You are on page 1of 8

EGS300BS-6

Diesel Power 50Hz / 60Hz


Bonnet & Soundproof Type Generator Set

GENERATOR SET PERFORMANCE


50Hz at 0.8 Power Factor 60Hz at 0.8 Power Factor
PRIME STANDBY PRIME STANDBY
276kVA / 221kW 303kVA / 242kW 302kVA / 242kW 333kVA / 266kW

3-Phase Rated Voltage


380V, 400V and 415V 440V, 460V and 480V

GENERAL INFORMATION
Application
A factory designed generator set equipped with a standard AC/DC generator control panel. The
generator set is ready to be connected to your fuel and power line to start up once the installation
completed.

The MCCB box mounts at the end of alternator and the terminal box completed with a 3-phase and
neutral busbars ready for power cables connection.

Applicable Standard
Generator sets design, assembly and testing meet or exceed many international standards, such as
IEC 34-1, IEC 34-5, IEC 34-6, JEC 114, JEC 139 and JEC 146. The power rating is set in
accordance with ISO 8528, ISO 3046-1, DIN 6271 and BS 5514.

Structure Outline
The generator set has selected materials and equipment of high performance, which are durable
and anti-vibration. The assembly work meets the quality control system.

The concept of the design and manufacturing is for easy operation and maintenance, to be compact
and light weight too.

The single bearing alternator frame is coupled to the engine housing directly. With one end of the
rotor is supported by bearing and the other end of rotor shaft is connected to the engine flywheel
with a steel laminate plates.

All components and necessary equipment are mounted on the common skid base.

Rubber Isolator Mounting


The rubber isolators are mounted between engine, alternator and its common skid base.

Applicable Conditions Dimensions and Weight


Installation Place : Outdoor Overall Length : 4,400 mm
Ambient Temperature : 0°C ~ 40°C Overall Width : 1,400 mm
Ambient Humidity : Below 80% Overall Height : 2,100 mm (w/o silencer)
Altitude : Maximum 1,000 m Weight : Approx. 3,300kg

Painting Color Fuel Tank


Engine and Alternator : Yellow Skid Base Type : 500 liter
Generator Control Panel : Black and Yellow
Skid Base : Black
* Materials and specifications are subjected to change without prior notice.
SPEC: ES0300T3-6 REVISION: 0 DATE: 1 APR ‘04 PAGE: 1 / 8
EGS300BS-6
Diesel Power 50Hz / 60Hz
Bonnet & Soundproof Type Generator Set

TECHNICAL DATA
50Hz (1500RPM) 60Hz (1800RPM)
ENGINE Maker and Model KOMATSU SA6D125-1
BODY Rating Type Prime Standby Prime Standby
Engine Output (with Fan) HP 319 351 350 385
kWm 238 262 261 287
Aspiration Turbocharged and Aftercooled
Cylinder Arrangement 6 in-line
Type Water Cooled, 4 Cycles, Overhead Valve
Direct Injection Type
Bore x Stroke mm x mm 125 x 150
Piston Displacement Liter 11.04
Starting Method Electric Motor, 24V – 5.5kW x 1
Charging Alternator DC 24V – 35A (Brushless)
Turbocharger Schwitzer S3A Type
Cooling Fan and Diameter mm 6 Blades Pusher Type, 800
V – Belt and Pulley, Fan Drive Ratio 0.91
Oil Cooler Water Cooled, Multi-plate Type
Air Cleaner Dry Type, Cyclopac 2 Stage Paper Element
Water Separator Cartridge Type
Corrosion Resistor Cartridge, Spin On / Off Type
Stop Solenoid Energized to Run Mode
Flywheel Housing / Flywheel SAE #1 / SAE #14 (Metric Tread)
Flywheel Ring Gear Teeth 148
Battery (Lead Acid Type) DC 12V – 150Ah x 2 pc (INCOE or equivalent)
ENGINE Oil Pan (High / Low Level) Liter 26 / 22
LUBRICANT Oil Filter Liter 2.5
System Total Liter 30
Grade SAE #30, 10W, 10W-30 or 15W-40
API, Class CD, CE, CF
ENGINE Radiator and Ambient Temp. °C Corrugate Fin Type, 40
COOLANT Cooling System Forced Circulation by Centrifugal Water Pump
Engine Capacity Liter 20
Radiator Capacity Liter 41
Radiator Heat Rejection kcal/h 108,600 122,600 125,300 142,700
ENGINE Pressure Mean Effective (PME) kPa 1,725 1,897 1,577 1,734
DATA Mean Piston Speed m/s 7.5 9.0
Sound Level (Average at 1m)
Full Load dB(A) 97.5 98.8 97.5 98.8
Speed Regulation (Droop) % Mechanical Governor, within 5
Thermostat (Wax Type)
Water Coolant °C Cracking 82, Fully Open 95
Oil Cooler °C Cracking 85, Fully Open 100
Engine Shutdown Device
Coolant Temp (Sensor Type) °C 101 + 3% (VDO or equivalent)
Oil Pressure (Sensor Type) kPa 49 + 3% (0.5 + 3% bar) (VDO or equivalent)
FUEL and BSFC (at 100% Load) g/kWh 214 217
OIL Lubricating Oil (Nominal Value) Liter/h 0.12 0.13
CONSUMPTION Fuel Consumption (with Fan) Load 25% 50% 75% 100%
Prime Rating at 50Hz Liter/h 18.8 31.3 42.9 59.0
Prime Rating at 60Hz Liter/h 21 35 48 66

* Materials and specifications are subjected to change without prior notice.


SPEC: ES0300T3-6 REVISION: 0 DATE: 1 APR ‘04 PAGE: 2 / 8
EGS300BS-6
Diesel Power 50Hz / 60Hz
Bonnet & Soundproof Type Generator Set

TECHNICAL DATA
50Hz (1500RPM) 60Hz (1800RPM)
ALTERNATOR Type Self Excited, Brushless
Construction Single Bearing, Self Ventilation
Insulation Class H
Allowable Winding Temp Rise °C Max. 140
Allowable Bearing Temp Rise °C Max. 80
Winding, No of Pole 2/3 Pitch, 4 Poles
Number of Phase / Wire 3 – Phase / 4 – Wires
Drip Protection IP 22 Enclosed
Over Speed Capability rpm 2,250
Voltage Regulation
Steady State % < + 1.0
Auto Voltage Regulator (AVR) Solid State Type
Sustained Short Circuit Current % 300 (10sec)
Telephone Interference
Total Harmonic, TGH / THC % Deviation < 4
Wave Form, TIF, THF % < 50, < 2
3
AIR Combustion Air Flow m /min 15.8 17.0 20.3 21.7
3
VENTILATION Cooling Fan Air Flow m /min 318 318 360 360
3
Total m /min 334 335 380 402
3
EXHAUST Gas Flow (at Full Load) Nm /min 40 43 51 55
GAS Temperature (at T/C Outlet) °C 535 550 510 530
Allowable Back Pressure kPa 10 (1,020mmAq)
Bellow Size (Inner Diameter) mm 101.6
RECOMMEND Diesel Fuel (Grade) ASTM D975, 1-D or 2-D
Lubricating Oil (Grade) API, Class CD, CE, CF
Exhaust Gas Pipe
Engine to Silencer Inch 3
After Silencer to outside Inch 5
Opening Area for Fresh Air
2
Passed Air Ratio 100% m 1.59 1.81
2
Passed Air Ratio 50% m 3.18 3.62
Discharge Opening Area mxm 1.1 (V) x 1.2 (H) x 360 mm (above ground)
Pipe Size of Fuel Line
Supply (Minimum) Inch 3/4 (Branch), 1 (Main)
Return (Minimum) Inch 3/4 (Branch), 1 (Main)
GENERATOR Generator Control Module DSE 5220
CONTROL DC Measurements Engine Water Temperature, °C
PANEL Engine Oil Pressure, bar
Engine Speed, RPM
Battery Voltage, V
Hour Run, hrs
Fuel Level, % (Optional)
AC Measurements Gen Voltage (L1-N, L2-N, L3-N), V
Gen Voltage (L1-L2, L2-L3, L3-L1), V
Gen Current (L1, L2, L3), A
Gen Frequency, Hz
Gen Power Factor, Cos Φ
Gen Apparent Power, kVA
Gen Active Power, kW
Mains Voltage (L1-N, L2-N, L3-N), V
Mains Voltage (L1-L2, L2-L3, L3-L1), V
Mains Frequency, Hz

* Materials and specifications are subjected to change without prior notice.


SPEC: ES0300T3-6 REVISION: 0 DATE: 1 APR ‘04 PAGE: 3 / 8
EGS300BS-6
Diesel Power 50Hz / 60Hz
Bonnet & Soundproof Type Generator Set

TECHNICAL DATA

50Hz (1500RPM) 60Hz (1800RPM)


GENERATOR Safety Protections & Setting
CONTROL Low Oil Pressure bar < 0.5
PANEL High Water Temperature °C > 101
Under / Over Speed rpm + 15% of Rated Speed
Fail to Start s > 37 (failed to start up after 3 attempts)
Low / High Battery Volts V 22 / 30
Charge Failed V < 20
Under / Over Gen Volts V + 10% of Rated Voltage
Under / Over Gen Hz Hz + 15% of Rated Frequency
Over Current A > 100% of Prime Current (IDMTL)
Pushbuttons
Manual Stop / Reset To stop generator set while in Manual mode, or, to
reset and silent the buzzer when fault has been
removed.
Manual Mode To set the operation to Manual mode.
To test run the generator set while in Standby
Test Mode
position.
Auto Mode To set the operation to Automatic mode.
To start up the generator set while in Manual
Manual Start
mode.
Scroll To scroll through the display window.
Event Log To view the history or record of faults.
Exercise Scheduler This function can be used to provide a regular
generator set exercise feature on weekly basis.
Event Logging This captures the latest 15 shutdown events along
with date and time for reference.
Key Switch This key can be used to lock the operation of all
pushbuttons except Emergency Stop button so
that unauthorized personnel not able to make
adjustment.
Emergency Stop This button can be used to shutdown the
generator set operation immediately.
Buzzer Cancel This button can be used to cancel the audible
alarm.
Buzzer This is to provide audible alarm.
CANOPY Sound Level (Average at 1m)
SOUND Full Load dB(A) 85 + 2 85 + 2
LEVEL

SCOPE OF Consignment Parts


SUPPLY Oil Filter 1 pc 600-211-1231
Fuel Filter 1 pc 600-311-8293
Corrosion Resistor 1 pc 600-411-1151
Air Cleaner 1 pc 6125-81-7032
Tool Assembly 1 pc 6991-81-8902
Filter Wrench 1 pc 09019-08035
Battery Cables 1 set -----
Engine Parts Book 1 pc PEPB003200
Engine Operation Manual 1 pc SEAMG6000006
Alternator Maintenance Manual 1 pc -----
Generator Parts Book 1 pc EGSPB#1-0404
Generator Operation and 1 pc EGSOM#1-0404
Maintenance Manual

* Materials and specifications are subjected to change without prior notice.


SPEC: ES0300T3-6 REVISION: 0 DATE: 1 APR ‘04 PAGE: 4 / 8
EGS300BS-6
Diesel Power 50Hz / 60Hz
Bonnet & Soundproof Type Generator Set

GENERATOR CONTROL PANEL


EGS Generator Sets have a compact and intelligent generator control
module, which is one box type for easy operation and maintenance.

This control module minimizes the required control components and


wiring inside the panel. This will certainly simplify its maintenance.

The clear icon based language free can identify the engine status more
directly and to be easily recognized.

This panel provides indication of operational status and fault condition. It automatically shutting down the
generator set, indicating failures by means of a LCD display and providing audible alarm when fault occurred.

This panel equips with a built-in Automatic Mains Failure (AMF) function, which capable of monitoring the 3-
phase voltages and frequency of mains supply. It will automatically start the standby generator set when failure
happened.

SAFETY PROTECTIONS
HEAVY The engine cannot be started after 3 attempts.
ALARM Fail To Start The total time taken is 37 sec for the whole cranking process.
When this happened, the LCD will light up and the audible alarm will turn on.
(SHUTDOWN)
The engine oil pressure falls below the pre-set value, 0.5 bar.
Low Oil
When this happened, the LCD will light up, the audible alarm will turn on and the
Pressure engine will shutdown.
The engine water temperature exceeds the pre-set value, 101°C.
High Water
When this happened, the LCD will light up, the audible alarm will turn on and the
Temperature engine will shutdown.
The engine speed falls below / exceeds the pre-set value, 85% / 115% of rated
Under /Over
speed. When this happened, the LCD will light up, the audible alarm will turn on
Speed and the engine will shutdown.
Generator The generator voltage falls below / exceeds the pre-set value, 90% / 110% of rated
Low /High voltage. When this happened, the LCD will light up, the audible alarm will turn on
Voltage and the engine will shutdown.
Generator The generator frequency falls below / exceeds the pre-set value, 85% / 115% of
Low /High rated frequency. When this happened, the LCD will light up, the audible alarm will
Frequency turn on and the engine will shutdown.
Generator The loading current exceeds the pre-set value, 100% of prime current (IDMTL
Over Load curve). When this happened, the LCD will light up, the audible alarm will turn on
/Current and the engine will shutdown.
Emergency Once the pushbutton was pressed, the engine will stop immediately.
Stop
LIGHT When the LCD lit up, this indicates that the charging alternator is not working.
Charge Fail The audible alarm will turn on but no shutdown.
ALARM
(WARNING) When the LCD lit up, this indicates that the battery voltage falls below / exceeds
Battery Low
the pre-set value, 20V / 30V of battery voltage. The audible alarm will turn on but
/High Voltage no shutdown.
OPTIONAL Mains The mains voltage falls below / exceeds the pre-set value, 90% / 110% of mains
Low /High voltage. When this happened, the LCD will light up, the standby generator set will
Voltage automatically start up.
Mains The mains frequency falls below / exceeds the pre-set value, 85% / 115% of mains
Low /High frequency. When this happened, the LCD will light up, the standby generator set
Frequency will automatically start up.
Low Fuel When the LCD lit up, this indicates the diesel fuel level drops below the pre-set
Level value, 20%. The audible alarm will turn on but no shutdown.

* Materials and specifications are subjected to change without prior notice.


SPEC: ES0300T3-6 REVISION: 0 DATE: 1 APR ‘04 PAGE: 5 / 8
EGS300BS-6
Diesel Power 50Hz / 60Hz
Bonnet & Soundproof Type Generator Set

GENERATOR SET DRAWING

Unit: mm

LEFT SIDE VIEW

TOP VIEW

* Materials and specifications are subjected to change without prior notice.


SPEC: ES0300T3-6 REVISION: 0 DATE: 1 APR ‘04 PAGE: 6 / 8
EGS300BS-6
Diesel Power 50Hz / 60Hz
Bonnet & Soundproof Type Generator Set

GENERATOR SET DRAWING

Unit: mm

FRONT VIEW

REAR VIEW

* Materials and specifications are subjected to change without prior notice.


SPEC: ES0300T3-6 REVISION: 0 DATE: 1 APR ‘04 PAGE: 7 / 8
EGS300BS-6
Diesel Power 50Hz / 60Hz
Bonnet & Soundproof Type Generator Set

GENERATOR SET DRAWING

GENERATOR CONTROL PANEL

* Materials and specifications are subjected to change without prior notice.


SPEC: ES0300T3-6 REVISION: 0 DATE: 1 APR ‘04 PAGE: 8 / 8

You might also like