You are on page 1of 6

Analysis of active power sharing and synchronization

in MultiDG micro grid


Rahul S.Somalwar Snehal P.Vaidya Sumant G.Kadwane Snehal P.Gawande
Department of Electrical Department of Electrical Department of Electrical Department of Electrical
D.M.I.E.T.R D.M.I.E.T.R Y.C.C.E Y.C.C.E
Wardha, M.S. India Wardha, M.S. India Nagpur, M.S. India Nagpur, M.S. India
rahulsomalwar@gmail.com sneh01v@gmail.com sgkadwane@gmail.com spgawande_18@yahoo.com

Abstract— The increasing demand of efficiency, cost outages in the main grid [4]. When a micro grid is
effectiveness, environmental aspects has driven the development disconnected from the main grid, there should be power
of micro grid technology. The controlling of the micro grid in sharing in micro grid. In general, a micro grid is interfaced to
standalone mode and grid connected mode is the major concern. the main power system by a fast semiconductor switch called
The active power sharing after grid disconnection and as static transfer switch (STS). It is most important switch for
resynchronization with the utility grid are the challenging task in protection of micro grid in both grid connected and the
micro grid. In this paper, proper relay coordination are proposed islanded mode of the operation against all faulty condition[6].
for islanding and power sharing of multi distribution generations
(DGs) unit in single phase system. Also discussed the The aim of this paper is to analyze power sharing cases for
synchronization of DGs with utility grid using Static Transfer different load conditions and propose a micro switch between
Switch (STS) called as micro switch. Various conditions consider the utility grid and DGs for islanding and synchronization.
for islanding, active power sharing of multi DGs and Verify the simulation results for both the condition. From the
synchronization between grid with two parallel connected DG’s. simulation results using simulink models is shown that the
The simulation results reported in this paper are based on scheme provides the micro grid with a deterministic and
MATLAB software. Result shows that Static transfer switch reliable reconnection to the grid. The purpose of this paper, is
works effectively and synchronized the system in proper way. to propose an automatic synchronizing method for a micro
grid which can be applicable.
Keywords—Active power sharing,Distribution generations,
islanding, micro grid,Micro switch, Sysnchronization, utility grid. The rest of the paper described as follows. Section II
describes power sharing methods in micro grid, Section III
I. INTRODUCTION discussed a proposed system, Section IV suggests flow chart
In today’s world the biggest trouble which everyone of the proposed system, Section V analysis of simulation
facing is energy crises. Near about 60% of natural resources results, Section VI conclusion.
are used for generating energy which are conventional energy
sources[1]. Due to increasing the demand of electricity as well II. POWER SHARING METHODS IN MICRO GRID
as rapid depletion of fossil fuels and the government policies The fast development of digital signal processors has brought
on reduction of green house gas emissions, renewable energy an increase in control techniques for the parallel operation of
techniques are more attractive. Various types of distribution inverters [7]. These control schemes can be classified into two
generation (DG) sources such as wind turbines, generators and main groups, communication based techniques and droop
solar photovoltaic panels are being connected to low voltage characteristics based techniques. The first techniques based on
distribution network [2]. Due to popular use of distribution active load sharing e.g. Concentrated control, master/slave
generation (DGs) and its advantages, the DG’s are preferred
control, distributed control and second techniques for the
with utility grid. Therefore, the new concept introduced which
are micro grid. Basically as per IEEE, micro grid is a cluster parallel operation of inverters is mainly based on droop
of loads, Distribution generation (DGs) unit and Energy method. This technique consists of adjusting the frequency
storage system (ESS) are operated in co-ordination to reliably and voltage amplitude in terms of active and reactive power
supply electricity, connected to the power system at the injected by the inverters [7]-[8]. A several innovative
distribution level at a single point of connection called as the techniques have been used for proper power sharing and
point of common coupling (PCC) [3]. All over the world, stability of the system. The one of the best method for proper
there are many major practical research projects are enduring active power sharing is droop control method without
on the micro grid. One of the basic objectives of micro grid is affecting the voltage and the frequency at the point of
to achieve accurate power sharing while maintaining common coupling(PCC)[9].Normally, the droop constant of a
magnitude of voltage and frequency. The unique feature of DG is considered to be a fixed parameter so that the load
micro grid which allows both synchronized grid connected as demand is shared among DGs in proportional to their rating
well as islanded operation in case of instabilities or power capacity. The real and reactive power sharing can be achieved

978-1-5386-4318-1/17/$31.00 ©2017 IEEE


by controlling two independent parameters, one is the III. PROPOSED SYSTEM
frequency and another one is the voltage magnitude [5].
The active and reactive power transmitted across lossless line STATIC TRANSFER
is shown below SWITCH UTILITY
S1 GRID
V1 V2 PCC

P sin G (1)
X DG 1 Inverter RL
1 LOAD Micro Switch
Q (V2  V1 cos G ) (2) 1 Control

Signal from
STS S3
The active and reactive power sharing is directly proportional Vpcc FpccVg Fg
Inverter
DG 2
to the power angle and voltage difference respectively. Below 2 RL S2
LOAD2 Trip signal
equations forms the basis of frequency and voltage droop to Inverters

control where active and reactive power are adjusted


according to linear characteristics based on the following
control equations. Fig. 1. Proposed System with Static Transfer switch.

The basic power system model with two DG sources


V V0  K q (Q  Q0 ) (3) connected to the loads at the point of common coupling (PCC)
f f 0  K p ( P  P0 ) (4) is shown in Fig.1. The micro grid can run in grid connected
mode or islanded mode. In grid connected mode, the micro
Where grid either draws or supplies power from or to the main grid,
f is the system frequency depending on the generation & load conditions. When the
f0 is the base frequency. circuit breaker (CB) S1 is closed the system runs in grid
kp is the frequency droop control setting. connected mode, otherwise it should be islanded. A Static
P is the active power of the unit. transfer switch (STS) is used for disconnection of utility grid
P0 is the base active power of the unit. from micro grid under faulty condition and resynchronized
V is the voltage at the measurement location. when normal condition occurred. It gives trip signal to
V0 is the base voltage. inverters for islanding. In STS consist of micro switch control
Q is the reactive power of the unit. which gives command signal to the disconnection switch.
Q0 is the base reactive power of the unit. Voltage and frequency at PCC and grid respectively gives
kq is the voltage droop control setting. signal to the micro switch control unit. There are two RL
loads. Initially switch S2 is closed and only Load 1 connected
The poor active and reactive power sharing problems due to with system. Load 2 is in series with load 1when circuit
the influence of impedance mismatch of the DG feeders and breaker S3 closed which is initially open. For varying the load,
the different ratings of the DG units are predictable when the used load 2. The operation of load 2 is controlled by switch
conventional droop control scheme is adopted. There are some S3. The various effects analyzed after grid disconnection. The
drawbacks in droop control method like if the line impedance relay coordination which internally constructed in micro-
between point of common coupling and the inverters are switch is proposed in the system. If, after some time fault has
different, it may result of large circulating current and low been cleared in the grid, micro grid resynchronized with the
precision of power sharing among inverters. help of static transfer switch. The detail structure of STS is
when the parallel system must share non linear load the droop shown in the Fig.2
control method is not suitable. This method is focus on
fundamental power sharing but does not take harmonic
Static Transfer Switch
sharing into account in case of non linear loads. Therefore, the
adaptive/improved droop control, network-based control Thyristor bridge
methods and cost-based droop schemes are compared and S

summarized in [2] for active power sharing.


To preserve the power sharing stability, an adaptive
decentralized droop controller of paralleled inverter-based DG Vg
Firing Board
units is presented and power sharing strategy which is based
on the static droop characteristics combined with an adaptive Vpcc
transient droop function discussed in [8]. The literature shows Trip Micro switch
control Fpcc
that the active power sharing is major concern in micro grid. Fg
Hence in this paper the active power sharing between two
DGs with the help of STS is proposed.
Fig. 2. Structure of Static Transfer Switch
Broadly, the STS consist of two components thyristor bridge voltage crosses the permissible limit (253 volt), the DG1
and the Micro switch control unit. The STS is the exclusive should be trip. If not then again check the delay time. The
connection in between the micro grid and utility grid. Switch value remain in the same range up to the delay time (delay
S1 disconnect the utility grid from DGs and it re-synchronized time is 10 msec ), in that condition synchronization condition
after getting the signal from micro switch control unit. A to be checked.
thyristor bridge is consisting of two anti-parallel SCRs as
shown in the Fig 2.
The thyristor bridge is controlled by the firing board, which
gets an on/off signal from the micro switch controls for
synchronization or disconnection respectively. The function of
micro switch unit is to gathers its voltage, frequency
information from both the grid and micro grid sides and
generate the signal for islanding or re-synchronization. The
detail of micro switch control is shown in the Fig 3.

Vpcc Vg fg
Over voltage
logic

Vpcc
Under voltage NOT AND
logic Synchronization Firing
logic board
active
signal

Fpcc Breakers
Under / over NOT AND disconnect
frequency logic
signal

Fig. 3. Details of micro switch

The micro switch controls perform two main functions


synchronization and islanding detection. The micro switch
control consist of synchronization logic unit, under/ over
voltage logic unit and Under/over frequency logic unit as
shown in the Fig 3. Working of under/ over voltage unit and
synchronization unit explain in the flow chart.
IV. FLOW CHART
Fig. 4. Flow chart of System
The proposed system works in three different conditions. All
these three conditions discussed in detail. At the point of Case 3. Here the generated power of DG1 is less than the
common coupling the various parameters like Voltage of grid, required load, in this situation voltage droop checking the
(Vg), Voltage at PCC (Vpcc), voltage of distribution value of VDG1, if the value crosses its threshold value then trip
generations (VDG1 and VDG2 ) are measured. If the requirement DG1. If the voltage is within the range, check the delay time
of load power fulfill by DG1 no need of DG2 operated. But and after that the condition of synchronization.
this is not the case every time, load may increase or decrease. The above all three cases are applicable to DG2 which is
Both the cases are considered in the flow chart. As the power shown in flow chart. All the parameters are within limit of
mismatch affects on the voltage of DG, islanding condition to DG1 and DG2 then only synchronization condition to be
be checked in this situation. The three different cases of power checked. For single phase synchronization there is no need to
mismatch for DG1explain in detail. check phase sequence hence only voltage and frequency of
Case 1. The power of DG1 will be equal to required load grid and PCC to be checked. In this situation if condition full
(PDG1=PL). Power of DG2 will be equal to required load fill, the synchronization to be done otherwise again the
(PDG2=PL). If this condition is full fill, at that time the variation parameter to be check.
of voltage will be in the permissible limit, hence directly The same flow chart to be verified in our simulation and
check the synchronization condition as shown in flow chart of shows the synchronization of DGs with grid.
Fig 4.
Case 2. If the generated power of DG1 is more than the V. SIMULATION RESULTS
required load power in that condition, the voltage of DG1 The specification of the system is shown in the table 1. The
increases, here maximum and minimum threshold value of Generating capacity of each DG is 10 kW. The load 1 is 10kW
voltage is decided, now it should be check that value, if and load 2 is variable in the range of 5-10kW.
Table No. 1. Parameters and their units
Sr. No. Parameters Units
1 DG Power 10kW each
2 DG voltage 230 V
3 Frequency 50Hz
4 Grid Voltage 230V
5 Grid Frequency 50Hz
6 Load 1 10kW,
Load 2 5-10kW
7 Inductor 6mH

The grid connected with DGs, if Load Power is less than


generating power (PL < PDG). In this case, initially in grid
connected mode, grid is sufficient to fulfill the power demand
of the load, as grid disconnected at t= 0.1sec due to faulty
condition. At this moment voltage increases at PCC as shown
in the Fig.6.
As the PCC voltage is more than its permissible limit over- Fig.7. The PL > PDG DG1 in islanding condition , DG2 sharing power and
voltage relay gives a trip signal to DG1 and hence its trip. At t Grid synchronized.
= 0.15sec the load changes which is again increases the load
power than generating power and again overvoltage relay
gives a trip signal to DG2, hence DG2 is trip. Now, the
system is in islanding condition. Now at t = 0.20sec the load
increases in sufficient way, the voltage is in permissible limit,
synchronization condition checked and grid synchronized at
t = 0.21sec.

Fig. 8. The PL > PDG, DG1 sharing Power DG2 in islanding condition, Grid
synchronized.

In above all condition the synchronization of grid is possible.


Now synchronization of DGs with the utility grid is to be test.
The grid disconnected at t= 0.10sec, DGs sharing the power as
per the required load. At t= 0.15sec the load again changed
Fig. 6. The PL < PDG ,both DGs in islanding condition , Grid synchronized.
which affects on voltage of PCC. The voltage of DG2 crosses
the permissible limit, under voltage relay trip the DG2.
In second case, the load power is more than the generating
power (PL > PDG ) when the grid disconnected at t= 0.10sec. At t= 0.19 sec, the load changes, checked the synchronization
Now the voltage at PCC is less than the permissible limit condition. Here the voltage conditions not fulfill
hence under voltage relay trips the DG1. At t= 0.15sec load synchronization condition hence relay operates and system not
reduces due to which DG2 share the required power. The PCC synchronized. After the adjusting the load, grid synchronized
shown in the Fig.9.
voltage after t= 0.15 sec allow to synchronized the grid. At t=
0.20 sec the gird synchronized as shown in the Fig.7. This
relay coordination indicates that power sharing of the load in
the DGs with their capacity is possible.
Now by simulation, the operation of DGs to be checked for
another condition. The grid disconnected at t = 0.10sec. The
load power share with the DG1.At t= 0.15 sec, load increases
which affects on the voltage of DG2. As a result the voltage at
PCC reduces and DG2 islanded. At t= 0.20sec, again the load
adjust in such a way that grid synchronized with DGs as
shown in the Fig 8.
Fig. 9. The PL > PDG DG1 sharing Power DG2 in islanding condition , Grid
not synchronized

Equal Power Sharing


In this case, Load 1= 10 KW, in grid connected mode, grid is
supplying 10 KW. Grid voltage is 325V (peak to peak
voltage).Now at t= 0.1 sec, grid is disconnected, voltage
should be reduced but it remain constant as DG1supplying
same load as grid and full fill the requirement. Now if the
load is suddenly increase say Load 2= 10 KW at t= 0.15 sec,
then DG2 ON having same voltage instead of reducing the
voltage, now both DGs are fulfill the load requirement up to
t=0.2 sec. At t= 0.2 sec, grid is synchronized with the help of
synchronization switch (STS) having voltage constant and grid
should give power to load. In equal power sharing throughout
voltage remain constant. The power sharing of DG1, DG2 and Fig. 12. Voltage at PCC and relay signal for the condition PL = PDG
Power at PCC are shown in the Fig. 10.
For the various conditions, the power of DG1 and DG2 as well
as Voltage of DG1 and DG2 are summarized in the table 2.
Table 2 : Effect of voltage and power for different condition
Sr. Condit DGs Effects of Effects of Effects of Effects of
No. ions of voltage on increasing active increasing or
DG1 DG1 & or power on decreasing load
and DG2 decreasing DG1 & on active power
DG2 load on DG2 at PCC
voltage of
DG1 &
DG2
1 Pg1 > DG1 Voltage Power
Ld. increases Voltage increases Power
Pg2 = DG2 Voltage decreases Power decreases
Ld. decreases decreases
2 Pg1 = DG1 Voltage Power
Fig. 10. Power sharing by the DGs for the condition PL = PDG
Ld. constant Voltage constant Power
Pg2 < DG2 Voltage increases Power increases
Ld. decreases decreases
Fig.11. shows that the voltage of DG1, DG2 and PCC are
3 Pg1 < DG1 Voltage Power
same in all the conditions i.e during grid disconnection, load Ld. decreases Voltage decreases Power
changes at t= 0.15sec and at the grid synchronization. Pg2 < DG2 Voltage decreases Power decreases
Ld. decreases decreases
4 Pg1 > DG1 Voltage Power
Ld. increases Voltage increases Power
Pg2 > DG2 Voltage increases Power increases
Ld. decreases decreases

VI. CONCLUSION
In this paper a static transfer switch (STS) operation has been
proposed in single phase system for grid disconnection,
islanding and resynchronization. The various conditions have
been analyzed and tested the working of STS. The required
load power are provided by DGs by efficient active power
Fig. 11. Voltage of DG1, DG2 and PCC when PL = PDG sharing between two DGs. The simulation results have shown
the good performance of STS. Result shows that if DGs power
The relay coordination for this condition is tested. The
voltage at DG1, DG2 and at PCC is nearly equal to grid voltage generating capacity is not sufficient to fulfill the required load
when grid disconnection condition occurs at 0.10 sec as well demand and this condition is remain for long time then DGs
as at 0.15 after load changes. Grid synchronized at 0.20 sec as should trip or if this condition is temporary at that time check
the voltage level is same even in this condition. The relay is the synchronization condition and synchronize with grid using
not generate any trip signal during all these conditions which the static transfer switch.
is shown in the Fig.12 VII ACKNOWLEDGMENT

The Authors of the paper are grateful for the authority of


DMIETR and YCCE for providing the facilities to carry out
this work.
VIII REFERENCES [13] Deshbhratar,P., Rahul Somalwar, and S. G. Kadwane. "Comparative
analysis of islanding detection methods for multiple DG based system." In
[1]Olivares, Daniel E., Ali Mehrizi-Sani, Amir H. Etemadi, Claudio A. Electrical, Electronics, and Optimization Techniques (ICEEOT), International
Cañizares, Reza Iravani, Mehrdad Kazerani, Amir H. Hajimiragha et al. Conference on, pp. 1525-1530. IEEE, 2016.
"Trends in microgrid control." IEEE Transactions on smart grid 5, no. 4 [14] Nikhar, Archana R., S. M. Apte, and Rahul Somalwar. "Review of
(2014): 1905-1919. various control techniques for DC-DC interleaved boost converters." In
[2]. Han, Hua, Xiaochao Hou, Jian Yang, Jifa Wu, Mei Su, and Josep M. Global Trends in Signal Processing, Information Computing and
Guerrero. "Review of power sharing control strategies for islanding operation Communication (ICGTSPICC), 2016 International Conference on, pp. 432-
of AC microgrids." IEEE Transactions on Smart Grid 7, no. 1 (2016): 200- 437. IEEE, 2016.
215.. [15]Nagraju Pogaku, Milan Prodanvoic, Timothy c. Green,”Modelling,
[3]. Han, Yang, Hong Li, Pan Shen, Ernane Antônio Alves Coelho, and Josep analysis and testing of Autonomous operation of an inverter based micro
M. Guerrero. "Review of active and reactive power sharing strategies in grid ” IEEE transactions on power electronics, vol.22, No.2, March 2017.
hierarchical controlled microgrids." IEEE Transactions on Power Electronics [16] Vasquez, Juan C., Josep M. Guerrero, Mehdi Savaghebi, Joaquin Eloy-
32, no. 3 (2017): 2427-2451. Garcia, and Remus Teodorescu. "Modeling, analysis, and design of stationary-
[4]. Tang, Fen, Josep M. Guerrero, Juan C. Vasquez, Dan Wu, and Lexuan reference-frame droop-controlled parallel three-phase voltage source
Meng. "Distributed active synchronization strategy for microgrid seamless inverters." IEEE Transactions on Industrial Electronics 60, no. 4 (2013):
reconnection to the grid under unbalance and harmonic distortion." IEEE 1271-1280.
Transactions on Smart Grid 6, no. 6 (2015): 2757-2769. [17]. Han, Hua, Yao Liu, Yao Sun, Mei Su, and Josep M. Guerrero. "An
[5] Katiraei, Farid, and Mohammad Reza Iravani. "Power management improved droop control strategy for reactive power sharing in islanded
strategies for a microgrid with multiple distributed generation units." IEEE microgrid." IEEE Transactions on Power Electronics 30, no. 6 (2015): 3133-
transactions on power systems 21, no. 4 (2006): 1821-1831. 3141.
[6]. Basak, Prasenjit, A. K. Saha, S. Chowdhury, and S. P. Chowdhury. [18]. Mohamed, Yasser Abdel-Rady Ibrahim, and Ehab F. El-Saadany.
"Microgrid: Control techniques and modeling." In Universities Power "Adaptive decentralized droop controller to preserve power sharing stability
Engineering Conference (UPEC), 2009 Proceedings of the 44th International, of paralleled inverters in distributed generation microgrids." IEEE
pp. 1-5. IEEE, 2009. Transactions on Power Electronics 23, no. 6 (2008): 2806-2816.
[7]. Guerrero, Josep M., L. Garcia De Vicuna, José Matas, Miguel Castilla, [19]. E. Barklund, Nagaraju. Pogaku,C. Hernandez, Aramburo, Tim C. Green,
and Jaume Miret. "A wireless controller to enhance dynamic performance of “Energy management in automatic micro grid using stability constrained
parallel inverters in distributed generation systems." IEEE Transactions on droop control of inverters”, 2008, IEEE.
power electronics 19, no. 5 (2004): 1205-1213. [20] Kroposki, Ben, Christopher Pink, Jonathan Lynch, Vinod John, S. Meor
[8]. Mohamed, Yasser Abdel-Rady Ibrahim, and Ehab F. El-Saadany. Daniel, E. Benedict, and I. Vihinen. "Development of a high-speed static
"Adaptive decentralized droop controller to preserve power sharing stability switch for distributed energy and microgrid applications." In Power
of paralleled inverters in distributed generation microgrids." IEEE Conversion Conference-Nagoya, 2007. PCC'07, pp. 1418-1423. IEEE, 2007.
Transactions on Power Electronics 23, no. 6 (2008): 2806-2816. [21] Majumder, Ritwik, Arindam Ghosh, Gerard Ledwich, and Firuz Zare.
[9]. Majumder, Ritwik, Arindam Ghosh, Gerard Ledwich, and Firuz Zare. "Load sharing and power quality enhanced operation of a distributed
"Power system stability and load sharing in distributed generation." In Power microgrid." IET Renewable Power Generation 3, no. 2 (2009): 109-119.
System Technology and IEEE Power India Conference, 2008. POWERCON
2008., pp. 1-6. IEEE, 2008.
[10] Vaidya Snehal, Rahul Somalwar, and Sumant G. Kadwane. "Review of
various control techniques for power sharing in micro grid." In Global Trends
in Signal Processing, Information Computing and Communication
(ICGTSPICC), 2016 International Conference on, pp. 438-443. IEEE, 2016.
[11]. Liu, He-Jin, Ke-Jun Li, Hong-Xia Gao, Ying Sun, Kai-qi Sun, and Wei-
Jen Lee. "Control and simulation of grid-connected micro-grid." In Power and
Energy Society General Meeting, 2012 IEEE, pp. 1-6. IEEE, 2012.
[12]. Majumder, Ritwik, Arindam Ghosh, Gerard Ledwich, and Firuz Zare.
"Control of parallel converters for load sharing with seamless transfer
between grid connected and islanded modes." In Power and Energy Society
General Meeting-Conversion and Delivery of Electrical Energy in the 21st
Century, 2008 IEEE, pp. 1-7. IEEE, 2008.

You might also like