Plan Floor Lighting Design

Partner for Contact:


Order No.:
Company:
Customer No.:

Date: 10.01.2020
Operator:
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Table of contents

Plan Floor Lighting Design


Project Cover 1
Table of contents 2
Luminaire parts list 5
PHILIPS RC125B W60L60 1 xLED34S/830 NOC
Luminaire Data Sheet 6
PHILIPS RS060B 1xLED5-36-/840
Luminaire Data Sheet 7
PHILIPS DN135B D165 1xLED10S/830
Luminaire Data Sheet 8
Washrooms
Summary 9
Luminaire parts list 10
Luminaires (layout plan) 11
Photometric Results 12
Room Surfaces
Workplane
Value Chart (E) 13
Office R1
Summary 14
Luminaire parts list 15
Luminaires (layout plan) 16
Photometric Results 17
Room Surfaces
Workplane
Value Chart (E) 18
Office R2
Summary 19
Luminaire parts list 20
Luminaires (layout plan) 21
Photometric Results 22
Room Surfaces
Workplane
Value Chart (E) 23
Entrance Gate
Summary 24
Luminaire parts list 25
Luminaires (layout plan) 26
Photometric Results 27
Room Surfaces
Workplane
Value Chart (E) 28
Cafeteria
Summary 29
Luminaire parts list 30
Luminaires (layout plan) 31
Photometric Results 32
Room Surfaces
Workplane
Value Chart (E) 33
Corridor 1
Summary 34
Luminaire parts list 35
Luminaires (layout plan) 36

Page 2
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Table of contents

Photometric Results 37
Room Surfaces
Workplane
Value Chart (E) 38
GM Office
Summary 39
Luminaire parts list 40
Luminaires (layout plan) 41
Photometric Results 42
Room Surfaces
Workplane
Value Chart (E) 43
Corridor 2
Summary 44
Luminaire parts list 45
Luminaires (layout plan) 46
Photometric Results 47
Room Surfaces
Workplane
Value Chart (E) 48
Conference Room
Summary 49
Luminaire parts list 50
Luminaires (layout plan) 51
Photometric Results 52
Room Surfaces
Workplane
Value Chart (E) 53
Deputy Manager
Summary 54
Luminaire parts list 55
Luminaires (layout plan) 56
Photometric Results 57
Room Surfaces
Workplane
Value Chart (E) 58
Project Manager
Summary 59
Luminaire parts list 60
Luminaires (layout plan) 61
Photometric Results 62
Room Surfaces
Workplane
Value Chart (E) 63
Entrance Area
Summary 64
Luminaire parts list 65
Luminaires (layout plan) 66
Photometric Results 67
Room Surfaces
Workplane
Value Chart (E) 68
Front Shell
Summary 69

Page 3
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Table of contents

Luminaire parts list 70


Luminaires (layout plan) 71
Photometric Results 72
Room Surfaces
Workplane
Value Chart (E) 73
Back Shell
Summary 74
Luminaire parts list 75
Luminaires (layout plan) 76
Photometric Results 77
Room Surfaces
Workplane
Value Chart (E) 78
Reception
Summary 79
Luminaire parts list 80
Photometric Results 81

Page 4
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Plan Floor Lighting Design / Luminaire parts list

61 Pieces PHILIPS DN135B D165 1xLED10S/830


Article No.:
Luminous flux (Luminaire): 1000 lm
Luminous flux (Lamps): 1000 lm
Luminaire Wattage: 13.0 W
Luminaire classification according to CIE: 100
CIE flux code: 46 78 95 100 100
Fitting: 1 x LED10S/830/- (Correction Factor
1.000).

41 Pieces PHILIPS RC125B W60L60 1 xLED34S/830 NOC


Article No.:
Luminous flux (Luminaire): 3400 lm
Luminous flux (Lamps): 3400 lm
Luminaire Wattage: 36.0 W
Luminaire classification according to CIE: 100
CIE flux code: 46 78 95 100 100
Fitting: 1 x LED34S/830/- (Correction Factor
1.000).

21 Pieces PHILIPS RS060B 1xLED5-36-/840


Article No.:
Luminous flux (Luminaire): 500 lm
Luminous flux (Lamps): 500 lm
Luminaire Wattage: 6.0 W
Luminaire classification according to CIE: 100
CIE flux code: 93 98 99 100 100
Fitting: 1 x LED5-36-/840 (Correction Factor
1.000).

Page 5
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

PHILIPS RC125B W60L60 1 xLED34S/830 NOC / Luminaire Data Sheet

Luminous emittance 1:

Luminaire classification according to CIE: 100 Luminous emittance 1:


CIE flux code: 46 78 95 100 100
CoreLine Panel – the clear choice for LED Whether for a new building or
renovation of an existing space, customers want lighting solutions that
provide quality of light and substantial energy and maintenance savings. The
new CoreLine Panel range of LED products can be used to replace
functional luminaires in general lighting applications. Both Non-Office
Compliant (NOC) version and Office Compliant version (OC) are now
available. The process of selecting, installing and maintaining is so easy –
it’s a simple switch.

Page 6
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

PHILIPS RS060B 1xLED5-36-/840 / Luminaire Data Sheet

Luminous emittance 1:

Luminaire classification according to CIE: 100 Due to missing symmetry properties, no UGR table
CIE flux code: 93 98 99 100 100 can be displayed for this luminaire.
ClearAccent - Affordable recessed LED spot ClearAccent is an entry-level
recessed spot range designed to replace halogen-based luminaires. Its
attractive price and high lumen per watt ratio make the decision to switch to
LED an easy one. The luminaire’s compact design, with built-in driver, is
suitable for a wide variety of applications. The dimensions of the fixation hole
meet the old halogen-based standard of 68 mm, which makes retrofitting
possible. Thanks to the screw-in connectors, installation is easy and safe.

Page 7
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

PHILIPS DN135B D165 1xLED10S/830 / Luminaire Data Sheet

Luminous emittance 1:

Luminaire classification according to CIE: 100 Due to missing symmetry properties, no UGR table
CIE flux code: 46 78 95 100 100 can be displayed for this luminaire.
CoreLine SlimDownlight - for every project, where light really matters
CoreLine SlimDownlight delivers on the CoreLine promise of innovative,
easy to use and high-quality luminaires.
CoreLine SlimDownlight is an innovative range of recessed and surface-
mounted luminaires. The high-quality CoreLine SlimDownlight is designed to
replace existing downlight luminaires with CFL-ni/CFL-l lamp technology and
provides even, natural lighting across multiple environments.
With instant energy savings and a longer lifetime, this is an environmentally
friendly and cost saving solution. Simple and easy installation means our
recessed luminaire fits the same size cut-out, while the minimal built-in depth
of 34mm makes this product an ideal space saving solution, especially for
projects with limited fitting space.
InterAct Ready luminaires with integrated wireless communications, fully
compatible with InterAct gateways, sensors and software, are also available.

Page 8
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Washrooms / Summary

Height of Room: 2.743 m, Light loss factor: 0.80 Values in Lux, Scale 1:100

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 195 94 253 0.484
Floor 20 170 93 212 0.547
Ceiling 80 48 33 94 0.688
Walls (4) 50 120 45 400 /

Workplane:
Height: 0.760 m
Grid: 128 x 128 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.647, Ceiling / Working Plane: 0.243.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
PHILIPS DN135B D165 1xLED10S/830
1 14 1000 1000 13.0
(1.000)
Total: 14000 Total: 14000 182.0

Specific connected load: 3.92 W/m² = 2.01 W/m²/100 lx (Ground area: 46.45 m²)

Page 9
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Washrooms / Luminaire parts list

14 Pieces PHILIPS DN135B D165 1xLED10S/830


Article No.:
Luminous flux (Luminaire): 1000 lm
Luminous flux (Lamps): 1000 lm
Luminaire Wattage: 13.0 W
Luminaire classification according to CIE: 100
CIE flux code: 46 78 95 100 100
Fitting: 1 x LED10S/830/- (Correction Factor
1.000).

Page 10
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Washrooms / Luminaires (layout plan)

Scale 1 : 53

Luminaire Parts List

No. Pieces Designation


1 14 PHILIPS DN135B D165 1xLED10S/830

Page 11
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Washrooms / Photometric Results

Total Luminous Flux: 14000 lm


Total Load: 182.0 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 147 48 195 / /
Floor 122 48 170 20 11
Ceiling 0.01 48 48 80 12
Wall 1 70 47 117 50 19
Wall 2 94 49 142 50 23
Wall 3 73 47 119 50 19
Wall 4 57 43 100 50 16

Uniformity on the working plane


u0: 0.484 (1:2)
Emin / Emax: 0.374 (1:3)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.647, Ceiling / Working Plane: 0.243.
Specific connected load: 3.92 W/m² = 2.01 W/m²/100 lx (Ground area: 46.45 m²)

Page 12
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Washrooms / Workplane / Value Chart (E)

Values in Lux, Scale 1 : 61


Not all calculated values could be displayed.
Position of surface in room:
Marked point:
(9.926 m, -6.774 m, 0.760 m)

Grid: 128 x 128 Points


Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax
195 94 253 0.484 0.374

Page 13
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Office R1 / Summary

Height of Room: 2.743 m, Mounting Height: 2.743 m, Light loss factor: Values in Lux, Scale 1:100
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 357 200 465 0.559
Floor 20 315 186 389 0.592
Ceiling 80 78 62 90 0.789
Walls (4) 50 194 78 311 /

Workplane:
Height: 0.760 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.545, Ceiling / Working Plane: 0.220.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
PHILIPS RC125B W60L60 1 xLED34S/830
1 9 3400 3400 36.0
NOC (1.000)
Total: 30600 Total: 30600 324.0

Specific connected load: 5.35 W/m² = 1.50 W/m²/100 lx (Ground area: 60.54 m²)

Page 14
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Office R1 / Luminaire parts list

9 Pieces PHILIPS RC125B W60L60 1 xLED34S/830 NOC


Article No.:
Luminous flux (Luminaire): 3400 lm
Luminous flux (Lamps): 3400 lm
Luminaire Wattage: 36.0 W
Luminaire classification according to CIE: 100
CIE flux code: 46 78 95 100 100
Fitting: 1 x LED34S/830/- (Correction Factor
1.000).

Page 15
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Office R1 / Luminaires (layout plan)

Scale 1 : 56

Luminaire Parts List

No. Pieces Designation


1 9 PHILIPS RC125B W60L60 1 xLED34S/830 NOC

Page 16
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Office R1 / Photometric Results

Total Luminous Flux: 30600 lm


Total Load: 324.0 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 280 77 357 / /
Floor 235 80 315 20 20
Ceiling 0.24 78 78 80 20
Wall 1 128 75 203 50 32
Wall 2 111 74 184 50 29
Wall 3 128 72 200 50 32
Wall 4 111 77 188 50 30

Uniformity on the working plane


u0: 0.559 (1:2)
Emin / Emax: 0.430 (1:2)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.545, Ceiling / Working Plane: 0.220.
Specific connected load: 5.35 W/m² = 1.50 W/m²/100 lx (Ground area: 60.54 m²)

Page 17
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Office R1 / Workplane / Value Chart (E)

Values in Lux, Scale 1 : 61


Not all calculated values could be displayed.
Position of surface in room:
Marked point:
(-2.287 m, -6.787 m, 0.760 m)

Grid: 64 x 64 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax
357 200 465 0.559 0.430

Page 18
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Office R2 / Summary

Height of Room: 2.743 m, Mounting Height: 2.743 m, Light loss factor: Values in Lux, Scale 1:100
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 353 208 446 0.589
Floor 20 299 192 367 0.640
Ceiling 80 82 61 91 0.741
Walls (4) 50 200 75 347 /

Workplane:
Height: 0.760 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.580, Ceiling / Working Plane: 0.231.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
PHILIPS RC125B W60L60 1 xLED34S/830
1 6 3400 3400 36.0
NOC (1.000)
Total: 20400 Total: 20400 216.0

Specific connected load: 5.81 W/m² = 1.65 W/m²/100 lx (Ground area: 37.19 m²)

Page 19
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Office R2 / Luminaire parts list

6 Pieces PHILIPS RC125B W60L60 1 xLED34S/830 NOC


Article No.:
Luminous flux (Luminaire): 3400 lm
Luminous flux (Lamps): 3400 lm
Luminaire Wattage: 36.0 W
Luminaire classification according to CIE: 100
CIE flux code: 46 78 95 100 100
Fitting: 1 x LED34S/830/- (Correction Factor
1.000).

Page 20
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Office R2 / Luminaires (layout plan)

Scale 1 : 53

Luminaire Parts List

No. Pieces Designation


1 6 PHILIPS RC125B W60L60 1 xLED34S/830 NOC

Page 21
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Office R2 / Photometric Results

Total Luminous Flux: 20400 lm


Total Load: 216.0 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 269 84 353 / /
Floor 214 85 299 20 19
Ceiling 0.25 81 82 80 21
Wall 1 106 80 185 50 29
Wall 2 130 76 207 50 33
Wall 3 105 80 185 50 30
Wall 4 131 80 211 50 34

Uniformity on the working plane


u0: 0.589 (1:2)
Emin / Emax: 0.466 (1:2)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.580, Ceiling / Working Plane: 0.231.
Specific connected load: 5.81 W/m² = 1.65 W/m²/100 lx (Ground area: 37.19 m²)

Page 22
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Office R2 / Workplane / Value Chart (E)

Values in Lux, Scale 1 : 61


Not all calculated values could be displayed.
Position of surface in room:
Marked point:
(-10.287 m, -6.787 m, 0.760 m)

Grid: 64 x 64 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax
353 208 446 0.589 0.466

Page 23
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Entrance Gate / Summary

Height of Room: 2.743 m, Mounting Height: 2.786 m, Light loss factor: Values in Lux, Scale 1:79
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 204 113 253 0.554
Floor 20 157 99 188 0.633
Ceiling 80 62 38 88 0.608
Walls (4) 50 131 49 369 /

Workplane:
Height: 0.760 m
Grid: 32 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.720, Ceiling / Working Plane: 0.305.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
PHILIPS DN135B D165 1xLED10S/830
1 6 1000 1000 13.0
(1.000)
Total: 6000 Total: 6000 78.0

Specific connected load: 5.94 W/m² = 2.92 W/m²/100 lx (Ground area: 13.14 m²)

Page 24
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Entrance Gate / Luminaire parts list

6 Pieces PHILIPS DN135B D165 1xLED10S/830


Article No.:
Luminous flux (Luminaire): 1000 lm
Luminous flux (Lamps): 1000 lm
Luminaire Wattage: 13.0 W
Luminaire classification according to CIE: 100
CIE flux code: 46 78 95 100 100
Fitting: 1 x LED10S/830/- (Correction Factor
1.000).

Page 25
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Entrance Gate / Luminaires (layout plan)

Scale 1 : 42

Luminaire Parts List

No. Pieces Designation


1 6 PHILIPS DN135B D165 1xLED10S/830

Page 26
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Entrance Gate / Photometric Results

Total Luminous Flux: 6000 lm


Total Load: 78.0 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 140 63 204 / /
Floor 101 56 157 20 9.97
Ceiling 0.00 62 62 80 16
Wall 1 53 49 103 50 16
Wall 2 81 55 136 50 22
Wall 3 74 56 130 50 21
Wall 4 81 55 136 50 22

Uniformity on the working plane


u0: 0.554 (1:2)
Emin / Emax: 0.447 (1:2)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.720, Ceiling / Working Plane: 0.305.
Specific connected load: 5.94 W/m² = 2.92 W/m²/100 lx (Ground area: 13.14 m²)

Page 27
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Entrance Gate / Workplane / Value Chart (E)

Values in Lux, Scale 1 : 49


Not all calculated values could be displayed.
Position of surface in room:
Marked point:
(-15.687 m, -15.787 m, 0.760 m)

Grid: 32 x 64 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax
204 113 253 0.554 0.447

Page 28
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Cafeteria / Summary

Height of Room: 2.743 m, Mounting Height: 2.769 m, Light loss factor: Values in Lux, Scale 1:98
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 177 94 229 0.531
Floor 20 148 88 186 0.597
Ceiling 80 45 32 66 0.720
Walls (4) 50 107 39 252 /

Workplane:
Height: 0.760 m
Grid: 128 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.642, Ceiling / Working Plane: 0.252.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
PHILIPS DN135B D165 1xLED10S/830
1 9 1000 1000 13.0
(1.000)
Total: 9000 Total: 9000 117.0

Specific connected load: 3.89 W/m² = 2.20 W/m²/100 lx (Ground area: 30.08 m²)

Page 29
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Cafeteria / Luminaire parts list

9 Pieces PHILIPS DN135B D165 1xLED10S/830


Article No.:
Luminous flux (Luminaire): 1000 lm
Luminous flux (Lamps): 1000 lm
Luminaire Wattage: 13.0 W
Luminaire classification according to CIE: 100
CIE flux code: 46 78 95 100 100
Fitting: 1 x LED10S/830/- (Correction Factor
1.000).

Page 30
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Cafeteria / Luminaires (layout plan)

Scale 1 : 52

Luminaire Parts List

No. Pieces Designation


1 9 PHILIPS DN135B D165 1xLED10S/830

Page 31
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Cafeteria / Photometric Results

Total Luminous Flux: 9000 lm


Total Load: 117.0 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 131 46 177 / /
Floor 103 45 148 20 9.43
Ceiling 0.01 45 45 80 11
Wall 1 49 39 88 50 14
Wall 2 68 42 110 50 17
Wall 3 71 44 116 50 18
Wall 4 67 42 109 50 17

Uniformity on the working plane


u0: 0.531 (1:2)
Emin / Emax: 0.410 (1:2)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.642, Ceiling / Working Plane: 0.252.
Specific connected load: 3.89 W/m² = 2.20 W/m²/100 lx (Ground area: 30.08 m²)

Page 32
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Cafeteria / Workplane / Value Chart (E)

Values in Lux, Scale 1 : 60


Not all calculated values could be displayed.
Position of surface in room:
Marked point:
(5.726 m, -6.774 m, 0.760 m)

Grid: 128 x 64 Points


Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax
177 94 229 0.531 0.410

Page 33
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Corridor 1 / Summary

Height of Room: 2.743 m, Mounting Height: 2.769 m, Light loss factor: Values in Lux, Scale 1:126
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 235 136 292 0.578
Floor 20 192 120 235 0.626
Ceiling 80 64 50 88 0.789
Walls (4) 50 147 63 272 /

Workplane:
Height: 0.760 m
Grid: 128 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.681, Ceiling / Working Plane: 0.271.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
PHILIPS DN135B D165 1xLED10S/830
1 12 1000 1000 13.0
(1.000)
Total: 12000 Total: 12000 156.0

Specific connected load: 5.69 W/m² = 2.42 W/m²/100 lx (Ground area: 27.39 m²)

Page 34
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Corridor 1 / Luminaire parts list

12 Pieces PHILIPS DN135B D165 1xLED10S/830


Article No.:
Luminous flux (Luminaire): 1000 lm
Luminous flux (Lamps): 1000 lm
Luminaire Wattage: 13.0 W
Luminaire classification according to CIE: 100
CIE flux code: 46 78 95 100 100
Fitting: 1 x LED10S/830/- (Correction Factor
1.000).

Page 35
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Corridor 1 / Luminaires (layout plan)

Scale 1 : 67

Luminaire Parts List

No. Pieces Designation


1 12 PHILIPS DN135B D165 1xLED10S/830

Page 36
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Corridor 1 / Photometric Results

Total Luminous Flux: 12000 lm


Total Load: 156.0 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 169 67 235 / /
Floor 129 63 192 20 12
Ceiling 0.01 64 64 80 16
Wall 1 73 56 129 50 21
Wall 2 89 59 148 50 23
Wall 3 90 61 151 50 24
Wall 4 90 61 151 50 24

Uniformity on the working plane


u0: 0.578 (1:2)
Emin / Emax: 0.466 (1:2)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.681, Ceiling / Working Plane: 0.271.
Specific connected load: 5.69 W/m² = 2.42 W/m²/100 lx (Ground area: 27.39 m²)

Page 37
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Corridor 1 / Workplane / Value Chart (E)

Values in Lux, Scale 1 : 77


Not all calculated values could be displayed.
Position of surface in room:
Marked point:
(-5.274 m, -6.774 m, 0.760 m)

Grid: 128 x 64 Points


Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax
235 136 292 0.578 0.466

Page 38
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

GM Office / Summary

Height of Room: 2.743 m, Mounting Height: 2.743 m, Light loss factor: Values in Lux, Scale 1:103
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 394 47 807 0.121
Floor 20 329 59 616 0.180
Ceiling 80 100 30 195 0.298
Walls (4) 50 238 39 993 /

Workplane:
Height: 0.760 m
Grid: 32 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.641, Ceiling / Working Plane: 0.253.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
PHILIPS RC125B W60L60 1 xLED34S/830
1 6 3400 3400 36.0
NOC (1.000)
Total: 20400 Total: 20400 216.0

Specific connected load: 7.12 W/m² = 1.81 W/m²/100 lx (Ground area: 30.35 m²)

Page 39
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

GM Office / Luminaire parts list

6 Pieces PHILIPS RC125B W60L60 1 xLED34S/830 NOC


Article No.:
Luminous flux (Luminaire): 3400 lm
Luminous flux (Lamps): 3400 lm
Luminaire Wattage: 36.0 W
Luminaire classification according to CIE: 100
CIE flux code: 46 78 95 100 100
Fitting: 1 x LED34S/830/- (Correction Factor
1.000).

Page 40
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

GM Office / Luminaires (layout plan)

Scale 1 : 55

Luminaire Parts List

No. Pieces Designation


1 6 PHILIPS RC125B W60L60 1 xLED34S/830 NOC

Page 41
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

GM Office / Photometric Results

Total Luminous Flux: 20400 lm


Total Load: 216.0 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 290 104 394 / /
Floor 228 102 329 20 21
Ceiling 0.29 99 100 80 25
Wall 1 19 50 69 50 11
Wall 2 156 92 248 50 39
Wall 3 224 139 363 50 58
Wall 4 157 91 248 50 39

Uniformity on the working plane


u0: 0.121 (1:8)
Emin / Emax: 0.059 (1:17)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.641, Ceiling / Working Plane: 0.253.
Specific connected load: 7.12 W/m² = 1.81 W/m²/100 lx (Ground area: 30.35 m²)

Page 42
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

GM Office / Workplane / Value Chart (E)

Values in Lux, Scale 1 : 63


Not all calculated values could be displayed.
Position of surface in room:
Marked point:
(-14.287 m, -6.774 m, 0.760 m)

Grid: 32 x 64 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax
394 47 807 0.121 0.059

Page 43
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Corridor 2 / Summary

Height of Room: 2.743 m, Mounting Height: 2.769 m, Light loss factor: Values in Lux, Scale 1:201
0.80
Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 152 86 189 0.568
Floor 20 127 80 145 0.625
Ceiling 80 39 29 65 0.754
Walls (4) 50 92 25 271 /

Workplane:
Height: 0.760 m
Grid: 128 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.653, Ceiling / Working Plane: 0.255.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
PHILIPS DN135B D165 1xLED10S/830
1 20 1000 1000 13.0
(1.000)
Total: 20000 Total: 20000 260.0

Specific connected load: 3.44 W/m² = 2.26 W/m²/100 lx (Ground area: 75.56 m²)

Page 44
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Corridor 2 / Luminaire parts list

20 Pieces PHILIPS DN135B D165 1xLED10S/830


Article No.:
Luminous flux (Luminaire): 1000 lm
Luminous flux (Lamps): 1000 lm
Luminaire Wattage: 13.0 W
Luminaire classification according to CIE: 100
CIE flux code: 46 78 95 100 100
Fitting: 1 x LED10S/830/- (Correction Factor
1.000).

Page 45
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Corridor 2 / Luminaires (layout plan)

Scale 1 : 201

Luminaire Parts List

No. Pieces Designation


1 20 PHILIPS DN135B D165 1xLED10S/830

Page 46
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Corridor 2 / Photometric Results

Total Luminous Flux: 20000 lm


Total Load: 260.0 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 112 40 152 / /
Floor 88 39 127 20 8.10
Ceiling 0.01 39 39 80 9.89
Wall 1 58 38 96 50 15
Wall 2 43 31 74 50 12
Wall 3 55 36 92 50 15
Wall 4 45 35 81 50 13

Uniformity on the working plane


u0: 0.568 (1:2)
Emin / Emax: 0.457 (1:2)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.653, Ceiling / Working Plane: 0.255.
Specific connected load: 3.44 W/m² = 2.26 W/m²/100 lx (Ground area: 75.56 m²)

Page 47
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Corridor 2 / Workplane / Value Chart (E)

Values in Lux, Scale 1 : 201


Not all calculated values could be displayed.
Position of surface in room:
Marked point:
(-10.724 m, -9.374 m, 0.760 m)

Grid: 128 x 32 Points


Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax
152 86 189 0.568 0.457

Page 48
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Conference Room / Summary

Height of Room: 2.743 m, Light loss factor: 0.80 Values in Lux, Scale 1:83

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 378 227 469 0.600
Floor 20 320 207 391 0.647
Ceiling 80 87 64 105 0.730
Walls (4) 50 212 84 322 /

Workplane:
Height: 0.760 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.575, Ceiling / Working Plane: 0.231.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
PHILIPS RC125B W60L60 1 xLED34S/830
1 6 3400 3400 36.0
NOC (1.000)
Total: 20400 Total: 20400 216.0

Specific connected load: 6.24 W/m² = 1.65 W/m²/100 lx (Ground area: 34.64 m²)

Page 49
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Conference Room / Luminaire parts list

6 Pieces PHILIPS RC125B W60L60 1 xLED34S/830 NOC


Article No.:
Luminous flux (Luminaire): 3400 lm
Luminous flux (Lamps): 3400 lm
Luminaire Wattage: 36.0 W
Luminaire classification according to CIE: 100
CIE flux code: 46 78 95 100 100
Fitting: 1 x LED34S/830/- (Correction Factor
1.000).

Page 50
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Conference Room / Luminaires (layout plan)

Scale 1 : 44

Luminaire Parts List

No. Pieces Designation


1 6 PHILIPS RC125B W60L60 1 xLED34S/830 NOC

Page 51
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Conference Room / Photometric Results

Total Luminous Flux: 20400 lm


Total Load: 216.0 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 289 89 378 / /
Floor 230 91 320 20 20
Ceiling 0.28 87 87 80 22
Wall 1 122 83 205 50 33
Wall 2 135 85 220 50 35
Wall 3 122 83 205 50 33
Wall 4 134 82 216 50 34

Uniformity on the working plane


u0: 0.600 (1:2)
Emin / Emax: 0.483 (1:2)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.575, Ceiling / Working Plane: 0.231.
Specific connected load: 6.24 W/m² = 1.65 W/m²/100 lx (Ground area: 34.64 m²)

Page 52
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Conference Room / Workplane / Value Chart (E)

Values in Lux, Scale 1 : 51


Not all calculated values could be displayed.
Position of surface in room:
Marked point:
(9.713 m, -15.787 m, 0.760 m)

Grid: 64 x 64 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax
378 227 469 0.600 0.483

Page 53
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Deputy Manager / Summary

Height of Room: 2.743 m, Mounting Height: 2.786 m, Light loss factor: Values in Lux, Scale 1:62
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 409 260 499 0.635
Floor 20 329 229 390 0.696
Ceiling 80 106 77 120 0.725
Walls (4) 50 247 107 494 /

Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.642, Ceiling / Working Plane: 0.258.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
PHILIPS RC125B W60L60 1 xLED34S/830
1 4 3400 3400 36.0
NOC (1.000)
Total: 13600 Total: 13600 144.0

Specific connected load: 7.98 W/m² = 1.95 W/m²/100 lx (Ground area: 18.04 m²)

Page 54
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Deputy Manager / Luminaire parts list

4 Pieces PHILIPS RC125B W60L60 1 xLED34S/830 NOC


Article No.:
Luminous flux (Luminaire): 3400 lm
Luminous flux (Lamps): 3400 lm
Luminaire Wattage: 36.0 W
Luminaire classification according to CIE: 100
CIE flux code: 46 78 95 100 100
Fitting: 1 x LED34S/830/- (Correction Factor
1.000).

Page 55
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Deputy Manager / Luminaires (layout plan)

Scale 1 : 33

Luminaire Parts List

No. Pieces Designation


1 4 PHILIPS RC125B W60L60 1 xLED34S/830 NOC

Page 56
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Deputy Manager / Photometric Results

Total Luminous Flux: 13600 lm


Total Load: 144.0 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 297 112 409 / /
Floor 220 108 329 20 21
Ceiling 0.36 105 106 80 27
Wall 1 128 99 228 50 36
Wall 2 161 97 258 50 41
Wall 3 129 103 232 50 37
Wall 4 161 99 261 50 41

Uniformity on the working plane


u0: 0.635 (1:2)
Emin / Emax: 0.521 (1:2)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.642, Ceiling / Working Plane: 0.258.
Specific connected load: 7.98 W/m² = 1.95 W/m²/100 lx (Ground area: 18.04 m²)

Page 57
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Deputy Manager / Workplane / Value Chart (E)

Values in Lux, Scale 1 : 38


Not all calculated values could be displayed.
Position of surface in room:
Marked point:
(1.726 m, -14.374 m, 0.760 m)

Grid: 32 x 32 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax
409 260 499 0.635 0.521

Page 58
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Project Manager / Summary

Height of Room: 2.743 m, Mounting Height: 2.786 m, Light loss factor: Values in Lux, Scale 1:62
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 260 161 332 0.620
Floor 20 199 140 235 0.703
Ceiling 80 66 47 78 0.701
Walls (4) 50 152 63 249 /

Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.625, Ceiling / Working Plane: 0.256.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
PHILIPS RC125B W60L60 1 xLED34S/830
1 2 3400 3400 36.0
NOC (1.000)
Total: 6800 Total: 6800 72.0

Specific connected load: 5.42 W/m² = 2.09 W/m²/100 lx (Ground area: 13.29 m²)

Page 59
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Project Manager / Luminaire parts list

2 Pieces PHILIPS RC125B W60L60 1 xLED34S/830 NOC


Article No.:
Luminous flux (Luminaire): 3400 lm
Luminous flux (Lamps): 3400 lm
Luminaire Wattage: 36.0 W
Luminaire classification according to CIE: 100
CIE flux code: 46 78 95 100 100
Fitting: 1 x LED34S/830/- (Correction Factor
1.000).

Page 60
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Project Manager / Luminaires (layout plan)

Scale 1 : 33

Luminaire Parts List

No. Pieces Designation


1 2 PHILIPS RC125B W60L60 1 xLED34S/830 NOC

Page 61
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Project Manager / Photometric Results

Total Luminous Flux: 6800 lm


Total Load: 72.0 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 187 73 260 / /
Floor 130 69 199 20 13
Ceiling 0.26 66 66 80 17
Wall 1 82 65 147 50 23
Wall 2 93 62 156 50 25
Wall 3 82 63 145 50 23
Wall 4 94 63 157 50 25

Uniformity on the working plane


u0: 0.620 (1:2)
Emin / Emax: 0.484 (1:2)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.625, Ceiling / Working Plane: 0.256.
Specific connected load: 5.42 W/m² = 2.09 W/m²/100 lx (Ground area: 13.29 m²)

Page 62
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Project Manager / Workplane / Value Chart (E)

Values in Lux, Scale 1 : 38


Not all calculated values could be displayed.
Position of surface in room:
Marked point:
(-1.287 m, -14.387 m, 0.760 m)

Grid: 32 x 32 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax
260 161 332 0.620 0.484

Page 63
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Entrance Area / Summary

Height of Room: 2.743 m, Mounting Height: 2.786 m, Light loss factor: Values in Lux, Scale 1:77
0.80

Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 434 271 528 0.626
Floor 20 362 245 442 0.677
Ceiling 80 104 80 125 0.763
Walls (4) 50 251 106 387 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.760 m Left Wall 20 19
Grid: 32 x 32 Points Lower Wall 21 19
Boundary Zone: 0.000 m (CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.606, Ceiling / Working Plane: 0.241.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
PHILIPS RC125B W60L60 1 xLED34S/830
1 6 3400 3400 36.0
NOC (1.000)
Total: 20400 Total: 20400 216.0

Specific connected load: 7.59 W/m² = 1.75 W/m²/100 lx (Ground area: 28.45 m²)

Page 64
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Entrance Area / Luminaire parts list

6 Pieces PHILIPS RC125B W60L60 1 xLED34S/830 NOC


Article No.:
Luminous flux (Luminaire): 3400 lm
Luminous flux (Lamps): 3400 lm
Luminaire Wattage: 36.0 W
Luminaire classification according to CIE: 100
CIE flux code: 46 78 95 100 100
Fitting: 1 x LED34S/830/- (Correction Factor
1.000).

Page 65
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Entrance Area / Luminaires (layout plan)

Scale 1 : 41

Luminaire Parts List

No. Pieces Designation


1 6 PHILIPS RC125B W60L60 1 xLED34S/830 NOC

Page 66
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Entrance Area / Photometric Results

Total Luminous Flux: 20400 lm


Total Load: 216.0 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 325 108 434 / /
Floor 254 108 362 20 23
Ceiling 0.38 104 104 80 27
Wall 1 144 98 242 50 38
Wall 2 162 97 259 50 41
Wall 3 144 98 242 50 38
Wall 4 162 97 259 50 41

Uniformity on the working plane UGR Lengthways- Across to luminaire axis


u0: 0.626 (1:2) Left Wall 20 19
Emin / Emax: 0.514 (1:2) Lower Wall 21 19
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.606, Ceiling / Working Plane: 0.241.

Specific connected load: 7.59 W/m² = 1.75 W/m²/100 lx (Ground area: 28.45 m²)

Page 67
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Entrance Area / Workplane / Value Chart (E)

Values in Lux, Scale 1 : 47


Not all calculated values could be displayed.
Position of surface in room:
Marked point:
(-13.274 m, -15.560 m, 0.760 m)

Grid: 32 x 32 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax
434 271 528 0.626 0.514

Page 68
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Front Shell / Summary

Height of Room: 2.743 m, Mounting Height: 2.798 m, Light loss factor: Values in Lux, Scale 1:132
0.80
Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 102 6.57 276 0.064
Floor 20 93 16 210 0.175
Ceiling 80 15 5.59 28 0.363
Walls (10) 50 26 5.20 147 /

Workplane:
Height: 0.760 m
Grid: 128 x 128 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.241, Ceiling / Working Plane: 0.150.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
1 16 PHILIPS RS060B 1xLED5-36-/840 (1.000) 500 500 6.0
Total: 8000 Total: 8000 96.0

Specific connected load: 1.64 W/m² = 1.61 W/m²/100 lx (Ground area: 58.39 m²)

Page 69
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Front Shell / Luminaire parts list

16 Pieces PHILIPS RS060B 1xLED5-36-/840


Article No.:
Luminous flux (Luminaire): 500 lm
Luminous flux (Lamps): 500 lm
Luminaire Wattage: 6.0 W
Luminaire classification according to CIE: 100
CIE flux code: 93 98 99 100 100
Fitting: 1 x LED5-36-/840 (Correction Factor
1.000).

Page 70
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Front Shell / Luminaires (layout plan)

Scale 1 : 132

Luminaire Parts List

No. Pieces Designation


1 16 PHILIPS RS060B 1xLED5-36-/840

Page 71
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Front Shell / Photometric Results

Total Luminous Flux: 8000 lm


Total Load: 96.0 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 89 13 102 / /
Floor 79 14 93 20 5.94
Ceiling 0.00 15 15 80 3.93
Wall 1 30 24 55 50 8.72
Wall 2 15 22 37 50 5.92
Wall 3 6.32 9.06 15 50 2.45
Wall 4 2.59 6.53 9.12 50 1.45
Wall 5 7.01 6.60 14 50 2.17
Wall 6 11 7.84 19 50 3.02
Wall 7 8.18 8.52 17 50 2.66
Wall 8 11 15 26 50 4.08
Wall 9 11 19 30 50 4.82
Wall 10 21 20 41 50 6.58

Uniformity on the working plane


u0: 0.064 (1:16)
Emin / Emax: 0.024 (1:42)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.241, Ceiling / Working Plane: 0.150.
Specific connected load: 1.64 W/m² = 1.61 W/m²/100 lx (Ground area: 58.39 m²)

Page 72
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Front Shell / Workplane / Value Chart (E)

Values in Lux, Scale 1 : 132


Not all calculated values could be displayed.
Position of surface in room:
Marked point:
(9.650 m, -9.600 m, 0.760 m)

Grid: 128 x 128 Points


Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax
102 6.57 276 0.064 0.024

Page 73
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Back Shell / Summary

Height of Room: 2.743 m, Mounting Height: 2.786 m, Light loss factor: Values in Lux, Scale 1:101
0.80
Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 78 8.74 191 0.112
Floor 20 64 20 106 0.317
Ceiling 80 10 6.31 16 0.607
Walls (8) 50 23 6.24 152 /

Workplane:
Height: 0.760 m
Grid: 128 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.296, Ceiling / Working Plane: 0.134.

Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
1 5 PHILIPS RS060B 1xLED5-36-/840 (1.000) 500 500 6.0
Total: 2500 Total: 2500 30.0

Specific connected load: 1.58 W/m² = 2.02 W/m²/100 lx (Ground area: 18.97 m²)

Page 74
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Back Shell / Luminaire parts list

5 Pieces PHILIPS RS060B 1xLED5-36-/840


Article No.:
Luminous flux (Luminaire): 500 lm
Luminous flux (Lamps): 500 lm
Luminaire Wattage: 6.0 W
Luminaire classification according to CIE: 100
CIE flux code: 93 98 99 100 100
Fitting: 1 x LED5-36-/840 (Correction Factor
1.000).

Page 75
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Back Shell / Luminaires (layout plan)

Scale 1 : 101

Luminaire Parts List

No. Pieces Designation


1 5 PHILIPS RS060B 1xLED5-36-/840

Page 76
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Back Shell / Photometric Results

Total Luminous Flux: 2500 lm


Total Load: 30.0 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 67 11 78 / /
Floor 52 11 64 20 4.05
Ceiling 0.00 10 10 80 2.65
Wall 1 4.53 8.40 13 50 2.06
Wall 2 4.86 9.23 14 50 2.24
Wall 3 9.13 12 21 50 3.33
Wall 4 12 13 25 50 3.93
Wall 5 15 14 29 50 4.57
Wall 6 16 14 30 50 4.71
Wall 7 5.73 12 18 50 2.82
Wall 8 14 12 25 50 4.04

Uniformity on the working plane


u0: 0.112 (1:9)
Emin / Emax: 0.046 (1:22)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.296, Ceiling / Working Plane: 0.134.
Specific connected load: 1.58 W/m² = 2.02 W/m²/100 lx (Ground area: 18.97 m²)

Page 77
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Back Shell / Workplane / Value Chart (E)

Values in Lux, Scale 1 : 101


Not all calculated values could be displayed.
Position of surface in room:
Marked point:
(3.163 m, 1.276 m, 0.760 m)

Grid: 128 x 64 Points


Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax
78 8.74 191 0.112 0.046

Page 78
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Reception / Summary

Height of Room: 2.743 m, Mounting Height: 2.786 m, Light loss factor: Values in Lux, Scale 1:33
0.80
Surface  [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 290 189 356 0.652
Floor 20 217 154 252 0.712
Ceiling 80 80 58 100 0.728
Walls (4) 50 179 78 326 /

Workplane:
Height: 0.760 m
Grid: 32 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.673, Ceiling / Working Plane: 0.277.
Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
PHILIPS RC125B W60L60 1 xLED34S/830
1 2 3400 3400 36.0
NOC (1.000)
Total: 6800 Total: 6800 72.0

Specific connected load: 6.63 W/m² = 2.29 W/m²/100 lx (Ground area: 10.86 m²)

Page 79
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Reception / Luminaire parts list

2 Pieces PHILIPS RC125B W60L60 1 xLED34S/830 NOC


Article No.:
Luminous flux (Luminaire): 3400 lm
Luminous flux (Lamps): 3400 lm
Luminaire Wattage: 36.0 W
Luminaire classification according to CIE: 100
CIE flux code: 46 78 95 100 100
Fitting: 1 x LED34S/830/- (Correction Factor
1.000).

Page 80
Plan Floor Lighting Design
10.01.2020

National Engineering Services Pakistan (PVT) LTD Operator


Telephone
Fax
e-Mail

Reception / Photometric Results

Total Luminous Flux: 6800 lm


Total Load: 72.0 W
Light loss factor: 0.80
Boundary Zone: 0.000 m

Surface Average illuminances [lx] Reflection factor [%] Average luminance [cd/m²]
direct indirect total
Workplane 202 87 290 / /
Floor 138 79 217 20 14
Ceiling 0.33 80 80 80 20
Wall 1 110 77 187 50 30
Wall 2 93 74 167 50 27
Wall 3 109 74 183 50 29
Wall 4 92 74 166 50 26

Uniformity on the working plane


u0: 0.652 (1:2)
Emin / Emax: 0.530 (1:2)

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.673, Ceiling / Working Plane: 0.277.
Specific connected load: 6.63 W/m² = 2.29 W/m²/100 lx (Ground area: 10.86 m²)

Page 81