C06. S03. P02 – P10


CasoLine curve

Including C06. S01. P02 – P08
Floors and ceilings introduction
Introduction

Floors and ceilings


This section details floors and ceilings systems which cover a multitude
of performance requirements in all sectors
Floors and ceilings
C06

british-gypsum.com
Introduction
Floors and ceilings
British Gypsum offers a full range of specifications
from simple plasterboard ceilings through to a
range of gypsum-based, acoustic suspended
ceilings and lay-in grid systems. They cover all
building categories, including private and social
housing, apartments, healthcare, educational
facilities, recreational and industrial properties in
both new-build and refurbishment and can satisfy
the most demanding performance requirements.

When specifying floor and ceiling solutions, a number of


performance characteristics are normally used to determine the
required solution. Depending on the project or construction type,
these performance parameters could be set by minimum regulatory

Floors and ceilings


standards, or a client or customer requirement, for buildings that
offer the highest standards of performance and comfort.

Our quick-reference floors and ceilings system guide, below, allows


you to simply select the performance categories of interest and
identify the British Gypsum floor and ceiling systems which best

C06
satisfy your project requirements.

Fire Installed
Acoustic performance
performance cavity depth System Page
mins mm RwdB Rw + CtrdB Ln,w dB αw

30 - 120 ≥100 56 - 66 50 - 55 68 - 50 0.35 - 0.85 CasoLine mf C06. S02. P02

- ≥100 - - - 0.35 - 0.852 CasoLine curve C06. S03. P02

30 - 90 25 - 175 52 - 63 50 66 - 55 0.35 - 0.85 GypLyner universal C06. S04. P02

30 - 90 - 54 - 63 47 - 51 63 - 55 - GypFloor silent1 C06. S05. P02

30 - 120 - 36 - 66 50 - 55 78 - 48 - Timber floors C06. S06. P02

30 - 60 - - - - - Cavity barriers C06. S07. P02

1
Where the floor can only be accessed from above, the fire and accoustic performances can be upgraded with the GypFloor silent system.
2
Indicative first test performance only.

0115 945 6123 bgtechnical.enquiries@bpb.com C06. S01. P02


Acoustic performance
Introduction

Table 1 – Recommended laboratory performance to meet requirements of Building Regulations Approved Document E
(England and Wales)
Where applicable Minimum airborne Recommended Maximum impact Recommended
sound insulation performance Rw + Ctr sound transmission performance
DnT,w + Ctr (site test result) (laboratory test result) L’nT,w (site test result) Ln,w (laboratory test result)
Separating walls between new homes 45dB 54dB - -
Separating walls between purpose-built 43dB 52dB - -
rooms for residential purposes
Separating walls between rooms created by 43dB 52dB - -
a change of use or conversion
Separating floors between new homes and 45dB 54dB 62dB 57dB - 52dB
purpose-built rooms for residential purposes (depending on
construction method)
Separating floors between rooms created by 43dB 52dB 64dB 59dB - 54dB
a change of use or conversion (depending on
construction method)

Table 2 – Recommended laboratory performance to meet requirements of Technical Handbook Section 5 (Scotland)
Where applicable Minimum airborne Recommended Maximum impact Recommended
sound insulation performance Rw sound transmission performance
DnT,w (site test result) (laboratory test result) L’nT,w (site test result) Ln,w (laboratory test result)
Floors and ceilings

Separating walls between new homes, 56dB 63dB - -


purpose-built rooms for residential purposes
and conversions (not including traditional
buildings1)
Separating walls between rooms created by 53dB 60dB - -
a change of use or conversion (traditional
buildings1)
Separating floors between new homes, 56dB 63dB 56dB 51dB - 46dB
C06

purpose-built rooms for residential purposes (depending on


and conversions (not including traditional construction method)
buildings 1)
Separating floors between rooms created by 53dB 60dB 58dB 53dB - 48dB
a change of use or conversion (traditional (depending on
buildings1) construction method)

1
Definition of traditional buildings.
A building or part of a building of a type constructed before or around 1919:
a) using construction techniques that were commonly in use before 1919; and
b) with permeable components, in a way that promotes the dissipation of moisture from the building fabric.

Good practice specification guidance


British Gypsum’s systems are designed and tested to meet
every performance requirement and are fully supported by
our SpecSure® lifetime system warranty.

This means that when our systems are installed following


our guidance they will achieve every performance claim we
make, and if they don’t then we’ll put it right. To maximise
the performance achieved on site, consider the following
good practice specification guidance: — Small openings such as gaps, cracks or holes will conduct
— Consider flanking transmission at the design stage and airborne sounds and can significantly reduce the sound
ensure construction detailing is specified to eliminate, insulation of a construction. For optimum sound
or at least to minimise, any downgrading of the acoustic insulation a construction must be airtight
performance. The sound insulation values quoted in — When designing spaces requiring separation by sound
system performance tables are laboratory values and insulating floors and ceilings abutting structural
the practicalities of construction will mean that acoustic steelwork, consideration should be given to the potential
performances measured in the laboratory will be difficult loss of sound insulation performance through the
to achieve on site steelwork

C06. S01. P03 british-gypsum.com


Gyptone performance

Introduction
Table 3 – Sound absorption data for Gyptone boards

QUATTRO 41 Sound absorption coefficient αp

Practical absorption coefficient αp


1.0
Gyptone quattro 41 (plenum depth 187mm)
0.8

Practical absorption coefficient αp


0.6

0.4 125 250 500 1k 2k 4k αW AC1 NRC2


0.2
0.50 0.70 0.80 0.70 0.60 0.55 0.65 C 0.70
0.0
125 250 500 1000 2000 4000
Frequency (Hz)

System reference C10A091

Floors and ceilings


QUATTRO 42 Sound absorption coefficient αp

Gyptone quattro 42 (plenum depth 50mm)3


Practical absorption coefficient αp

1.0

Practical absorption coefficient αp


0.8

0.6

0.4
125 250 500 1k 2k 4k αW AC1 NRC2

0.20 0.40 0.60 0.60 0.45 0.40 0.50 D 0.55


0.2

0.0

C06
125 250 500 1000 2000 4000
Frequency (Hz)

System reference C10A110

QUATTRO 46 Sound absorption coefficient αp


Practical absorption coefficient αp

1.0
Gyptone quattro 46 (plenum depth 400mm)
0.8 Gyptone quattro 46 (plenum depth 400mm plus
0.6
100mm Isover Spacesaver Ready-Cut)

0.4

Practical absorption coefficient αp


0.2

0.0 125 250 500 1k 2k 4k αW AC1 NRC2


125 250 500 1000 2000 4000
Frequency (Hz)
0.65 0.60 0.55 0.45 0.40 0.35 0.45(L) D 0.50
System reference C10A014
0.60 0.60 0.65 0.55 0.45 0.40 0.50(L) D 0.55
C10A015

1
AC - Absorption Class.
2
NRC - Noise Reduction Coefficient.
3
Due to installation limitations the minimum cavity size that can be constructed with CasoLine mf or CasoLine curve system is 100mm. The sound absorption
performance for these systems is estimated to be equivalent to that of the same system built with a 50mm plenum.

All products have been tested to BS EN 20354 and ISO 354. The single figure rating practical sound absorption coefficient αw is calculated in accordance
with EN ISO 11654. Suffix letters indicate where performance is limited at either low, medium or high frequencies.

0115 945 6123 bgtechnical.enquiries@bpb.com C06. S01. P04


Introduction

Gyptone performance (continued)

Table 3 (continued) – Sound absorption data for Gyptone boards

QUATTRO 47 Sound absorption coefficient αp

Practical absorption coefficient αp 1.0 Gyptone quattro 47 (plenum depth 400mm)


0.8
Gyptone quattro 47 (plenum depth 400mm plus
50mm Isover Acoustic Partition Roll (APR 1200))
0.6

Practical absorption coefficient αp


0.4

0.2

0.0
125 250 500 1k 2k 4k αW AC1 NRC2
125 250 500 1000 2000 4000
Frequency (Hz)
0.45 0.50 0.45 0.40 0.30 0.25 0.35(L) D 0.40

System reference
C10A016 0.50 0.55 0.50 0.40 0.30 0.30 0.40(L) D 0.45
C10A017
Floors and ceilings

LINE 6 Sound absorption coefficient αp

Gyptone line 6 (plenum depth 400mm)


Practical absorption coefficient αp

1.0

0.8
Gyptone line 6 (plenum depth 400mm plus
100mm Isover Spacesaver Ready-Cut)
0.6

Practical absorption coefficient αp


0.4

0.2

αW
C06

125 250 500 1k 2k 4k AC1 NRC2


0.0
125 250 500 1000 2000 4000
Frequency (Hz)
0.70 0.65 0.60 0.50 0.40 0.35 0.45(L) D 0.55
System reference
C10A001
0.70 0.70 0.65 0.65 0.50 0.45 0.55(L) D 0.65
C10A002

SIXTO 63 Sound absorption coefficient αp

Gyptone sixto 63 (plenum depth 200mm)


Practical absorption coefficient αp

1.0

Practical absorption coefficient αp


0.8

0.6

0.4
125 250 500 1k 2k 4k αW AC1 NRC2

0.2
0.35 0.60 0.70 0.60 0.55 0.55 0.60 C 0.60
0.0
125 250 500 1000 2000 4000
Frequency (Hz)

System reference
C10A115

1
AC - Absorption Class.
2
NRC - Noise Reduction Coefficient.

All products have been tested to BS EN 20354 and ISO 354. The single figure rating practical sound absorption coefficient αw is calculated in accordance
with EN ISO 11654. Suffix letters indicate where performance is limited at either low, medium or high frequencies.

C06. S01. P05 british-gypsum.com


Rigitone performance

Introduction
Table 4 – Sound absorption data for Rigitone boards

8-15-20 SUPER Sound absorption coefficient αp


Practical absorption coefficient αp

Rigitone 8-15-20 super (plenum depth 50mm)3


1.0

0.8
Rigitone 8-15-20 super (plenum depth 200mm)
0.6
Rigitone 8-15-20 super (plenum depth 200mm plus
0.4 50mm Isover Frame Batt 32)
0.2

0.0
Practical absorption coefficient αp
125 250 500 1000 2000 4000

Frequency (Hz) 125 250 500 1k 2k 4k αW AC1 NRC2

System reference C10A058 0.15 0.40 0.70 0.75 0.45 0.40 0.50(M) D 0.55
C10A059
0.35 0.75 0.75 0.55 0.40 0.30 0.45(LM) D 0.60
C10A069
0.60 0.85 0.80 0.65 0.45 0.30 0.45(LM) D 0.70

Floors and ceilings


8/18 Sound absorption coefficient αp

Rigitone 8/18 (plenum depth 50mm)3


Practical absorption coefficient αp

1.0

0.8
Rigitone 8/18 (plenum depth 200mm)
Rigitone 8/18 (plenum depth 200mm plus 50mm Isover Frame Batt 32)
0.6

Practical absorption coefficient αp


0.4

0.2

αW AC1 NRC2

C06
125 250 500 1k 2k 4k
0.0
125 250 500 1000 2000 4000
Frequency (Hz)
0.10 0.30 0.65 0.85 0.55 0.30 0.50(M) D 0.55

System reference C10A036 0.35 0.75 0.90 0.60 0.50 0.40 0.55(LM) D 0.70
C10A037
C10A060 0.60 0.95 0.95 0.80 0.70 0.50 0.70(LM) C 0.85

8/18 Q Sound absorption coefficient αp

Rigitone 8/18 q (plenum depth 50mm)3


Practical absorption coefficient αp

1.0

0.8
Rigitone 8/18 q (plenum depth 200mm)
Rigitone 8/18 q (plenum depth 200mm plus
0.6

25mm Isover Acoustic Partition Roll (APR 1200))


0.4

0.2
Practical absorption coefficient αp
0.0
125 250 500 1000
Frequency (Hz)
2000 4000
125 250 500 1k 2k 4k αW AC1 NRC2

0.15 0.25 0.60 0.85 0.65 0.50 0.55(M) D 0.60


System reference C10A125
C10A124 0.40 0.65 0.80 0.60 0.55 0.50 0.60 C 0.65
C10A126
0.40 0.70 0.85 0.80 0.80 0.70 0.80 B 0.80

1
AC - Absorption Class.
2
NRC - Noise Reduction Coefficient.
3
Due to installation limitations the minimum cavity size that can be constructed with CasoLine mf or CasoLine curve system is 100mm. The sound absorption
performance for these systems is estimated to be equivalent to that of the same system built with a 50mm plenum.

All products have been tested to BS EN 20354 and ISO 354. The single figure rating practical sound absorption coefficient αw is calculated in accordance
with EN ISO 11654. Suffix letters indicate where performance is limited at either low, medium or high frequencies.

0115 945 6123 bgtechnical.enquiries@bpb.com C06. S01. P06


Rigitone performance (continued)
Introduction

Table 4 (continued) - Sound absorption data for Rigitone boards

10/23 Sound absorption coefficient αp

Rigitone 10/23 (plenum depth 50mm)3


Practical absorption coefficient αp
1.0

0.8
Rigitone 10/23 (plenum depth 200mm)
Rigitone 10/23 (plenum depth 200mm plus
0.6

50mm Isover Frame Batt 32)


0.4

0.2 Practical absorption coefficient αp

αW AC1 NRC2
0.0
125 250 500 1000 2000 4000 125 250 500 1k 2k 4k
Frequency (Hz)

0.10 0.25 0.65 0.90 0.55 0.25 0.45(M) D 0.60


System reference C10A038
C10A039 0.35 0.70 0.85 0.60 0.50 0.35 0.50(LM) D 0.65
C10A061
0.65 0.95 0.90 0.80 0.65 0.45 0.65(LM) C 0.80
Floors and ceilings

12-20/66 Sound absorption coefficient αp

Rigitone 12-20/66 (plenum depth 50mm)3


Practical absorption coefficient αp

1.0

0.8 Rigitone 12-20/66 (plenum depth 200mm)


0.6
Rigitone 12-20/66 (plenum depth 200mm plus
50mm Isover Frame Batt 32)
0.4

0.2 Practical absorption coefficient αp


C06

αW AC1 NRC2
0.0
125 250 500 1000 2000 4000 125 250 500 1k 2k 4k
Frequency (Hz)

0.10 0.25 0.60 0.85 0.55 0.30 0.45(M) D 0.55


System reference C10A042
C10A043 0.40 0.70 0.85 0.60 0.50 0.35 0.50(LM) D 0.65
C10A063
0.55 0.95 1.00 0.85 0.70 0.55 0.70(LM) C 0.90

12/25 Sound absorption coefficient αp

Rigitone 12/25 (plenum depth 50mm)3


Practical absorption coefficient αp

1.0

0.8 Rigitone 12/25 (plenum depth 200mm)


0.6
Rigitone 12/25 (plenum depth 200mm plus
50mm Isover Frame Batt 32)
0.4

0.2
Practical absorption coefficient αp
0.0
125 250 500 1000 2000 4000
125 250 500 1k 2k 4k αW AC1 NRC2
Frequency (Hz)

0.05 0.25 0.65 0.85 0.65 0.50 0.55(M) D 0.60


System reference C10A127
C10A129 0.35 0.75 0.90 0.65 0.55 0.40 0.55(LM) D 0.70
C10A128
0.55 0.95 0.95 0.85 0.70 0.50 0.70(LM) C 0.85

1
AC – Absorption Class.
2
NRC – Noise Reduction Coefficient.
3
Due to installation limitations the minimum cavity size that can be constructed with CasoLine mf or CasoLine curve system is 100mm. The sound absorption
performance for these systems is estimated to be equivalent to that of the same system built with a 50mm plenum.

All products have been tested to BS EN 20354 and ISO 354. The single figure rating practical sound absorption coefficient αw is calculated in accordance
with EN ISO 11654. Suffix letters indicate where performance is limited at either low, medium or high frequencies.

C06. S01. P07 british-gypsum.com


Rigitone performance (continued)

Introduction
Table 4 (continued) – Sound absorption data for Rigitone boards

12/25 Q Sound absorption coefficient αp

Rigitone 12/25 q (plenum depth 50mm)3


Practical absorption coefficient αp 1.0

0.8 Rigitone 12/25 q (plenum depth 200mm)


0.6
Rigitone 12/25 q (plenum depth 200mm plus
50mm Isover Frame Batt 32)
0.4

0.2
Practical absorption coefficient αp
0.0

αW AC1 NRC2
125 250 500 1000 2000 4000

Frequency (Hz)
125 250 500 1k 2k 4k

System reference C10A131 0.10 0.30 0.65 0.90 0.80 0.60 0.60(M) C 0.65
C10A130
C10A132 0.35 0.75 0.90 0.70 0.65 0.50 0.65(LM) C 0.75

0.55 0.90 0.95 0.85 0.85 0.65 0.85(L) B 0.90

Floors and ceilings


15/30 Sound absorption coefficient αp

Rigitone 15/30 (plenum depth 50mm)3


Practical absorption coefficient αp

1.0

0.8
Rigitone 15/30 (plenum depth 200mm)
Rigitone 15/30 (plenum depth 200mm plus
0.6

50mm Isover Frame Batt 32)


0.4

0.2
Practical absorption coefficient αp

C06
αW
0.0
125 250 500 1000 2000 4000
125 250 500 1k 2k 4k AC1 NRC2
Frequency (Hz)

0.10 0.25 0.60 0.85 0.55 0.30 0.45(M) D 0.55


System reference C10A040
C10A041 0.35 0.70 0.85 0.60 0.50 0.35 0.50(LM) D 0.65
C10A062
0.60 0.95 1.00 0.85 0.70 0.55 0.70(LM) C 0.85

1
AC – Absorption Class.
2
NRC – Noise Reduction Coefficient.
3
Due to installation limitations the minimum cavity size that can be constructed with CasoLine mf or CasoLine curve system is 100mm. The sound absorption
performance for these systems is estimated to be equivalent to that of the same system built with a 50mm plenum.

All products have been tested to BS EN 20354 and ISO 354. The single figure rating practical sound absorption coefficient αw is calculated in accordance
with EN ISO 11654. Suffix letters indicate where performance is limited at either low, medium or high frequencies.

0115 945 6123 bgtechnical.enquiries@bpb.com C06. S01. P08


CasoLine curve

CasoLine curve
Concealed grid curved ceiling system

All our systems are covered by SpecSure® when using


genuine British Gypsum and Saint-Gobain Isover products
Floors and ceilings
C06
CasoLine curve
CasoLine curve
CasoLine curve is a lightweight, non-loadbearing,
System can be skim
suspended ceiling system for constructing finished with
ThistlePro PureFinish.

curved ceilings and soffit linings. It can be used Refer to C02. S01. P49

in conjunction with British Gypsum perforated


and non-perforated boards to create unique,
eye-catching ceiling designs as part of the Refer to C01. S01. P07

interior design.
Key benefits
— Can be used to create a unique, creative ceiling
design using concave or convex curves down to
a minimum radius of 600mm depending on
board used
— Compatible with a wide range of British Gypsum

Floors and ceilings


boards from the Gyproc, Glasroc, Gyptone and
Rigitone ranges
— Pre-formed components and standard fixings
make on-site installation straightforward,
requiring no specialist tools or equipment

C06

You may also be interested in...


For indicative sound absorbtion performances using
Gyptone and Rigitone boards with CasoLine curve.
Refer to C06. S01. P04 – Floors and ceilings introduction,
tables 3 and 4.

0115 945 6123 bgtechnical.enquiries@bpb.com C06. S03. P02


CasoLine curve design
CasoLine curve

Building design Board finishing

CasoLine curve comprises Gypframe MF7C Curved Support Refer to C08. S03. P04 – Finishes.
Channels, Gypframe MF5 Ceiling Sections and Gypframe MF7
Primary Support Channels. Whilst a good quality finish can be achieved using normal jointing
techniques, a plaster skim finish may be considered (with the exception of
Gyptone and Rigitone boards), particularly where there are a number of
Planning – key factors butt-end joints on the curve.

Gypframe MF7C Curved Support Channel is supplied pre-formed Refer to British Gypsum Ceiling Installation Guide.
to the radius required. Board joints should be avoided on the apex
of the curve for the exposed layer of board. Gypframe MF5 Ceiling
Section positions should therefore be pre-determined at the
design stage. SpecSure®
Degree of curvature All our systems are covered by SpecSure® when
In common with other sheet materials, board-ends have a tendency using genuine British Gypsum and Saint-Gobain
to remain straight, and so the minimum achievable radius will be Isover products.
influenced by the board characteristics, the length of curve, the
support centres, and the occurrence of board joints.

Refer to table 1.

Table 1 – Minimum radii and framing centres


Floors and ceilings

Board type Thickness Minimum radius1 MF52 centres Span (suspension points) of MF7C3 MF7C3 centres
mm mm mm mm mm

Glasroc F multiboard 6 600 300 900 1200

12 (2 x 6) 600 300 600 1200

Gyptone boards4 12.5 6000 300 900 1200

Rigitone boards4 12.5 5000 330 900 1000


C06

Gyproc WallBoard 9.5 1800 300 750 1200

12.5 3600 300 600 1200

15 4800 300 600 1200

Gyproc SoundBloc 12.5 2900 300 600 1200

15 3600 300 600 1200

Gyproc FireLine 12.5 4800 300 600 1200

1
Concave or convex.
2
Gypframe MF5 Ceiling Section.
3
Gypframe MF7C Curved Support Channel.
4
ACTIVair technology as standard.

It is not recommended to bend Rigidur h board.

C06. S03. P03 british-gypsum.com


CasoLine curve construction details

CasoLine curve
1 2

2
4
7

2
6

m
0m
30
10
1

Floors and ceilings


Gypframe MF6 Perimeter Channel cut and fixed
to line of curve at perimeter Wall junction

3 4

C06
4

11

7
3

3
7

Hanger - Gypframe MF7C Curved Support Channel Alternative hanger - Gypframe MF7C Curved Support Channel
connection using strap connection using Gypframe FEA1 Steel Angle

1 Gypframe MF6 Perimeter Channel 7 British Gypsum Wafer Head Jack-Point Screw
2 Gypframe MF5 Ceiling Section 8 Fixing to structure
3 Gypframe MF7C Curved Support Channel 9 Gypframe FEA1 Steel Angle
4 Gypframe MF8 Strap Hanger 10 Gypframe MF6 Perimeter Channel, cut and bent to required curve
5 Timber fillet 11 Gypframe FEA1 Steel Angle, cut and bent
6 British Gypsum lining board

0115 945 6123 bgtechnical.enquiries@bpb.com C06. S03. P04


CasoLine curve construction details (continued)
CasoLine curve

Standard method for simple curves

3 2
10 10
0m
0m
m m
Method: where curvature changes from convex to
concave an additional hanger is required.

Methods of joining Gypframe MF7C Curved Support Channels

6
A
Floors and ceilings

3 Section A-A

3
A
1
C06

2
2
1

Concave curvature

7
2
1

B
B

Section B-B
B 2
B
4 3

3 4

Convex curvature

1 Gypframe MF5 Ceiling Section


2 Gypframe MF7C Curved Support Channel
3 British Gypsum Wafer Head Jack-Point Screw
4 Small section of Gypframe MF7 Primary Support Channel fixed to provide
a flat, positive fixing for the Gypframe MF5 Ceiling Section positions

C06. S03. P05 british-gypsum.com


CasoLine curve system components

CasoLine curve
Gypframe metal components ( Refer to C10. S02. P02 for details)

Gypframe MF6 Perimeter Channel Gypframe FEA1 Steel Angle


Perimeter section to support Gypframe MF5 Ceiling Steel angle providing rigid hanger suspension of
Section and fixing of board. ceiling grid.

Gypframe MF7C Curved Support Channel1 Gypframe MF12 Soffit Cleat


Primary section to support Gypframe MF5 Suspension point, one leg connected to structural
Ceiling Section. soffit and the other leg connected to suspension
hanger Gypframe FEA1 Steel Angle or
Gypframe MF8 Strap Hanger.

Gypframe MF5 Ceiling Section Gypframe MF11 Nut & Bolt


Designed to provide seamless suspended ceilings For connecting suspension hanger (Gypframe FEA1
and secondary section to support fixing of board. or MF8) to Gypframe MF12 Soffit Cleat.

Gypframe MF8 Strap Hanger


Alternative suspension of ceiling grid, typically
1 metre maximum drop.

Floors and ceilings


1
Supplied pre-formed to radius required and subject to special order.
Minimum radius available is 600mm.

Board products ( Refer to C10. S03. P02 for details)

Gyproc WallBoard3 Gyproc FireLine3

C06
Standard gypsum plasterboard. Gypsum plasterboard with fire resistant additives.

Gyproc SoundBloc3 Glasroc F multiboard


Gypsum plasterboard with a high density core for Non-combustible glass-reinforced gypsum board.
enhanced sound insulation performance.

Ceiling boards
A full range of Gyptone2 and Rigitone2 boards are
available to meet specific aesthetic and/or acoustic
requirements.

Refer to C10. S08. P02

2
ACTIVair technology as standard.
3
Also available in Moisture Resistant (mr) version. mr boards are specified in intermittent wet use areas.

0115 945 6123 bgtechnical.enquiries@bpb.com C06. S03. P06


CasoLine curve system components (continued)
CasoLine curve

Fixing products ( Refer to C10. S04. P02 for details)

British Gypsum Drywall Screws British Gypsum Wafer Head Jack-Point Screws
Corrosion resistant self-tapping steel screws Corrosion resistant self-tapping steel screws
for fixing board to metal framing less than for fixing metal to metal framing 0.8mm thick
0.8mm thick. and greater, for example connecting Gypframe
components to the Gypframe MF7C Courved
Support Channel.

British Gypsum Collated Drywall Screws Rigitone Screws


Corrosion resistant self-tapping steel screws Specifically designed for fixing Rigitone board to
for fixing board to metal framing less than metal framing.
0.8mm thick.

British Gypsum Wafer Head Drywall Screws


Corrosion resistant self-tapping steel screws
for fixing metal to metal framing less than
0.8mm thick.

Plasterboard accessories ( Refer to C10. S05. P02 for details)


Floors and ceilings

Gyproc Jointing Material Gyproc Sealant


Jointing compounds, ready mixes and adhesives Used to seal air paths for optimum sound
for reinforcement and finishing of board joints. insulation.
Primers and sealers for treatment of boards for
pre-decoration.

Gyproc edge and angle beads Gyproc Joint Tape


C06

Protecting and enhancing board edges and corners. A paper tape designed for reinforcement of flat
joints or internal angles.

Finishing products ( Refer to C10. S06. P02 for details)

Thistle MultiFinish ThistlePro PureFinish


To provide a plaster skim finish on most common To provide a plaster skim finish with
backgrounds including undercoat plasters and ACTIVair technology. Used to finish most
plasterboard. common backgrounds including undercoat plasters
and plasterboard. For more information refer to
C02. S01. P49.

Thistle BoardFinish Plaster accessories


To provide a plaster skim finish to Gyproc Designed for the reinforcement and finishing of
plasterboards. board joints before plaster skimming.

Thistle ProTape FT50 Thistle ProTape FT100


Self-adhesive 48mm wide glass fibre mesh tape. Self-adhesive 100mm wide glass fibre mesh tape.

C06. S03. P07 british-gypsum.com


CasoLine curve system components (continued)

CasoLine curve
Ceiling products ( Refer to C10. S08. P02 for details)

Gyptone quattro 411 Gyptone quattro 471


Acoustic board with square perforations capable of Acoustic board with occasional square perforations
providing Class C sound absorption. and Class D absorption.

Gyptone quattro 421 Gyptone line 61


Acoustic board with square perforations capable of Gyptone board with a linear perforated pattern
providing Class D sound absorption. capable of providing Class D absorption.

Gyptone sixto 631 Gyptone quattro 461


Gyptone board with a unique hexagonal Acoustic board with intermittent square
perforated pattern capable of providing Class C perforations capable of providing Class D
absorption. absorption.

Rigitone 8-15-20 super1 Rigitone 12-20/661


Acoustic board with a random pattern of 8mm, Acoustic board with a perforated pattern of 12mm

Floors and ceilings


15mm and 20mm circles capable of providing Class and 20mm circles capable of providing Class C
D absorption. absorption.

Rigitone 8/181 Rigitone 12/251


Acoustic board with a perforated pattern of Acoustic board with a perforated pattern of
8mm circles capable of providing Class C 12mm circles capable of providing Class C
absorption. absorption.

C06
Rigitone 8/18 q1 Rigitone 12/25 q1
Acoustic board with a perforated pattern of Acoustic board with a perforated pattern of
8mm squares capable of providing Class B 12mm squares capable of providing Class B
absorption. absorption.

Rigitone 10/231 Rigitone 15/301


Acoustic board with a perforated pattern of Acoustic board with a perforated pattern of
10mm circles capable of providing Class C 15mm circles capable of providing Class C
absorption. absorption.

Rigitone Vario 60 Jointing Material Rigitone Large Jointing Kit


High-strength jointing material used for jointing of Jointing kit for application of Vario 60 into
Rigitone boards Rigitone boards.

Rigitone Spacing Tool


Spacer tool used to ensure accurate installation of
Rigitone boards.

1
ACTIVair technology as standard.

Insulation products ( Refer to C10. S09. P02 for details)

Isover Acoustic Partition Roll (APR 1200) Isover Spacesaver Ready-Cut


Glass mineral wool for enhanced acoustic and Glass mineral wool for enhanced acoustic and
thermal performance. thermal performance.

Isover Timber Frame Batts and Rolls


Glass mineral wool for enhanced acoustic and
thermal performance.

0115 945 6123 bgtechnical.enquiries@bpb.com C06. S03. P08


CasoLine curve installation overview
CasoLine curve

This is intended to be a basic description of how the system is built.


For detailed installation guidance refer to the British Gypsum Ceiling Installation Guide.

Gypframe MF6 Perimeter Channel is fixed Suspension for a flat soffit Gypframe MF5 Ceiling sections are screw
at wall positions to the line of the curve. Gypframe MF12 Soffit Cleats are secured to fixed at right angles to the underside of the
Timber fillets are installed where required to the soffit using appropriate fixings. pre-formed support channel to form the
pack out the channel. Gypframe FEA1 Steel Angle hangers are pre- secondary grid, with two British Gypsum
cut and secured to the soffit cleats. Wafer Head Jack-Point Screws per junction.
Pre-formed Gypframe MF7C Curved Support
Channel is installed over the perimeter For convex curvature, insert a small section
of Gypframe MF7 Primary Support Channel to
channels and secured to the hangers. provide a flat, positive fixing at the apex. Refer to
construction detail 7.
Suspension from timber joists
Floors and ceilings

The procedure is as for a flat soffit except


that soffit cleats are not required. Hangers
are fixed directly to the side of the joists
using two fixings.
C06

Boards are fixed to the secondary grid to


form the curvature of the ceiling.

When using Gyptone or Rigitone products please refer to the current British Gypsum Ceiling Installation Guide.

Additional information
For full installation details, refer to the
British Gypsum Ceiling Installation Guide, available to
download from british-gypsum.com

C06. S03. P09 british-gypsum.com


CasoLine curve
Floors and ceilings
C06

0115 945 6123 bgtechnical.enquiries@bpb.com C06. S03. P10