1 S EC TI ON 16230

2 STANDBY DIESEL ENGINE GENERATOR SETS

3PART 1 - GENERAL

41.1 SUMMARY

5 A. Section Includes: Extent of diesel generator set work as indicated by Drawings and
6 Schedules, and is hereby defined to include, but not by way of limitation:
7 1. Diesel engine
8 2. Electrical generator
9 3. Engine starting system, including batteries, instrument control panel, protective
10 housing, day tanks, annunciator panel, exhaust silencer, wall thimble, and accessories.
11 4. Walk-in sound attenuated type weatherproof generator enclosure

12 B. Types of generator sets required for the Project include:


13 1. Permanent Diesel Engine-driven Generator

141.2 SUBMITTALS

15 A. Submit in accordance with Section 01300 "Submittals," Shop Drawings covering the
16 items included under this Section. Shop Drawing submittals shall include:
17 1. Product Data: Submit manufacturer's data on diesel engine driven generator sets and
18 components.
19 a. Generator dimensions
20 b. Generator weight
21 c. Generator rating
22 d. Alternator rating
23 e. Generator Starting System Data
24 (1) Battery size and ratings
25 (2) Charging system capacity
26 (3) Battery heater data
27 (4) Battery warranty
28 f. Generator Control Panel Data
29 (1) Layout
30 (2) Wiring diagrams
31 (3) Control interconnection
32 (4) Instrumentation
33 g. Exhaust System Data
34 (1) Muffler size
35 (2) Decibel reduction curve
36 (3) Fuel system data
37 h. Cooling System Data
38 (1) Radiator capacity
39 (2) Cooling reduction capacity

1 16230 - 1 of 12
2OCU Master CIP Technical Specifications rev: August, 2012
1 i. Enclosure Data
2 (1) Materials
3 (2) Size
4 (3) Assembly/disassembly instructions
5 (4) Door locations
6 (5) Noise reduction
7 j. Warranty data
8 k. Accessory and miscellaneous equipment
9 l. Generator Load Calculations
10 (1) Max loading shall be 80%
11 (2) Loads shall be on a staged, motors shall be started in sequence, not block
12 loaded during generator start.
13 (3) Calculation shall be provided via manufacturer's software.
14 2. Wiring Diagrams: Submit wiring diagrams for diesel engine driven generator units
15 showing connections to electrical power panels, feeders, and ancillary equipment.
16 Differentiate between portions of wiring that are manufacturer installed and portions
17 that are field installed.
18 3. Agreement to Maintain: Prior to time of final acceptance, Installer shall submit 4-
19 copies of an agreement for continued service and maintenance of diesel engine driven
20 generator sets for County's possible acceptance. Offer terms and conditions for
21 furnishing parts and providing continued testing and servicing, including replacement
22 of materials and equipment, for 1-year period with option for renewal of Agreement
23 by County.
24 4. Certifications: Provide diesel engine driven generator sets certified test record of the
25 following final production testing:
26 a. Staged load pickup
27 b. Transient and steady-state governing
28 c. Safety shutdown device testing
29 d. Voltage regulation
30 e. Rated power
31 f. Maximum power
32 g. Provide certified test record prior to engine-driven generator set being shipped
33 from factory to Project location.

341.3 QUALITY ASSURANCE

35 A. Codes and Standards


36 1. NFPA Compliance: Comply with applicable requirements of NFPA 37, "Installation
37 and Use of Stationary Combustion Engines and Gas Turbines," NFPA 99, "Standard
38 for Health Care Facilities," and NFPA 101, "Code for Safety to Life from Fire in
39 Buildings and Structures."
40 2. UL Compliance: UL 486A, "Wire Connectors and Soldering Lugs for Use with
41 Copper Conductors," UL 2200, "Standard for Safety for Stationary Engine Generator
42 Assemblies," rated 600 volts or less.
43 3. ANSI/NEMA Compliance: Comply with applicable requirements of ANSI/NEMA
44 MG1, "Motors and Generators," and MG2, "Safety and Use of Electric Motors and
45 Generators."

1 16230 - 2 of 12
2OCU Master CIP Technical Specifications rev: August, 2012
1 4. IEEE Compliance: Comply with applicable portions of IEEE Standard 446, "IEEE
2 Recommended Practice for Emergency and Standby Power Systems for Industrial and
3 Commercial Applications."

4 B. Warranty: Submit in accordance with requirements of Section 01740 "Warranties and


5 Bonds," warranties covering the items included under this Section. Unit shall be
6 provided with a full factory warranty of 2-years from date of County's acceptance.

7PART 2 - PRODUCTS

82.1 STANDBY POWER GENERATOR SYSTEM

9 A. Subject to compliance with specified requirements, approved manufacturers as listed in


10 Appendix D "List of Approved Products" offering products which may be incorporated in
11 Work.

12 B. The emergency generator set and accessories shall be of a type that complies with the
13 latest edition of the National Electrical Code and all applicable state and local building
14 codes and shall be UL listed per UL 2200 "Standard for Stationary Engine Generator
15 Assemblies," current edition.

16 C. The material and workmanship used in the manufacture of this equipment shall be of the
17 highest quality consistent with the current standards for like equipment, and the
18 equipment shall be manufactured in such a manner so as to conform to the latest
19 applicable IEEE, ANSI, ISA, and NEMA standards.

20 D. A complete engine generator system shall be furnished and installed with fuel transfer
21 pump, fuel tank, day tank (only if required by manufacturer), battery, battery charger,
22 muffler, radiator, control panel, remotely mounted automatic transfer switch, and all
23 other accessories required for an operational system. A normally closed control solenoid
24 with manual override in the supply line and backflow preventer in the return line shall be
25 provided in the generator fuel line. All materials and parts of the generator set shall be
26 new and unused. Each component shall be of current manufacture from a firm regularly
27 engaged in the production of such equipment. The set shall be of a standard model in
28 regular production at the manufacturer's place of business. Generators mounted or
29 stacked above the fuel tank shall not be permitted.

30 E. Base Mounting: A suitable number of spring-type vibration isolators with a noise


31 isolation pad shall be provided to support the set and its liquids. Isolators shall be bolted
32 to concrete generator pad.

33 F. Electrical Connections: All connections to the generator set shall be underground.

1 16230 - 3 of 12
2OCU Master CIP Technical Specifications rev: August, 2012
1 G. Except as otherwise indicated, provide manufacturer's standard diesel engine driven
2 generator set and auxiliary equipment as indicated by published product information, and
3 as required for a complete installation. Generator set shall be rated to continuously
4 power the total accumulated load and starting load shown on Schedule at 100°F ambient
5 temperature and at altitude where installed.

6 H. Diesel Engine: Provide a 4-cycle, compression ignition type engine for operation on a
7 No. 2 domestic burner oil grade of petroleum fuel oil. The engine shall be equipped with
8 fuel, lube oil and intake air filters; lube oil coolers, fuel transfer pump, fuel priming
9 pump, and jacket water heater, 105°C/220°F gear driven water pump. Engine operating
10 speed shall not exceed 1,800 rpm and shall be controlled by a governor to maintain
11 alternator frequency within plus or minus 3 Hertz of 60 hertz from no load to full load.
12 Frequency shall recover to steady-state tolerance within 5-seconds after application of
13 90% rated load.

14 I. Starting System: Provide engine generator unit with 12 or 24 volt, negative ground,
15 starting system including positive engagement solenoid shift-starting motor, batteries,
16 and 35-ampere, or greater, automatic battery charging alternator with solid-state voltage
17 regulator. Mount batteries in a plastic- or epoxy-coated metal platform near the starter
18 but not on the generator and coat battery terminals with an anti-oxidant. Generator sets
19 rated 150 kW or less shall have a battery rated 650-amperes cold cranking at 0°F and
20 170-minutes reserve capacity by SAE Standard J-537. Larger generators shall have a
21 battery rated either 220-ampere-hours or 900-amperes cold cranking, and 430-minutes
22 reserve capacity. Batteries shall have a 12-month full warranty and 60-month prorated
23 warranty.

24 J. Battery Charger: Provide a solid-state, current limiting, float-type battery charger with 5-
25 ampere minimum capacity. Charger shall operate from 120 volt AC single phase, 60
26 hertz power and shall automatically keep batteries at full charge. Equip charger with
27 ammeter and voltmeter. The battery charger shall be readily accessible and designed that
28 it shall not be damaged and shall not trip its circuit protective device during engine
29 cranking or it shall be automatically disconnected from battery during cranking period.
30 The charger shall be mounted inside the emergency generator enclosure. The charger
31 shall have a 7-day/24-hour timer control.

32 K. Alternator: Provide a single bearing brushless, self-excited alternator with inherently


33 regulated rotating rectifier exciter system or a revolving field design with a temperature
34 compensated solid-state voltage regulator. Connect the alternator housing directly to the
35 engine flywheel housing. Couple the alternator rotor directly to engine flywheel with a
36 semi-flexible steel disk coupling.
37 1. Provide windings with Class F insulation with epoxy impregnation and fungus-
38 resistant coating. Temperature rise shall be as defined in NEMA Standard MG1-
39 22.40.
40 2. The alternator shall be capable of starting load given on Schedule with 35%
41 maximum instantaneous voltage dip. Recovery to stable equation within plus or
42 minus 5% of rated voltage shall occur within 3-seconds.

1 16230 - 4 of 12
2OCU Master CIP Technical Specifications rev: August, 2012
1 L. Engine Cooling Radiator: Provide a complete engine cooling system equipped with a
2 radiator and blower type fan sized to maintain safe operation, 190°F engine outlet water
3 temperature at 100°F maximum ambient temperature. The engine cooling system shall
4 be filled with a solution of 50% ethylene glycol. On indoor mounted units, radiator shall
5 be equipped with a duct adapter flange. An air duct with flexible connecting sections
6 shall be provided between radiator duct flange and exhaust damper.

7 M. Generator
8 1. The generator shall be a 3-phase, 60 hertz, single bearing, synchronous type,
9 Permanent Magnet Generator (PMG) built to NEMA Standards. Epoxy impregnated
10 Class F insulation shall be used on the stator and the rotor.
11 2. The excitation system shall employ a generator mounted volt per hertz type regulator.
12 Voltage regulation shall be plus/minus 2% from no load to full load. Readily
13 accessible voltage drop, voltage level and voltage gain controls shall be provided.
14 Voltage level adjustment shall be a minimum of plus/minus 5%.

15 N. Instrument Control Panel: Provide engine generator set with engine oil pressure and
16 water temperature indicators, reset circuit breaker, static voltage regulator, voltage-
17 adjusting rheostat, voltmeter, ammeter with phase selector switch with an OFF position,
18 and with running time indicator and frequency meters, as required to satisfactory control
19 the engine generator set. Select circuitry of plug-in design capable of quick replacement,
20 and capable of accepting a plug-in device which allows maintenance to test control panel
21 performance without operating the engine.
22 1. Provide a cranking limiter to open starting circuit in 45 to 90-seconds if engine has
23 not started within that time or after a series of 3 or more cranking intervals separated
24 by 2 or more rest periods.
25 2. Provide engine safety devices to shut unit down on high engine temperature, low oil
26 pressure, overspend, and over crank. Provide, for each of these conditions, an alarm
27 light and an unpowered, normally open contact for remote use. Provide an audible
28 alarm with silence switch which is activated by any alarm condition.
29 3. Provide a relay with 2 normally open and 2 normally closed contacts rated 5A at 120
30 volts AC and which is energized when unit is running. Wire these contacts to
31 terminal strips for remote use.
32 4. Provide a 4-function switch marked AUTO, MANUAL, OFF, and STOP. In AUTO
33 position unit shall start when a remote contact closes and stop when contact opens. In
34 MANUAL position unit shall start and run until OFF position is selected.
35 5. Mount instrument control panel on unit such that it is isolated from generator set
36 vibration.
37 6. Provide a minimum of twelve form “C” auxiliary contacts to include contacts for
38 generator run and generator failure for connection to SCADA. All LCD screens
39 exposed to the sun shall have an aluminum sunshield painted white with hinged flap
40 covering the screen surrounding the manufacturer's enclosure.
41 7. Metering Equipment: Metering equipment shall include 3-1/2-inch meters (dial or
42 digital type frequency meter, 2% accuracy voltmeter, and ammeter and ammeter
43 voltmeter phase selector switch). The control panel shall also include the engine
44 water temperature, lube oil pressure and hour meter.

1 16230 - 5 of 12
2OCU Master CIP Technical Specifications rev: August, 2012
1 8. Fault Indicators: Individual press to test fault indicator lights for low oil pressure,
2 high water temperature, low water level, over speed, over crank, and for aboveground
3 storage tank and high and low fuel level shall be provided. Provide relay dry contacts
4 for interface of fault alarms with SCADA system.

52.2 ENGINE GENERATOR SET ACCESSORIES

6 A. Sound Attenuation: Enclosure shall be insulated to attenuate sound and include sound
7 attenuating features that direct radiant cooling air in a route to minimize ambient noise
8 when generator is running. Enclosure shall reduce noise by 8 dBA minimum.

9 B. Coolant Heater: Provide an engine coolant heater, of voltage indicated on Schedule, with
10 thermostatic controls to maintain engine coolant at proper temperature to fulfill start-up
11 requirements of NFPA 99.

12 C. Inlet and Exhaust Systems: Silencers and exhaust ducting to silencers shall be self-
13 supporting when assembled so that the engine does not support its weight. The exhaust
14 system shall be a part of generator enclosure. Provide all necessary supporting members
15 for ductwork between silencer and outlet. Provide all required cutting as shown on
16 Drawings and noted herein. The unit shall be complete with stainless steel weatherproof
17 rain cap. All exhaust duct shall be Schedule 10 stainless steel pipe, minimum. Inlet
18 silencer and filter to be self-supporting. Provide necessary supports for all intake
19 ductwork. All intake duct shall be Schedule 10 stainless steel pipe, minimum.
20 1. Provide bellows sections, insulated wall thimbles, inlet and outlet flexible section as
21 shown on Drawings. Design of exhaust silencer and stack including all ducting
22 shown shall have a pressure drop not exceeding 5-inches of water.
23 2. Provide a silencer which meets sound standards of a critical area. Silencer shall
24 provide attenuation (input to output) of 25 dB or greater at frequencies of 125 hertz to
25 8 kilohertz. A curve shall be submitted with Shop Drawings showing attenuation
26 (input to output) in dB versus frequency. Curve shall be on manufacturer's standard
27 data sheet or from an independent test lab. A spiral or bellows-type flexible section
28 of pipe shall be installed in the exhaust line between the muffler and engine manifold
29 connection. An insulated thimble section shall be provided where exhaust line passes
30 through roof or wall. Exhaust lines shall be pitched and a condensation trap provided
31 at non-draining low points in line.

32 D. Circuit Breaker: A generator power circuit breaker shall be installed as a manual load
33 circuit interrupter and an automatic overload and short circuit protection device.
34 1. The circuit breaker shall be a solid-state trip type for all sizes rated 300-amp
35 continuous and larger. Solid-state trip shall include Long-time, Short-time, and
36 Instantaneous. Ground fault trip required on breakers 1,000-amps and above.
37 2. Trip settings for all breakers shall be selected for the rating of the generator power
38 circuit as indicated on Drawings or on Schedule.

1 16230 - 6 of 12
2OCU Master CIP Technical Specifications rev: August, 2012
12.3 WEATHERPROOF GENERATOR ENCLOSURE: WALK-IN SOUND ATTENUATED TYPE

2 A. A weatherproof walk in sound attenuated type enclosure shall be provided to house the
3 engine/generator and accessories. The enclosure shall be designed to perform without
4 overheating in the ambient temperature specified and shall be UL listed per UL 2200
5 Standard for Stationary Engine Generator Assemblies, current edition.

6 B. The enclosure is to be in complete compliance with the National Electrical Code (NEC),
7 and the National Fire Protection Association (NFPA) with regard to clearances around
8 electrical equipment specified herein. The enclosure shall conform to the following
9 construction and design criteria as set forth:
10 1. Rigidity wind test equal to 120 MPH
11 2. Roof load equal to 50-pounds per square foot
12 3. Florida Department of Community Affairs Modular Building Insignia

13 C. Enclosure shall consist of a roof, 2 sidewalls, 2 end walls, and be manufactured of formed
14 aluminum components. The enclosure is to be provided with a means for securely
15 attaching the entire structure to the structural steel base as specified within.

16 D. A minimum clearance of 24-inches shall be allowed for walkway space between the
17 generator frame and interior sidewalls. A minimum walkway clearance of 30-inches
18 shall be allowed between the generator end frame and the interior rear wall of the
19 enclosure. The radiator front face shall be sealed to the front wall utilizing and 2-inch
20 minimum rubber gasket material to minimize recirculation of radiator air discharge and
21 prevent the transmission of vibration from the packaged generator set to the enclosure.

22 E. Wall framing shall be incorporated in the panels by forming an open back box structure.
23 Skin material shall be minimum thickness .090-inch marine grade aluminum. Enclosure
24 shall have a baked on powder-coat finish for maximum corrosion resistance. Exterior
25 skin panels shall be integral to the wall structure and not separate pieces riveted onto
26 framing members. Wall panels shall be no wider than 36-inches each and shall be
27 removable without the use of special tools. Wall and roof panels shall be designed so
28 that field replacement can be accomplished without disassembly of the entire structure if
29 damage should occur.

30 F. Standard enclosure exterior color is WHITE unless otherwise specified.

31 G. Roof assembly shall be peaked to aid in rainwater runoff. Cambered roof designs and
32 roofs with thicknesses of less than 0.090-inch nominally shall not be considered. Roof
33 assemblies are to be mechanically fastened to the vertical wall sections. Glued or
34 crimped roofs shall not be allowed nor considered as an acceptable alternative.

1 16230 - 7 of 12
2OCU Master CIP Technical Specifications rev: August, 2012
1 H. Air handling shall be as follows: Air will enter the enclosure through a Hood, Plenum or
2 Sound Attenuated Louvers/Baffles, as determined by the specific application and shall
3 allow for the airflow demand for proper cooling to generator set package. The cooling air
4 Inlet system shall prevent water intrusion into the enclosure with the generator set
5 operating at full rated load while allowing for a maximum air restriction of less than 0.30-
6 inches of water. Radiator Discharge shall be through a gravity operated extruded
7 aluminum back draft type damper and into a vertical discharge plenum or hood.
8 Discharge plenum/hood shall discharge air upward and be provided with a means to
9 positively drain any and all water entering the discharge device. Air discharge devices
10 shall in no event restrict airflow by more than 0.25-inches of water. To ensure adequate
11 airflow for cooling and combustion the static restriction over the entire system shall not
12 exceed 0.50-inches of water. Both Intake and Discharge hoods and plenums shall be
13 provided with removable bird/rodent screening to prevent the entrance of debris, birds,
14 rodents and other vermin.

15 I. Acoustical insulation materials shall consist of a UL Classified Thermofiber® or equal


16 insulation material with a heat/fire resistance rating up to 2400ºF and provide superior
17 sound attenuation performance. Acoustical insulation material on interior roof and walls
18 is to be mechanically held in place by 0.032-inch mill-finished perforated aluminum with
19 tuned engineered hole diameter for optimum sound attenuation at 1,000 Hz. Interior
20 perforated aluminum material shall protect the insulation material as well as allow noise
21 to permeate the absorptive material.

22 J. Four-point lifting provisions shall be provided and have sufficient capacity suitable for
23 rigging the entire Enclosure assembly.

24 K. A minimum of 2 single personnel access doors minimum size 36-inch shall be provided.
25 Doors shall be manufactured of the same material as enclosure. Doors shall be fully
26 gasketed to form a weather tight perimeter seal. Door hinges shall be full-length stainless
27 steel piano type and shall be attached with stainless steel hardware. Door handles shall
28 be of a corrosion resistant material. Main enclosure entry doors shall be equipped with
29 weatherproof stainless steel pushbutton combination locks. Doors shall be insulated with
30 no less insulation than is provided in the enclosure walls for sound attenuation.

31 L. Enclosure manufacturer shall provide all necessary hardware to internally mount the
32 exhaust silencer(s) specified herein. Silencer mounting hardware shall maintain the
33 weatherproof integrity of the enclosure system. Silencer shall discharge through radiator
34 discharge plenum of enclosure and have rain shield to prevent entry of moisture.

35 M. As a minimum the enclosure shall provide an average 30dbA sound reduction as


36 measured at 7-meters, 5-feet above grade level under free field conditions.

1 16230 - 8 of 12
2OCU Master CIP Technical Specifications rev: August, 2012
1 N. Electrical Package: Enclosure Shall Contain a minimum 100-Ampere, 120/208, 1-Phase
2 Load Center Main Lug Only with minimum 8/16 circuit spacing. Panel shall be mounted
3 to provide minimum 36-inch front working space per NEC. Load Center Shall Contain
4 Adequate Circuit Breakers to Support the following loads:
5 1. Three, 48-inch, T-8, 2-Bulb, Florescent Lights in Vapor Proof Fixtures. Lights shall
6 be controlled by 3-way switches located at each of the personnel entrance doors.
7 2. Two 20-Ampere, Duplex, 120 Volt AC, GFCI Receptacles. One Receptacle shall be
8 located adjacent to each personnel entrance door.
9 3. Engine Jacket Water Heater
10 4. Alternator Space Heater (if equipped)
11 5. Engine Starting Battery Charger

12 O. Structural Steel Base with Interior Finish Floor: A base under frame with interior finished
13 floor shall be provided and designed to support the installed equipment specified. The
14 floor structure shall be rated for a minimum distributed load of no less than 200-
15 pounds/square foot and reinforced as required to support equipment-loading
16 requirements. The under frame assembly shall consist of structural or formed steel
17 channel or I-beams welded together to form the outer perimeter of the sub-frame.
18 Structural or formed steel cross members shall be installed and welded on nominal 16-
19 inch centers to create a welded steel support structure for internal equipment installation
20 and distributed load support. The top deck interior shall consist of a minimum 3/16-inch
21 diamond steel deck plate mechanically fastened to the under frame structure. Seams of
22 the interior deck plate shall be solid seam welded their entire width. Tack welded or
23 caulked seams will not be allowed. Vibration isolator mounts shall be each located above
24 a frame member and securely welded to the top plate to ensure adequate load support.
25 Isolator mounting plates are to be 1-inch thick steel plate, tapped for isolator bolting. The
26 entire steel frame, interior floor and under frame shall be coated with a wear resistant,
27 high quality anti-corrosive material and topcoat.

28 P. Enclosure shall be provided with adequate overhead fluorescent vapor proof lighting
29 controlled by 3-way switches located at each side of the personnel entry doors.

30 Q. Enclosure hardware shall be stainless steel.

31 R. Four hinged doors shall be provided to allow complete access without their removal.
32 Doors shall be pad lockable on handles. Main enclosure entrance doors shall be equipped
33 with weatherproof stainless steel push button combination locks.

34 S. Each door shall have at least 2 latch-bearing points.

35 T. Panels shall be completely and simply removable for major service access. Additional
36 doors in front of the radiator shall be supplied for easy removal of radiator assembly.

37 U. Enclosure shall be waterproof and the roof shall be peaked to allow drainage of
38 rainwater.

39 V. Baked enamel finish with primer and finish coat shall be painted before assembly. All
40 fasteners shall be stainless steel.

1 16230 - 9 of 12
2OCU Master CIP Technical Specifications rev: August, 2012
1 W. Unit shall have sufficient guards to prevent entrance by small animals.
2 1. Batteries shall be designed to fit inside enclosure and alongside the engine and shall
3 be easily removable for service. Batteries under the generator are not acceptable.
4 2. Unit shall have coolant and oil drains outside the unit to facilitate maintenance. Each
5 drain line shall have a high quality valve located near the fluid source.
6 3. Fuel filter shall be inside the base perimeter and located so spilled fuel cannot fall on
7 hot parts of engine or generator. A cleanable primary fuel strainer shall be used to
8 collect water and sediment between tank and main engine fuel filter.
9 4. Crankcase fumes disposal shall terminate in front of the radiator to prevent oil from
10 collecting on the radiator core and reducing cooling capacity.

112.4 AUTOMATIC TRANSFER SWITCH

12 A. The automatic transfer switch shall be housed in a NEMA 4X 316-stainless steel


13 enclosure with drip shield and door gasket. There shall be permanently affixed to the
14 interior side of the enclosure door both a data-plate that includes generator KVA/KW,
15 fuel tank capacity, rated fuel consumption, serial and model number of generator set, and
16 a 10-inch by 12-inch pocket for log sheet storage.

17 B. The transfer switch shall be provided with the following features:


18 1. Complete protection, close differential voltage sensing relays monitoring all 3-phases
19 (pick up set for 95% of nominal voltage, dropout set for 85% nominal voltage).
20 2. Voltage sensing relay on emergency source (pick up set for 95% of nominal
21 frequency).
22 3. Time delay on engine starting-adjustable from 1-second to 300-seconds (factory set at
23 3-second)
24 4. Time delay normal to emergency transfer-adjustable from zero second to 300-seconds
25 (factory set at 1-second). The CONTRACTOR shall request time delay settings in
26 accordance with the priority rating or their respective loads.
27 5. Time delay emergency to normal transfer-adjustable 30-seconds to 30-minutes
28 (factory set at 5-minutes), and time delay bypass switch shall be provided on door of
29 the switch cabinet.
30 6. Unload running time delay for emergency engine generator cooling down adjustable
31 from zero to 5-minutes (factory set at 5-minutes) unless the engine generator control
32 panel includes the cool down timer.

33PART 3 - EXECUTION

343.1 INSTALLATION OF DIESEL ENGINE-DRIVEN GENERATOR SETS

35 A. Install diesel engine-driven generator units as indicated, in accordance with equipment


36 manufacturer's written instructions, and with recognized industry practices, to ensure that
37 engine-generator units fulfill requirements. Comply with NFPA and NEMA standards
38 pertaining to installation of engine-generator sets and accessories.

1 16230 - 10 of 12
2OCU Master CIP Technical Specifications rev: August, 2012
1 B. Coordinate with other work, including raceways, electrical boxes and fittings, fuel tanks,
2 piping, and accessories, as necessary to interface installation of engine generator
3 equipment work with other work.

4 C. Tighten connectors and terminals, including screws and bolts, in accordance with
5 equipment manufacturer's published torque-tightening values for equipment connectors.
6 Where manufacturer's torquing requirements are not indicated, tighten connectors and
7 terminals to comply with tightening torques specified in UL Standards 486A and B, and
8 the National Electrical Code.

9 D. Install units on steel spring type vibration isolators fastened to an inertia base in
10 accordance with manufacturer's instructions.

11 E. Connect fuel piping to generator equipment as indicated, and comply with manufacturer's
12 installation instructions.

133.2 GROUNDING

14 A. Provide equipment grounding connections for diesel engine-driven generator units as


15 indicated. Tighten connections to comply with tightening torques specified in UL
16 Standard 486A to ensure permanent and effective grounding.

173.3 FIELD QUALITY CONTROL

18 A. Start-up Testing
19 1. Engage local equipment manufacturer's representative to perform start-up and
20 building load tests upon completion of installation, with the County in attendance;
21 provide certified test record. Tests are to include the following:
22 a. Check fuel, lubricating oil, and antifreeze in liquid-cooled models for conformity
23 to manufacturer's recommendations under environmental conditions present.
24 b. Test prior to cranking engine for proper operation, accessories that normally
25 function while the set is in a standby mode. Accessories include: engine heaters,
26 battery charger, generator strip heater, and remote annunciator.
27 c. Check, during start-up test mode, for exhaust leaks, path of exhaust gases outside
28 the building, cooling airflow, movement during starting and stopping, vibration
29 during running, normal and emergency line-to-line voltage, and phase rotation.
30 d. Test, by means of simulated power outage, automatic start-up by remote-
31 automatic starting, transfer of load, and automatic shutdown. Prior to this test,
32 adjust for proper system coordination, transfer switch timers. Monitor throughout
33 the test, engine temperature, oil pressure, battery charge level, generator voltage,
34 amperes, and frequency.
35 (1) On generating sets exceeding 50 kW, a starting load test is to be performed
36 after installation. Voltage dip will be observed with a recording oscilloscope
37 furnished by supplier for this test only. Voltage dip is defined as the peak-to-
38 peak voltage minimum, at starting compared to the average peak-to-peak
39 voltage with the starting load running. The difference shall be less than 30%
40 of the running P-P voltage.

1 16230 - 11 of 12
2OCU Master CIP Technical Specifications rev: August, 2012
1 e. Upon completion of installation, demonstrate capability and compliance of system
2 with requirements. Where possible, correct malfunctioning units at Site, then
3 retest to demonstrate compliance; otherwise, remove and replace with new units,
4 and proceed with retesting. Initial testing and retesting to be at no cost to County.

53.4 PERSONNEL TRAINING

6 A. Operating Personnel Training: Train County's personnel in procedures for starting-up,


7 testing, and operating diesel engine-driven generator sets. In addition, train County's
8 personnel in periodic maintenance of batteries.
9
10
11

12 END OF SECTION