Graph : Current Transformer Excitation Ratio and Phase Test Set

Test Name IEC Test

File Name IEC Test

Tap No 1S1-1S3

Serial No OC3639/1/1/2

Ratio 400/1

Burden 0

Manufacture MEHRU

Date 28.02.2013

Time 15.19.25
Parameters Values
Voltage (V) Current (A)

class 20VA5P30 3500.5679 1


Knee Voltage 2825 V 3500.5679 1
Knee Current 0.033 A 3383.6533 0.4037
Rw@75 10.89 Ohm 3356.1025 0.3068
Ratio 401.24 3327.6263 0.2413
Remanence 0% 3295.2152 0.1913
Loss 47.92 W 3258.2387 0.1503
Power Factor 0.507 3218.7107 0.1197
Insulation 2.9G Ohm 3178.564 0.0967
LossE 47.2 % 3139.2795 0.0804
ISF 174.8 3094.0609 0.0666
Frequency 50 Hz 3033.0341 0.0535
2961.9344 0.0435
2901.1743 0.0385
2817.2249 0.0327
2702.2048 0.0273
2578.188 0.0232
2425.8269 0.0196
2253.2223 0.0166
2059.4298 0.014
1837.3338 0.0118
1566.3023 0.0097
1192.3513 0.0076
915.237 0.0061
703.3362 0.005
539.8116 0.0041
414.354 0.0034
316.4466 0.0028
240.9512 0.0023
183.1292 0.0019
138.3999 0.0016

Page 1 of 2 2:48:22PM
Voltage (V) Current (A)
104.5475 0.0013
78.4858 0.0011
59.1724 0.0009
44.6167 0.0007
33.4715 0.0006

Page 2 of 2 2:48:22PM