1 INVERTER SELECTION INVERTER SELECTION MAKE DELTA MAKE DELTA ENTER THE Imax OF ALL INVERTER ON SITE ENTER THE Imax OF ALL INVERTER ON INVERTER CAPACITY I(max) INVERTER CAPACITY INV 1 50 KW 80 Amps INV 1 50 INV 2 30 KW 50 Amps INV 2 30 INV 3 30 KW 50 Amps INV 3 30 INV 4 0 KW Amps INV 4 0 INV 5 0 KW Amps INV 5 0 INV 6 0 KW Amps INV 6 0 TOTAL TOTAL INV power 110 KW 180 I(max) TOTAL INV power 110 2 CABLE SELECTION CABLE SELECTION MAKE POLYCAB MAKE POLYCAB SIZE 95 SQ MM SIZE 70 RESISTANCE 0.41 ῼ/KM RESISTANCE 0.325 CCC 240 Amps CCC 198 LENGTH OF WIRE 100 meters LENGTH OF WIRE 100 3 APPLICABLE DERATING OF CABLE APPLICABLE DERATING OF CABLE (DF)COVERED IN OPEN AIR 0.83 COVERED IN TRENCH 4 DERATED CCC OF CABLE DERATED CCC OF CABLE DCCC=DF*CCC DCCC=DF*CCC SO DCCC = 199.2 Amps SO DCCC = 164.34 NOTE: DCCC › I(max) NOTE: DCCC < I(max) 5 CALCULATING POWER LOSS% CALCULATING POWER LOSS% P(loss)%=(Imax²*R*L*100)/INV power P(loss)%=(Imax²*R*L*100)/INV power resistance R = 0.00041 ῼ/M resistance R = 0.000325 TOTAL INV power 110000 Watt TOTAL INV power 110000 so P(loss)% = 1.207636 % so P(loss)% = 0.957273 B TO MDB(CLIENT'S SIDE) SE 2 CASE 3 SELECTION INVERTER SELECTION DELTA MAKE DELTA E Imax OF ALL INVERTER ON SITE ENTER THE Imax OF ALL INVERTER ON SITE CAPACITY I(max) INVERTER CAPACITY I(max) KW 80 Amps INV 1 50 KW 80 Amps KW 50 Amps INV 2 30 KW 50 Amps KW 50 Amps INV 3 30 KW 50 Amps KW Amps INV 4 0 KW Amps KW Amps INV 5 0 KW Amps KW Amps INV 6 0 KW Amps TOTAL TOTAL KW 180 I(max) TOTAL INV power 110 KW 180 I(max) SELECTION CABLE SELECTION POLYCAB MAKE POLYCAB SQ MM SIZE 50 SQ MM ῼ/KM RESISTANCE 0.82 ῼ/KM Amps CCC 138 Amps meters LENGTH OF WIRE 100 meters RATING OF CABLE APPLICABLE DERATING OF CABLE 0.83 COVERED IN TRENCH 0.87 CCC OF CABLE DERATED CCC OF CABLE =DF*CCC DCCC=DF*CCC Amps SO DCCC = 120.06 Amps CC < I(max) NOTE: DCCC › I(max) G POWER LOSS% CALCULATING POWER LOSS% R*L*100)/INV power P(loss)%=(Imax²*R*L*100)/INV power ῼ/M resistance R = 0.00082 ῼ/M Watt TOTAL INV power 110000 Watt % so P(loss)% = 2.415273 %