Remarks :
1. We adjusted Proact governor setting of 2 units as attached.
2. Hunting is happened atIsochronus mode, we adjust setting for reduce hunting. Afterthen, confirmed with load test.
3. According to BME request, rated speed setting was changed to 1500min-1
4. Some factory setting is changed. Therefore are possibility of out of warranty case according to failure situation.
1. Overview
MGS1000B V5799
S12H-PTA-S #35539
2. MGS lavel
V5799
#35539
Page 2 of 4
Attachment 1 :
Condition Check Result Report For Diesel Generator Set
5. Overview
MGS1000B V5799
S12H-PTA-S #35539
6. MGS lavel
V5800
#35553
Page 3 of 4
Setting adjustoment point
MGS PIN No. Engine No. Parameter Original setting After Adjust Remark
Gain A 0.1200 0.1100 For reduce hunting at Isochronus mode
Stability 0.160 0.070 For reduce hunting at Isochronus mode
V5799 35539 Compensation 0.800 0.700 For reduce hunting at Isochronus mode
Rated Speed 1582 1500 BME Request
Droop 6.70 2.00 BME Request
MGS PIN No. Engine No. Parameter Original setting After Adjust Remark
Gain A 0.1500 0.1100 For reduce hunting at Isochronus mode
Stability 0.160 0.070 For reduce hunting at Isochronus mode
V5800 35553 Compensation 0.800 0.700 For reduce hunting at Isochronus mode
Rated Speed 1582 1500 BME Request
Droop 6.70 2.00 BME Request