You are on page 1of 1

352.

1 ARTICLE 352 — RIGID POLYVINYL CHLORIDE CONDUIT: TYPE PVC

largest trade size of an entering raceway. These conduit bodies


ARTICLE 352 shall not support luminaires or other equipment and shall not
contain devices other than splicing devices as permitted by
Rigid Polyvinyl Chloride Conduit: Type 110.14(B) and 314.16(C)(2).
PVC (I) Insulation Temperature Limitations. Conductors or cables
rated at a temperature higher than the listed temperature
Part I. General rating of PVC conduit shall be permitted to be installed in PVC
conduit, provided the conductors or cables are not operated at
352.1 Scope. This article covers the use, installation, and a temperature higher than the listed temperature rating of the
construction specifications for rigid polyvinyl chloride conduit PVC conduit.
(PVC) and associated fittings.
352.12 Uses Not Permitted. PVC conduit shall not be used
Informational Note: Refer to Article 353 for High Density Poly‐ under the conditions specified in 352.12(A) through (E).
ethylene Conduit: Type HDPE, and Article 355 for Reinforced
Thermosetting Resin Conduit: Type RTRC. (A) Hazardous (Classified) Locations. In any hazardous (clas‐
sified) location, except as permitted by other articles of this
352.2 Definition. Code.
Rigid Polyvinyl Chloride Conduit (PVC). A rigid nonmetallic (B) Support of Luminaires. For the support of luminaires or
raceway of circular cross section, with integral or associated other equipment not described in 352.10(H).
couplings, connectors, and fittings for the installation of elec‐
trical conductors and cables. (C) Physical Damage. Where subject to physical damage
unless identified for such use.
352.6 Listing Requirements. PVC conduit, factory elbows, and
associated fittings shall be listed. (D) Ambient Temperatures. Where subject to ambient
temperatures in excess of 50°C (122°F) unless listed otherwise.
(E) Theaters and Similar Locations. In theaters and similar
Part II. Installation
locations, except as provided in 518.4 and 520.5.
352.10 Uses Permitted. The use of PVC conduit shall be
352.20 Size.
permitted in accordance with 352.10(A) through (I).
Informational Note: Extreme cold may cause some nonmetallic
(A) Minimum. PVC conduit smaller than metric designator 16
conduits to become brittle and, therefore, more susceptible to (trade size 1∕2) shall not be used.
damage from physical contact.
(B) Maximum. PVC conduit larger than metric designator
(A) Concealed. PVC conduit shall be permitted in walls, 155 (trade size 6) shall not be used.
floors, and ceilings. Informational Note: The trade sizes and metric designators are
(B) Corrosive Influences. PVC conduit shall be permitted in for identification purposes only and do not relate to actual
dimensions. See 300.1(C).
locations subject to severe corrosive influences as covered in
300.6 and where subject to chemicals for which the materials 352.22 Number of Conductors. The number of conductors
are specifically approved. shall not exceed that permitted by the percentage fill specified
in Table 1, Chapter 9.
(C) Cinders. PVC conduit shall be permitted in cinder fill.
Cables shall be permitted to be installed where such use is
(D) Wet Locations. PVC conduit shall be permitted in
not prohibited by the respective cable articles. The number of
portions of dairies, laundries, canneries, or other wet locations,
cables shall not exceed the allowable percentage fill specified
and in locations where walls are frequently washed, the entire
in Table 1, Chapter 9.
conduit system, including boxes and fittings used therewith,
shall be installed and equipped so as to prevent water from 352.24 Bends — How Made. Bends shall be so made that the
entering the conduit. All supports, bolts, straps, screws, and so conduit will not be damaged and the internal diameter of the
forth, shall be of corrosion-resistant materials or be protected conduit will not be effectively reduced. Field bends shall be
against corrosion by approved corrosion-resistant materials. made only with identified bending equipment. The radius of
the curve to the centerline of such bends shall not be less than
(E) Dry and Damp Locations. PVC conduit shall be permitted
shown in Table 2, Chapter 9.
for use in dry and damp locations not prohibited by 352.12.
352.26 Bends — Number in One Run. There shall not be
(F) Exposed. PVC conduit shall be permitted for exposed
more than the equivalent of four quarter bends (360 degrees
work. PVC conduit used exposed in areas of physical damage
total) between pull points, for example, conduit bodies and
shall be identified for the use.
boxes.
Informational Note: PVC Conduit, Type Schedule 80, is identi‐
fied for areas of physical damage. 352.28 Trimming. All cut ends shall be trimmed inside and
outside to remove rough edges.
(G) Underground Installations. For underground installa‐
tions, PVC shall be permitted for direct burial and under‐ 352.30 Securing and Supporting. PVC conduit shall be instal‐
ground encased in concrete. See 300.5 and 300.50. led as a complete system as provided in 300.18 and shall be
fastened so that movement from thermal expansion or contrac‐
(H) Support of Conduit Bodies. PVC conduit shall be permit‐ tion is permitted. PVC conduit shall be securely fastened and
ted to support nonmetallic conduit bodies not larger than the supported in accordance with 352.30(A) and (B).

70 –202 NATIONAL ELECTRICAL CODE 2017 Edition

You might also like