the applicable model (or other identification) number, parts number and other
information for the specific equipment purchased shall be clearly identified.
C. SUBMERSIBLE PUMP
Vertical Submersible pumps are required to pump open well water to sump and are
required to operate properly and reliably for long duration continuously.
The motor shall be designed for maximum pump output, low noise level. The pump shall
be suitable for vertical installation.
The Submersible pumping units shall be self contained, integral pump / motor units
designed to operate at continuous full load in partially or completely submerged
condition without the need of any external cooling devices like water jackets.
The pumps along with their auxiliary equipment shall be suitable for the required duty
conditions and shall be designed and constructed for continuous duty at full load.
Pumps shall be suitable for a capacity range of 25% to 125% of duty point capacity.
Capacity - vs. - discharge pressure curve for each pump shall preferably be
continuously drooping from the shut-off point to the rated operation point and be
suitable for parallel operation. The pumps shall be designed to avoid cavitations at any
of the operating points.
The required duty range for a pump shall be on stable portion of its head-capacity curve
close to the best efficiency point. The head developed at the best efficiency point
shall be close to the required differential pressure so that throttling is not required
at pump discharge.
The equipment and auxiliaries shall be designed for quick and economical maintenance.
The rotating elements of the pumps shall be checked for critical speed in bending as well
as torsion. The critical speeds shall be at least 30% away from the normal speed for units
with flexible shafts and at least 20% away from the maximum operating speed in case of
stiff shafts.
All passages inside the pump casing and impellers, which may be inaccessible to
machining, shall be ground to a smooth finish as far as practicable.
The direction of rotation shall be clearly marked either by incorporating it on the casing
or by separate metal plate arrow securely fitted to the casing.
14
Table 4: Material of Construction of Submersible Pumps
Item Material
Impeller CrNi steel
Casing CrNiMo steel
Casing wear ring Acrylnitrill – Butadiene – Rubber
Shaft CrNi steel
CrNi steel
Impeller wear ring
Suction strainer CrNiMo steel
End piece CrNiMo steel
A stainless steel name plate shall be furnished and securely attached by stainless steel
pins at an easily accessible point on the pump. The plate shall be stamped with the
following minimum information:-
2. Duty Continuous
3. Name plate – Power Operating ambient temperature of 50degC
rating is to be given at
4. Degree of protection IP 68
5. Rated voltage 415V
Rated voltage variation + 10%
- Dry type suction air filter cum silencer with filtering element of fibre glass felt
sandwiched between wire mesh with supporting arrangement and fixing bolts, nuts,
etc. The suction filter design will be such that it will draw air from minimum 4 sides.
- Belt guard with fixing arrangement.
- Intercooler and after cooler of shell and tube type in horizontal configuration provided
with moisture separator and trap station.
- Rotary gear oil pump with oil filter/strainer, oil level indicator and oil piping, pipe
coupling/unions and oil cooler.
- Teflon rings for piston and teflon gland packing.
- Foundation bolts & washers for the compressor
- Non return valve and isolating valve at the discharge side of the compressor.
- Compressor motor should have minimum 10% margin above maximum power
requirement of the compressor.
- Companion flanges, reducers. tee, bends, nuts, bolts and gaskets for all types of
flanged connections in pipes, valves and equipment.
- Pressure gauge at the outlet of compressed air discharge pipe line.
- Interconnecting pipe work between compressor & air receiver.
Recommended tests on Air Compressors are listed hereunder. Compressors may be tested using a
suitable shop motor.
a) Volumetric and overall efficiency (type test)
b) Capacity (Routine test)
c) Specific power consumption from no load to full load (Routine test)
d) Speed (Routine Test)
16
e) Testing of unloaded (Routine test)
f) Safety valve test (Routine test)
1) All the pipes and fittings including valves required for compressed air units & air
receiver unit up to surge tank shall be provided by the Tenderer.
2) The pipe work shall be completed with necessary fittings, valves, strainers,
supports, clamps, etc. whichever is necessary and shall form part of the contract.
3) The values of velocity used in pipe sizing shall conform to 8-10m/s as per normal
design practice.
4) Interconnecting pipe & pipe fittings work between compressor & air receiver.
MATERIAL SPECIFICATIONS
Unless otherwise indicated in the data sheet/drawing, the following materials shall be
used:
h) Electrodes
INTERNAL FITTINGS
a) Internal baffles, tray support beams or other internals spanning a chord or diameter of the
vessel shall be provided with a means for allowing for differential expansions between
the part and the vessel shell.
b) Internal non-pressure piping for carbon steel vessels shall be fabricated either from
seamless or ERW pipes.
18