IPS Residential Building lighting illumination level calculations

Table of contents

Project 1
Table of contents 1
Philips TCW 079/179/279 TCW079 HS 2xTL-D36W/830
Luminaire Data Sheet 3
Philips Fugato Compact FBS261 C 2xPL-C/2P18W/830
Luminaire Data Sheet 4
Philips Fugato Compact FBS261 C 2xPL-C/2P26W/830
Luminaire Data Sheet 5
Philips Europa 2 FBS122 O 2xPL-C/2P13W/830
Luminaire Data Sheet 6
Philips TBS230 C6 4xTL-D18W/830
Luminaire Data Sheet 7
Philips TCW 079/179/279 TCW179 HS 2xTL-D36W/830
Luminaire Data Sheet 8
BED ROOM (TYP)
Summary 9
Photometric Results 10
CORRIDOR 1
Summary 11
Photometric Results 12
CORRIDOR 2
Summary 13
Photometric Results 14
LINEN ROOM
Summary 15
Photometric Results 16
STAIRCASE CORRIDOR
Summary 17
Photometric Results 18
PANTRY
Summary 19
Photometric Results 20
LOBBY
Summary 21
Photometric Results 22
AIR LOCK ROOM 1
Summary 23
Photometric Results 24
AIR LOCK ROOM - 2
Summary 25
Photometric Results 26
PUMP ROOM-1
Summary 27
Photometric Results 28
PUMP ROOM-2
Summary 29
Photometric Results 30
JANITOR ROOM
Summary 31
Photometric Results 32
TELECOM ROOM
Summary 33
Photometric Results 34
ELECTRICAL ROOM

Page 1
IPS Residential Building lighting illumination level calculations

Table of contents

Summary 35
Photometric Results 36
PAY PHONE ROOM
Summary 37
Photometric Results 38
FIRE EXIT
Summary 39
Photometric Results 40

Page 2
IPS Residential Building lighting illumination level calculations

Philips TCW 079/179/279 TCW079 HS 2xTL-D36W/830 / Luminaire Data Sheet

Luminous emittance 1:

135° 150° 165° 180° 165° 150° 135°


140

120

100
120° 120°
80

60

105° 40 105°

90° 90°

75° 75°

60° 60°

45° 30° 15° 0° 15° 30° 45°

cd/klm  63%


C0 - C180 C90 - C270

Luminaire classification according to CIE: 86 Luminous emittance 1:


CIE flux code: 37 65 85 87 63
Glare Evaluation According to UGR
 Ceiling 70 70 50 50 30 70 70 50 50 30
 Walls 50 30 50 30 30 50 30 50 30 30
 Floor 20 20 20 20 20 20 20 20 20 20
Room Size Viewing direction at right angles Viewing direction parallel
X Y to lamp axis to lamp axis

2H 2H 17.5 18.8 18.0 19.3 19.8 14.8 16.1 15.3 16.6 17.1
3H 20.3 21.5 20.8 22.0 22.6 16.2 17.3 16.7 17.8 18.4
4H 22.1 23.2 22.6 23.7 24.3 16.7 17.8 17.2 18.4 18.9
6H 24.1 25.1 24.6 25.7 26.3 17.2 18.2 17.7 18.7 19.3
8H 25.1 26.2 25.7 26.7 27.3 17.3 18.3 17.9 18.9 19.5
12H 26.3 27.2 26.8 27.8 28.4 17.5 18.5 18.1 19.0 19.6
4H 2H 18.1 19.2 18.6 19.7 20.3 16.1 17.2 16.7 17.8 18.3
3H 21.2 22.2 21.8 22.7 23.3 17.8 18.7 18.4 19.3 19.9
4H 23.1 24.0 23.7 24.6 25.3 18.5 19.4 19.1 20.0 20.6
6H 25.4 26.2 26.0 26.8 27.5 19.2 20.0 19.8 20.6 21.3
8H 26.6 27.3 27.2 27.9 28.7 19.5 20.2 20.1 20.8 21.5
12H 27.9 28.5 28.5 29.2 29.9 19.7 20.4 20.4 21.0 21.8
8H 4H 23.5 24.2 24.1 24.9 25.6 19.9 20.6 20.5 21.3 22.0
6H 26.1 26.7 26.8 27.4 28.1 21.0 21.6 21.6 22.2 23.0
8H 27.5 28.1 28.2 28.7 29.5 21.5 22.0 22.1 22.7 23.4
12H 29.0 29.5 29.7 30.2 31.0 21.9 22.4 22.6 23.1 23.9
12H 4H 23.5 24.2 24.2 24.8 25.6 20.5 21.2 21.1 21.8 22.5
6H 26.2 26.8 26.9 27.5 28.2 21.8 22.4 22.5 23.0 23.8
8H 27.8 28.2 28.4 28.9 29.7 22.5 23.0 23.2 23.6 24.4

Variation of the observer position for the luminaire distances S

S = 1.0H +0.1 / -0.1 +0.1 / -0.1


S = 1.5H +0.3 / -0.3 +0.2 / -0.3
S = 2.0H +0.4 / -0.5 +0.3 / -0.5

Standard table --- BK13


Correction
--- 3.8
Summand
Corrected Glare Indices referring to 6700lm Total Luminous Flux

Page 3
IPS Residential Building lighting illumination level calculations

Philips Fugato Compact FBS261 C 2xPL-C/2P18W/830 / Luminaire Data Sheet

Luminous emittance 1:

105° 105°

90° 90°

75° 75°

60° 60°

200

45° 45°
300

30° 15° 0° 15° 30°

cd/klm  66%


C0 - C180 C90 - C270

Luminaire classification according to CIE: 100 Luminous emittance 1:


CIE flux code: 76 100 100 98 66
Glare Evaluation According to UGR
 Ceiling 70 70 50 50 30 70 70 50 50 30
 Walls 50 30 50 30 30 50 30 50 30 30
 Floor 20 20 20 20 20 20 20 20 20 20
Room Size Viewing direction at right angles Viewing direction parallel
X Y to lamp axis to lamp axis

2H 2H 21.8 22.7 22.1 22.9 23.1 20.4 21.4 20.7 21.6 21.8
3H 21.7 22.5 22.0 22.8 23.0 20.3 21.1 20.6 21.4 21.6
4H 21.6 22.4 22.0 22.7 22.9 20.2 21.0 20.5 21.3 21.5
6H 21.6 22.3 21.9 22.6 22.9 20.1 20.9 20.5 21.1 21.4
8H 21.5 22.2 21.9 22.5 22.8 20.1 20.8 20.5 21.1 21.4
12H 21.5 22.1 21.9 22.5 22.8 20.1 20.7 20.4 21.0 21.3
4H 2H 21.7 22.5 22.0 22.7 23.0 20.4 21.2 20.7 21.5 21.7
3H 21.6 22.3 22.0 22.6 22.9 20.3 20.9 20.6 21.2 21.6
4H 21.6 22.1 21.9 22.5 22.8 20.2 20.8 20.6 21.1 21.5
6H 21.5 22.0 21.9 22.3 22.7 20.1 20.6 20.6 21.0 21.4
8H 21.5 21.9 21.9 22.3 22.7 20.1 20.5 20.5 20.9 21.3
12H 21.4 21.8 21.9 22.2 22.6 20.1 20.5 20.5 20.9 21.3
8H 4H 21.5 21.9 21.9 22.3 22.7 20.1 20.5 20.5 20.9 21.3
6H 21.4 21.7 21.8 22.1 22.6 20.0 20.4 20.5 20.8 21.2
8H 21.3 21.6 21.8 22.1 22.5 20.0 20.3 20.5 20.7 21.2
12H 21.3 21.5 21.8 22.0 22.5 19.9 20.2 20.4 20.7 21.1
12H 4H 21.4 21.8 21.9 22.2 22.6 20.1 20.5 20.5 20.9 21.3
6H 21.3 21.6 21.8 22.1 22.5 20.0 20.3 20.5 20.7 21.2
8H 21.3 21.5 21.8 22.0 22.5 19.9 20.2 20.4 20.7 21.1

Variation of the observer position for the luminaire distances S

S = 1.0H +1.0 / -2.2 +1.4 / -3.6


S = 1.5H +2.4 / -4.5 +2.8 / -12.1
S = 2.0H +4.2 / -18.3 +4.7 / -23.5

Standard table BK00 BK00


Correction
1.8 0.5
Summand
Corrected Glare Indices referring to 2400lm Total Luminous Flux

Page 4
IPS Residential Building lighting illumination level calculations

Philips Fugato Compact FBS261 C 2xPL-C/2P26W/830 / Luminaire Data Sheet

Luminous emittance 1:

105° 105°

90° 90°

75° 75°

100
60° 60°

150

45° 200 45°

250

300

30° 15° 0° 15° 30°

cd/klm  50%


C0 - C180 C90 - C270

Luminaire classification according to CIE: 100 Luminous emittance 1:


CIE flux code: 75 98 100 100 50
Glare Evaluation According to UGR
 Ceiling 70 70 50 50 30 70 70 50 50 30
 Walls 50 30 50 30 30 50 30 50 30 30
 Floor 20 20 20 20 20 20 20 20 20 20
Room Size Viewing direction at right angles Viewing direction parallel
X Y to lamp axis to lamp axis

2H 2H 22.0 22.9 22.3 23.1 23.4 21.1 22.0 21.4 22.2 22.4
3H 21.9 22.7 22.2 23.0 23.2 21.0 21.8 21.3 22.0 22.3
4H 21.8 22.6 22.2 22.9 23.1 20.9 21.7 21.2 21.9 22.2
6H 21.8 22.5 22.1 22.8 23.0 20.8 21.5 21.2 21.8 22.1
8H 21.7 22.4 22.1 22.7 23.0 20.8 21.5 21.1 21.8 22.1
12H 21.7 22.3 22.0 22.6 23.0 20.7 21.4 21.1 21.7 22.0
4H 2H 21.9 22.7 22.2 23.0 23.2 21.1 21.8 21.4 22.1 22.4
3H 21.8 22.5 22.2 22.8 23.1 20.9 21.6 21.3 21.9 22.2
4H 21.8 22.3 22.1 22.7 23.0 20.9 21.4 21.2 21.8 22.1
6H 21.7 22.2 22.1 22.5 22.9 20.8 21.3 21.2 21.6 22.0
8H 21.6 22.1 22.1 22.5 22.9 20.8 21.2 21.2 21.6 22.0
12H 21.6 22.0 22.0 22.4 22.8 20.7 21.1 21.2 21.5 21.9
8H 4H 21.6 22.1 22.1 22.5 22.9 20.8 21.2 21.2 21.6 22.0
6H 21.6 21.9 22.0 22.3 22.8 20.7 21.0 21.1 21.4 21.9
8H 21.5 21.8 22.0 22.3 22.7 20.6 20.9 21.1 21.4 21.8
12H 21.5 21.7 22.0 22.2 22.7 20.6 20.8 21.1 21.3 21.8
12H 4H 21.6 22.0 22.0 22.4 22.8 20.7 21.1 21.2 21.5 21.9
6H 21.5 21.8 22.0 22.3 22.7 20.6 20.9 21.1 21.4 21.8
8H 21.5 21.7 22.0 22.2 22.7 20.6 20.8 21.1 21.3 21.8

Variation of the observer position for the luminaire distances S

S = 1.0H +1.1 / -2.6 +1.3 / -3.3


S = 1.5H +2.6 / -5.4 +2.8 / -11.4
S = 2.0H +4.5 / -23.2 +4.7 / -25.3

Standard table BK00 BK00


Correction
1.0 0.1
Summand
Corrected Glare Indices referring to 3600lm Total Luminous Flux

Page 5
IPS Residential Building lighting illumination level calculations

Philips Europa 2 FBS122 O 2xPL-C/2P13W/830 / Luminaire Data Sheet

Luminous emittance 1:

105° 105°

90° 90°

75° 75°

40
60° 60°

60

45° 80 45°

100

120

30° 15° 0° 15° 30°

cd/klm  32%


C0 - C180 C90 - C270

Luminaire classification according to CIE: 100 Luminous emittance 1:


CIE flux code: 48 80 96 100 32
Glare Evaluation According to UGR
 Ceiling 70 70 50 50 30 70 70 50 50 30
 Walls 50 30 50 30 30 50 30 50 30 30
 Floor 20 20 20 20 20 20 20 20 20 20
Room Size Viewing direction at right angles Viewing direction parallel
X Y to lamp axis to lamp axis

2H 2H 21.5 22.8 21.8 23.0 23.3 21.4 22.7 21.7 23.0 23.2
3H 23.0 24.2 23.3 24.4 24.7 22.9 24.1 23.3 24.4 24.7
4H 23.6 24.7 23.9 25.0 25.3 23.5 24.6 23.9 24.9 25.2
6H 23.9 25.0 24.3 25.3 25.6 23.9 24.9 24.3 25.2 25.6
8H 24.0 25.0 24.4 25.3 25.7 24.0 25.0 24.4 25.3 25.6
12H 24.1 25.0 24.5 25.4 25.7 24.0 25.0 24.4 25.3 25.7
4H 2H 22.1 23.3 22.5 23.5 23.8 22.1 23.2 22.5 23.5 23.8
3H 23.8 24.8 24.2 25.1 25.5 23.8 24.8 24.2 25.1 25.4
4H 24.5 25.4 24.9 25.7 26.1 24.5 25.4 24.9 25.7 26.1
6H 25.0 25.8 25.4 26.1 26.5 25.0 25.7 25.4 26.1 26.5
8H 25.2 25.8 25.6 26.2 26.6 25.1 25.8 25.6 26.2 26.6
12H 25.2 25.8 25.7 26.2 26.7 25.2 25.8 25.6 26.2 26.6
8H 4H 24.8 25.5 25.2 25.9 26.3 24.8 25.5 25.2 25.9 26.3
6H 25.4 26.0 25.9 26.4 26.8 25.4 25.9 25.8 26.4 26.8
8H 25.6 26.1 26.1 26.5 27.0 25.6 26.0 26.0 26.5 27.0
12H 25.7 26.1 26.2 26.6 27.1 25.7 26.1 26.2 26.6 27.1
12H 4H 24.8 25.4 25.3 25.8 26.3 24.8 25.4 25.2 25.8 26.3
6H 25.4 25.9 25.9 26.4 26.9 25.4 25.9 25.9 26.4 26.8
8H 25.7 26.1 26.1 26.5 27.0 25.6 26.0 26.1 26.5 27.0

Variation of the observer position for the luminaire distances S

S = 1.0H +0.1 / -0.1 +0.1 / -0.1


S = 1.5H +0.2 / -0.3 +0.2 / -0.4
S = 2.0H +0.4 / -0.7 +0.4 / -0.7

Standard table BK05 BK05


Correction
4.1 4.0
Summand
Corrected Glare Indices referring to 1800lm Total Luminous Flux

Page 6
IPS Residential Building lighting illumination level calculations

Philips TBS230 C6 4xTL-D18W/830 / Luminaire Data Sheet

Luminous emittance 1:

105° 105°

90° 90°

75° 75°

60° 60°

160

45° 45°
240

30° 15° 0° 15° 30°

cd/klm  66%


C0 - C180 C90 - C270

Luminaire classification according to CIE: 100 Luminous emittance 1:


CIE flux code: 71 100 100 100 66
Glare Evaluation According to UGR
 Ceiling 70 70 50 50 30 70 70 50 50 30
 Walls 50 30 50 30 30 50 30 50 30 30
 Floor 20 20 20 20 20 20 20 20 20 20
Room Size Viewing direction at right angles Viewing direction parallel
X Y to lamp axis to lamp axis

2H 2H 14.4 15.3 14.6 15.5 15.8 15.9 16.8 16.1 17.0 17.2
3H 14.2 15.1 14.5 15.3 15.6 15.7 16.6 16.0 16.8 17.1
4H 14.1 14.9 14.5 15.2 15.5 15.6 16.4 16.0 16.7 17.0
6H 14.1 14.8 14.4 15.1 15.4 15.6 16.3 15.9 16.6 16.9
8H 14.0 14.7 14.4 15.0 15.3 15.5 16.2 15.9 16.5 16.8
12H 14.0 14.7 14.4 15.0 15.3 15.5 16.2 15.9 16.5 16.8
4H 2H 14.3 15.1 14.6 15.4 15.6 15.7 16.5 16.0 16.7 17.0
3H 14.2 14.8 14.5 15.1 15.4 15.5 16.2 15.9 16.5 16.8
4H 14.1 14.7 14.5 15.0 15.3 15.5 16.0 15.8 16.4 16.7
6H 14.0 14.5 14.4 14.9 15.3 15.4 15.9 15.8 16.2 16.6
8H 14.0 14.4 14.4 14.8 15.2 15.4 15.8 15.8 16.2 16.6
12H 13.9 14.3 14.4 14.7 15.2 15.3 15.7 15.8 16.1 16.5
8H 4H 14.0 14.4 14.4 14.8 15.2 15.4 15.8 15.8 16.2 16.6
6H 13.9 14.2 14.3 14.7 15.1 15.3 15.6 15.7 16.1 16.5
8H 13.8 14.2 14.3 14.6 15.1 15.2 15.5 15.7 16.0 16.5
12H 13.8 14.1 14.3 14.5 15.0 15.2 15.4 15.7 15.9 16.4
12H 4H 13.9 14.3 14.4 14.7 15.2 15.3 15.7 15.8 16.1 16.5
6H 13.8 14.2 14.3 14.6 15.1 15.2 15.5 15.7 16.0 16.5
8H 13.8 14.1 14.3 14.5 15.0 15.2 15.4 15.7 15.9 16.4

Variation of the observer position for the luminaire distances S

S = 1.0H +2.2 / -9.7 +1.5 / -2.2


S = 1.5H +3.9 / -20.6 +2.8 / -19.7
S = 2.0H +5.9 / -24.0 +4.7 / -26.5

Standard table BK00 BK00


Correction
-5.6 -4.2
Summand
Corrected Glare Indices referring to 5400lm Total Luminous Flux

Page 7
IPS Residential Building lighting illumination level calculations

Philips TCW 079/179/279 TCW179 HS 2xTL-D36W/830 / Luminaire Data Sheet

Luminous emittance 1:

135° 150° 165° 180° 165° 150° 135°


300

250

120° 200 120°

150

105° 100 105°

90° 90°

75° 75°

60° 60°

45° 30° 15° 0° 15° 30° 45°

cd/klm  71%


C0 - C180 C90 - C270

Luminaire classification according to CIE: 89 Due to missing symmetry properties, no UGR table
CIE flux code: 44 75 92 89 71 can be displayed for this luminaire.

Page 8
IPS Residential Building lighting illumination level calculations

BED ROOM (TYP) / Summary

160 6.00 m
240 240 80
80 320
320 240
400
160 320 320
400
320 320
240 80
80
240
160

320 160
320
240 400 80
80 320
320 400
320 160
240 240

0.00
0.00 4.00 m

Height of Room: 2.500 m, Mounting Height: 2.585 m, Light loss factor: Values in Lux, Scale 1:78
0.70

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 205 33 412 0.162
Floor 20 177 83 239 0.471
Ceiling 50 27 18 32 0.664
Walls (4) 50 50 17 141 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.760 m Left Wall 15 16
Grid: 64 x 64 Points Lower Wall 14 16
Boundary Zone: 0.000 m (CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.176, Ceiling / Working Plane: 0.133.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 2 Philips TBS230 C6 4xTL-D18W/830 (1.000) 5400 70.0
Total: 10800 140.0

Specific connected load: 5.83 W/m² = 2.84 W/m²/100 lx (Ground area: 24.00 m²)

Page 9
IPS Residential Building lighting illumination level calculations

BED ROOM (TYP) / Photometric Results

Total Luminous Flux: 10800 lm


Total Load: 140.0 W
Light loss factor: 0.70
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 189 17 205 / /
Floor 154 23 177 20 11
Ceiling 0.00 27 27 50 4.34
Wall 1 36 23 59 50 9.35
Wall 2 19 25 45 50 7.11
Wall 3 36 23 59 50 9.38
Wall 4 19 24 44 50 6.95

Uniformity on the working plane UGR Lengthways- Across to luminaire axis


u0: 0.162 (1:6) Left Wall 15 16
Emin / Emax: 0.081 (1:12) Lower Wall 14 16
(CIE, SHR = 0.25.)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.176, Ceiling / Working Plane: 0.133.

Specific connected load: 5.83 W/m² = 2.84 W/m²/100 lx (Ground area: 24.00 m²)

Page 10
IPS Residential Building lighting illumination level calculations

CORRIDOR 1 / Summary

100 100 150 100 150 100 150 100 2.20 m


100 100 100 100 150 100 100 100 150 100 100 100 150 100 100 100
0.00
0.00 30.60 m

Height of Room: 2.500 m, Mounting Height: 2.630 m, Light loss factor: Values in Lux, Scale 1:219
0.70

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 128 33 260 0.257
Floor 20 105 53 141 0.502
Ceiling 50 19 14 22 0.749
Walls (4) 50 44 13 114 /

Workplane:
Height: 0.760 m
Grid: 128 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.304, Ceiling / Working Plane: 0.151.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 8 Philips Fugato Compact FBS261 C 2xPL-C/2P26W/830 (1.000) 3600 72.4
Total: 28800 579.2

Specific connected load: 8.60 W/m² = 6.72 W/m²/100 lx (Ground area: 67.32 m²)

Page 11
IPS Residential Building lighting illumination level calculations

CORRIDOR 1 / Photometric Results

Total Luminous Flux: 28800 lm


Total Load: 579.2 W
Light loss factor: 0.70
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 112 16 128 / /
Floor 86 19 105 20 6.71
Ceiling 0.00 19 19 50 3.08
Wall 1 27 18 45 50 7.17
Wall 2 11 17 27 50 4.34
Wall 3 27 18 45 50 7.17
Wall 4 11 17 28 50 4.39

Uniformity on the working plane


u0: 0.257 (1:4)
Emin / Emax: 0.127 (1:8)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.304, Ceiling / Working Plane: 0.151.

Specific connected load: 8.60 W/m² = 6.72 W/m²/100 lx (Ground area: 67.32 m²)

Page 12
IPS Residential Building lighting illumination level calculations

CORRIDOR 2 / Summary

150 150 150 100 150 100 150 2.20 m


50 50 50 50
50 150 50 50 150 50 150
50 150 50 150 50 150 50
150 250 50 150 250 50 150 250
50 150 50 50 150 250
50 50 50
150 150 150
0.00
0.00 17.00 m

Height of Room: 2.500 m, Mounting Height: 2.630 m, Light loss factor: Values in Lux, Scale 1:122
0.70

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 115 22 260 0.195
Floor 20 94 39 139 0.415
Ceiling 50 17 12 21 0.699
Walls (4) 50 38 10 113 /

Workplane:
Height: 0.760 m
Grid: 128 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.296, Ceiling / Working Plane: 0.148.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 4 Philips Fugato Compact FBS261 C 2xPL-C/2P26W/830 (1.000) 3600 72.4
Total: 14400 289.6

Specific connected load: 7.74 W/m² = 6.74 W/m²/100 lx (Ground area: 37.40 m²)

Page 13
IPS Residential Building lighting illumination level calculations

CORRIDOR 2 / Photometric Results

Total Luminous Flux: 14400 lm


Total Load: 289.6 W
Light loss factor: 0.70
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 101 14 115 / /
Floor 77 17 94 20 5.99
Ceiling 0.00 17 17 50 2.71
Wall 1 24 16 40 50 6.41
Wall 2 7.54 15 23 50 3.62
Wall 3 24 16 40 50 6.41
Wall 4 7.54 15 22 50 3.54

Uniformity on the working plane


u0: 0.195 (1:5)
Emin / Emax: 0.086 (1:12)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.296, Ceiling / Working Plane: 0.148.

Specific connected load: 7.74 W/m² = 6.74 W/m²/100 lx (Ground area: 37.40 m²)

Page 14
IPS Residential Building lighting illumination level calculations

LINEN ROOM / Summary

3.60 m
100

150 150
150
200 200
200
250
150 200 250 200
250 250
200
250 250
150
250 250
200
200 200
150
150
100

0.00
0.00 1.95 2.90 3.30 m

Height of Room: 2.500 m, Mounting Height: 2.500 m, Light loss factor: Values in Lux, Scale 1:47
0.70

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 164 69 282 0.420
Floor 20 120 75 160 0.629
Ceiling 50 83 39 293 0.465
Walls (5) 50 105 50 433 /

Workplane:
Height: 0.760 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.713, Ceiling / Working Plane: 0.506.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 1 Philips TCW 079/179/279 TCW079 HS 2xTL-D36W/830 (1.000) 6700 70.0
Total: 6700 70.0

Specific connected load: 7.36 W/m² = 4.48 W/m²/100 lx (Ground area: 9.51 m²)

Page 15
IPS Residential Building lighting illumination level calculations

LINEN ROOM / Photometric Results

Total Luminous Flux: 6700 lm


Total Load: 70.0 W
Light loss factor: 0.70
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 111 53 164 / /
Floor 72 48 120 20 7.63
Ceiling 34 49 83 50 13
Wall 1 39 42 81 50 13
Wall 2 92 42 134 50 21
Wall 3 40 38 78 50 12
Wall 4 40 44 84 50 13
Wall 5 64 43 107 50 17

Uniformity on the working plane


u0: 0.420 (1:2)
Emin / Emax: 0.245 (1:4)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.713, Ceiling / Working Plane: 0.506.

Specific connected load: 7.36 W/m² = 4.48 W/m²/100 lx (Ground area: 9.51 m²)

Page 16
IPS Residential Building lighting illumination level calculations

STAIRCASE CORRIDOR / Summary

4.60 m
50 150 150
100
200
150 250 250
200 100
200
250 250
100
150 200
200
100

100 200
200
250 150
250
250
250 200 100
200
100
200 150
150
0.00
0.00 3.50 m

Height of Room: 2.500 m, Mounting Height: 2.630 m, Light loss factor: Values in Lux, Scale 1:60
0.70

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 143 37 266 0.260
Floor 20 120 57 171 0.477
Ceiling 50 19 13 23 0.689
Walls (4) 50 39 13 95 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.760 m Left Wall 22 21
Grid: 64 x 64 Points Lower Wall 22 21
Boundary Zone: 0.000 m (CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.223, Ceiling / Working Plane: 0.135.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 2 Philips Fugato Compact FBS261 C 2xPL-C/2P26W/830 (1.000) 3600 72.4
Total: 7200 144.8

Specific connected load: 8.99 W/m² = 6.27 W/m²/100 lx (Ground area: 16.10 m²)

Page 17
IPS Residential Building lighting illumination level calculations

STAIRCASE CORRIDOR / Photometric Results

Total Luminous Flux: 7200 lm


Total Load: 144.8 W
Light loss factor: 0.70
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 129 14 143 / /
Floor 101 18 120 20 7.61
Ceiling 0.00 19 19 50 3.08
Wall 1 25 18 43 50 6.78
Wall 2 19 19 37 50 5.91
Wall 3 25 17 42 50 6.76
Wall 4 19 18 36 50 5.81

Uniformity on the working plane UGR Lengthways- Across to luminaire axis


u0: 0.260 (1:4) Left Wall 22 21
Emin / Emax: 0.140 (1:7) Lower Wall 22 21
(CIE, SHR = 0.25.)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.223, Ceiling / Working Plane: 0.135.

Specific connected load: 8.99 W/m² = 6.27 W/m²/100 lx (Ground area: 16.10 m²)

Page 18
IPS Residential Building lighting illumination level calculations

PANTRY / Summary

2.50 m
280

140 140
210 280
280
350 210
350 Residential Building lighting illumination level calculations
MPS
350 280
280 350
210 140
140 350
350 210
280
280 350
350
210
350 280 140
140 350 210
280
350

210 280
280
210
0.00
0.00 3.95 m

Height of Room: 2.500 m, Mounting Height: 2.630 m, Light loss factor: Values in Lux, Scale 1:33
0.70

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 216 69 395 0.318
Floor 20 160 100 218 0.623
Ceiling 50 28 20 35 0.708
Walls (4) 50 67 19 192 /

Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.249, Ceiling / Working Plane: 0.130.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 1 Philips TBS230 C6 4xTL-D18W/830 (1.000) 5400 70.0
Total: 5400 70.0

Specific connected load: 7.09 W/m² = 3.28 W/m²/100 lx (Ground area: 9.87 m²)

Page 19
IPS Residential Building lighting illumination level calculations

PANTRY / Photometric Results

Total Luminous Flux: 5400 lm


Total Load: 70.0 W
Light loss factor: 0.70
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 190 26 216 / /
Floor 126 34 160 20 10
Ceiling 0.00 28 28 50 4.46
Wall 1 46 28 74 50 12
Wall 2 28 28 55 50 8.80
Wall 3 46 28 74 50 12
Wall 4 28 28 56 50 8.84

Uniformity on the working plane


u0: 0.318 (1:3)
Emin / Emax: 0.174 (1:6)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.249, Ceiling / Working Plane: 0.130.

Specific connected load: 7.09 W/m² = 3.28 W/m²/100 lx (Ground area: 9.87 m²)

Page 20
IPS Residential Building lighting illumination level calculations

LOBBY / Summary

200 6.00 m
150 200

250 250 250 200


250 250
250 250

250 250 250 250


250 250
250 250
200
250 250 200
250 300 250 300 250 250
300 300
250 250 250 250 250
250 250 250
200
250 250 250 200
250 250 250

250 250 250 200 250


200
200
0.00
0.00 9.10 m

Height of Room: 2.500 m, Mounting Height: 2.630 m, Light loss factor: Values in Lux, Scale 1:78
0.70

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 234 88 310 0.375
Floor 20 213 108 261 0.506
Ceiling 50 39 29 45 0.727
Walls (4) 50 76 25 135 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.760 m Left Wall 22 21
Grid: 128 x 128 Points Lower Wall 22 21
Boundary Zone: 0.000 m (CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.296, Ceiling / Working Plane: 0.169.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 12 Philips Fugato Compact FBS261 C 2xPL-C/2P18W/830 (1.000) 2400 50.6
Total: 28800 607.2

Specific connected load: 11.12 W/m² = 4.76 W/m²/100 lx (Ground area: 54.60 m²)

Page 21
IPS Residential Building lighting illumination level calculations

LOBBY / Photometric Results

Total Luminous Flux: 28800 lm


Total Load: 607.2 W
Light loss factor: 0.70
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 208 26 234 / /
Floor 183 30 213 20 14
Ceiling 0.00 39 39 50 6.28
Wall 1 46 33 80 50 13
Wall 2 38 34 72 50 11
Wall 3 46 34 80 50 13
Wall 4 38 32 70 50 11

Uniformity on the working plane UGR Lengthways- Across to luminaire axis


u0: 0.375 (1:3) Left Wall 22 21
Emin / Emax: 0.284 (1:4) Lower Wall 22 21
(CIE, SHR = 0.25.)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.296, Ceiling / Working Plane: 0.169.

Specific connected load: 11.12 W/m² = 4.76 W/m²/100 lx (Ground area: 54.60 m²)

Page 22
IPS Residential Building lighting illumination level calculations

AIR LOCK ROOM 1 / Summary

2.10 m
250
250 200
200 250
300 300
300
250
350 300
250
300 350 350
350
350 300
350 250
250 300 350
350 350 300

300 250
300 300
250

250 250
200

0.00
0.00 2.70 m

Height of Room: 2.500 m, Mounting Height: 2.630 m, Light loss factor: Values in Lux, Scale 1:27
0.70

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 267 142 363 0.532
Floor 20 193 141 228 0.729
Ceiling 50 42 29 50 0.679
Walls (4) 50 100 28 232 /

Workplane:
Height: 0.760 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.374, Ceiling / Working Plane: 0.158.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 2 Philips Fugato Compact FBS261 C 2xPL-C/2P18W/830 (1.000) 2400 50.6
Total: 4800 101.2

Specific connected load: 17.85 W/m² = 6.69 W/m²/100 lx (Ground area: 5.67 m²)

Page 23
IPS Residential Building lighting illumination level calculations

AIR LOCK ROOM 1 / Photometric Results

Total Luminous Flux: 4800 lm


Total Load: 101.2 W
Light loss factor: 0.70
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 221 46 267 / /
Floor 145 48 193 20 12
Ceiling 0.00 42 42 50 6.69
Wall 1 56 43 99 50 16
Wall 2 60 42 102 50 16
Wall 3 56 43 99 50 16
Wall 4 60 42 102 50 16

Uniformity on the working plane


u0: 0.532 (1:2)
Emin / Emax: 0.391 (1:3)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.374, Ceiling / Working Plane: 0.158.

Specific connected load: 17.85 W/m² = 6.69 W/m²/100 lx (Ground area: 5.67 m²)

Page 24
IPS Residential Building lighting illumination level calculations

AIR LOCK ROOM - 2 / Summary

160 2.10 m
200 160 160
160
200 240 240
240 200 240
240 240
160 240 240 240 240 200 240 240
200 240 240
200
200 160 160
160 160
0.00
0.00 9.10 m

Height of Room: 2.500 m, Mounting Height: 2.630 m, Light loss factor: Values in Lux, Scale 1:66
0.70

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 188 79 258 0.420
Floor 20 149 90 174 0.605
Ceiling 50 29 19 33 0.666
Walls (4) 50 66 19 121 /

Workplane:
Height: 0.760 m
Grid: 128 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.324, Ceiling / Working Plane: 0.152.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 4 Philips Fugato Compact FBS261 C 2xPL-C/2P18W/830 (1.000) 2400 50.6
Total: 9600 202.4

Specific connected load: 10.59 W/m² = 5.64 W/m²/100 lx (Ground area: 19.11 m²)

Page 25
IPS Residential Building lighting illumination level calculations

AIR LOCK ROOM - 2 / Photometric Results

Total Luminous Flux: 9600 lm


Total Load: 202.4 W
Light loss factor: 0.70
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 162 26 188 / /
Floor 119 30 149 20 9.51
Ceiling 0.00 29 29 50 4.54
Wall 1 40 28 68 50 11
Wall 2 30 27 56 50 8.94
Wall 3 40 28 68 50 11
Wall 4 30 27 56 50 8.95

Uniformity on the working plane


u0: 0.420 (1:2)
Emin / Emax: 0.306 (1:3)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.324, Ceiling / Working Plane: 0.152.

Specific connected load: 10.59 W/m² = 5.64 W/m²/100 lx (Ground area: 19.11 m²)

Page 26
IPS Residential Building lighting illumination level calculations

PUMP ROOM-1 / Summary

12.00 m

300 240 240 300


180 300 300
300 300
300
300 300
300 300 360
300 300 360
360
300 300 300
180 300
300
300 360
300 300 300
360
300
240 300
300
180
300
240 300
240
0.00
0.00 10.40 m

Height of Room: 3.000 m, Mounting Height: 3.000 m, Light loss factor: Values in Lux, Scale 1:155
0.70

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 261 98 372 0.376
Floor 20 238 106 311 0.446
Ceiling 50 92 36 643 0.390
Walls (4) 50 151 50 274 /

Workplane:
Height: 0.760 m
Grid: 128 x 128 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.589, Ceiling / Working Plane: 0.354.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 12 Philips TCW 079/179/279 TCW179 HS 2xTL-D36W/830 (1.000) 6700 70.0
Total: 80400 840.0

Specific connected load: 6.73 W/m² = 2.58 W/m²/100 lx (Ground area: 124.80 m²)

Page 27
IPS Residential Building lighting illumination level calculations

PUMP ROOM-1 / Photometric Results

Total Luminous Flux: 80400 lm


Total Load: 840.0 W
Light loss factor: 0.70
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 205 56 261 / /
Floor 180 58 238 20 15
Ceiling 34 59 92 50 15
Wall 1 87 54 141 50 22
Wall 2 166 57 223 50 35
Wall 3 87 54 141 50 22
Wall 4 47 48 95 50 15

Uniformity on the working plane


u0: 0.376 (1:3)
Emin / Emax: 0.264 (1:4)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.589, Ceiling / Working Plane: 0.354.

Specific connected load: 6.73 W/m² = 2.58 W/m²/100 lx (Ground area: 124.80 m²)

Page 28
IPS Residential Building lighting illumination level calculations

PUMP ROOM-2 / Summary

180 12.00 m
240
240 240
120 240 300
240
240 240 240
300
300
300
240 240
120 240 300
300 300
240 240 300
240
300
180
240 240 240
120
240 300
300
240 180
240
0.00
0.00 8.00 m

Height of Room: 3.000 m, Mounting Height: 3.000 m, Light loss factor: Values in Lux, Scale 1:155
0.70

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 221 78 344 0.352
Floor 20 198 86 267 0.433
Ceiling 50 79 30 632 0.379
Walls (4) 50 125 43 214 /

Workplane:
Height: 0.760 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.572, Ceiling / Working Plane: 0.356.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 8 Philips TCW 079/179/279 TCW179 HS 2xTL-D36W/830 (1.000) 6700 70.0
Total: 53600 560.0

Specific connected load: 5.83 W/m² = 2.64 W/m²/100 lx (Ground area: 96.00 m²)

Page 29
IPS Residential Building lighting illumination level calculations

PUMP ROOM-2 / Photometric Results

Total Luminous Flux: 53600 lm


Total Load: 560.0 W
Light loss factor: 0.70
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 173 48 221 / /
Floor 148 50 198 20 13
Ceiling 29 50 79 50 13
Wall 1 72 46 117 50 19
Wall 2 131 48 179 50 28
Wall 3 72 46 118 50 19
Wall 4 38 42 80 50 13

Uniformity on the working plane


u0: 0.352 (1:3)
Emin / Emax: 0.226 (1:4)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.572, Ceiling / Working Plane: 0.356.

Specific connected load: 5.83 W/m² = 2.64 W/m²/100 lx (Ground area: 96.00 m²)

Page 30
IPS Residential Building lighting illumination level calculations

JANITOR ROOM / Summary

1.85 m
210 240 270
270 210

270 300
300 300 240
270
240
300 300
270

300 300 270 240

270 300
240 300
270
300
300 240
270 300

270
240 270

0.00
0.00 2.30 m

Height of Room: 2.500 m, Mounting Height: 2.500 m, Light loss factor: Values in Lux, Scale 1:24
0.70

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 261 189 328 0.724
Floor 20 170 140 192 0.824
Ceiling 50 173 97 341 0.563
Walls (4) 50 194 85 476 /

Workplane:
Height: 0.760 m
Grid: 16 x 16 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.886, Ceiling / Working Plane: 0.664.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 1 Philips TCW 079/179/279 TCW079 HS 2xTL-D36W/830 (1.000) 6700 70.0
Total: 6700 70.0

Specific connected load: 16.45 W/m² = 6.31 W/m²/100 lx (Ground area: 4.26 m²)

Page 31
IPS Residential Building lighting illumination level calculations

JANITOR ROOM / Photometric Results

Total Luminous Flux: 6700 lm


Total Load: 70.0 W
Light loss factor: 0.70
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 159 101 261 / /
Floor 91 79 170 20 11
Ceiling 69 104 173 50 28
Wall 1 129 84 213 50 34
Wall 2 86 85 171 50 27
Wall 3 129 83 212 50 34
Wall 4 86 85 171 50 27

Uniformity on the working plane


u0: 0.724 (1:1)
Emin / Emax: 0.575 (1:2)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.886, Ceiling / Working Plane: 0.664.

Specific connected load: 16.45 W/m² = 6.31 W/m²/100 lx (Ground area: 4.26 m²)

Page 32
IPS Residential Building lighting illumination level calculations

MPS Residential Building lighting illumination level calculations

TELECOM ROOM / Summary

2.80 m

200 160
200
200
240 240
200 240 240

280 200
280
240
280
240 280
280
280 240
280
240
200 240 240
240
200
200 200
160

0.00
0.00 2.30 m

Height of Room: 2.500 m, Mounting Height: 2.500 m, Light loss factor: Values in Lux, Scale 1:36
0.70

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 212 129 297 0.609
Floor 20 146 110 173 0.751
Ceiling 50 119 61 299 0.511
Walls (4) 50 143 72 330 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.760 m Left Wall 18 15
Grid: 32 x 32 Points Lower Wall 18 15
Boundary Zone: 0.000 m (CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.769, Ceiling / Working Plane: 0.559.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 1 Philips TCW 079/179/279 TCW079 HS 2xTL-D36W/830 (1.000) 6700 70.0
Total: 6700 70.0

Specific connected load: 10.87 W/m² = 5.12 W/m²/100 lx (Ground area: 6.44 m²)

Page 33
IPS Residential Building lighting illumination level calculations

TELECOM ROOM / Photometric Results

Total Luminous Flux: 6700 lm


Total Load: 70.0 W
Light loss factor: 0.70
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 139 74 212 / /
Floor 83 63 146 20 9.31
Ceiling 49 70 119 50 19
Wall 1 62 61 123 50 20
Wall 2 100 60 160 50 25
Wall 3 62 61 123 50 20
Wall 4 100 59 159 50 25

Uniformity on the working plane UGR Lengthways- Across to luminaire axis


u0: 0.609 (1:2) Left Wall 18 15
Emin / Emax: 0.435 (1:2) Lower Wall 18 15
(CIE, SHR = 0.25.)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.769, Ceiling / Working Plane: 0.559.

Specific connected load: 10.87 W/m² = 5.12 W/m²/100 lx (Ground area: 6.44 m²)

Page 34
IPS Residential Building lighting illumination level calculations

ELECTRICAL ROOM / Summary

3.00 m
240 200
240 240

280 280 280

320 320 320 240


280 320 280
320

320
280
280 320

320
320 320 320
280
280 240
280 280
240
240 240 200

0.00
0.00 4.00 m

Height of Room: 2.500 m, Mounting Height: 2.500 m, Light loss factor: Values in Lux, Scale 1:39
0.70

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 269 155 353 0.577
Floor 20 202 139 243 0.689
Ceiling 50 136 83 310 0.611
Walls (4) 50 180 99 337 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.760 m Left Wall 21 17
Grid: 32 x 32 Points Lower Wall 22 18
Boundary Zone: 0.000 m (CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.750, Ceiling / Working Plane: 0.505.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 2 Philips TCW 079/179/279 TCW079 HS 2xTL-D36W/830 (1.000) 6700 70.0
Total: 13400 140.0

Specific connected load: 11.67 W/m² = 4.34 W/m²/100 lx (Ground area: 12.00 m²)

Page 35
IPS Residential Building lighting illumination level calculations

ELECTRICAL ROOM / Photometric Results

Total Luminous Flux: 13400 lm


Total Load: 140.0 W
Light loss factor: 0.70
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 182 87 269 / /
Floor 123 79 202 20 13
Ceiling 55 81 136 50 22
Wall 1 116 71 187 50 30
Wall 2 97 73 170 50 27
Wall 3 116 72 188 50 30
Wall 4 97 73 170 50 27

Uniformity on the working plane UGR Lengthways- Across to luminaire axis


u0: 0.577 (1:2) Left Wall 21 17
Emin / Emax: 0.440 (1:2) Lower Wall 22 18
(CIE, SHR = 0.25.)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.750, Ceiling / Working Plane: 0.505.

Specific connected load: 11.67 W/m² = 4.34 W/m²/100 lx (Ground area: 12.00 m²)

Page 36
IPS Residential Building lighting illumination level calculations

PAY PHONE ROOM / Summary

5.50 m
270 270
270 5.10
360 360
450

360 360
270 270
180

90

0.00
0.00 1.20 2.20 m

Height of Room: 2.500 m, Mounting Height: 2.585 m, Light loss factor: Values in Lux, Scale 1:71
0.70

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 255 6.63 453 0.026
Floor 20 176 9.90 256 0.056
Ceiling 50 40 7.60 63 0.189
Walls (5) 50 86 5.06 391 /

Workplane:
Height: 0.760 m
Grid: 128 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.335, Ceiling / Working Plane: 0.158.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 1 Philips TBS230 C6 4xTL-D18W/830 (1.000) 5400 70.0
Total: 5400 70.0

Specific connected load: 10.77 W/m² = 4.23 W/m²/100 lx (Ground area: 6.50 m²)

Page 37
IPS Residential Building lighting illumination level calculations

PAY PHONE ROOM / Photometric Results

Total Luminous Flux: 5400 lm


Total Load: 70.0 W
Light loss factor: 0.70
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 206 48 255 / /
Floor 127 49 176 20 11
Ceiling 0.00 40 40 50 6.39
Wall 1 0.23 8.94 9.17 50 1.46
Wall 2 47 33 80 50 13
Wall 3 65 51 115 50 18
Wall 4 65 51 116 50 18
Wall 5 47 33 80 50 13

Uniformity on the working plane


u0: 0.026 (1:38)
Emin / Emax: 0.015 (1:68)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.335, Ceiling / Working Plane: 0.158.

Specific connected load: 10.77 W/m² = 4.23 W/m²/100 lx (Ground area: 6.50 m²)

Page 38
IPS Residential Building lighting illumination level calculations

FIRE EXIT / Summary

6.60 m
100
150

200 250
250
250 300
250
250 300
250 250

200
2.70
250 250 150
200 1.90
300
200
250 1.00
250
200 0.60

0.00
0.00 0.82 1.90 2.60 4.00 m

Height of Room: 2.500 m, Mounting Height: 2.500 m, Light loss factor: Values in Lux, Scale 1:85
0.70

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 201 69 311 0.341
Floor 20 152 77 194 0.505
Ceiling 50 104 36 305 0.351
Walls (9) 50 133 52 418 /

Workplane:
Height: 0.760 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.748, Ceiling / Working Plane: 0.514.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  [lm] P [W]


1 2 Philips TCW 079/179/279 TCW079 HS 2xTL-D36W/830 (1.000) 6700 70.0
Total: 13400 140.0

Specific connected load: 9.06 W/m² = 4.50 W/m²/100 lx (Ground area: 15.45 m²)

Page 39
IPS Residential Building lighting illumination level calculations

FIRE EXIT / Photometric Results

Total Luminous Flux: 13400 lm


Total Load: 140.0 W
Light loss factor: 0.70
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 137 65 201 / /
Floor 93 59 152 20 9.70
Ceiling 42 62 104 50 16
Wall 1 90 64 154 50 25
Wall 2 113 66 179 50 28
Wall 3 125 69 194 50 31
Wall 4 37 51 88 50 14
Wall 5 91 51 142 50 23
Wall 6 31 45 76 50 12
Wall 7 83 53 136 50 22
Wall 8 85 62 148 50 23
Wall 9 91 60 151 50 24

Uniformity on the working plane


u0: 0.341 (1:3)
Emin / Emax: 0.221 (1:5)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.748, Ceiling / Working Plane: 0.514.

Specific connected load: 9.06 W/m² = 4.50 W/m²/100 lx (Ground area: 15.45 m²)