Controlling Duct Pressure
Access Control
Actuators and Dampers
Alarms and Indication
The UCM-420A is one of the most versatile products sold by Kele . Although this product is capable of
Control Valves performing many control functions, it was primarily designed as a Setpoint Controller. Since the
Disinfection Solutions introduction of the UCM-420A, response from customers indicates that pressure control is a popular
application for this product. This article will discuss a typical application - controlling static pressure in
Electrical Wiring Materials
a duct by varying fan speed with a Variable Frequency Drive (VFD). This system could also be used
Enclosures to control the pressure with inlet vanes, discharge dampers, bypass dampers, etc. The same principles
Flow involved in this application could be used in other control applications, such as controlling water pressure
Gas and Specialty Sensors with variable speed pumping, VAV zone control or humidifier control.

Hazardous Locations
Humidity
Leak REFPRESC

Level
Lighting Controls
Motor Controls Figure 1 shows a simple Variable Air Volume (VAV) system. As the spaces served by the VAV terminals
are satisfied, the zone dampers will modulate closed and, without a pressure control system, the static
Network and Wireless
 Leave
pressure in the duct will rise. For this example, assume that a static pressure of 2" W.C. is required. To us a message.
Panel Fabrication monitor the static pressure in the duct, we will use a Model T30-030 Differential Pressure Transducer
Pneumatics and Fittings with a range of 0-3" W.C. The 4-20 mA signal from this device will be fed into a UCM-420A Setpoint
Power Monitoring and Controller, which in turn will control the speed of the fan by sending a 4-20 mA control signal to the fan
Protection VFD. The manual potentiometer on the UCM-420A will be used to set the static pressure at the desired
Power Supplies level. See the wiring diagram in Figure 3 on next page for system wiring. This wiring diagram shows a
Model DT13 Signal Isolator. The DT13 will not be needed unless the VFD requires an isolated control
Pressure
signal.
Relays and Contactors
Temperature Sensors and
Transmitters
Project
Thermostats and All programming of the UCM-420A is done by dip switches and jumpers. A list of the functions which are Portal
Controllers programmed by DIP switches as well as those programmed by jumpers is shown below. The proper
Tools and Test Equipment settings for this example are also shown.

Transducers
Variable Frequency Drives
(VFD) DIP SWITCH FUNCTIONS ----------------------------------------------------------- Remote Setpoint Enable/Dis
New Products
Kele Branded Products
smart>buy In this example, we are using the setpoint potentiometer on the UCM-420A to adjust the pressure, so the
local setpoint should be enabled and the remote setpoint disabled. As the pressure in the duct increases,
Quick Order the control signal from the UCM-420A must decrease to slow down the fan speed (assuming the VFD is
TYPE IT IN COPY & PASTE direct acting-speed increases with an increase in control signal) therefore, reverse acting control should be
selected for the UCM-420A. The integral reset rate and throttling range required will vary from system to
system and must be determined in the field. This will be discussed later in this article. Since pulse-width
modulation is not to be used in this example, all PWM functions are disabled. The jumpers will be set for
three-wire potentiometer local setpoint and 4-20 mA input from the pressure transducer. The instructions
furnished with the UCM-420A will explain in detail how to set the DIP switches and jumpers to
accomplish the above setting.

The input to the UCM-420A from the Static Pressure Transducer has a range of 0-3" W.C. Therefore,
when there is no pressure in the duct, the input will be 4 mA and when the static pressure in the duct is
3" W.C., the input will be 20 mA. The setpoint potentiometer scale on the UCM-420A is labeled 0-100%.
In our example, we require 2" W.C. in the duct so the setpoint potentiometer should be set for 2/3 x 100
= 67%.

As stated earlier, the throttling range and integral reset must be fine tuned in the field and cannot be
calculated. The throttling range is defined as the amount of signal change at the input required to cause
the output to go through its entire range (4-20 mA). For example, a 50% throttling range means that for
every 1 mA change in the input, there will be a 2 mA change in the output. To properly adjust the
throttling range, first disable the integral reset and set the throttling range at 100%. Then reduce the
throttling range in increments until the controller begins to hunt. When the controller begins to hunt, the
throttling range is too narrow, so widen it one step. The integral reset rate may now be adjusted. The
integral reset corrects the output of the UCM-420A to compensate for the offset inherent in proportional-
only controllers. The integral reset ramps the output in the direction that forces the input signal to exactly
match the setpoint. The number of times per minute this offset is overcome by the output signal is the
integral reset rate. The quicker the system responds, the higher (more resets per minute) the reset rate __
Log-In | New Customer? Register Now | 877.826.9045
may be set.

This control system will provide very smooth, precise static pressure control in the discharge duct. It will
products project portal tools account
also saveservices
energy sincewhy
the kele contact
fan will use us much horsepower as required to maintain the setpoint
only as
Enter keyword or product
pressure. In this example the pressure is adjusted with the setpoint potentiometer on the UCM-420A.
This pressure could also be controlled by a remote potentiometer or an analog or pulse width signal from
a BAS controller.

Another application would be controlling multiple zones (such as VAV boxes) from one BAS controller
output by using the multiplex PWM mode. In this application a PreCon Type 3 Thermistor could be used
as the temperature input to each UCM-420A and the BAS controller could send eight different setpoint
signals to the zones. Multiple UCM-420As could receive the same setpoint signal.

REFPRESD

WHO WE ARE WHAT WE DO HOW WE CAN HELP POLICIES


Kele Overview Product Categories Video Gallery Terms of Sale
24 Product Categories Technical Expertise Kele Calculator Privacy Policy
Line Card, 300+ Vendors Panel Fabrication Blog Return Policy
Free Shipping Custom Valve Assembly Insights Newsletter Shipping Policy
International BAS Project Support Log-In / Create My Account Material Safety Data Sheets
Customer Testimonials Customer Survey Conflict Materials Policy
Careers with Kele Saved Projects RoHS Policy
 Leave us a message.
Reach Policy

CALL A SALES REPRESENTATIVE QUESTIONS? GET SPECIAL OFFERS CONNECT WITH KELE
& PROMOTIONS
877.826.9045 USA EMAIL US
901.382.6084 International SIGN UP
Monday - Friday
7:00AM - 6:00PM (CST)

Project
Portal
ABOUT SSL CERTIFICATES

Privacy Policy | Return Policy | Shipping Policy | Terms of Sale | Site Map | Careers with Kele

You might also like