of the invoice will be expected in full.
• Return authorization documentation will be sent with the replacement part. This documentation
must be sent back with the defective part to APC for proper identification of the warranty
return. Mark the warranty return number on the outside of the package.
• After the part has been received at APC, we will determine the status of the credit based on the
findings of the returned part. Parts that are damaged from: lack of maintenance, mis-application,
improper installation, shipping damage, and acts of man/nature will not be covered under the
parts warranty.
• Any warranty parts request received before 1:00 PM EST will be shipped same day standard
ground delivery. Any costs associated with Next Day or Airfreight will be the responsibility of
the party requesting the part.
• Return freight of warranty parts to APC is the responsibility of the party requesting the part.
Entire contents copyright © 2003 American Power Conversion. All rights reserved.
Reproduction in whole or in part without permission is prohibited. APC, the APC logo,
Symmetra and InfraStruXure are trademarks of American Power Conversion Corporation
and may be registered in some jurisdictions. All other trademarks, product names, and
corporate names are the property of their respective owners and are used for informational
purposes only.
990-1460B
*990-1460B* 11/2003