Diesel Generator

Operation and Maintenance Manual

HYUNDAI ENGINE Series


SafetyandWarning
Beforeoperationandmaintenanceforthegeneratorsets,pleasereadcarefullyaboutthismanualandmakesurea
goodunderstandingofthisoperationmanualandotherdocumentswhichattachedwiththeengine.

Correctinstallationofthegeneratorsetisthepreconditionofnormaloperation.Qualifiedsparepartsshallbeused
formaintenancetoensuregoodrunningconditionandlonglifeexpectancyofthegeneratorsets.

Thegeneratorsetshallbeoperatedonlybythestaffswhohavereceivedtrainingontheoperationandtherepair
shallbemadebytheauthorizedstaffs.Operatorandmaintenancestaffshallbeclearaboutsafetyandpreventive
actionsandoperationmaintenanceprocedure.

The generator sets can only be startedunder safety conditions.Please do notstart the generatorsets when any
abnormalconditionhasbeenfoundsothattoavoidaccidents.

Whenclean,maintainandrepairthegeneratorsets,pleaseshutdownthegeneratorsetandcutofftheconnection
ofnegativepolarofthebatteryordismantlebatteryconnectingcable,andplacewarninglabelattherelativeplace
sothattoavoidaccident.

The exhaustair discharged from engineis harmful for peoples health. All of the generatorsets installed indoors
shalldischargetheexhaustgastooutsidedoors.

Duringtheperiodofgeneratorsetrunning,theexhaustpipeandsilencerwillgeneratehightemperature.Therefore
whenthegeneratorsetisinstalled,thesepartsneedtobecoveredwithinsulationmaterialsandbekeptfaraway
frominflammablematerials.
Pleaseensuregoodventilationandorganizedenvironmentforthegeneratorsetsinstallationroom.
Pleasedonotplaceinflammablematerialsandexplosives(liquid)neartheengine.

Smoking,sparkover,andotherfirelightingbehaviorsarenotallowedintheareawhichisclosetothebatteryand
fuelbecausethemixtureofvolatilizationfromfuelandhydrogengeneratedbybatterychargingprocesswillcause
explosionwhenitmeetssparkleornakedflame.

The generator set installation room shall be facilitated with BC and ABC fire extinguisher, and operators shall be
familiarwiththeknowledgeonhowtouseit.

Whenfanprotectioncoverorotherprotectioncoverhasbeendetached,pleasedonottrytostartthegenerator
set; andwhenthegeneratorsethastobestarted, pleasedontputyourhandintheareawheretheprotection
coverismissingormakerepairaroundtheseareas.
Pleasekeepyourpalm,arm,longhair,jewelryandlooseclothesfarawayfrom beltpulley,beltandotherpower
transmissionparts.
Whenworkinginthegeneratorsetinstallationroom,pleasewareworkingclothes,glovesandhat.
Afterthegeneratorsetbeingstarted,pleasedonttrytoopenthecoveroftheradiatorbeforetheantifreezefully
cooleddown,sothattoavoidsteam(hotwater)burstforthtohurtpeople.
Please dont swallow or let your skin contact with the harmful materials such as fuel, antifreeze, lubricant and
electrolyte.Whenyouskinisspatteredwiththesekindsofliquids,pleaseuseplentyofwatertorinse.
Long time stay in high noise level environment will cause harm to your hearing. If you have to work around the
generatorsetfrequently,youdbetterwarethedevicetoprotectyourear.
When the generator set need to make cable connections to output power, the operation shall conform to the
condition, specification, standard related to power distribution. Qualified cable shall be used to make power
distribution.
Whentheinstallationofgeneratorsetinvolveswithwelding,pleasedonotconnecttothegroundcircuitormake
groundingthroughgeneratorset(engine)sothattoavoidthebigcurrentgeneratedfromweldingoperationhurt
theelectricappliance,bearingandbearingbushetc.insideofthegeneratorset.
Pleaseensurethesafetyofgeneratorsetandreliablegrounding.
Safetylabelsinformation
TRANSPORTWARNING

! Never lift the generating set by attaching to the


engine or alternator lifting lugs, instead use the
liftingpointsonthebaseframeorcanopy.
! Ensure that the lifting rigging and supporting
structure is in good condition and has a capacity
suitablefortheload.
! Keep all personnel away from the generating set
whenitissuspended.



MECHANICALWARNING

!Donotattempttooperatethegeneratingsetwith
thesafetyguardsremoved.Whilethegeneratingset
isrunningdonotattempttoreachunderoraround
the guards to do maintenance or for any other
reason.
! Keep hands, arms, long hair, loose clothing and
jewelersawayfrompulleys,beltsandothermoving
parts.

SAFEGUARDWARNING

! Generating sets that are not equipped with sound


attenuating enclosures can produce noise levels in
excess of 105 dB (A). Prolonged exposure to noise
levelsabove85dB(A)ishazardoustohearing.
! Wear protective clothing including gloves and hat
whenworkingaroundthegeneratingset.

!Ifequippedkeepaccessdoorsonenclosuresclosed
andlockedwhennotrequiredtobeopen.
!Avoidcontactwithhotoil,hotcoolant,hotexhaust
gases,hotsurfacesandsharpedgesandcorners.

CHEMICALWARNING

!Ensure that the generating set room is properly


ventilated.
!Keep the room, the floor and the generating set
clean.When spillsoffuel,oil,batteryelectrolyteor
coolant occur, they should be cleaned up
immediately.
!Neverstoreflammableliquidsneartheengine.
!Do not smoke or allow sparks, flames or other
sources of ignition around fuel or batteries. Fuel
vapors are explosive. Hydrogen gas generated by
chargingbatteriesisalsoexplosive.
!Neverstoreflammableliquidsneartheengine.
!Do not smoke or allow sparks, flames or other
sources of ignition around fuel or batteries. Fuel
vapors are explosive. Hydrogen gas generated by
chargingbatteriesisalsoexplosive.

ELECTRICALWARNING

! The generating set should be shutdown with the


batterynegative()terminaldisconnectedpriorto
attempting to connect or disconnect load
connections.
! Do not attempt to connect or disconnect load
connections while standing in water or on wet or
soggyground.

!Makesureconnectgeneratorsettoearth.

! Replace the generating set terminal box cover as


soon as connection or disconnection of the load
cables is complete. Do not operate the generating
setwithoutthecoversecurelyinplace.
! Connect the generating set only to loads and/ or
electrical systems that are compatible with its
electrical characteristics and that are within its
ratedcapacity.
! Keep all electrical equipment clean and dry.
Replace any wiring where the insulation is cracked,
cut, abraded or otherwise degraded. Replace
terminals that are worn, discolored or corroded.
Keepterminalscleanandtight.

! Do not touch electrically energized parts of the


generating set and/or interconnecting cables or
conductors with any part of the body or with any
noninsulatedconductiveobject.
Table of Contents

1 General Introduction 2.11 Power distribution system11

1.1 Brief Introduction1 3 Operation


1.2 Generator Set Main Parts Specifications1 3.1 Inspect Before Operation 12

1.4 Alternator 1 3.2 Generator sets running 12

1.3 Diesel Engine 1 3.3 After Running 13

1.4 Alternator 1 3.4 Record for running 13

1.5 Cooling System 2 3.5 Matters need attention 13

1.6 Electrical System 2 3.6 Operation for control system 14

1.7 Coupling 2 3.7 ATS control panel 16

1.8 Fuel Tank and Base Frame 2 4 Maintenance


1.9 Control Panel 2 4.1 General outline18

1.10 Optional for Canopy Generator Set 2 4.2 Engine 18

1.11 Others 3 4.3 Alternator 19

2 Installation 4.4 Control panel 19

2.1 General Outline 4 4.5 Start battery 19

2.2 Transportation 4 4.6 Maintenance record 19

2.3 Design for Foundation 4 5 Check for Malfunction


2.4 Design for Generator Set Working Room 4 5.1 General outline20

2.5 Installation of Generator Set5 5.2 Malfunction checklist 21

2.6 Cooling system 7


2.7 Lubricant system 8 APPENDIX
2.8 Fuel system8
2.9 Battery 10
2.10 Electrical Connection11
User manual

1GeneralIntroduction
1.1BriefIntroduction
HYUNDAI series diesel engine generator sets is the
core products of HYUNDAI Power Equipment
Manufacturing Co.,Ltd. Thanks to their good
performance, the generator sets are widely used in
the fields of construction, communication, banking
business, mining, leasing industry and other special
sites.Aswhatyouareexpecting,HYUNDAIgenerator
setsendeavortomeetyourneedsfortheconceptof
individual design through the excellent features of
more safe, more reliable and more clean. The
generator sets provided by HYUNDAI Power is
reliableandprofessional.Theadvantageoflownoise
level, energy conservation, and stable performance
hasmadeacredibleassuranceformanyenterprises.
Our generator sets supply the following power
service:
Continuousservice
Usedasmainpowersupplytogenerateelectricityfor
severalpurposes:motionforce,lighting,heatingetc.
Thegeneratorsetscancontinuerunningandallow10%
overloadfor1hourper12hoursundervariableload,
whichisusedforremotearea. NO NAME
Standbyservice
1 CONTROL PANEL
Used as standby power supply to provide continue
electricpowerfornoninvariableloads.Thegenerator 2 BUSBAR PANEL
set is suitable for the area where must ensure
3 LIFTING LUG
continue power supply, such as hospitals, industrial
facilities,airportsetc.Keepthegeneratorsetstandby 4 BASEFRAME FUEL TANK
state at any time and start to run when the mains
supplyisabnormal. 5 ENGINE
Emergencyservice 6 BATTERY
Used as auxiliary power supply to solve energy
interruptions that may cause serious problems to 7 RADIATOR
people, physical and /or financial damage or to face
8 ALTERNATOR
consumption peaks. The generator set can start in
short order to provide steady electric power for the 9 FUEL DRAIN OUTLET
loadswhenthemainssupplyhappenabnormity,and
10 FUEL LEVEL SENSOR\
switch to stop after the mains supply becomes
normal. Generally the generator set continues 11 ABSORBER
workingforseveralhours.
1.2GeneratorSetMainPartsSpecifications

1.3DieselEngine
Accordingtodifferentoutputpowerofthegenerator
sets,andcombinewiththeadvantageofeachmodel
ofdieselengineinaspecificrangeofpoweroutput,
HYUNDAIPowerchoosestheengineswithfirstclass
performance and high reliability. And furthermore,
HYUNDAI Power pay special attention to the
1
User manual

technical advantage of engines in the aspects of fittediftheywerespecified.


reducing exhaust gas, decrease fuel consumption
rateandgoodnoiselevelcontrol. 1.7Coupling
Engineandalternatorarefirmlyjoinedbyacoupling
1.4Alternator cone that guarantees theproper assembly coaxiality
AllofthealternatorschosenbyHYUNDAIPowerare Singlesupport machines are also used a special
single bearing selfexcitation brushless alternators flexiblediskisusedinplaceofaflexiblecoupling.
with the attributes of international top brand. By
citing Stamford alternator as an example, we can 1.8FuelTankandBaseFrame
illustratethefeaturesofouralternatorsasfollows: The engine and alternator are coupled together and
Four polar brushless selfexcitation, single bearing, mountedonaheavydutysteelbaseframe.Thisbase
insulationclassisHandprotectionlevelisIP22. frame includes a fuel tank with capacity of
Statorsarewoundto2/3pitch,whichcaneffectively approximately8hoursoperationundervariableloads.
eliminatestripleandcurbswaveformdeformationof The tank is complete with filling cap and fuel level
output voltage. When in parallel with the mains or gaugeandisconnectedbyflexiblejointstotheintake
other generator sets, this type of winding can piping and to the overflow piping containing fuel
effectively avoid excessive neutral currents and from the injector drain. Big capacity generator's fuel
reducesinductiveheat. tankisseparatefromgeneratorset.
Beforebeingassembled,rotorsneedtopassdynamic
balance testing. The improved damper reduces 1.9ControlPanel
voltagedeviationandheatunderunstableload. All models of HYUNDAI Power generator sets use
The exciter rotor output is fed to the main rotor highgradecontrolpanel.Thecoreofcontrolpanelis
through a three phase full wave bridge rectifier, the an imported digital diesel engine control module,
rectifier is protected by a surge suppressor against which has been facilitated with more complex
surges caused by short circuit or outofphase functions such as further monitors, demonstration,
paralleling. peoplemodule dialogue, distance communication
Automatic voltage regulator has the feature of andprotectionetc.
automatic load curtailment which is used to protect HYUNDAI Power generator set control panel use
the engine, and make it possible to add full load to steel plate structure, which ensures security and
the alternator at one time. Steady state voltage reliability,andthesurfaceofithasbeentreatedwith
adjusting rate can reach 1% (under certain static powder painting. The outside appearance is
requirements,steadystatevoltageadjustingratecan beautiful. Special lock has been used to fix it. It has
meet 0.5%). If PMG system is chosen, the motor beendesignedforeasymaintenance.
will have high starting capacity and the ability of
interference rejection for the deformed voltage
waveform fed by the main stator generated by
nonlinear load(such as silicon control DC electric 1.10OptionalforCanopyGeneratorSet
motor,UPSetc).
Telephone influence factor TIF<50, telephone
1.10.1Externalantifreezeaddinghole
Ourgeneratorsetshasbeenfacilitatedwithexternal
harmonic wave factor THF<2%the brushless style
antifreeze filling hole. When user intends to add
and high quality AVR ensures low interference with
antifreeze, He only needs to open the antifreeze
Radio.
filling hole on the roof of canopy and the radiators
1.5CoolingSystem pressure valve cap to directly add antifreeze to the
Theenginecoolingsystemiswatercooled.Thewater hole,andeasilywatchtheantifreezelevel.
cooledsystemiscomprisedofaradiatorapusherfan
and thermostat. The alternator has its own internal
fantocoolthealternatorcomponents.
1.6ElectricalSystem
Theengineelectricalsystemis12voltor24voltsDC,
negative ground/earth. This system includes an
electric engine starter, a battery and a battery
charging alternator. For DC 12 volts electrical system
onebatteryisgiven.For24voltsystemtwoleadacid
batteries are given. Other types of batteries may be
2
User mannual

1.10.2Lubricantdischaargeholewh
hichdirectlyy allso it can prevent the generator sets from be
eing
connecttooutside daamagedbyc coldwinterw
weather!
Our generrator sets have been facilitated with
lubricant diischarge valvve which co
onnect direcctly to
outside. Thhis lubricantt discharge valve is an
nother
humanized design feature of HYU UNDAI Pow wer. It
offers morre convenien nt operation for the users.
When you want to diischarge surrplus lubricaant or
change it, you can easily make itt by opening the
lubricantdisschargeballvalve.


1..11Others
Exxceptforab bovemention nedcompon nents,thedie esel
geenerator sett has other main compo onents such as:
baattery for start motor, battery cable, silencer,
co
orrugated pipe,
p exhau ust elbow, highefficie ency
viibration redu
uction unit, aand other allternative paarts,
su
uch as base frame type e fuel tank, daily fuel taank,
1.10.3Imprroveddesign on
nforeasytrransportatio caanopy,theluubricantused dbytheengineatfirsttime,
Our canopyy generator sets have been
b designeed for anntifreezeanndotherparttsspeciallyre equestedbythe
easy hoistinng and tran nsportation. Standard caanopy cu
ustomer etcc. For the e specific accessory paarts,
generator set
s is facilitaated with liffting hole on
o the please refer to generaator set paacking list and
base frame. For the smmall power generator setts, we co
ontract.
have design ned hoisting g lug on the canopy roo
of and
forklift opeening in the e base framme, which better
b
serves the needs of customers who have statiionary
power supp plier but nee
ed to move the generato or set
frequently.

1.11 Preheaater for gen


nerator set (Optional Spare
S
Part)
Ourgenerattorsethasb
beenfacilitate
edwithheatterfor
waterjackeet.Thepurpo
osetoinstallthepreheaateris
toensureth
hatthegeneeratorsetcannbestartedunder
low temperature and some emerg gency casess, and
3
User manual

Ensurefoundationslevelnessandsmoothness.
Ifpossible,wastedischargesinkcanbesuedsothat
2 Installation the waste oil can be discharged in a timely manner.
Cablechannelforgeneratorpoweroutputcableneed
2.1GeneralOutline tobereserved.
Correct installation of generator set is the Normally,concretefoundationisreliable,simpleand
preconditionwhichensurethenormalworkingstatus preferable. When pouring the concrete foundation,
ofthegeneratorset.Theworkingroomforgenerator pleasemakesurethesurfaceofconcreteisflat,and
set shall be designed specifically to meet the no scratch is allowed. Gradienter or similar
expectedfunctionsandmaintenanceoperations,and instruments need to be used during installation of
atthesametimethedesignofgeneratorsetworking generatorsetanditsexhaustsystem.
room shall conform to local governments laws and The design of foundation can refer to following
regulations on architecture, fire protection laws and calculation formula: (below is the diagram for diesel
otherapplicableregulations. generatorsetfoundation)
1.Generatordimensionlengthwidth:L1W1
2.2Transportation 2.Foundationdimensionlengthwidth:L2W2
L2=L1+400(mm)
During the period of shipment, protection shall be
W2=W1+400(mm)
made for the generator set. In addition, the
3.B=2M/(L2W2D)
generator set shall be tightly secured in the loading
B:Thicknessoffoundation
truck so that to avoid any vibration during shipment
M:Generatorsetweight
which will cause the generator sets components
L2:Lengthoffoundation
loosen and even damaged. During the process of
W2:Widthoffoundation
shipment of generator set, no people or other
D:DensityofConcrete(referto2322kg/m3)
material is allowed to place above thegenerator set
(FoundationdrawingRefertoAPPENDIXA)
so that to avoid damage to generator set caused by

weight.
When loading or unloading the generator set to the
truck,forkliftorhoistingdeviceshallbeusedtoavoid
thegeneratorsetbecometiltedorfelltotheground, 2.4DesignforGeneratorSetWorkingRoom
whichcausesdamage. Theinstallationofgeneratorsetshallbedesigned,so
Lifting holes have been designed on the common that to meet the demand of planned operation and
base frame of our generator sets. Some of the maintenance.Thecompleteinstallationshallconform
specifically designed generator sets has been to local architecture laws, fire protection laws and
facilitated with lifting holes on the roof and forklift other applicable regulations. Except the above
openingsonthebaseframeetc.Userscantransport matters, there are other matters needs your
thegeneratorsetaccordingtotheguidancespecified attentionasfollows:
on the specific labels sticked on the generator set. Ensuredieselenginegeneratorsetworkingroomis
Pleasedonotusetheliftinglugsontheengineoron furnishedwithrainproof,sunscreen,andwindproof.
thealternatortohoistthewholegeneratorset. Ensuredieselenginegeneratorsetworkingroomhas
2.3DesignforFoundation good ventilation and good exhaust system, and the
areaforventilationissufficient,andatthesametime
Thefoundationwhichusedtoinstallandfixthediesel use pipes to let out the hot air generated from the
generator set is very important, it must conform to radiatorandpreventthehotairfromreturning.
thefollowingrequirement: Ensurethewastegasgeneratedduringgeneratorset
Haveenoughhardnessandstability,sothattoavoid running period can be discharged to outside timely,
deformation, which will affect the concentricity of andtryyourbesttoreducetheadverseeffectcaused
diesel engine and alternator and other accessory to environment. The silencer and exhaust pipe shall
parts. be supported by the roof, the supporter shall allow
Tosupporttheweightofthewholegeneratorsetand the exhaust pipe to expand. It is not permitted to
toabsorbthedynamicimpactcausedbyunbalanced install the exhaust system directly on the generator
forceandvibrationduringenginesrunningperiod. set.
Generatorsetsfoundationisnotallowedtoconnect Enough space shall be reserved for the diesel
tootherarchitecturesfoundation. generator set for convenience of cooling, operation
The width and depth of foundation shall meet andmaintenanceetc.Generallyspeaking,noforeign
requirement. material is allowed to be placed within the area of
4
User manual

1~1.5 m of distance from the generator set and Softconnectionisneededtoconnectthepartsofthe


1.5~2mabovethegeneratorset. generator set to outside. For example: corrugated
The generator set working room shall be furnished vibration reduction pipe has been used to connect
with fire extinguish hydrant which conform to the exhaust pipes, air exhaust path, fuel inlet pipe, fuel
specifiedstandard. return pipe and busbar cable etc., all of these parts
Emergency lighting facilities shall be installed in the needtousesoftconnections.Onlyinthiswaywecan
generator set working room for the convenience of reducetheadverseeffectcausedbythevibrationof
operationandmaintenance. generatorsettotheminimumextent.
No combustible and explosive materials are allowed
2.5.2Ventilation
tobeplacedinthegeneratorsetworkingroom.
Whenageneratorsetwithacompletesetofradiator
Belowisthelayoutfortheopensystemgeneratorset
assemblyhasbeeninstalledintheworkingroom,the
workingroom.
basic principle is to discharge the hot air in the
(FoundationdrawingRefertoAPPENDIXB) working room to outside and let in the low
temperature air from outside, and try you best to
avoidthehotaircomeinfromoutside.
Thediagramintherightsidedemonstratestheideal
positionofageneratorsetintheworkingroom.
The purpose of this arrangement is to get cold air
fromthelowestpointasmuchaspossible,andforce
themtopassthroughtheradiatorcore,andthenlead
themout.
Note:

Our company can make drawings and design
installation dimensions for generator set working
roomaccordingtocustomersspecialrequirements.

Belowisthelayoutforthecanopysystemgenerator
setworkingroom.

(FoundationdrawingRefertoAPPENDIXC)

Users can use metal plate or canvas to make a wind
guide cover, the connection between wind guide
cover and the radiator shall be soft connection, so
Note: thattocutoffthetransmissionofvibrationfromthe
Canopied generator set can work outdoor directly. If generatorset,andalsoensurethehotairexhaustto
users wants to operate the generator set indoor, outsidethoroughly.
above diagram can be taken as reference. we can The effective circulation sectional area inside of the
designthelayoutofgeneratorsetworkingroomand wind guide cover shall be bigger than 1.25 times of
installationdimensionaccordingtocustomersspecial thefrontfaceareaoftheradiatorcore.Andthewind
requirements. guide cover shall be smooth, no sharp angle and
cambersothattoreducetheresistancetothewind.
2.5InstallationofGeneratorSet At the same time, the effective circulation sectional
areaintheairinletopeningshallalsobebiggerthan
2.5.1Locatethepositionofgeneratorset 1.25timesofthefrontfaceareaoftheradiatorcore.
Vibration reduction units have been installed on our Whentheusershaveinstalledmeshcoverorshutters
generator sets (except a few generator sets dont in the air inlet /outlet opening or there is too many
havethiskindoffacility).Userscantakereferenceon cambers in the air inlet/outlet opening, the effective
the installation diagram, correctly install the air circulation sectional area will be reduced and
generatorsetonaflatandhardfoundation,usethe resistance will increase, and therefore, its necessary
expansionboltstotightlyfixthegeneratorsettothe tofurtherincreaseaircirculationarea.
concretefoundationthroughtheinstallationholeson
the base frame. When no special requirement is
needed, we dont suggest customers to install
additionalvibrationreductionunits.
5
User manual

andsidestress.
Reserve some space for hot shrinkage and cold
expansion.
Reservespaceforgeneratorsetvibration.
Reduceexhaustnoiselevel.
Overload of exhaust backpressure will cause
followingadverseeffect:
Outputpowerloss
Fuelefficiencyreduce
Exhaustgastemperaturerise


Note:
When more than one generator set are installed, try
not to discharge all of the generator sets gas from
one exhaust path. If no separated exhaust pipe is
allowed, under the condition that the total
backpressurewillnotexceedthegeneratorsetstotal

Under normal conditions, the air volume generated backpressure a moveable separate panel shall be
from the radiators fan is enough to meet the installed inside of the branch exhaust pipe so that to
requirementoftheworkingroomventilation. preventthegasfromreturn.
Theairinlettemperatureoftheengineshallbebelow
30 degree Celsius. If the air inlet temperature keep
rising above 30 degree Celsius, the engines output In the exhaust system, soft corrugated pipe shall be
power will be reduced, and therefore fresh air from used to connect the exhaust pipe with the
outside shall be introduced into the generator sets turbocharger, this pipe has three functions as
workingroominatimelymanner. follows:
If the generator set is furnished with a remote Separate the diesel engine with vibration and the
radiator, forced air circulation for the generator set weightofexhaustpipe.
working room is a must. The forced air circulation Compensatetheheatexpansionofexhaustpipe.
need two fans, one fan is responsible for air intake, If the diesel generator set is installed on the
another is air exhaust, which exhausts hot air to antivibration base frame, the corrugated pipe can
outside. compensatesidewaymovementwhenenginestartor
Whentheengineisfurnishedwithpropelledfan,itis stop.
recommended that a separate pipe is needed to
exhaustthegaswhichgeneratedfromthecrankcase Note:
to outside. Otherwise the exhaust gas from the 1. Serious damage will occur when rainor condensed
crankcasewillaccumulateontheradiator,whichwill water enter into engines exhaust system.
cause the radiator stuck by dirty material, and as a Therefore, one water discharge opening shall be
result,theheatsinkingcapacitywillbereduced. installed in the long exhaust pipe, the position of
whichshallbeclosetothegeneratorset.
2. When the top of the exhaust pipe is above the
architecture, lightening protection is needed
2.5.3Exhaust (connecttotheground)
Our standard configuration diesel generator sets
provide accessories such as industry heavy silencer,
softcorrugatedpipeandelbowetc.Userscandesign
2.5.4Noisereduction
the exhaust system of generator set working room
Whendieselgeneratorsetisrunning,normallyitwill
by themselves. When design and install the exhaust
generatenoiselevelof90110dB,andthemorethe
system,pleaseconsiderthefollowingaspects:
load,thehigherthenoiselevel.
Ensurethetotalexhaustbackpressurenohigherthan
Inordertomeetthenoiselevelstandardsestablished
the maximum allowed value specified by the
bythelocalenvironmentalprotectionbureauandto
engine(usually generator sets maximum exhaust
prevent the noise pollution caused to ambient
backpressure is no more than 5Kpa) Fix the exhaust
environment, which will affect peoples normal life,
system to make sure the exhaust manifold and
to reduce noise level of diesel generator set is also
turbochargerarenotsubjecttotheverticalpressure
6
User manual

veryimportant. radiator,ensuretheantifreezewillnotfreezeunder
Noise reduction engineering is a comprehensive and low temperature. In the area when there is low
professional engineering. During the process when possibilityoffreezing,thecoolantcanbeamixtureof
users try to design the scheme for noise reduction water and antirust, according to the antirust which
project, at the same time please fully consider the recommendedbytheenginesupplierandrefertoits
bottom limit of air inlet/outlet volume needed by operation manual, mix the liquids in a separate
engines normal running and the maximum allowed container evenly and then add the mixture into the
value for exhaust backpressure etc. Otherwise, the radiator.Atthefirsttimewhenantirustisadded,the
noisereductionprojectwillseriouslyaffectgenerator generatorsetshallbekeptrunninguntilitgettohot
sets output power, and make generator set s sothattoachievethebesteffectofanticorrosion.
temperature rise, cause frequent malfunction of the
generator set, and even it will shorten the life Engines coolant shall have three functions listed as
expectancyofgeneratorset. below:
Provideenoughheattransmissioncapacity
Note: Prevent all metal material and sealing material
HYUNDAI Power can provide customers with overall within the cooling system from corrosion(Cave
soundproofgeneratorset. corrosion)
Providesufficientantifreezecapacity

2.6Coolingsystem Warning:
!Tochoosetheantifreezewhichisrecommendedand
Ourstandardconfigurationdieselgeneratorsetsare approved by the qualified engine supplier is the
closed cycling water chilling units with fan and criticalpointtoensureenginesnormalrunning.
radiator installed. Closed water chilling engine drive !Donotmixtheantifreezeandantirustofanytypes,
the cooling pump to generate circulation power, this will generate a large amount of bubble and
which keep the antifreeze in the paths of cylinder reducethecoolantsperformance.
body and cover continuous circulation and heat
elimination.Enginescoolingpump,radiator(orheat !Iftheantifreezeusedinthegeneratorsetisofbad
exchanger) forms a closed, pressure cycling and quality and not approved by the engine supplier,
coolingsystem. which cause the malfunction of the generator set
The most common cooling system is cooling fan (water leakage, contamination and etc.), this
directly driven by radiator and engine, which can be malfunction(s) does not belong to the scope of
replaced by heat exchanger, remote radiator or warranty.
remote cooling tower etc. If the installation position
of the remote cooling fan is relatively higher,
transmission radiator is needed to prevent the
2.6.2Changeofcoolant
damageofheatexchangercausedbytoobiginternal
Theeffectofantifreezeandantirustwilldecreaseby
pressure.
thetimeperiodofservice.Andthereforeperiodically

change of antifreeze is a must. The mixture of


Note:
antifreeze shall be changed in every two years. The
The dirty material stay in the radiators core will
mixtureofantirustshallbechangedatleastonetime
greatly affect radiators cooling capacity. And
every year. And if filter of the coolant is installed, at
thereforeitisnecessarytocleantheradiatoroften.
leastthisfiltershallbechangedineveryhalfofyear
(pleaserefertotheengineoperationmanualforthe
2.6.1Coolant specificintervalsofthechangesrequired).
Cooling system shall use the coolant which can When it is time to discharge the coolant, make sure
protecttheenginefromcontaminationandfreezing. thegeneratorsethasbeenshutdownandtheengine
Coolant shall be a mixture of pure water and hasbeenfullycooleddown,thenopentheradiators
antifreeze or pure water and antirust fluid. In this liquid adding hole. After that open the discharge
mixture, water PH value shall be between 68, valve installed in the radiator and in the engine
usually suggest to use distilled water. The specific respectivelytodischargethewater.Ifthegenerator
mixingratioshallbeaccordingtolocalweather,and set is furnished with coolant filter, it shall be
that of the coolant recommended by the engine detachedfromtheengineandbechanged.
supplier,andreferencetotheoperation(preparation)
manual of the coolant. Mix the liquids in a separate
2.6.3Cleaningofcoolingsystem
container evenly and then add the mixture into the
7
User manual

Whenchangethecoolant,cleaningisneededforthe pleaseopenthefiltersvalvebeforeputintouse.
cooling system, the cleaning procedures are
suggestedasfollows: 2.7Lubricantsystem
Emptythecoolingsystem Lubricant system is composed of oil pan, oil pump,
Usewatertorinsecoolingsystem strainer, oil pipe, oil cooling unit, oil filter unit, and
Feed 15%~20% condensed coolant to the cooling the oil path inside of the engine and all kinds of
system, timely run the generator set for one or two lubricantpartswhichareinrelativemotionetc. The
timesthendischargethecoolant main purpose of the lubricant system is to provide
Empty the cooling system then use normal mixed sustainedtemperedoilfilmbetweenthepartswhich
liquidtorinse areinmotionsothattoreducefrictionandwear,and
If contaminant still exists, then repeat the cleaning draws off part of the heat absorbed by the parts,
procedureuntilnocontaminantexistsinthesystem bath mechanical part, improve sealing effect and
After the system has been fully rinsed, feed new preventrustfromeachpartssurface.
coolantwhichhasbeenmixedaccordingtospecified Userscandeterminethemodeloflubricantaccording
proportion to the specific working environment and conditions.
For the first time lubricant, normally users shall
Note: change it within 100 hours upon and from the time
Ifthecoolingsystemiscleanedperiodically,onlyrinse whenthegeneratorsetfirststarted.(detailsreferto
it with small amount of additives or clean water is enginemaintenancemanual)
enough.
Note:
Thecriticalpointistousequalifiedlubricantoilwhich
2.6.4Feedingofcoolant is with proper viscosity and conform to the engines
Before adding coolant to the coolant system, please requirement,andperiodicallychangethelubricantoil
make sure the radiator s discharge valve and the and oil filter so that to ensure the generator sets
enginesdischargevalvearetightlyclosed. normal working. The malfunctions caused by wrong
Add the coolant to the system in a proper speed so modeloflubricantoilwithlowqualityorlongtimeno
thattoavoidaircockbeingformedinthesystem. change of lubricant oil, or oil filter do not belong to
Air shall be discharged through the adding hole or thescopeofwarranty.
thedischargevalveintheenginebody.Ifthecooling
systemisfurnishedwithheater,thecontrolvalvefor We recommend that high quality multi grade SAE
theheatershallbeopened.Ensureventilationofthe 15W/40 high service engine oil in diesel engines are
unitwhenaddingthecoolant. used. At ambient temperatures above 15 degree
Celsius is 15W40. The minimum API oil quality levels
Note: recommended for use is CH / CI4, CH or CI4 can be
The air discharge valve in the engine body shall be used in areas where CF4 oil is not yet available, but
locatedinthetoppointofthewaterpathornearthe the oil interval must be reduced API CA, CB, CC, CD,
thermostat or water temperature sensor, or you can CE,CG4categoriesnotrecommended,donotuse.
slightly loose the water temperature sensor and
retighten itwhen you see coolant run out from it so
thattodischargetheair.

When adding the coolant, the surface of liquid shall 2.8Fuelsystem


reach to the level that is 5 centimeters below the Our generator sets requires the fuel diesel shall be
radiators welded surface (or shall reach the level clean, without air and water and with proper
indicating Line). Be sure that the generator set has pressure, of which all kinds of parameters such as
stopped and become fully cooled before adding sulphur content etc. shall meet national standards,
Coolant. Before the system is capable of ventilation and end use temperature grade meet the
and the liquid is added to the required level, please requirement of customers working environment.
dontstartthegeneratorset.Afterthecoolantbeing Generally generator sets fuel system includes two
fed,pleasestartandpreheatthegeneratorset,and parts, that is, engines fuel system and external fuel
at the same time check the liquid level and add system. HYUNDAI is only responsible for installation
coolant if needed. The coolant which needs to be of the external fuel system which includes fuel tank
added to the radiator shall be of the same andconnectingfuelpipesetc.
specificationasthatexistingintheradiator.
For some generator sets installed with coolant filter, 2.8.1FuelRecommendations
8
User manual

The following fuel oil specification is typical. For a


specific engine refer to manufacturers data sheets
forfueloildetails. 2.8.2Fueltank
FuelRecommendedPhysicalPropertiesFeature Ourgeneratorsetsprovidebaseframestylefueltank
Viscosity for customer. The base frame style fuel tank is
1.3to5.8centistrokes(1.3to5.8mmpersecond)at40C(104F) installed with fuel tank, fuel pipes and fuel level
(ASTMD445) indicator. This fuel supply system does not need
CetaneNumber customertomakeotherinstallations.Customersonly
40 Minimum above 0C (32F) ~45 Minimum below 0C (32F) needtoaddfueltothebaseframe.
(ASTMD613) Users who intend to self manufacture the fuel tank
SulphurContent shall use stainless steel or steel plate to make the
Nottoexceed0.5masspercent*(ASTMD129or1552)
backup tank, do not make painting or galvanization
ActiveSulfurCopperStripCorrosion
inside of the fuel tank so that to avoid the possible
NottoexceedNo.2ratingafterthreehoursat50C(122F)
(ASTMD130) chemical reaction between these kind of materials
WaterandSediment anddiesel,whichmaygeneratethematerialharmful
Nottoexceed.05volumepercent(ASTMD1796) to the generator set and decrease the quality, Merit
CarbonResidue Rating and combustion efficiency of diesel. In
Not to exceed 0.35 mass percent on 10 volume percent addition,theconfigurationoffueltankassemblyshall
residuum(ASTMD524orD189) beasfollows:
Density Airventilationpipeabovefueltanksurface
42to30APIgravityat60F(0.816to0.876g/ccat15C).
Manholeonthetopsurfaceoffueltank
(ASTMD287)
CloudPoint Watchwindowforfuellevel
6C(10F)belowlowestambienttemperatureatwhichthefuel Dischargevalveatthebottomoffueltank
isexpectedtooperate(ASTMD97) Groundcablebetweenfueladdingholeandfueltank
Ash Separate panel with holes between fuel supply area
Not to exceed 0.02 mass percent (0.05 mass percent with andfuelreturnarea,sothattoreduceheatexchange
lubricatingoilblending)(ASTMD482)
Theendoffuelsupplypipeshallbe50mmabovethe
Distillation
bottom of base frame so that to avoid the deposit
The distillation curve must be smooth and continuous (ASTM
D86) and water at the bottom of fuel tank being sucked
AcidNumber intofuelsupplypipe.
Nottoexceed0.1MgKOHper100ML(ASTMD664) Part of the generator sets fuel level shall be higher
Lubricity thanthepositionoffuelinjector,sothattoavoidfuel
3100 grams or greater scuffing BOCLE test or Wear Scar returnfromfuelinjector,whichcausestartdifficulty.
Diameter(WSD)lessthan.45mmat60C(WSDlessthan.38mm
at25C)asmeasuredwiththeHFRRmethod.
2.7.2Installationoffueltank
DieselFuelPropertyDefinition The position of the fuel tank shall ensure the
Ash Mineral residue in fuel. High ash content leads maximumsuctionfuelheadisnolessthan2meters.
to excessive oxide build up in the cylinder and/ or Suction fuel head of the fuel transfer pump shall be
injector. calculatedfromthebottomofthefueltank.
Cetane Number Ignitability of fuel. The lower the The position of the fuel tank shall ensure maximum
cetan number, the harder it is to start and run the returnfuelheadnolessthan1.5meters.Returnfuel
engine.Lowcetanefuelsignitelaterandburnslower. head shall be calculated from the top of the base
This could lead to explosive detonation by having frame.
excessivefuelinthechamberatthetimeofignition. Thearrangementofthefuelpipeshallavoidthefuel
Incoldweatherorwithprolongedlowloads,ahigher being affected from the heat elimination from
cetanenumberisdesirable. generatorsettoomuch.
SulphurAmountofsulphurresidueinthefuel.The The maximum temperature of the fuel before fuel
sulphur combines with the moisture formed during pumpshallbelowerthan60degreeCelsius.
combustiontoformsulphuricacid. Noleakageoffuelandairisallowedinthefuelinlet
Viscosity Influences the size of the atomized andfuelreturnpipe.Thisisveryimportant.
dropletsduringinjection.Improperviscositywilllead Hose need to be used to connect generator set with
todetonation,powerlossandexcessivesmoke.Fuels fuel transfer pipe. If the generator set use soft
that meet the requirements of ASTM or 2.0 diesel connection (through vibration reduction unit), hose
fuelsaresatisfactorywithfuelsystems. shallbeused.

When engines fuel inlet pipe is above 6 meters and


9
User manual

below10meters,thisfuelinletpipesinsidediameter controlledlocallybymanual,andalsocanbestarted
shall be at least 20% bigger than that of the hose orstoppedbyremotecontrol(controlledbyexternal
installed in this engine. Fuel return pipe shall be signalline)usersarerequiredtocorrectlyconnectthe
connected to the top of fuel tank. Dont directly signal line to this control panel.(details see the
connectittofuelinletpipe. controlpaneloperationmanual)
Automatictransferpanel(optional):istheautomatic
transfer switch for transfer between generator set
and mains.(details refer to control panel operation
manual)

2.9Battery
Our generator set standard configuration provides
start battery as accessory parts. According to users
different requirements, our company can provide
2.7.3Fuelconsumption
twotypesofbatteries,thatishighefficientplumbous
Thecontentofdieselplaysaverycriticalroleindiesel
acidbatteryandmaintenancefreebattery.
engines performance, life expectancy and the
If maintenance free battery is used, users only need
content of discharged material. In order to achieve
toconnectcablesforthebattery.
the rated power, fuel economy and specified
If plumbous acid battery is used, before being used,
emission standard, only the fuel which refer to
users need to use standard battery to electrolyze
international standard or national standard can be
primary liquid. Untighten the battery cover, slowly
used.
pourelectrolyteintothebatteryuntiltheelectrolyte
The parameters of diesel fuel include low
level reach the indicating line in the internal polar
temperaturefeature,sulphurcontent,specificgravity,
plates(notallowtoexceedthisline),thentakeoffthe
water content and foreign material content shall be
lable from the battery covers air hole and close the
thefirstprioritywhenuserneedtochoosethequality
cover.Aftertheelectrolytebeingadded,pleasedont
ofthefuel.Differentqualityoffuelwilldirectlyaffect
use it immediately, keep the battery in static status
dieselgeneratorsetsstart,lubricating,outputpower,
for thirty to sixty minutes. In low temperature
discharge,andfuelfilterchangecycleetc.
environment, this time period need to be extended
Specific requirement for fuel please refer to engine
(use battery charger to charge battery when
operationmanualwhichattachedwiththegenerator
necessary)
set.
Users can use the standard connecting cable

attached with the generator set, the red color shall


Warning:
be connected to positive polar, black (or blue) to
! When you intend to add fuel into the fuel tank,
negative polar, correctly connect to the generator
pleasemakesurethegeneratorsethasbeenstopped.
setsstartmotor.Mostofthedieselgeneratorsets
Only after the added fuel become static for some
cables have been connected to the engines before
time, this generator set can be started again. This
shipment.
way to avoid the foreign material in the diesel fuel

being sucked to fuel supply hose, which will cause
The energy storage capacity of the start battery will
fuel filter stuck and fail to supply engine with
determine if the diesel engine generator set can
sufficient fuel, and in turn decrease the output
smoothly start in a specified period. During the
power.
process of generator sets running, the charging
! The malfunction caused by bad quality of fuel does
alternator installed in the engine will continuously
notbelongtothescopeofwarranty.
chargebatterytostartbattery.

2.8Controlsystem Warning:
Our diesel generator sets has been furnished with ! Please ensure the connection for positive and
control panel. All of the control panels choose negative polar is correct. Wrong connection will
importeddigitalmeterasthecoreofcontrolsystem cause malfunction! (Wrong connection will surely
forthegeneratorsets. causedamagetothechargingalternator)
Digital control panel: the generator set can be !Whengeneratorsetisrunning,batterycablesarenot
allowedtobecutdown!
10
User manual

out with temporary links or disconnected. Any


controlwiringmustalsobedisconnected.
A500VMeggerorsimilarinstrumentshouldbeused.
Disconnect any earthing conductor connected
2.10ElectricalConnection between neutral and earth and megger an output
Only full qualified and experienced electrical terminaltoearth.
technicians should carry out electrical installation, Theinsulationresistanceshouldbeinexcessof1M
serviceandrepairwork. toearth.Shouldtheinsulationresistancebelessthan
1Mwindingmustbedriedout.
Warning:
! Make electrical connections in compliance with
relevant electrical codes, standards or other 2.11Powerdistributionsystem
requirements.
Ourdieselenginegeneratorsetusethreephasefive

line system for power distribution. That is, three


2.10.1Cabling phase live wires, one neutral line, one ground line.
Due to movement of generating sets on their The neutral line and the ground line are not
vibrationmounts,theelectricalconnectiontotheset connected. Users can choose three phase four lines
should be made with flexible cable. The cable must forpowerdistributionaccordingtorequirementthat
be suitable for the output voltage of the generating is to connect the neutral line to the ground (base
set and the rated current of the set. In determining frame),sothattosolvetheproblemoffeintthatthe
the size, allowances should be made for ambient neutrallinesometimesiselectriferous.
temperature. Method of installation, proximity of
othercables,etc.Allconnectionsshouldbecarefully Note:
checkedforintegrity. HYUNDAI Power series diesel engine generator sets
Currentcarryingcapacityofpowercablesthatwillbe require users to safely connect generator sets and
given in APPENDIX A. On the other hand, there is a baseframestotheground,pleaserefertotheground
onemoreimportantpointwhilecablecrosssections labelforconnectingpoint.
arebeingselected.Ifthedistancebetweenloadand
generator is too length, voltage falling at the load
side can be too much at the transient current
duration. The voltage drop across a cable can be
determinedasfollows:
3 L I Rcos Xsin )
U
1000
U Voltagedrop(V)
L Lengthofconductors(m)
I Ratedcurrent(A)
R Resistance(/kmtoVDE0102)
X Reactance(/kmtoVDE0102)

RefertoAPPENDIXECableCurrentloadstandard.
2.10.2Grounding/EarthingRequirements
The frame of the generating set must be connected
to an earth ground. Since the set is mounted on
vibration isolators, the ground connection must be
flexible to avoid possible breakage due to vibration.
Ground connection cables or straps should have at
least full load current carrying capacity and meet
applicableregulations.

2.10.3InsulationTest
Before starting the generating set after installation,
test the insulation resistance of the windings. The
Automatic Voltage Regulator (AVR) should be
disconnected and the rotating diodes either shorted
11
User manual




3.2.3Start
3Operation Part of the generator set control panel has been
furnishedwithidlespeed/fullspeedtransferswitch,
3.1InspectBeforeOperation userscanchooseiftheengineneedtobestartedin
After finished installation, our diesel engine idlespeedorinonetimefullspeed.Usuallythetime
generator set can be put into use. Each time before period for idle speed shall not exceed five minutes.
starting the generator set, following items shall be Do not run the generator set in idle speed in a long
checkedwithoutfail: timeperiod.
If there is foreign material exists in the surface of Press on the start button, the duration shall not
generator set or in the ambient environment which exceed30seconds,enginewillbestartedbythestart
mayhamperthegeneratorsetsoperation. motor.Assoonastheenginebestartedsuccessfully,
If the air inlet and ventilation path in the generator you can release the start button and the generator
setworkingroomisexpedite. setwillenterintorunningstatus.
Iftheantifreezelevelisnormal.
Suggestion:
Iftheairfilterindicatorworkswell
Inordertoextendthelifeexpectancyofstartbattery
Ifthelubricantleveliswithinthespecifiedrange
andstartmotor,thedurationforonetimestartshall
Ifthefuelvalveisopen,ifthefuelhasbeensupplied
becontrolledwithin5to10seconds.Ifonetimestart
totheenginenormally.
fails, stop for some time and begin the second time
If the cable has been connected to the battery in a startprocedure.
correctway.
Checkiftheloadequipmenthasbeenwellprepared. For the control panels which are installed with
Whenthegeneratorsetdirectlyconnectstotheload, selfstart(or communication) instrument, the
theairswitchshallbecutoffbeforestart. generator set preheating, startup period and
starting times have been controlled by the program
Warning: (this program can be set and modified by user).
Operators shall establish good operation Operation procedure please refers to operation
(maintenance) procedure, this is the precondition for manual.
generatorsetssmoothrunninginlongtimeperiod. When the generator set control panel has
malfunction(s), timely overhauling is needed before
Restartthecontrolpanel.

Warning:
3.2Generatorsetsrunning Foranystartupwhichismadethroughforce,notby
3.2.1Preheat control panel, the malfunction caused by it do not
For the generator set which is installed with belongtothescopeofwarranty.
preheater,operatorsneedtodecideifpreheatingis
needed before start the generator set according to 3.2.4Running
environmenttemperature.Thecontrolpanelwhichis When the generator set begins full speed running,
installedwithpreheatswitchcaninstructtheengine and the alternators voltage and frequency becomes
tostartthepreheatersothattoachievethepurpose normal and stable, operators can put the generator
ofpreheating. setintonormalrunning.
Duringthegeneratorsetsrunningperiod,operators
shalloftenwatchandchecktheparameterssuchasif
3.2.2Connecttopower the generator set is running normally, if the control
TurntheairswitchinthecontrolpanelfromOFFto panelinstrumentisindicatingtherightposition,ifthe
ON, watch the panel until the background light controlpanelhasprewarningindication,andthefuel
turn on, that means the control panel has been levelinthebaseframeetc,andmakerecordforthe
successfully connected to the power. At the same parameters.(seeattachfile)
time make sure the fuel pipes are open, and the
speed governor or the control unit in the electronic 3.2.5Emergencystop
fuelinjectiongeneratorsetisunderworkingstatus. In case the generator set was found to have severe
12
User manual

malfunction or power distribution malfunction. downetc.


Please press down the emergency stop on the
controlpanel,sothattoimmediatelyshutdownthe Only when the correct and complete record for
generatorset.Undernormalcondition,pleasedonot running (maintenance) has been kept very well, the
useemergencystoptostopthegeneratorset. user can get correct and excellent after sales
(warranty)service.
3.2.6Normalstopthegeneratorset
Before stop the generator set under normal 3.5Mattersneedattention
condition,firstseparatetheloadfromthisgenerator
Warning:
set, then run the generator set with no load for a
! When engines temperature is very low, the time
certain period of time(3 to 5 minutes), so that to
period for idle speed shall be properly extended.
make sure the generator set become fully cooled,
However,whenthegeneratorsetbecomewarm,itis
after that the generator set can be stopped. (Please
notallowedtorunthegeneratorsetwithidlespeed
donotmakecoolingrunningunderidlespeed)
foralongtime,itisnotallowedtocontinuouslyrun
For some generator sets which have been installed
the generator set under empty or small load. Such
with stop solenoid, it is impossible to stop the
kindofoperationwillcauseservercarbondeposition
generator set by cutting off the key switch on the
and oil leakage in engines turbocharger and
controlpanel.Correctoperationis:topressthestop
exhaustsystem.
button when the power of the control panel being
! It is not allowed to run the generator set with
resumed,onlyinthiswayyoucanstopthegenerator
overloadinlongtimeperiod,otherwisemalfunction
set.(press the stop button until the generator set
willoccur,whichwilldecreasethegeneratorsetslife
fullystoprunning)
expectancy.
3.3AfterRunning ! It is forbidden to detach or change the components
ofthegeneratorsetwhenitisrunning.
After the generator set stop running, it is necessary ! The coolant which is going to be added need to be
tocarryonfollowingjobs: thesamespecificationasthatoftheoriginalcooling
To check if the generator set has three leakage system.Whenopenthecoverofwateraddinghole,
(lubricant,fuel,antifreezeleakage) please pay attention to the temperature and avoid
Shutdownfuelvalve thesteamorhightemperaturecoolantburstforthto
Shut down air inlet and air exhaust facility in the hurtpeople.
generatorsetsworkingroom(whennecessary) ! When discharge the high temperature lubricant oil,
Shutdownthegeneratorsetsoutputairswitch pleaseavoidbeingburnt.
Shutdownthepowerkeyswitchonthecontrolpanel, ! The fuel being used shall be conform to national
takeoutthekeyandkeepitingoodcondition(when standard, otherwise it will cause malfunction of the
necessary) enginesfuelpumporfuelinjector.
Whenthegeneratorsetneedtobeshutdownfora ! For the engines installed with turbocharger, it is
longtimeorisundermaintenance,pleasedisconnect suggested not to add 50% or above instant load to
the start batterys negative polar cable, and fully thegeneratorset.Otherwisethiswillcauserelatively
discharge the fuel and antifreeze liquid when bigstalltothegeneratorset.
necessary. !Forthelargeelectricityconsumptionequipment,itis
For the selfstart generator set, some of the above suggested that the users need to use methods such
terms are not applicable. After the selfstart as voltage decrease and frequency change etc. to
generatorsetstops,pleasekeepitinthesamestatus controlthestart,sothattoreducebigimpactonthe
asthatofprestart(readytostart),sothatitcanstart generatorsetwhenthefacilitystart.
atanytimeunderemergencycases. ! Backup generator sets or the generator sets which
haventbeenrunforalongtime,itissuggestedthat
thesekindsofgeneratorsetsshallberuntoworking
3.4Recordforrunning temperatureatleastonetimeamonth.Thesekinds
of generator sets need to be continuously run with
For each running operation, user shall make record.
fullloadfor4hoursatleastonetimeperyear.
Runningrecordhasvariousforms.Thebasiccontent
! For the generator sets which are connected in
shall cover: the time period for this running,
parallel and controlled by manual, operators must
accumulated running time for this generator set,
make sure they are running synchronously(same
value of engines oil pressure gauge, temperature
frequency, same phasesequence, same phase, and
meter, output voltage, frequency, maximum
samevoltage)beforeswitchon,andmustswitchoff
power(current)etc.andtherunningsituation,andif
before trying to stop the generator sets group.
thereisanymalfunctionwarning/generatorsetshut
13
User manual

Duringthegeneratorsetsgrouprunning,pleasekeep
watching to avoid the generator sets group stop
running because of individual generator sets
malfunction.

3.6Operationforcontrolsystem
3.6.1Generatorcontrolpaneloperation
Our generator set standard supply two different
control module: one is single generator with remote
start function, the other is single generator with

AutomaticMainsFailture(withATSpanel).
Startupgenerator NO Model
1) Set every circuit breaker and switch of loads to 1 startpanelpowerswitch
OFF position. 2 batterychargerswitch
2) Turn the Generator set Main Circuit Breaker and 3 fuse
othercircuitbreakerstothe OFF position. 4 batterycharger
3)Connecttheenginebatterycablewithbattery. 5 controlmodule
4)Turnonthepanelpowerswitch1S1(Ref. Appendix 6 electricgovernor
Dcircuitdiagram)tothestartposition.
5)Pressthemodulestartbutton.
6)Ifgeneratorsetassemblepreheater(airintakeor 3.6.2Generatingsetcontrolsystem
water preheater). The Preheat engine will To control and monitor the generating set, an
illuminate on module LCD. Preheating time varies electronic control system has been used. P10/16
by coolant temperature. Usually water preheater model control system is fitted from 10 kVA to 2000
completes in about 60 seconds, air intake KVA single generator set running system. P20/25
preheatercompletes10seconds.Afterpreheating control system is fitted from 10 kVA to 2000 kVA
theLCDputsoutandtheenginebeginstostart.It transfer with mains power. Control panel provides a
willattempttostartagainabout5secondslaterif means of starting and stopping the generating set,
theenginefailstostart. monitoring its operation and output and
7) After the engine starts successfully, allow the automatically shutting down the set in the event of
engine to warm up for about 5 minutes. If the critical condition arising such as low oil pressure or
enginecouldnotfireduringthepresetnumberof highenginetemperature.(DSEControlsystemplease
attemptstostart(startattemptsnumber:3times), readtheDSEusersmanual)
the Alarm LCD would flash. If you need to restart, P20/25controlsystemmoduleintroduction
waitatleast30secondsbeforetheretry.
8)CheckthereadingofVoltageMeterandFrequency
Meter by operating the Voltmeter ChangeOver
Switch. Once the generator set is running at the
correctvoltageandfrequency,TurntheGenerator
setmaincircuitbreakerto ON.
9) Turn on every switch or circuit breaker of loads
(fromheavytolightloadinsequence),sendpower
totheloadside.
Controlpanelintroduction


MainfunctionofP20/25
The control system of diesel generator set is
developed through the use of model AMF20/25
module, a special diesel controller, made by Czech
COMAP Company. This module is mainly used for
auto/manual startup, protective stop and
manual/autoswitchoverthegeneratorsetpowerand
mains power. It can also remote
14
User manual

control/measure/monitor generator set through When the power supply LED is light means AMF
computer. The AMF20/25 panel has a LCD to display controller is active, then user can select operation
generator set parameters, and has type(OFF/MAN/AUTO/MEASUREMENT)
OFF/MAN/AUTO/MEASUREMENTmode. A.OFFmode
Start;stop;mainspoweron/off;generatorsetpower
IntroductionofpushbuttonandLEDintheAMF20/25 on/offisinactiveinthismode
controlpanel B.MANmode
1.Startup Starttheengine. 1.Pressstartpushbuttontostartengine
2.Stop Stoptheengine. 2.Whenoutputvoltageisinthesetrange
3.Reset Cleanfailureandalarmstate. a.Pressmainspoweron/offpushbuttontoturn
4.Hornreset Deactivatesthehorn ontheswitch
5.Modeleft b. Press mains power on/off pushbutton, the
Changethegeneratorsetmode. switchwillbeturnedon,otherwisenotifthe
lefthanded(MEASUREMENTAUTOMANOFF) outputvoltageisnotingear
6.Moderight 3.Pressgeneratorsetpoweron/offpushbuttonto
Change the generator set mode lefthanded. turnontheswitch
(OFFMANAUTOMEASUREMENT) 4. Press mains power on/off pushbutton, the
7.Generatorsetpoweron/off switch will be turned on, otherwise not if the
Manualgeneratorsetpowerswitch. mainspowervoltageisnotingear.
8.Mainspoweron/off 5.Pressstoppushbuttonforawhiletostopengine
Manualmainspowerswitch. C.AUTOmode
9.Generatorsetpowerfault 1.Whenmainspowerisconfirmed
Red LED flash, generator set power fault. After a.Controllerturnsonthemainspowerswitch
pressresetpushbutton,redLEDlight(stillfaultand b. Controller start engine after emergency
alarm)orno(noalarm). startingupdelay
10.Generatorsetpoweringear c.Ifmainspowercomesbackduringthestartup
GreenLEDlight. period, controller will turn off the mains
11.Connectgeneratorsetpowerpresent power switch and stop engine after switch
GreenLEDlight,generatorsetoutputswitchison, delay
otherwisethegreenLEDflash. 2. After engine rotate speed is higher than the
12.Connectmainspowerpresent lowestsetvalueinmaximaldelay,controllerwill
Green LED light, mains power switch is on, turn on the generator set power switch,
otherwisethegreenLEDflash. otherwisecontrollerwillalarmandstopengine
13.Mainspoweringear 3.Aftermainspowercomeback
GreenLEDlightmeansmainspowerisingearand a. Controller will turn on the generator set
hastherightvoltage. powerswitchafterthemainspowercomebackdelay
14.Nomainspower b.Controllerwillturnonthemainspowerswitch
Red LED flash means no mains power and afterthegeneratorsetpowerdelay.
generator set is not running; red LED light, means c.Cooldownandstoptheengine
generatorsetisrunningandmainspowerisactive D.Alarm
butnotconnect. User can activate alarm list in the last display of
15.LEDSpresent MEASUREMENTmenu,SelectMEASUREMENTmenu,
16.Page Displaymenu(calculatesethistory). pressUPbutton,youwillseeallactivealarmnumber
17. Up Page up selection, select screen or add set in the left upper LCD. All active alarm is in shadow
value. otherwiseisnot,andalsonotconfirmed.
18. Down Page down selection, select screen or Press reset button to confirm all alarm, all inactive
minishsetvalue. alarm will be canceled at once, If a new alarm
19.Enter Confirmselection. happens,thisactivealarmwillbedisplayinLCDandis
activestateinmainmeasurementscreen.

P10/16controlsystemmoduleintroduction
Checkparameter
A. Press page push button several times to select
MEASUREMENTmenu
B.UseUP/DOWNpushbuttontocheckthedetail
Operationandapplication
15
User manual

3.7ATScontrolpanel
3.7.1ATSpanelgeneralintroduction
Our customer will need this ATS if generator set is
usedforselfstartstandbypower.Inordertoachieve
full automatic transfer between mains power and
generator set power to guarantee all load present,
ourATSpanelselectthebestATSforallgeneratorset.
And to the most possibility to serve our customers
demand,wepreparetwotypesofATS:MRSandAMF.
Besides MRS and AMF can be jointed to a double
standbyATSafteralittlechange,whichisusedfor2
generatorsetsworktogetherstandbymainspower.
Please reference relevant details of ATS for its
IntroductionofAMF10/16controlmodule function,application,operationandsoon.
IntroductionofiLMRS10/16controllerpanelasfollow

1.Startup.Starttheengine.
2.Stop.Stoptheengine.
3.Reset.Cleanfailureandalarmstate.
4.Hornreset.deactivatesthehorn SaftyAttention:
5. Mode left. Change the generator set mode !Weareverypleasureforyoursupportofourproduct,
lefthanded(MEASUREMENTAUTOMANOFF) before you use our ATS please read this instruction
6. Mode right. Change the generator set mode carefully.
lefthanded.(OFFMANAUTOMEASUREMENT) We mark three attention parts in accordance with
7.Generatorsetpoweron/off.Manualturnon/offthe differentsituation:
generatorsetpowerswitch Danger:
8.Generatorsetfailure:redLEDstartsflashingwhen !Ifyoudowrongaction,Personaldeathorotherbig
generatorsetfailureoccur.Afterfaultresetbutton disastermustbehappened.
is pressed, goes to steady light (if an alarm is still
active)orisoff(ifnoalarmisactive) MovingAttention
9. Generator set voltage present: green LED is on, if Danger:
genvoltageispresentandwithinlimits ! When you move ATS by crane or elevator, dont
10.Connectgeneratorsetpowerpresent.GreenLED standbeneaththeATS,toavoidpersonaldeath.
light,generatorsetoutputswitchison,otherwise
thegreenLEDflash. InstallationAttention
11. Page. Cyclic selection of the display mode Attention:
(measurementadjustment) !Alloperatorsmustbeprofessionalelectrician.
12. Up. Select the set point, select the screen or !Cutoffallpowerbeforeinstallation.
increasesetvaluepoint !FixscrewinaccordancewithTORPUEstandard.
13. Down. Select the set point, select the screen or !PlaceATSonplaneinverticaldirection.
decreasesetvaluepoint !DontinstallATSintheenvironment,wherearehigh
14.Enter.Confirmthesetpointvalue temperature,humidororfilledwithcorrosiongas.
Introductionoffunctionandoperation !ConnectneutralpolewithNpolewhileyouinstall
MRS10/16 selfstart control module is low a level to 4polesofATS.
AMF20/25 control module, it is a single module
without mains power measurement function, and OperationAttention
also has less I/O terminals than AMF20/25. Besides, Danger:
their other function and operation are similar or ! Dont connect energized main circuit or control line
same. withterminal.
Attention:
!IfATSistripping,cutoffpowersource,findproblem
andsolveitatfirst.
Our company supply ATS panel should use for AMF
series generator control module, from the diagram
youcanseeitisveryeasytoconnectcableandeasy
install ATS panel. Our panel can use in AUTO or
16
User manual

MANUALstatus.
Manualstatusoperation:
Step1
Youshouldcheckthegeneratorcontrolmodulesetin
MANUAL status, then use the operate handle insert
theswitchaxis.


Step2
Operatingdirectionofthearrow
No MODEL
1 ATSswitch
2 panellock
3 mainspoweroutputhole
4 generatorpoweroutputhole
5 communicatewithgeneratormoduleport
6 loadpowercableoutput
Step3
7 panelongroundleg
CheckthepositiononAorB.
Maintenance,inspectorexchangepartsattention:
Attention:
!Alloperatormustbeprofessionalelectrician.
!TurnswitchonOFFposition,makesuremainline
orcontrollineisntenergizing.
! When you want to inspect inside part, make sure
AUTOstatusoperation powerABisoff,toavoidfingerinjury.
You can connect the special cable connector with !Fixscrewofterminalinelectricalway.
generator set. Then set the generator module in
AUTO,that is OK!(detail operate step refer module
controlsystem)
ATSPANELintroduction

17
User manual

4 Maintenance For each 50~600 hours of running or at least each 12


months
!Changelubricantandlubricantfilter
4.1Generaloutline !Becausethequalityoflubricantoil,sulfurcontentof
For different types of generator sets, users need to the fuel, and lubricant consumption rate of each
refer to the matched engines operation and engine is different, the interval for lubricant oil
maintenance manual to implement correct changeforeachgeneratorsetwillbedifferent.When
maintenanceoperation. change the lubricant oil, at the same time oil filter
needstobechanged,otherwisethechangeofoilwill
Inordertoobtainmaximumoperationsafetyandlife becomemeaningless.Onthecontrary,ifthelubricant
expectancy of the generator sets, periodic oilremainsingoodstatus,wecanfilterthelubricant
maintenanceisveryimportant.Strictlyobservanceof muchbetterbychangetheoilfilter.
thetermsongeneratorsetsmaintenancecanensure ! Change fuel filter, clean or change first stage fuel
generator sets performance and reduce its damage filter core, oil water separators core (some of the
toenvironment. generator sets have), check and organize fuel pipes
arrangement.
Correctly identify and strictly observe the labels ! The change interval of above fuel filter (core)
(drawings, words and warnings etc.) On diesel depends on the quality of fuel (if it contains many
generator sets can be of great help to correct impurity), the fuel adding method is reasonable or
maintenanceandsafeoperations. not, the fuel tank is cleaned periodically or not
(contaminant discharge). Once the color of engine
Maintenance of the generator sets shall be made exhaust air is found to be abnormal and the output
when it has been stopped and the cable which power decrease, first the fuel system needs to be
connecttothenegativepolarofthebatteryshallbe checked.
disconnectedsothattoensurethegeneratorsetwill
notmistakenlystart.

4.2Engine
Foreach400hoursofrunning
Eachtimebeforestarttheengine
!Checkandadjustthetransmissionbeltandchangeit
!Checklubricantoillevel
whennecessary
!Checkcoolantlevel
!Checkandcleanradiatorcore
!Checkairfilterindicator
!Dischargedepositinthefueltank
! Check the ventilation of radiator and ambient
environment
!Checkenginestransmissionbelt Foreach800hoursofrunning
!Checkfuelsupplystatus !Checkiftheturbochargerhasleakage
Generator sets which run frequently need to be !Checkiftheairinletpipeshasleakage
checked one time every 6 to 8 hours. Backup
generator sets need to be checked once more after
beingstopped. Foreach1200hoursofrunning
!Adjustvalveclearance

Depends on the new generator sets running status,


when it is necessary, within 100 to 300 Hours, Foreach2000hoursofrunningoratleast24months
followingactionsshallbetaken: ! Change air filter (depend on ambient air quality,
!Checkthevalveclearance decideifthisneedtobechangedearlier)
!Checkthefuelinjector ! Change coolant and coolant filter (some generator
setshave)
Foreach0~50hoursofrunning !Thoroughlycleanradiatorcoreandwaterpath
! Discharge the water remained in the oilwater
separator Foreach2400hoursofrunning
! Check the batterys electrolyte level (except !Checkfuelinjector
maintenancefreebattery) !Thoroughlycheckandcleanturbocharger
!Comprehensivelycheckengineequipment

18
User manual

4.3Alternator Please do not use the battery to startthe generator


set under low temperature because the battery
Inside and outside of the alternator shall be cleaned capacitance can not output normally under low
periodically. And the frequency of cleaning depends temperature, and long time discharge may cause
on the generator sets ambient environment. When batterymalfunction(crakeorexplode).
the cleaning becomes necessary, following Warning:
procedurescanbefollowed:cutoffallofthepowers, ! The battery of the backup generator set shall be
wipeoffthedirt,contaminant,oilstain,waterorany periodicallymaintainedandcharged.Itissuggested
other liquid from the surface. The ventilation mesh thatuserscanbuyfloatingchargerforthebattery.
alsoneedstobecleaned.Theadhesivenessofthese
materialstothecoilswillcausethecoilsoverheator
damagetheinsulation.
4.6Maintenancerecord
The dirt and contaminant need to be absorbed by
dust collector. Please dont use air blow or high Each time after maintenance, users shall make
pressurewaterspraytocleanthealternator. detailedrecordforthemaintenancejob.
The humidity of alternator will decrease insulation
resistance.Thealternatorshallbedried.Pleaserefer
to Alternators Operation and Maintenance Manual Warning:
forthemethodofdryinganddetailedmaintenance. !Completemaintenancerecordprovidesevidencefor
userstomaintainthegeneratorset,andatthesame
4.4Controlpanel time is a precondition for lawful after sales service
Daily maintenance for the control panel shall ensure (warranty).
thecleannessofitssurface,maketheindicatormore For example: Maintenance record (Refer toAppendix
clearandeasyforreading,andtheoperationbutton FandG)
flexibleandreliable.
During the generator sets running period, vibration
willcausetheshiftof0positionintheinstrument
of control panel and loose of tightened parts, and
therefore periodically check the instrument of the
control panel and parts and cables connections are
veryimportant.
Repair for the control panel can only be done after
thorough learning of the principle of this control
panel (please refer to Control Panel Operation
Manualfordetails)

4.5Startbattery
Batterieswhichhavebeenstoredinalongtimeshall
be properly charged before being used, so that to
ensure normal capacitance of the battery.
(Densimeter can be used to check the actual
capacitanceofthebattery)
Normal operation and battery charging will cause
some water inside of the battery being vaporized.
And therefore constant fluid infusion is needed.
Before fluid infusion, first the contaminant around
the adding hole shall be cleaned so that to avoid
them falling into the battery. Then open the adding
hole,addproperamountofdistilledwaterorpurified
water. Do not add too much (shall be according to
the indicating line in the battery polar plate),
Otherwise the inside electrolyte will overflow from
theaddingholewhenthebatteryisunderdischarge
or charging, which will cause contamination to the
ambientmaterialandenvironment.


19
User manual

5CheckforMalfunction
5.1Generaloutline
There are many factors which may cause the
generatorsetsmalfunction,andthemalfunctionsare
usually closely related to each other. This section
mainly summarize and list the possible malfunctions
ofgeneraldieselgeneratorsets.Thisisjustforusers
reference when they try to eliminate the
malfunction(s). (Especially important for new
generatorsetscustomer)
One thing must to be emphasized: most of the
malfunctions are caused by users improper
installation, operation, and maintenance. Users are
entitledtodoubtthatthemalfunction(s)iscausedby
the generator sets manufacture failure, but this
conclusion shall be based on correct installation,
operation and periodically maintenance. Otherwise,
we can not assure you the normal operation of the
generatorsetandthedeservedaftersalesservice.

5.2Malfunctionchecklist

20
APPENDIX E

1
2
3
APPENDIX F
Generator set running record
TIME ENGINE PARAMETER GENERATOR PARAMETER IF RECORD
Start/stop Accumulated FOR
Oil OPERATOR REMARK
generator running Temperature Voltage Current Frequency Power MALFUNCTION
pressure IS AVAILABLE
set time time
APPENDIX G
Maintenance Record

Maintenance Time: SN:


Generator set model: Engine model: Alternator Model:

Generator set serial No.: Engine serial No.: Alternator serial No.:

Accumulated running hours: Maintenance cycle:

Reasons for maintenance (periodic maintenance or malfunction maintenance)

Inspection and repair

Inspection and adjustment

Change of parts

Clean and maintenance

Others
Conclusion for maintenance:

Maintenance staff signature: