Fixed Issues Page 1 of 5

MAJOR SIM REFERENCE PRODUCT AREA DETAILS Column1


9.50 0 DE3442,00388066 LD PLC EGD Smart Build does not catch an EGD error on second validation.
9.50 0 DE3547,00392832 LD PLC EGD EGD Configuration Server does not update correctly.
9.50 0 DE3122,00348202 LD PLC EGD Crash when configuring an EGD produced exchange for a 90-30 target with a CPU364
9.50 0 DE3693 LD PLC EGD Embedded Ports are not interacting with the EGD config server properly
9.50 0 DE2805,00290111 LD PLC EQUALITY RX3i redundancy system - config going not equal
9.50 0 DE3194 LD PLC FBD FBD Preview from Toolchest no longer works
9.50 0 DE3154,00350257 LD PLC FUNCTION BLOCKS Fixed issue where monitoring a UDFB instances with variable description turned on would cause memory usage to
constantly increase and would also cause an increase in CPU usage.
9.50 0 DE3381,00380354 LD PLC HELP CPE330 missing F1 help in InfoViewer.
9.50 0 DE3105,00343087 LD PLC HELP Assigning a %I to a coil generate validation error when help says it's allowed for 9030
9.50 0 DE3180,00354602 LD PLC HELP Updated PACSystems RX3i Serial Communications Modules Companion help file
9.50 0 DE3184,00346312 LD PLC HELP Bad Gateway IP leads to misleading error - 0.0 Mismatch of Communications Interface
9.50 0 DE3727,00416239 LD PLC HELP Help is wrong for command line launch
9.50 0 DE3050,00335382 LD PLC HWC Fixed Versamax Profibus DP issue - GSD Module crash after selection
9.50 0 DE3114,00343621 LD PLC HWC Fixed issue where the incorrect configuration was being generated for a Profibus slave module under a BEM003
Profibus Master and the Slave module had more than 4 data area.
9.50 0 DE3117,00339138 LD PLC HWC Fixed issue where uploading into a new target from a controller that was downloaded using either Moderate or High
compression would fail.
9.50 0 DE3225,00365198 LD PLC HWC Fixed GSDML issue regarding missing Device Type names.
9.50 0 DE3271,00368751 LD PLC HWC Fixed issue when opening older 5.70 projects.
9.50 0 DE3343,00375833 LD PLC HWC Opening a RX3i NIU project can cause variable terminals on ETM001 to be deleted.
9.50 0 DE3357,00377387 LD PLC HWC Fixed issue that caused a project corruption when upgrading a redundant CPE330 to a new catalog version. Also
added some code that repairs projects already corrupted by this issue. These repaired projects will require manual
review of the Redundant Transfer List settings.
9.50 0 DE3358 LD PLC HWC HWC export was mising GSDMLs from embedded PNCs.
9.50 0 DE3362,00360824 LD PLC HWC Redundancy Tab in Online Status is not there for CPE330
9.50 0 DE3405 LD PLC HWC Added ability to Change GSDML for the CPE330.
9.50 0 DE3424,00385613 LD PLC HWC Converting a 90-30 target to RX3i did not always convert DeviceNet devices properly.
9.50 0 DE3427,00385694 LD PLC HWC Embedded PNC Variable mode target property could not be enabled and IO Variables on embedded PNC devices
were incorrect.
9.50 0 DE3625,00393994 LD PLC HWC Importing configuration for IEC61850 doesn't always clean up previous configuration properly.
9.50 0 DE3832,00423540 LD PLC HWC CPE330 Variable Mode Crash
9.50 0 DE3112,00339410 LD PLC HWC Versamax IO carrier popup selection box is empty
9.50 0 DE3425 LD PLC HWC Cannot copy/paste Profinet IO device from PNC to Embedded one on CPE330
9.50 0 DE3227 LD PLC HWC Number Media Redundancy Managers >1 not detecting embedded Profinet on CPE330
9.50 0 DE3258 LD PLC HWC PME CPE330 Overlapping Subnet Detection Issue
9.50 0 DE3261 LD PLC HWC PME crashes when IO device added to Embedded Profinet
9.50 0 DE3420 LD PLC HWC Redundancy mode should be disabled for Embeded PNC devices when redundancy switched to True on CPE330

9.50 0 DE3149,00350294 LD PLC IMPORT Fixed issue where importing the latest GSDML files for the PNS001 and CEP001 on a 32-bit OS would result in a
"out of memory error".
9.50 0 DE3056 LD PLC IMPORT Importing Redundany HWC with Catalog upgrades has bad results when selecting 'No'
9.50 0 DE3216,00362907 LD PLC INSTALL PME9.0 with 8.60 remnants (left over sims) results in unexpected behaviors (MasterList)
9.50 0 DE3199,00355827 LD PLC LOGIC FBD F11/F12 toggle functions not working.
9.50 0 DE3203,00324912 LD PLC LOGIC CPE305 Crash when Array with Variable Index Used as Input to Parametrized LD Block.
9.50 0 DE3208,00360032 LD PLC LOGIC Unable to Add VersaSafe Logic Blocks.
9.50 0 DE3209 LD PLC LOGIC Updated PACSystems C Toolkit URL for VersaSafe blocks.
9.50 0 DE3218,00359998 LD PLC LOGIC Fixed issue for VersaSafe startup error: warning unable to check safety logic for block.
9.50 0 DE3279,00371051 LD PLC LOGIC Improved security for locked blocks.
9.50 0 DE3314,00374007 LD PLC LOGIC Fixed crash when Validation issues too many errors.
9.50 0 DE3320,00362169 LD PLC LOGIC Upload Versamax project including IC200BEM003 or empty carrier fails.
9.50 0 DE3338,00377381,0037610 LD PLC LOGIC Can no longer configure submodule I/O on Profinet submodules.
9
9.50 0 DE3404,00367313 LD PLC LOGIC Memory Leak when monitoring alias variables
9.50 0 DE3408,00408245 LD PLC LOGIC Project with a DSM module configured shows all logic elements as not equal after Verify
9.50 0 DE3443,00382185 LD PLC LOGIC Unable to download Cam Files
9.50 0 DE3563,00399426 LD PLC LOGIC ARRAY_SIZE always gives value of 1 for PSB input parameter.
9.50 0 DE3636,00408245 LD PLC LOGIC PME Rejects Valid Ladder Logic Rung
9.50 0 DE3795,00410232 LD PLC LOGIC PME crashes when validate the Rx3i project
9.50 0 DE3318,00373375 LD PLC LOGIC Unable to add VersaSafe Logic to the PME
9.50 0 DE3835 LD PLC OPTIONS Sync Process System Data property is missing from Controller General options
9.50 0 DE3092 LD PLC REPORTING Redundant 9070 material report is showing HWC from one configuration only
9.50 0 DE3702 LD PLC ST In ST - Compare Length is using the head of the array and not the entire array
9.50 0 DE3851,00406099 LD PLC UDT PACsystems C Toolkit mislocating UDT data
9.50 0 DE3624 LD PLC UDT The length of a UDT string member is not importing Properly when imported as part of a UDFB
9.50 0 DE3124,00348982 LD PLC UPLOAD Fixed issue where uploading from a 9070 Controller that contained a large number of blocks(>200) would fail.
9.50 0 DE3803,00410539 LD PLC UPLOAD Upload issue from Rx3i with a PMM335
9.50 0 DE3174,00354075 LD PLC VALIDATION Upon import getting a HSDR .ext error on import. PME then crashes when Processing SEQUENC .exp
9.50 0 DE3407 LD PLC VALIDATION PNS modules disappear from Profinet on Primary HWC after second mirroring.
9.50 0 DE3406 LD PLC VALIDATION Validation does not remove PNC submodules from Secondary HWC.
9.50 0 DE3363,00376325 LD PLC VARIABLES Fixed Feedback Zone References tab.
9.50 0 DE3421,00379019 LD PLC VARIABLES Fixed issues moving values into variables.
9.50 0 185176 PCM GENERAL Make Latest operation caused Machine Edition to terminate unexpectedly
9.50 0 185178,00332993 PCM GENERAL A Machine Edition project got locked out after an Undo Checkout of the project failed with a crash
9.50 0 185183,00364900 PCM GENERAL The project popup menu items were not always enabled or disabled according to the current status of the project

9.50 0 185186,00377682 PCM GENERAL Label item for undo checkout of a ME project showed up in the project's History Report when the server was using
VSS as backend.

This fix will prevent the issue from occurring in the future. However, the existing label items containing the label
string '_FUndoCheckout' have to be manually changed to '_FUndoCheckin' in the server VSS DB in order for them
to stop showing up in the History Report.
9.50 0 185190,00408038 PCM GENERAL Layout of tool windows was reset after PME close and re-open
9.50 0 DE3428,185188,00386830 PCM LOCAL MANAGER Machine Edition crashed when logging on to the Local Change Management
9.50 0 185187,00378887 PCM PLANT LAYOUT The pages of a factory layout were randomly listed in the Navigator and in the InfoViewer
9.50 0 185181,00341471 PCM SECURITY Read-only ME project allowed user to force the values in the Reference View Tables
9.50 0 185182,00364055 PCM SECURITY User with the Logic Changes permission was not able to edit Structured Text files in a ME project
9.50 0 185189,00405892 PCM SECURITY Unauthorized users were allowed to create or add projects to local computer and server
9.50 0 185180,00346403 PCM Toolchest The toolchest drawers in the server location didn't show up
9.50 0 DE3673 PME CONVERT Project with max Lans allows CPU310 to be replaced with CPE330.
9.50 0 DE3175,00352218 PME INTERFACE Find in target command disappears from the quick access toolbar
9.50 0 DE3077 PME LICENSING Fixed issue where a project could not be saved when the project was opened with an unlicensed PME and license
was subsequently added.
9.50 0 DE3429 PME PME Local Change Management option is missing on PME 9.0
9.50 0 DE3477,00392699 PME PME Apply Machine Edition Updates on Startup does not work, but works in older version 8.50
9.50 0 DE3049,00384202 PME PROJECT DeviceNet Communications Module was preventing opening of project
9.50 0 DE3544,00392435 PME PROJECT Closing a shared project would sometimes cause PME to crash.
9.50 0 DE3121 PME PROJECT DW Lists initialize error during openning empty project after download of a large project
9.50 0 DE3033 PME PROJECT Pressing the 'X' to close PME while opening or saving a large project may lead to a crash
9.50 0 DE3249 PME PROJECT Project will not open if another project is already open
9.50 0 DE3136,00350320 PME REPORTING Fixed issue where the Page Setup Print Options(paper, orientation and margins) were missing.
9.50 0 DE3111,00315909 PME SETTINGS Fixed issue where Custom Colors in the Options Tab are not saved.
9.50 0 DE3541,00393282 PME TOOLCHEST Previews were not appearing in the Companion Help window.
9.50 0 DE3065,00349787 PME UTILITIES Fixed issue where launching of utilities via the Ribbon Bar are offset by 1.
9.50 0 DE3540,00392869 PME VARIABLES In some cases, it was possible to delete variables that were in use.
9.50 0 DE3543,00397071 PME VARIABLES Performance can degrade when selecting variables.
9.50 0 DE3059,00335275 PPS PPS BLOCKS The Formula for the ADV_PID and PID blocks has been reverted to it's previous version without scaling factor
added
9.50 0 00312808 VIEW EDITORS Opening a project with 10 targets is taking more time.
9.50 0 00284942 VIEW RUNTIME Web view was not getting updated with values though runtime was working fine.

© 2019 Emerson. All rights reserved. https://digitalsupport.ge.com/communities/en_US/Article/Proficy-Fixed-Issues 10/17/2019


Fixed Issues Page 2 of 5

9.50 0 00316263 VIEW RUNTIME QPV & QP+ ChangeImage bug using negative height bmp file.
9.50 0 00361547 VIEW RUNTIME Send Email functionality through scripts was failing in QP+.
9.50 0 00333539,00346412 VIEW RUNTIME Memory Leak on QP+ view runtime.
9.50 0 00358586,00382204,003894 VIEW RUNTIME QP+ View closes when email is sent.
50,00367513,00369063,003
89427
9.50 0 00342078,00367696,003856 VIEW SECURITY QP+ even with security enabled vnc server still allow access .
67
9.50 0 DE3888,00428995 LD PLC CBLOCKS PME exists abnormally when validating target with C block
9.50 0 DE3911,00430824 LD PLC CONTROL MODULES Redundant CPU330 is not showing Transfer List columns on control modules
9.50 0 DE3914,00432783 LD PLC HWC Adding a data area to IC693DNM200 crashes
9.50 0 DE3917,00432034 LD PLC VERSASAFE Adding new VersaSafe Logic Blocks does not generate the correct functions
9.50 1 DE3927 LD PLC GSDML Embedded Profinet ports did not support update GSDML
9.50 1 DE3932,00425410 LD PLC LOGIC Unable to RMS a project upgraded from PME 8.50
9.50 1 DE3958,00437548 LD PLC LOGIC Downloading logic with PACMotions Instructions cause the IC695CPE400 to halt
9.50 1 DE3953,00422519 PME VARIABLES Infinite refresh loop seen in status bar on certain variables
9.50 1 DE3989 LD PLC HWC Materials List status column was blank
9.50 2 US20079 LD PLC HWC Add RSTi-EP Family to Lite License
9.50 2 US20077 LD PLC VALIDATION Added Validation Error for unsupported Interrupts in CPE400 and CPE100
9.50 2 US20057 LD PLC HWC Enforced documented memory limitations for CPE100
9.50 2 00288828 LDPC RUNTIME QP+ 7 and 12 - PC Control - Positive Transition Contact will pass power flow when attempting a RMS (Run Mode
Store)
9.50 2 00311809 VIEW WEBVIEW WebVIEW when QP is in portrait
9.50 2 00419810 VIEW RUNTIME Email wont send
9.50 2 00439839 VIEW RUNTIME ChangeBitmap Problem with bmp that have negative image height
9.50 2 DE4002,00442312,0044324 LD PLC HWC Software Crashes when trying to edit IC200ALG620 module carrier field
6
9.50 2 DE4028 LD PLC PROFINET PROFINET Explorer feature doesn't populate data on target EPSCPE100
9.50 2 00448300 LDPC CONTROL RUNTIME PME v9.5 - Win 10 x32 or x64 try to download a QP+ with View and PC in Simulator
9.50 2 DE4033,00450633 LD PLC IMPORT Import of FBD Block Corruption
9.50 2 DE4010,00445056 LD PLC IMPORT Import of Block using Global Variables fails
9.50 3 DE4029 LD PLC VARIABLES PME Hangs when the Value Resolution of Relocated Variable dialog is displayed during a download.
9.50 3 DE4030,00449750 LD PLC CONVERT Fix issue with converting DeviceNet from 90-30 to RX3i
9.50 3 TT185193 PCM GENERAL History Report doesn't function with IE 11 in use
9.50 3 TT185194 PCM GENERAL Unable to get the Checked Out Projects Report with IE 11 in use
9.50 3 TT185195 PCM GENERAL Clicking a iFIX or CIMPLICITY project node in the Navigator window brings up a script error when IE 11 is in use

9.50 3 TT185196 PCM GENERAL Comparison Report shows up with compare results missing when IE 11 is in use
9.50 3 TT185197 PCM GENERAL Download to PC Device operation of RSLogix 5/500/5000 project fails with a script error
9.50 3 00398653,TT185198 PCM GENERAL PME crashes when trying to set the Communication Type property for a LM9030/9070 project
9.50 3 TT185200 PCM PLANT LAYOUT The pages of the sample layout 'GenericLayout' show up blank in the InfoViewer when IE 11 is in use
9.50 3 00392922 , 00395469 VIEW RUNTIME Alarms Buffering Enhancement
9.50 3 US 19411 VIEW RUNTIME A new option provided in the data entry Keyboard and keypad of the Runtime object to increase its size
9.50 3 00447429 VIEW RUNTIME TrendX crashes when trying to view the log
9.50 3 DE4107 LD PLC IMPORT Import of of PSB and UDFB blocks fail
9.50 3 00384629 VIEW RUNTIME View Script Bug - AppExec numStartMode does not work in QP+
9.50 4 DE4065,00436787 LD PLC LOGIC Crash on Edit Block properties after Import of Control Modules.
9.50 4 DE4121,00437917 LD PLC LOGIC Fixes 8512 unknown validation exception that randomly occurred.
9.50 4 TT185201 PCM GENERAL Various PCM operations on custom projects fail when the Debug property of the custom project type is set to 1

9.50 4 US21053 LD PLC HWC Enable Profinet MRP Support for the EPSCPE100
9.50 4 TT185202 PCM GENERAL Custom property in the Inspector doesn't display its new value automatically after its custom edit dialog is closed

9.50 4 00354563 VIEW RUNTIME QuickPanel + n/a QP View update via CFcard deleted user
9.50 4 00388366 VIEW RUNTIME Logging to Historian on a QP+
9.50 4 00361102 VIEW EDITOR QP+ Enhanced security doesn`t work
9.50 4 TT185203,00407902 PCM 3RD PARTY COMPONENTSPME crashes when adding GE Fanuc CNC project
9.50 4 DE4098 LD PLC IMPORT Import Control Module from file does not bring in CM ID
9.50 4 DE3949, 00436787 LD PLC IMPORT Crash on Edit Block properties after Import of Control Modules
9.50 4 DE4088, 00459037 LD PLC IMPORT Possibly Different Tags mapped to same memory symbolic memory area?
9.50 4 00395033 VIEW RUNTIME SetDisplayBrightness to turn on the backlight
9.50 4 DE4169 LD PLC LOGIC SIZE_OF in ST could return wrong size in specific case
9.50 4 DE4064 LD PLC IMPORT Upload 9.6 project to 9.0 or 9.5 version should not be allowed
9.50 5 00474434 VIEW RUNTIME Error with License in PME
9.50 5 00474557 VIEW RUNTIME pme950 sim3 - Server Busy error in Machine Edition
9.50 6 DE4227, 00478381 PME DOWNLOAD Config NE status on download, verify config says equal
9.50 6 DE4206, 00473136 LD PLC IMPORT Block Export and Import
9.50 6 DE4201, 00462930 PME LOGIC Mystery Xfer Behaviour
9.50 6 DE4185, 00463701 LD PLC ST Trying to move one array to another array in structure text getting error "8028 variable is too small for parameter"

9.50 6 DE4264 PME HWC Crash when adding variable to VersaMax PNS IO Terminal
9.50 6 00362116 LD PC RUNTIME LD PC Drivers - Ethernet IOFaults - IC200EBI001
9.50 6 00470913 VIEW RUNTIME Runtime Crash when trying to execute SQL command dbFileSQL
9.50 6 00482659 VIEW RUNTIME Problem with dbSQL SELECT
9.50 6 00491664 VIEW RUNTIME Unable to download to Older Quickpanels
9.50 6 00431572 LD PC RUNTIME Outputs dropping out, QP+ IC200EBI001 with ME 9.0 Sim 6
9.50 6 00436999 VIEW COMMUNICATIONS PME 9.50 - Target Viewer Crashed on connect to a target
9.50 6 00441401 VIEW RUNTIME PME 9.5 - Windows 10 -locking up when downloading to a Win target
9.50 6 00448660 LD PC RUNTIME QP+ 7" - Control Ethernet Driver COM Drop with VersaMax EBI001
9.50 6 00464078 VIEW RUNTIME Quickpanel QPICxxxxxxxx - trying to download to old quickpanel and is getting error 8272 binary file exceeds
allowable size.
9.50 6 00474605 VIEW RUNTIME PME 9.50 SIM 3 - Out of Memory Error on TCP QP Download
9.50 6 00474665 VIEW RUNTIME Proficy Machine Edition 9.5- Error:Unable to convert database type to match string tag
9.50 6 00477368 VIEW IMPORT PME 9.5 - import QuickPanel Jr crashes
9.50 6 00480039 VIEW RUNTIME out of memory error when attempting download to qpj-3xxxx
9.50 6 00480352 VIEW RUNTIME PME 9.5 sim4 problem supporting an older Quickpanel 7.4
9.50 6 00480514 VIEW COMMUNICATIONS Target Viewer does not work at Windows 10 build 1703
9.50 6 00484360 VIEW COMMUNICATIONS pme v9.50 - unable to connect to old quickpanel
9.50 6 00485201 VIEW RUNTIME PME 9.50 - TCP QP CQPICTDE0000-A project download PME crash with OUT OF Memory Error
9.50 6 00492016 VIEW EDITOR DH485 driver on QP+
9.50 6 00493051 VIEW RUNTIME PME 9.50 TCP QP - Out of Memory Error on TCP QP download
9.50 6 00497688 view COMMUNICATIONS PME 9.50 - Target Viewer Crashed on connect to a target
9.50 6 DE4266 LD PLC HWC Recoverable Local Memory Error Setting Missing from CPE400 HWC Faults Tab
9.50 6 DE4274, 00485846 LD PLC LOGIC Crash with "Catastrophic Failure" error
9.50 6 DE4275, 00485849 LD PLC LOGIC Software will not validate and crashes
9.50 6 DE4233, 00478148 LD PLC LOGIC Crashes PME: will not show rung 69
9.50 6 DE4272, 00475691 LD PLC LOGIC PME can crash when viewing reference addresses in LD editor
9.50 6 DE4279 LD PLC HWC PME Store fails with embedded PNC and PROFINET Device with HSB Redundancy enabled
9.50 6 DE4253, 00481936 LD PLC HWC Addition of ETM will change all EGD to new adapter
9.50 6 DE4214, 00474626 LD PLC HWC Unable to assign IO variables to ALG630 in versamax PNS
9.50 6 DE4276, 00485851 LD PLC LOGIC Program File Corrupted
9.50 6 DE4245 LD PLC GENERAL CPE400/CPE330 Redundancy REQUIRES Background Window Timer (ms) = 5ms
9.50 6 DE4205, 00472992 LD PLC HWC Unhandled exception when editing profinet device
9.50 6 DE4255, 00440013 LD PLC GENERAL Multi-Instance connection issue with 2 or more PLCs
9.50 7 TT185204 PCM GENERAL PME crashes when choosing to go into disconnected mode after loss of connection to the PCM server
9.50 7 TT185206 PCM HELP Need update help files about using Oracle or Microsoft SQL Server type of audit trail database
9.50 7 TT185207,00496191 PCM 3RD PARTY COMPONENTSPME crashes when adding Modicon ProWORX Project
9.50 7 00490448 VIEW RUNTIME Runtime Crash - QP+ application closes while navigating through graphical panels
9.50 7 00512093 VIEW RUNTIME PME 9.5 -SIM 6 - View OPC Driver in Demo mode and expired in 2 hours
9.50 7 00507487 VIEW RUNTIME quickpanel+ security
9.50 7 00508756 VIEW RUNTIME Typing password at large keyboard at Quickpanel+

© 2019 Emerson. All rights reserved. https://digitalsupport.ge.com/communities/en_US/Article/Proficy-Fixed-Issues 10/17/2019


Fixed Issues Page 3 of 5

9.50 7 00516739 VIEW RUNTIME PME 9.50 View Runtime - Logon Dialog Password is not Masked when enter from screen Keypad
9.50 7 00517354 VIEW RUNTIME PME 9.50 View Runtime - Logon Dialog Password is not Masked when enter from screen Keypad
9.50 7 DE4408, 00522545 LD PLC LOGIC Member modification can corrupt user block
9.50 7 DE4291, 00490706 LD PLC CORE EGD Management Tool fails to launch
9.50 7 DE4412 LD PLC HWC Some PROFINET parameter fields are blank rather than 'Default value'
9.50 7 DE4284, 00488174 LD PLC HWC Crash when click yes to update catalog
9.50 7 DE4332, 00498093 LC PLC LOGIC Interconnected rung power flow error
9.50 7 DE4247 LD PLC HWC Mirroring a CPE400 redundant HWC with an MRP Ring creates a second ring manager
9.50 7 DE4418, 00483583 LD PLC CORE %L registers not updating when uploading
9.50 7 DE4422 LD PLC LOGIC Fixed issue with importing UDFB from XML
9.50 8 DE4469, CS0100438 LD PLC GENERAL Right-click menu stops working
9.50 8 DE4571, DE4404, LD PLC LOGIC Cannot edit logic if a network connection to a PLC is lost. once the connection is re-established the PLC program
CS0096090, CS0155331 becomes un-editable even when offline.
9.50 8 DE4397, CS00516391 LD PLC HWC Unable to configure 61850 card
9.50 8 00470913 ,CS0089864 VIEW RUNTIME Runtime Crash when trying to execute SQL command dbFileSQL
9.50 8 00503506 VIEW EDITOR PME Crash on QP target validate or download
9.50 8 0089847 LD PLC EDITOR PME Crash when references address show in LD Editor enabled.
9.50 9 DE4581 LD PLC GENERAL On CPE115, under the producer exchange property "Network ID" parameter is missing.
9.50 9 TT185209, CS0132167 PCM GENERAL User groups assigned to a ME project sometimes disappear leaving just Administrators group
9.50 9 DE4339, CS0089867 LD PLC VALIDATION Machine Edition crashes during validate/save
9.50 9 00500234 VIEW RUNTIME PME 9.50 SIM 5 - SetDisplayBrightness will not work on QP+ 12" FW Build 23
9.50 9 00518636 VIEW RUNTIME Scripting function for set display brightness for 15" is not working as with smaller 7" QP+.
9.50 9 00542473 VIEW RUNTIME SetDisplayBrightness ViewScript function does not change display brightness.
9.50 9 00478796 DE4285 LD PLC GENERAL Symbolic Managed Memory Error 3977 while validating configuration
9.50 9 DE4622, CS0183713 LD PLC VALIDATION cannot build ANY 90-70 project that contains at least one line of code with sim8
9.50 9 DE4421 LD PLC GENERAL CPE115 not appearing in the Explore PROFINET Window
9.50 9 DE4521 LD PLC UTILITIES Profinet DCP No Valid Ethernet Adapters
9.50 9 DE4327 LD PLC HWC Config NE status after verify when using PMM with a Fiber Terminal ID that is less than 4 chars
9.50 9 DE4594 LD PLC GENERAL CPU Halt when using MOVE_TO_FLAT or MOVE_FROM_FLAT in certain conditions
9.50 9 DE4600 LD PLC HWC Config showing NE when going online after a redundant download in specific use case
9.50 9 DE4617 LD PLC HWC High compression on HWC could cause loss of equality when working in multiple time zones
9.50 9 DE4620 LD PLC GENERAL Validating online could cause PNIO_DEV_COMM instruction to drop outputs
9.50 9 DE4631 LD PLC HWC Array elements on terminals of PNC devices were not being restored properly during verify equality operation
9.50 9 DE4633 LD PLC HWC Unexpected error about I/O overlap when validating redundant system while online.
9.50 10 DE4736 LD PLC GENERAL Possible to crash PME when validating MOVE_FROM_FLAT or MOVE_TO_FLAT in FBD or ST in SIM 9
9.50 10 DE4744 LD PLC LOGIC Performance issues in ST editor when scrolling with mouse
9.50 10 DE4776 LD PLC LOGIC Unexpected validation errors when using VAR CONSTANT in multiple ST blocks
9.50 10 DE4760 LD PLC GENERAL Add check to prevent VersaSafe from being added to CPE400 and RSTi targets since it's not supported on those

9.50 10 DE4762 LD PLC LOGIC Find in target could cause PME to crash in specific case
9.50 10 DE4767 LD PLC LOGIC Importing block could create variable instead of using parameter
9.50 10 DE4228, 00478902, LD PLC LOGIC Machine edition crashes after a point import
CS0089719
9.50 10 DE4741, CS0089849 LD PLC HWC CPE400 Redundancy Transfer List Not auto creating when adding in profinet IO
9.50 10 TT185211 PCM 3RD PARTY COMPONENTSMenu items "New..." and "Add..." for some custom project types are enabled for users who have no permission to
create and add projects to the PCM Server.
9.50 10 DE4769 LD PLC LOGIC Unable to download to 90-70 controller.
9.50 10 DE4785 LD PLC GENERAL Unable to add %L to RVT before connecting to controller
9.50 10 DE4739, CS0090153 LD PLC UDT Editor Boolean can NOT un-check Retentive property as soon as it added
9.50 10 DE4740, CS0127752 LD PLC Edit HW Config PME 9.50 SIM 7 LD PLC - ProfiNet Scanner Device is locked after Mirror ProfiNet IO from Primary to Secondary

9.50 10 CS0206892 VIEW RUNTIME PME 9.50 SIM 9 View Runtime not showing ActiveX component
9.50 10 CS0089909 VIEW RUNTIME PME 9.00 SIM 12 - Web Browser In View Panel - Getting Active X Control Error
9.50 10 DE4790 LD PLC LOGIC Cannot add more than 256 blocks to RX3i Rackless or RSTi targets
9.50 10 DE4797 LD PLC GENERAL PME can appear to lock up after making changes to UDT
9.50 10 CS0204353 VIEW OPC A&E SERVER PME 9.50 OPC A&E Server Error on launch
9.50 10 DE4796, CS0176378 LD PLC LOGIC IEC Transitionals used in LD could cause symbolic error on download
9.50 10 DE4578, CS0126955 CORE GENERAL References are not populated corrected for variables used within UDFBs
9.50 10 DE4759, CS0089686 LD PLC GENERAL Password restrictions cause inefficient editing experience.
9.50 10 DE4565 LD PLC HWC PME Crashes when doing a redundant download to both Primary and Secondary Controllers
9.50 10 DE4816,CS0219056 LD PLC LOGIC Error when using defined constant in function call in ST logic
9.50 11 CS0212955 VIEW RUNTIME CPE115 Talking to QP+ Cannot Get Symbolics Working With Simulator
9.50 11 DE4059, CS00455144 LD PLC HELP Update catalog version history for CPE330, CPE400 and CPE100
9.50 11 DE4821, CS0211130 LD PLC LOGIC Setting SBA to 0 generates incorrect error in non-redundant system
9.50 11 DE4822, CS0212429 LD PLC LOGIC Crash when downloading after SIM update and error on ST string assignment
9.50 11 DE4840 LD PLC LOGIC Crash when validating with CPE100 that was not upgraded from version 1
9.50 11 DE4841, CS0229097 LD PLC GENERAL PACSAnalyzer prompts to set clock when running in silent mode
9.50 11 DE4798, CS0137905 LD PLC HWC PME 9.5 allocated duplicate addresses for the Ethernet status and the Profinet status
9.50 11 DE4839, CS0228304 PME LICENSING ME opens old user interface of License Client
9.50 11 DE4597, CS0127868 LD PLC LOGIC Stuck in monitor mode after cancelling pme reconnect attempt with PLC
9.50 11 DE4328, 00501574 LD PLC HWC Profinet Manager configuration setting is copied from Primary to Secondary controller in CPE400 HA system
9.50 11 DE4852,CS0234398 LD PLC LOGIC MOVE_FROM_FLAT in ST was using the size from IN rather than Q when using parameters instead of variables

9.50 11 DE4836 LD PLC HWC Add "Avaialble" to port mode parameter drop down for ports
9.50 11 DE4842, CS0227297 LD PLC LOGIC Downloading logic only could give error about HWC and Logic being coupled when they are not
9.50 12 DE4893, 00615760 LD PLC LOGIC String assignment in ST could cause CPU to halt
9.50 12 DE4895, 00605933 LD PLC LOGIC Error 12588 when validating 90-70 project
9.50 12 DE4905, 00616676 LD PLC LOGIC Unexpected error when passing arrays to functions in ST
9.50 12 DE4867, 00471451 LD PLC HWC GSDML file failed to import: its IO-Devices are not editable
9.50 12 DE4392, 00510806 LD PLC VALIDATION pme950 sim7 software crashes on validate of PLC project
9.50 12 DE4850, CS06091 LD PLC LOGIC PME problem while doing upload, block/parameter name collision
9.50 12 DE4923, 00612613 LD PLC HWC ME 95sim10 crash viewing hardware config data
9.50 12 DE4335, 00494915 LD PLC HWC Redundancy wizard carries over the ip address of eds001 module, when it should not
9.50 12 DE4416, 00524703 LD PLC CORE In main menu, the RESTORE option becomes unavailable after opening and closing a project
9.50 12 DE4394, 00512095 LD PLC VARIABLES String variables affecting next register
9.50 12 DE4897, 00571020 LD PLC VARIABLES PME 9.5 crashes if variable with null value is imported
9.50 12 DE4395, 00512551 LD PLC VARIABLES Duplicating String Variables does not work as expected
9.50 12 DE4903, 00602556 LD PLC HWC Adding Drive GSDML, unable to map the desired drive profile
9.50 12 DE4929, 00618997 LD PLC IMPORT Export of a valid block fails
9.50 12 DE4949, 00579459 LD PLC IMPORT Importing CSV
9.50 12 DE4915, 00618196 LD PLC VARIABLES ST editor hovering over var while online issue
9.50 12 DE4927, 00618143 LD PLC HWC CPU backplane comm window mode parameter reseting to default on project load issue
9.50 12 DE4063, 00455619 LD PLC HWC PME 9.00 sim9 Crashes on PLC Redundant download (when variable mode is enabled on GCG)
9.50 12 DE4761, CS0181745 LD PLC HWC Redundant CPE330 LAN 2 cannot send EGD multicast
9.50 12 00458475 VIEW RUNTIME OPC doesn't manage MSB of unsigned DINT/DWORD properly when reading and writing to PLC
9.50 13 DE4997, 00637878, LD PLC LOGIC PLC Status Dialog Redundancy Tab missing
00642014
9.50 13 DE4986, 00636356 LD PLC HWC Project corruption when changing target from CPL410 to Rx3i
9.50 13 DE4977, 00623896 LD PLC EDIT HW CONFIG Could not add 3rd party ProfiNet Device
9.50 13 DE4743 ,0089934, LD PLC HWC Unable to download to cpuE05. Controller Error - No system memory available. [0x05][0x95
00488610
9.50 13 DE4823, 00601491 LD PLC HWC Problems uploading /downloading versamax config
9.50 13 DE4897, 00626253, LD PLC VALIDATION ME 9.5 Sim 11 versasafe validation error
00634111
9.50 13 DE4965, 00630872 LD PLC LOGIC LDBK "PMCS_30" view locked and won't unlock with password
9.50 13 DE5011, 00637500 LD PLC LOGIC PME slowing down and becoming unresponsive in ST editor when online
9.50 13 00626370 VIEW DOWNLOAD QP15" View Runtime 64K remote data error Message
9.50 13 CS0093082 VIEW HISTORIAN Memory leakage issue in QP+6
9.50 13 DE4334, 00505486 LD PLC GENERAL PTCoil and NTCoil Tool Bar Items Create Wrong Coil Type (POS/NEG)
9.50 13 DE5026, 00645105 LD PLC GENERAL RSTi-EP power tool icon on ME utility ribbon missing "-EP"
9.50 13 DE5031, 00609086 LD PLC LOGIC Cannot copy or edit from Edit Locked file LD

© 2019 Emerson. All rights reserved. https://digitalsupport.ge.com/communities/en_US/Article/Proficy-Fixed-Issues 10/17/2019


Fixed Issues Page 4 of 5

9.50 13 DE5029, 00517312, LD PLC IMPORT When importing ladder logic XML files, ME will not recognize UDT variables within
00621178, 00597103
9.50 13 DE4988, 00634373 LD PLC IMPORT Import XML block issue
9.50 13 DE4992, 00638565, LD PLC LOGIC CPU Halts when passing string arrays in structures by reference
00615760, 00642981
9.50 13 DE5007, 00635319 LD PLC IMPORT Block imported creates external variable instead of member variable
9.50 13 DE5034, 00647250 LD PLC IMPORT Importing block into PME changes variable reference from array name to array element
9.50 13 DE5025, 00640491 LD PLC HWC ME shifts analog I/O when replacing a CPE
9.50 13 DE5032, 00568079 LD PLC LOGIC pme950 sim8 - Not possible to copy text from temporary unlocked ST
9.50 13 DE5008, 00602042 LD PLC NAVIGATOR Inspector fails to sync with navigator when in ST Editor
9.50 13 DE5059, 00653413 LD PLC LOGIC Existing variables in SMT were getting new addresses during online edits which led to increased memory usage

9.50 14 DE4974, 00512774 LD PLC HWC VersaConf Plus allows non-safe power terminals on safety project
9.50 14 DE4887, 00478607 LD PLC HWC ProfiNet configuration incomplete with non-English OS language
9.50 14 DE5134, 00665322 LD PLC CORE using Cntrl - X to cut descriptions in EGD configuration crashes Proficy
9.50 14 DE4644 ,00520956 VIEW RUNTIME QuickPanel+ 7" text sizing issues
9.50 14 DE5078 ,00622308 VIEW RUNTIME Pop-up box not displaying properly in View Simulator (PME 9.5 only) - WIN 10 (VM is WIN 7)
9.50 14 DE4635 ,00485522 LD PC LOGIC SFC Logic:press on Initial Step and a Macro Step is added to logic & vice-versa
9.50 14 DE5176 ,00665660 PME GENERAL PME 9.5 SIM 13 projects unable to be opened in SIM 11 Missing UDT Manager
9.50 14 DE4882, 00615144 LD PLC LOGIC Validation error when assigning "" to string in ST
9.50 14 DE4558, 00552890 LD PLC LOGIC Added validation warning when using duplicate variables on wires in FBD
9.50 14 DE4598, 00560667 LD PLC LOGIC Drag to select in FBD only works in one direction
9.50 14 DE5092, 00655717 LD PLC UPLOAD 950 sim12 - Program Upload Issue - CPE305
9.50 14 DE5129, 00570342 LD PLC UPLOAD pme950 sim8 - Error 8058: Unable to import Hardware Configuration.
9.50 14 DE5154, 00582551 LD PLC HWC pme950 sim8 - 9030 to rx3i conversion results in DNM200 slaves deleted
9.50 14 DE5143, 00665390 LD PLC HELP PME 9.5 SIM 13 Non-existent link in Help system.
9.50 14 00659723 VIEW EDITOR OPC driver for A/B Compact Logix stopped working in PME 9.5 SIM 13
9.50 14 DE5171 ,00646890 VIEW EDITOR PME 9.50 SIM 12 - View OPC Driver quit working on QPView IC754VSI12VCTD
9.50 14 DE5172, 00671983 VIEW EDITOR Feature Request PME 9.50 SIM13 - QP+ Enhanced Security to disable Error AND Warning msg
9.50 14 DE5174 ,00605241 VIEW EDITOR Window sizes and positions in ' Runtime' do not match sizes and positions in the editor.
9.50 14 DE5176 ,00661012 PME GENERAL PME 9.50 SIM 13 - Error on project open - Missing UDT
9.50 14 00660530 VIEW RUNTIME PME splash screen and system info details.
9.50 14 00663013 VIEW RUNTIME Writing negative values to DINT[DWORD] variables, will not update the value provided.
9.50 14 DE5164, 00641695 LD PLC UPLOAD 950 sim11 - 9070 upload results in new Errors
9.50 14 DE5137, 00593447 LD PLC HWC 950 sim9 - Mirroring Primary to Secondary causes Config NE status
9.50 14 DE4330, 00500213 LD PLC HWC CPE330 OPCUA server doesn't support "Coordinated Universal Time"
9.50 14 DE5168, 00664060, LD PLC LOGIC Copy and Pasting LD code silently overwrites variable descriptions
00542654
9.50 14 DE5192, 00574452, PME GENERAL PME 9.5 Quick Access Toolbar Customization not retained
00642017
9.50 14 DE5167, 00677981 LD PLC LOGIC Proficy crashes when duplicating block
9.50 14 DE5214, 00677907 LD PLC VARIABLES Editing a variable in LD-PLC Editor causes PME to crash
9.50 14 DE5183, 00614118 LD PLC VARIABLES Variable Conflict Resolution doesn't allow symbolic addresses
9.50 14 DE5088, 00656186 LD PLC DOWNLOAD CPE305 Error 8097: Controller Error - No user memory available
9.50 14 DE5148, 00586446 LD PLC EDIT HW CONFIG HW configuration, Profinet Device settings do not show-up
9.50 14 DE4910, 00561547 PME GENERAL RSTi-EP Power Supply Tool crash after clicking Help in the RSTi tool
9.50 14 DE5085, 00654469 LD PLC EQUALITY Loss of equality issue when viewing hardware configuration online
9.50 14 DE5180, 00677844 LD PLC VALIDATION String Warning 8022: Type Mismatch between variable and instruction when passing a string to a function block

9.50 14 DE4908, 00552890 LD PLC LOGIC FBD Wire Duplication


9.50 14 DE5009, 00615144 LD PLC LOGIC In ST Editor for PAC system can't put in double quoted blank string for constant
9.50 14 DE4982, 00629425 LD PLC HWC CPU310 does not support Profinet
9.50 14 DE5125, 00668020 LD PLC VALIDATION PME 9.50 SIM 13 - crashes when validate a Control Module with String type Parameters
9.50 14 DE4560, 00547921 LD PLC DOWNLOAD PME 9.5 SIM 8 - Unexpected Error when adding a second target while in run and downloading
9.50 14 DE5165, 00523689 LD PLC EQUALITY Verify Equality always returns "Source NOT EQUAL" when performing a Verify Equality command
9.50 14 DE5233, 00679565 LD PLC EQUALITY Verify Logic equality for ST blocks does not work
9.50 15 DE5237, 00683337 LD PLC LOGIC String Assignment fails with array of structures
9.50 15 DE5215, 00644878 LD PLC GENERAL DataWatch List do not get saved
9.50 15 DE5262, 00625376, LD PLC GENERAL PME 9.5 Does not remember view settings for data watch window
00621509
9.50 15 DE5268, 00683338 LD PLC LOGIC String Assignment is failing to zero terminate
9.50 15 DE5289, 00677409 LD PLC LOGIC Nested case statements don't work with var_constant declarations
9.50 15 DE5312, 00720603 LD PLC LOGIC String Issues
9.50 15 DE5077, 00568068 LD PLC GENERAL PME 9.50 Sim 11 Unable to initialize tag database on QP+ projects
9.50 15 DE5317, 00677806 LD PLC GENERAL Loading circle does not got away
9.50 15 DE5077, 00719894 VIEW GENERAL Restoring a 8.6 HMI Project in 9.5 causes an error on open
9.50 15 DE5274, 00644974 VIEW RUNTIME QP+ 12" PME 9.50 SIM 13 - Runtime Shutdown Unexpectedly
9.50 15 DE5179, 00669035 VIEW GENERAL PME 9.50 SIM 13 - QPView Target restore getting Tag Database initialization error
9.50 15 DE5321, 00690146 VIEW RUNTIME QP+ 10 - View Runtime Shutdown unexpectedly
9.50 16 DE5358, 00717096 CORE GENERAL RSTi-EP Power Supply Tool versions not matching on GUI
9.50 16 DE5173, 00674584 VIEW RUNTIME Modbus Slave RTU Serial Channel Unresponsive
9.50 16 DE4376, 00491631 VIEW RUNTIME problems with alarms displaying correctly when keep history property set to false
9.50 16 DE5381, 00687564 PC CONTROL EDITOR PID controller does not allow Loop update time to change
9.50 16 DE5385, 00724447 PC CONTROL GENERAL PME 9.5 crashes when trying to open old 6.00 project
9.50 16 DE5187, 00655718 VIEW RUNTIME PME 9.50 SIM 13 - View OPC Driver do not read Symbolic Var when CPU OEM protection lock is enabled​​.
9.50 16 DE5426, 00735811 VIEW DRIVER PME 9.50 SIM 15 View OPC Driver Warning pop up - Customer request configuration disable the warning message

9.50 16 DE5428, 00737363 VIEW DRIVER EXT: Astor technical case ME9.50 -warning on OPC drivers
9.50 16 00738398 VIEW RUNTIME PME 9.50 SIM 15 - ViewScript Commnad - FileCopy no longer work on QP+
9.50 16 DE5429, 00738461 VIEW DRIVER PME 9.50 SIM 15 - Request QPView OPC Driver warning message update for QPView / control project
9.50 16 DE5453, 00738521 VIEW EDITOR PME 9.50 SIM 15 - Crash on Convert TCP QP3 project into QPView / Control
9.50 16 DE5453, 00738547 VIEW EDITOR QP Conversion to QPV or QP+ Not Working, Shutting Down ME 9.5 SIM 15
9.50 16 DE5453,00746104 VIEW EDITOR PME 9.50 SIM 15 - Crash on Convert TCP project into QPView / Control
9.50 16 DE5503,00730450 VIEW RUNTIME PME 9.50 SIM 15 - View runtime Simulator Pop up Screen stretched when show caption ON
9.50 16 DE5384,00720986 VIEW GENERAL PME 9.50 SIM 15 - TCP QP Download Error 12045
9.50 16 DE5384,00723045 VIEW GENERAL PME 9.50 SIM 15 - TCP QP Download Error 12045
9.50 16 DE4889,00484928 LD PLC EQUALITY PME 9.50 SIM 4 - Config not equal and validation error in redundant CPE330 system
9.50 16 DE4330,00500213 LD PLC HWC CPE330 OPCUA server doesn't support "Coordinated Universal Time"
9.50 16 DE5163,00561815 LD PLC EQUALITY PME 9.50 SIM 7 - Verify equality makes opposite controller of a HSB system go not equal
9.50 16 DE5334,00724169 LD PLC EQUALITY Building only EGD makes config not equal
9.50 16 DE5335,00722398 LD PLC GENERAL PME 9.50 SIM 14 - pme hangs and disappears during target conversion
9.50 16 DE5336,00720286 LD PLC GENERAL Cannoy replace RX3i with RX3i Rackless in the atached project
9.50 16 DE5337,00720425 LD PLC GENERAL PME 9.50 SIM 14 - Warning 13718 should not be there for CPE100/115 target
9.50 16 DE5340,00719149 LD PLC EDITOR UDT editor fails to update member in ST code
9.50 16 DE5403,00729691 LD PLC GENERAL PME 9.50 SIM 11 - Validation problem
9.50 16 DE5465,00741220 LD PLC GENERAL Can't do stop mode store with UDFB change (8097, Proficy crashes)
9.50 16 US29628,00672294 LD PLC EDITOR PME enhancement request, duplicate structures
9.50 16 DE5228,00743716 VIEW RUNTIME PME 9.50 SIM 15 - Runtime Simulator mode shutdown unexpectedly when Web Documented added
9.50 17 DE432,00479876 VIEW RUNTIME View OPC DA issue
9.50 17 DE5596,00747273 VIEW OPC DRIVER PME 9.50 SIM 15 – View OPC driver – GE Ethernet Driver do not support String Data problem in %AI Memory

9.50 17 DE5601,00777289 PC CONTROL EDITOR pme950 sim16 crashes when trying to add new subroutine to a qp+ target.
9.50 17 DE5805,00785994 VIEW RUNTIME PME 9.5 Sim 16 QuickPanel+ ModbusRTU Cannot Set Negative Numbers Mark
9.50 17 DE5804,00786034 VIEW RUNTIME Inconsistent bit changes within DWORD or DINT while manipulating MSB
9.50 17 DE4369 ,00468486 PC CONTROL DOWNLOAD QP+ - Modbus TCP I/O Driver does not update properly the variables
9.50 17 DE4371,00476598 VIEW WEB VIEW Can't Lose Alarms - Force Write to Alarm History File - View for PC
9.50 17 DE5501,00744259 VIEW EDITOR PME9.50 SIM 16 - View OPC Driver Getting invalid address when accessing Driver Device system tag
9.50 17 DE5528,00748721 VIEW WEB VIEW WEBServer of QP+. Anmation does work well when variable fields are used
9.50 17 DE5598,00751466 VIEW RUNTIME I need to disable a popup when not connected to a Modicon TCP/IP Device
9.50 17 DE5601,00765779 PC CONTROL EDITOR PME 9.50 SIM 15 / SIM 16 - PME Crash and shutdown unexpectly when adding subroutine into LDPC Logic
9.50 17 DE5771,00773836 VIEW RUNTIME QP+ screen shifted

© 2019 Emerson. All rights reserved. https://digitalsupport.ge.com/communities/en_US/Article/Proficy-Fixed-Issues 10/17/2019


Fixed Issues Page 5 of 5

9.50 17 DE5601,00782213 PC CONTROL EDITOR Proficy Machine Edition Crashes


9.50 17 00791816 VIEW RUNTIME PME 9.50 SIM 16 - QP+ 12" View runtime Pop up screen get shift down 20 pixel when Windows Task Bar Show

9.50 17 00798877 VIEW RUNTIME PME 9.50 SIM 16 - QP+ 12" View runtime Pop up screen get shift down 20 pixel when Windows Task Bar Show

9.50 17 00692699 VIEW DOWNLOAD QP+ 7': XML:Syntax error detected! Line 1 Column 10380
9.50 17 00601491 LD PLC DOWNLOAD PME 9.50 Sim 9 - Problems uploading/downloading versamax config
9.50 17 DE5669, 00648775 LD PLC GENERAL PME 9.50 Sim 12 - Double click on supplemental files folders doesn't bring to front of screen
9.50 17 DE5549, 00735608 LD PLC DOWNLOAD Error 8097: Controller Error - Controller program reference exceeds configured reference problem
9.50 17 00758691, DE5664 LD PLC LOGIC Can't reorder UDT members
9.50 17 00766053, DE5686 LD PLC HWC Error 8300: Invalid Configuration for IC695CPE302 MODULE [HWC Location: 0.2, OPC UA: UTC Offset]
9.50 17 00488610, DE4743, DE4823 LD PLC DOWNLOAD PME 9.50 Sim5 Unable to Download to cpuE05 (9.00 work, 9.50 does not)
9.50 17 00757654, DE5593 LD PLC DOWNLOAD Error 8097: Controller Error - Controller program reference exceeds configured reference problem
9.50 17 00778510 LD PLC HWC PME 9.50 Sim 16 crashes when updating GCG GSDML file when variable mode enabled
9.70 0 DE5601,00765779 LD PC EDITOR PME 9.50 SIM 15 / SIM 16 - PME Crash and shutdown unexpectly when adding subroutine into LDPC Logic
9.70 0 DE5601,00756413 LD PC EDITOR PME9.50 SIM16 Quick Panel Target: Can not add Subroutines
9.70 0 DE5601,00777289 LD PC EDITOR PME 9.50 sim16 crashes when trying to add new subroutine to a qp+ target.
9.70 0 DE5528,00748721 VIEW WEB VIEW WEBServer of QP+. Anmation does work well when variable fields are used
9.70 0 DE5598,00751466 VIEW RUNTIME I need to disable a popup when not connected to a Modicon TCP/IP Devic
9.70 0 00591391 LD PLC EDITOR At times, Machine edition will cover the whole window with the structured text editor
9.70 0 00601491 LD PLC DOWNLOAD PME 9.50 Sim 9 - Problems uploading/downloading versamax config
9.70 0 DE5669, 00648775 LD PLC GENERAL PME 9.50 Sim 12 - Double click on supplemental files folders doesn't bring to front of screen
9.70 0 DE5269, 00683058 LD PLC EDITOR ST Editor window moving around
9.70 0 00695256 LD PLC EDITOR Very slow typing at ST editor in PME 9.50
9.70 0 DE5610, 00719826 LD PLC LOGIC Importing of UDTs causes logic to be refactored
9.70 0 DE5549, 00735608 LD PLC DOWNLOAD Error 8097: Controller Error - Controller program reference exceeds configured reference problem
9.70 0 00743134 LD PLC EDITOR ST block application in PME
9.70 0 00758691, DE5664 LD PLC LOGIC Can't reorder UDT members
9.70 0 00766053, DE5686 LD PLC HWC Error 8300: Invalid Configuration for IC695CPE302 MODULE [HWC Location: 0.2, OPC UA: UTC Offset]
9.70 0 00488610, DE4743, DE4823 LD PLC DOWNLOAD PME 9.50 Sim5 Unable to Download to cpuE05 (9.00 work, 9.50 does not)

9.70 0 00757654, DE5593 LD PLC DOWNLOAD Error 8097: Controller Error - Controller program reference exceeds configured reference problem
9.70 0 00778510 LD PLC HWC PME 9.50 Sim 16 crashes when updating GCG GSDML file when variable mode enabled

© 2019 Emerson. All rights reserved. https://digitalsupport.ge.com/communities/en_US/Article/Proficy-Fixed-Issues 10/17/2019