Factory Acceptance Test Report

NR Electric Co., Ltd.


Preface

Copyright
Version: R1.00 NR ELECTRIC CO., LTD.
P/N: EN_TSDG9001.0086.0001 69 Suyuan Avenue. Jiangning, Na njing 211102,China
Tel: 86-25-87178185, Fax: 86-25-87178208
Copyright © NR 2010. All rights reserved Website: www.nari-relays.com
Email: nr_techsupport@nari-relays.com
We reserve all rights to this document and to the information
contained herein. Improper use in particular reproduction and
dissemination to third parties is strictly forbidden except where
expressly authorized.

The information in this manual is carefully checked periodically,


and necessary corrections will b e included in future editions. If
nevertheless any errors are detected, suggestions for correction or
improvement are greatly appreciated.

We reserve the rights to make technical improvements without


notice.

NR ELECT RIC CO., LTD. i


ii NR ELECTRIC CO., LTD.
DRRMS Factory Acceptance Test Report

Table of Contents
Preface.............................................................................................................................................. i

Table of Contents .......................................................................................................................... iii

Chapter 1 Establish Test Environment ........................................................................................ 1

1.1 Test Environment.............................................................................................................. 1

1.2 Configuration of RCS-9798A............................................................................................ 2

1.3 Configuration of PCS-9010 (Server & Local HMI).......................................................... 3

1.4 Front-end Configuration................................................................................................... 6

Chapter 2 Communication Services between RCS-9798A and IEDs........................................ 7

2.1 Record of Communication Services Test ...................................................................... 7

Chapter 3 Clock Synchronization ................................................................................................11

3.1 Test Functions of RCS-9785C ........................................................................................11

3.2 Test of Clock Synchronization Function of DRRMS................................................... 12

Chapter 4 PCS-9010 DRRMS Front-end Function .................................................................... 15

4.1 FE Communication ......................................................................................................... 15

Chapter 5 PCS-9010 DRRMS Online Tool .................................................................................. 17

5.1 System Clock Synchronization ..................................................................................... 17

5.2 Graph Browsing .............................................................................................................. 17

5.3 Event Alarm ..................................................................................................................... 18

5.4 Settings and Operation Management ........................................................................... 20

5.5 Relay Faults and Grid Faults ......................................................................................... 22

5.6 Historical Fault Information Query................................................................................ 23

5.7 Waveform File Management .......................................................................................... 23

5.8 Panel Information............................................................................................................ 24

5.9 Authority Check .............................................................................................................. 25

5.10 Authority Management Tool ........................................................................................ 25

Chapter 6 PCS-9010 DRRMS WEB Tool..................................................................................... 27

Chapter 7 Manual Version History .............................................................................................. 29

NR ELECTRIC CO., LTD. iii


DRRMS Factory Acceptance Test Report

iv NR ELECTRIC CO., LTD.


Chapter 1 Establish Test Environment

Chapter 1 Establish Test Environment


1.1 Test Environment

The first step of the test procedure of NR Digital Relays Remote Monitoring System (DRRMS for
short) is to establish the test environment. The hardware and software configuration to establish
the test environment are listed as below:

Server (For example: SSP Centraline Server):

IP address: 198.87.91.200

Subnet mask: 255.255.255.0

Type: HP ML370

OS: Windows 2003 Server Enterprise

Database system: Oracle 9i

Software PCS-9010 DRRMS software

Local HMI (For example: Local HMI of MOB):

IP address: 198.87.91.201

Subnet mask: 255.255.255.0

Type: FUJITSU TX-150

OS: Windows 2003 Server Enterprise

Software PCS-9010 DRRMS software

Avalanche Test Server:

IP address: 198.87.91.220

Subnet mask: 255.255.255.0

Type: IBM X3500

OS: Windows7.0

Software Substation automation test environment V1.0

RCS-9798A Protection Management Unit:

Upward:

IP address: 198.87.91.199 Subnet mask: 255.255.255.0

Gateway: 198.87.91.199

Downward:

NR ELECTRIC CO., LTD. 1


Chapter 1 Establish Test Environment

IP address 1: 198.120.0.199 Subnet mask 1: 255.255.0.0

IP address 2: 198.121.0.199 Subnet mask 2: 255.255.0.0

RCS-9785C Clock Synchronization Unit:

IP address: 198.120.0.20 Subnet mask: 255.255.255.0

IP address: 198.121.0.20 Subnet mask: 255.255.255.0

PCS-9611 Feeder Management Relay 1:

IP address 1: 198.120.0.11 Subnet mask 1: 255.255.0.0

IP address 2: 198.121.0.11 Subnet mask 2: 255.255.0.0

PCS-9611 Feeder Management Relay 2:

IP address 1: 198.120.0.12 Subnet mask 1: 255.255.0.0

IP address 2: 198.121.0.12 Subnet mask 2: 255.255.0.0

PCS-9611 Feeder Management Relay 3:

IP address 1: 198.120.0.13 Subnet mask 1: 255.255.0.0

IP address 2: 198.121.0.13 Subnet mask 2: 255.255.0.0

TOSHIBA GRL150:

Serial port connection, address: 3, port number: a

SIEMENS 7SD61:

Serial port connection, address: 2, port number: b

“Wireshark”:

A software tool for monitoring NTP message

“Substation automation test environment V1.0”:

A software tool for avalanche test

1.2 Configuration of RCS-9798A

Functional description:

Configure RCS-9798A by using RCS9798 Configuration Tool to realize successful communication


between RCS-9798A and PCS-9010 main station.

No. Test content Test method and procedure Test result

Select IEC61850 for


Configure downward communication
1 PCS-9611
protocol
Select IEC60870-5-103

2 NR ELECTRIC CO., LTD.


Chapter 1 Establish Test Environment

protocol for GRL150 and


7SD61
Add IEDs:
PCS-9611 X 3,
2 Add downward IEDs
TOSHIBA GRL150 X 1,
SIEMENS 7SD61 X 1
Configure upward communication
3 Select NW103 protocol
protocol
Download communication
4
configuration

1.3 Configuration of PCS-9010 (Server & Local HMI)

Functional description: Access the PCS-9010 DRRMS Configuration Tool (DRRMS


Configuration Tool for short) by clicking the drrms icon on the desktop.

DRRMS Configuration Tool supports offline configuration, the main functions include:

1) DRRMS main station modeling,

2) Interrogation of substation configuration,

3) Interrogation of device configuration,

4) File interrogation,

5) Import .svg graphic file,

6) Import/edit graph,

7) Verify/publish database,

8) Front-end configuration.

...

NOTE:In this manual:

Logic database (ldb for short) is an offline database which is not in service. The
modification on ldb will not influence the operation of DRRMS.

Logic database (ldb for short) is an offline database which is not in service. The
modification on ldb will not influence the operation of DRRMS.

Program name: drrms

Test result
No. Test content Test method and procedure Local
Server
HMI
Click “Add Area”in the right-click menu under the
5 Add Area
root node in left node tree area to add new

NR ELECTRIC CO., LTD. 3


Chapter 1 Establish Test Environment

Test result
No. Test content Test method and procedure Local
Server
HMI
sub-area of the grid into the node tree. Click
“Publish Model” button to publish ldb verified
successfully to pdb. Check the publishing result
of the model through PCS-9010 DRRMS Online
Tool.
Click “Delete Area”in the right-click menu under
the area in left node tree area to delete the
sub-area of the grid into the node tree. Click
6 Delete Area “Publish Model” button to publish ldb verified
successfully to pdb. Check the publishing result
of the model through PCS-9010 DRRMS Online
Tool.
Click “Delete Substation”in the right-click menu
under the substation in left node tree area to
delete the substation model on the node tree.
7 Delete Substation Click “Publish Model” button to publish ldb
verified successfully to pdb. Check the publishing
result of the model through PCS-9010 DRRMS
Online Tool.
Click “Add Bay”in the right-click menu under the
substation in left node tree area to add new bay
under the substation. Click “Publish Model”
8 Add Bay
button to publish ldb verified successfully to pdb.
Check the publishing result of the model through
PCS-9010 DRRMS Online Tool.
Click “Delete Bay”in the right-click menu under
the bay in left node tree area to delete the bay
model on the node tree. Click “Publish Model”
9 Delete Bay
button to publish ldb verified successfully to pdb.
Check the publishing result of the model through
PCS-9010 DRRMS Online Tool.
Click “Add Graph”in the right-click menu under
root node, area, substation, bay and devices etc.
10 Add Graph
in left node tree area to add a graph under the
corresponding node.
Click “Delete Graph”in the right-click menu under
11 Delete Graph the graph in left node tree to delete the graph on
the node tree.
Click “Retrieve Model” in the right-click menu
Retrieve
12 under the substation in left node tree area to
substation model
observe the interrogation result of the information

4 NR ELECTRIC CO., LTD.


Chapter 1 Establish Test Environment

Test result
No. Test content Test method and procedure Local
Server
HMI
such as primary equipment configuration and
secondary device configuration. Select some of
the devices in the device list to retrieve detailed
information, and check the interrogation result of
the information through the Front-end Monitor.
Click “Import Model”in the right-click menu under
the substation in left node tree area. Check the
modification result of ldb configuration through
Import substation PCS-9010 DRRMS Configuration Tool. Click
13
model “Publish Model”button to verify ldb and publish
ldb to pdb if ldb is verified successfully. Check the
publishing result of the model through PCS-9010
DRRMS Online Tool.
Click “Import .svg file” in the right-click menu
under the substation in left node tree area to pop
up a dialog to select a .svg graphic file. Match the
Import .svg grapgic primitive in the .svg file with the primary
14
file equipment in the popped dialog. Check the
importing result and the association result of the
primary equipment and secondary equipment
after acknowledgment.
Click “Import Device” in the right-click menu
under a certain device in left node tree area to
15 Import Device
update selected device. Click “Publish Model”to
publish ldb to pdb.
Click “File Operation” in the right-click menu
under the substation in left node tree area, click
Retrieve the submenu “Retrieve File”to pop up a dialog to
generic retrieve file. Set “Start Time”and “End Time”and
files then retrieve the generic file list of RCS-9798A.
Click a file item to retrieve the generic files saved
in RCS-9798A.
File Click “File Operation” in the right-click menu
16
operation under the substation in left node tree area, click
“Download File”to pop up a dialog to download
Download file. Select a generic file to download. Check
generic whether the files have been downloaded
files successfully.

NOTE:The function of “Download File”

NR ELECTRIC CO., LTD. 5


Chapter 1 Establish Test Environment

Test result
No. Test content Test method and procedure Local
Server
HMI
supports downloading multiple files in
batches.

1.4 Front-end Configuration

Functional description:

The configuring work of the Front-end Configurator mainly includes the configuring of the channel
group, channel, data model and protocol.

Program name: fe_config

Test result
No. Test content Teat method and step Local
Server
HMI
Select “Add Channel Group”by right-clicking the
Add
tree list of Front-end Configurator, and then pop up
17 communication
a configuration dialog to create a communication
channel group
channel group.
Delete Select “Delete Channel Group” in the tree list of
18 communication Front-end Configurator to delete the selected
channel group communication channel group.
Configure
Configure the information of the communication
19 communication
channel group.
channel group
Add Select “Add Channel” by right-clicking under the
20 communication channel group to pop up a dialog to add
channel communication channel.
Delete Select “Delete Channel”by right-clicking under the
21 communication channel to delete the selected communication
channel channel.
Configure
Configure the information of the communication
22 communication
channel.
channel

6 NR ELECTRIC CO., LTD.


Chapter 2 Communication Services between RCS-9798A and IEDs

Chapter 2 Communication Services between


RCS-9798A and IEDs
2.1 Record of Communication Services Test

Functional description:

Test the communication and application functions between RCS-9798A and the protection
devices.

Test result
No. Test content Test method and procedure
RCS- Local
S erver
9798A HMI
Send clock synchronization messages
from RCS-9798A and check whether the
Clock
23 time displayed on RCS-9798A and the N/A N/A
synchronization
time displayed on the device are the
same.
Alarm simulation test.
Check whether the device can send out
24 Alarm information the alarm information to RCS-9798A and
whether RCS-9798A can display the
received alarm information correctly.
Simulation test.
Check if the device can send out the
Status change
status change information of binary inputs
25 information of
to RCS-9798A and whether RCS-9798A
binary inputs
can display the received information
correctly.
Simulation test.
Check whether the device can send out
Operation
26 the action information to RCS-9798A and
information
whether RCS-9798A can display the
received information correctly.
Fault simulation test.
The disturbance & fault recording (DFR
for short) device generates the records of
27 DFR function waveform recording. Check whether
RCS-9798A can retrieve the records of
waveform recording of the device
successfully.

NR ELECTRIC CO., LTD. 7


Chapter 2 Communication Services between RCS-9798A and IEDs

Test result
No. Test content Test method and procedure
RCS- Local
S erver
9798A HMI
Disconnect the network cable of
RCS-9798A or the device, or disconnect
Communication the power supply of the device during the
28
status information communication process to test whether
RCS-9798A can acquire correct
communication status of this device.
RCS-9798A sends general interrogation
to the designated device at regular time.
RCS-9798A will directly compare the
General
29 retrieved binary inputs and waveform lists
interrogation
with the actual binary inputs and
waveform lists of the device and check
whether they are the same.
Retrieve the active setting group No. of
the designated device from RCS-9798A.
Retrieve setting RCS-9798A will directly compare the
30
group No. retrieved setting group No. with the actual
setting group No. of the device and check
whether they are the same.
Retrieve the active settings of the
designated setting group No. of the
designated device from RCS-9798A.
31 Retrieve settings RCS-9798A will directly compare the
retrieved settings with the actual settings
of the device and check whether they are
the same.
Retrieve the analog values of the
designated device from RCS-9798A.
Retrieve analog RCS-9798A will directly compare the
32
values retrieved analog values with the actual
analog values of the device and check
whether they are the same.
Retrieve the VEBI settings of the
designated device from RCS-9798A.
Retrieve VEBI RCS-9798A will directly compare the
33
settings retrieved VEBI settings with the actual
VEBI settings of the device and check
whether they are the same.

8 NR ELECTRIC CO., LTD.


Chapter 2 Communication Services between RCS-9798A and IEDs

Test result
No. Test content Test method and procedure
RCS- Local
S erver
9798A HMI
Send the command to modify setting to
the device from RCS-9798A and check
34 Modify setting
whether the setting was modified
successfully.
Send the command to enable/disable
Enable/Disable VEBI from RCS-9798A to the protection
35
VEBI device and check whether the VEBI was
enabled/disabled successfully.
Use software “Substation automation
test environment V1.0”to simulate 60
sets of PCS-9611 and they are triggered
36 Avalanche test
to release alarm messages
simultaneously, check the alarm
messages are received accordingly.

NR ELECTRIC CO., LTD. 9


Chapter 2 Communication Services between RCS-9798A and IEDs

10 NR ELECTRIC CO., LTD.


Chapter 3 Clock Synchronization

Chapter 3 Clock Synchronization


3.1 Test Functions of RCS-9785C

No. Test content Test method and procedure Test result

Energize RCS-9785C, check:


1) The LED “HEALTHY” is on, and there is no
alarm signal.
2) The LED “PPS”flashes per second.
3) If the LED “MASTER”is off, modify the setting
[Running mode] from “Slave” to “Master” in
37 LED
the submenu “Device setting”, check the LED
“MASTER”is on.
4) If the LED “MASTER”is on, modify the setting
[Running mode] from “Master”to “Slave” in
the submenu “Device setting”, check the LED
“MASTER”is off.
1) Configure the setting [Net timing] as “ON”in
the submenu “Device setting”, and then use
38 Network the software tool “Wireshark”to monitor SNTP
broadcast messages per minute for the 4
network segments from the 2 Ethernet ports.
1) In the submenu “Channel setting”:
configure the settings [Input channel A] and
[Input channel B] as “ON”,
configure the settings [Fiber-optic channel A]
and [Fiber-optic channel B] as “LIGHT ON”
and select the jumpers JP1~JP8 on the optical
output module NR1217 according to instruction
manual.
configure the settings [Electrical channel A]
IRIG-B
39 and [Electrical channel B] as “TTL”.
(Optical signal)
2) Select the jumpers JP11 and JP22 on NR1217
to make the output signals as IRIG-B signal.
3) Ensure the electrical input port of the GPS
module NR1141 is disconnected.
4) Connect an optical signal to NR1141 from
NR1217 with a multi-mode optical fiber.
5) Check “Input CHNL-A:ON/Y” and “Input
CHNL-B:ON/Y”displayed on the main menu of
RCS-9785C, and ensure that there is no alarm

NR ELECTRIC CO., LTD. 11


Chapter 3 Clock Synchronization

signal.
1) In the submenu “Channel setting”:
configure the settings [Input channel A] and
[Input channel B] as “ON”,
configure the settings [Fiber-optic channel A]
and [Fiber-optic channel B] as “LIGHT ON”
and select the jumpers JP1~JP8 on the optical
output module NR1217 according to instruction
manual.
configure the settings [Electrical channel A]
IRIG-B and [Electrical channel B] as “RS-485”.
40
(Electric signal) 2) Select the jumpers JP11 and JP22 on NR1205
to make the output signals as IRIG-B signal.
3) Ensure the optical input port of the GPS module
NR1141 is disconnected.
4) Connect an electrical signal to NR1141 from
NR1205 with a twisted-pair shielded cable.
5) Check “Input CHNL-A:ON/Y” and “Input
CHNL-B:ON/Y”displayed on the main menu of
RCS-9785C, and ensure that there is no alarm
signal.
1) Record the current date & time of the
RCS-9785C.
2) Modify the setting [Time zone] in the submenu
41 Time Zone
“Device setting”.
3) Check the current date & time of the
RCS-9785C.
1) De-energize RCS-9785C.
2) Connect the antenna to the RCS-9785C,
42 Antenna
3) Energize RCS-9785C, in general, 7 satellites
will be tracked in five minutes.

3.2 Test of Clock Synchronization Function of DRRMS

Functional description:

RCS-9785C is used as clock source in DRRMS system. For the convenience of clock modification
in the test, the antenna should not be connected to the RCS-9785C. Other devices adopt the
SNTP network clock synchronization through the Ethernet switch, or the IRIG-B signal clock
synchronization through the electri cal cable.

No. Test content Test method and procedure Test result

43 Local HMI 1) Modify the current time of the workstation.

12 NR ELECTRIC CO., LTD.


Chapter 3 Clock Synchronization

2) Wait a few minutes.


3) Current time of the workstation should be the
same as the RCS-9785C after the clock
synchronization is successful.
1) Modify the current time of the RCS-9798A.
2) Wait a few minutes.
44 RCS-9798A 3) Current time of the RCS-9798A should be the
same as the RCS-9785C after the clock
synchronization is successful.
1) Modify the current time of the PCS-9611.
2) Wait a few minutes.
45 PCS-9611 3) Current time of the PCS-9611 should be the
same as the RCS-9785C after the clock
synchronization is successful.
1) Modify the current time of the 7SD61.
2) Wait a few minutes.
46 7SD61 3) The current time of the 7SD61 should be same
with the RCS-9785C after the clock
synchronization is successful.
1) Modify the current time of the GRL150.
2) Wait a few minutes.
47 GRL150 3) The current time of the GRL150 should be
same with the RCS-9785C after the clock
synchronization is successful.

NR ELECTRIC CO., LTD. 13


Chapter 3 Clock Synchronization

14 NR ELECTRIC CO., LTD.


Chapter 4 PCS-9010 DRRMS Front-end Function

Chapter 4 PCS-9010 DRRMS Front-end Function


4.1 FE Communication

Functional description:

The PCS-9010 DRRMS Front-end (FE for short) module is applied to receive various information
sent by each RCS-9798A and provides the information to SCADA module and DRRMS
management module. The information received includes:

1) Running status of the protection devices;

2) Acquired data;

3) Tripping reports of the protection devices;

4) Tripping reports of the circuit breakers;

5) Alarm and supervisory information of the protection devices;

6) DFR files;

7) Settings of the protection devices;

8) Alarm and events of the DRRMS substation;

9) Configuration information of RCS-9798A;

Program name: fe_config

Test result
No. Test content Test method and procedure
Local
Server
HMI
Browse the status of each RCS-9798A in FE
Status display of
running tools and the running status of each
48 RCS-9798A and
protection device corresponding to this
protection device
RCS-9798A.
Real-time data of Browse the binary input status of the protection
49
protection device device.
Browse the
Click the “Browse all channel sets”button in the
50 information of all
menu or the toolbar.
channel sets
Browse the
Click the “Browse all channels”button in the menu
51 information of all
or the toolbar.
channels

NR ELECTRIC CO., LTD. 15


Chapter 4 PCS-9010 DRRMS Front-end Function

Test result
No. Test content Test method and procedure
Local
Server
HMI

Browse the
Click the “Browse all substations” button in the
52 information of all
menu or the toolbar.
substations
Browse the channel property by double-clicking
Browse the channel
53 the channel in the tree list or by clicking the
property
right-button menu of the channel in the tree list.

16 NR ELECTRIC CO., LTD.


Chapter 5 PCS-9010 DRRMS Online Tool

Chapter 5 PCS-9010 DRRMS Online Tool


5.1 System Clock Synchronization

Functional description:

Check the clock correctness and consistency of each HMI computer of the PCS-9010 DRRMS
system.

Test result

No. Test content Test method and procedure


Local
Server
HMI

Clock of each
HMI computer
of the Check whether the clock of each HMI computer is
54
PCS-9010 synchronized.
DRRMS
system

The clock of RCS-9798A can be synchronized if


corresponding RCS-9798A is enabled to receive clock
synchronization message from PCS-9010 DRRMS.
RTU
55 Right-click a substation on the left of node tree in the
synchronization
PCS-9010 DRRMS Online Tool, select “RTU
Synchronization” to send out clock synchronization
messages to RCS-9798A.

5.2 Graph Browsing

Functional description:

Browse the following graphs:

System configuration graph, flow chart, protection management unit status supervisory chart,
substation primary system chart and secondary device template chart.

Program name: drrms

NR ELECTRIC CO., LTD. 17


Chapter 5 PCS-9010 DRRMS Online Tool

Test result
No. Test content Test method and procedure
Local
Server
HMI

Use PCS-9010 DRRMS Online Tool to view every


area flow chart, view geographic distribution of
56 Regional flow chart substations and substations accessing master
station of protection and fault information
management in the system.

Use PCS-9010 DRRMS Online Tool to view the


primary wiring diagram imported by each substation
Substation primary
57 and automatically connected secondary equipment,
system diagram
click secondary equipment and enter into
appropriate device screen.
Click the device in the substation primary system
chart, and browse device information, protective
measurement, state variables, alarms, etc. In case
of a number of state variable signals from the
Device information
58 device, view whether the value of any state variable
graph
is changed. In case of any change in protective
telemetering of the device, view whether the value
of protective measurement on the screen is
changed
Communication Use PCS-9010 DRRMS Online Tool to view
59 status of protection communication status of RCS-9798A, and observe
management unit working condition of RCS-9798A.
Use PCS-9010 DRRMS Online Tool to view
System node
60 system node supervision map, and observe running
supervision
conditions of each system node.
Click the “Previous” or “Next” button in the
PCS-9010 DRRMS Online Tool to browse the
61 Next/Previous Page
previous/next page, with the selected node in the
node tree on the left following the changes.

5.3 Event Alarm

Functional description:

When PCS-9010 has received event information from substation, it will sort them and then display
the alarm signals.. The alarm signals include audio alarm, save into history database/real-time
database, etc.

18 NR ELECTRIC CO., LTD.


Chapter 5 PCS-9010 DRRMS Online Tool

Program name: drrms

Test result
No. Test content Test method and procedure
Local
Server
HMI

In the “Relay Operations”sub-Tab page of the “Events”


Protection
Tab page in PCS-9010 DRRMS Online Tool, check the
62 operation,
protection action, fault location, etc. issued by
fault location
RCS-9798A.

In the “Alarms”sub-Tab page of the “Events”Tab page


63 Alarms in PCS-9010 DRRMS Online Tool, check the
protection alarm information issued by RCS-9798A.
In the “EBI/VEBI Status”sub-Tab page of the “Events”
Tab page in PCS-9010 DRRMS Online Tool, check the
EBI/VEBI status change information of the EBI/VEBI issued by
64
Status RCS-9798A.
EBI :Enabling binary inputs
VEBI :Virtual enabling binary inputs
In the “Binary Inputs”sub-Tab page of the “Events”Tab
Status change
65 page in PCS-9010 DRRMS Online Tool, check the
of binary Inputs
binary status change events issued by RCS-9798A.
In the “Communication”sub-Tab page of the “Events”
Communication Tab page in PCS-9010 DRRMS Online Tool, check the
66
status communication status change information issued by
RCS-9798A.
In the “Setting Surveillance” sub-Tab page of the
Setting
67 “Events”Tab page in PCS-9010 DRRMS Online Tool,
Surveillance
check the setting changes of protection device.
In the “Persistent Events”sub-Tab page of the “Events”
Tab page in PCS-9010 DRRMS Online Tool, check the
Persistent
68 items in “Persistent Communication Events”,
Events
“Persistent Protection Alarms”, “Persistent Setting
Changes”.
In the “Relay Faults“Tab page in PCS-9010 DRRMS
Online Tool, check the tripping element, fault time,
69 Relay Faults
fault phase, auto-reclosing, fault location, waveform file
name, etc.
In the “Grid Faults”Tab page in PCS-9010 DRRMS
Online Tool, check the grid faults information
70 Grid Faults
generated by the comprehensive analysis. E.g.: tripping
events, alarms, settings, EBI/VEBI, relay faults, etc.

NR ELECTRIC CO., LTD. 19


Chapter 5 PCS-9010 DRRMS Online Tool

Test result
No. Test content Test method and procedure
Local
Server
HMI
Select the area, substation, primary equipment and
secondary device in the node tree on the left window of
Hierarchical PCS-9010 DRRMS Online Tool, and display the event
71
alarm query, relay fault and grid faults on the right window
according to the selected options on the left
window(Grid faults will not be filtered by area).
Click the “Filter” on the right window in PCS-9010
DRRMS Online Tool, the “Event Filter”dialog will pop
up. Customize the search conditions in the dialog, such
72 Alarm search
as Start time/End time, and after acknowledgment,
search relevant events, relay faults and grid faults
information in history database.
In the right window in the PCS-9010 DRRMS Online
Tool, click “Ack &All”, or double click a certain entry to
Acknowledge
73 acknowledge all or to acknowledge one by one. The
alarm
alarm acknowledgment status will be refreshed and
sent out to other computers.

5.4 Settings and Operation Management

Functional description:

Browse and compare active setting group No.. active settings and virtual enabling binary inputs
(VEBI for short) etc.; and store history values about them.

Program name: drrms

Test result
No. Test content Test method and procedure
Local
Server
HMI
1. Select protection device from left node tree in the
PCS-9010 DRRMS Online Tool.
2. Send the command to retrieve setting group No. to
Browse setting the selected device to show the setting group No.
74
group No. 3. Observe whether the device address matches with
the integrated address, and whether the setting group
No. is consistent with the value viewed on the protection
device.
Browse active 1. Select a protection device from left node tree in the
75
settings PCS-9010 DRRMS Online Tool.

20 NR ELECTRIC CO., LTD.


Chapter 5 PCS-9010 DRRMS Online Tool

Test result
No. Test content Test method and procedure
Local
Server
HMI

2. Select a CPU number or all CPU numbers.


3. Issue the read setting command to protection device,
and display protection settings in batch.
4. Observe whether device address and setting group
No. match with the integrated values, and whether the
setting are consistent with the value displayed on
protection device.
1. Select a protection device from left node tree in the
PCS-9010 DRRMS Online Tool.
2. Select a CPU number or all CPU numbers.
3. Issue the read VEBI setting command, and display
Browse VEBI
76 the value of the VEBI settings after return.
settings
4. Observe whether the device address matches with
the integrated address, and whether the VEBI state is
consistent with the value displayed on protection
device.
1. Select protection device from left node tree in the
Compare
PCS-9010 DRRMS Online Tool.
current settings
77 2. After uploading the settings of device, the results of
with historical
the comparison of current value and historical value can
settings
be seen, “≠ ”will be displayed if consistent.
1. Select protection device from left node tree in the
Compare
PCS-9010 DRRMS Online Tool.
current VEBI
78 2. After upload the value of the VEBI, the comparison
with historical
results of the current and historical values of VEBI can
VEBI
be seen, “≠ ”will be displayed if consistent.
Save settings
1. Select the “Settings”Tab page of protection device.
79 as historical
2. Click “Save as history value”and checked the result.
settings
Save VEBI as 1. Select protection device “VEBI”Tab page.
80
historical VEBI 2. Click “Save as history value”and checked the result.
After select protection device, click the “print”button on
Print the setting
81 the “Settings”Tab page, print the setting value sheet by
value sheet
the customized options.
View the results of daily settings checking, and analyze
whether the check is successful by the refresh time.
82 Check settings
View whether the alarm information has changes in
valuing, or whether the pressure plate state changes.

NR ELECTRIC CO., LTD. 21


Chapter 5 PCS-9010 DRRMS Online Tool

5.5 Relay Faults and Grid Faults

Functional description:

Relay Faults :

The fault information sent by RCS-9798A in form of sheet:

E.g.: substation, primary equipment, secondary device, tripping element, fault time, fault phase,
auto-reclosing, fault location, waveform file name, etc.

Grid Faults:

Comprehensive relay faults displayed in a list:

E.g.: fault time, XML file name.

Program name: drrms

Test result
No. Test content Test method and procedure
Local
Server
HMI

In the “Relay Faults” Tab page in the PCS-9010


View waveform
DRRMS Online Tool, select a certain entry, right-click
83 file in the Relay
on it to select “Open Waveform File”and use “WaveEv”
Faults
to display waveform.

In the “Grid Faults”Tab page by the PCS-9010 DRRMS


Online Tool:
Browse details 1. Right click an entry in the relay faults.
84 of the Grid 2. In the pop-up menu, select detailed fault information.
Faults 3. When the detailed fault information window pops up,
check detailed fault information, including relay faults,
protection operation, alarm, supervisory alarm.
In the “Grid Faults” generated by the PCS-9010
DRRMS Online Tool:
1. Right click any entry in the relay faults.
Filter 2. In the pop-up menu, select detailed fault information.
information by 3. When the detailed fault information window pops up,
85
the substation view detailed fault information, including relay faults,
and device protection operation, alarm, supervisory alarm.
4. In the pop-up window, select the desired substation
and device, click filter button, and only display relevant
filter content.

22 NR ELECTRIC CO., LTD.


Chapter 5 PCS-9010 DRRMS Online Tool

Test result
No. Test content Test method and procedure
Local
Server
HMI

In the detailed fault information interface, double click


View waveform
86 relevant entry in “Grid Faults”, and use “WaveEv”to
in Grid Faults
view waveform.

In the detailed fault information interface, click “Report”


Print Grid
87 button to pop up “Report Editor” to customize print
Faults
format and print grid faults.

5.6 Historical Fault Information Query

Functional description:

Query historical fault information by duration and fault type, including protective action, alarms,
supervisory information, SOE, binary input state change and fault location information.

Program name: drrms

Test result
No. Test content Test method and procedure
Local
Server
HMI

In the “Events in Device”Tab page in the PCS-9010


Query historical
DRRMS Online Tool, select start/end time, fault
fault information
88 information type, click “Retrieve history event”button,
by duration and
and view whether the historical fault information sent
fault type
by the substation is correct.

5.7 Waveform File Management

Functional description:

Search waveform from local commercial database, retrieve historical waveform list from
RCS-9798A and retrieve historical waveform file, etc.

Program name: drrms

NR ELECTRIC CO., LTD. 23


Chapter 5 PCS-9010 DRRMS Online Tool

Test result
No. Test content Test method and procedure
Local
Server
HMI

In the “Waveforms in Device” Tab page in the


Search
PCS-9010 DRRMS Online Tool, click “Local search”
waveform file in
89 to query historical waveform information of the
local commercial
selected device in Oracle database by specified
database
start-end time.

In the “Waveforms in Device” Tab page in the


Retrieve
PCS-9010 DRRMS Online Tool, click “Retrieve List”
90 RCS-9798A
button, and view the waveform list information issued
waveform list
by RCS-9798A.
In the “Waveforms in Device” Tab page in the
PCS-9010 DRRMS Online Tool, click “Retrieve File”
Retrieve
button, view the waveform file sent by RCS-9798A,
91 RCS-9798A
and after master station receives completely, check
waveform file
whether the value “Exist in history database or not?”
changes from “No”to “Yes”.
Waveform file Before interrogating the waveform, use “sqlplus”tool to
automatically log in commercial database, use “select count(*)
92 saved in from wave_file_table”; and check the number of
commercial records in the list of waveform files, check the number
database of records again after waveform interrogation.
in the “Waveforms in Device” Tab page in the
Display
PCS-9010 DRRMS Online Tool, double click the entry
93 historical
whose “Exist in history database or not?”is “YES”, and
waveform file
use “WaveEv”to display historical waveform.

5.8 Panel Information

Functional description:

Panel No., primary equipment name, secondary name, communication status, virtual connection,
etc..

Program name: drrms

Test result
No. Test content Test method and procedure
Local
Server
HMI
In the “Panel Info”Tab page in the PCS-9010 DRRMS
94 Curve display
Online Tool, double click an analog quantity to view

24 NR ELECTRIC CO., LTD.


Chapter 5 PCS-9010 DRRMS Online Tool

corresponding curves.

In the “Panel Info” Tab page, double click


Virtual
95 “VC(Port-Addr)”to pop up the virtual connection tool
connection tool
for corresponding device.
Open conductor
In the “Panel Info”Tab page, check whether the status
supervision;
96 of open conductor supervision. VTS supervision, CVT
VTS/CTS
supervision is correct.
supervision

5.9 Authority Check

Functional description:

3 authorization codes are allocated for various responsibilities. A dialog will pop up to prompt the
user to log in senior authorization code when the operation is over the limit of existing log in
authorization code.

3 levels of authorization codes are available:

1) “Super user”;
2) “Administrator”;
3) “Engineer”.

Program name: drrms

Test result
No. Test content Test method and procedure
Local
Server
HMI
“Super user”can log in DRRMS Online Tool,
Authority of
97 DRRMS Configuration Tool and
“Super user”
Authority Management Tool.
“Administrator”can log in DRRMS Online Tool and
Authority of
98 DRRMS Configuration Tool but can not log in
“Administrator”
Authority Management Tool.

Authority of
99 “Engineer”can only log in DRRMS Online Tool.
“Engineer”

5.10 Authority Management Tool

Functional description:

Authority Management Tool is applied to edit the responsibilities for various authorization codes
and allocate staff to the authorization codes.

NR ELECTRIC CO., LTD. 25


Chapter 5 PCS-9010 DRRMS Online Tool

Program name: drrms

Test result
No. Test content Test method and procedure
Local
Server
HMI

Authority Authority Management Tool can be used to edit and


100 Management modify the authority of various codes, allocate users to
Tool the codes and then check the result.

26 NR ELECTRIC CO., LTD.


Chapter 6 PCS-9010 DRRMS WEB Tool

Chapter 6 PCS-9010 DRRMS WEB Tool


Functional description:

Online monitoring function of relay protection operation and fault information (Region Ⅲ).

Input “http://WEB-host-ip:8080”in the login page of IE.

E.g.: if the IP of DRRMS server is 198.87.91.200, then input:

“http:// 198.87.91.200:8080”.

Test result
No. Test content Test method and procedure
Local
Server
HMI

101 Graph browsing Use middle button.

In the “Relay Operations” sub-Tab page of the


Protection
“Events” Tab page in PCS-9010 DRRMS Online
102 operation,
Tool, check the protection action, fault location, etc.
fault location
issued by RCS-9798A.
In the “Alarms”sub-Tab page of the “Events”Tab
103 Alarms page in PCS-9010 DRRMS Online Tool, check the
protection alarm information issued by RCS-9798A.
In the “Binary Inputs”sub-Tab page of the “Events”
Status change of Tab page in PCS-9010 DRRMS Online Tool, check
104
binary Inputs the binary status change events issued by
RCS-9798A.
In the “Communication” sub-Tab page of the
Communication “Events” Tab page in PCS-9010 DRRMS Online
105
status Tool, check the communication status change
information issued by RCS-9798A.
In the “Setting Surveillance” sub-Tab page of the
Setting
106 “Events” Tab page in PCS-9010 DRRMS Online
Surveillance
Tool, check the setting changes of protection device.

In the “Relay Faults“Tab page in PCS-9010 DRRMS


Online Tool, check the tripping element, fault time,
107 Relay Faults
fault phase, auto-reclosing, fault location, waveform
file name, etc.

In the “Grid Faults”Tab page in PCS-9010 DRRMS


Online Tool, check the grid faults information
108 Grid Faults generated by the comprehensive analysis. E.g.:
tripping events, alarms, settings, EBI/VEBI, relay
faults, etc.

NR ELECTRIC CO., LTD. 27


Chapter 6 PCS-9010 DRRMS WEB Tool

Select the area, substation, primary equipment and


secondary device in the node tree on the left window
Hierarchical of PCS-9010 DRRMS Online Tool, and display the
109
alarm event query, relay fault and grid faults on the right
window according to the selected options on the left
window(Grid faults will not be filtered by area).
Click the “Filter”on the right window in PCS-9010
DRRMS Online Tool, the “Event Filter”dialog will
pop up. Customize the search conditions in the
110 Alarm search
dialog, such as Start time/End time, and after
acknowledgment, search relevant events, relay
faults and grid faults information in history database.
1. Select a protection device from left node tree in
the PCS-9010 DRRMS Online Tool.
111 Browse settings 2. Select a CPU number or all CPU numbers.
3. Click “Settings” Tab page, check corresponding
setting values.
1. Select a protection device from left node tree in
the PCS-9010 DRRMS Online Tool.
112 Browse VEBI 2. Select a CPU number or all CPU numbers.
3. Click “VEBI”Tab page, view corresponding VEB
values.
In the “Relay Faults” Tab page in the PCS-9010
View waveform
DRRMS Online Tool, select a certain entry,
113 file in the Relay
right-click on it to select “Open Waveform File”and
Faults
use “WaveEv”to display waveform.
In the “Grid Faults” Tab page by the PCS-9010
DRRMS Online Tool:
1. Right click an entry in the relay faults.
Browse details 2. In the pop-up menu, select detailed fault
114 of the Grid information.
Faults 3. When the detailed fault information window pops
up, check detailed fault information, including relay
faults, protection operation, alarm, supervisory
alarm.

28 NR ELECTRIC CO., LTD.


Chapter 7 Manual Version History

Chapter 7 Manual Version History


In the current version of the instruction manual, several descriptions on existing features have
been modified.

Manual version and modification history records

Manual Version Software


Date Description of change
Source New Version
1.00 / 2010-11-27 Form the original manual.

NR ELECTRIC CO., LTD. 29