You are on page 1of 3

UNY and UNF Unions

Explosionproof, Dust-Ignitionproof

NEC/CEC:
Class I, Division 1 and 2 Groups A, B, C, D
Class II, Division 1 and 2 Groups E, F, G
Class III

Applications
• UNY and UNF unions are used for joining conduit and
connecting conduit to enclosures. Facilitates modifications,
permits removal of enclosures without turning or removal of
conduit.
• Expansion unions compensate for expansion and contraction
of conduit.
Features
• Explosionproof, dust-ignitionproof.
• Smooth, rounded integral bushing in each hub protects
conductor insulation.
• Accurately tapped, tapered threads for tight, rigid joints and
ground continuity.
• Non-expansion unions
— Concentric ring interlocked design of 1/2”,3/4” and 1” sizes
makes possible smaller diameter, allowing use in tighter
spaces. 1-1/4” and larger UNY sizes have removable male
nipple.
— Concretetight
• Expansion unions
— One-piece design eliminates need for disassembly during
installation.
— Telescoping cylinder within cylinder design permits expansion
or contraction.
— Standard or long types available.
— Small external diameters—excellent in restricted areas in
wiring of pumps, motors, and other equipment.
— Internal phosphor bronze “bonding jumper” ring assures
positive ground between telescoping cylinders.
Standard Materials
• UNY and UNF (non-expansion) unions:
— 1/2” thru 1”: steel or aluminum
— 1-1/4” thru 6”: malleable iron or copperfree (4/10 of 1% max.)
aluminum
• UNY and UNF expansion unions: steel
• Concretetight
Standard Finishes
• Malleable iron products: triplecoat — (1) zinc electroplate, (2)
chromate and (3) epoxy powder coat
• Steel products: zinc electroplate
• Aluminum products 1/2" thru 4": natural
Options
• PVC coating available on select unions. Add suffix -PVC to
catalog number.
• Stainless steel UNF/UNY available 1/2",3/4", and 1". Add suffix
-SS to catalog number.
NEC/CEC Certifications and Compliances
• UL Standard: 886
• UL Listed: E-34997
• CSA Standard: C22.2 No. 30
• CSA Certified: 065181
NEC Articles 500-503 and 505
Mil. Spec: Mil-F28675

Visit our website at www.ozgedney.com or contact us at (800) 621-1506. 37


© January 2016
UNY and UNF Unions
Explosionproof, Dust-Ignitionproof

NEC/CEC:
Class I, Division 1 and 2 Groups A, B, C, D
Class II, Division 1 and 2 Groups E, F, G
Class III

Dimensions in Millimeters Dimensions in Millimeters Dimensions in Millimeters


(Inches) (Inches) (Inches)

Trade Size Overall Malleable Overall Copper Free Overall


(Inches) Steel Length Max. Dia. Iron Length Max. Dia. Aluminum Length Max. Dia.
1/2 UNF-50S 1-1/2 1-1/2 — — — UNF-50A 1-1/2 1-1/2
3/4 UNF-75S 1-1/2 1-3/4 — — — UNF-75A 1-1/2 1-3/4
1 UNF-100S 2-23/32 2 — — — UNF-100A 1-23/32 2
1-1/4 — — — UNF-125 2-1/5 2-13/16 UNF-125A 2-1/5 2-13/16
1-1/2 — — — UNF-150 2-1/5 3-1/16 UNF-150A 2-1/5 3-1/16
2 — — — UNF-200 2-5/16 3-23/32 UNF-200A 2-5/16 3-23/32
2-1/2 — — — UNF-250 3-3/8 4-7/8 UNF-250A 3-3/8 4-7/8
3 — — — UNF-300 3-3/8 5-3/8 UNF-300A 3-3/8 5-3/8
4 — — — UNF-400 3-1/2 6-7/16 UNF-400A 3-1/2 6-7/16
5 — — — UNF-500 3-7/8 8-3/8 UNF-500A 4-5/16 8-1/4
6 — — — UNF-600 4 9-5/8 UNF-600A 4-5/16 9-3/8

Dimensions in Millimeters Dimensions in Millimeters Dimensions in Millimeters


(Inches) (Inches) (Inches)

Trade Size Overall Malleable Overall Copper Free Overall


(Inches) Steel Length Max. Dia. Iron Length Max. Dia. Aluminum Length Max. Dia.
1/2 UNY-50S 2-9/64 1-15/32 — — — UNY-50A 2-9/64 1-15/32
3/4 UNY-75S 2-5/32 1-3/4 — — — UNY-75A 2-5/32 1-1/4
1 UNY-100S 2-5/8 2 — — — UNY-100A 2-5/8 2
1-1/4 — — — UNY-125 3-1/8 2-13/16 UNY-125A 3-1/8 2-13/16
1-1/2 — — — UNY-150 3-1/4 3-1/16 UNY-150A 3-1/4 3-1/16
2 — — — UNY-200 3-5/8 3-23/32 UNY-200A 3-5/8 3-23/32
2-1/2 — — — UNY-250 4-13/16 4-7/8 UNY-250A 4-13/16 4-7/8
3 — — — UNY-300 4-13/16 5-3/8 UNY-300A 4-13/16 5-3/8
3-1/2 — — — UNY-350 4-15/16 5-7/8 UNY-350A 4-15/16 5-7/8
4 — — — UNY-400 5-1/8 6-7/16 UNY-400A 5-1/8 6-7/16
5 — — — UNY-500 5-5/8 8-3/8 UNY-500A 6-1/8 8-1/4
6 — — — UNY-600 5-3/4 9-5/8 UNY-600A 6-1/8 9-5/8

 CSA Listed.

38 Visit our website at www.ozgedney.com or contact us at (800) 621-1506.


© January 2016
UNY and UNF Unions
Explosionproof, Dust-Ignitionproof

NEC/CEC:
Class I, Division 1 and 2 Groups A, B, C, D
Class II, Division 1 and 2 Groups E, F, G
Class III

Millimeters (Inches) Catalog Number


Size Steel (1/2” to 1”) Aluminum
(Inches) A B and Malleable (1-1/4” to 6”) (1/2” to 4”)
UNY Unions — For connecting conduit to enclosure
Male/Female (Nipple Not Removable)
1/2 54.4 (2.147) 37.3 (1.47) UNY-50S  UNY-50A 
3/4-1/2 54.8 (2.16) 37.3 (1.47) UNY-75-50S 
UNY-75-50A 
3/4 54.8 (2.16) 44.5 (1.75) UNY-75S  
UNY-75A 
1/2" — 1" 1 66.7 (2.62) 50.8 (2.00) UNY-100S  UNY-100A 
Male/Female (Removable Male Nipple)
1-1/4 79.4 (3.13) 71.4 (2.81) UNY-125  UNY-125NA 
1-1/2 82.6 (3.25) 77.8 (3.06) UNY-150  
UNY-150NA 
2 92.1 (3.63) 94.5 (3.72) UNY-200  UNY-200NA 
1-1/4" — 4"
2-1/2 122.2 (4.81) 123.8 (4.88) UNY-250  UNY-250A 
3 122.2 (4.81) 136.5 (5.38) UNY-300  
UNY-300A 
3-1/2 125.4 (4.94) 149.2 (5.88) UNY-350  
UNY-350A 
4 130.2 (5.13) 163.5 (6.44) UNY-400  
UNY-400A 
5" — 6" 5 142.9 (5.63) 212.7 (8.33) UNY-500  UNY-500A
6 146.1 (5.75) 244.5 (9.63) UNY-600  UNY-600A
UNF Female Unions — For connecting conduit to conduit
1/2 37.3 (1.47) 37.3 (1.47) UNF-50S  UNF-50A 
3/4-1/2  37.3 (1.47) 37.3 (1.47) UNF-75-50S 
UNF-75-50A 
3/4 37.3 (1.47) 44.5 (1.75) UNF-75S  
UNF-75A 
1/2" — 1" 1 43.7 (1.72) 50.8 (2.00) UNF-100S  UNF-100A 
1-1/4 55.6 (2.19) 71.4 (2.81) UNF-125NR  UNF-125A 
1-1/2 55.6 (2.19) 77.8 (3.06) UNF-150NR  
UNF-150A 
2 58.7 (2.31) 94.5 (3.72) UNF-200NR  
UNF-200A 
2-1/2 85.7 (3.38) 123.8 (4.88) UNF-250R  
UNF-250A 
1-1/4" — 4"
3 85.7 (3.38) 136.5 (5.38) UNF-300R  UNF-300A 
3-1/2 85.7 (3.38) 149.2 (5.88) UNF-350R  UNF-350A 
4 88.9 (3.50) 163.5 (6.44) UNF-400R  
UNF-400A 
5 98.4 (3.88) 212.7 (8.38) UNF-500R  UNF-500A
5" — 6"
6 101.6 (4.00) 244.5 (9.63) UNF-600R  UNF-600A

 Male end given first


 PVC coating available on select unions. Add suffix -PVC to catalog number.
 Indicates items in the shaded area which are UL Listed for Class I, Groups A, B, C, D; Class II, Groups E, F, G; and Class III.
 Indicated items in the shaded area which are UL Listed for Class I, Groups B, C, D; Class II, Groups E, F, G; and Class III.

Visit our website at www.ozgedney.com or contact us at (800) 621-1506. 39


© January 2016

You might also like