Professional Documents
Culture Documents
SECTION 13113 Impressed Current CP of Reinforced .......... Structures Rev 0
SECTION 13113 Impressed Current CP of Reinforced .......... Structures Rev 0
SECTION 13113:
KINGDOM
OFSAUDIARABIA
~~~1 ~J-!ll~I
forJubail&Yanbu
RoyalCommission ~~ ~ ~144f.l1
SECTION 13113
IMPRESSED CURRENT CATHODIC PROTECTION OF REINFORCED CONCRETE STRUCTURES
TABLE OF CONTENTS
PART 1 GENERAL............................................................................................................ 1
1.04 REFERENCES..................................................................................................... 2
1.05 DEFINITIONS....................................................................................................... 4
1.06 SUBMITTALS....................................................................................................... 8
1.11 INTERFACES..................................................................................................... 18
3.02 INSTALLATION.................................................................................................. 34
PART 1 GENERAL
A. The Contractor shall design, install, test, commission and document impressed
current cathodic protection (CP) for existing and new reinforced concrete structures.
The purpose of the CP system is to protect the reinforcing steel in concrete
structures against corrosion by passing a low voltage current from an anode system
to the reinforcing steel.
B. The Contractor shall furnish all labor, materials, tools and equipment required to
complete the Work.
A. This Section establishes the general criteria for the design, installation, testing,
energizing, and commissioning of impressed current CP for reinforced concrete
structures as required for this and other related Sections of these Specifications.
B. This Section does not include cathodic protection using galvanic anodes.
1.04 REFERENCES
A. The referred codes and standards are intended to provide an acceptable level of
quality for materials and products. In case of conflict between these references and
text specification, the specification text shall govern.
B. The latest revision of the referred codes and standards shall be used wherever
applicable. In case of conflict between codes and/or references, the Contractor shall
conform to the BS EN Standards.
10. BS DD ENV 1504-9 Products and Systems for the Protection and Repair
of Concrete Structures. Definitions, Requirements,
Quality Control and Evaluation of Conformity.
General Principles for the Use of Products and
Systems
11. BS EN 1504-10 Products and Systems for the Protection and Repair
of Concrete Structures. Definitions, Requirements,
Quality Control and Evaluation of Conformity. Site
Application of Products and Systems and Quality
Control of Works
12. BS EN 1542 Products and Systems for the Protection and Repair
of Concrete Structures. Test Methods. Measurement
of Bond Strength by Pull-Off
1.05 DEFINITIONS
D. anode zone: The anode system may be divided into zones to supply current to a
fully continuous reinforcement matrix, and a current provision to each zone can be
separately controlled and measured.
F. bond: Metal conductor, usually copper, connecting two metallic points on the same
or on different structures usually with the intention of making the points equipotential.
G. buried structure: Any metal construction built or laid beneath ground level or built
on ground level and covered with earth.
H. carbonation: The process by which carbon dioxide in the atmosphere reacts with
water in concrete pores to form carbonic acid and then reacts with alkalis in the
pores, neutralizing them.
M. conductive coating: A paint, mastic or metallic spray which is heavily loaded with
an electrically conducting component.
V. electrolyte resistivity: The specific resistance of the electrolyte assuming that the
electrolyte is homogenous. Note: Usually expressed in ohm.meter (Ω·m).
X. foreign structure: Any metallic structure that is not intended as a part of a system
under cathodic protection.
Y. galvanic anode: A metal that provides sacrificial protection to another metal that is
more noble when electrically coupled in the electrolyte. This type of anode is the
source in one type of cathodic protection.
AA. immersed structure: Any metallic structure or part of a structure laid in a liquid
environment such as fresh water (rivers, lakes), brackish water (estuaries), or sea
water.
CC. impressed current station: Station which comprises the equipment and materials
required to provide cathodic protection by impressed current. Such materials and
equipment will include impressed current anodes, cables and a DC source.
DD. interference: Any change in the structure to electrolyte potential, which is caused by
foreign electrical sources.
EE. interference test: Test to determine the severity of corrosion interaction between
two buried or immersed structures.
FF. IR drop: Voltage difference, due to any current, developed in an electrolyte such as
the soil, between the reference electrode and the metal of the structure, in
accordance with Ohm's Law (V = I x R).
GG. IR free potential: Structure potential measured without the voltage error caused by
the IR drop due to the protection current or any other current.
II. measuring point: The point at which the actual measurement takes place. Note: In
case of structure to electrolyte potentials, this refers to the location of the reference
electrode.
KK. instant off potential: Structure to electrolyte potential measured immediately after
synchronous interruption of all sources of applied cathodic protection current.
LL. on potential: Structure to electrolyte potential measured with the cathodic protection
current flowing.
NN. polarization: Change in the potential of an electrode (e.g. structure) as the result of
current flow to or from that electrode.
OO. primary anode: Current is fed from the rectifier to the primary anodes, which serves
QQ. protection current: Current made to flow into a metallic structure from its electrolytic
environment in order to effect cathodic protection of the structure.
RR. protection potential: Structure to electrolyte potential for which the metal corrosion
rate is acceptable.
TT. service life: The time until safety, serviceability and acceptable appearance of the
structure or its main components falls below a defined minimum level or requires
unduly high costs for maintenance and repair.
UU. shield: Conductive or non-conductive object, which modifies the protection current
distribution on a structure to be protected.
WW. stray current corrosion: Corrosion caused by electric current from a source
external to the intended electrical circuit, for example, extraneous current in the
earth.
XX. structure: Metallic construction, whether coated or not, which is in contact with an
electrolyte (e.g. soil, water). Note: The structure may represent a construction of
great length, such as a pipeline, pipe networks, underground electric cables, or well
casings as well as constructions on a smaller scale such as piles, sheet pilings, tanks
or other underground constructions.
AAA. test station: Installation that provides measuring and test facilities for the buried
structure. Note: Such installations will include cabling and structure connections.
CCC. zinc electrode: Measuring electrode made from sufficiently pure zinc.
1.06 SUBMITTALS
A. The Contractor shall submit to the Royal Commission, under the provisions of
SECTION 01330, the following items for review and approval before commencing
Work:
1. Manufacturer's Data
2. Shop Drawings
b) The Shop Drawings shall indicate component sizes, locations, and cable
and anode routings. Identify any special handling requirements for each
of the components.
3. Calculations
Anodes
(a) Type, number and configuration.
4) Calculation of anode zone layout.
5) Circuit resistance of each zone.
4. Method Statements
a) Provide method statements for items included in par. 3.01 A, for e.g.
visual inspection, delamination survey, concrete cover, verification of
reinforcement size and position, ‘as found' potential survey and
verification of environmental parameters such as electrical resistivity of
concrete.
5. Submit the following items for review and approval before commissioning:
b) As-Built Drawings
1) Submit copies of As-built Drawings per SECTION 01780,
following installation of the CP system. The Drawings shall
provide complete details including, but not limited to, the power
supply system, anode system, test stations, negative connections,
cables, data acquisition system, data communication systems,
signals I/O-lists and the central monitoring and central control
system. The As-built Drawings shall further indicate component
sizes, locations, anode zones and cable runs.
A. The Contractor shall be responsible for the quality of work and shall develop and
propose programs and methods of construction and testing to achieve the specified
quality to the approval of the Royal Commission, in accordance with
SECTION 01450.
B. The design, installation and commissioning of the CP system shall meet the Royal
Commission’s Quality Control standards. In addition, the CP system component
manufacturer’s own recommended installation and material standards and
procedures shall be recognized as part of this Specification. No deviations shall be
permitted without prior written agreement by the Royal Commission. The Contractor
and Subcontractor shall review and remain cognizant of all other specifications
related to this scope of work.
D. Each element of the work shall be undertaken in accordance with a fully documented
quality plan.
E. Each and every stage of the work including installation, energizing, commissioning
and long term operation shall be subject to appropriate visual inspection, mechanical
and/or electrical testing and all testing shall be documented.
1. The Contractor shall be responsible for the coordination of all works relating to
this Contract. It shall be the responsibility of the Contractor to ensure that all
work and equipment to be furnished under the Contract results in a complete
and satisfactory installation.
2. All work shall be carried out under the supervision of an experienced Cathodic
Protection Engineer. The Cathodic Protection Specialist/Engineer shall have a
Degree in Electrical or Electrochemical Engineering or Science Degree in
Physics or Chemistry from a recognized Institution, a minimum of 10 years
practical experience in cathodic protection design, installation and
commissioning. A professionally qualified NACE Certified Cathodic Protection
Specialist or a professional member of the Institute of Corrosion, with a
Bachelor Degree in Physical Science or Engineering is preferable.
3. All Contractor’s engineers and supervisory staff involved with the installation of
the cathodic protection (CP) system shall have at least 3 years experience in
this type of work and the Contractor shall provide Resumes for the Royal
Commission’s approval prior to commencement of work.
5. Supervision shall be carried out to a high standard throughout the works. All
equipment shall be inspected upon delivery and again prior to installation.
Inspection hold points shall be introduced for items or works which will be
buried so that assurance and responsibility is recorded for all items or works
prior to backfilling.
6. Any defect shall be reported to the Royal Commission and shall be recorded in
a retrievable data system. Corrective actions taken, which must be approved
by the Royal Commission, shall also be recorded.
7. The Contractor shall submit a quality plan, detailing his proposed procedure for
Quality Control, for review and approval by the Royal Commission.
8. All testing and commissioning work shall be carried out the by above Cathodic
Protection Specialist Staff. The staff who are deemed to have insufficient
experience shall be prohibited from carrying out critical work tasks as
described in the relevant parts of the specification. In such cases, replacement
manpower and any delays incurred shall be borne by the Contractor.
accordance with the respective health and safety requirements established by the
following:
3. Contractor
B. In the absence of any of the above, best accepted industry practice shall be
employed throughout.
C. Measures shall be taken to avoid any safety hazards caused by the cathodic
protection system. The considerations shall include, but not be limited to, electric
shock, hydrogen and chlorine gas generation.
A. System Description
b) Anode System
1) Consisting of anode(s) including any overlay, associated power
distribution bars, cables, and all fastening devices to support the
anode material.
(a) For new structures, an anode system shall consist of an
activated titanium anode system.
(b) For existing structures, an anode system shall consist of
activated titanium anodes (mesh, ribbon, rods, wire, tubes
etc.) mounted directly on the concrete surface with a
cementitious overlay or placed in holes or slots encased in
cementitious grout/graphite backfill.
(c) The anode system may consist of other anode types
specific for the particular structure being protected.
(d) The type of anode system shall be chosen taking into
consideration, among others, factors such as the
c) Cathode System
1) Consisting of the negative cabling from the rectifier connected to
the reinforcement, including the structure continuity ties or clamps
and any other metallic items or objects to be protected.
a) For above ground level and above water tidal level, the following
protective criteria shall be achieved:
1) An ‘INSTANT OFF’ potential more negative than - 720 mV with
reference to Ag/AgCl/0.5M KCl.
2) A potential decay after maximum 24 hours of at least 100 mV
from 'INSTANT OFF' or a potential decay after more than
24 hours of at least 150 mV.
b) For below ground level and below water tidal level, the following
protective criteria shall be achieved:
1) A minimum negative shift in 'INSTANT OFF' potential to - 720 mV
with respect to Ag/AgCl/0.5 M KCl.
C. CP Zones
1. The CP system shall be sectioned into zones with the anode circuit being the
principal basis of zoning. A zone is defined as a discrete section of concrete
structure energized as an independent unit. A zone may be divided into
smaller elements called sub-zones comprising different sections of concrete.
The sections of concrete combined into a single zone shall have similar
environmental exposure and conditions as well as similar conditions of
separation of anode to reinforcement steel and similar concrete quality.
2. For existing structures, the total design current requirement of a single zone
shall not exceed 4 A. In case the driving voltage to obtain the 4 A exceeds the
manufacturer’s recommended maximum driving voltage, the anode zones shall
be sub-divided to meet the manufacturer’s requirements.
3. For new structures, the total design current requirement of a single zone shall
not exceed 2.5 A.
6. No zone shall be designed so that the voltage drop within the system exceeds
250 mV from the power supply terminals of the T/R unit to the furthest point in
the circuit, i.e., positive supply terminal to furthest anode and negative terminal
to furthest section of reinforcement.
7. Cable sizes and lengths shall be selected such that the resistance of each
anode feeder and system negative in a given zone or sub-zone shall be within
80 to 120% of the value of any other anode feeder and system negative in that
zone or sub-zone.
1. The anode system shall provide protection against reinforcement corrosion for
the required service life:
c) The service life of the CP system shall be in accordance with the Royal
2. The design and installation of all elements shall be made such that no major
maintenance shall be required within the service life unless replacement of the
anode system is part of the design.
3. The design of the anode system for the existing structures shall be such that it
contains a 25% redundancy in anode current output as well as 25%
redundancy in rectifier output current for each zone.
4. The design of the anode system for the new structures shall be such that it
contains a 50% redundancy in anode current output as well as 50%
redundancy in rectifier output current for each zone.
5. The design of the anode system shall be such that not more than 5% of an
anode within a given zone is made inoperative under either one random break
down in power feed or two random breaks in the anode system.
d) For concrete sections with thickness between 300 and 400 mm, a single
line of anode at 300 mm maximum spacing, supported on central links
may be adopted. This option is an alternative to the option of positioning
double anode layers; each secured to the reinforcement.
f) Where double anode layers are required, the anodes shall be mounted
directly on the reinforcing cage using appropriate non-metallic fasteners
for reasons of anode-to-reinforcement separation. The fasteners shall
be positioned at every crossing point of anode and reinforcement. The
anode ribbon shall be positioned between, and not on, the parallel
reinforcement bars wherever possible.
2. All metallic items in addition to the reinforcement, which lie in or are mounted
on the concrete surface, shall be accounted for in calculating cathode current
requirements and shall be made continuous with the reinforcement.
A. Examine conditions of the Project site and the reinforced concrete structure for which
the CP system shall be installed. Do not proceed with installation until all
unsatisfactory conditions have been corrected.
2. Document structural assessment results, which will include test location and
results. All results shall be recorded on a plan sheet designating each location
to be tested.
3. Any defect area (e.g. delaminated, cover less than 15 mm, high resistance)
within the concrete cover with respect to installing a cathodic protection system
shall be repaired. The repair bond strength shall be verified by pull-off testing.
The electrical resistance of the repair material shall be tested, and an
acceptance criterion corresponding to the original concrete resistance shall be
established.
4. The repairs, inclusive the bond strength testing and electrical resistance
testing of the repair material shall be documented. The extent of the repairs
shall be documented on the plan sheet. An original plan sheet shall be
provided to the Royal Commission for review and approval following repairs.
B. Verify electrical continuity of the reinforcement steelwork (see par. 1.09 E) as well as
other externally mounted steel items which may experience stray current corrosion.
Verify that the appropriate methodology of producing continuity is in place
(par. 3.01 C).
2. Provide electrical continuity Method Statement for review and approval by the
Royal Commission.
3. Electrical continuity shall be verified for all reinforcement layers, including links,
saddles, etc. and other embedded metallic fixtures according to par. 3.01 D.
If discontinuity exists, document such conditions and verify that corrections are
made.
4. Document continuity test results, which will include test location and resistance
reading. All resistance readings shall be recorded on a plan sheet designating
each location to be tested.
6. It shall be verified that bonding cables are present for those metallic
components not yet placed, but to be installed after the concrete pour.
1.11 INTERFACES
A. The Contractor shall identify and define all interfaces between his works and other
parties' work, including other plant and systems under the responsibility of the Royal
Commission, other Contractors' plant and systems and third parties' plant and
systems. The Contractor shall keep updated records of all interface agreements
made with other parties.
1. Power supply to transformer rectifiers (T/R). For each T/R, the exact point of
2. Integration with the Royal Commission remote monitoring system. For each
T/R the physical interface, the communication protocol and the data format
and content shall be defined and agreed with the Royal Commission.
A. The Contractor shall deliver, handle and store equipment and material in accordance
with SECTIONS 01650 and 01660, as well as the following requirements:
6. Spare Parts
PART 2 PRODUCTS
2.01 GENERAL
A. All goods and products covered by these Specifications shall be procured, when
available, from an in-Kingdom manufacturer. Procurement of all goods and products
manufactured out-of-Kingdom must be approved by the Royal Commission.
A. All the equipment and components for the Cathodic Protection systems shall be rated
for the nominal voltage, current, and frequency as specified in the Contract
Drawings/Documents, and the Saudi Electricity Company (SEC) or Marafiq
guidelines, and shall include the requirements indicated below.
B. General
1. The transformer rectifiers (T/R) shall provide fully controllable DC output to the
anodes and shall meet or better the requirements of this Specification. The
units shall be installed adjacent to the structures to be protected.
6. The transformer rectifiers shall have the provisions ready to connect hardware
systems with a remote monitoring and data management systems as specified
in the Contract Drawings/Documents. Refer to SECTION 13450 for remote
monitoring and central control system.
C. Enclosures
2. Doors shall be gasketed, stiff and lockable with a brass lock or padlock. All
transformer rectifier enclosure locks shall be capable of being opened with the
same key. Unhindered access to the DC positive and negative cable
terminations is required.
1. Each individual transformer rectifier shall supply the designed output current to
the anodes as detailed in the design and shall include:
b) Each power supply unit shall have its own logical address and each
channel in the rectifier shall have a unique address so that it is possible
to individually control and monitor every single zone and reference
electrode.
e) All fuse holders shall be labeled with the circuit designation and rating of
individual fuses and shall be marked by indelible labels in accordance
with SECTION 16075 on the panel adjacent to the appropriate fuse
holder.
a) When there are more than one rectifier/power supply unit for the facility
or Project with multiple structures, they shall be controlled and
monitored from a common, central control unit to be placed in a location
to be agreed with the Royal Commission.
b) The communication between local units and the central unit shall be
able to utilize telephone lines, spare fiber optic cores, or wireless
communication. Necessary terminal equipment such as modems or
equal, and communication software shall be provided by the Contractor
in accordance with approved Contract Drawings/Documents.
c) The central control unit shall be able to set and/or read operating
parameters of each rectifier/power supply channel and process, time
stamp and store collected data for reporting and alarm, as a minimum
’INSTANT OFF’ and depolarization data over 24 hours, actual and set
output voltage and output current, and reference cell potentials.
d) The monitoring data shall be stored in the central unit, which shall allow
for storage of data for 3 years operation.
e) The central control unit shall have capability for communication with the
Royal Commission's remote monitoring system in accordance with
agreed communication protocols. For central control refer to
SECTION 13450.
E. Electronic Components
3. The rectifiers shall conform to BS EN 60146 and shall be silicon type with
suitable AC surge protection. Semi-conductor fuses shall be used to protect
the rectifiers on the AC side and varistors on the DC side. Rectifiers shall be
rated for continuous operation at the maximum design outputs with a peak
inverse voltage of at least 800 V. Varistors shall be compatible with the rectifier
peak inverse voltage levels.
1. All test procedures shall be submitted to the Royal Commission for approval.
Tests shall be carried out by the manufacturer and test reports and certificates
shall be submitted to the Royal Commission for approval.
3. Unless otherwise specified and approved, all electrical tests shall be carried
out in the manner as proposed by the Contractor and approved by the Royal
Commission.
H. Electrical Protection
1. To avoid stray currents caused by reverse currents in the anode wire, the
power supply systems shall be electrically insulated from one another. The
insulation shall ensure that each power supply system works as an electrically
independent unit, unaffected by electrical influence from other electrical
sources. The power supply systems shall be designed to suppress external
noise. The AC input and AC terminals shall be shrouded in accordance with
IEEE Wiring Regulations to prevent accidental contact. An electrical isolation
switch shall be provided between the AC power input cable and the power
supply to allow the safe disconnection of the power supply if required.
A. General
B. Voltage Stabilizers
1. Voltage stabilizers shall be provided where needed for the power supply to
meet the power input specifications for the T/R's. All stabilizers shall be of
static magnetic transformer type, rated for working at 65°C and regulation of
1% of the nominal voltage at full load current. They shall fully comply with
specifications IEEE/ANSI 449 for specialty transformers.
C. Distribution Boxes
1. Distribution boxes shall be of the dead front type, rated to meet the
requirements of this Specification. The distribution and junction boxes shall be
metal cabinet with front doors, latches and locks. All locks shall be of similar
type and shall be operable by a single key.
D. Circuit Breakers
A. The anode system shall be capable of supplying current and distributing, thus
allowing for the performance required by the CP design as specified in par. 1.09 B.
B. The calculated or anticipated life shall be sufficient for the design life incorporated
into the design with, where necessary, planned maintenance or replacement of the
anode system or part of the system at periods designated in the design.
D. The calculated and anticipated life shall be sufficient for the design life (50 years) of
the new anode system as specified in par. 1.09 D.1, with no major maintenance
requirement or replacement of anode system components required during this
period.
E. The anode system shall consist of positive cable connection devices, anode system
inclusive current distributors, anode connectors, fastening devices and overlays. The
Contractor shall submit sufficient data to enable evaluation and approval of the
performance capability of the anode system proposed. The characteristic for each of
the components is provided below.
1. The selection of the anode material shall consider likely variations in cathode
current density requirements, steel distribution, concrete electrical resistivity
and any other factors likely to result in uneven distribution of current demand
or current discharge from anode. The anode materials shall be chosen among
the following types unless otherwise agreed by the Royal Commission:
3. The anodes, primary anodes and conductor bars shall be anchored to the
concrete surface or in larger repairs to the reinforcement by means of
fasteners of non-conducting material such as plastic. The type, number and
A. The negative connections are the return power feed connections for the cathodic
protection system. The connection shall be constructed as follows:
2. The pre-stripped copper core of the negative cable shall be placed inside the
hole and braze welded to the rebar.
B. In each zone or sub-zone, the reference electrodes shall be positioned such that they
represent the most exacting geometric configuration, such as diametric opposition.
4. The temperature coefficient and the temperature range of operation shall also
5. Each reference electrode shall be fitted with a suitable length of cable, such
that no splices are required within the cementitious anode overlay. The
connection between the cable and the electrode shall be completely sealed
and capable of total immersion without leakage under a water head of 1 m.
6. All reference electrodes shall be clearly and discretely marked on the electrode
case and at the cable termination point. This number shall be recorded on the
calibration test certificate and shall be recorded against its location on the As-
built Drawings.
B. Positive and negative cables shall be color-coded the same for all areas. Colors are
RED for positive (anode) and BLACK for negative (reinforcement steel) in single core
cables. Reference electrode and test connection cables shall have separate colors,
not BLACK or RED. Proposed color scheme shall be submitted to the Royal
Commission for approval.
D. The conductor shall be 7/0.2 mm² strand annealed copper, insulated with
polyethylene over which shall be a layer of plain copper braiding. Overall sheathing
shall be PVC.
E. The capacitance shall be less than 103 pF/m at temperatures up to 50°C. Cables
shall be color-coded for identification.
F. Reference electrode cabling from the junction box to T/R shall run in conduit and
shall be screened multi-core, multi-strand type of minimum cross-section of 1.25 mm²
per core.
G. All cables shall be terminated by crimped connectors suitable for the terminals
provided in the junction boxes. All cables and wiring shall be appropriately identified
within 25 mm of each end using permanent wire markers intended for the purpose.
Where cable identifications have been given in the Contract Drawings, these shall be
used. For termination of wires and cables, refer to SECTION 16150.
H. Cable Splices
1. Cables can only be spliced with the written approval of the Royal Commission
and the Contractor shall nominate the location of each splice when seeking
each approval prior to commencement of any splicing and physically
demonstrate the capacity of a sample of the splice to the Royal Commission.
b) The length of the first, inner heat shrink will be determined by the length
of the crimp and the extent of exposed inner cable insulation. Each end
of the heat shrink shall extend a minimum of 30 mm over the inner
insulation, but must not ride up over the outer cable insulation.
c) Prior to positioning the mastic-filled heat shrink, the inner insulation shall
be lightly roughened using emery paper to promote good adhesion.
Then all surfaces will be wiped down with a volatile cleaner (methylated
spirits, or similar) to remove dirt, dust, grease, etc., and the heat shrink
will be immediately positioned and applied. For the outer section of heat
shrink, the PVC cable insulation will only require cleaning prior to
applying the heat shrink.
d) The Contractor shall take care to ensure that all the components are
kept clean and dry during the splicing process and that the conductor is
not damaged when the insulating layers are being stripped.
B. All doors shall be gasketed, lockable and stiffened. All locks shall be capable of being
opened with the same key. Cable entry shall be through suitable compression gland
or in sealed conduits. Appropriate precaution shall be taken to ensure that the cable
entry system in no way compromises the junction box IP rating.
C. The terminals shall be clearly marked with the zone/sub-zone, component type and
number as appropriate and shall also be marked with suitable identification
corresponding to each particular unit. The typical control layout for the control panel
shall be shown in the Drawings. All terminals shall be clearly labeled with their
correct function, using white engraved background on black surface. Material shall be
traffolyte or equivalent.
D. Cable connectors shall be DIN rail mounted terminals. Only 1 conductor per terminal
shall be permitted. Circuit expansion shall be achieved by standard bridging strips,
E. Layout of terminals/panels within the junction boxes shall be shown in the detail
Drawings. The proposed layout details shall be submitted to the Royal Commission
for approval prior to commencement of work.
F. The junction box installation shall conform to BS 7671. The junction box shall be
securely and rigidly fastened in place in accordance with BS 7671.
G. The junction boxes shall be grounded in accordance with the provision of BS 7671.
For more details on Grounding and Bonding, refer to SECTION 16060.
PART 3 EXECUTION
3.01 GENERAL
A. The Contractor shall provide all equipment and labor as deemed necessary for the
proper execution of the work.
D. The Contractor shall be fully responsible for any mechanical damage upon
installation of complete cathodic protection system and their related accessories.
3.02 PREPARATION
A. Environmental Survey
a) Environmental Conditions
1) Seawater, buried, submerged, splash zone, atmospherically
exposed, industrial exposure, etc. Resistivity of environment for
submerged or buried structures.
b) Climatic Conditions
1) Humidity and temperature.
1. As basis for the design calculation of the steel reinforcement area, the steel
density and geometry according to the structural reinforcement drawing shall
be verified.
C. Structural Assessment
a) Visual inspection.
4. All test equipment shall have a valid calibration certificate traceable from a test
laboratory approved by the Royal Commission.
2. The Contractor shall perform a continuity survey to ensure that all the steel
reinforcement layers including links, tie bars saddles, etc., and any other
embedded metallic fixtures within the structure to be protected are electrically
continuous. Sufficient reinforcement shall be exposed and continuity tested at
representative locations in each unit or discrete part of the structure subject to
approval by the Royal Commission. In addition, all steel exposed during
concrete repairs or other works shall be continuity tested. The frequency of
continuity testing shall be increased in the areas were discontinuity is found.
The number of additional locations to be measured shall be approved by the
Royal Commission.
3. Unless alternative testing procedures and criteria have been selected in the
design, the electrical continuity between reinforcing steel or elements of steel
in concrete shall be tested by DC reverse polarity resistance measurement
technique. This technique measures and compares the resistance using a DC
resistance instrument and then reversing the polarity of the test leads.
5. The locations selected for continuity testing should represent the most
exacting geometric configurations possible, e.g. change in sections, change of
7. Any bar or component failing the continuity testing shall be continuity bonded
to ensure long-term resistance of less than 1 ohm. Where discontinuity exists,
electrical continuity shall be provided by tack welding or clamps.
E. Repairs
3. The repairs shall include any defects that can impair the effectiveness of the
CP system. Repairs shall be performed in accordance with SECTION 03930 or
BS EN 12696, BS DD ENV 1504-9 and BS EN 1504-10.
F. A trial installation shall be carried out - one for each anode system - to demonstrate
that the design anode performance is achieved. The trial shall include all activities
associated with the installation such as surface preparation by sand or water
blasting, any drilling or saw cutting, fixation of anodes or primary anodes, encasing in
cementitious overlay or graphite backfill, application of coating or conductive overlay
and any subsequent testing of the complete encasement, bond strength and
thickness of overlay. The methods for surface preparation, fastening, application, etc.
shall be in strict accordance with the manufacturer's guidelines. The results of the
trial installation shall be forwarded to the Royal Commission for review and approval.
3.03 INSTALLATION
3. Consideration shall be given to the need to provide temporary protection for all
cables up to the time of final concrete installation and thereafter.
B. The trial installation as specified in par. 3.01 F shall be accepted by the Royal
Commission before the installation process can proceed.
1. The anode system shall be installed in strict accordance with the methods
accepted by the Royal Commission as part of the trial installation. The
installation shall comply with the requirements stated below.
a) The spacing between the anode system and the reinforcing steel in the
structure shall be a minimum of 15 mm at any location. Particular care
shall be taken for the cover to the reinforcement in any slots, holes, etc.
used for succeeding anode placement.
3. Wires, Ribbons, Rods, Tubes, etc., Placed in Recesses in the Concrete Cover
or in Holes Within the Structure.
a) The anode shall be placed in the recess in the concrete surface so that
the anode does not move during casting and hardening and ensure that
the anode is satisfactorily embedded in the cementitious material. The
installation of the anode within holes in the structure shall be conducted
so complete encasing is ensured, whether a graphite backfill is used or
a cementitious grout.
D. Positive Connection
3. Special care shall be taken to ensure that the cables are not damaged during
compaction or that the cables are not unintentionally cut, for e.g., outside the
framework. After placement of the concrete, the part of cables outside the
structure shall be protected until installation in the transformer rectifier.
E. Negative Connection
1. The system negative connections within each zone shall be made to the
reinforcing steel in the manner shown on the design drawings. Reliable
connections such as welding to the reinforcing steel shall be used.
2. At the location within each zone (the exact positions to be agreed with the
Royal Commission on site), the reinforcement shall be thoroughly cleaned to
expose clean bright steel around its full circumference. The system negative
cable shall then be connected to the reinforcing steel in the manner shown on
5. Special care shall be taken to ensure that the cables are not damaged during
compaction or that the cables are not unintentionally cut, for e.g., outside the
formwork. After placement of the concrete, the part of cables outside the
structure shall be protected until installation in the transformer rectifier.
F. Reference Electrodes
3. Special care shall be taken to ensure that the cables from the reference
electrodes are not damaged during compaction or that the cables are not
unintentionally cut, for e.g., outside the formwork. After placement of the
concrete, the part of cables outside the structure shall be protected.
3. All test instrumentation shall have valid calibration certificates from a testing
laboratory approved by the Royal Commission.
4. The electrical testing shall include, but not be limited to, the following:
a) Anode System
1) The anode system shall be tested to detect any short circuits. The
electrical resistance shall be measured by means of a DC
resistance measurement and recorded. The DC resistance shall
be greater than 1 M ohm. The tests shall be conducted between
the anode and the reinforcement and the anode and any other
metallic items before, during and after casting.
b) Negative Connection
1) The DC resistance between each connection of the reinforcing
steel shall be measured and recorded. If the measured resistance
is greater than 1 ohm, an additional system negative connection
shall be made at a location approved by the Royal Commission
until the measured resistance is less than 1 ohm.
c) Polarity Checks
1) The results for polarity check for all circuits shall be unambiguous.
d) Continuity Checks
1) Continuity checks for all circuits by DC resistance measurements.
The results of the individual circuits shall demonstrate values
within 10% of those calculated from cable and component values.
5. All testing according to the control plan shall be documented and the
documentation shall be forwarded to the Royal Commission for acceptance
before commissioning.
B. Pre-Commissioning Checks
output and all anode connections within each anode zone at the junction
boxes using a DC resistance meter. Stable resistance of less than
1 ohm will indicate continuity of the anode circuit.
g) The Contractor shall record the circuit verification results to certify that
the pre-commissioning checks have been carried out successfully and
this shall be treated as a hold point.
C. Initial Energization
1. The Contractor shall energize the CP system per approved plans and
procedures. As a minimum, the Contractor shall meet the following
requirements:
b) The Contractor shall ensure that the anode current does not exceed the
maximum recommended current by the anode manufacturer and that
a - 1100 mV (and - 900 mV for pre-stressed concrete) versus the
Ag/AgCl reference electrode is not exceeded at any reference electrode.
c) After the system operates for 7 days, the ‘INSTANT OFF’ potential of
the reinforcing steel shall be evaluated at each reference electrode. If
necessary, adjust the current to the full design output subject to the
’INSTANT OFF’ not being more than - 1100 mV Ag/AgCl at any location.
e) The data shall then be analyzed to assess compliance with the specified
criteria for cathodic protection.
D. Operation
1. The Contractor shall operate the CP system for the period of time until the
Royal Commission’s initial acceptance of the Facility from the Contractor. The
system operation shall include performance monitoring and system review.
E. Performance Monitoring
c) The power supply shall be checked, noting the integrity of all input and
output cables.
d) The driving voltage, back EMF and applied current to each zone shall be
recorded.
f) The Contractor shall carry out any adjustment to the control settings,
which is considered to be necessary.
F. System Review
1. The system review shall be carried out at the end of the 12 month period of
operation. The system review shall include the performance monitoring
specified above. The Contractor shall review all data collected during the
12 months of operation and make recommendations on the future operation of
the system including the following:
2. The system review report shall be issued for comment within 28 days of the
completion of the 12-months monitoring visit.
A. General
B. Test Procedures
1. The ‘as found’ potentials of pipeline and other facilities located in close
proximity shall be measured before the commissioning of the CP system.
2. After the CP system has been commissioned, the interference testing shall
commence. The ON/OFF timer of the CP transformer rectifier(s) shall be set to
operate at 8 seconds ’ON’, 3 seconds ‘OFF’.
3. All the other facilities shall be measured by recording the potentials for a
minimum of 60 seconds during the cyclic ‘ON/OFF’ period. Interference shall
be deemed to be present if the anodic potential shift, as measured on the other
facilities during this period, is coincident with the switching of the transformer
rectifiers.
5. The Contractor shall submit full details for carrying out interference testing for
review and approval by the Royal Commission.
2. The test report shall include all data obtained, details and location of all tests
and indicate the level (if any) of interference observed. Recommendations for
rectification shall be included. The test report shall be submitted to the Royal
Commission.
A. An Operation and Maintenance Manual shall be provided by the Contractor and shall
be a complete and comprehensive reference manual with all relevant information
within one document. The Operation and Maintenance manual shall be provided in
accordance with SECTION 01830.
B. The Contractor shall submit a procedure, as part of the Operation and Maintenance
Manual, detailing how the CP system should be managed. This management shall
include criteria, fault finding, system malfunction checks and details of storage and
presentation of data. The system shall also include other periodic tests, which do not
fall within the interference testing and ‘ON/OFF’ potential surveys.
A. Description
1. As part of the works, the Contractor shall provide training to the nominated
Royal Commission staff in the operation and maintenance of the CP system,
including the system monitoring.
2. Each person trained shall be provided a full set of the course material. All
training material shall be supplied by the Contractor for training purposes.
5. The minimum requirements for these are outlined below. Instruction may take
place in any order and at various times within the Contract period.
B. Routine Operation
1. The data collected from the manual monitoring system and that from periodic
surveys shall be reviewed by an experienced Cathodic Protection Engineer.
Instruction shall be provided on the trend analysis of data and the type of data
required and changes in its recorded level which may signify that the CP
system requires adjustment or some form of remedial action.
END OF SECTION