The frequency response analysis test is a very A Recurrent Surge Generator (RSG) is used to
sensitive technique for detecting winding movement generate the low voltage pulse which is applied to the
caused by loss of clamping pressure or by short circuit transformer HV winding terminal H1. The LV winding
forces. This test has been used extensively to terminals X1 and X2 are, in turn, grounded through a
successfully detect winding movements. current shunt. The applied voltage (to terminal H1) and
the voltage across the current shunt (representing the
Test Method capacitively coupled current into the secondary winding)
The frequency response analysis (FRA) method of are recorded on a digital oscilloscope. The recorded
detecting transformer winding movement is based on transients are stored for processing and archiving.
taking a "signature” of the winding. A short low voltage
impulse (300 V) is applied to one winding. The applied
impulse and the capacitively coupled current in another
winding are recorded. Changes in capacitances
between the two windings as well as changes in the
inter-turn winding capacitances - caused by winding
movement - are reflected in the change of the
waveshape of the coupling current. The current and
voltage measurements are recorded with a digital
oscilloscope and stored for later analysis.