Professional Documents
Culture Documents
Procedure Overview
In this procedure, you will set up and operate a basic closed loop control
system to control the level of a liquid in a process tank. You will first configure
the controller then operate the closed loop system.
1. Perform a lockout/tagout.
2. Perform the following substeps to set up the T5552, as shown in figure 5-1.
NOTE
The appearance of the electrical outlet will differ based on the electrical
power supplied at your location.
FT2
FLOWPVALVE
ALM2 MIN
0
SET
DI 1234
PV LT1 LT2
OUT 1234
-sp 0.0
OUTPUT RELAY 1
CURRENT INPUT
SP NO COM NC
mA
ENTER
CR2
4-20mA
DISCRETE 9 10 11 12 13 14 15 16
DI1
AUX. POWER
ALARM
AL1 CR3
DISCRETE
DC POWER SUPPLY PLC ANALOG I/O
DI2 4-20mA
24 VDC 24 VDC 24VDC 24VDC 24VDC
AL2 OPEN COLLECTOR
SOLENOID VALVES
1 2 3 4 5 6 7 8
SV1 SV2 SV3
GND
9 10 11 12 13 14 15 16
HV 100D
HV 100A
(HV2) AIR SUPPLY
CONNECTION
MANUAL DRAIN
VALVES
(HV 300 (HV3) &
HV 100C (HV4))
CLOSED
PRESSURE
REGULATOR
HAND VALVES SET TO 20 PSI
HV 100B
OPEN (HV1) MANUAL FLOW
CONTROL VALVE
(FV 100 (HFV))
OPEN
D. Close (fully clockwise) the two process tank manual drain valves, HV 300
(HV3) and HV 100C (HV4).
E. Open (fully counterclockwise) the manual flow control valve, FV 100
(HFV).
F. Open (fully counterclockwise) the flow control hand valves, HV 100B
(HV1) and HV 100A (HV2).
G. Open (fully counterclockwise) the flow control hand valve HV 100D.
H. Connect the circuit shown in figure 5-2.
This circuit allows you to operate a closed loop level control system.
0
DI 1234 LEVEL SENSORS
PV LT1 LT2
OUT 1234
-sp 0.0 SP
Setup Run
Hold
AI1 AO1
CR2
DISCRETE
DI1 ALARM
AL1 CR3
DC POWER SUPPLY
DI2
24VDC 24VDC 24VDC
AL2
SOLENOID VALVES
SV1 SV2 SV3
GND
Figure 5-3 shows the wiring diagram for the level control circuit.
DC POWER
SUPPLY
CIRC. PUMP ANALOG OUTPUT
SS1 P1 CONNECTIONS
+ A01 FV1
- CONTROLLER I/P
OUTPUT CONVERTER
4-20mA
SS2 SV3 + +
24 + - -
VDC -
LT1
AI1
LEVEL
CONTROLLER INPUTS SENSOR
+
+ - +
-
-
Figure 5-3. Wiring Diagram for a Level Sensor Connected to a Honeywell Controller
IY PI PI PC
100 100D 100-C 100
FIT
100
T5552 P&ID
FCV
AIR
FE 100
100
LET LSH LSH
200-B 200-A 200-B
DUAL-COMPARTMENT
PROCESS TANK
OVERFLOW
PRESSURE
SENSOR
LET
S S 200-A
HV SV HV SV
300 100-B 100-C 100-C
FI
100
INTERFACE
TO
T5553,
T5554,
HV SV OR
100-A 100-A
T5555
HV
S 100D
PI FV PI
HV 100-A 100 100-B
400
WATER
PUMP
DRAIN
HV
100-B
RESERVOIR
TANK
S05-3
Figure 5-4 shows the P&ID for the T5552. The active components and
SKILL 5 CONFIGURE AND OPERATE A HONEYWELL UDC 3500 CONTROLLER BASED CLOSED LOOP LIQUID LEVEL SYSTEM
SKILL 5 CONFIGURE AND OPERATE A HONEYWELL UDC 3500 CONTROLLER BASED CLOSED LOOP LIQUID LEVEL SYSTEM
Q. Press the Func Loop 1/2 key until CONT ALG appears on the screen.
R. Use the up and down keys to set this parameter to PID A.
S. Press the Setup key repeatedly to scroll through the different selections
until CONTROL appears on the display.
T. Press the Func Loop 1/2 key until the indicated parameter is displayed,
and then use the up and down keys to set the parameter to the indi-
cated value.
PARAMETER SETTING
SP HiLIM 10.0
SP LoLIM 0.0
ACTION DIRECT
PBorGAIN GAIN
MINorRPM MIN
U. Press the Setup key repeatedly to scroll through the different selections
until TUNING appears on the display.
V. Press the Func Loop 1/2 key until the indicated parameter is displayed,
and then use the up and down keys to set the parameter to the indi-
cated value.
PARAMETER SETTING
GAIN 20.0
RATE MIN 0.0
RSET MIN 0.25
PV VALUE
ALM 1234 A
DI 1234
PV
OUT 1234
SP
SP VALUE
G. Use the Lower Display key to display the output (OUT) in the lower
display.
H. Determine if the controller is changing the output (OUT) to control the
valve as the PV approaches the SP.
Is the output changing? _______________________________ (Yes/No)
You should find that the controller is changing the output because it is in
automatic mode.
I. When the output (OUT) of the controller reaches 100%, observe the value
of the PV as indicated on the display of the controller.
Is the PV above or below the SP? __________________ (Above/Below)
You should find that the PV stabilizes above the SP. The controller may
not be programmed (tuned) to properly control the PV at the SP.
NOTE
This result depends on the settings in the controller. If the settings have
been changed from the default values, you may get a different result.