ABSTRACT Fault detection in resonant grounding (RG) distribution networks remains a challenge due to
weak fault signals, extremely complex fault conditions, and unstable intermittent arc grounding faults. This
paper addresses this issue by applying generalized S-transform (GST) with a variable factor to conduct
denoising of transient zero-sequence currents based on threshold filtering followed by time-frequency
distribution filtering in sequence. Meanwhile, this paper proposes a comprehensive multi-criteria faulty
feeder detection method based on the transient zero-sequence current polarity (criterion 1), the energy relative
entropy (criterion 2), and the total transient current energy (criterion 3). Here, criteria 2 and 3 are based on
the time-frequency representation of the GST. The performances of the proposed denoising and faulty feeder
detection methods are evaluated under single line to ground faults based on simulations conducted using a
modeled 10 kV RG networks with overhead and cable mixed lines in addition to reasonably sophisticated
permanent and intermittent arc discharge models to ensure that the simulations faithfully represent actual
complex working conditions. Compared with existing method, simulation experiments and field test show
that the method proposed in this paper provide a better denoising effect with stronger self-adaptability, higher
detection accuracy, and a faster calculation speed.
INDEX TERMS Fault detection, resonant grounding distribution networks, generalized S-transform,
variable factor, denoising method, intermittent arc grounding fault, multi-criteria.
This work is licensed under a Creative Commons Attribution 4.0 License. For more information, see https://creativecommons.org/licenses/by/4.0/
VOLUME 8, 2020 91351
Z. Wei et al.: Fault Detection Based on the GST With a Variable Factor for RG Distribution Networks
TABLE 1. Pros and cons of the existing methods and the proposed method.
detection. Owing to the richness and stability of transient and then, selected the effective coefficients based on the
fault signal features, the detection methods employed in change rate of a wavelet packet energy entropy to recon-
RG systems are mainly the passive detection based on struct an effective signal of the arc fault. Guo et al. [9]
transient signals. Primary examples of detection methods acquired time-frequency gray scale images for all feeders via
employing these features include the wavelet transform (WT) the continuous wavelet transform (CWT), and distinguished
[7]–[10], Hibert-Huang transform (HHT) [11], [12], images associated with the faulty feeder from those associ-
S-transform (ST) [13]–[18], Prony algorithm [19], [20], ated with healthy feeders using a trained convolutional neural
mathematical morphology (MM) [21]–[23], fuzzy c-means network (CNN). Fault detection has also been facilitated
(FCM) clustering [24], [25], and support vector machine by applying the wavelet packet transform to segregate the
(SVM) [26], [27]. Each of these techniques have pros and high-frequency components of three-phase current signals
cons as listed in Table 1. during power swings [10].
The WT provides a time-frequency window that varies The HHT employs empirical mode decomposition (EMD)
according to the frequency so that it can extract time and Hilbert transform, and is applicable for the analysis of
and frequency information from transient fault signals. nonlinear and non-stationary signals. Chen et al. [11] used the
Wang et al. [7] constructed a mixed atom dictionary by a EMD to resolve the current into several intrinsic mode func-
cosine packet and a wavelet and adopted the matching pursuit tion (IMF), and then calculated Hilbert transform for IMF to
algorithm to extract characteristic atoms of each feeder to obtain the Hilbert spectrum of arc fault current signals to rec-
extract transient signals. Guo et al. [8] used wavelet packet to ognize the series arc fault. Wang et al. [12] utilized complete
make five-layer decomposition of main loop current firstly, ensemble EMD with adaptive noise (CEEMDAN) to extract
the first intrinsic mode function (IMF) of the zero-sequence time warping (DTW), and then the faulty feeder was selected
current and used the Hilbert transform to obtain a fault detec- by FCM cluster method without setting threshold [25].
tion index for identifying the faulty feeder. The SVM is a supervised learning model that serves as
For the ST, Stockwell et al. [13] presented a lossless and a kind of generalized linear classifier for the binary classi-
reversible multiresolution time-frequency analysis method fication of data. An SVM classification algorithm has been
in 1996, where the resolution was adjustable according to employed for single-phase arc-fault detection in distribution
changes in the frequency based on a moving and scalable networks based on a combination of transient zero-sequence
localizing Gaussian window. Pinnegar and Mansinha [14] current and two-phase current difference characteristics [26].
modified the ST into a generalized ST (GST) form to obtain Chaitanya et al. [27] presented an high-impedance faults
time-frequency spectra with different time-frequency reso- detection technique for distribution lines incorporating the
lutions by manually changing the value of an adjustable distributed generators, where variational mode decomposi-
parameter. However, the process was not adaptive. Zhou and tion was used to obtain the analytic signal and then used this
Chen [15] addressed this limitation in the local window reso- data as the input into the support vector machine to create an
lution of the time-frequency spectrum by adopting a variable intelligent classifier.
factor that improves the scalability of the localizing Gaussian
window. He et al. [16] obtained the time-frequency matrix B. PROBLEMS OF EXISTING FAULTY FEEDER DETECTION
of transient zero-sequence currents via the GST, and realized METHODS FOR RG SYSTEMS
fault section location by comparisons of the relative entropy 1) FAULT SIGNAL PROCESSING
of the transient current energies (i.e., transient current energy The presence of noise distorts the characteristics of fault
relative entropy). Fault detection has also been facilitated by signals. However, most existing methods extract fault features
extracting features from three-phase current signals by the directly without first filtering the signals to remove noise.
ST, and distinguishing features associated with the faulty
feeder from those associated with healthy feeders using a 2) FAULT FEATURE EXTRACTION
feedforward neural network (FFNN) [17]. Peng et al. [18]
For WT-based methods, the wavelet basis function is difficult
utilized ST to extract the standard amplitude ratios of the
to select, and this seriously restricts the adaptability of WT
frequency components in zero-mode transients of each feeder
signal decomposition to accommodate variations in signal
and proposed a faulty feeder detection criterion by utilizing
features. The HHT has three problems that distort the signal
the amplitude information of the zero-mode transients cap-
decomposition results. These include the end effect of EMD,
tured at both terminals.
the EMD mode mixing problem, and the residual noise. The
The Prony algorithm is a method for fitting data sampled
specific mother wavelet of the original ST proposed by Stock-
in equal intervals using a linear combination of a set of
well renders adjustments to the time-frequency resolution
exponential terms. Faulty feeder detection was conducted
inflexibly because of the fixed window width of Gaussian
based on a linear relationship between the fault location and
window function, and the later proposed modifications to
the inverse of the damping coefficient of the fundamental
the GST are not effectively applied in fault detection. Sig-
frequency component in the Prony model [19]. Liu et al. [20]
nal feature extraction conducted by the Prony algorithm is
utilized Prony algorithm to extract the transient information
susceptible to noise, and its fitting effect for high frequency
of main frequency components at each feeder to select faulty
signals is not good.
feeder.
The MM approach is a mature method of nonlinear sig-
3) FAULTY FEEDER DETECTION CRITERIA
nal analysis that was originally applied in the field of
image signal processing. Barik et al. [21] was the first to Most existing faulty feeder detection methods apply a single
utilize MM for identifying faulty feeders in RG systems. detection criterion. As a result, these methods are prone to
Shu et al. [22] detected faulty feeders according to the mor- incorrectly detect faulty feeders due to variations in signal
phological peak-valley features of the constructed wavelet features. Although multi-criteria methods have been devel-
coefficients under characteristic bands. The morphological oped to improve the accuracy of faulty feeder detection,
median filter is exploited to wrest unique fault features which existing methods are difficult to utilize because of the vast
are then fed as an input to a decision tree classifier to classify sample libraries required, complicated procedures, and long
the fault type [23]. calculation times.
The FCM clustering algorithm automatically classifies
sample data to obtain the membership of each sample point C. CONTRIBUTIONS
to sample centers. Guo and Yang [24] applied FCM clus- The above problems are addressed in the present study, and
tering to the amplitude-polarity feature matrix (APFM) of thereby makes the following contributions.
transient fault signals to detect faulty feeders according to
matrix elements lying outside of a threshold setting. Ampli- 1) THE PURITY OF RECORDED FAULT DATA
tude correlation coefficient matrix (ACCM) of transient The GST is modified to include a variable factor σ for
zero-sequence currents was obtained via improved dynamic self-adaptively adjusting the local window resolution of the
Here, n = 0, 1,. . . , N −1. Equation (8) can be discretized by Then, the appropriate value of η is obtained by analyzing data
letting f → n NT and τ → kT , where N is the number of in each interval. The threshold function is given as follows.
sampling points, n = 0, 1, 2, . . . , N −1 denotes the frequency
(
1, GST (k, n) ≥ η
sequence, k = 0, 1, 2, . . . , N − 1 denotes the time sequence, H1 (k, n) = (k, n) ∈ R (16)
and T is the sampling interval, which yields the following 0, GST (k, n) < η
discrete GST. After conducting threshold filtering, GST(k, n) is trans-
N −1 2 2 2 formed as follows.
n + m −2π m2 σf i2πmn
h n i X
GSTσ kT , = H e n e N (10)
NT
m=0
NT GST1 (k, n) = GST (k, n) ∗ H1 (k, n) (17)
FIGURE 6. Model of 10 kV RG distribution network. FIGURE 8. Arc discharge model established in PSCAD.
FIGURE 11. The transient current energy relative entropy of all feeders in
the selected frequency band (SFB) under −5 dB SNR condition after an
SLG fault occurs in the feeder L1 , L3 , L5 , and bus respectively.
FIGURE 12. Simulated zero-sequence currents of all feeders after arc trial frequency period after an arc grounding fault occurs in
grounding faults occurred in PSCAD. the feeder L1 , L2 , L3 , and L4 respectively, where (a) and
(c) are current waveforms obtained after a permanent arc
occurs in the feeder L1 and an intermittent arc grounding grounding fault occurs in the feeder L1 and L3 with an SNR
fault with the arc resumption intervals of 10 ms occurs in the of −5 dB respectively, (b) and (d) are current waveforms
feeder L2 . obtained after an intermittent arc grounding fault with 10 ms
Fig. 13 presents the comparisons of original current wave- resumption intervals occurs in the feeder L2 and L4 with
forms, current waveforms with noise, and denoised current an SNR of 0 dB respectively. From these figures, we can
waveforms of all feeders obtained during the first 1/4 indus- see that the denoised waveforms have a little distortion
FIGURE 14. The transient current energy relative entropy of all feeders in
the SFB after an arc grounding fault occurs in the feeder L1 , L2 , L3 , and
L4 , and bus respectively.
TABLE 6. Denoising performance results of the simulated signals obtained for L1 during L1 faults in the 10 kV RG system.
TABLE 7. The comparisons between paper [16], [31], [36] and this paper.
TABLE 8. The comparison of calculation times. TABLE 9. Detection results of field test.
FIGURE 17. The scene when the SLG fault occurs in feeder No.114.
FIGURE 16. The 10 kV RG distribution network topology.
These results indicate that the method proposed in this paper method of paper [31] also applied single criterion based on ST
provides superior faulty feeder detection accuracy than the energy from short window data. We note from the table that
existing methods considered. the proposed comprehensive multi-criteria detection method
In addition, the calculation times required by the com- requires less calculation time than the other methods, partic-
pared detection methods were evaluated for the detection ularly that of paper [26]. Therefore, in practical applications,
process results discussed above for the SLG fault, and the the proposed method has a faster judgment speed.
times are listed in Table 8. Here, the methods of paper [26]
and paper [31] are added to test the compared calculation VII. FIELD TEST OF SLG FAULT
times. Paper [26] applied the single-criterion method based In order to verify the performance of the proposed method,
on the difference of two-phase current with SVM, and the we carried out a field test at 10 kV distribution power line
[9] M.-F. Guo, X.-D. Zeng, D.-Y. Chen, and N.-C. Yang, ‘‘Deep-learning- [30] Y. Xue, Z. Feng, and B. Xu, ‘‘Analysis of transient characteristics of signals
based earth fault detection using continuous wavelet transform and convo- phase earth fault in non-solidly Earthed network,’’ J. Xi’an Jiaotong Univ.,
lutional neural network in resonant grounding distribution systems,’’ IEEE vol. 38, no. 2, pp. 195–199, 2004.
Sensors J., vol. 18, no. 3, pp. 1291–1300, Feb. 2018. [31] H. Shu and S. Peng, ‘‘A fault line detection algorithm for distribu-
[10] B. Patel and P. Bera, ‘‘Fast fault detection during power swing on a hybrid tion network of overhead line and underground cable mixed lines using
transmission line using WPT,’’ IET Gener., Transmiss. Distrib., vol. 13, S-transform energy from short window data,’’ Trans. China Electrotechn.
no. 10, pp. 1811–1820, May 2019. Soc., vol. 24, no. 10, pp. 152–159, 2009.
[11] C. Chen, F. Guo, Y. Liu, Z. Wang, Y. Chen, and H. Liang, ‘‘Recognition of [32] H. Shu and J. Liu, ‘‘Adaptive method for fault circuit selection in arc
series arc fault based on the Hilbert huang transform,’’ in Proc. IEEE 61st suppression coils system by using transient energy,’’ Autom. Electr. Power
Holm Conf. Electr. Contacts (Holm), Oct. 2015, pp. 324–330. Syst., vol. 30, no. 11, pp. 72–76, 2006.
[12] X. Wang, J. Gao, X. Wei, Z. Zeng, Y. Wei, and M. Kheshti, ‘‘Single line to [33] L. Wang, H. Gao, and G. Zou, ‘‘Modeling methodology and fault simula-
ground fault detection in a non-effectively grounded distribution network,’’ tion of distribution networks integrated with inverter-based DG,’’ Protec-
IEEE Trans. Power Del., vol. 33, no. 6, pp. 3173–3186, Dec. 2018. tion Control Mod. Power Syst., vol. 2, no. 1, pp. 370–378, Dec. 2017.
[34] Y. Xu, M. Guo, B. Chen, and G. Yang, ‘‘Modeling and simulation analysis
[13] R. G. Stockwell, L. Mansinha, and R. P. Lowe, ‘‘Localization of the
of arc in distribution network,’’ Power Syst. Protection Control, vol. 43,
complex spectrum: The s transform,’’ IEEE Trans. Signal Process., vol. 44,
no. 7, pp. 57–64, 2015.
no. 4, pp. 998–1001, Apr. 1996.
[35] R. Gu, X. Cai, H. Chen, Z. Jin, and W. Gao, ‘‘Modeling and simulating
[14] C. R. Pinnegar and L. Mansinha, ‘‘The S-transform with windows of of single-phase arc grounding fault in non-effective Earthed networks,’’
arbitrary and varying shape,’’ Geophysics, vol. 68, no. 1, pp. 381–385, Autom. Electr. Power Syst., vol. 33, no. 13, pp. 63–67, 2009.
Jan. 2003. [36] H. Shu and S. Peng, ‘‘Distribution network fault line detection using the
[15] Z. Zhou and Y. Chen, ‘‘Generalized S-transform with variable-factor and full waveband complex relative entropy of wavelet energy,’’ High Voltage
its time-frequency filtering,’’ Coal Geol. Explor., vol. 39, no. 6, pp. 63–66, Eng., vol. 35, no. 7, pp. 1559–1564, Jul. 2009.
and 71, 2011.
[16] L. He, C. Shi, Z. Yan, J. Cui, and B. Zhang, ‘‘A fault section location
method for small current neutral grounding system based on energy rel-
ative entropy of generalized S-transform,’’ Trans. China Electrotech. Soc.,
vol. 32, no. 8, pp. 274–280, 2017.
[17] M. Shafiullah and M. A. Abido, ‘‘S-transform based FFNN approach for
distribution grids fault detection and classification,’’ IEEE Access, vol. 6,
pp. 8080–8088, 2018. ZHINONG WEI (Member, IEEE) received the
[18] N. Peng, K. Ye, R. Liang, T. Hou, G. Wang, X. Chen, and S. Teng, B.S. degree from the Hefei University of Technol-
‘‘Single-phase-to-earth faulty feeder detection in power distribution net- ogy, Hefei, China, in 1984, the M.S. degree from
work based on amplitude ratio of zero-mode transients,’’ IEEE Access, Southeast University, Nanjing, China, in 1987, and
vol. 7, pp. 117678–117691, 2019. the Ph.D. degree from Hohai University, Nanjing,
[19] B. Gou and K. O. Owusu, ‘‘Linear relation between fault location and the in 2004.
damping coefficient in faulted signals,’’ IEEE Trans. Power Del., vol. 23, He is currently a Professor of electrical engi-
no. 4, pp. 2626–2627, Oct. 2008.
neering with the College of Energy and Electri-
[20] M. Liu, ‘‘A new correlation analysis approach to fault line selection based cal Engineering, Hohai University. His research
on transient main-frequency components,’’ Power Syst. Protection Control,
interests include power system state estimation,
vol. 44, no. 2, pp. 74–79, 2016.
integrated energy systems, smart distribution systems, optimization and plan-
[21] M. A. Barik, A. Gargoom, M. A. Mahmud, M. E. Haque, H. Al-Khalidi,
ning, load forecasting, and integration of distributed generation into electric
and A. M. T. Oo, ‘‘A decentralized fault detection technique for detecting
single phase to ground faults in power distribution systems with resonant
power systems.
grounding,’’ IEEE Trans. Power Del., vol. 33, no. 5, pp. 2462–2473,
Oct. 2018.
[22] H. Shu, H. Huang, X. Tian, J. Dong, and R. Huang, ‘‘Fault line selec-
tion in resonant Earthed system based on morphological peak-valley
detection,’’ Autom. Electr. Power Syst., vol. 43, no. 1, pp. 228–233,
2019.
YUEXUAN MAO received the B.S. degree in elec-
[23] R. Godse and S. Bhat, ‘‘Mathematical morphology-based feature-
trical engineering from the College of Energy and
extraction technique for detection and classification of faults on power
Electrical Engineering, Hohai University, Nanjing,
transmission line,’’ IEEE Access, vol. 8, pp. 38459–38471, 2020.
China, in 2018, where she is currently pursuing the
[24] M.-F. Guo and N.-C. Yang, ‘‘Features-clustering-based Earth fault detec-
M.S. degree.
tion using singular-value decomposition and fuzzy c-means in resonant
grounding distribution systems,’’ Int. J. Electr. Power Energy Syst., vol. 93, Her research interest includes the fault location
pp. 97–108, Dec. 2017. for distribution networks.
[25] X. Shao, M. Guo, and L. You, ‘‘Faulty line selection method using mutual
correlation cluster of grounding fault waveforms based on improved DTW
method,’’ Electr. Power Autom. Equip., vol. 38, no. 11, pp. 63–71, and 78,
2018.
[26] K. Chen and B. Chen, ‘‘Research on arc fault line selection based on
improved transient correlation analysis and support vector machine,’’
Power Syst. Protection Control, vol. 44, no. 24, pp. 66–73, 2016.
[27] B. K. Chaitanya, A. Yadav, and M. Pazoki, ‘‘An intelligent detection of ZHIHUA YIN received the B.S. degree in electri-
high-impedance faults for distribution lines integrated with distributed cal engineering from the China University of Min-
generators,’’ IEEE Syst. J., vol. 14, no. 1, pp. 870–879, Mar. 2020. ing and Technology, Xuzhou, China, in 2014, and
[28] J. Cai and X. Li, ‘‘Gear fault diagnosis based on time–frequency domain the M.S. degree from Hohai University, Nanjing,
de-noising using the generalized s transform,’’ J. Vib. Control, vol. 24, China, in 2018, where he is currently pursuing the
no. 15, pp. 3338–3347, Aug. 2018. Ph.D. degree.
[29] S. V. Khond and G. A. Dhomane, ‘‘Optimum coordination of directional His research interest includes the fault location
overcurrent relays for combined overhead/cable distribution system with for distribution networks.
linear programming technique,’’ Protection Control Mod. Power Syst.,
vol. 4, no. 1, pp. 114–120, Dec. 2019.
GUOQIANG SUN received the B.S., M.S., and HAIXIANG ZANG received the B.S. degree in
Ph.D. degrees in electrical engineering from Hohai electrical engineering from Nanjing Normal Uni-
University, Nanjing, China, in 2001, 2005, and versity, in 2009, and the Ph.D. degree in electrical
2010, respectively. engineering from Southeast University, in 2014.
From 2015 to 2016, he was a Visiting Scholar He is currently an Associate Professor with
with North Carolina State University, Raleigh, NC, the College of Energy and Electrical Engineering,
USA. He is currently an Associate Professor with Hohai University, Nanjing, China. His research
the College of Energy and Electrical Engineering, interests include generation of renewable energy,
Hohai University. His research interests include operation, and control of power systems, and so
power system analysis, economic dispatch, and on.
optimal control of integrated energy systems.