Release Date: Jul. 2018 / Manual Revision: 1.

01

Recloser Control ETR300-R & EVRC2A-NT

IEC 60870-5-101/104 Protocol


Technical Manual
(TYPE : RECLOSER-MAP-S)

ENTEC ENTEC
ELECTRIC & ELECTRONIC CO., LTD

Copyright © 2011 by ENTEC ELECTRIC & ELECTRONIC CO., LTD all right reserved. Forerunner Distribution & Automation
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

Release Note:

[Dec. 2017] Ver1.00


New IEC 60870-5-101/104 Protocol Technical Manual for new type Recloser Control ETR300-R

[Jul. 2018] Ver1.01


Manual additionally applicable for new type Recloser Control EVRC2A-NT

ENHANCED TECHNOLOGY i
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

TABLE OF CONTENTS

A. Introduction ………………………..…………………………………………………………...1

B. Configuration for IEC 60870-5-101/104 ..…....……………………………………………….2

C. Analogue Event Reporting …............…...……………………………………………………10

D. Interoperability Document …...........…...….……………………………………………….12

E. IEC 60870-5-101/104 Point Table ……………………………………………...……………..35

ii ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

A. Introduction

IEC 60870-5 provides a communication method to send basic telecontrol messages between two
systems. The IEC Technical Committee 57 have developed a protocol standard for Telecontrol,
Teleprotection, and associated telecommunications for electric power systems.

This document is based on IEC 60870-5-101/-104. This document describes communication


method between Entec’s Recloser Control (ETR300-R or EVRC2A-NT) and Master Station, and
provides “Interoperability Document”, “Point table” and parameter explanations of IEC 60870-5-
101/-104.

IEC 60870-5-101/-104 are applied to tele-control equipment and systems with coded bit serial data
transmission for monitoring and controlling geographically widespread processes.
IEC 60870-5-101 protocol uses the standard of asynchronous serial tele-control channel interface
between DTE (Data Terminal Equipment) and DCE (Data Communication Equipment). The
standard is suitable for multiple configurations like point-to-point and multipoint.
IEC 60870-5-104 protocol is an extension of IEC 60870-5-101 protocol with the changes in terms
of transport, network, link & physical layer services for the complete network access. The standard
uses an open TCP/IP interface to network to have connectivity to the LAN(Local Area Network)
and routers with different facility(ISDN, X.25, Frame relay etc) can be used to connect to the WAN
(Wide Area Network). Application layer of IEC 60870-5-104 is preserved same as that of IEC
60870-5-101 with some of the data types and facilities not used. There are two separate link layers
defined in the standard and suitable for data transfer over Ethernet & serial line (PPP - Point-to-
Point Protocol).

ENHANCED TECHNOLOGY 1
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

B. Configuration for IEC 60870-5-101/104

1. Configuration for IEC 60870-5-101


Table B-1. Configuration for IEC 60870-5-101

Setting Item Description Step Default


Function Whether to use IEC60870-5-101 (ENABLE, DISABLE) - DISABLE
COM Port Communication Port Setting (PORT1, PORT2, PORT3,) - PORT1
Address Slave(Recloser Control) address for IEC60870-5-101(1 ~ 65535) 1 1
ASDU Addr Application service data unit address (0 ~ 65535) 1 0
Cyclic Period Cyclic Period. It is to set interval time between Point set for Cyclic(1~60000sec) 1 60sec
Event Period Delay time before events are sent (0 ~ 255sec) 1 15sec
Retries Data retires number 1 0
Conf. Timeout Wait time till receive the Data Confirm (ACK) of master after transfer the Data(1 ~ 255sec) 1 10 sec
Max Poll Tim Data Polling period time (1 ~ 255sec) 1 10 sec
ADSU Addr Size Size of common address of ASDU(1~2) 1 2
Link Confirm Link layer confirm mode (NEVER, ALWAYS) - ALWAYS
Link Addr Size Link Address Size (1~2) 1 1
Rx Frame Size Maximum size of receive frame (0~261) 1 261
Maximum amount of time to wait for a complete frame after receiving the 1
Rx Frame TO 15
frame sync (0(OFF), 1~255sec)
Tx Frame Size Maximum size of transmit frame (0~261) 1 261
COT Size Size of Cause of transmission (1~2) 1 1
IOA Size Size of information object address (1~3) 1 2
Allowed to send one character response instead of a fixed length NACK when -
One Ch Response NO
no response data available(NO, YES)
Frame Repet’ TO The time out for repetition of frames (0(OFF), 1~255sec) 1 30
Select Timeout The period after a previously received select will timeout (0(OFF), 1~255sec) 1 5
Whether to send Activation Termination upon completion of commands other -
CMD Termination NO
than set point commands(NO, YES)
Whether to send Activation Termination upon completion of set point -
CSE Termination YES
commands (NO, YES).
Clock Sync’ Evt Whether to generate spontaneous clock synchronization events (NO, YES) - YES
MSP Time-Tag Time tag format for single-point (CP56, CP24) - CP56
MIT Time-Tag Time tag format for integrated totals (CP56, CP24) - CP56
Time tag format for measured value and normalized value, in case of general -
MME Time-Tag CP56
event (CP56, CP24)
Time tag format for measured value and normalized value in fault current -
Flt Time-Tag CP56
event (CP56, CP24)

2 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

Function
Select whether to use IEC60870-5-101 Protocol.

Use Port
Set physical port to use IEC60870-5-101 communication.

Link Address
Enter the slave address for IEC60870-5-101 communication.

ASDU Address
Enter the Application Service Data Unit Address.

Cyclic Period
Enter the Cyclic Period. It is to set interval time between Point set for Cyclic.

Event Period
Enter the delay time before events are sent. Single event or several events occur and then if new
event is not generated during the delay time, the event(s) already generated is(are) sent to a Master.

Retries
Enter the Data retires number.

Conf. Timeout
Enter the wait time till receive the Data Confirm (ACK) of master after transfer the Data. If there isn’t
the Confirm during this setting time and Data retries is available, Entec’s Recloser Control transfers
the Data again.

Max Poll Time


Enter the Data Polling period time.

ADSU Addr Size


Enter the size of cause of transmission.

Link Confirm
Enter the Link layer confirm mode.

Link Addr Size


Enter the size of link address.

ENHANCED TECHNOLOGY 3
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

Rx Frame Size
Enter the maximum size of received frame.

Rx Frame TO
Enter the maximum amount of time to wait for a complete frame after receiving the frame sync.

Tx Frame Size
Enter the maximum size of transmitted frame.

COT Size
Enter the size of cause of transmission.

IOA Size
Enter the size of information object address.

One Ch Response
This allows to send one character response instead of a fixed length NACK when no response data
available.

Frame Repet’ TO
Enter the time out for repetition of frames(or incremental application layer timeout).

Select Timeout
Enter the period after a previously received select will timeout.

CMD Termination
Select whether to send Activation Termination upon completion of commands other than set point
commands.

CSE Termination
Select whether to send Activation Termination upon completion of set point commands.

Clock Sync’ Evt


Select whether to generate spontaneous clock synchronization events

4 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

MSP Time-Tag
Select whether a time tag format for single-point.

MIT Time-Tag
Select whether a time tag format for integrated totals.

MME Time-Tag
Select whether a time tag format for measured value and normalized value for general event except
for fault current event.

Flt Time-Tag
Select whether a time tag format for measured value and normalized value for fault current event.

ENHANCED TECHNOLOGY 5
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

2. Configuration for IEC 60870-5-104


Table B-4. Configuration for IEC 60870-5-104

Setting Item Description Step Default


Function Whether to use IEC60870-5-104 (ENABLE, DISABLE) - DISABLE
COM Port Communication Port Setting (PORT4, PORT5) - PORT4
ASDU Addr Application service data unit address (0 ~ 65535) 1 0
Cyclic Period. It is to set interval time between Point set for 1 60sec
Cyclic Period
Cyclic(1~60000sec)
Time Out(t0) Timeout for connection establishment (1 ~ 255sec) 1 120 sec
Time Out(t1) Timeout for send or test APDUs(1 ~ 255sec) 1 15 sec
Time Out(t2) Timeout for acknowledgements in case of no data message(1 ~ 255sec) 1 10 sec
Time Out(t3) Timeout for sending test frame in case of a long idle state(1 ~ 255sec) 1 20 sec
Event Period delay time before events are sent(0 ~ 255sec) 1 15sec
TCP Port No TCP/IP Port of Slave(Recloser Control) for IEC60870-5-104(0 ~ 65535) 1 2404
Rx Frame Size* Maximum size of receive frame (0~255) 1 255
Tx Frame Size* Maximum size of transmit frame (0~255) 1 255
The period after a previously received select will timeout (0(OFF), 1
Select Timeout* 5
1~255sec)
Whether to send Activation Termination upon completion of commands -
CMD Termination* YES
other than set point commands(NO, YES)
Whether to send Activation Termination upon completion of set point -
CSE Termination* YES
commands(NO, YES).
Clock Sync’ Evt* Whether to generate spontaneous clock synchronization events (NO, YES) - YES
MSP Time-Tag** Time tag format for single-point (CP56, CP24) - CP56
MIT Time-Tag** Time tag format for integrated totals (CP56, CP24) - CP56
Time tag format for measured value and normalized value, in case of general -
MME Time-Tag** CP56
event (CP56, CP24)
Time tag format for measured value and normalized value in fault current -
Flt Time-Tag** CP56
event (CP56, CP24)
*. NOTE ) 1. The above setting marked with * shall be Ver. 2.05 or higher of CPU firmware to be indicated.
2. The above setting marked with ** shall be Ver. 2.10 or higher of CPU firmware to be indicated.

Function
Select whether to use IEC60870-5-104 Protocol.

COM Port
Enter a port for IEC60870-5-104 communication. It is fixed in PORT4.

ASDU Address
Enter the Application Service Data Unit Address.

6 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

Cyclic Period
Enter the Cyclic Period. It is to set interval time between Point set for Cyclic.

Timeout(t0)
Select the Timeout for connection establishment.

Timeout(t1)
Select the Timeout for send or test APDUs.

Timeout(t2)
Select the Timeout for acknowledgements in case of no data message ( t2<t1).

Timeout(t3)
Select the Timeout for sending test frame in case of a long idle state.

Event Period
Select the delay time before events are sent. Single event or several events occur and then if new
event is not generated during the delay time, the event(s) already generated is(are) sent to a Master.

TCP Port
Set the TCP Port of Entec’s Recloser Control for IEC60870-5-104 Protocol communication.

Rx Frame Size
Enter the maximum size of received frame.

Tx Frame Size
Enter the maximum size of transmitted frame.

Select Timeout
Enter the period after a previously received select will timeout.

CMD Termination
Select whether to send Activation Termination upon completion of commands other than set point
commands.

CSE Termination
Select whether to send Activation Termination upon completion of set point commands.

ENHANCED TECHNOLOGY 7
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

Clock Sync’ Evt


Select whether to generate spontaneous clock synchronization events.

MSP Time-Tag
Select whether a time tag format for single-point.

MIT Time-Tag
Select whether a time tag format for integrated totals.

MME Time-Tag
Select whether a time tag format for measured value and normalized value for general event except
for fault current event.

Flt Time-Tag
Select whether a time tag format for measured value and normalized value for fault current event.

8 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

3. Configuration for IOA(Information Object Address)


Setting Item Description Step Default
MSP Start Single-point information 1 1000

MDP Start Double-point information 1 1500

MMENA Start Measured value, normalized value 1 2000

MMENB Start Measured value, scaled value 1 2500

MMENC Start Measured value, short floating point value 1 8000

MMEND Start Measured value, normalized value without quality descriptor 1 6000

MIT Start Integrated totals 1 3000

CSC Start Single command 1 21000

CDC Start Double command 1 32000

CSEMA Start Set point command, normalized value 1 26000

CSEMB Start Set point command, scaled value 1 27000

PMENA Start Parameter of measured value, normalized value 1 10000

PMENB Start Parameter of measured value, scaled value 1 12000

PMENC Start Parameter of measured value, short floating point value 1 14000

ENHANCED TECHNOLOGY 9
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

C. Analogue Event Reporting


 Threshold Configuration

NOTE )
“Threshold” used in IEC60870-5-101/104 protocol is described as “Deadband” in the settings
and manuals of all ENTEC’s products.
In order to change the Threshold Configuration for IEC 60870-5-101/104 protocol
communication, change settings such as Limit Low, Limit High, Dead Band or Smoothing
Factor in the “DB MAP CONFIGURATION” setting on the application program.
“Threshold” is described as “Deadband” in the explanation below.

A maximum or minimum value of an analog input can be configured to set the desired range for
analog event reporting. Deadband value is set to generate the event when the analog input’s
value difference between the last value and the current value exceeds the deadband value. The
time period of data updating is 1sec.

Figure C-1. Threshold (Deadband) configuration

- Max./Min. value: Maximum and minimum values set by a device.


- Limit High: Highest value configured by a user
- Limit Low: Lowest value configured by a user
- Smoothing: Not used
- Deadband: Event will be generated when during data updating time period (1sec), analog

10 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

input’s value difference between the last value and the current value is over the
deadband value configured by a user. For example, in Figure 1, if the value
difference between the analog input’s values at t1 and t2 exceeds the deadband
value, the event occurs. If the measured value at t4 is below the “Limit Low”
value, the value difference between t3 and t4 is considered as the difference
between the analog input value at t3 and t4 and so the variation between t3 and t4
generates event if it is over the deadband value.
However, after the measured value crosses down the “Limit Low” value once like
the value at t4 and if the subsequent measured values after the time t4 keep
changing below the “Limit Low” value, those variations below the “Limit Low”
value do not generate event even though the variations below the “Limit Low”
value exceeds the deadband value. If the measured value comes in the range
between the “Limit High” and the “Limit Low” values again and the variation at
that time exceeds the deadband value, the event for the variation is generated. In
the same way, an event is generated for the value crossing over or down the
“Limit High” value.

*. “AEvt Method” setting in the “GLOBAL SETTING / COMMUNICATION / EVENT&ETC”


menu of Entec’s Recloser Control must be set to be “DB” or “BOTH” to generate analogue
events.

ENHANCED TECHNOLOGY 11
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

D. Interoperability Document

1. Interoperability Document for IEC 60870-5-101


This document is adapted from the IEC 60870-5-101 standard. For the section the boxes indicate
the following: ▣ – used in standard direction; □ – not used; ■ – cannot be selected in IEC 60870-
5-101 standard.

(1) SYSTEM OR DEVICE:


□ System Definition

□ Controlling Station Definition (Master)

▣ Controlled Station Definition (Slave)

(2) NETWORK CONFIGURATION:


▣ Point-to-Point ▣ Multipoint

□ Multiple Point-to-Point □ Multipoint Star

(3) PHYSICAL LAYER


Transmission Speed (control direction):

Unbalanced Interchange Unbalanced Interchange Balanced Interchange circuit

Circuit V.24/V.28 Standard: Circuit V.24/V.28 Recommended X.24/X.27:

if>1200 bits/s:

□ 100bits/sec. ▣ 2400bits/sec. ▣ 2400bits/sec.

□ 200bits/sec. ▣ 4800bits/sec. ▣ 4800bits/sec.

□ 300bits/sec. ▣ 9600bits/sec. ▣ 9600bits/sec.

□ 600bits/sec. ▣ 19200bits/sec.

▣ 1200bits/sec. ▣ 38400bits/sec.

▣ 56000bits/sec.

□ 64000bits/sec

12 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

Transmission Speed (monitor direction):

Unbalanced Interchange Unbalanced Interchange Balanced Interchange circuit

Circuit V.24/V.28 Standard: Circuit V.24/V.28 Recommended X.24/X.27:

if>1200 bits/s:

□ 100bits/sec. ▣ 2400bits/sec. ▣ 2400bits/sec.

□ 200bits/sec. ▣ 4800bits/sec. ▣ 4800bits/sec.

□ 300bits/sec. ▣ 9600bits/sec. ▣ 9600bits/sec.

□ 600bits/sec. ▣ 19200bits/sec.

▣ 1200bits/sec. ▣ 38400bits/sec.

▣ 56000bits/sec.

□ 64000bits/sec

(4) LINK LAYER


Link Transmission Procedure: Address Field of the Link:

□ Balanced Transmission □ Not Present (Balanced Transmission Only)

▣ Unbalanced Transmission ▣ One Octet

▣ Two Octets (*)

□ Structured

▣ Unstructured
*. NOTE ) The above item marked with * are supported from Ver. 2.05 of
CPU firmware.

Frame Length :

255 : Maximum length L(control direction)


255 : Maximum length L(monitor direction)
Configurable : Time during which repetitions are permitted (Trp) or number of repetitions.

When using an unbalanced link layer, the following ADSU types are returned in class 2 messages (low
priority) with the indicated causes of transmission:

▣ The standard assignment of ADSUs to class 2 messages is used as follows:

Type identification Cause of transmission

9 <1>

□ A special assignment of ADSUs to class 2 messages is used as follows:

※ Note) In response to a class 2 poll, a controller station may respond with class 1 data when there is no

class 2 data available.

ENHANCED TECHNOLOGY 13
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

(5) APPLICATION LAYER


Transmission Mode for Application Data:
Mode 1 (least significant octet first), as defined in Clause 4.10 of IEC 60870-5-1, is used exclusively in
this companion standard.

Common Address of ADSU:


▣ One Octet (*) ▣ Two Octets

*. NOTE ) The above item marked with * are supported from Ver. 2.05 of CPU firmware.

Information Object Address:


▣ One Octet (*) □ Structured

▣ Two Octets ▣ Unstructured


▣ Three Octets (*)

*. NOTE ) The above item marked with * are supported from Ver. 2.05 of CPU firmware.

Cause of Transmission:
▣ One Octet

▣ Two Octets (with originator address). Originator address is set to zero if not used. (*)

*. NOTE ) The above item marked with * are supported from Ver. 2.05 of CPU firmware.

Selection of standard ASDUs:


For the following lists, the boxes indicate the following:

▣– used in standard direction; □ – not used; ■ – cannot be selected in IEC 60870-5-104 standard.

Process information in monitor direction


▣ <1> := Single-point information M_SP_NA_1

▣ <2> := Single-point information with time tag(**) M_SP_TA_1

▣ <3> := Double-point information M_DP_NA_1

■ <4> := Double-point information with time tag M_DP_TA_1

□ <5> := Step position information M_ST_NA_1

■ <6> := Step position information with time tag M_ST_TA_1

□ <7> := Bitstring of 32 bits M_BO_NA_1

■ <8> := Bitstring of 32 bits with time tag M_BO_TA_1

▣ <9> := Measured value, normalized value M_ME_NA_1

▣ <10> := Measured value, normalized value with time tag(**) M_NE_TA_1

14 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

▣ <11> := Measured value, scaled value M_ME_NB_1

■ <12> := Measured value, scaled value with time tag M_NE_TB_1

□ <13> := Measured value, short floating point value M_ME_NC_1

■ <14> := Measured value, short floating point value with time tag M_NE_TC_1

▣ <15> := Integrated totals M_IT_NA_1

▣ <16> := Integrated totals with time tag(**) M_IT_TA_1

■ <17> := Event of protection equipment with time tag M_EP_TA_1

■ <18> := Packed start events of protection equipment with time tag M_EP_TB_1

■ <19> := Packed output circuit information of protection equipment with time tag M_EP_TC_1

■ <20> := Packed single-point information with status change detection M_SP_NA_1

▣ <21> := Measured value, normalized value without quantity descriptor M_ME_ND_1

▣ <30> := Single-point information with time tag CP56Time2a M_SP_TB_1

▣ <31> := Double-point information with time tag CP56Time2a M_DP_TB_1

□ <32> := Step position information with time tag CP56Time2a M_ST_TB_1

□ <33> := Bitstring of 32 bits with time tag CP56Time2a M_BO_TB_1

▣ <34> := Measured value, normalized value with time tag CP56Time2a (*) M_ME_TD_1

□ <35> := Measured value, scaled value with time tag CP56Time2a M_ME_TE_1

□ <36> := Measured value, short floating point value with time tag CP56Time2a M_ME_TF_1

▣ <37> := Integrated totals with time tag CP56Time2a M_IT_TB_1

□ <38> := Event of protection equipment with time tag CP56Time2a M_EP_TD_1

□ <39> := Packed start events of protection equipment with time tag CP56Time2a M_EP_TE_1

□ <40> := Packed output circuit information of protection equipment

with time tag CP56Time2a M_EP_TF_1

Either the ASDUs of the set <2>, <4>, <6>, <8>, <10>, <12>, <14>, <16>, <17>, <18>, and <19> or of the

set <30> to <40> are used.

*. NOTE ) 1. The above item marked with * are supported from Ver. 2.05 of CPU firmware.
2. The above item marked with * are supported from Ver. 2.10 of CPU firmware.

Process information in control direction


▣ <45> := Single command C_SC_NA_1

▣ <46> := Double command C_DC_NA_1

□ <47> := Regulating step command C_RC_NA_1

▣ <48> := Set point command, normalized value C_SE_NA_1

□ <49> := Set point command, scaled value C_SE_NB_1

□ <50> := Set point command, short floating point value C_SE_NC_1

□ <51> := Bitstring of 32 bits C_BO_NA_1

ENHANCED TECHNOLOGY 15
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

System information in monitor direction


▣ <70> := End of initialization M_EI_NA_1

System information in control direction


▣ <100> := Interrogation command C_IC_NA_1

▣ <101> := Counter interrogation command C_CI_NA_1

▣ <102> := Read command C_RD_NA_1

▣ <103> := Clock synchronization command (see Clause 7.6 in standard) C_CS_NA_1

■<104> := Test command C_TS_NA_1

▣<105> := Reset process command C_RP_NA_1

■<106> := Delay acquisition command C_CD_NA_1

Parameter in control direction


▣ <110> := Parameter of measured value, normalized value PE_ME_NA_1

□ <111> := Parameter of measured value, scaled value PE_ME_NB_1

□ <112> := Parameter of measured value, short floating point value PE_ME_NC_1

□ <113> := Parameter activation PE_AC_NA_1

File transfer
□ <120> := File Ready F_FR_NA_1

□ <121> := Section Ready F_SR_NA_1

□ <122> := Call directory, select file, call file, call section F_SC_NA_1
□ <123> := Last section, last segment F_LS_NA_1

□ <124> := Ack file, ack section F_AF_NA_1

□ <125> := Segment F_SG_NA_1

□ <126> := Directory C_CD_NA_1

Type identifier and cause of transmission assignments


(station-specific parameters)

In the following table:

• Shaded boxes are not required.

• Black boxes are not permitted in this companion standard.

• Blank boxes indicate functions or ASDU not used.

•‘X’ if only used in the standard direction

TYPE CAUSE OF TRANSMISSION

16 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

IDENTIFICATION

PERIODIC, CYCLIC

BACKGROUND SCAN

SPONTANEOUS

INITIALIZED

REQUEST OR REQUESTED

ACTIVATION

ACTIVATION CONFIRMATION

DEACTIVATION

DEACTIVATION CONFIRMATION

ACTIVATION TERMINATION

RETURN INFO CAUSED BY REMOTE CMD

RETURN INFO CAUSED BY LOCAL CMD

FILE TRANSFER

INTERROGATED BY GROUP <NUMBER>

REQUEST BY GROUP <N> COUNTER REQ

UNKNOWN TYPE IDENTIFICATION

UNKNOWN CAUSE OF TRANSMISSION

UNKNOWN COMMON ADDRESS OF ADSU

UNKNOWN INFORMATION OBJECT ADDR


20 37
NO. MNEMONIC 1 2 3 4 5 6 7 8 9 10 11 12 13 to to 44 45 46 47
36 41

<1> M_SP_NA_1 X X X

<2> M_SP_TA_1** X X X

<3> M_DP_NA_1

<4> M_DP_TA_1

<5> M_ST_NA_1

<6> M_ST_TA_1

<7> M_BO_NA_1

<8> M_BO_TA_1

<9> M_ME_NA_1 X X X X

<10> M_ME_TA_1** X

<11> M_ME_NB_1

<12> M_ME_TB_1

<13> M_ME_NC_1

<14> M_ME_TC_1

<15> M_IT_NA_1 X X

<16> M_IT_TA_1** X

<17> M_EP_TA_1

<18> M_EP_TB_1

<19> M_EP_TC_1

<20> M_PS_NA_1

<21> M_ME_ND_1 X X

<30> M_SP_TB_1 X X X

<31> M_DP_TB_1

<32> M_ST_TB_1

ENHANCED TECHNOLOGY 17
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

TYPE CAUSE OF TRANSMISSION


IDENTIFICATION

PERIODIC, CYCLIC

BACKGROUND SCAN

SPONTANEOUS

INITIALIZED

REQUEST OR REQUESTED

ACTIVATION

ACTIVATION CONFIRMATION

DEACTIVATION

DEACTIVATION CONFIRMATION

ACTIVATION TERMINATION

RETURN INFO CAUSED BY REMOTE CMD

RETURN INFO CAUSED BY LOCAL CMD

FILE TRANSFER

INTERROGATED BY GROUP <NUMBER>

REQUEST BY GROUP <N> COUNTER REQ

UNKNOWN TYPE IDENTIFICATION

UNKNOWN CAUSE OF TRANSMISSION

UNKNOWN COMMON ADDRESS OF ADSU

UNKNOWN INFORMATION OBJECT ADDR


20 37
NO. MNEMONIC 1 2 3 4 5 6 7 8 9 10 11 12 13 to to 44 45 46 47
36 41

<33> M_BO_TB_1

<34> M_ME_TD_1* X

<35> M_ME_TE_1

<36> M_ME_TF_1

<37> M_IT_TB_1* X

<38> M_EP_TD_1

<39> M_EP_TE_1

<40> M_EP_TF_1

<45> C_SC_NA_1 X X X X X

<46> C_DC_NA_1

<47> C_RC_NA_1

<48> C_SE_NA_1 X X X X X

<49> C_SE_NB_1

<50> C_SE_NC_1

<51> C_BO_NA_1

<70> M_EI_NA_1* X

<100> C_IC_NA_1 X X X X X

<101> C_CI_NA_1 X X X

<102> C_RD_NA_1 X

<103> C_CS_NA_1 X X X

<104> C_TS_NA_1

<105> C_RP_NA_1 X X

<106> C_CD_NA_1

18 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

TYPE CAUSE OF TRANSMISSION


IDENTIFICATION

PERIODIC, CYCLIC

BACKGROUND SCAN

SPONTANEOUS

INITIALIZED

REQUEST OR REQUESTED

ACTIVATION

ACTIVATION CONFIRMATION

DEACTIVATION

DEACTIVATION CONFIRMATION

ACTIVATION TERMINATION

RETURN INFO CAUSED BY REMOTE CMD

RETURN INFO CAUSED BY LOCAL CMD

FILE TRANSFER

INTERROGATED BY GROUP <NUMBER>

REQUEST BY GROUP <N> COUNTER REQ

UNKNOWN TYPE IDENTIFICATION

UNKNOWN CAUSE OF TRANSMISSION

UNKNOWN COMMON ADDRESS OF ADSU

UNKNOWN INFORMATION OBJECT ADDR


20 37
NO. MNEMONIC 1 2 3 4 5 6 7 8 9 10 11 12 13 to to 44 45 46 47
36 41

<110> P_ME_NA_1 X X X

<111> P_ME_NB_1

<112> P_ME_NC_1

<113> P_AC_NA_1

<120> F_FR_NA_1

<121> F_SR_NA_1

<122> F_SC_NA_1

<123> F_LS_NA_1

<124> F_AF_NA_1

<125> F_SG_NA_1

<126> F_DR_TA_1*

- Blank or X only
*. NOTE ) 1. The above item marked with * are supported from Ver. 2.05 of CPU firmware.
2. The above item marked with * are supported from Ver. 2.10 of CPU firmware.

ENHANCED TECHNOLOGY 19
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

(6) BASIC APPLICATION


FUNCTIONS Station Initialization:
▣ Remote initialization

Cyclic Data Transmission:


▣ Cyclic data transmission

Read Procedure:
▣ Read procedure

Spontaneous Transmission:
▣ Spontaneous transmission

Double transmission of information objects with cause of transmission


spontaneous:
The following type identifications may be transmitted in succession caused by a single status change of

an information object. The particular information object addresses for which double transmission is
enabled are defined in a project-specific list.

□ Single point information: M_SP_NA_1, M_SP_TA_1, M_SP_TB_1, and M_PS_NA_1

□ Double point information: M_DP_NA_1, M_DP_TA_1, and M_DP_TB_1

□ Step position information: M_ST_NA_1, M_ST_TA_1, and M_ST_TB_1

□ Bitstring of 32 bits: M_BO_NA_1, M_BO_TA_1, and M_BO_TB_1 (if defined for a specific project)

□ Measured value, normalized value: M_ME_NA_1, M_ME_TA_1, M_ME_ND_1, and M_ME_TD_1

□ Measured value, scaled value: M_ME_NB_1, M_ME_TB_1, and M_ME_TE_1

□ Measured value, short floating point number: M_ME_NC_1, M_ME_TC_1, and M_ME_TF_1

Station interrogation:
▣ Global

▣ Group 1 ▣ Group 5 ▣ Group 9 ▣ Group 13

▣ Group 2 ▣ Group 6 ▣ Group 10 ▣ Group 14

▣ Group 3 ▣ Group 7 ▣ Group 11 ▣ Group 15

▣ Group 4 ▣ Group 8 ▣ Group 12 ▣ Group 16

20 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

Clock synchronization:
▣ Clock synchronization (optional)

□ Day of week used

▣ RES1, GEN (time tag substituted/ not substituted) used

□ SU-bit (summertime) used

Command transmission:
▣ Direct command transmission

▣ Direct set point command transmission

▣ Select and execute command

▣ Select and execute set point command

□ C_SE ACTTERM used

□ No additional definition

▣ Short pulse duration (duration determined by a system parameter in the outstation)

▣ Long pulse duration (duration determined by a system parameter in the outstation)

□ Persistent output

Transmission of integrated totals:


▣ Mode A: Local freeze with spontaneous transmission (**)

▣ Mode B: Local freeze with counter interrogation (**)

▣ Mode C: Freeze and transmit by counter-interrogation commands (**)

▣ Mode D: Freeze by counter-interrogation command, frozen values reported simultaneously (**)

▣ Counter read

▣ Counter freeze without reset (**)

▣ Counter freeze with reset (**)

▣ Counter reset (**)

▣ General request counter

▣ Request counter group 1 (**)

▣ Request counter group 2 (**)

▣ Request counter group 3 (**)

▣ Request counter group 4 (**)

*. NOTE ) The above item marked with ** are supported from Ver. 2.10 of CPU firmware.

ENHANCED TECHNOLOGY 21
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

Parameter loading:
▣ Threshold value

□ Smoothing factor

▣ Low limit for transmission of measured values

▣ High limit for transmission of measured values

Parameter activation:
□ Activation/deactivation of persistent cyclic or periodic transmission of the addressed object

Test procedure:
□ Test procedure

File transfer:
File transfer in monitor direction:

□ Transparent file

□ Transmission of disturbance data of protection equipment

□ Transmission of sequences of events

□ Transmission of sequences of recorded analog values

File transfer in control direction:

□ Transparent file

Background scan:
□ Background scan

Acquisition of transmission delay:


□ Acquisition of transmission delay

22 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

2. Interoperability Document for IEC 60870-5-104


This document is adapted from the IEC 60870-5-104 standard. For the section the boxes indicate
the following: ▣ – used in standard direction; □ – not used; ■ – cannot be selected in IEC 60870-
5-104 standard.

(1) SYSTEM OR DEVICE:


□ System Definition

□ Controlling Station Definition (Master)

▣ Controlled Station Definition (Slave)

(2) NETWORK CONFIGURATION:


■ Point-to-Point ■ Multipoint

■ Multiple Point-to-Point ■ Multipoint Star

(3) PHYSICAL LAYER


Transmission Speed (control direction):

Unbalanced Interchange Unbalanced Interchange Balanced Interchange circuit

Circuit V.24/V.28 Standard: Circuit V.24/V.28 Recommended X.24/X.27:

if>1200 bits/s:

■ 100bits/sec. ■ 2400bits/sec. ■ 2400bits/sec.

■ 200bits/sec. ■ 4800bits/sec. ■ 4800bits/sec.

■ 300bits/sec. ■ 9600bits/sec. ■ 9600bits/sec.

■ 600bits/sec. ■ 19200bits/sec.

■ 1200bits/sec. ■ 38400bits/sec.

■ 56000bits/sec.

■ 64000bits/sec.

ENHANCED TECHNOLOGY 23
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

Transmission Speed (monitor direction):

Unbalanced Interchange Unbalanced Interchange Balanced Interchange circuit

Circuit V.24/V.28 Standard: Circuit V.24/V.28 Recommended X.24/X.27:

if>1200 bits/s:

■ 100bits/sec. ■ 2400bits/sec. ■ 2400bits/sec.

■ 200bits/sec. ■ 4800bits/sec. ■ 4800bits/sec.

■ 300bits/sec. ■ 9600bits/sec. ■ 9600bits/sec.

■ 600bits/sec. ■ 19200bits/sec.

■ 1200bits/sec. ■ 38400bits/sec.

■ 56000bits/sec.

■ 64000bits/sec.

(4) LINK LAYER


Link Transmission Procedure: Address Field of the Link:

■ Balanced Transmission ■ Not Present (Balanced Transmission Only)

■ Unbalanced Transmission ■ One Octet

■ Two Octets

■ Structured

■ Unstructured

Frame Length (maximum length, number of octets): Not selectable in companion IEC 60870-5-104 standard

When using an unbalanced link layer, the following ADSU types are returned in class 2 messages (low
priority) with the indicated causes of transmission:

■ The standard assignment of ADSUs to class 2 messages is used as follows:

■ A special assignment of ADSUs to class 2 messages is used as follows:

(5) APPLICATION LAYER


Transmission Mode for Application Data:
Mode 1 (least significant octet first), as defined in Clause 4.10 of IEC 60870-5-4, is used exclusively in
this companion standard.

Common Address of ADSU:


■ One Octet ▣ Two Octets

24 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

Information Object Address:


■ One Octet □ Structured

■ Two Octets □ Unstructured

▣ Three Octets

Cause of Transmission:
■ One Octet

▣ Two Octets (with originator address). Originator address is set to zero if not used.

Maximum Length of APDU: 253 (the maximum length may be reduced by the system.)

Selection of standard ASDUs:


For the following lists, the boxes indicate the following:

▣– used in standard direction; □ – not used; ■ – cannot be selected in IEC 60870-5-104 standard.

Process information in monitor direction


▣ <1> := Single-point information M_SP_NA_1

▣ <2> := Single-point information with time tag(**) M_SP_TA_1

▣ <3> := Double-point information M_DP_NA_1

■ <4> := Double-point information with time tag M_DP_TA_1

□ <5> := Step position information M_ST_NA_1

■ <6> := Step position information with time tag M_ST_TA_1

□ <7> := Bitstring of 32 bits M_BO_NA_1

■ <8> := Bitstring of 32 bits with time tag M_BO_TA_1

▣ <9> := Measured value, normalized value M_ME_NA_1

▣ <10> := Measured value, normalized value with time tag(**) M_NE_TA_1

□ <11> := Measured value, scaled value M_ME_NB_1

■ <12> := Measured value, scaled value with time tag M_NE_TB_1

□ <13> := Measured value, short floating point value M_ME_NC_1

■ <14> := Measured value, short floating point value with time tag M_NE_TC_1

▣ <15> := Integrated totals M_IT_NA_1

▣ <16> := Integrated totals with time tag(**) M_IT_TA_1

■ <17> := Event of protection equipment with time tag M_EP_TA_1

■ <18> := Packed start events of protection equipment with time tag M_EP_TB_1

■ <19> := Packed output circuit information of protection equipment with time tag M_EP_TC_1

■ <20> := Packed single-point information with status change detection M_SP_NA_1

ENHANCED TECHNOLOGY 25
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

▣ <21> := Measured value, normalized value without quantity descriptor M_ME_ND_1

▣ <30> := Single-point information with time tag CP56Time2a M_SP_TB_1

▣ <31> := Double-point information wiht time tag CP56Time2a M_DP_TB_1

□ <32> := Step position information with time tag CP56Time2a M_ST_TB_1

□ <33> := Bitstring of 32 bits with time tag CP56Time2a M_BO_TB_1

▣ <34> := Measured value, normalized value with time tag CP56Time2a (*) M_ME_TD_1

▣ <35> := Measured value, scaled value with time tag CP56Time2a M_ME_TE_1

□ <36> := Measured value, short floating point value with time tag CP56Time2a M_ME_TF_1

▣ <37> := Integrated totals with time tag CP56Time2a M_IT_TB_1

□ <38> := Event of protection equipment with time tag CP56Time2a M_EP_TD_1

□ <39> := Packed start events of protection equipment with time tag CP56Time2a M_EP_TE_1

□ <40> := Packed output circuit information of protection equipment

with time tag CP56Time2a M_EP_TF_1

Either the ASDUs of the set <2>, <4>, <6>, <8>, <10>, <12>, <14>, <16>, <17>, <18>, and <19> or of the

set <30> to <40> are used.

*. NOTE ) 1. The above item marked with * are supported from Ver. 2.05 of CPU firmware.
2. The above item marked with * are supported from Ver. 2.10 of CPU firmware.

Process information in control direction


▣ <45> := Single command C_SC_NA_1

▣ <46> := Double command C_DC_NA_1

□ <47> := Regulating step command C_RC_NA_1

▣ <48> := Set point command, normalized value C_SE_NA_1

□ <49> := Set point command, scaled value C_SE_NB_1

□ <50> := Set point command, short floating point value C_SE_NC_1

□ <51> := Bitstring of 32 bits C_BO_NA_1

□ <58> := Single command with time tag CP56Time2a C_SC_TA_1

□ <59> := Double command with time tag CP56Time2a C_DC_TA_1

□ <60> := Regulating step command with time tag CP56Time2a C_RC_TA_1

□ <61> := Set point command, normalized value with time tag CP56Time2a C_SE_TA_1

□ <62> := Set point command, scaled value with time tag CP56Time2a C_SE_TB_1

□ <63> := Set point command, short floating point value with time tag CP56Time2a C_SE_TC_1

□ <64> := Bitstring of 32 bits with time tag CP56Time2a C_BO_TA_1

Either the ASDUs of the set <45> to <51> or of the set <58> to <64> are used.

26 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

System information in monitor direction


▣ <70> := End of initialization M_EI_NA_1

System information in control direction


▣ <100> := Interrogation command C_IC_NA_1

▣ <101> := Counter interrogation command C_CI_NA_1

▣ <102> := Read command C_RD_NA_1

▣ <103> := Clock synchronization command (see Clause 7.6 in standard) C_CS_NA_1

■<104> := Test command C_TS_NA_1

▣<105> := Reset process command C_RP_NA_1

■<106> := Delay acquisition command C_CD_NA_1

▣<107> := Test command with time tag CP56Time2a C_TS_TA_1

Parameter in control direction


▣ <110> := Parameter of measured value, normalized value PE_ME_NA_1

□ <111> := Parameter of measured value, scaled value PE_ME_NB_1

□ <112> := Parameter of measured value, short floating point value PE_ME_NC_1

□ <113> := Parameter activation PE_AC_NA_1

File transfer
□ <120> := File Ready F_FR_NA_1

□ <121> := Section Ready F_SR_NA_1

□ <122> := Call directory, select file, call file, call section F_SC_NA_1

□ <123> := Last section, last segment F_LS_NA_1

□ <124> := Ack file, ack section F_AF_NA_1

□ <125> := Segment F_SG_NA_1

□ <126> := Directory (blank or X, available only in monitor [standard] direction) C_CD_NA_1

Type identifier and cause of transmission assignments


(station-specific parameters)

In the following table:

• Shaded boxes are not required.

• Black boxes are not permitted in this companion standard.

• Blank boxes indicate functions or ASDU not used.

•‘X’ if only used in the standard direction

ENHANCED TECHNOLOGY 27
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

TYPE CAUSE OF TRANSMISSION


IDENTIFICATION

PERIODIC, CYCLIC

BACKGROUND SCAN

SPONTANEOUS

INITIALIZED

REQUEST OR REQUESTED

ACTIVATION

ACTIVATION CONFIRMATION

DEACTIVATION

DEACTIVATION CONFIRMATION

ACTIVATION TERMINATION

RETURN INFO CAUSED BY REMOTE CMD

RETURN INFO CAUSED BY LOCAL CMD

FILE TRANSFER

INTERROGATED BY GROUP <NUMBER>

REQUEST BY GROUP <N> COUNTER REQ

UNKNOWN TYPE IDENTIFICATION

UNKNOWN CAUSE OF TRANSMISSION

UNKNOWN COMMON ADDRESS OF ADSU

UNKNOWN INFORMATION OBJECT ADDR


20 37
NO. MNEMONIC 1 2 3 4 5 6 7 8 9 10 11 12 13 to to 44 45 46 47
36 41

<1> M_SP_NA_1 X X X

<2> M_SP_TA_1** X X X

<3> M_DP_NA_1

<4> M_DP_TA_1

<5> M_ST_NA_1

<6> M_ST_TA_1

<7> M_BO_NA_1

<8> M_BO_TA_1

<9> M_ME_NA_1 X X X X

<10> M_ME_TA_1** X

<11> M_ME_NB_1

<12> M_ME_TB_1

<13> M_ME_NC_1

<14> M_ME_TC_1

<15> M_IT_NA_1 X X

<16> M_IT_TA_1** X

<17> M_EP_TA_1

<18> M_EP_TB_1

<19> M_EP_TC_1

<20> M_PS_NA_1

<21> M_ME_ND_1 X X

<30> M_SP_TB_1 X X X

<31> M_DP_TB_1

28 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

TYPE CAUSE OF TRANSMISSION


IDENTIFICATION

PERIODIC, CYCLIC

BACKGROUND SCAN

SPONTANEOUS

INITIALIZED

REQUEST OR REQUESTED

ACTIVATION

ACTIVATION CONFIRMATION

DEACTIVATION

DEACTIVATION CONFIRMATION

ACTIVATION TERMINATION

RETURN INFO CAUSED BY REMOTE CMD

RETURN INFO CAUSED BY LOCAL CMD

FILE TRANSFER

INTERROGATED BY GROUP <NUMBER>

REQUEST BY GROUP <N> COUNTER REQ

UNKNOWN TYPE IDENTIFICATION

UNKNOWN CAUSE OF TRANSMISSION

UNKNOWN COMMON ADDRESS OF ADSU

UNKNOWN INFORMATION OBJECT ADDR


20 37
NO. MNEMONIC 1 2 3 4 5 6 7 8 9 10 11 12 13 to to 44 45 46 47
36 41

<32> M_ST_TB_1

<33> M_BO_TB_1

<34> M_ME_TD_1* X

<35> M_ME_TE_1

<36> M_ME_TF_1

<37> M_IT_TB_1* X

<38> M_EP_TD_1

<39> M_EP_TE_1

<40> M_EP_TF_1

<45> C_SC_NA_1 X X X X X

<46> C_DC_NA_1

<47> C_RC_NA_1

<48> C_SE_NA_1 X X X X X

<49> C_SE_NB_1

<50> C_SE_NC_1

<51> C_BO_NA_1

<58> C_SC_TA_1 X X X X X

<59> C_DC_TA_1

<60> C_RC_TA_1

<61> C_SE_TA_1 X X X X X

<62> C_SE_TB_1

<63> C_SE_TC_1

<64> C_BO_TA_1

ENHANCED TECHNOLOGY 29
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

TYPE CAUSE OF TRANSMISSION


IDENTIFICATION

PERIODIC, CYCLIC

BACKGROUND SCAN

SPONTANEOUS

INITIALIZED

REQUEST OR REQUESTED

ACTIVATION

ACTIVATION CONFIRMATION

DEACTIVATION

DEACTIVATION CONFIRMATION

ACTIVATION TERMINATION

RETURN INFO CAUSED BY REMOTE CMD

RETURN INFO CAUSED BY LOCAL CMD

FILE TRANSFER

INTERROGATED BY GROUP <NUMBER>

REQUEST BY GROUP <N> COUNTER REQ

UNKNOWN TYPE IDENTIFICATION

UNKNOWN CAUSE OF TRANSMISSION

UNKNOWN COMMON ADDRESS OF ADSU

UNKNOWN INFORMATION OBJECT ADDR


20 37
NO. MNEMONIC 1 2 3 4 5 6 7 8 9 10 11 12 13 to to 44 45 46 47
36 41

<70> M_EI_NA_1* X

<100> C_IC_NA_1 X X X X X

<101> C_CI_NA_1 X X X

<102> C_RD_NA_1 X

<103> C_CS_NA_1 X X X

<104> C_TS_NA_1

<105> C_RP_NA_1 X X

<106> C_CD_NA_1

<107> C_TS_TA_1 X X

<110> P_ME_NA_1 X X X

<111> P_ME_NB_1

<112> P_ME_NC_1

<113> P_AC_NA_1

<120> F_FR_NA_1

<121> F_SR_NA_1

<122> F_SC_NA_1

<123> F_LS_NA_1

<124> F_AF_NA_1

<125> F_SG_NA_1

<126> F_DR_TA_1*

- Blank or X only
*. NOTE ) 1. The above item marked with * are supported from Ver. 2.05 of CPU firmware.
2. The above item marked with * are supported from Ver. 2.10 of CPU firmware.

30 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

(6) BASIC APPLICATION


FUNCTIONS Station Initialization:
▣ Remote initialization

Cyclic Data Transmission:


▣ Cyclic data transmission

Read Procedure:
▣ Read procedure

Spontaneous Transmission:
▣ Spontaneous transmission

Double transmission of information objects with cause of transmission


spontaneous:
The following type identifications may be transmitted in succession caused by a single status change of

an information object. The particular information object addresses for which double transmission is
enabled are defined in a project-specific list.

□ Single point information: M_SP_NA_1, M_SP_TA_1, M_SP_TB_1, and M_PS_NA_1

□ Double point information: M_DP_NA_1, M_DP_TA_1, and M_DP_TB_1

□ Step position information: M_ST_NA_1, M_ST_TA_1, and M_ST_TB_1

□ Bitstring of 32 bits: M_BO_NA_1, M_BO_TA_1, and M_BO_TB_1 (if defined for a specific project)

□ Measured value, normalized value: M_ME_NA_1, M_ME_TA_1, M_ME_ND_1, and M_ME_TD_1

□ Measured value, scaled value: M_ME_NB_1, M_ME_TB_1, and M_ME_TE_1

□ Measured value, short floating point number: M_ME_NC_1, M_ME_TC_1, and M_ME_TF_1

Station interrogation:
▣ Global

▣ Group 1 ▣ Group 5 ▣ Group 9 ▣ Group 13

▣ Group 2 ▣ Group 6 ▣ Group 10 ▣ Group 14

▣ Group 3 ▣ Group 7 ▣ Group 11 ▣ Group 15

▣ Group 4 ▣ Group 8 ▣ Group 12 ▣ Group 16

ENHANCED TECHNOLOGY 31
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

Clock synchronization:
▣ Clock synchronization (optional)

Command transmission:
▣ Direct command transmission

▣ Direct set point command transmission

▣ Select and execute command

▣ Select and execute set point command

□ C_SE ACTTERM used

□ No additional definition

▣ Short pulse duration (duration determined by a system parameter in the outstation)

▣ Long pulse duration (duration determined by a system parameter in the outstation)

□ Persistent output
▣ Supervision of maximum delay in command direction of commands and set point commands

Maximum allowable delay of commands and set point commands: 10 s

Transmission of integrated totals:


▣ Mode A: Local freeze with spontaneous transmission

▣ Mode B: Local freeze with counter interrogation

▣ Mode C: Freeze and transmit by counter-interrogation commands

▣ Mode D: Freeze by counter-interrogation command, frozen values reported simultaneously

▣ Counter read

▣ Counter freeze without reset

▣ Counter freeze with reset

▣ Counter reset

▣ General request counter

▣ Request counter group 1

▣ Request counter group 2

▣ Request counter group 3

▣ Request counter group 4

Parameter loading:
▣ Threshold value

□ Smoothing factor

▣ Low limit for transmission of measured values

▣ High limit for transmission of measured values

32 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

Parameter activation:
□ Activation/deactivation of persistent cyclic or periodic transmission of the addressed object

Test procedure:
□ Test procedure

File transfer:
File transfer in monitor direction:

□ Transparent file

□ Transmission of disturbance data of protection equipment

□ Transmission of sequences of events

□ Transmission of sequences of recorded analog values

File transfer in control direction:

□ Transparent file

Background scan:
□ Background scan

Acquisition of transmission delay:


■ Acquisition of transmission delay

Definition of time outs:

PARAMETER DEFAULT REMARKS SELECTED

VALUE VALUE

t0 30 s Timeout of connection establishment 120 s

t1 15 s Timeout of send or test APDUs 15 s

t2 10 s Timeout for acknowledgements in case of no data messages t2 < t1 10 s

t3 20 s Timeout for sending test frames in case of a long idle state 20 s

Maximum range of values for all time outs: 1 to 255 s, accuracy 1 s

ENHANCED TECHNOLOGY 33
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

Maximum number of outstanding I-format APDUs k and latest acknowledge


APDUs (w):

PARAMETER DEFAULT REMARKS SELECTED

VALUE VALUE

Maximum difference receive sequence number to send state


k 12 APDUs 12 APDUs
variable

w 8 APDUs Latest acknowledge after receiving w I-format APDUs 8 APDUs

Maximum range of values k: 1 to 32767 (215 – 1) APDUs, accuracy 1 APDU

Maximum range of values w: 1 to 32767 APDUs, accuracy 1 APDU


Recommendation: w should not exceed two-thirds of k.

Port number:

PARAMETER VALUE REMARKS

Port number 2404 In all cases

RFC 2200 suite:


RFC 2200 is an official Internet Standard which describes the state of standardization of protocols used in

the Internet as determined by the Internet Architecture Board (IAB). It offers a broad spectrum of actual

standards used in the Internet. The suitable selection of documents from RFC 2200 defined in this
standard for given projects has to be chosen by the user of this standard.

▣ Ethernet 802.3

□ Serial X.21 interface

□ Other selection(s) from RFC 2200 (list below if selected)

34 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

E. IEC 60870-5-101/104 Point Table


1. IEC 60870-5-101/104 Point Table for Default User Map

Table E-1. IEC60870-5-101/104 INDEX – Single-point information(1/6)


S: Spontaneous , G: General Group, C: Cyclic
Point
IOA Description Group Status Base
Property
No*
S G C No. 0 1
1000 CLOSE STATUS ۷ ۷ - 1 - CLOSE 63

1001 OPEN STATUS ۷ ۷ - 1 - OPEN 64

1002 TROUBLE STATUS ۷ ۷ - 1 OK TROUBLE 65

1003 MECHENISM LOCK ۷ ۷ - 1 FREE LOCK 67

1004 GAS ALARM ۷ ۷ - 1 OK ALARM 70

1005 PANEL SLEEP MODE ۷ ۷ - 2 DEASSERT ASSERT 0

1006 SECTIONALIZER MODE ۷ ۷ - 2 DEASSERT ASSERT 3

1007 DOOR OPEN ۷ ۷ - 2 CLOSE OPEN 71

1008 AC POWER FAIL ۷ ۷ - 2 DEASSERT ASSERT 74

1009 CHARGER VOLTAGE BAD ۷ ۷ - 2 DEASSERT ASSERT 75

1010 BATTERY VOLTAGE BAD ۷ ۷ - 2 DEASSERT ASSERT 76

1011 POWER DOWN ۷ ۷ - 2 DEASSERT ASSERT 77

1012 BATTERY NO EXIST ۷ ۷ - 2 DEASSERT ASSERT 78

1013 PROTECTION ENABLED ۷ ۷ - 2 DISABLE ENABLE 88

1014 GROUND PROTECTION ENABLED ۷ ۷ - 2 DISABLE ENABLE 90

1015 SEF PROTECTION ENABLED ۷ ۷ - 2 DISABLE ENABLE 92

1016 RECLOSE ENABLED ۷ ۷ - 2 DISABLE ENABLE 94

1017 CONTROL LOCK ۷ ۷ - 2 UNLOCK LOCK 96

1018 REMOTE ENABLED ۷ ۷ - 2 DISABLE ENABLE 98

1019 LOOP CONTROL ENABLED ۷ ۷ - 2 DISABLE ENABLE 100

1020 LOOP CONTROL AUTO RESTORE ENABLED ۷ ۷ - 2 DISABLE ENABLE 102

1021 HOT-LINE TAG ENABLED ۷ ۷ - 2 DISABLE ENABLE 104

1022 AUX1 ENABLED ۷ ۷ - 2 DISABLE ENABLE 106

1023 AUX2 ENABLED ۷ ۷ - 2 DISABLE ENABLE 108

1024 SCADA INPUT PORT-1 ۷ ۷ - 3 DEASSERT ASSERT 124

1025 SCADA INPUT PORT-2 ۷ ۷ - 3 DEASSERT ASSERT 125

1026 SCADA INPUT PORT-3 ۷ ۷ - 3 DEASSERT ASSERT 126

1027 SCADA INPUT PORT-4 ۷ ۷ - 3 DEASSERT ASSERT 127

1028 SCADA INPUT PORT-5 ۷ ۷ - 3 DEASSERT ASSERT 128

ENHANCED TECHNOLOGY 35
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

Table E-1. IEC60870-5-101/104 INDEX - Single-point information (2/6)


S: Spontaneous , G: General Group, C: Cyclic
Point
IOA Description Group Status Base
Property
No*
S G C No. 0 1
1029 SCADA INPUT PORT-6 ۷ ۷ - 3 DEASSERT ASSERT 129

1030 SCADA INPUT PORT-7 ۷ ۷ - 3 DEASSERT ASSERT 130

1031 SCADA INPUT PORT-8 ۷ ۷ - 3 DEASSERT ASSERT 131

1032 SCADA INPUT PORT-9 ۷ ۷ - 3 DEASSERT ASSERT 132

1033 SCADA INPUT PORT-10 ۷ ۷ - 3 DEASSERT ASSERT 133

1034 SCADA INPUT PORT-11 ۷ ۷ - 3 DEASSERT ASSERT 134

1035 SCADA INPUT PORT-12 ۷ ۷ - 3 DEASSERT ASSERT 135

1036 SCADA OUTPUT PORT-1 ۷ ۷ - 3 DEASSERT ASSERT 144

1037 SCADA OUTPUT PORT-2 ۷ ۷ - 3 DEASSERT ASSERT 145

1038 SCADA OUTPUT PORT-3 ۷ ۷ - 3 DEASSERT ASSERT 146

1039 SCADA OUTPUT PORT-4 ۷ ۷ - 3 DEASSERT ASSERT 147

1040 SCADA OUTPUT PORT-5 ۷ ۷ - 3 DEASSERT ASSERT 148

1041 SCADA OUTPUT PORT-6 ۷ ۷ - 3 DEASSERT ASSERT 149

1042 SCADA OUTPUT PORT-7 ۷ ۷ - 3 DEASSERT ASSERT 150

1043 SCADA OUTPUT PORT-8 ۷ ۷ - 3 DEASSERT ASSERT 151

1044 USER LOGIC BIT-01 ۷ ۷ - 4 DEASSERT ASSERT 19

1045 USER LOGIC BIT-02 ۷ ۷ - 4 DEASSERT ASSERT 20

1046 USER LOGIC BIT-03 ۷ ۷ - 4 DEASSERT ASSERT 21

1047 USER LOGIC BIT-04 ۷ ۷ - 4 DEASSERT ASSERT 22

1048 USER LOGIC BIT-05 ۷ ۷ - 4 DEASSERT ASSERT 23

1049 USER LOGIC BIT-06 ۷ ۷ - 4 DEASSERT ASSERT 24

1050 USER LOGIC BIT-07 ۷ ۷ - 4 DEASSERT ASSERT 25

1051 USER LOGIC BIT-08 ۷ ۷ - 4 DEASSERT ASSERT 26

1052 USER LOGIC BIT-09 ۷ ۷ - 4 DEASSERT ASSERT 27

1053 USER LOGIC BIT-10 ۷ ۷ - 4 DEASSERT ASSERT 28

1054 USER LOGIC BIT-11 ۷ ۷ - 4 DEASSERT ASSERT 29

1055 USER LOGIC BIT-12 ۷ ۷ - 4 DEASSERT ASSERT 30

1056 USER LOGIC BIT-13 ۷ ۷ - 4 DEASSERT ASSERT 31

1057 USER LOGIC BIT-14 ۷ ۷ - 4 DEASSERT ASSERT 32

1058 USER LOGIC BIT-15 ۷ ۷ - 4 DEASSERT ASSERT 33

1059 USER LOGIC BIT-16 ۷ ۷ - 4 DEASSERT ASSERT 34

1060 LIVE LINE TIMEOUT : SOURCE VOLTAGE ۷ ۷ - 5 DEASSERT ASSERT 239

36 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

Table E-1. IEC60870-5-101/104 INDEX - Single-point information (3/6)


S: Spontaneous , G: General Group, C: Cyclic
Point
IOA Description Group Status Base
Property
No*
S G C No. 0 1
1061 LIVE LINE TIMEOUT : LOAD VOLTAGE ۷ ۷ - 5 DEASSERT ASSERT 241

1062 OPEN PHASE - A ۷ ۷ - 5 DEASSERT ASSERT 280

1063 OPEN PHASE - B ۷ ۷ - 5 DEASSERT ASSERT 281

1064 OPEN PHASE - C ۷ ۷ - 5 DEASSERT ASSERT 282

1065 OPEN PHASE - R ۷ ۷ - 5 DEASSERT ASSERT 283

1066 OPEN PHASE - S ۷ ۷ - 5 DEASSERT ASSERT 284

1067 OPEN PHASE - T ۷ ۷ - 5 DEASSERT ASSERT 285

1068 PHASE DIFFERENCE TIMEOUT - A ۷ ۷ - 5 DEASSERT ASSERT 286

1069 PHASE DIFFERENCE TIMEOUT - B ۷ ۷ - 5 DEASSERT ASSERT 287

1070 PHASE DIFFERENCE TIMEOUT - C ۷ ۷ - 5 DEASSERT ASSERT 288

1071 SETTING GROUP1 ACTIVE ۷ ۷ - 6 DEASSERT ASSERT 82

1072 SETTING GROUP2 ACTIVE ۷ ۷ - 6 DEASSERT ASSERT 83

1073 SETTING GROUP3 ACTIVE ۷ ۷ - 6 DEASSERT ASSERT 84

1074 SETTING GROUP4 ACTIVE ۷ ۷ - 6 DEASSERT ASSERT 85

1075 SETTING GROUP5 ACTIVE ۷ ۷ - 6 DEASSERT ASSERT 86

1076 SETTING GROUP6 ACTIVE ۷ ۷ - 6 DEASSERT ASSERT 87

1077 Gas Low Lock ۷ ۷ - 6 DEASSERT ASSERT 111

1078 LOAD CURRENT ALARM - A ۷ ۷ - 6 DEASSERT ASSERT 218

1079 LOAD CURRENT ALARM - B ۷ ۷ - 6 DEASSERT ASSERT 219

1080 LOAD CURRENT ALARM - C ۷ ۷ - 6 DEASSERT ASSERT 220

1081 79 RESET ۷ ۷ - 6 DEASSERT ASSERT 229

1082 79 CYCLE ۷ ۷ - 6 DEASSERT ASSERT 230

1083 79 LOCKOUT ۷ ۷ - 6 DEASSERT ASSERT 231

1084 RECLOSE SEQUENCE 0 ۷ ۷ - 6 DEASSERT ASSERT 232

1085 RECLOSE SEQUENCE 1 ۷ ۷ - 6 DEASSERT ASSERT 233

1086 RECLOSE SEQUENCE 2 ۷ ۷ - 6 DEASSERT ASSERT 234

1087 RECLOSE SEQUENCE 3 ۷ ۷ - 6 DEASSERT ASSERT 235

1088 RECLOSE SEQUENCE 4 ۷ ۷ - 6 DEASSERT ASSERT 236

1089 FAULT TIMEOUT - A ۷ ۷ - 6 DEASSERT ASSERT 250

1090 FAULT TIMEOUT - B ۷ ۷ - 6 DEASSERT ASSERT 251

1091 FAULT TIMEOUT - C ۷ ۷ - 6 DEASSERT ASSERT 252

1092 FAULT TIMEOUT - GROUND ۷ ۷ - 6 DEASSERT ASSERT 253

ENHANCED TECHNOLOGY 37
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

Table E-1. IEC60870-5-101/104 INDEX - Single-point information (4/6)


S: Spontaneous , G: General Group, C: Cyclic
Point
IOA Description Group Status Base
Property
No*
S G C No. 0 1
1093 FAULT TIMEOUT - S.E.F ۷ ۷ - 6 DEASSERT ASSERT 255

1094 FAULT TIMEOUT - NEG SEQ ۷ ۷ - 6 DEASSERT ASSERT 256

PHASE INSTANTANEOUS OVERCURRENT


1095 ۷ ۷ - 6 DEASSERT ASSERT 260
(50P) TIMEOUT

GROUND INSTANTANEOUS OVERCURRENT


1096 ۷ ۷ - 6 DEASSERT ASSERT 261
(50G) TIMEOUT

1097 SESITIVE EARTH FAULT (50SG) TIMEOUT ۷ ۷ - 6 DEASSERT ASSERT 263

NEG SEQ INSTANTANEOUS OVERCURRENT


1098 ۷ ۷ - 6 DEASSERT ASSERT 264
(50Q) TIMEOUT

1099 PHASE TIME OVERCURRENT (51P) TIMEOUT ۷ ۷ - 6 DEASSERT ASSERT 265

GROUND TIME OVERCURRENT (51G)


1100 ۷ ۷ - 6 DEASSERT ASSERT 266
TIMEOUT

NEG SEQ TIME OVERCURRENT (51Q)


1101 ۷ ۷ - 6 DEASSERT ASSERT 269
TIMEOUT

1102 UNDER VOLTAGE (27) TIMEOUT ۷ ۷ - 6 DEASSERT ASSERT 270

1103 OVER VOLTAGE (59) TIMEOUT ۷ ۷ - 6 DEASSERT ASSERT 271

1104 GROUND OVER VOLTAGE (64G) TIMEOUT ۷ ۷ - 6 DEASSERT ASSERT 272

1105 UNDER FREQUENCY (81U) TIMEOUT ۷ ۷ - 6 DEASSERT ASSERT 274

1106 OVER FREQUENCY (81O) TIMEOUT ۷ ۷ - 6 DEASSERT ASSERT 275

1107 DEMAND (49D) TIMEOUT ۷ ۷ - 6 DEASSERT ASSERT 276

1108 DIRECTION POWER (32P) TIMEOUT ۷ ۷ - 6 DEASSERT ASSERT 277

1109 FORWARD POWER (32FP) TIMEOUT ۷ ۷ - 6 DEASSERT ASSERT 278

ACTIVATE INRUSH RESTRAINT FOR PHASE


1110 ۷ ۷ - 6 DEASSERT ASSERT 299
TIME OVERCURRENT

ACTIVATE INRUSH RESTRAINT FOR GROUND


1111 ۷ ۷ - 6 DEASSERT ASSERT 300
TIME OVERCURRENT

ACTIVATE INRUSH RESTRAINT FOR S.E.F


1112 ۷ ۷ - 6 DEASSERT ASSERT 301
TIME OVERCURRENT

ACTIVATE INRUSH RESTRAINT FOR NEG SEQ


1113 ۷ ۷ - 6 DEASSERT ASSERT 302
TIME OVERCURRENT

1114 PHASE TIME OVERCURRENT (51P) ALARM ۷ ۷ - 7 DEASSERT ASSERT 366

1115 GROUND TIME OVERCURRENT (51G) ALARM ۷ ۷ - 7 DEASSERT ASSERT 367

38 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

Table E-1. IEC60870-5-101/104 INDEX - Single-point information (5/6)


S: Spontaneous , G: General Group, C: Cyclic
Point
IOA Description Group Status Base
Property
No*
S G C No. 0 1
1116 NEG SEQ TIME OVERCURRENT (51Q) ALARM ۷ ۷ - 7 DEASSERT ASSERT 370

1117 UNDER VOLTAGE (27) ALARM ۷ ۷ - 7 DEASSERT ASSERT 371

1118 OVER VOLTAGE (59) ALARM ۷ ۷ - 7 DEASSERT ASSERT 372

1119 NEUTRAL OVER VOLTAGE (64N) ALARM ۷ ۷ - 7 DEASSERT ASSERT 373

1120 SAG TIMEOUT - A ۷ ۷ - 8 DEASSERT ASSERT 315

1121 SAG TIMEOUT - B ۷ ۷ - 8 DEASSERT ASSERT 316

1122 SAG TIMEOUT - C ۷ ۷ - 8 DEASSERT ASSERT 317

1123 SWELL TIMEOUT - A ۷ ۷ - 8 DEASSERT ASSERT 319

1124 SWELL TIMEOUT - B ۷ ۷ - 8 DEASSERT ASSERT 320

1125 SWELL TIMEOUT - C ۷ ۷ - 8 DEASSERT ASSERT 321

1126 INTERRUPTION TIMEOUT - A ۷ ۷ - 8 DEASSERT ASSERT 323

1127 INTERRUPTION TIMEOUT - B ۷ ۷ - 8 DEASSERT ASSERT 324

1128 INTERRUPTION TIMEOUT - C ۷ ۷ - 8 DEASSERT ASSERT 325

1129 PQ OVER VOLT TIMEOUT - A ۷ ۷ - 8 DEASSERT ASSERT 309

1130 PQ OVER VOLT TIMEOUT - B ۷ ۷ - 8 DEASSERT ASSERT 310

1131 PQ OVER VOLT TIMEOUT - C ۷ ۷ - 8 DEASSERT ASSERT 311

1132 PQ OVER VOLT TIMEOUT - R ۷ ۷ - 8 DEASSERT ASSERT 312

1133 PQ OVER VOLT TIMEOUT - S ۷ ۷ - 8 DEASSERT ASSERT 313

1134 PQ OVER VOLT TIMEOUT - T ۷ ۷ - 8 DEASSERT ASSERT 314

1135 PQ UNDER VOLT TIMEOUT - A ۷ ۷ - 8 DEASSERT ASSERT 303

1136 UNBALANCE TIMEOUT - SOURCE VOLTAGE ۷ ۷ - 8 DEASSERT ASSERT 327

1137 PQ UNDER VOLT TIMEOUT - B ۷ ۷ - 8 DEASSERT ASSERT 304

1138 UNBALANCE TIMEOUT - LOAD VOLTAGE ۷ ۷ - 8 DEASSERT ASSERT 328

1139 PQ UNDER VOLT TIMEOUT - C ۷ ۷ - 8 DEASSERT ASSERT 305

1140 UNBALANCE TIMEOUT - CURRENT ۷ ۷ - 8 DEASSERT ASSERT 329

1141 PQ UNDER VOLT TIMEOUT - R ۷ ۷ - 8 DEASSERT ASSERT 306

1142 PQ UNDER FREQUENCY TIMEOUT ۷ ۷ - 8 DEASSERT ASSERT 330

1143 PQ UNDER VOLT TIMEOUT - S ۷ ۷ - 8 DEASSERT ASSERT 307

1144 VOLTAGE THD TIMEOUT - A ۷ ۷ - 8 DEASSERT ASSERT 342

1145 PQ UNDER VOLT TIMEOUT - T ۷ ۷ - 8 DEASSERT ASSERT 308

1146 VOLTAGE THD TIMEOUT - B ۷ ۷ - 8 DEASSERT ASSERT 343

1147 VOLTAGE THD TIMEOUT - C ۷ ۷ - 8 DEASSERT ASSERT 344

ENHANCED TECHNOLOGY 39
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

Table E-1. IEC60870-5-101/104 INDEX - Single-point information (6/6)


S: Spontaneous , G: General Group, C: Cyclic
Point
IOA Description Group Status Base
Property
No*
S G C No. 0 1
1148 CURRENT THD TIMEOUT - A ۷ ۷ - 8 DEASSERT ASSERT 346

1149 CURRENT THD TIMEOUT - B ۷ ۷ - 8 DEASSERT ASSERT 347

1150 CURRENT THD TIMEOUT - C ۷ ۷ - 8 DEASSERT ASSERT 348

1151 DIAGNOSTIC ADC (A/D Converter) ۷ ۷ - 10 DEASSERT ASSERT 51

1152 DIAGNOSTIC OPERATION POWER ۷ ۷ - 10 DEASSERT ASSERT 52

1153 DIAGNOSTIC CLOSE COIL ۷ ۷ - 10 DEASSERT ASSERT 53

1154 DIAGNOSTIC TRIP COIL ۷ ۷ - 10 DEASSERT ASSERT 54

1155 DIAGNOSTIC IGBT ۷ ۷ - 10 DEASSERT ASSERT 55

1156 DIAGNOSTIC ALARM STATUS ۷ ۷ - 10 DEASSERT ASSERT 61

1157 DIAGNOSTIC ERROR STATUS ۷ ۷ - 10 DEASSERT ASSERT 62

NOTE
*. All Single Points can change assigned Point Property, Group Number and Object Address on ETIMS Interface Software.

Please refer to “ETIMS Interface Software User’s Manual” for more detail information.
*. By the use of the "Base Number" specified to each point above, the detailed description for the corresponding point

can be confirmed on "Table 1. BASE DATA POINTS - BINARY INPUT" of the "Recloser Control ETR300-R

and EVRC2A-NT Communication Protocol MAP Configuration User Manual".

40 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

Table E-2. IEC 60870-5-101/104 INDEX – Single Command


TR/CL Base
IOA Description Block Condition Remark
Field No*

21000 CB CLOSE/OPEN ON/OFF CTR Lock || Mec’ Lock || Synchro 0

21001 CB OPEN ON CTR Lock 1

21002 PROTECTION ENABLE/DISABLE ON/OFF CTR Lock 2

21003 PROTECTION DISABLE/NONE ON CTR Lock 3

21004 GROUND ENABLE/DISABLE ON/OFF CTR Lock 4

21005 GROUND DISABL ON CTR Lock 5

21006 S.E.F ENABLE/DISABLE ON/OFF CTR Lock 6

21007 S.E.F DISABLE ON CTR Lock 7

21008 RECLOSE ENABLE/DISABLE ON/OFF CTR Lock 8

21009 RECLOSE DISABLE ON CTR Lock 9

21010 CONTROL LOCK/UNLOCK ON/OFF CTR Lock 10

21011 CONTROL UNLOCK ON CTR Lock 11

21012 LOOP CONTROL ENABLE/DISABLE ON/OFF CTR Lock 12

21013 LOOP CONTROL DISABLE ON CTR Lock 13

LOOP CONTROL AUTO RESTORE


21014 ON/OFF CTR Lock 14
ENABLE/DISABLE
LOOP CONTROL AUTO RESTORE
21015 ON CTR Lock 15
DISABLE
21016 HOT LINE TAG ENABLE/DISABLE ON/OFF CTR Lock 16

21017 HOT LINE TAG DISABLE ON CTR Lock 17

NOTE
*. Block Condition Description
- CTR Lock(Control Lock) : CONTROL function is locked status in panel
- Mec’ Lock(Mechanism Lock) : Recloser(Tank) is locked status
- Seq’ Running : Currently Sequence is conducting(79 CYCLE).
- Synchro : Synchronism check element is detected.
- AC Fail : External AC Power is not supplied.
*. All “Single Command” points can change assigned Object Address and the value(ON/OFF) of single command can be

inverted on ETIMS Interface Software. Please refer to “ETIMS Interface Software User’s Manual” for more detail
information.

ENHANCED TECHNOLOGY 41
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

Table E-3. IEC60870-5-101/104 - Integrated Total


Base
IOA Description Point Property Remark
No*
3000 RESTART Static 16bit 0

3001 DIAGNOSIS Static 16bit 1

3002 OPERATION Static 16bit 130

3003 TRIP Static 16bit 131

NOTE
*. 16 bit rollover Counter.
*. All “Integrated Totals” Points can change assigned Point Property, Group Number and Object Address on ETIMS

Interface Software. Please refer to “ETIMS Interface Software User’s Manual” for more detail information.

42 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

Table E-4. IEC60870-5-101/104 – Normalized Measurands (1/2)


S: Spontaneous , G: General Group, C: Cyclic
Base
IOA Description Point Property Group
Notes No*
S G C No.
2000 CURRENT A (RMS) ۷ ۷ 16 1A/1Count 153

2001 CURRENT B (RMS) ۷ ۷ 16 1A/1Count 154

2002 CURRENT C (RMS) ۷ ۷ 16 1A/1Count 155

2003 CURRENT G (RMS) ۷ ۷ 16 1A/1Count 156

2004 CURRENT N (RMS) ۷ ۷ 16 1A/1Count 157

2005 CURRENT SEF (RMS) ۷ ۷ 16 1A/1Count 158

2006 POSITIVE CURRENT(I1) ۷ ۷ 16 1A/1Count 165

2007 NEGATIVE CURRENT(I2) ۷ ۷ 16 1A/1Count 166

2008 ZERO SEQ. CURRENT(I0) ۷ ۷ 16 1A/1Count 167

2009 VOLTAGE A (RMS) (SOURCE) ۷ ۷ 16 1V/1Count 187

2010 VOLTAGE B (RMS) (SOURCE) ۷ ۷ 16 1V/1Count 188

2011 VOLTAGE C (RMS) (SOURCE) ۷ ۷ 16 1V/1Count 189

2012 LINE-LINE VOLTAGE AB (RMS) ۷ ۷ 16 1V/1Count 195

2013 LINE-LINE VOLTAGE BC (RMS) ۷ ۷ 16 1V/1Count 196

2014 LINE-LINE VOLTAGE CA (RMS) ۷ ۷ 16 1V/1Count 197

2015 POSITIVE VOLTAGE V1 (SOURCE) ۷ ۷ 16 1V/1Count 201

2016 NEGATIVE VOLTAGE V2 (SOURCE) ۷ ۷ 16 1V/1Count 202

2017 ZERO SEQ. VOLTAGE V0 (SOURCE) ۷ ۷ 16 1V/1Count 203

2018 ACTIVE POWER A ۷ ۷ 16 1KW/1Count 233

2019 ACTIVE POWER B ۷ ۷ 16 1KW/1Count 234

2020 ACTIVE POWER C ۷ ۷ 16 1KW/1Count 235

2021 ACTIVE POWER (3Φ) ۷ ۷ 16 1KW/1Count 236

2022 REACTIVE POWER (3Φ) ۷ ۷ 16 1KVar/1Count 240

2023 APPARENT POWER (3Φ) ۷ ۷ 16 1KVA/1Count 244

2024 POSITIVE REAL POWER (3Φ) ۷ ۷ 16 1KW/1Count 252

2025 NEGATIVE REAL POWER (3Φ) ۷ ۷ 16 1KW/1Count 256

2026 POWER FACTOR A ۷ ۷ 16 1%/1Count 245

2027 POWER FACTOR B ۷ ۷ 16 1%/1Count 246

2028 POWER FACTOR C ۷ ۷ 16 1%/1Count 247

2029 POWER FACTOR (3Φ) ۷ ۷ 16 1%/1Count 248

2030 CHANNEL1 FREQUENCY ۷ ۷ 16 1Hz/1Count 19

ENHANCED TECHNOLOGY 43
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr

Table E-4. IEC60870-5-101/104 – Normalized Measurands (2/2)


NOTE
Object Address Point of Normalized Measurands has three Parameter normalized Value(Threshold, Low Limit, High

Limit) and these are dedicated for Group 14 in General Interrogation.

Following tables shows IOA, Value, Flags( Threshold, Low Limit, High Limit) at address 2002.

Address IOA Value Flags

10008 50 0х01(Threshold)

2000 10010 -32000 0х03(Low Limit)

10011 32000 0х04(High Limit)

*. All “Normalized Measurands” Points can change assigned Point Property, Group Number and Object Address on
ETIMS Interface Software. Please refer to “ETIMS Interface Software User’s Manual” for more detail information.
*. By the use of the "Base Map Number" specified to each point above, the detailed description for the corresponding

point can be confirmed on "Table 4. BASE DATA POINTS - ANALOG INPUT" of the " Recloser Control ETR300-

R Communication Protocol MAP Configuration User Manual".

44 ENHANCED TECHNOLOGY