MAINTAINING ELECTRO-HYDRAULICCONTROL(EHC)

SYSTEMS FOR TURBINE GENERATOFIS USING


PHOSPHATE ESTER EHC FLUID

RAY CRANE
IEEE Member #7326135 (Sr. Member)
Weyerhaeuser Paper Company
Columbus Pulp and Paper Complex
P. 0. Box 1830
Columbus, MS 39703-1830

Abstract-The reliability of Electro-Hydraulic-Controlled Some of the key elements in maintaining the fluid are:
(EHC) turbine generators can be increased by properly 1. Cleanliness by proper maintenance and use of the
maintaining the hydraulic system and fluid. With auxiliary filtering system.
increasing cost of production downtime and energy, the 2. Maintain moisture content below 0.10%.
demand for reliable turbine generator operation 3. Maintain the temperature of the fluid
becomes more prevalent year after year. The purpose between 110°F and 115°F.
of this paper is to describe the necessary requirements 4. Maintain resistivity of the fluid above 5,000
for maintaining the electro-hydraulic system through meg. ohms/cm.
proper care of the phosphate ester fluid. Also it will 5. Maintain acid neutralization number below 0.20, (mg
also address the expected results of operating a system KOH/g) which is affected by all of the above.
with contaminated fluid and the cleanup of a
contaminated system. II. CLEANLINESS

1. INTRODUCTION The EHC fluid cleanliness can be maintained free of


particulate by proper filtration. Maintaining cleanliness
Phosphate ester fluids are used on EHC turbine can be done by the auxiliary recycle system where a
generator controls due to their fire resistant small (typically 0.5 GPM) amount of EHC fluid is
characteristics which reduces the risk of fires if a leak circulated from the reservoir through two filters back
were to occur. Properly maintained, phosphate ester into the reservoir. (See Fig. 1.) The first unit is the
fluids will result in years of trouble-free operation of large Selexsorb GT filter. The main purpose of the first
turbine generators controlled by the electro-hydraulic filter will be discussed under the moisture and acid
process. number paragraph. The second filter is a 1/2 micron
particulate element whose only purpose is particulate

Fig. 1. Hydraulic System for EHC Controlled Turbine Generator

183 CH3142-719210000-0183 $3.00 C 1992 IEEE


Also, the main hydraulic pumps have an inline stainless element in the auxiliary filtering system should help to
steel suction filter and a discharge filter made of dual keep the acid number low. If, in testing, the acid
filter elements, 25 micron inside stainless steel element number begins to creep up or the resistivity creeps
with an outside element of 10 micron size. (See Fig. 1.) down on an operating system, change the Selexsorb
It is vital to keep the particulate count to a minimum GTR filter element and it should bring these values
due to very close tolerances in servo valves and back into specified ranges.
switching valves which can easily be plugged, stick or
operate sluggishly if particulate count rises beyond N. TEMPERATURE
specified recommendations.
Maintain the temperature of phosphate ester fluid
Another element of concern in cleanliness of the fluid between 110°F and 115°F. It is recommended that
is inadvertently contaminating it with a petroleum based the hydraulic fluid temperature in the reservoir be
hydraulic oil. Adding additional EHC fluid should not be measured and maintained by water cooled heat
necessary unless a leak occurs. If the need arises to exchangers and a control valve that modulates the
add fluid, make sure that only phosphate ester fluids of water flow controlling the fluid temperature at the
the same manufacturer and grade that is in the unit are desired setpoint. This system should be checked and
used and that it is installed with utensils that have been calibrated often.
thoroughly cleaned with mineral spirits.
Heat accelerates the hydrolysis process causing the
111. MOISTURECONTENT acid number to rise more rapidly, however, the
temperature should be higher than the ambient
Moisture content is the most vital element to control. temperature by 10" F or 15" F to keep down
Unlike petroleum oil, phosphate ester fluid will combine condensation in the reservoir.
with water or hydrolyze to form acids. This is the
primary reason phosphate esters breakdown in service. V. FLUID RESISTIVITY
As moisture content rises and combines with the
phosphate ester fluids, a chemical reaction occurs Resistivity of the fluid should be maintained at 5,000
forming another product. Unfortunately, this product meg ohms/cm or greater. Resistivity is directly affected
being formed is acid. The usual concern is that when by the moisture content, acid number and particulate
weak acids come into contact with the mechanical count. Pay close attention to the resistivity number
system, corrosion occurs and with phosphate ester from the testing procedure and trend it. If the trend
fluids deposits form. These deposits and corrosion starts down, it is a clear indication that trouble looms
cause havoc in EHC control systems. Phosphorus acids around the corner.
extract metal ions from such items as "fullers earth" filter
elements, servo valves, switching valves, pumps, rams, VI. ACID NUMBER
etc. The tolerances in servo valves are very close and
when the metal is attached by the phosphorus acid, the As stated previously in this article, the key reason for
tolerances increase to the point where the leakage elevated acid numbers is moisture content. The acid
across the servo valve becomes so great that the main number should be maintained below 0.10.This value is
hydraulic pump motors become overloaded and will trip determined by a titration test of mg KOH/g of fluid.
out. This value can easily be maintained by the system
breathing through the silica gel packets and by using
The hydraulic system reservoir is equipped with a the Selexsorb GT' filter element in the auxiliary filter
breather vent canister. Inside this canister is a number system.
of silica gel material packets used to absorb moisture
that may enter the reservoir and combine with the VII. OPERATING A CONTAMINATED SYSTEM
phosphate ester fluid. These packets should be dried
out every quarter by placing them in a controlled As previously stated, the cleanliness of the phosphate
temperature oven at 250" F for 16-24 hours. This ester fluid is vital, as contaminated fluid will cause both
should be done by placing 1/2 of the packets at a time sludge deposits and will extract metal ions forming
in the oven. When they are reinstalled, the other 1/2 of phosphorus acids. This condition will very quickly result
the packets should be dried, then reinstalled. Also, in servo valve failures. Tolerances will increase in the
never use water or water-base materials around the servo valve spool and body, causing larger GPM flows
hydraulic unit. Any cleaning of cans, funnels, hoses or from the high pressure main hydraulic pump that is in
the tank itself, should be done with a good quality service. Generally the motors driving these pumps are
mineral spirit. sized for the normal GPM flow required to operate the
turbine valves. As the flow increases, the HP
All General Electric EHC controlled turbine generators requirements increase proportionately while maintaining
sold since the fifties have had "fullers earth' elements system pressure and overloads the motor causing it to
supplied in the auxiliary filtering system. It has been trip. When this occurs, the second motor/pump will
proven that once the moisture content begins to rise automatically start on low pressure and it too will be
that the "fullers earth" element compounds the problem overloaded due to the same large flow and trip out
increasing the acid number. This problem can be taking the turbine generator off line. A good procedure
eliminated by changing the "fullers earth' element to a is to take and record motor load readings regularly. If
Selexsorb GT element. Using the Selexsorb GTR the load starts to increase, you can be sure that flows

184
are changing and very probably indicates changed recommendations. With this process, any change in the
tolerances in the servo valve due to contaminated fluid. fluid quality can quickly be detected and the
appropriate steps taken to correct the problem.
VIII. CLEANING A CONTAMINATED SYSTEM Whereas with extended operation, the system will
become severelycontaminated and component damage
When a system has been operated contaminated for will occur.
long periods of time, follow the procedure listed below
to clean it up: X RECOMMENDATIONS

rn Remove the "fullers earth" filter and change the 1/2 Test the fluid every three (3) months.
micron backup element in the auxiliary filtering system.
(See Fig. 1.) Replace the "fullers earth filter with a Selexsorb GTR
element in the auxiliary filtering system. Change this
With unit operating, add 5% of 88050 Fyrquel element as needed or at least once a year.
flushing fluid and run for 12 hours, watching for
foaming. If foaming occurs, add a small amount of Change the 5 micron filter element in the auxiliary
silicone defoamer. (88050 purchased from AKZO filtering system every six (6) months.
Chemical, Inc., Gallipolis Ferry, WV, 25515).
Dry the silica packets in the breathing compartment
Add an additional 5% of 88050 flushing fluid and of the hydraulic reservoir in a controlled temperature
operate for another 12 hours watching for the foaming oven at 250" F for 16-24 hours every 6 months.
possibility.
Maintain temperature of the EHC fluid in the
With the machine down, shut the hydraulic system reservoir between 110" F and 115"F.
down and lock out the pumps. Drain all the EHC and
88050 fluid. Change the hydraulic supply pump in-line filter first-
stage element (outside 10 micron) and wash the second
Clean the tank and auxiliary filter reservoirs stage stainless steel inside unit once a year on a clean
thoroughly using lint-free rags dampened with a good system. This can be done on the run by switching
quality mineral spirit and refill with Fyrquel EHC fluid. pumps.
Run for 24 to 48 hours and shut the system down, lock
the pumps out and drain the tank. This step removes Make sure that the system is not inadvertently
the sludge deposits that have been dislodged by the contaminated with mineral oil by clearly posting a sign
88050 cleaning fluid. Once again, clean the tank and "Fyrquel EHC Fluid Only" on the hydraulic reservoir.
filter reservoirs thoroughly.
Use a good quality mineral spirits to clean all
rn Refill the tank with Fyrquel EHC fluid. components that will come in contact with the
phosphate ester fluid. CAUTION!!! Never use any other
rn Install a Selexsorb GTR filter element in the Hilco- cleaning fluid.
Hiflo filter (P/N ST718-00-03WCO with gasket FB-811-
6). rn Take hydraulic pump motor load readings and
record them watching for any increase from normal.
Start the system back up and flush the servo valves
and rams. This can be done by disconnecting the drain XI. SUMMARY
lines and connecting a hose to catch the fluid in a 5-
gallon container for proper disposal. Reconnect the In order to keep your turbine hydraulic control system
drain lines and put the turbine generator back into operating trouble-free, maintain your phosphate ester
operation. Run for 7 days and take a sample of the EHC fluid in top condition by keeping the system dry as
fluid and send to AKZO Chemical, Inc., for testing. possible, particulate count low, temperature between
110" F and 115" F avoiding high temperature
DC SAF€W/ENVIRONMENTAL conditions and of utmost importance, maintain a low
acid number. This can be done through a
USE CHEMICAL HANWNG GLOVES AT Au. TIMES comprehensive fluid maintenance program. This
WHEN H A N W N G PHOSPHATE ESTER RUIDS. program should include a quarterly monitoring and
ALWAYS F W O W MSDS PROCEDURES WHEN testing program of the fluid by a qualified phosphate
HANWNG OR DISPOSING Of THE FLUID. ester testing laboratory.

X TESTING PROCEDURES NI. REFERENCE

Phosphate ester fluids, such as FyrquelR EHC supplied The numbers and suppliers used above are for a
by AKZO Chemical, Inc., are very different from standard General Electric furnished hydraulic system for
petroleum oils and should be tested only by the people turbine control of an EHC machine.
furnishing the fluid. The supplier of the fluid supply test
kit and will test the fluid quarterly free of charge and
furnish a d e t a i l e d test r e p o r t i n c l u d i n g