10
COOLING WATER TREATMENT
Cz water is circulated through equipment to absorb and carry away heat. ‘The three basic types
‘of cooling water systems are shown in Figure 10.1.
‘The open recirculating cooling water system is by far the most common and is the type used in
most gas processing plants to cool compressed gas and overhead streams from fractionating towers.
Closed recirculating systems usually involve much smaller volumes of water and are often used to
cool natural gas engine jackets and compressor cylinders.
Once-through cooling systems are seldom used because of the large volumes of water required
and potential pollution problems when the water is discharged back to the environment.
OPEN RECIRCULATING COOLING SYSTEMS
In open recirculating cooling systems, the cooling water is pumped through a heat exchanger
where the process stream is cooled and the water is heated. The warm water then passes to a cooling
tower or spray basin where it is cooled by contact with air before circulation back to the heat ex-
changer.
‘The water is cooled in the tower or spray pond by evaporation of a portion of the circulating
water, This evaporation loss results in an increase in the concentration of the dissolved solids in the
circulating water since the evaporated water contains no dissolved solids. The water lost by evapora-
tion must be replaced by makeup water.
Water is also lost by entrainment of droplets in the circulating air. This is called drift or windage
loss. These droplets of circulating water contain the same concentration of dissolved solids as the rest
of the circulating water. Therefore, their loss does not contribute to the concentration of dissolved
solids in the system as does evaporation loss. However, windage losses must also be replaced by
makeup water.
Water lost by inadvertent leakage must also be replaced.
Evaporation Losses
It requires approximately 1000 Btu's to evaporate one pound of water. This is equal to the
amount of heat required to raise the temperature of 100 pounds of water 10°F [5.5°C]. Therefore, for
CHAPTER 10 27COOLING WATER TREATMENT
OPEN RECIRCULATING
——Examples__ —Characteristics_ —Common Problems_
Diesel-Engine Jackets: Average Temperature Change - Corrosion
ile Radiators 10° to 15°F Fouling
Chilled-Water System Amount of Water Used -
Negligible:
ONCE-THROUGH
=
Characteristics _ Common Problems
‘Average Temperature Change - Corrosion
Sto 10°F Fouling
‘Amount of Water Used - Scale
Extremoly Large Microbiological
Figure 10.1 Cooling System Characteristics
APPLIED WATER TECHNOLOGYOPEN RECIRCULATING COOLING SYSTEMS
each drop of 10°F [5.5°C] through the tower, one pound of water will be lost by evaporation per 100
Pounds of water cooled. This is the equivalent of 1% of the water circulating. Therefore, the evapora-
tion rate can be calculated as follows:
Evaporation Rate(gpm) = Temperature Drop (°F) , Circulation Rate (gpm) (10.1)
10 100
Windage Loss
Windage loss for induced draft cooling towers may be estimated as from 0.10 to 0.20 percent of
water circulation. Reference to the cooling tower manufacturer's specification sheet will often estab-
lish this figure for the installation in question. Where 0.2 percent is guaranteed, use 0.15 percent, and
where 0.1 percent is guaranteed, use 0.07 percent.
‘A much wider variation (0.3 to 1.0 percent) in windage losses occurs in natural draft towers, and
‘most calculations can be based on total mechanical loss; i.e., blowdown plus windage. Windage loss in
spray pond systems is typically 1 to 5 percent of the circulation rate.
Blowdown
Blowdown is the continuous or intermittent removal of some of the circulating water.
Evaporation results in increased concentration of the dissolved solids in the circulating water.
The concentration is decreased by removing a portion of the circulating water and replacing it with
makeup water containing a lower concentration of dissolved solids. Thus, the circulating water is
diluted to control the buildup of dissolved solids in the circulating water.
Cycles Of Concentration
Cycles of concentration, or concentration ratio, is an expression of the degree to which the dis-
solved solids concentration in the original circulating water has been increased or concentrated by
evaporation losses. Since the water originally introduced into the circulating system was “makeup
water,” the degree of concentration, or cycles of concentration, can be expressed as follows:
pmchlorides in circulating water (10.2)
Gyeles
Hees =" ppmchloride in makeup water
The chloride ion is normally used because it is quite soluble and seldom lost from water by
precipitation,
Makeup Water
‘The amount of makeup water required is equal to the sum of all losses of water from the circulat-
ing system.
‘Makeup = Blowdown + Windage + Evaporation (10.3)
CHAPTER 10 299COOLING WATER TREATMENT
Material Balance Calculations
In previous sections we have defined evaporation and windage losses, blowdown, cycles of con-
centration, and makeup. It is now possible to derive an equation for the calculation of blowdown rate
‘by making a material balance based on chloride ion concentrations.
‘At equilibrium, the chlorides entering the system must equal the chlorides leaving the system.
Furthermore, the chloride concentration in the blowdown is the same as in the circulating water.
Consider the following four equations:
MX Cly =(B+W)xCly 10.4)
Cly =Clp (10.5)
M=B+W+E (10.6)
Clr
IE 10.7,
Cha 10.7)
= Circulation rate
Blowdown rate
Makeup rate
= Windage rate
Evaporation rate
Cycles of concentration
omékun
Substituting Equations 10.4 and 10.5 into Equation 10.3, we obtain:
(B+ WH E)X Cly =(B+ M)x Cly
Rearranging this expression into the form of Equation 10.6:
Cl _B+W+E
ory (10.8)
Equation 10.7 can be rearranged and solved for B to yield the following expression:
E-[wx(C-1)]
ea (10.9)
Example 10.1: Given:
Circulation Rate = 10.000 gpm
‘Water to tower 100°F
‘Water from tower = 80°F
Guaranteed maximum windage loss 0.2%
Chlorides in tower makeup = 100 ppm
Chlorides in circulating water = 500 ppm
300 APPLIED WATER TECHNOLOGYCOOLING WATER TREATMENT OBJECTIVES
Example 10.1 (Cont'd):
Determine:
Windage loss rate
Evaporation rate
Cycles of concentration
Blowdown rate
Total makeup rate
Solution:
1. W=0.0015x10000gpm = 1Sgpm
(Assumes that actual losses were only 75% of the guaranteed maximum.)
100-80, 10000
= —— =
10 * 100 = 08m
i E-lWxte-y _ 200-5 (5-1) «scm
M = B+W+E=35+15+200=250gpm
COOLING WATER TREATMENT OBJECTIVES
Cooling waters are treated to prevent four types of problems:
1. Scale formation on the heat transfer surfaces.
2. Corrosion of metal piping and heat exchangers by the cooling waters.
3. Fouling of the heat exchangers and the cooling tower.
4, Deterioration of wooden cooling towers.
Scale Prevention
Calcium Carbonate Scale
Calcium carbonate scale is extremely common in cooling waters, especially in the heat exchang-
‘ers where the water is hottest.
The Ryznar Index
The Ryznar Stability Index is commonly used to estimate calcium carbonate scaling tendencies
for cooling waters. It should be calculated for both the makeup water and the circulating water. The
‘most common methods of preventing calcium carbonate scale are:
1. If the makeup water is not scaling, control the number of cycles of concentration so that the
Ryznar Stability Index will not exceed 6.0.
CHAPTER 10 301COOLING WATER TREATMENT
2. Add sufficient acid to the makeup water to maintain the pH of the circulating water at a
value slightly less than pHs.
Sulfuric acid is normally used for pH control since it is usually the most economical.
However, caution must be exercised not to precipitate calcium sulfate scale. This is most
likely to occur when the makeup water is high in sulfates and alkalinity.
The rule of thumb for avoiding calcium sulfate scale is to limit the concentration of cal-
cium sulfate in the circulating water to a maximum of 1700 ppm. Another guide is that the
calcium concentration multiplied by the sulfate concentration (when both are expressed in
pm) should not exceed 500 000.
If calcium sulfate scale becomes a problem, HCI can be substituted for HSOx.
3. Use inorganic polyphosphates (sometimes in conjunction with pH control) or organic scale
inhibitors.
Magnesium Scales
‘Magnesium hydroxide will precipitate only in very alkaline waters and is not a widespread prob-
Jem. Magnesium carbonate is usually controlled in the same manner as calcium carbonate.
Silicates
Prevention of silicate scale deposition is normally achieved by limiting the silica concentration in
the cooling water to a maximum value of 175 ppm (preferably 150 ppm).
The cycles of concentration based on the silica ratio should not be allowed to fall appreciably
below the cycles based on chlorides and hardness, as this would indicate silica deposition. If both
silica and magnesium cycle at a lower figure than chlorides, this indicates deposition of magnesium
ate
Pretreatment of Makeup Water
The formation of calcium and magnesium scales can be prevented by removing the calcium and
magnesium ions (hardness) and alkalinity from the water by a softening process. The cold lime process
(see Chapter 6) is commonly used for cooling water.
Corrosion Control
Inorganic corrosion inhibitors such as chromates, polyphosphates, or a combination of the two,
have been used for corrosion contro! for many years. Zinc is also used in combination with either
chromates, polyphospates, or both, to improve inhibition,
Since many of these materials are toxic to living organisms, disposal of blowdown into surface
waters can pose a serious pollution hazard. In fact, chromates are seldom used because of disposal
problems.
Organic inhibitors have generally been less effective in cooling waters than the inorganics.
Microbiological Control
Algae, fungi, and bacteria can all contribute to problems in open cooling water systems. They
‘can encourage corrosion, cause fouling and cause deterioration of the wood in cooling towers.
302 ‘APPLIED WATER TECHNOLOGYCLOSED RECIRCULATING COOLING SYSTEMS
Chlorine is most widely used to control the growth of microorganisms.‘"2) A chlorine residual of
0.3 to 1.0 ppm is usually adequate. Chlorine residuals of greater than 1.0 ppm for long periods can
cause deterioration of tower wood, and should be avoided.
‘A common procedure is to chlorinate to a residual of 1.0 ppm for four hours each day. Continu-
ous chlorination to maintain a residual of 0.2-0.3 ppm is also used, but this may necessitate a periodic
slug treatment with another biocide to kill resistant growths.
Fouling
Fouling of heat exchanger tubes and cooling towers is usually defined as the deposition of non-
scale-forming materials such as:
1. Suspended sotids in the makeup water
2. Particulate matter from the atmosphere
iological masses
4. Corrosion products
5. Hydrocarbon contamination due to process leaks
Filtration and/or coagulation and settling may be employed to remove suspended solids from the
makeup water. Side stream filtration and/or silt dispersants may be employed in the circulating system
to reduce solids deposition. Biocides and corrosion inhibitors are used to prevent the generation of
corrosion products and biological masses.
Tower Wood Deterioration
‘Tower wood deterioration can usually be avoided by following three rules:
1. Maintain an effective biocide treating program from start-up.
2. Avoid excessive chlorination. (1.0 ppm residual for long periods)
3. Maintain the pH of the water at less than 8.3.
CLOSED RECIRCULATING COOLING SYSTEMS
A closed recirculating cooling system is one in which the water is circulated in a closed loop.
The heat absorbed in the cooling operation is dissipated in some type of heat exchanger. Air-fan
coolers are frequently used.
Since the cooling system is closed, there is no evaporation, and therefore no change in water
composition
High chemical treatment levels are often required, but since water losses are negligible, these
levels are economical. Excellent quality makeup water is generally used for best system operation.
‘The advantages of a closed system lie in improved control of cooling water temperature through
the heat producing unit, and in the relative freedom from the problems of operating an open system.
CHAPTER 10 303COOLING WATER TREATMENT
10.1
102
103
REFERENCES
Ostroff, A. G.: Introduction to Oilfield Water Technology, Second Edition, National Association of Corro-
sion Engineers, Houston, Texas (1979),
Kemmer, Frank, N., Editor: The Nalco Water Handbook, McGraw Hill, New York (1979).
Betz: Betz Handbook of Industrial Water Conditioning, Seventh Edition, Betz Laboratories, Inc., Trevose,
Pa, (1976)
‘APPLIED WATER TECHNOLOGY