2. Facilities Planning and
Programming
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-1
California State University
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-2
California State University
and terminal resources (network electronics). One of the most costly parts of
that process is the renovation of pathways and spaces within and between
buildings that is often required before any new media can be installed.
Frequently, the principal reason for the high costs of renovations is that the
Facilities designed to designs for the original structures supported specific systems and
support a single applications, and were not a response to an overall media or cabling plan.
technology solution, no Under such circumstances, rooms, connection points, and pathways to user
matter how locations were probably designed to meet very specific needs, with little
technologically allowance for future growth or technologic change. In the contemporary
advanced, will telecommunications world, growth and change are constant occurrences, and
dramatically limit the provision for them must be an integral part of any facility design concept.
university’s ability to
provide for future needs
Flexibility is a primary characteristic that must be incorporated into the
and applications.
design of any CSU campus facility. Due to rapid technology changes, the
normal design cycle of a capital project covers at least two generations of
network systems. This circumstance results in an obvious inability to
recognize and incorporate specific equipment models during the initial design
process for a new building.
Flexibility is key to the In the last decade, standards have been developed that lead the designer to
support of technology improved infrastructure solutions. The American National Standards Institute
in the long-term use of (ANSI), the Telecommunications Industry Association (TIA), and the Electronics
a facility. Industry Association (EIA) are the major providers of published
telecommunications-related standards.
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-3
California State University
a. General Requirements
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-4
California State University
10. BICSI - Wireless Design Reference Manual, 2nd Edition. This revised
manual incorporates current information required for planning, designing
and implementing a wide array of wireless design projects.
1
This series of RUS Bulletins replaces all former Rural Electrification Association (REA) materials such as
PE-89 and PE-39.
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-5
California State University
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-6
California State University
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-7
California State University
Telecommunications
Rooms
(each floor)
Equipment
Room
Telecommunications
Utility Vault
Figure 2-1
Intrabuilding Design Elements
Building designs that require the cable installer to drill holes in walls and
place sleeves through fire partitions after their construction should be
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-8
California State University
avoided. While technology will certainly change between the time of the initial
architectural planning and building occupancy, the infrastructure (pathways
and spaces) will be in place for the life of the building and must be capable of
supporting multiple changes in technology without frequent modification.
Back Feed
Backbone
Communication Vault
Dual Entrance
Backbone
Figure 2-2
Interbuilding Design Elements
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-9
California State University
All telecommunication In working with private industry on a recent project attempting to rationalize
and categorize the diverse parameters involved in telecommunications service
spaces will have specific
space planning, CSU personnel were introduced to the concept of criticality,
requirements for the
which is an attempt to take into consideration the relative “importance” of the
following:
activities supported by a particular space. Power consumption, device
• Floor & wall space dimensions, voltages required, and other basic characteristics of the space’s
• Heating & air physical contents are generally not difficult to assess, and determining the
handling requirements needed to respond to those characteristics is comparatively
• Electrical and straightforward. Support for criticality, on the other hand, involves value
grounding judgments about needs for power and cooling redundancy, reserve cooling
• Access (media & capacity, monitoring strategies, robustness of physical security, and fire
personnel)
protection. For this reason, criticality can be a useful way to categorize
• Floor loading standard room “types.” The subjective decisions regarding criticality support
• Room location can then be made in a general context, and standardized in a table of
recommendations by space type. An example of this approach is offered later
in this TIPS section, as applied to telecommunications room (TR) planning.
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-10
California State University
If used only as a service entrance room in the strict sense, such a space
requires no special air handling provisions unless unusual environmental
conditions exist. Service entries normally should not be located in or directly
adjacent to the building’s electrical service entrance, transformer room, or
mechanical room, although such limitations should be evaluated by the
designer to assure their actual applicability. If exceptions seem necessary, a
mitigating technology (e.g., UPS or other electrical noise filtering) may be
employed.
The equipment room will house sensitive electronic components that will
often be connected to a backup power source and will generate heat 24 hours
a day, 365 days a year. It is important this space be designed with necessary
environmental controls and backup systems to maintain the conditions
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-11
California State University
The air handling system for equipment rooms must be designed to provide
positive airflow and cooling even during times when the main building
systems are shut down. This requires separate stand-alone cooling systems
or separate temperature control zones. If the equipment room is to be used
as a campus communications hub and the equipment is served by an auxiliary
power supply, the air handling system for this space should also be connected
to the building’s backup power generation system if one exists.
The equipment room must be located near the service entrance room and
must have adequate access from outside the building to allow for the
installation of large equipment cabinets (36” wide by 96” tall). However, every
effort must be exerted to avoid locations in basements or at other low levels
where there exists any possibility of flooding. The minimum size of this room
is ten (10) feet by fifteen (15) feet. However, campus-specific requirements
may easily increase its size.
3. The room must be open from floor to true ceiling. No false ceiling should
be installed.
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-12
California State University
4. A floor loading of 100 lbs. per square foot (distributed loading) must be
the minimum structural design standard for this space.
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-13
California State University
Figure 2-3
Equipment Room Space Requirements3
This space is used to terminate the media from station outlets and backbone
(riser) systems and to house and support local area network equipment, cable
cross-connects, video distribution equipment, wireless resources, and system
monitoring components
It is important to give the design and location of these spaces high priority
within a building plan. At a minimum, these spaces must meet the following
design constraints:
3
Figure 2-3 taken from ANSI/TIA/EIA 569-A
4
Figure 2-4 taken from ANSI/TIA/EIA 569-A
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-14
California State University
Figure 2-4
Telecommunications Room Size4
6. The minimum room size is ten feet by eight feet. Additional square
footage should be provided if the space will need to accommodate optical
fiber cable to individual station outlets and/or to house significant
network routing or computing server equipment.
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-15
California State University
It was mentioned earlier in this TIPS section that the criticality concept might
be useful in telecommunications space planning, and that is particularly true
with regard to telecommunications rooms. Because of the University’s large
size and scope, planning and design personnel across the CSU typically must
cope with an extremely wide range of physical and environmental
considerations in programming TRs, from the very simple to the
extraordinarily complex. Under such circumstances, it can be expedient to
seek commonalities rather than differences—and relative space criticality can
provide a basic structure for such processes.
1
“Network and Technology Alliance Recommendations for Telecommunications Room Guidelines,” NTA-
IPPWG & American Power Conversion, 2006
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-16
California State University
Figure 2 – 5
An Example of Possible Criticality Levels for Telecommunications Rooms (TRs)
Criticality
Equipment Supported Importance Typical TR features
level
Wiring connections. Disruption of hours or even days can Open racks or wall-mount for cable
Criticality
be tolerated. Loss of operation causes connection boxes. Little or no power;
0 minor inconvenience. Little or no heating, ventilation or air
conditioning. Little or no security.
Small electronic devices Disruption of minutes or hours can be Open racks or wall-mounting for
supporting activities or tolerated. Loss of availability is roughly electronic devices. Low power
Criticality processes that are not critical. equivalent to loss of local productivity. requirement. Extremes of
Minor consequences for business temperature, humidity, dirt, or power
1 operations. disturbances could damage
equipment. Short-duration power
back-up. Light security.
Small to mid-size electronics Loss of availability could widely affect Open or enclosed racks for electronic
supporting important business productivity, depending upon timing. devices. Power disturbances or
processes and Downtime can be tolerated if given extremes of temperature, humidity, or
communications warning and time to respond. Full dirt could damage equipment.
Criticality
recovery following momentary, Several minutes of power back-up
2 unplanned downtime might take
significant time and/or require human
available. Environmental
management & remote annunciation
intervention. Maintenance downtime present. Limited access.
can be regularly scheduled or planned
with short notice.
“High-end” electronics Loss of availability could have serious Enclosed racks for electronic
supporting critical business life safety and/or business continuity devices. Extremes of temperature,
processes and implications, including damage to humidity, dirt, or power disturbances
communications. VoIP reputation with students, parents, and could damage equipment. Several
Criticality
applications that need to be the general public. Full recovery minutes to hours of power back-up
3 available in emergencies.
Criticality 3 actually rare for a
following momentary unplanned
downtime could take hours or days.
available. Environmental
management, remote annunciation
TR; described environment Maintenance downtime or low-risk and/or control present. Controlled
would be more typical of ERs, windows can be scheduled, but well in access.
MDFs and data centers. advance.
Criticality levels based on Syska Hennessy Group, Syska Criticality Level Definitions, 2005, with permission.
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-17
California State University
Figure 2 – 6
Example of Typical Environmental Guidelines
Keyed to Standard Telecommunications Room (TR) Types
1 2 3
Criticality level
See Figure 2-5 Low Medium High
(Rare for TRs)
UPS redundancy N
(No redundancy)
N+1 2N
Sprinkler or same as
Sprinkler or same as Pre-action, clean-agent,
adjoining rooms, with
Fire suppression adjoining rooms with high-temp heads
high-temp heads
Clean-agent portable Clean-agent portable
Clean-agent portable
fire extinguisher fire extinguisher
fire extinguisher
NOTES:
1. These examples assume a “standard” physical room. They do not take into
account constraints imposed by existing room conditions that might pose special
challenges.
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-18
California State University
Figure 2 – 6 (Continued)
Criticality level 1 2 3
See Figure 2-5 Low Medium High
Remote shutdown
None Graceful shutdown Graceful shutdown
capability
UPS battery
monitoring Local Local Local
Personnel test with
probes
Remote alarm Remote alarm & trending
Water leaks
If there is fan coil, piping, or Leak rope
None Leak rope with local alarm
other water source in or above
2
Local & remote alarm
the room
NOTES:
1. These examples assume a “standard” physical room. They do not take into
account any constraints imposed by existing room conditions that might pose special
challenges.
1
Smart card, keypad, biometric or other technology that allows selective and updatable access
2
For new construction, strive to keep wet piping out of the TR
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-19
California State University
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-20
California State University
Although most design projects for new CSU campus buildings incorporate
interconnection of telecommunications links from outside the building, the
scope of the project rarely includes required renovation or expansion work on
major interbuilding pathways impacted by the new facility. In some cases, a
separate construction project may be required to provide adequate pathways
up to the point at which the building project is to be interconnected.
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-21
California State University
the university faculty, staff, and students for service during an active cutover
(conversion).
1. All backbone conduits and sleeves must be four (4) inches in diameter.
2. Pathways must be designed with no more than two (2) ninety (90) degree
bends, with a maximum distance between pull boxes of 100 feet.
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-22
California State University
Refer to Section 3., The horizontal pathways between telecommunications rooms and station
Infrastructure and outlet locations receive the heaviest usage and are the source of the most
Pathway Design, for complaints of any component of a telecommunications distribution system.
detailed design Such pathways can be addressed in a number of alternative ways, but
elements. inadequate solutions are frequently adopted in efforts to meet budget
restrictions. When working in this realm, the designer should identify specific
methods for placing and supporting the initial cable, while at the same time
providing the flexibility required to meet future changes in technology.
Almost no facility design concept exists that will permit the use of a single
telecommunications distribution method throughout an entire structure.
Structure-based systems, such as cell floors, raised floors, and trench and
duct systems, all have limitations as well as advantages. Alternative systems,
such as cable trays, zone or direct-run conduits, and floor monuments, must
be analyzed for specific space requirements; it cannot simply be assumed that
space will be available somewhere within the building structure to support
adequate pathway installation.
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-23
California State University
3. Any outlet separated from the main horizontal support system (such as a
cable tray) by a fire or smoke partition must have a rated pathway, such as
a sleeve that can be fire-stopped after cable is installed or an enclosed
conduit or raceway directly from the outlet to the tray side of the partition.
4. Every room must be provided a specific pathway from the false ceiling
area (used to access user jack locations) to the main horizontal
distribution pathway (such as the cable tray).
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-24
California State University
Obviously, the unusual feature of wireless systems is the very fact that no
media exists, in the physical sense of wire or cable, to connect the end-user
to a wired electronic network. Instead, the connection is made through radio
frequency signal transmission, thus introducing a new realm of technology
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-25
California State University
While it is certainly well beyond the scope of this TIPS document to provide a
detailed description of WLAN technology, one or two historical and
developmental notes may be helpful. The “802.11” connotation simply refers
to a family of IEEE standards for wireless LANs that were designed to extend
802.3 (wired Ethernet) into the wireless domain. The 802.11 standard is
more widely known as "Wi-Fi" because the Wi-Fi Alliance, an organization
independent of IEEE, provides certification for products that conform to
802.11. The first 802.11 specifications were introduced in 1997 and included
two spread-spectrum methods for transmission in the 2.4GHz band. At the
present time, the 802.11 family includes six over-the-air modulation
techniques all using essentially the same protocol: the original legacy 802.11
standard and its a, b, g, i and n amendments.
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-26
California State University
Figure 2 - 7
An important limitation on wireless throughput rates is that the available
Typical WLAN Complex bandwidth is shared by all users connected to a particular WAP, so that
significant service degradation occurs when the number becomes too large
for the existing conditions. Further, as explained above, the available
bandwidth is by no means the full advertised capacity of the device. One key
factor in the equation is Signal to Noise Ratio (SNR), a measure that takes into
account the relevant signal adjusted to the electronic background “noise”
impacting the system; thus a strong wireless signal is not necessarily the
most accurate indicator of signal capacity.
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-27
California State University
In the early days of wireless deployment at CSU campuses (only a few short
years ago), an access point installation was typically a single device located to
serve a particular space to the extent that its signal strength and throughput
capacity would cover the desired area. This sort of implementation became
known as a wireless “hotspot.” More recently, however, the demands for ever
greater coverage and capacity have resulted in the development of strategies
for using multiple WAP units distributed in patterns providing coverage with
deliberate partial signal overlap. Such groupings are typically designed to
yield some redundancy in case of single unit failure and to meet estimated
coverage and capacity requirements as seamlessly as possible within the
limitations of the RF equipment being deployed. Recent equipment
announcements from some vendors suggest a migration toward so-called
“lightweight” (less intelligent, also referred to as “thin” or even “ultra-thin”)
access point devices connected to wired Ethernet through multi-point
controllers capable of monitoring and managing the array of WAP units
attached to them. One argument for this approach is based on the improved
security implications: if an AP is stolen there are no network configurations or
business secrets to be had.
Security issues for WLAN installations extend well beyond physical theft, as
they are subject to electronic intrusion from a variety of sources, including:
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-28
California State University
In addition to APs and AMs and their related antennas, other devices
commonly associated with Wi-Fi systems include:
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-30
California State University
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-31
California State University
12. A coverage map or blueprint for each facilities area surveyed, including
SNR/Noise/Signal Strength indications
13. Photos of individual AP placements and their related telecommunications
room (TR/IDF)
14. A logical network diagram
The CSU normally expects that WLAN design consultants will provide for an
appropriate site survey in preparing construction/installation documents for a
campus facility incorporating wireless capability. However, that responsibility
will vary depending upon the nature of the project:
Whether dealing with one WAP or many, the problem for the
telecommunications physical plant designer seeking to assure adequate
support for an interior WLAN installation is to locate wired Ethernet and
electrical power outlets in some convenient configuration responding to the
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-32
California State University
WAP deployment pattern. Fortunately for the designer, the advent of PoE
switch technology has reduced that problem at sites so equipped by
combining the needed power connection with Ethernet in a single outlet.
Unfortunately for the designer, the possibility exists that the advance of
technology might change the deployment pattern in a particular space over
time—thus the outlet distribution should be planned for future flexibility as
well as current convenience and cost-effectiveness. As another rule of
thumb, an Ethernet outlet (and if PoE technology is not being employed, an
electrical outlet) should certainly be provided within 25 feet of all projected
WAP locations. Some CSU campuses have adopted strategies for outlet
deployment, and the designer should certainly evaluate them, as they typically
are conditioned by prevailing local circumstances. However, to assure
maximum flexibility and resiliency, a hexagonal pattern of outlets on 50-foot
centers should be considered if circumstances and budgetary resources
permit.
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-33
California State University
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-34
California State University
foliage: surveys of the same site are likely to yield different answers in
winter as contrasted with summer!
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-35
California State University
Figure 2-12 summarizes some of the key information reviewed in Section 2.3.
Fig. 2 - 12
Telecommunications Space Physical Requirements
Room Type
Space
Service Network Technology/ Roof/
Requirement
Entrance Telecom Hub or Equipment Computer Antenna
Center Laboratory Site
Equipment None Active Active Active Active devices, Active
devices devices, devices workstations devices
monitoring, and/or PBX and printers;
mgm’t. & possibly servers
control
equipment
Floor Space Shared Dedicated Dedicated Dedicated Shared Shared
System(s)
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-36
California State University
2.4.1 Offices
Office spaces range from the standard one-person space to multi-room office
suites, and all need to be suitably equipped to afford access to various
campus telecommunications resources. All offices must be designed with
multiple voice, data, and video outlets situated to allow changes in furniture
layouts. Other specific design considerations include:
2. Larger offices and open suite areas should have multiple communication
outlets (minimum of one per 75 square feet) but no fewer than one at
every-other electrical outlet.
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-37
California State University
1. Rooms longer than twelve (12) feet should be equipped with one or more
floor outlet boxes that provide power and two signal pathways. (One
signal pathway is for connection to the building network, and the other is
for room control equipment.)
2. Separate lighting controls should be provided upon entry to the room and
at the front of the room (presentation area) to provide presenter and task
lighting and a switch-activated power outlet. Signal and power needs and
distribution methods must be coordinated with the selected furniture
layout.
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-38
California State University
Trends within education are being impacted not only by technology but also
by a different perspective on how people learn and share knowledge. Many
faculty are moving away from the traditional lecture mode of instruction.
There is a trend to more interaction between faculty and students, between
students, and with technology.
New approaches in teaching and learning will impact the size, shape, and use
of classroom space across the university. The challenge to the building
designer is to meet current requirements and budgets while still providing
flexibility for change. The challenge for the designer of technology systems is
in determining specific requirements and defining sufficient flexibility to meet
emerging instructional trends.
Several issues related to the increased use and reliance upon technology in
the instructional setting must be addressed in the planning process.
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-39
California State University
9. Any built-in seating must be designed to provide pathways for both power
and telecommunications to every seat, even if those services will not be
initially installed.
12. Classrooms must be designed to support both the instructor and the
student in their efforts to use technology and to learn. Some general
guidelines for classroom design related to display systems or imaging
systems are as follows:
a. The size of the display screen(s) must allow students at all locations
within the room to obtain an unobstructed view. Without other specific
requirements, the viewing distance should be between two and eight
times the height of the image. For example; if the room is configured
so the most distant seating row is 24 feet from the display screen or
monitor, the image should be three feet in height (24’ ÷ 8 = 3’). In
addition, if the image is three feet in height the minimum distance to
the closest viewing row would be six feet (3’ × 2 = 6’).
b. The location of seating in front of the screen should enable the student
to remain at a workstation and still view the display. This means the
end seats of the front rows should be at an angle of 35 degrees or less
in relation to the centerline of the room and screen.
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-40
California State University
1. Overhead projector
2. Videotape recorder/player
3. Digital Video Disk (DVD) player
4. Video monitor/receiver(s) or video projector
5. Television monitor/HDTV monitor
6. Teleconferencing equipment
7. Video camera presenter
8. Assistive listening devices/microphone & amplifier
9. Media retrieval system
10. Personal computer
11. Motorized screen
12. TV mount(s), stand(s) or cabinets
13. Multimedia/graphic display systems
It is conceivable, if not probable, that an instructor will "cue up" all media
resources before commencing a lecture -- e.g., turn on the TV
monitor/receivers and/or video projector and VCR, load the videotape, power
up and load the PC, and place the equipment in "hot standby."
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-41
California State University
14. The standard hardware listed above for smaller classrooms, but with
improved quality of certain equipment and/or facilities (e.g., two or more
overheads, 35 mm or 16 mm projectors; TV monitor/receivers; two or
more screens; and voice, data, and video connectivity).
d. Video and audio services to include front, side, and ceiling speakers,
record/playback services
Larger classrooms and lecture halls utilizing extensive media equipment will
require increases in the electrical and communications infrastructure design
above that required for the smaller classrooms. In addition, selected facilities
will have additional requirements for projection booth/control room spaces
and supporting infrastructure in order to make the best use of the media.
Such large classrooms and lecture spaces may also require support for
student workstation locations involving conditioned power and
communication outlets at each student's workspace.
2.4.3.4 Laboratories
Laboratories must be equipped to handle the same telecommunications and
media presentation services as those defined for small classrooms. In
addition, many laboratory locations will require student workstation facilities
either built into the top of counter space or located at multiple locations
along outer walls, or possibly both. Many of the functions performed in
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-42
California State University
Some lab spaces will utilize their own computer-based systems, and adequate
space near the lab must be provided to house this equipment and terminate
any locally-distributed cables. In addition, staff and control rooms, which
generally surround a laboratory space, must be fully equipped with
communication outlets in a manner similar to faculty offices.
High technology spaces must be designed and configured to support the on-
going modification of technology and network connection within rooms and
between similarly equipped rooms. If built-in furniture is used, it must
support extensive power and telecommunications cabling. If freestanding
tables are used, a specific pathway design must be prepared for each room
including one or more of the following:
1. A floor duct and trench system, separate from any pathway required for
other services on the same floor, running the length of the room every five
to seven feet apart.
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-43
California State University
Cable
interconnection panel
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-44
California State University
The room or space used to house the equipment must be provided with
additional cooling, electrical service, and telecommunications services
regardless of the final configuration. Generally, this area will be the location
in which all cable from a specific room is terminated and the hardware
interconnected into the campus backbone network. As such, the distribution
system, such as a floor trench system or dedicated conduit or raceway, must
extend to this point; and a cable support system must be designed into the
space.
Figure 2 - 14
Schematic of Typical Raised cable distribution floor
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-45
California State University
These floors are generally not suited for use in a computer room environment
due the limited capacity for below grade cable and/or cooling pathways.
Fortunately, high tech rooms usually need only a few inches of clearance, and
if the system is well planned, it can support changes over many years.
2.4.4 Libraries
Library facilities are frequently the central hub for electronic information on a
campus. In addition to the main automated systems designed specifically for
libraries, such as reference and information retrieval systems, libraries are
often the focal point for instructional media (video) and a variety of
instructional and academic computing systems.
areas, rather than "common" outlets shared by all users in a given room. In
short, every residence hall student should have his/her own voice, data, and
video station outlet.
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-47
California State University
KEY
POINTS For Architects and Facility Planners
TIA/EIA standards must be used to define the minimum size criteria for
telecommunications spaces. Campus-specific requirements will often
increase the size above those minimums.
TIP Standards
Effective May 2007
F ACILITIES PL ANNING AND PROGR AMMING Page 2-48