W W W. S C I E N T I F I C C O L U M B U S . C O M
DPMS
Contents Page Contents Page
Digilogic
Registration Reply Card Exceltronic XLP Modular Plug-In Transducers
Contents 1 (Accuracy to ± 0.2% of Reading) 81-98
Transducer Overview 2-3
Selecting the Proper Introduction 81
Watt or Var Transducer for the Job 4-5 Specifications 82-88
Enclosure Drawings 89
Ordering Procedure 90-91
Digital Power Measurement System 6-9 Wiring Diagrams 92-97
Exceltronic
Test Equipment 98
Digital Power Measurement System 6 JEM Multifunction Transducer 98
Digital Transducer 7
Digital Display 8
Specifications 9 Exceltronic II XLG Transducers
(Accuracy to ± 0.2% of Reading) 99-108
XLP Plug-In
Watt or Var 103-105
Watt or Var 10-15 Combined Watt/Var 106-108
Combined Watt/Watthour 16-23
Combined Var/Varhour 16-23
Volt-Amp 24-29 Instrumentation 110-125
Combined Volt-Amp/Volt-Amphour 24-29
DC Watt Transducer 110-111
DC Voltage Isolation Amplifier 112-115
Exceltronic Transducers DC Instrument Amplifier 116-117
(Accuracy to ± 0.2% of Reading) 31-79 Analog-to-Pulse Converter 118-121
Registers 122-123
XLG
Current or Voltage 31-40 Calibrator 124-125
Harmonics 36
Transducer Accuracy 41
Watt or Var 42-47 Reference 126-137
Combined Watt/Var 48-52
Analog Totalizers 53 Case Dimensions 126-127
Combined Watt/Watthour 54-61 Glossary 128-131
Instrumentation
Combined Var/Varhour 54-61 Special Options & Abbreviations 132
Phase Angle (Power Factor) 62-67 AC & Calibration Formulas 133
Phase Angle or Voltage Angle 68-71 Terms & Conditions 134
Frequency 72-75
Temperature 76-79
Other SCIENTIFIC COLUMBUS Products
JEM10 Meter 30
DM-10 Demand Manager 80
SC-30 Field Standard 109
Reference
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
1
SCI Transducer Cat. 1-51(MTD) 1 1/9/02, 5:21 PM
SCIENTIFIC
Meeting Your Accuracy, Output, and Bud get Requirements–Without Compromise.
COLUMBUS
Technical Support Fast Price Quotations
and Applications Consult the factory for pricing
Scientific Columbus offers four dedicated Assistance 1-800-274-5368 and delivery estimates.
Speak directly to a Scientific Our Local Sales
Metal Cans:
lines of transducers that give you flexibility Seamless, cold-rolled steel
cans, primed and painted
inside and out, assure the
Columbus technical specialist
who will help you with ques-
Representative Will
Come to You
tions pertaining to installation,
for meeting your power-measurement needs. product’s integrity and long
life.
mounting, accuracy, or measure-
ment applications.
In addition to our factory field-
service support, Scientific
Columbus sales representatives
will come to you to demon-
strate products, discuss your
1. Digilogic™ Line - These are the most accurate application, or provide "hands-
commercially available transducers and are ideal for your on" application assistance.
most precise measurement applications (accuracy to 0.1%
of reading). See pages 10-29.
Maintenance, Rentals,
4. Exceltronic® II XLG Line - Smaller can size, and Calibration Services
4-20 mAdc output, and UL recognition in both U.S. and Available
Canada make this line ideal for utility and process-control Scientific Columbus maintains a
applications (accuracy to 0.2% of reading). See pages 99-108. complete maintenance
facility and state-of-the-art
calibration laboratory traceable
to the National Institute of
Standards and Technology.
For information and a list of
services and rental equipment,
consult the factory.
Maintenance, Rentals,
4. Exceltronic® II XLG Line - Smaller can size, and Calibration Services
4-20 mAdc output, and UL recognition in both U.S. and Available
Canada make this line ideal for utility and process-control Scientific Columbus maintains a
applications (accuracy to 0.2% of reading). See pages 99-108. complete maintenance
facility and state-of-the-art
calibration laboratory traceable
to the National Institute of
Standards and Technology.
For information and a list of
services and rental equipment,
consult the factory.
▼
displacement. 2
CALIBRATION RANGE FOR P-OPTION WATT, VAR, AND COMBINED WATT/VAR (60% to 180% of Nominal)
Output in mAdc
Transducer Terminology
The label on a toaster, power drill, or radio might read,
“for use on 120 Vac,” and the actual measured voltage at Nominal Input 1 Element 11/2 or 2 Element 21/2 or 3 Element
the wall socket is 114.2 Vac. The device works because the 1 ▼ Voltage Current From To From To From To
120 Vac statement is a nominal, or general-case value.
Cal. Watts 69 V 0–1 A 30 90 60 180 90 270
Nominal inputs for a watt or var transducer might be (or Vars) 69 V 0–2.5 A 75 225 150 450 225 675
120 Vac, 5 A. For linear operation, however, the input 69 V 0–5 A 150 450 300 900 450 1350
69 V 0–7.5 A 225 675 450 1350 675 2025
voltage may vary from 0 to 150 Vac and the current from 0
to 10 A. There is a maximum value for the product of the 0 69 V 0–10 A 300 900 600 1800 900 2700
69 V 0–15 A 450 1350 900 2700 1350 4050
two inputs in addition to a maximum-current and a maxi- 0 500 W 1000 W 69 V 0–25 A 750 2250 1500 4500 2250 6750
mum-voltage value. This limit is twice the calibrating watts (or Vars) (or Vars) 120 V 0–1 A 60 180 120 360 180 540
(or vars). For example, if the voltage varies up to 150 Vac, 120 V 0–2.5 A 150 450 300 900 450 1350
then the maximum-allowable current with linearity is 6.66 A Input Watts (or Vars)—1 Element 120 V 0–5 A 300 900 600 1800 900 2700
(1000 W (or vars)/150 Vac). If the maximum current is 10 120 V 0–7.5 A 450 1350 900 2700 1350 4050
120 V 0–10 A 600 1800 1200 3600 1800 5400
A, the maximum-allowable voltage is 100 Vac (1000 W (or 120 V 0–15 A 900 2700 1800 5400 2700 8100
vars)/10 A). The preceding graph indicates that the transducer has a 120 V 0–25 A 1500 4500 3000 9000 4500 13500
linear output range of 2 mAdc which equals 1000 W (or
vars). The calibrating watts (or vars) are stamped on the 240 V 0–1 A 120 360 240 720 360 1080
The 1000 W (or vars) value in the previous calculations 240 V 0–2.5 A 300 900 600 1800 900 2700
refers to the effective range of the transducer and is usually unit’s name plate. The standard calibrating watts (or vars) 240 V 0–5 A 600 1800 1200 3600 1800 5400
twice the calibrating watts (or vars) value. The 150 Vac, 10 depend on the nominal-input voltage rating, the nominal- 240 V 0–7.5 A 900 2700 1800 5400 2700 8100
A, and 1000 W (or vars) values are maximum values. When input current, and the number of elements. 240 V 0–10 A 1200 3600 2400 7200 3600 10800
240 V 0–15 A 1800 5400 3600 10800 5400 16200
calibrating watts (or vars) are applied, the resulting output is 240 V 0–25 A 3000 9000 6000 18000 9000 27000
the rated output (RO). The watt or var transducer acts as a The following tables show calibration ranges for standard or
current generator. The rated output flows provided the load P-Option watt, var, or combined watt/var transducers: 480 V 0–1 A 240 720 480 1440 720 2160
480 V 0–2.5 A 600 1800 1200 3600 1800 5400
impedance is less than or equal to 10,000 Ω. In other words, 480 V 0–5 A 1200 3600 2400 7200 3600 10800
the voltage across the output terminals rises to a value 480 V 0–7.5 A 1800 5400 3600 10800 5400 16200
necessary to force the proper current flow through the load 480 V 0–10 A 2400 7200 4800 14400 7200 21600
resistance. The available voltage is guaranteed to be greater 480 V 0–15 A 3600 10800 7200 21600 10800 32400
480 V 0–25 A 6000 18000 12000 36000 18000 54000
than or equal to 10 Vdc, the compliance voltage of the
transducer.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
4 5
SCI Transducer Cat. 1-51(MTD) 4-5 1/9/02, 5:21 PM
Selecting the Proper Selecting the Proper
Watt or Var Transducer for the Job Watt or Var Transducer for the Job
▼
displacement. 2
CALIBRATION RANGE FOR P-OPTION WATT, VAR, AND COMBINED WATT/VAR (60% to 180% of Nominal)
Output in mAdc
Transducer Terminology
The label on a toaster, power drill, or radio might read,
“for use on 120 Vac,” and the actual measured voltage at Nominal Input 1 Element 11/2 or 2 Element 21/2 or 3 Element
the wall socket is 114.2 Vac. The device works because the 1 ▼ Voltage Current From To From To From To
120 Vac statement is a nominal, or general-case value.
Cal. Watts 69 V 0–1 A 30 90 60 180 90 270
Nominal inputs for a watt or var transducer might be (or Vars) 69 V 0–2.5 A 75 225 150 450 225 675
120 Vac, 5 A. For linear operation, however, the input 69 V 0–5 A 150 450 300 900 450 1350
69 V 0–7.5 A 225 675 450 1350 675 2025
voltage may vary from 0 to 150 Vac and the current from 0
to 10 A. There is a maximum value for the product of the 0 69 V 0–10 A 300 900 600 1800 900 2700
69 V 0–15 A 450 1350 900 2700 1350 4050
two inputs in addition to a maximum-current and a maxi- 0 500 W 1000 W 69 V 0–25 A 750 2250 1500 4500 2250 6750
mum-voltage value. This limit is twice the calibrating watts (or Vars) (or Vars) 120 V 0–1 A 60 180 120 360 180 540
(or vars). For example, if the voltage varies up to 150 Vac, 120 V 0–2.5 A 150 450 300 900 450 1350
then the maximum-allowable current with linearity is 6.66 A Input Watts (or Vars)—1 Element 120 V 0–5 A 300 900 600 1800 900 2700
(1000 W (or vars)/150 Vac). If the maximum current is 10 120 V 0–7.5 A 450 1350 900 2700 1350 4050
120 V 0–10 A 600 1800 1200 3600 1800 5400
A, the maximum-allowable voltage is 100 Vac (1000 W (or 120 V 0–15 A 900 2700 1800 5400 2700 8100
vars)/10 A). The preceding graph indicates that the transducer has a 120 V 0–25 A 1500 4500 3000 9000 4500 13500
linear output range of 2 mAdc which equals 1000 W (or
vars). The calibrating watts (or vars) are stamped on the 240 V 0–1 A 120 360 240 720 360 1080
The 1000 W (or vars) value in the previous calculations 240 V 0–2.5 A 300 900 600 1800 900 2700
refers to the effective range of the transducer and is usually unit’s name plate. The standard calibrating watts (or vars) 240 V 0–5 A 600 1800 1200 3600 1800 5400
twice the calibrating watts (or vars) value. The 150 Vac, 10 depend on the nominal-input voltage rating, the nominal- 240 V 0–7.5 A 900 2700 1800 5400 2700 8100
A, and 1000 W (or vars) values are maximum values. When input current, and the number of elements. 240 V 0–10 A 1200 3600 2400 7200 3600 10800
240 V 0–15 A 1800 5400 3600 10800 5400 16200
calibrating watts (or vars) are applied, the resulting output is 240 V 0–25 A 3000 9000 6000 18000 9000 27000
the rated output (RO). The watt or var transducer acts as a The following tables show calibration ranges for standard or
current generator. The rated output flows provided the load P-Option watt, var, or combined watt/var transducers: 480 V 0–1 A 240 720 480 1440 720 2160
480 V 0–2.5 A 600 1800 1200 3600 1800 5400
impedance is less than or equal to 10,000 Ω. In other words, 480 V 0–5 A 1200 3600 2400 7200 3600 10800
the voltage across the output terminals rises to a value 480 V 0–7.5 A 1800 5400 3600 10800 5400 16200
necessary to force the proper current flow through the load 480 V 0–10 A 2400 7200 4800 14400 7200 21600
resistance. The available voltage is guaranteed to be greater 480 V 0–15 A 3600 10800 7200 21600 10800 32400
480 V 0–25 A 6000 18000 12000 36000 18000 54000
than or equal to 10 Vdc, the compliance voltage of the
transducer.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
4 5
SCI Transducer Cat. 1-51(MTD) 4-5 1/9/02, 5:21 PM
SCIENTIFIC SCIENTIFIC
DPMS
Digital Power Measurement System Digital Transducer
COLUMBUS COLUMBUS
One Enclosure!
37 Measurements! DPMS
Configure the DPMS to the Digital Power Measurement System
exact measurment that you need. With traditional transducers, one transducer is required for each measure-
ment that you need. With the DPMS, one transducer can make multiple
measurements. In fact, you can take up to 37 measurements simulta-
neously with just one DPMS unit! This means you can
often specify one DPMS instead of multiple transducers.
With direct communications capability, think of the
savings that can be achieved in every aspect of a new
project. Not only is it easier for Engineering, the DPMS
will also save on wiring and valuable panel space.
SCIENTIFIC CHECK THE SPECS! You will find the DPMS to be highly accurate,
durable, flexible, and economical. The future of transducers has arrived,
COLUMBUS and it’s the DPMS – Digital Programmable Measurement System from
Easily change transducer settings and
outputs with DPMSTalk configuration
DPMS Rochester Instrument Systems, the world leader in transducer technology! software.
Digital Power Measurement System
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
6 7
SCI Transducer Cat. 1-51(MTD) 6-7 1/9/02, 5:22 PM
SCIENTIFIC SCIENTIFIC
DPMS
Digital Power Measurement System Digital Transducer
COLUMBUS COLUMBUS
One Enclosure!
37 Measurements! DPMS
Configure the DPMS to the Digital Power Measurement System
exact measurment that you need. With traditional transducers, one transducer is required for each measure-
ment that you need. With the DPMS, one transducer can make multiple
measurements. In fact, you can take up to 37 measurements simulta-
neously with just one DPMS unit! This means you can
often specify one DPMS instead of multiple transducers.
With direct communications capability, think of the
savings that can be achieved in every aspect of a new
project. Not only is it easier for Engineering, the DPMS
will also save on wiring and valuable panel space.
SCIENTIFIC CHECK THE SPECS! You will find the DPMS to be highly accurate,
durable, flexible, and economical. The future of transducers has arrived,
COLUMBUS and it’s the DPMS – Digital Programmable Measurement System from
Easily change transducer settings and
outputs with DPMSTalk configuration
DPMS Rochester Instrument Systems, the world leader in transducer technology! software.
Digital Power Measurement System
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
6 7
SCI Transducer Cat. 1-51(MTD) 6-7 1/9/02, 5:22 PM
Digital Display Specifications
DPMS
DIGITAL POWER MEASUREMENT SYSTEM
Communicate with Fully Programmable
15 DPMS Units! Digital & Analog Transducer with
Built-in Communications
• Multi-Function Transducer is perfect solution Programmable Configuration Measurement/Calculation Accuracy
for many varied applications 2 element for 3 phase 3 wire delta Volts, Amps, Watts, Vars: 0.2%
• Configured by User (or factory as needed) 2 1/2 element for 3 phase 4 wire wye Watthours, Varhours: 0.2%
3 element for 3 phase 4 wire wye Neutral current: 0.75%
• Programmable as 2, 2.5 or 3 elements Volt Amps: 0.5%
• Configurable Analog Outputs and Digital Measured and/or calculated quantities Power Factor: ±0.008* (rated VA/input VA)
Contact & Alarm Outputs Watts – per phase and total Analog output: ±0.1%
Vars – per phase and total
• Excellent for replacement strategy: Voltage – phase to neutral and phase to phase Environment
One unit replaces many makes and models Current – phase and neutral (calculated) Operating Temperature range: -20° to +70°C
Volt Amps – per phase and total Storage Temperature: -40° to +85°C
• Highly Accurate
DPMS-D • Excellent for back-up strategy:
Frequency
Distortion – Total Harmonic Distortion
Humidity: 20 to 90% RH non condensing
RFI: <1% when subjected to 10 V/M @ 1 meter
Optional Digital Display of each voltage & current
One unit on shelf backs up many varied units in the field. Watthours – delivered and received
ESD: IEC 801-2 level 3 (8 kV) with no damage
Surge Withstand: ANSI/IEEE C37.90, IEC 801-4 Class 4
Display • Programmable Communications of MODBUS and DNP 3.0 Varhours – delivered and received Isolation: 2500 VAC RMS from Input/Output/Power/Case
4 line x 20 character vacuum fluorescent display allows Unit • Economical Power Factor – per phase and system 500 VAC RMS between digital outputs
ID and 3 simultaneous measurements to be viewed • Remote Display Option available Communication/Configuration ports share common
Character height 0.19 inch Inputs with the analog outputs
Color-blue • Space Saving Size 3.75" x 5.375" x 6.5" Current Nominal – 5 amps
Operating Range – 0 to 10 amps
3 key switches allow selection of data to be viewed • Transformer Loss Compensation (TLC) Burden per Element = 0.25 VA
Influences Affecting Accuracy
12 standard display screens and Temperature: Conversion only: 75 ppm/°C
Voltage Nominal – 120 volts Including analog outputs: 125 ppm/°C
4 custom display screens Operating Range – 85 to 150 volts
Displays in primary units
(CT&PT ratios configured in DPMS)
DPMS Optional: 69 VAC Nominal, Range
Long Term Stability: 0.1% of rated output/year,
noncumulative
50-85 277 VAC Nominal, Range 180-
Order Configuration Sheet 320 VAC 480 VAC Nominal, Range
Humidity: less than 0.05% of rated output
over the operating range
Quantities available for display 310-550 VAC
Watts – per phase and total Burden per Element: 0.05 VA
A base DPMS is standard equipped with: a nominal potential Mechanical
Vars – per phase and total Frequency 45 to 65 Hertz
Size: 3.75" x 5.375" x 6.5"
Watthours – delivered and received of 120V, nominal current of 5 Amps, no analog outputs, Sample Rate 128 Samples/Cycle
Weight: 2.6 lbs. (1.2 kg.)
Varhours – delivered and received Power Supply 95 to 265 VAC @ 50/60 Hz or DC
Voltage – phase to neutral and phase to phase
no digital outputs, and communications kit for programming 6 VA Maximum @ 120 V
Communications
Current – phase and neutral (calculated) the DPMS. The communications kit is standard and includes Hardware Protocol: RS-232 (full duplex)
Outputs
Volt Amps – per phase and total DPMSTalk programming software and a RS-232/485 adapter 3 Channel Analog: or RS-485 (half duplex)
Power Factor – per phase and system frequency with cable. Programmable Software Protocol
Distortion – total harmonic distortion of each voltage All (3) channels are independently configured and scaled
with DPMSTalk software Modbus: RTU or ASCII Mode
and current Option A1: 0 to ± 1 ma, maximum 10 volt compliance DNP 3.0
Watthours – bidirectional Additional Options: Option A2: 4 to 20 ma, maximum 12 volt compliance
Varhours – bidirectional Nominal voltage input: P2 = 277V Response Time </= 200 mS
6 Channel Digital – Option D1:
Communications P3 = 480V All (6) channels are independently configured and scaled with
Multi Addressing allows communication to up to 15 DPMS P4 = 69V. DPMSTalk software as KYZ contacts for energy measurements or as
units per DPMS-D display module high/low threshold alarms.
Half duplex RS-485 Solid state rated 50 ma @135 VAC/VDC
Recommended maximum distance between DPMS and Analog output option: A1 = 0-1mA with less than 5 volt drop
DPMS-D is 4000 feet A2 = 4-20mA. 54,000 CPH maximum
Mechanical
Panel cutout 4.38 x 3.75 inches Programming Kit: R0 = Without Programming kit
Weight 1.4 lbs. (0.64 kg.) consisting of DPMSTalk
Configuration Software and
Environmental
Operating Temperature range: -20° to +70°C RS-232/485 adapter cable
Storage Temperature: -40° to +85°C
Humidity: 20 to 90% RH non condensing Fill in the order codes as shown below
RFI: no effect when subjected to 10 V/M @ 1 meter to create model number:
ESD: IEC 801-2 level 3 (8 kV) with no damage
Surge Withstand: ANSI/IEEE C37.90, IEC 801-4 Class 4 Example: DPMS-P3-A1-D1 is a DPMS at 480V with 1mA analog outputs,
Visit Us Online!
Isolation: 2500 VAC RMS from power to Case or digital contact outputs, and with RS-232/485 adapter cable and DPMSTalk
Communications port1 configuration software. WWW.ROCHESTER.COM
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
8 9
SCI Transducer Cat. 1-51(MTD) 8-9 1/9/02, 5:22 PM
Digital Display Specifications
DPMS
DIGITAL POWER MEASUREMENT SYSTEM
Communicate with Fully Programmable
15 DPMS Units! Digital & Analog Transducer with
Built-in Communications
• Multi-Function Transducer is perfect solution Programmable Configuration Measurement/Calculation Accuracy
for many varied applications 2 element for 3 phase 3 wire delta Volts, Amps, Watts, Vars: 0.2%
• Configured by User (or factory as needed) 2 1/2 element for 3 phase 4 wire wye Watthours, Varhours: 0.2%
3 element for 3 phase 4 wire wye Neutral current: 0.75%
• Programmable as 2, 2.5 or 3 elements Volt Amps: 0.5%
• Configurable Analog Outputs and Digital Measured and/or calculated quantities Power Factor: ±0.008* (rated VA/input VA)
Contact & Alarm Outputs Watts – per phase and total Analog output: ±0.1%
Vars – per phase and total
• Excellent for replacement strategy: Voltage – phase to neutral and phase to phase Environment
One unit replaces many makes and models Current – phase and neutral (calculated) Operating Temperature range: -20° to +70°C
Volt Amps – per phase and total Storage Temperature: -40° to +85°C
• Highly Accurate
DPMS-D • Excellent for back-up strategy:
Frequency
Distortion – Total Harmonic Distortion
Humidity: 20 to 90% RH non condensing
RFI: <1% when subjected to 10 V/M @ 1 meter
Optional Digital Display of each voltage & current
One unit on shelf backs up many varied units in the field. Watthours – delivered and received
ESD: IEC 801-2 level 3 (8 kV) with no damage
Surge Withstand: ANSI/IEEE C37.90, IEC 801-4 Class 4
Display • Programmable Communications of MODBUS and DNP 3.0 Varhours – delivered and received Isolation: 2500 VAC RMS from Input/Output/Power/Case
4 line x 20 character vacuum fluorescent display allows Unit • Economical Power Factor – per phase and system 500 VAC RMS between digital outputs
ID and 3 simultaneous measurements to be viewed • Remote Display Option available Communication/Configuration ports share common
Character height 0.19 inch Inputs with the analog outputs
Color-blue • Space Saving Size 3.75" x 5.375" x 6.5" Current Nominal – 5 amps
Operating Range – 0 to 10 amps
3 key switches allow selection of data to be viewed • Transformer Loss Compensation (TLC) Burden per Element = 0.25 VA
Influences Affecting Accuracy
12 standard display screens and Temperature: Conversion only: 75 ppm/°C
Voltage Nominal – 120 volts Including analog outputs: 125 ppm/°C
4 custom display screens Operating Range – 85 to 150 volts
Displays in primary units
(CT&PT ratios configured in DPMS)
DPMS Optional: 69 VAC Nominal, Range
Long Term Stability: 0.1% of rated output/year,
noncumulative
50-85 277 VAC Nominal, Range 180-
Order Configuration Sheet 320 VAC 480 VAC Nominal, Range
Humidity: less than 0.05% of rated output
over the operating range
Quantities available for display 310-550 VAC
Watts – per phase and total Burden per Element: 0.05 VA
A base DPMS is standard equipped with: a nominal potential Mechanical
Vars – per phase and total Frequency 45 to 65 Hertz
Size: 3.75" x 5.375" x 6.5"
Watthours – delivered and received of 120V, nominal current of 5 Amps, no analog outputs, Sample Rate 128 Samples/Cycle
Weight: 2.6 lbs. (1.2 kg.)
Varhours – delivered and received Power Supply 95 to 265 VAC @ 50/60 Hz or DC
Voltage – phase to neutral and phase to phase
no digital outputs, and communications kit for programming 6 VA Maximum @ 120 V
Communications
Current – phase and neutral (calculated) the DPMS. The communications kit is standard and includes Hardware Protocol: RS-232 (full duplex)
Outputs
Volt Amps – per phase and total DPMSTalk programming software and a RS-232/485 adapter 3 Channel Analog: or RS-485 (half duplex)
Power Factor – per phase and system frequency with cable. Programmable Software Protocol
Distortion – total harmonic distortion of each voltage All (3) channels are independently configured and scaled
with DPMSTalk software Modbus: RTU or ASCII Mode
and current Option A1: 0 to ± 1 ma, maximum 10 volt compliance DNP 3.0
Watthours – bidirectional Additional Options: Option A2: 4 to 20 ma, maximum 12 volt compliance
Varhours – bidirectional Nominal voltage input: P2 = 277V Response Time </= 200 mS
6 Channel Digital – Option D1:
Communications P3 = 480V All (6) channels are independently configured and scaled with
Multi Addressing allows communication to up to 15 DPMS P4 = 69V. DPMSTalk software as KYZ contacts for energy measurements or as
units per DPMS-D display module high/low threshold alarms.
Half duplex RS-485 Solid state rated 50 ma @135 VAC/VDC
Recommended maximum distance between DPMS and Analog output option: A1 = 0-1mA with less than 5 volt drop
DPMS-D is 4000 feet A2 = 4-20mA. 54,000 CPH maximum
Mechanical
Panel cutout 4.38 x 3.75 inches Programming Kit: R0 = Without Programming kit
Weight 1.4 lbs. (0.64 kg.) consisting of DPMSTalk
Configuration Software and
Environmental
Operating Temperature range: -20° to +70°C RS-232/485 adapter cable
Storage Temperature: -40° to +85°C
Humidity: 20 to 90% RH non condensing Fill in the order codes as shown below
RFI: no effect when subjected to 10 V/M @ 1 meter to create model number:
ESD: IEC 801-2 level 3 (8 kV) with no damage
Surge Withstand: ANSI/IEEE C37.90, IEC 801-4 Class 4 Example: DPMS-P3-A1-D1 is a DPMS at 480V with 1mA analog outputs,
Visit Us Online!
Isolation: 2500 VAC RMS from power to Case or digital contact outputs, and with RS-232/485 adapter cable and DPMSTalk
Communications port1 configuration software. WWW.ROCHESTER.COM
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
8 9
SCI Transducer Cat. 1-51(MTD) 8-9 1/9/02, 5:22 PM
SCIENTIFIC
Digilogic AC Watt or Var Transducers SCIENTIFIC
Specifications
COLUMBUS COLUMBUS
DIGILOGIC AC WATT OR VAR TRANSDUCERS
Digilogic watt and var
Digilogic
transducers provide utility, Specifications 0 to ±1 mAdc Watts P-Option* Watts 0 to ±1 mAdc Vars P-Option* Vars
(Watt Transducer) (Watt Transducer) (Var Transducer) (Var Transducer)
laboratory, and industrial
Current Nominal 5A
users with the highest degree Input Range** 0–10 A
of accuracy for applications Overload Continuous 20 A
Overload 1 Second/Hour 250 A
requiring precision measurement Burden/Element 0.2 VA (maximum) at 5 A
of real and reactive electrical Voltage Nominal 120 V
Input Range** 0–150 V
power. A precision electronic Overload Continuous 200 V
Burden/Element 0.02 VA (maximum) at 120 V
multiplier allows measurement
External Input Range 85–135 Vac 100–130 Vac 85–135 Vac 100–130 Vac
of true power to within 0.1% of Auxiliary Frequency Range 50–500 Hz 50–500 Hz 50–500 Hz 50–500 Hz
reading throughout a wide range of input Power Burden 3 VA Nominal 6 VA Nominal 3 VA Nominal 6 VA Nominal
voltage, current, power factor, and environmental conditions. Rated Output (RO) = ±1 mAdc for 5, 20, or 50 mAdc for ±1 mAdc for 5, 20, or 50 mAdc for
500 Watts or Vars/Element Standard Calibration Std. Calibration, depending on Standard Calibration Std. Calibration, depending on
selected output range* selected output range*
Accuracy ±(0.09% Reading + 0.005% RO) ±(0.1% Reading + 0.05% RO) ±(0.15% Reading + 0.01% RO) ±(0.15% Reading + 0.05% RO)
at 0–200% RO at 0–120% RO at 0–200% RO at 0–120% RO
Features Applications Outputs Temperature Effect on Accuracy ± 0.005% / ° C ±0.0065% / ° C ±0.009% / ° C ±0.01% / ° C
Operating Temperature Range -20° C to +70° C -20° C to +50° C -20° C to +60° C -20° C to +50° C
u Accuracy to 0.1% of reading u Utility billing u 0 to ±1 mAdc Compliance Voltage 10 Vdc 10 Vdc
See Table 2 on page 8. See Table 2 on page 8.
Load 0–10,000 Ω 0–10,000 Ω
u Exceptional reliability u Test laboratories u 1–5 or 1–3–5 mAdc
Output Ripple Peak < 0.5% RO < 0.25% RO < 0.5% RO < 0.25% RO
u Excellent long-term stability u State estimation u 4–20 or 4–12–20 mAdc Response Time < 400 ms to 99% < 1 Second to 99% < 400 ms to 99% < 1 Second to 99%
u No zero adjustment required u 10–50 or 10–30–50 mAdc Power Factor Any
PF Effect on Accuracy ±0.04% VA (maximum) (Included in Accuracy specification above.)
Standard Calibration Gain ± 1% of Reading (minimum) ±10% of Span (minimum) ± 1% of Reading (minimum) ±10% of Span (minimum)
Adjustments Zero None Required ±5% of Zero Point (minimum) None Required ±5% of Zero Point (minimum)
Frequency Range 58–62 Hz 60 Hz
Measure Power Plant Losses with Digilogic Watt or Var Transducers
Stability (per year) ±0.05% RO, ± 0.1% of Span, ± 0.1% RO, ±0.2% of Span,
Noncumulative Noncumulative Noncumulative Noncumulative
The exceptional accuracy of the Digilogic Transducer line allows for uncom-
Operating Humidity 0–95% Noncondensing
mon measurements that have real payback.
Isolation Complete (Input/Output/Power/Case)
As in any system, generation losses represent unrecovered expense. Within Dielectric Withstand 1500 VRMS at 60 Hz
the generating station, losses between the generator terminals and the high-
Surge Withstand ANSI/IEEE C37.90.1
voltage side of the generator step-up (GSU) transformer can be significant.
These losses, which result from the high currents and large voltage change Maximum Net Weight 4 lbs., 6 oz. (2 kg) 4 lbs., 12 oz. (2.2 kg) 4 lbs., 8 oz. (2 kg) 4 lbs., 14 oz. (2.2 kg)
through the GSU, can affect the precision of the control room real and reactive Approximate Dimensions 7.0" W x 3.7" D x 5.6" H 7.2" W x 5.3" D x 5.8" H 7.0" W x 3.7" D x 5.6" H 7.2" W x 5.3" D x 5.8" H
power and energy measurements. (excluding mounting plate) (178 mm x 94 mm x 142 mm) (183 mm x 135 mm x 147 mm) (178 mm x 94 mm x 142 mm) (183 mm x 135 mm x 147 mm)
Style I Case, see page 122 Style V Case, see page 123 Style I Case, see page 122 Style V Case, see page 123
The Digilogic Transducer’s measurement accuracy allows precise measure- Overrange with Linearity 500–1000 Watts/Element 500–600 Watts/Element 500–1000 Vars/Element 500–600 Vars/Element
ment of the difference between terminal power and GSU high-side power. This No additional error within voltage compliance. Reduce load resistance as required.
difference, characterized as a station loss, is measurable because the random
errors associated with this type of measurement are negligible when using * P-Option includes 1–5/1–3–5, 4–20/4–12–20, and 10–50/10–30–50 mAdc outputs. Specifications subject to change without notice.
**Total input not to exceed 200% of standard-calibration watts or vars on units with 0 to ±1 mAdc output.
high-accuracy Digilogic Transducers. Total input not to exceed 120% of standard-calibration watts or vars on units with P-Option outputs.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
10 11
SCI Transducer Cat. 1-51(MTD) 10-11 1/9/02, 5:22 PM
SCIENTIFIC
Digilogic AC Watt or Var Transducers SCIENTIFIC
Specifications
COLUMBUS COLUMBUS
DIGILOGIC AC WATT OR VAR TRANSDUCERS
Digilogic watt and var
Digilogic
transducers provide utility, Specifications 0 to ±1 mAdc Watts P-Option* Watts 0 to ±1 mAdc Vars P-Option* Vars
(Watt Transducer) (Watt Transducer) (Var Transducer) (Var Transducer)
laboratory, and industrial
Current Nominal 5A
users with the highest degree Input Range** 0–10 A
of accuracy for applications Overload Continuous 20 A
Overload 1 Second/Hour 250 A
requiring precision measurement Burden/Element 0.2 VA (maximum) at 5 A
of real and reactive electrical Voltage Nominal 120 V
Input Range** 0–150 V
power. A precision electronic Overload Continuous 200 V
Burden/Element 0.02 VA (maximum) at 120 V
multiplier allows measurement
External Input Range 85–135 Vac 100–130 Vac 85–135 Vac 100–130 Vac
of true power to within 0.1% of Auxiliary Frequency Range 50–500 Hz 50–500 Hz 50–500 Hz 50–500 Hz
reading throughout a wide range of input Power Burden 3 VA Nominal 6 VA Nominal 3 VA Nominal 6 VA Nominal
voltage, current, power factor, and environmental conditions. Rated Output (RO) = ±1 mAdc for 5, 20, or 50 mAdc for ±1 mAdc for 5, 20, or 50 mAdc for
500 Watts or Vars/Element Standard Calibration Std. Calibration, depending on Standard Calibration Std. Calibration, depending on
selected output range* selected output range*
Accuracy ±(0.09% Reading + 0.005% RO) ±(0.1% Reading + 0.05% RO) ±(0.15% Reading + 0.01% RO) ±(0.15% Reading + 0.05% RO)
at 0–200% RO at 0–120% RO at 0–200% RO at 0–120% RO
Features Applications Outputs Temperature Effect on Accuracy ± 0.005% / ° C ±0.0065% / ° C ±0.009% / ° C ±0.01% / ° C
Operating Temperature Range -20° C to +70° C -20° C to +50° C -20° C to +60° C -20° C to +50° C
u Accuracy to 0.1% of reading u Utility billing u 0 to ±1 mAdc Compliance Voltage 10 Vdc 10 Vdc
See Table 2 on page 8. See Table 2 on page 8.
Load 0–10,000 Ω 0–10,000 Ω
u Exceptional reliability u Test laboratories u 1–5 or 1–3–5 mAdc
Output Ripple Peak < 0.5% RO < 0.25% RO < 0.5% RO < 0.25% RO
u Excellent long-term stability u State estimation u 4–20 or 4–12–20 mAdc Response Time < 400 ms to 99% < 1 Second to 99% < 400 ms to 99% < 1 Second to 99%
u No zero adjustment required u 10–50 or 10–30–50 mAdc Power Factor Any
PF Effect on Accuracy ±0.04% VA (maximum) (Included in Accuracy specification above.)
Standard Calibration Gain ± 1% of Reading (minimum) ±10% of Span (minimum) ± 1% of Reading (minimum) ±10% of Span (minimum)
Adjustments Zero None Required ±5% of Zero Point (minimum) None Required ±5% of Zero Point (minimum)
Frequency Range 58–62 Hz 60 Hz
Measure Power Plant Losses with Digilogic Watt or Var Transducers
Stability (per year) ±0.05% RO, ± 0.1% of Span, ± 0.1% RO, ±0.2% of Span,
Noncumulative Noncumulative Noncumulative Noncumulative
The exceptional accuracy of the Digilogic Transducer line allows for uncom-
Operating Humidity 0–95% Noncondensing
mon measurements that have real payback.
Isolation Complete (Input/Output/Power/Case)
As in any system, generation losses represent unrecovered expense. Within Dielectric Withstand 1500 VRMS at 60 Hz
the generating station, losses between the generator terminals and the high-
Surge Withstand ANSI/IEEE C37.90.1
voltage side of the generator step-up (GSU) transformer can be significant.
These losses, which result from the high currents and large voltage change Maximum Net Weight 4 lbs., 6 oz. (2 kg) 4 lbs., 12 oz. (2.2 kg) 4 lbs., 8 oz. (2 kg) 4 lbs., 14 oz. (2.2 kg)
through the GSU, can affect the precision of the control room real and reactive Approximate Dimensions 7.0" W x 3.7" D x 5.6" H 7.2" W x 5.3" D x 5.8" H 7.0" W x 3.7" D x 5.6" H 7.2" W x 5.3" D x 5.8" H
power and energy measurements. (excluding mounting plate) (178 mm x 94 mm x 142 mm) (183 mm x 135 mm x 147 mm) (178 mm x 94 mm x 142 mm) (183 mm x 135 mm x 147 mm)
Style I Case, see page 122 Style V Case, see page 123 Style I Case, see page 122 Style V Case, see page 123
The Digilogic Transducer’s measurement accuracy allows precise measure- Overrange with Linearity 500–1000 Watts/Element 500–600 Watts/Element 500–1000 Vars/Element 500–600 Vars/Element
ment of the difference between terminal power and GSU high-side power. This No additional error within voltage compliance. Reduce load resistance as required.
difference, characterized as a station loss, is measurable because the random
errors associated with this type of measurement are negligible when using * P-Option includes 1–5/1–3–5, 4–20/4–12–20, and 10–50/10–30–50 mAdc outputs. Specifications subject to change without notice.
**Total input not to exceed 200% of standard-calibration watts or vars on units with 0 to ±1 mAdc output.
high-accuracy Digilogic Transducers. Total input not to exceed 120% of standard-calibration watts or vars on units with P-Option outputs.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
10 11
SCI Transducer Cat. 1-51(MTD) 10-11 1/9/02, 5:22 PM
Ordering Procedure Ordering Procedure
Digilogic AC Watt or Var Transducers Digilogic AC Watt or Var Transducers
Specify by base model number and appropriate selection or option suffixes in the order shown in the following example. Option Description Input Range Frequency Range Burden
(0 to ±1 mAdc Units)
Digilogic
Auxiliary Current Voltage -RS/Freq. Option Option External A2** External Auxiliary Power (120 Vac std.) 85-135 Vac 50-500 Hz 3 VA
Base Model No. Output Power Input Input Option #1 #2 #3 Aux. Power A4 Internal Auxiliary Power (self-powered) 70-112% of Nominal Aux. Power Voltage Equals Input Frequency 3 VA
(P-Option Units)
Table 1 Table 2 Table 3 Table 4 Table 4 Table 5 Table 6 Table 6 Table 3
A2** (leave blank) External Auxiliary Power (120 Vac std.) 100-130 Vac 50-500 Hz 6 VA
A4 Internal Auxiliary Power (self-powered) 84-108% of Nominal Aux. Power Voltage Equals Input Frequency 6 VA
0 to ±1 mAdc
output A2
** For external auxiliary power voltages other than 120 Vac, specify the voltage in the last position of the complete model number. (Example: 240 Vac Aux.)
DL342K5 -5 -1 -RS -SM -SC DC external auxiliary power available; see Special Options on page 128.
DL342K5PAN7A4-5-1-RS-SM-SC **** Option -8 requires a Style V case. (See page 123 for case dimensions.
3-element, 4-20 mAdc Watt Transducer; internal auxiliary power; 10 A input; 240 V input; resistor scaling (converts current Maximum height of terminal strip(s) is 1.07" for units with -8 option.)
output to voltage output); seismic brace; special calibration (example: 7200 W).
Table 5 Scaling Resistor (-RS)/Frequency Options
Numbers. For outputs PAN7 4-20 mAdc 15 Vdc/750 Ω 30 Vdc This information is not part of the model number, but must be provided
other than 0 to ±1 mAdc, PAN8 10-50 mAdc 15 Vdc/300 Ω 30 Vdc to the factory when you place your order.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
12 13
SCI Transducer Cat. 1-51(MTD) 12-13 1/9/02, 5:22 PM
Ordering Procedure Ordering Procedure
Digilogic AC Watt or Var Transducers Digilogic AC Watt or Var Transducers
Specify by base model number and appropriate selection or option suffixes in the order shown in the following example. Option Description Input Range Frequency Range Burden
(0 to ±1 mAdc Units)
Digilogic
Auxiliary Current Voltage -RS/Freq. Option Option External A2** External Auxiliary Power (120 Vac std.) 85-135 Vac 50-500 Hz 3 VA
Base Model No. Output Power Input Input Option #1 #2 #3 Aux. Power A4 Internal Auxiliary Power (self-powered) 70-112% of Nominal Aux. Power Voltage Equals Input Frequency 3 VA
(P-Option Units)
Table 1 Table 2 Table 3 Table 4 Table 4 Table 5 Table 6 Table 6 Table 3
A2** (leave blank) External Auxiliary Power (120 Vac std.) 100-130 Vac 50-500 Hz 6 VA
A4 Internal Auxiliary Power (self-powered) 84-108% of Nominal Aux. Power Voltage Equals Input Frequency 6 VA
0 to ±1 mAdc
output A2
** For external auxiliary power voltages other than 120 Vac, specify the voltage in the last position of the complete model number. (Example: 240 Vac Aux.)
DL342K5 -5 -1 -RS -SM -SC DC external auxiliary power available; see Special Options on page 128.
DL342K5PAN7A4-5-1-RS-SM-SC **** Option -8 requires a Style V case. (See page 123 for case dimensions.
3-element, 4-20 mAdc Watt Transducer; internal auxiliary power; 10 A input; 240 V input; resistor scaling (converts current Maximum height of terminal strip(s) is 1.07" for units with -8 option.)
output to voltage output); seismic brace; special calibration (example: 7200 W).
Table 5 Scaling Resistor (-RS)/Frequency Options
Numbers. For outputs PAN7 4-20 mAdc 15 Vdc/750 Ω 30 Vdc This information is not part of the model number, but must be provided
other than 0 to ±1 mAdc, PAN8 10-50 mAdc 15 Vdc/300 Ω 30 Vdc to the factory when you place your order.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
12 13
SCI Transducer Cat. 1-51(MTD) 12-13 1/9/02, 5:22 PM
Wiring Diagrams Wiring Diagrams
Digilogic AC Watt or Var Transducers Digilogic AC Watt or Var Transducers
WIRING DIAGRAMS FOR 0 to ±1 mAdc UNITS (Style I Case) WIRING DIAGRAMS FOR P-OPTION UNITS (Style V Case)
1 Element, Single Phase, 2 Wire 11/2 Element, Single Phase, 3 Wire 1 Element, Single Phase, 2 Wire 11/2 Element, Single Phase, 3 Wire
Digilogic
LINE
LINE
L1 L2 L1 N L2
LINE LINE
L1 L2 L1 N L2
DC DC
OUTPUT OUTPUT
DC DC - + - +
OUTPUT OUTPUT
- + - +
1 2 3 4 5 6 6A 1 2 3 4 5 6 6A
1 2 3 4 5 6 6A 1 2 3 4 5 6 6A
7 8 9 10 11 12 12A 7 8 9 10 11 12 12A
7 8 9 10 11 12 12A 7 8 9 10 11 12 12A
LOAD
LOAD
EXTERNAL EXTERNAL LOAD NOTE: For units with -8 option, connect
AUX. POWER NOTE: For units with -8 option, AUX. POWER
EXTERNAL current input to terminals 7 (•) & 10. EXTERNAL
connect current input to terminals 7 AUX. POWER AUX. POWER
LOAD
DC DC
DC DC OUTPUT OUTPUT
OUTPUT OUTPUT - + - +
- + - +
1 2 3 4 5 6 6A 1 2 3 4 5 6 6A
1 2 3 4 5 6 6A 1 2 3 4 5 6 6A
7 8 9 10 11 12 12A 7 8 9 10 11 12 12A
7 8 9 10 11 12 12A 7 8 9 10 11 12 12A
EXTERNAL EXTERNAL
AUX. POWER LOAD AUX. POWER LOAD
DC DC
OUTPUT OUTPUT
- + - +
DC DC
OUTPUT OUTPUT
- + - +
1 2 3 4 5 6 6A 1 2 3 4 5 6 6A
1 2 3 4 5 6 6A 1 2 3 4 5 6 6A
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
7 8 9 10 11 12 12A 7 8 9 10 11 12 12A
7 8 9 10 11 12 12A 7 8 9 10 11 12 12A
LOAD LOAD
LOAD
LOAD
Adjust A2 Models: Shown. A4 Models: External aux. power not required. Adjust A2 Models: Shown. A4 Models: External aux. power not required.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
14 J 1001-9111 (10K)
15
SCI Transducer Cat. 1-51(MTD) 14-15 1/9/02, 5:23 PM
Wiring Diagrams Wiring Diagrams
Digilogic AC Watt or Var Transducers Digilogic AC Watt or Var Transducers
WIRING DIAGRAMS FOR 0 to ±1 mAdc UNITS (Style I Case) WIRING DIAGRAMS FOR P-OPTION UNITS (Style V Case)
1 Element, Single Phase, 2 Wire 11/2 Element, Single Phase, 3 Wire 1 Element, Single Phase, 2 Wire 11/2 Element, Single Phase, 3 Wire
Digilogic
LINE
LINE
L1 L2 L1 N L2
LINE LINE
L1 L2 L1 N L2
DC DC
OUTPUT OUTPUT
DC DC - + - +
OUTPUT OUTPUT
- + - +
1 2 3 4 5 6 6A 1 2 3 4 5 6 6A
1 2 3 4 5 6 6A 1 2 3 4 5 6 6A
7 8 9 10 11 12 12A 7 8 9 10 11 12 12A
7 8 9 10 11 12 12A 7 8 9 10 11 12 12A
LOAD
LOAD
EXTERNAL EXTERNAL LOAD NOTE: For units with -8 option, connect
AUX. POWER NOTE: For units with -8 option, AUX. POWER
EXTERNAL current input to terminals 7 (•) & 10. EXTERNAL
connect current input to terminals 7 AUX. POWER AUX. POWER
LOAD
DC DC
DC DC OUTPUT OUTPUT
OUTPUT OUTPUT - + - +
- + - +
1 2 3 4 5 6 6A 1 2 3 4 5 6 6A
1 2 3 4 5 6 6A 1 2 3 4 5 6 6A
7 8 9 10 11 12 12A 7 8 9 10 11 12 12A
7 8 9 10 11 12 12A 7 8 9 10 11 12 12A
EXTERNAL EXTERNAL
AUX. POWER LOAD AUX. POWER LOAD
DC DC
OUTPUT OUTPUT
- + - +
DC DC
OUTPUT OUTPUT
- + - +
1 2 3 4 5 6 6A 1 2 3 4 5 6 6A
1 2 3 4 5 6 6A 1 2 3 4 5 6 6A
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
7 8 9 10 11 12 12A 7 8 9 10 11 12 12A
7 8 9 10 11 12 12A 7 8 9 10 11 12 12A
LOAD LOAD
LOAD
LOAD
Adjust A2 Models: Shown. A4 Models: External aux. power not required. Adjust A2 Models: Shown. A4 Models: External aux. power not required.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
14 J 1001-9111 (10K)
15
SCI Transducer Cat. 1-51(MTD) 14-15 1/9/02, 5:23 PM
SCIENTIFIC
Digilogic AC Watt/Watthour SCIENTIFIC
Specifications
or Var/Varhour Transducers
COLUMBUS COLUMBUS
DIGILOGIC AC WATT/WATTHOUR OR VAR/VARHOUR TRANSDUCERS
Digilogic combined watt/watt-
Digilogic
hour and var/varhour transducers Specifications 0 to ±1 mAdc Watts P-Option* Watts 0 to ±1 mAdc Vars P-Option* Vars
provide high accuracy with two (Watt/Watthour (Watt/Watthour (Var/Varhour (Var/Varhour
Transducer) Transducer) Transducer) Transducer)
simultaneous outputs: an analog
output directly proportional to Current Nominal 5A
Input Range** 0–10 A
instantaneous watts or vars, and a Overload Continuous 20 A
Overload 1 Second/Hour 250 A
digital (pulse) output (Form-C Burden/Element 0.2 VA (maximum) at 5 A
mercury-wetted relay or solid-state) Voltage Nominal 120 V
Input Range** 0–150 V
directly proportional to watthours or Overload Continuous 200 V
varhours. All models are available in Burden/Element 0.02 VA (maximum) at 120 V
either unidirectional or bidirectional configurations. External Input Range 85–135 Vac 100–130 Vac 85–135 Vac 100–130 Vac
Auxiliary Frequency Range 50–500 Hz 50–500 Hz 50–500 Hz 50–500 Hz
Power Burden 3 VA Nominal 6 VA Nominal 3 VA Nominal 6 VA Nominal
Rated Output (RO) = ±1 mAdc for 5, 20, or 50 mAdc for ±1 mAdc for 5, 20, or 50 mAdc for
500 Watts or Vars/Element Standard Calibration Std. Calibration, depending on Standard Calibration Std. Calibration, depending on
selected output range* selected output range*
Features Applications Outputs Accuracy ±(0.09% Reading + 0.005% RO) ±(0.1% Reading + 0.05% RO) ± (0.15% Reading + 0.01% RO) ± (0.15% Reading + 0.05% RO)
at 0–200% RO at 0–120% RO at 0–200% RO at 0–120% RO
±0.005% / ° C ±0.0065% / ° C ±0.009% / ° C ± 0.01% / ° C
◆ Accuracy to 0.1% of reading ◆ Utility billing ◆ 0 to ±1 mAdc Temperature Effect on Accuracy
Operating Temperature Range -20° C to +70° C -20° C to +50° C -20° C to +60° C -20° C to +50° C
◆ Analog & digital outputs ◆ Test laboratories ◆ 1–5 or 1–3–5 mAdc Compliance Voltage 10 Vdc 10 Vdc
See Table 2 on page 14. See Table 2 on page 14.
◆ Exceptional reliability ◆ Process control ◆ 4–20 or 4–12–20 mAdc Load 0–10,000 Ω 0–10,000 Ω
Output Ripple Peak < 0.5% RO < 0.25% RO < 0.5% RO < 0.25% RO
◆ Excellent long-term stability ◆ 10–50 or 10–30–50 mAdc Relay Contact Rating (-60XX option) 15 VA at 1 A (maximum) or 150 Vac/15 Vdc (maximum) with resistive load. Contact protection required for inductive loads.
◆ Wide selection of current & ◆ Relay and solid-state Relay Contact Life (-60XX option) One billion operations when operated within specifications.
voltage input ranges outputs for watthour and Solid-State Output Contact
Rating (-62XX option) 28 Vdc (maximum) VCESAT: 1 Vdc (maximum) at 7 mAdc
varhour functions
Response Time < 400 ms to 99% < 1 Second to 99% < 400 ms to 99% < 1 Second to 99%
Power Factor Any
PF Effect on Accuracy ±0.04% VA (maximum) (Included in Accuracy specification above.)
Standard Calibration Gain ±1% of Reading (minimum) ±10% of Span (minimum) ±1% of Reading (minimum) ±10% of Span (minimum)
Adjustments Zero None Required ± 5% of Zero Point (minimum) None Required ± 5% of Zero Point (minimum)
Frequency Range 58–62 Hz 60 Hz
Stability (per year) ± 0.05% RO, ±0.1% of Span, ±0.1% RO, ±0.2% of Span,
Noncumulative Noncumulative Noncumulative Noncumulative
Digilogic Transducers Used to Calibrate Accuracy Standards Operating Humidity 0–95% Noncondensing
Isolation Complete (Input/Output/Power/Case) All KYZ outputs are isolated.
The Digilogic Transducer is recognized as the premier power-system
parameter-measurement device. A new twist in DL application Dielectric Withstand 1500 VRMS at 60 Hz
results from the exceptional long-term stability of the patented Surge Withstand ANSI/IEEE C37.90.1
Digilogic design. Maximum Net Weight 4 lbs., 12 oz. (2.2 kg) 5 lbs., 2 oz. (2.3 kg) 4 lbs., 14 oz. (2.2 kg) 5 lbs., 4 oz. (2.4 kg)
Approximate Dimensions 7.0" W x 3.7" D x 5.6" H 7.2" W x 5.3" D x 5.8" H 7.0" W x 3.7" D x 5.6" H 7.2" W x 5.3" D x 5.8" H
Many Scientific Columbus customers have found that the accuracy (excluding mounting plate) (178 mm x 94 mm x 142 mm) (183 mm x 135 mm x 147 mm) (178 mm x 94 mm x 142 mm) (183 mm x 135 mm x 147 mm)
and stability of our Digilogic Transducers rival or exceed the preci- Style I Case, see page 122 Style V Case, see page 123 Style I Case, see page 122 Style V Case, see page 123
sion of their best laboratory standards. As one Scientific Columbus Overrange with Linearity 500–1000 Watts/Element 500–600 Watts/Element 500–1000 Vars/Element 500–600 Vars/Element
customer stated, “If my standard indicates that one of my Digilogic
No additional error within voltage compliance. Reduce load resistance as required.
Transducers is no longer accurate, I send the standard in for repair!”
* P-Option includes 1–5/1–3–5, 4–20/4–12–20, and 10–50/10–30–50 mAdc outputs. Specifications subject to change without notice.
**Total input not to exceed 200% of standard-calibration watts or vars on units with 0 to ±1 mAdc output.
Total input not to exceed 120% of standard-calibration watts or vars on units with P-Option outputs.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
16 17
SCI Transducer Cat. 1-51(MTD) 16-17 1/9/02, 5:23 PM
SCIENTIFIC
Digilogic AC Watt/Watthour SCIENTIFIC
Specifications
or Var/Varhour Transducers
COLUMBUS COLUMBUS
DIGILOGIC AC WATT/WATTHOUR OR VAR/VARHOUR TRANSDUCERS
Digilogic combined watt/watt-
Digilogic
hour and var/varhour transducers Specifications 0 to ±1 mAdc Watts P-Option* Watts 0 to ±1 mAdc Vars P-Option* Vars
provide high accuracy with two (Watt/Watthour (Watt/Watthour (Var/Varhour (Var/Varhour
Transducer) Transducer) Transducer) Transducer)
simultaneous outputs: an analog
output directly proportional to Current Nominal 5A
Input Range** 0–10 A
instantaneous watts or vars, and a Overload Continuous 20 A
Overload 1 Second/Hour 250 A
digital (pulse) output (Form-C Burden/Element 0.2 VA (maximum) at 5 A
mercury-wetted relay or solid-state) Voltage Nominal 120 V
Input Range** 0–150 V
directly proportional to watthours or Overload Continuous 200 V
varhours. All models are available in Burden/Element 0.02 VA (maximum) at 120 V
either unidirectional or bidirectional configurations. External Input Range 85–135 Vac 100–130 Vac 85–135 Vac 100–130 Vac
Auxiliary Frequency Range 50–500 Hz 50–500 Hz 50–500 Hz 50–500 Hz
Power Burden 3 VA Nominal 6 VA Nominal 3 VA Nominal 6 VA Nominal
Rated Output (RO) = ±1 mAdc for 5, 20, or 50 mAdc for ±1 mAdc for 5, 20, or 50 mAdc for
500 Watts or Vars/Element Standard Calibration Std. Calibration, depending on Standard Calibration Std. Calibration, depending on
selected output range* selected output range*
Features Applications Outputs Accuracy ±(0.09% Reading + 0.005% RO) ±(0.1% Reading + 0.05% RO) ± (0.15% Reading + 0.01% RO) ± (0.15% Reading + 0.05% RO)
at 0–200% RO at 0–120% RO at 0–200% RO at 0–120% RO
±0.005% / ° C ±0.0065% / ° C ±0.009% / ° C ± 0.01% / ° C
◆ Accuracy to 0.1% of reading ◆ Utility billing ◆ 0 to ±1 mAdc Temperature Effect on Accuracy
Operating Temperature Range -20° C to +70° C -20° C to +50° C -20° C to +60° C -20° C to +50° C
◆ Analog & digital outputs ◆ Test laboratories ◆ 1–5 or 1–3–5 mAdc Compliance Voltage 10 Vdc 10 Vdc
See Table 2 on page 14. See Table 2 on page 14.
◆ Exceptional reliability ◆ Process control ◆ 4–20 or 4–12–20 mAdc Load 0–10,000 Ω 0–10,000 Ω
Output Ripple Peak < 0.5% RO < 0.25% RO < 0.5% RO < 0.25% RO
◆ Excellent long-term stability ◆ 10–50 or 10–30–50 mAdc Relay Contact Rating (-60XX option) 15 VA at 1 A (maximum) or 150 Vac/15 Vdc (maximum) with resistive load. Contact protection required for inductive loads.
◆ Wide selection of current & ◆ Relay and solid-state Relay Contact Life (-60XX option) One billion operations when operated within specifications.
voltage input ranges outputs for watthour and Solid-State Output Contact
Rating (-62XX option) 28 Vdc (maximum) VCESAT: 1 Vdc (maximum) at 7 mAdc
varhour functions
Response Time < 400 ms to 99% < 1 Second to 99% < 400 ms to 99% < 1 Second to 99%
Power Factor Any
PF Effect on Accuracy ±0.04% VA (maximum) (Included in Accuracy specification above.)
Standard Calibration Gain ±1% of Reading (minimum) ±10% of Span (minimum) ±1% of Reading (minimum) ±10% of Span (minimum)
Adjustments Zero None Required ± 5% of Zero Point (minimum) None Required ± 5% of Zero Point (minimum)
Frequency Range 58–62 Hz 60 Hz
Stability (per year) ± 0.05% RO, ±0.1% of Span, ±0.1% RO, ±0.2% of Span,
Noncumulative Noncumulative Noncumulative Noncumulative
Digilogic Transducers Used to Calibrate Accuracy Standards Operating Humidity 0–95% Noncondensing
Isolation Complete (Input/Output/Power/Case) All KYZ outputs are isolated.
The Digilogic Transducer is recognized as the premier power-system
parameter-measurement device. A new twist in DL application Dielectric Withstand 1500 VRMS at 60 Hz
results from the exceptional long-term stability of the patented Surge Withstand ANSI/IEEE C37.90.1
Digilogic design. Maximum Net Weight 4 lbs., 12 oz. (2.2 kg) 5 lbs., 2 oz. (2.3 kg) 4 lbs., 14 oz. (2.2 kg) 5 lbs., 4 oz. (2.4 kg)
Approximate Dimensions 7.0" W x 3.7" D x 5.6" H 7.2" W x 5.3" D x 5.8" H 7.0" W x 3.7" D x 5.6" H 7.2" W x 5.3" D x 5.8" H
Many Scientific Columbus customers have found that the accuracy (excluding mounting plate) (178 mm x 94 mm x 142 mm) (183 mm x 135 mm x 147 mm) (178 mm x 94 mm x 142 mm) (183 mm x 135 mm x 147 mm)
and stability of our Digilogic Transducers rival or exceed the preci- Style I Case, see page 122 Style V Case, see page 123 Style I Case, see page 122 Style V Case, see page 123
sion of their best laboratory standards. As one Scientific Columbus Overrange with Linearity 500–1000 Watts/Element 500–600 Watts/Element 500–1000 Vars/Element 500–600 Vars/Element
customer stated, “If my standard indicates that one of my Digilogic
No additional error within voltage compliance. Reduce load resistance as required.
Transducers is no longer accurate, I send the standard in for repair!”
* P-Option includes 1–5/1–3–5, 4–20/4–12–20, and 10–50/10–30–50 mAdc outputs. Specifications subject to change without notice.
**Total input not to exceed 200% of standard-calibration watts or vars on units with 0 to ±1 mAdc output.
Total input not to exceed 120% of standard-calibration watts or vars on units with P-Option outputs.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
16 17
SCI Transducer Cat. 1-51(MTD) 16-17 1/9/02, 5:23 PM
Ordering Procedure Ordering Procedure
Digilogic AC Watt/Watthour Digilogic AC Watt/Watthour
or Var/Varhour Transducers or Var/Varhour Transducers
Digilogic
Auxiliary Pulse Mounting Current Voltage -RS/Freq. Option Option Ext. Aux. A2*** External Auxiliary Power (120 Vac std.) 85-135 Vac 50-500 Hz 3 VA
Base Model No. Output Power Output Orientation Input Input Option #1 #2 #3 Power A4 Internal Auxiliary Power (self-powered) 70-112% of Nominal Aux. Power Voltage Equals Input Frequency 3 VA
(P-Option Units)
Table 1 Table 2 Table 3 Table 4 Table 4 Table 5 Table 5 Table 6 Table 7 Table 7 Table 3
A2*** (leave blank) External Auxiliary Power (120 Vac std.) 100-130 Vac 50-500 Hz 6 VA
A4 Internal Auxiliary Power (self-powered) 84-108% of Nominal Aux. Power Voltage Equals Input Frequency 6 VA
0 to ±1 mAdc
output A2 *** For external auxiliary power voltages other than 120 Vac, specify the voltage in the last position of the complete model number. (Example: 240 Vac Aux.)
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
18 19
SCI Transducer Cat. 1-51(MTD) 18-19 1/9/02, 5:23 PM
Ordering Procedure Ordering Procedure
Digilogic AC Watt/Watthour Digilogic AC Watt/Watthour
or Var/Varhour Transducers or Var/Varhour Transducers
Digilogic
Auxiliary Pulse Mounting Current Voltage -RS/Freq. Option Option Ext. Aux. A2*** External Auxiliary Power (120 Vac std.) 85-135 Vac 50-500 Hz 3 VA
Base Model No. Output Power Output Orientation Input Input Option #1 #2 #3 Power A4 Internal Auxiliary Power (self-powered) 70-112% of Nominal Aux. Power Voltage Equals Input Frequency 3 VA
(P-Option Units)
Table 1 Table 2 Table 3 Table 4 Table 4 Table 5 Table 5 Table 6 Table 7 Table 7 Table 3
A2*** (leave blank) External Auxiliary Power (120 Vac std.) 100-130 Vac 50-500 Hz 6 VA
A4 Internal Auxiliary Power (self-powered) 84-108% of Nominal Aux. Power Voltage Equals Input Frequency 6 VA
0 to ±1 mAdc
output A2 *** For external auxiliary power voltages other than 120 Vac, specify the voltage in the last position of the complete model number. (Example: 240 Vac Aux.)
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
18 19
SCI Transducer Cat. 1-51(MTD) 18-19 1/9/02, 5:23 PM
Wiring Diagrams Wiring Diagrams
Digilogic AC Watt/Watthour Digilogic AC Watt/Watthour
or Var/Varhour Transducers or Var/Varhour Transducers
WIRING DIAGRAMS FOR 0 to ±1 mAdc UNITS (Style I Case) WIRING DIAGRAMS FOR 0 to ±1 mAdc UNITS (Style I Case)
Digilogic
1 Element, Single Phase, 2 Wire 21/2 Element, 3 Phase, 4 Wire, Wye
DC DC DC DC
OUTPUT OUTPUT OUTPUT OUTPUT
- + - + - + - +
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H
LOAD LOAD
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
LOAD LOAD
Omitted on -6070 Models Omitted on -6270 Models Omitted on -6070 Models Omitted on -6270 Models
NOTE: For 1-element units with -8 option, connect current input to terminals 7 (•) & 10.
DC DC
OUTPUT OUTPUT
- + - +
DC DC
OUTPUT OUTPUT
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
- + - +
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H
Adjust A2 Models: Shown. A4 Models: External aux. power not required. Adjust A2 Models: Shown. A4 Models: External aux. power not required.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
20 21
SCI Transducer Cat. 1-51(MTD) 20-21 1/9/02, 5:23 PM
Wiring Diagrams Wiring Diagrams
Digilogic AC Watt/Watthour Digilogic AC Watt/Watthour
or Var/Varhour Transducers or Var/Varhour Transducers
WIRING DIAGRAMS FOR 0 to ±1 mAdc UNITS (Style I Case) WIRING DIAGRAMS FOR 0 to ±1 mAdc UNITS (Style I Case)
Digilogic
1 Element, Single Phase, 2 Wire 21/2 Element, 3 Phase, 4 Wire, Wye
DC DC DC DC
OUTPUT OUTPUT OUTPUT OUTPUT
- + - + - + - +
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H
LOAD LOAD
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
LOAD LOAD
Omitted on -6070 Models Omitted on -6270 Models Omitted on -6070 Models Omitted on -6270 Models
NOTE: For 1-element units with -8 option, connect current input to terminals 7 (•) & 10.
DC DC
OUTPUT OUTPUT
- + - +
DC DC
OUTPUT OUTPUT
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
- + - +
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H
Adjust A2 Models: Shown. A4 Models: External aux. power not required. Adjust A2 Models: Shown. A4 Models: External aux. power not required.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
20 21
SCI Transducer Cat. 1-51(MTD) 20-21 1/9/02, 5:23 PM
Wiring Diagrams Wiring Diagrams
Digilogic AC Watt/Watthour Digilogic AC Watt/Watthour
or Var/Varhour Transducers or Var/Varhour Transducers
WIRING DIAGRAMS FOR P-OPTION UNITS (Style V Case) WIRING DIAGRAMS FOR P-OPTION UNITS (Style V Case)
Digilogic
1 Element, Single Phase, 2 Wire 21/2 Element, 3 Phase, 4 Wire, Wye
DC DC DC
DC
OUTPUT OUTPUT OUTPUT
OUTPUT
- + - + - + - +
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H
LOAD LOAD 7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
LOAD LOAD
Omitted on -6070 Models Omitted on -6270 Models Omitted on -6070 Models Omitted on -6270 Models
NOTE: For 1-element units with -8 option, connect current input to terminals 7 (•) & 10.
DC DC
OUTPUT OUTPUT
- + - +
DC DC
OUTPUT OUTPUT
- + - +
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H
EXTERNAL LOAD EXTERNAL
AUX. POWER LOAD
AUX. POWER
Adjust A2 Models: Shown. A4 Models: External aux. power not required. Adjust A2 Models: Shown. A4 Models: External aux. power not required.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
22 23
SCI Transducer Cat. 1-51(MTD) 22-23 1/9/02, 5:23 PM
Wiring Diagrams Wiring Diagrams
Digilogic AC Watt/Watthour Digilogic AC Watt/Watthour
or Var/Varhour Transducers or Var/Varhour Transducers
WIRING DIAGRAMS FOR P-OPTION UNITS (Style V Case) WIRING DIAGRAMS FOR P-OPTION UNITS (Style V Case)
Digilogic
1 Element, Single Phase, 2 Wire 21/2 Element, 3 Phase, 4 Wire, Wye
DC DC DC
DC
OUTPUT OUTPUT OUTPUT
OUTPUT
- + - + - + - +
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H
LOAD LOAD 7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
LOAD LOAD
Omitted on -6070 Models Omitted on -6270 Models Omitted on -6070 Models Omitted on -6270 Models
NOTE: For 1-element units with -8 option, connect current input to terminals 7 (•) & 10.
DC DC
OUTPUT OUTPUT
- + - +
DC DC
OUTPUT OUTPUT
- + - +
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H
EXTERNAL LOAD EXTERNAL
AUX. POWER LOAD
AUX. POWER
Adjust A2 Models: Shown. A4 Models: External aux. power not required. Adjust A2 Models: Shown. A4 Models: External aux. power not required.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
22 23
SCI Transducer Cat. 1-51(MTD) 22-23 1/9/02, 5:23 PM
SCIENTIFIC
Digilogic AC Volt-Amp or Combined SCIENTIFIC
Specifications
Volt-Amp/Volt-Amphour Transducers
COLUMBUS COLUMBUS
DIGILOGIC AC VOLT-AMP OR COMBINED VOLT-AMP/VOLT-AMPHOUR TRANSDUCERS
Digilogic volt-amp transducers provide a dc output signal
Digilogic
proportional to input volt-amps, using an arithmetic RMS Specifications 0–1 mAdc Volt-Amps P-Option* Volt-Amps
(Volt-Amp or Combined (Volt-Amp or Combined
volt-amp measurement technique. These transducers are Volt-Amp/Volt-Amphour Transducer) Volt-Amp/Volt-Amphour Transducer)
accurate over any range of power factor, are immune to the Current Nominal 5A
effects of distorted wave forms, and are stable over time and Input Range** 0–10 A
Overload Continuous 20 A
in wide extremes of environmental conditions. Overload 1 Second/Hour 250 A
Burden/Element 0.2 VA (maximum) at 5 A
Voltage Nominal 120 V
Digilogic combined volt-amp/volt-amphour transducers Input Range** 0–150 V
provide two simultaneous outputs: an analog output Overload Continuous 200 V
Burden/Element 0.02 VA (maximum) at 120 V
directly proportional to volt-amps and a digital (pulse) External Input Range 85–135 Vac 100–130 Vac
output (Form-C mercury-wetted relay or solid-state) directly Auxiliary Frequency Range 50–500 Hz 50–500 Hz
Power Burden 3 VA Nominal 6 VA Nominal
proportional to volt-amphours.
Rated Output (RO) = 1 mAdc for Standard Calibration 5, 20, or 50 mAdc for Standard Calibration,
500 Volt-Amps/Element depending on selected output range*
Accuracy ±(0.2% Reading + 0.1% RO) ±(0.2% Reading + 0.15% RO)
at 0–200% RO at 0–120% RO
Features Applications Outputs Temperature Effect on Accuracy ± 0.01% / ° C ±0.015% / ° C
Operating Temperature Range -20° C to +70° C -20° C to +50° C
◆ Accuracy to 0.2% of reading ◆ Utility billing ◆ 0–1 mAdc Compliance Voltage 10 Vdc
See Table 2 on page 22.
Load 0–10,000 Ω
◆ Analog & digital outputs ◆ Test laboratories ◆ 1–5 mAdc Output Ripple Peak < 2% RO
◆ Exceptional reliability ◆ Process control ◆ 4–20 mAdc Relay Contact Rating (-6070 option) 15 VA at 1 A (maximum) or 150 Vac/15 Vdc (maximum) with resistive load. Contact protection required for inductive loads.
Relay Contact Life (-6070 option) One billion operations when operated within specifications.
◆ Excellent long-term stability ◆ 10–50 mAdc
Solid-State Output Contact
◆ Wide selection of current & 28 Vdc (maximum) VCESAT: 1 Vdc (maximum) at 7 mAdc
Rating (-6270 option)
◆ Relay and solid-state
voltage input ranges outputs for volt-amphour Response Time < 400 ms to 99% < 1 Second to 99%
function Power Factor Any
PF Effect on Accuracy (Included in Accuracy specification above.)
Standard Calibration Gain ±5% of Reading (minimum) ±20% of Span (minimum)
Adjustments Zero None Required ± 5% of Zero Point (minimum)
Frequency Range 58–62 Hz
Stability (per year) ±0.2% RO, Noncumulative
Operating Humidity 0–95% Noncondensing
Isolation Complete (Input/Output/Power/Case) All KYZ outputs are isolated.
Dielectric Withstand 1500 VRMS at 60 Hz
Surge Withstand ANSI/IEEE C37.90.1
Determining Volt-Amphour Levels in Submetering Applications Maximum Volt-Amp 4 lbs., 8 oz. (2 kg) 5 lbs., 8 oz. (2.5 kg)
Net Weight Volt-Amp/Volt-Amphour 4 lbs., 14 oz. (2.2 kg) 6 lbs. (2.7 kg)
Digilogic Transducers can be employed in submetering applications Approximate Dimensions 7.2" W x 5.3" D x 5.8" H 8.0" W x 7.0" D x 6.0" H
(excluding mounting plate) (183 mm x 135 mm x 147 mm) (203 mm x 178 mm x 152 mm)
to measure the level of volt-amps or volt-amphours. For example, Style V Case, see page 123 Special Case, contact factory for drawing
install a Scientific Columbus Volt-Amp/Volt-Amphour Transducer
Overrange with Linearity 500–1000 Volt-Amps/Element 500–600 Volt-Amps/Element
and a counter to monitor the total system burden consumed by a
specific process within your facility. No additional error within voltage compliance. Reduce load resistance as required.
* P-Option includes 1–5, 4–20, and 10–50 mAdc outputs. Specifications subject to change without notice.
**Total input not to exceed 200% of standard-calibration volt-amps on units with 0–1 mAdc output.
Total input not to exceed 120% of standard-calibration volt-amps on units with P-Option outputs.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
24 25
SCI Transducer Cat. 1-51(MTD) 24-25 1/9/02, 5:23 PM
SCIENTIFIC
Digilogic AC Volt-Amp or Combined SCIENTIFIC
Specifications
Volt-Amp/Volt-Amphour Transducers
COLUMBUS COLUMBUS
DIGILOGIC AC VOLT-AMP OR COMBINED VOLT-AMP/VOLT-AMPHOUR TRANSDUCERS
Digilogic volt-amp transducers provide a dc output signal
Digilogic
proportional to input volt-amps, using an arithmetic RMS Specifications 0–1 mAdc Volt-Amps P-Option* Volt-Amps
(Volt-Amp or Combined (Volt-Amp or Combined
volt-amp measurement technique. These transducers are Volt-Amp/Volt-Amphour Transducer) Volt-Amp/Volt-Amphour Transducer)
accurate over any range of power factor, are immune to the Current Nominal 5A
effects of distorted wave forms, and are stable over time and Input Range** 0–10 A
Overload Continuous 20 A
in wide extremes of environmental conditions. Overload 1 Second/Hour 250 A
Burden/Element 0.2 VA (maximum) at 5 A
Voltage Nominal 120 V
Digilogic combined volt-amp/volt-amphour transducers Input Range** 0–150 V
provide two simultaneous outputs: an analog output Overload Continuous 200 V
Burden/Element 0.02 VA (maximum) at 120 V
directly proportional to volt-amps and a digital (pulse) External Input Range 85–135 Vac 100–130 Vac
output (Form-C mercury-wetted relay or solid-state) directly Auxiliary Frequency Range 50–500 Hz 50–500 Hz
Power Burden 3 VA Nominal 6 VA Nominal
proportional to volt-amphours.
Rated Output (RO) = 1 mAdc for Standard Calibration 5, 20, or 50 mAdc for Standard Calibration,
500 Volt-Amps/Element depending on selected output range*
Accuracy ±(0.2% Reading + 0.1% RO) ±(0.2% Reading + 0.15% RO)
at 0–200% RO at 0–120% RO
Features Applications Outputs Temperature Effect on Accuracy ± 0.01% / ° C ±0.015% / ° C
Operating Temperature Range -20° C to +70° C -20° C to +50° C
◆ Accuracy to 0.2% of reading ◆ Utility billing ◆ 0–1 mAdc Compliance Voltage 10 Vdc
See Table 2 on page 22.
Load 0–10,000 Ω
◆ Analog & digital outputs ◆ Test laboratories ◆ 1–5 mAdc Output Ripple Peak < 2% RO
◆ Exceptional reliability ◆ Process control ◆ 4–20 mAdc Relay Contact Rating (-6070 option) 15 VA at 1 A (maximum) or 150 Vac/15 Vdc (maximum) with resistive load. Contact protection required for inductive loads.
Relay Contact Life (-6070 option) One billion operations when operated within specifications.
◆ Excellent long-term stability ◆ 10–50 mAdc
Solid-State Output Contact
◆ Wide selection of current & 28 Vdc (maximum) VCESAT: 1 Vdc (maximum) at 7 mAdc
Rating (-6270 option)
◆ Relay and solid-state
voltage input ranges outputs for volt-amphour Response Time < 400 ms to 99% < 1 Second to 99%
function Power Factor Any
PF Effect on Accuracy (Included in Accuracy specification above.)
Standard Calibration Gain ±5% of Reading (minimum) ±20% of Span (minimum)
Adjustments Zero None Required ± 5% of Zero Point (minimum)
Frequency Range 58–62 Hz
Stability (per year) ±0.2% RO, Noncumulative
Operating Humidity 0–95% Noncondensing
Isolation Complete (Input/Output/Power/Case) All KYZ outputs are isolated.
Dielectric Withstand 1500 VRMS at 60 Hz
Surge Withstand ANSI/IEEE C37.90.1
Determining Volt-Amphour Levels in Submetering Applications Maximum Volt-Amp 4 lbs., 8 oz. (2 kg) 5 lbs., 8 oz. (2.5 kg)
Net Weight Volt-Amp/Volt-Amphour 4 lbs., 14 oz. (2.2 kg) 6 lbs. (2.7 kg)
Digilogic Transducers can be employed in submetering applications Approximate Dimensions 7.2" W x 5.3" D x 5.8" H 8.0" W x 7.0" D x 6.0" H
(excluding mounting plate) (183 mm x 135 mm x 147 mm) (203 mm x 178 mm x 152 mm)
to measure the level of volt-amps or volt-amphours. For example, Style V Case, see page 123 Special Case, contact factory for drawing
install a Scientific Columbus Volt-Amp/Volt-Amphour Transducer
Overrange with Linearity 500–1000 Volt-Amps/Element 500–600 Volt-Amps/Element
and a counter to monitor the total system burden consumed by a
specific process within your facility. No additional error within voltage compliance. Reduce load resistance as required.
* P-Option includes 1–5, 4–20, and 10–50 mAdc outputs. Specifications subject to change without notice.
**Total input not to exceed 200% of standard-calibration volt-amps on units with 0–1 mAdc output.
Total input not to exceed 120% of standard-calibration volt-amps on units with P-Option outputs.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
24 25
SCI Transducer Cat. 1-51(MTD) 24-25 1/9/02, 5:23 PM
Ordering Procedure Ordering Procedure
Digilogic AC Volt-Amp or Combined Digilogic AC Volt-Amp or Combined
Volt-Amp/Volt-Amphour Transducers Volt-Amp/Volt-Amphour Transducers
Digilogic
Auxiliary Pulse Mounting Current Voltage -RS/Freq. Option Option Ext. Aux. A2** External Auxiliary Power (120 Vac std.) 85-135 Vac 50-500 Hz 3 VA
Base Model No. Output Power Output Orientation Input Input Option #2 #3 Power A4 Internal Auxiliary Power (self-powered) 70-112% of Nominal Aux. Power Voltage Equals Input Frequency 3 VA
Table 1 Table 2 Table 3 Table 4 Table 4 Table 5 Table 5 Table 6 Table 7 Table 7 Table 3 (P-Option Units)
A2** (leave blank) External Auxiliary Power (120 Vac std.) 100-130 Vac 50-500 Hz 6 VA
A4 Internal Auxiliary Power (self-powered) 84-108% of Nominal Aux. Power Voltage Equals Input Frequency 6 VA
0-1 mAdc ** For external auxiliary power voltages other than 120 Vac, you must specify the voltage in the last position of the complete model number. (Example: 240 Vac)
output A2
DC external auxiliary power available; see Special Options on page 128.
DLVA31K521/2 -6070 -V -5 -1 -RS -SM -SC Table 4 Pulse Output Selection
Option Description CPH Range*** Mounting Orientation****
P-Option Specify Specify Specify -6070 Form-C Mercury-Wetted Relay, Unidirectional 2-14,000 -V (Vertical) or -H (Horizontal)
outputs PAN7 A4 Standard cph is one
counts output input -6270 Form-C Solid-State, Unidirectional 2-900,000 Not Applicable
count/volt-amphour.
per hour voltage value
*** You must specify the desired counts per hour. This information is not part of the model number, but must be provided to the factory when you place your order.
If A2 is selected, leave this space blank; specify If other than 120 Vac (std.), specify ext. aux.
ext. aux. power voltage at end of model no. power voltage: 69 Vac, 240 Vac, 277 Vac, or 480 Vac **** You must specify the desired mounting orientation for units with mercury-wetted relays.
Table 5 Input Selection
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
26 27
SCI Transducer Cat. 1-51(MTD) 26-27 1/9/02, 5:24 PM
Ordering Procedure Ordering Procedure
Digilogic AC Volt-Amp or Combined Digilogic AC Volt-Amp or Combined
Volt-Amp/Volt-Amphour Transducers Volt-Amp/Volt-Amphour Transducers
Digilogic
Auxiliary Pulse Mounting Current Voltage -RS/Freq. Option Option Ext. Aux. A2** External Auxiliary Power (120 Vac std.) 85-135 Vac 50-500 Hz 3 VA
Base Model No. Output Power Output Orientation Input Input Option #2 #3 Power A4 Internal Auxiliary Power (self-powered) 70-112% of Nominal Aux. Power Voltage Equals Input Frequency 3 VA
Table 1 Table 2 Table 3 Table 4 Table 4 Table 5 Table 5 Table 6 Table 7 Table 7 Table 3 (P-Option Units)
A2** (leave blank) External Auxiliary Power (120 Vac std.) 100-130 Vac 50-500 Hz 6 VA
A4 Internal Auxiliary Power (self-powered) 84-108% of Nominal Aux. Power Voltage Equals Input Frequency 6 VA
0-1 mAdc ** For external auxiliary power voltages other than 120 Vac, you must specify the voltage in the last position of the complete model number. (Example: 240 Vac)
output A2
DC external auxiliary power available; see Special Options on page 128.
DLVA31K521/2 -6070 -V -5 -1 -RS -SM -SC Table 4 Pulse Output Selection
Option Description CPH Range*** Mounting Orientation****
P-Option Specify Specify Specify -6070 Form-C Mercury-Wetted Relay, Unidirectional 2-14,000 -V (Vertical) or -H (Horizontal)
outputs PAN7 A4 Standard cph is one
counts output input -6270 Form-C Solid-State, Unidirectional 2-900,000 Not Applicable
count/volt-amphour.
per hour voltage value
*** You must specify the desired counts per hour. This information is not part of the model number, but must be provided to the factory when you place your order.
If A2 is selected, leave this space blank; specify If other than 120 Vac (std.), specify ext. aux.
ext. aux. power voltage at end of model no. power voltage: 69 Vac, 240 Vac, 277 Vac, or 480 Vac **** You must specify the desired mounting orientation for units with mercury-wetted relays.
Table 5 Input Selection
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
26 27
SCI Transducer Cat. 1-51(MTD) 26-27 1/9/02, 5:24 PM
Wiring Diagrams Wiring Diagrams
Digilogic AC Volt-Amp or Combined Digilogic AC Volt-Amp or Combined
Volt-Amp/Volt-Amphour Transducers Volt-Amp/Volt-Amphour Transducers
WIRING DIAGRAMS FOR 0-1 mAdc UNITS (Style V Case) AND P-OPTION UNITS (Special Case) WIRING DIAGRAMS FOR 0-1 mAdc UNITS (Style V Case) AND P-OPTION UNITS (Special Case)
Digilogic
21/2 Element, 3 Phase, 4 Wire, Wye
-6070 Models -6270 Models
L1
LINE
L2 L1
LINE
L2
-6070 Models -6270 Models
LINE
LINE
L1 L2 L3 N
L1 L2 L3 N
DC DC
OUTPUT OUTPUT
DC
- + - + DC
OUTPUT OUTPUT
- + - +
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H
LOAD LOAD
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H
DC DC
OUTPUT OUTPUT
- + - +
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H
LOAD LOAD
LOAD LOAD
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
28 29
SCI Transducer Cat. 1-51(MTD) 28-29 1/9/02, 5:24 PM
Wiring Diagrams Wiring Diagrams
Digilogic AC Volt-Amp or Combined Digilogic AC Volt-Amp or Combined
Volt-Amp/Volt-Amphour Transducers Volt-Amp/Volt-Amphour Transducers
WIRING DIAGRAMS FOR 0-1 mAdc UNITS (Style V Case) AND P-OPTION UNITS (Special Case) WIRING DIAGRAMS FOR 0-1 mAdc UNITS (Style V Case) AND P-OPTION UNITS (Special Case)
Digilogic
21/2 Element, 3 Phase, 4 Wire, Wye
-6070 Models -6270 Models
L1
LINE
L2 L1
LINE
L2
-6070 Models -6270 Models
LINE
LINE
L1 L2 L3 N
L1 L2 L3 N
DC DC
OUTPUT OUTPUT
DC
- + - + DC
OUTPUT OUTPUT
- + - +
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H
LOAD LOAD
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H
DC DC
OUTPUT OUTPUT
- + - +
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H
LOAD LOAD
LOAD LOAD
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
28 29
SCI Transducer Cat. 1-51(MTD) 28-29 1/9/02, 5:24 PM
DM-10 DEMAND MANAGER SCIENTIFIC
SCIENTIFIC
Exceltronic AC Current
or Voltage Transducers
COLUMBUS
COLUMBUS
EFFECTIVELY ELIMINATE
EXCESS DEMAND CHARGES!
Imput Signals Exceltronic current and voltage transducers
All signals are optically isolated, 120 Vac norminal are available as either average-sensing
(90-140 V). devices calibrated to indicate RMS, or as
true-RMS devices. The average-sensing transduc-
Output Signal
ers are offered as single units or triple units which
All pulse outputs are by (Form-A) relay contacts rated at
2A ac or dc, 200W. Relay operation is synchronized to the combine three individual measurements in one
ac line zero crossing to maximize contact life. compact enclosure. Average-sensing voltage
transducers also are available as
Exceltronic
Demand expanded-scale voltage transducers.
Maximum capacity of 1999 counts. The current demand
interval is user-selectable at 15, 30 or 60 minutes. Storage
is provided for 3500 sequential demand intervals providing The Exceltronic current and voltage transducers provide a dc output signal proportional to input amps or volts.
36 days of storage at 15 minute intervals. Each interval is The dc output is a filtered, true current of 0–1, 1–5, 4–20, or 10–50 mAdc.
Maximum value in power consuption means staying within time-stamped.
your contractual demand limits. Once you exceed that limit,
the costs start adding up. The Scientific Columbus DM-10 Demand Count Inputs
Demand Manager accumulates pulses which allows it to One set of KYZ inputs (Form-C). Each toggle of the input
predict the demand level obtainable by the end of a demand will increment the demand register. Features Applications Outputs
interval. It also calculates and displays the level of demand Cumulative Consuption
to be shed to stay below a contractual level. The cumulative total of all input counts is maintained. ◆ Accuracy to 0.15% of reading ◆ Substation monitoring ◆ 0–1 mAdc
Register counts to 99,999,999 and then rolls over to zero. ◆ Exceptional reliability ◆ SCADA ◆ 1–5 mAdc
The DM-10 measures and stores customer demand by using
Display and Keypad ◆ Excellent long-term stability ◆ Distribution circuit monitoring ◆ 4–20 mAdc
the watthour KYZ pulses from an existing utility billing
The display and keypad are used to view all stored and ◆ Average-sensing or true-RMS ◆ Process control ◆ 10–50 mAdc
meter. The Demand Manager provides flexibility by featur- operational values, set all controllable parameters, and measurement available
ing two user-defined alarm set points. The low set point indicate any detected error conditions.
(threshold) allows for internal control and monitoring of a ◆ Expanded-scale voltage
Keypad models available
desired demand level. The high threshold is set at the
utility’s contractual peak point. Four sealed-membrane keys provide all data entry and ◆ Most popular models are
control by intuitive selection and scaling techniques. UL Recognized
The DM-10 Demand Manager features a serial RS-232 Serial Output
communication port for data retrieval. Connecting a por- Provides comma-delimited CSV data for downloading to
table printer to this port allows the user to obtain demand a spreadsheet. The serial port is the master and utilizes
interval information. In addition, the port can be connected X-on/X-off data-stream control. Baud rate is selectable Also available in XLP modular, plug-in format for limited-
from 300-4800 bps. Normal operation provides all current space applications requiring large numbers of transducers.
to a PC-compatible computer to download demand history parameters and all demand intervals since the last download.
in comma-delimited format for easy spreadsheet analysis.
◆ Up to six transducers in one module
Auxiliary Power
90-140 Vac, 50 or 60 Hz, less than 1 A. ◆ Two, four, or eight modules in one enclosure
◆ Easy to install, expand, or repair
Internal Battery
◆ Convenient front-panel access for calibration and output-
User-replaceable battery provides memory backup and
current jacks available
clock operation for up to eight accumulated months of
Headquarters power outage. Minimum life is 10 years without power See pages 77–94 for more information.
50 Fordham Road
CER
255 North Union Street outage. Battery condition is monitored and displayed.
Wilmington, MA 01887 Rochester, NY 14605
TIFIE
Tel: 978-988-4101 D
Tel: 585-263-7700 Time-of-Use
Fax: 978-988-4179 Fax: 585-454-7805 The DM-10 features one time-of-use setting for operation
E-Mail: power.industrial@ametek.com E-Mail: info@rochester.com during peak hours. AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
30 31
SCI Transducer Cat. 1-51(MTD) 30-31 1/9/02, 5:24 PM
DM-10 DEMAND MANAGER SCIENTIFIC
SCIENTIFIC
Exceltronic AC Current
or Voltage Transducers
COLUMBUS
COLUMBUS
EFFECTIVELY ELIMINATE
EXCESS DEMAND CHARGES!
Imput Signals Exceltronic current and voltage transducers
All signals are optically isolated, 120 Vac norminal are available as either average-sensing
(90-140 V). devices calibrated to indicate RMS, or as
true-RMS devices. The average-sensing transduc-
Output Signal
ers are offered as single units or triple units which
All pulse outputs are by (Form-A) relay contacts rated at
2A ac or dc, 200W. Relay operation is synchronized to the combine three individual measurements in one
ac line zero crossing to maximize contact life. compact enclosure. Average-sensing voltage
transducers also are available as
Exceltronic
Demand expanded-scale voltage transducers.
Maximum capacity of 1999 counts. The current demand
interval is user-selectable at 15, 30 or 60 minutes. Storage
is provided for 3500 sequential demand intervals providing The Exceltronic current and voltage transducers provide a dc output signal proportional to input amps or volts.
36 days of storage at 15 minute intervals. Each interval is The dc output is a filtered, true current of 0–1, 1–5, 4–20, or 10–50 mAdc.
Maximum value in power consuption means staying within time-stamped.
your contractual demand limits. Once you exceed that limit,
the costs start adding up. The Scientific Columbus DM-10 Demand Count Inputs
Demand Manager accumulates pulses which allows it to One set of KYZ inputs (Form-C). Each toggle of the input
predict the demand level obtainable by the end of a demand will increment the demand register. Features Applications Outputs
interval. It also calculates and displays the level of demand Cumulative Consuption
to be shed to stay below a contractual level. The cumulative total of all input counts is maintained. ◆ Accuracy to 0.15% of reading ◆ Substation monitoring ◆ 0–1 mAdc
Register counts to 99,999,999 and then rolls over to zero. ◆ Exceptional reliability ◆ SCADA ◆ 1–5 mAdc
The DM-10 measures and stores customer demand by using
Display and Keypad ◆ Excellent long-term stability ◆ Distribution circuit monitoring ◆ 4–20 mAdc
the watthour KYZ pulses from an existing utility billing
The display and keypad are used to view all stored and ◆ Average-sensing or true-RMS ◆ Process control ◆ 10–50 mAdc
meter. The Demand Manager provides flexibility by featur- operational values, set all controllable parameters, and measurement available
ing two user-defined alarm set points. The low set point indicate any detected error conditions.
(threshold) allows for internal control and monitoring of a ◆ Expanded-scale voltage
Keypad models available
desired demand level. The high threshold is set at the
utility’s contractual peak point. Four sealed-membrane keys provide all data entry and ◆ Most popular models are
control by intuitive selection and scaling techniques. UL Recognized
The DM-10 Demand Manager features a serial RS-232 Serial Output
communication port for data retrieval. Connecting a por- Provides comma-delimited CSV data for downloading to
table printer to this port allows the user to obtain demand a spreadsheet. The serial port is the master and utilizes
interval information. In addition, the port can be connected X-on/X-off data-stream control. Baud rate is selectable Also available in XLP modular, plug-in format for limited-
from 300-4800 bps. Normal operation provides all current space applications requiring large numbers of transducers.
to a PC-compatible computer to download demand history parameters and all demand intervals since the last download.
in comma-delimited format for easy spreadsheet analysis.
◆ Up to six transducers in one module
Auxiliary Power
90-140 Vac, 50 or 60 Hz, less than 1 A. ◆ Two, four, or eight modules in one enclosure
◆ Easy to install, expand, or repair
Internal Battery
◆ Convenient front-panel access for calibration and output-
User-replaceable battery provides memory backup and
current jacks available
clock operation for up to eight accumulated months of
Headquarters power outage. Minimum life is 10 years without power See pages 77–94 for more information.
50 Fordham Road
CER
255 North Union Street outage. Battery condition is monitored and displayed.
Wilmington, MA 01887 Rochester, NY 14605
TIFIE
Tel: 978-988-4101 D
Tel: 585-263-7700 Time-of-Use
Fax: 978-988-4179 Fax: 585-454-7805 The DM-10 features one time-of-use setting for operation
E-Mail: power.industrial@ametek.com E-Mail: info@rochester.com during peak hours. AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
30 31
SCI Transducer Cat. 1-51(MTD) 30-31 1/9/02, 5:24 PM
Specifications Specifications
Exceltronic AC Average-Sensing Exceltronic AC True-RMS
Current or Voltage Transducers Current or Voltage Transducers
Specifications 0–1 mAdc Amps P-Option* Amps 0–1 mAdc Volts P-Option* Volts Specifications 0–1 mAdc Amps P-Option* Amps 0–1 mAdc Volts P-Option* Volts
(Current Transducer) (Current Transducer) (Voltage Transducer) (Voltage Transducer) (Current Transducer) (Current Transducer) (Voltage Transducer) (Voltage Transducer)
Current Nominal 5A 5A Current Nominal 5A
Input Calibrating Range 0–5 A 0–5 A Input Calibrating Range 0–5 A
Range with Linearity 0–10 A 0–6 A N/A N/A Range with Linearity 0.25–6 A** N/A
Overload Continuous 20 A 20 A Overload Continuous 15 A
Overload 1 Second/Hour 250 A 250 A Overload 1 Second/Hour 250 A
Burden/Element 0.25 VA (maximum) at 5 A 0.25 VA (maximum) at 5 A Burden/Element 0.2 VA (maximum) at 5 A
Voltage Nominal 120 V 120 V Voltage Nominal 120 V
Input Calibrating Range 0–150 V 0–150 V Input Calibrating Range 0–150 V
Range with Linearity N/A N/A 0–150 V 0–165 V Range with Linearity N/A 7.5–150 V***
Overload Continuous 180 V 180 V Overload Continuous 180 V
Exceltronic
Burden/Element 2.2 VA (maximum) at 120 V 2.2 VA (maximum) at 120 V Burden/Element 0.035 VA (maximum) at 120 V
External Input Range 100–130 Vac 100–130 Vac External Input Range 85–135 Vac 100–135 Vac 85–135 Vac 100–130 Vac
Auxiliary Frequency Range None Required 50–500 Hz None Required 50–500 Hz Auxiliary Frequency Range 50–500 Hz 50–500 Hz 50–500 Hz 50–500 Hz
Power Burden/Element 3 VA Nominal 3 VA Nominal Power Burden/Element 2 VA Nominal 5 VA Nominal 2 VA Nominal 5 VA Nominal
Rated Output (RO) = 1 mAdc for 5, 20, or 50 mAdc for 1 mAdc for 5, 20, or 50 mAdc for Rated Output (RO) = 1 mAdc for 5, 20, or 50 mAdc for 1 mAdc for 5, 20, or 50 mAdc for
5 A or 150 V/Element Standard Calibration Std. Calibration, depending on Standard Calibration Std. Calibration, depending on 5 A or 150 V/Element Standard Calibration Std. Calibration, depending on Standard Calibration Std. Calibration, depending on
selected output range* selected output range* selected output range* selected output range*
Accuracy Standard ±(0.15% Reading + 0.1% RO) ±(0.15% Reading + 0.1% RO) Accuracy ±(0.15% Reading + 0.1% RO) ± 0.5% of Span ±(0.15% Reading + 0.1% RO) ± 0.5% of Span
± 0.5% of Span ± 0.5% of Span
A4 Models ±(0.1% Reading + 0.05% RO) ±(0.1% Reading + 0.05% RO)
Temperature Effect on Accuracy ± 0.01% / ° C ± 0.025% / ° C ±0.01% / ° C ±0.025% / ° C
Temperature Effect on Accuracy ±0.01% / ° C ±0.025% / ° C ± 0.01% / ° C ± 0.025% / ° C
Operating Temperature Range -20° C to +60° C 0° C to +50° C -20° C to +60° C 0° C to +50° C
Operating Temperature Range -20° C to +60° C -20° C to +50° C -20° C to +60° C -20° C to +50° C
Compliance Voltage 10 Vdc 10 Vdc
Compliance Voltage 10 Vdc 10 Vdc See Table 2 on page 30. See Table 2 on page 30.
See Table 2 on page 30. See Table 2 on page 30. Load 0–10,000 Ω 0–10,000 Ω
Load 0–10,000 Ω 0–10,000 Ω
Output Ripple Peak < 1% RO ≤ 1% of Span < 1% RO ≤ 1% of Span
Output Ripple Peak < 0.25% RO < 0.1% of Span < 0.25% RO < 0.1% of Span
Response Time < 600 ms to 99% < 2 Seconds to 99% < 600 ms to 99% < 2 Seconds to 99%
Response Time < 400 ms to 99% < 1 Second to 99% < 400 ms to 99% < 1 Second to 99%
Standard Calibration Gain ± 5% of Reading (minimum) ±20% of Span (minimum) ± 5% of Reading (minimum) ±20% of Span (minimum)
Standard Calibration Gain ±10% of Reading (minimum) ±20% of Span (minimum) ±10% of Reading (minimum) ±20% of Span (minimum) Adjustments Zero ±0.1% of RO ±5% of Zero Point (minimum) ±0.1% of RO ±5% of Zero Point (minimum)
Adjustments Zero None Required ±5% of Zero Point (minimum) None Required ±5% of Zero Point (minimum)
Frequency Range 55–65 Hz (fundamental and through ninth harmonic) (specify nominal)
Frequency Range 50–500 Hz (specify nominal)
Crest Factor 2 :1 (maximum)
Stability (per year) ±0.1% RO, ±0.15% of Span, ±0.25% RO, ±0.3% of Span,
Noncumulative Noncumulative Noncumulative Noncumulative Stability (per year) ±0.1% RO, ±0.15% of Span, ± 0.1% RO, ±0.15% of Span,
Noncumulative Noncumulative Noncumulative Noncumulative
Operating Humidity 0–95% Noncondensing
Operating Humidity 0–95% Noncondensing
Isolation Complete Complete Complete Complete
(Input/Output/Case) (Input/Output/Power/Case) (Input/Output/Case) (Input/Output/Power/Case) Isolation Complete (Input/Output/Power/Case)
Maximum Single 13 oz. (0.4 kg) 2 lbs., 11 oz. (1.2 kg) 13 oz. (0.4 kg) 2 lbs., 11 oz. (1.2 kg) Maximum Net Weight 2 lbs., 1 oz. (0.9 kg) 3 lbs., 8 oz. (1.6 kg) 2 lbs., 1 oz. (0.9 kg) 3 lbs., 8 oz. (1.6 kg)
Net Weight Triple 1 lb., 13 oz. (0.8 kg) 3 lbs., 14 oz. (1.8 kg) 1 lb., 13 oz. (0.8 kg) 3 lbs., 14 oz. (1.8 kg) Approximate Dimensions 4.4" W x 3.9" D x 4.7" H 7.0" W x 3.7" D x 5.6" H 4.4" W x 3.9" D x 4.7" H 7.0" W x 3.7" D x 5.6" H
Approximate Single 3.3" W x 2.1" D x 4.1" H 7.0" W x 3.7" D x 5.6" H 3.3" W x 2.1" D x 4.1" H 7.0" W x 3.7" D x 5.6" H (excluding mounting plate) (112 mm x 99 mm x 119 mm) (178 mm x 94 mm x 142 mm) (112 mm x 99 mm x 119 mm) (178 mm x 94 mm x 142 mm)
Dimensions (84 mm x 53 mm x 104 mm) (178 mm x 94 mm x 142 mm) (84 mm x 53 mm x 104 mm) (178 mm x 94 mm x 142 mm) Style II Case, see page 122 Style I Case, see page 122 Style II Case, see page 122 Style I Case, see page 122
(excluding Style III Case, see page 122 Style I Case, see page 122 Style III Case, see page 122 Style I Case, see page 122 * P-Option includes 1–5, 4–20, and 10–50 mAdc outputs. Specifications subject to change without notice.
mounting plate) ** Operates at reduced accuracy from 0–0.25 Aac.
Triple 4.4" W x 3.9" D x 4.7" H 7.2" W x 5.3" D x 5.8" H 4.4" W x 3.9" D x 4.7" H 7.2" W x 5.3" D x 5.8" H ***Operates at reduced accuracy from 0–7.5 Vac.
(112 mm x 99 mm x 119 mm) (183 mm x 135 mm x 147 mm) (112 mm x 99 mm x 119 mm) (183 mm x 135 mm x 147 mm)
Style II Case, see page 122 Style V Case, see page 123 Style II Case, see page 122 Style V Case, see page 123
* P-Option includes 1–5, 4–20, and 10–50 mAdc outputs. Specifications subject to change without notice.
**Dielectric levels as indicated for UL Recognized models; levels may vary on non-UL Recognized models.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
32 33
SCI Transducer Cat. 1-51(MTD) 32-33 1/9/02, 5:24 PM
Specifications Specifications
Exceltronic AC Average-Sensing Exceltronic AC True-RMS
Current or Voltage Transducers Current or Voltage Transducers
Specifications 0–1 mAdc Amps P-Option* Amps 0–1 mAdc Volts P-Option* Volts Specifications 0–1 mAdc Amps P-Option* Amps 0–1 mAdc Volts P-Option* Volts
(Current Transducer) (Current Transducer) (Voltage Transducer) (Voltage Transducer) (Current Transducer) (Current Transducer) (Voltage Transducer) (Voltage Transducer)
Current Nominal 5A 5A Current Nominal 5A
Input Calibrating Range 0–5 A 0–5 A Input Calibrating Range 0–5 A
Range with Linearity 0–10 A 0–6 A N/A N/A Range with Linearity 0.25–6 A** N/A
Overload Continuous 20 A 20 A Overload Continuous 15 A
Overload 1 Second/Hour 250 A 250 A Overload 1 Second/Hour 250 A
Burden/Element 0.25 VA (maximum) at 5 A 0.25 VA (maximum) at 5 A Burden/Element 0.2 VA (maximum) at 5 A
Voltage Nominal 120 V 120 V Voltage Nominal 120 V
Input Calibrating Range 0–150 V 0–150 V Input Calibrating Range 0–150 V
Range with Linearity N/A N/A 0–150 V 0–165 V Range with Linearity N/A 7.5–150 V***
Overload Continuous 180 V 180 V Overload Continuous 180 V
Exceltronic
Burden/Element 2.2 VA (maximum) at 120 V 2.2 VA (maximum) at 120 V Burden/Element 0.035 VA (maximum) at 120 V
External Input Range 100–130 Vac 100–130 Vac External Input Range 85–135 Vac 100–135 Vac 85–135 Vac 100–130 Vac
Auxiliary Frequency Range None Required 50–500 Hz None Required 50–500 Hz Auxiliary Frequency Range 50–500 Hz 50–500 Hz 50–500 Hz 50–500 Hz
Power Burden/Element 3 VA Nominal 3 VA Nominal Power Burden/Element 2 VA Nominal 5 VA Nominal 2 VA Nominal 5 VA Nominal
Rated Output (RO) = 1 mAdc for 5, 20, or 50 mAdc for 1 mAdc for 5, 20, or 50 mAdc for Rated Output (RO) = 1 mAdc for 5, 20, or 50 mAdc for 1 mAdc for 5, 20, or 50 mAdc for
5 A or 150 V/Element Standard Calibration Std. Calibration, depending on Standard Calibration Std. Calibration, depending on 5 A or 150 V/Element Standard Calibration Std. Calibration, depending on Standard Calibration Std. Calibration, depending on
selected output range* selected output range* selected output range* selected output range*
Accuracy Standard ±(0.15% Reading + 0.1% RO) ±(0.15% Reading + 0.1% RO) Accuracy ±(0.15% Reading + 0.1% RO) ± 0.5% of Span ±(0.15% Reading + 0.1% RO) ± 0.5% of Span
± 0.5% of Span ± 0.5% of Span
A4 Models ±(0.1% Reading + 0.05% RO) ±(0.1% Reading + 0.05% RO)
Temperature Effect on Accuracy ± 0.01% / ° C ± 0.025% / ° C ±0.01% / ° C ±0.025% / ° C
Temperature Effect on Accuracy ±0.01% / ° C ±0.025% / ° C ± 0.01% / ° C ± 0.025% / ° C
Operating Temperature Range -20° C to +60° C 0° C to +50° C -20° C to +60° C 0° C to +50° C
Operating Temperature Range -20° C to +60° C -20° C to +50° C -20° C to +60° C -20° C to +50° C
Compliance Voltage 10 Vdc 10 Vdc
Compliance Voltage 10 Vdc 10 Vdc See Table 2 on page 30. See Table 2 on page 30.
See Table 2 on page 30. See Table 2 on page 30. Load 0–10,000 Ω 0–10,000 Ω
Load 0–10,000 Ω 0–10,000 Ω
Output Ripple Peak < 1% RO ≤ 1% of Span < 1% RO ≤ 1% of Span
Output Ripple Peak < 0.25% RO < 0.1% of Span < 0.25% RO < 0.1% of Span
Response Time < 600 ms to 99% < 2 Seconds to 99% < 600 ms to 99% < 2 Seconds to 99%
Response Time < 400 ms to 99% < 1 Second to 99% < 400 ms to 99% < 1 Second to 99%
Standard Calibration Gain ± 5% of Reading (minimum) ±20% of Span (minimum) ± 5% of Reading (minimum) ±20% of Span (minimum)
Standard Calibration Gain ±10% of Reading (minimum) ±20% of Span (minimum) ±10% of Reading (minimum) ±20% of Span (minimum) Adjustments Zero ±0.1% of RO ±5% of Zero Point (minimum) ±0.1% of RO ±5% of Zero Point (minimum)
Adjustments Zero None Required ±5% of Zero Point (minimum) None Required ±5% of Zero Point (minimum)
Frequency Range 55–65 Hz (fundamental and through ninth harmonic) (specify nominal)
Frequency Range 50–500 Hz (specify nominal)
Crest Factor 2 :1 (maximum)
Stability (per year) ±0.1% RO, ±0.15% of Span, ±0.25% RO, ±0.3% of Span,
Noncumulative Noncumulative Noncumulative Noncumulative Stability (per year) ±0.1% RO, ±0.15% of Span, ± 0.1% RO, ±0.15% of Span,
Noncumulative Noncumulative Noncumulative Noncumulative
Operating Humidity 0–95% Noncondensing
Operating Humidity 0–95% Noncondensing
Isolation Complete Complete Complete Complete
(Input/Output/Case) (Input/Output/Power/Case) (Input/Output/Case) (Input/Output/Power/Case) Isolation Complete (Input/Output/Power/Case)
Maximum Single 13 oz. (0.4 kg) 2 lbs., 11 oz. (1.2 kg) 13 oz. (0.4 kg) 2 lbs., 11 oz. (1.2 kg) Maximum Net Weight 2 lbs., 1 oz. (0.9 kg) 3 lbs., 8 oz. (1.6 kg) 2 lbs., 1 oz. (0.9 kg) 3 lbs., 8 oz. (1.6 kg)
Net Weight Triple 1 lb., 13 oz. (0.8 kg) 3 lbs., 14 oz. (1.8 kg) 1 lb., 13 oz. (0.8 kg) 3 lbs., 14 oz. (1.8 kg) Approximate Dimensions 4.4" W x 3.9" D x 4.7" H 7.0" W x 3.7" D x 5.6" H 4.4" W x 3.9" D x 4.7" H 7.0" W x 3.7" D x 5.6" H
Approximate Single 3.3" W x 2.1" D x 4.1" H 7.0" W x 3.7" D x 5.6" H 3.3" W x 2.1" D x 4.1" H 7.0" W x 3.7" D x 5.6" H (excluding mounting plate) (112 mm x 99 mm x 119 mm) (178 mm x 94 mm x 142 mm) (112 mm x 99 mm x 119 mm) (178 mm x 94 mm x 142 mm)
Dimensions (84 mm x 53 mm x 104 mm) (178 mm x 94 mm x 142 mm) (84 mm x 53 mm x 104 mm) (178 mm x 94 mm x 142 mm) Style II Case, see page 122 Style I Case, see page 122 Style II Case, see page 122 Style I Case, see page 122
(excluding Style III Case, see page 122 Style I Case, see page 122 Style III Case, see page 122 Style I Case, see page 122 * P-Option includes 1–5, 4–20, and 10–50 mAdc outputs. Specifications subject to change without notice.
mounting plate) ** Operates at reduced accuracy from 0–0.25 Aac.
Triple 4.4" W x 3.9" D x 4.7" H 7.2" W x 5.3" D x 5.8" H 4.4" W x 3.9" D x 4.7" H 7.2" W x 5.3" D x 5.8" H ***Operates at reduced accuracy from 0–7.5 Vac.
(112 mm x 99 mm x 119 mm) (183 mm x 135 mm x 147 mm) (112 mm x 99 mm x 119 mm) (183 mm x 135 mm x 147 mm)
Style II Case, see page 122 Style V Case, see page 123 Style II Case, see page 122 Style V Case, see page 123
* P-Option includes 1–5, 4–20, and 10–50 mAdc outputs. Specifications subject to change without notice.
**Dielectric levels as indicated for UL Recognized models; levels may vary on non-UL Recognized models.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
32 33
SCI Transducer Cat. 1-51(MTD) 32-33 1/9/02, 5:24 PM
Ordering Procedure Ordering Procedure
Exceltronic AC Average-Sensing & Exceltronic AC Average-Sensing &
True-RMS Current or Voltage Transducers True-RMS Current or Voltage Transducers
Specify by base model number and appropriate selection or option suffixes in the order shown in the following example. Option Description Input Range Frequency Range Burden
(0-1 mAdc Units)
Auxiliary Current or -RS/Freq. Option Option Ext. Aux. None required for average-sensing units.
Base Model No. Output Power Voltage Input Option #1 #2 #3 Power A2** (leave blank) External Auxiliary Power (120 Vac std.) 85-135 Vac 50-500 Hz 2 VA
(true-RMS units only)
Table 1 Table 2 Table 3 Table 4 Table 5 Table 6 Table 6 Table 3
0-1 mAdc (P-Option Units)
output VT110A2 A2** (leave blank) External Auxiliary Power (120 Vac std.) 100-130 Vac 50-500 Hz 3 VA
A4 Internal Auxiliary Power (self-powered) 84-108% of Nominal Aux. Power Voltage Equals Input Frequency 3 VA
-1 -RS -SM -SC (voltage units only)
P-Option
outputs VT110 PAN7 A4
Exceltronic
Specify Specify ** For external auxiliary power voltages other than 120 Vac, specify the voltage in the last position of the complete model number. (Example: 240 Vac Aux.)
output input
If A2 is selected, leave space blank; specify voltage value
DC external auxiliary power available; see Special Options on page 128.
ext. aux. power voltage at end of model no.
If other than 120 Vac (std.), specify ext. aux. Table 4 Input Selection
power voltage: 69 Vac Aux., 240 Vac Aux.,
277 Vac Aux., or 480 Vac Aux. Current Units Only Voltage Units Only
Calibration at Rated Output Calibration at Rated
EXAMPLES: VT110A2-1-RS-SM-SC Output
0-1 mAdc Average-Sensing Voltage Transducer with 0.25% accuracy, 240 V input, resistor scaling (converts current Option Nominal Current Range (5 A Nominal Input) Option Nominal Voltage Range (120 V Nominal Input)
output to voltage output), seismic brace, special calibration (example: 360 V). -3 1A 0-2 A 1 A/Element Std.*** 120 V 0-150 V 150 V/Element
Std.*** 5A 0-10 A 5 A/Element -1 240 V 0-300 V 300 V/Element
VT110PAN7A4-1-RS-SM-SC -5 10 A 0-20 A 10 A/Element -2 480 V 0-600 V 600 V/Element
-8**** 25 A 0-30 A 25 A/Element *** Leave "Input" positions blank in the model number.
4-20 mAdc Average-Sensing Voltage Transducer, internal auxiliary power, 240 V input, resistor scaling (converts current
output to voltage output), seismic brace, special calibration (example: 360 V).
**** Option -8 requires a larger case: Style II case for Models CT510A2 and CT510A4; Style I case for Models 4044 and
4074. (See page 132 for case dimensions. Maximum height of terminal strip(s) is 1.07" on units with -8 option.)
Table 1 Base Model Number Selection
Table 5 Scaling Resistor (-RS)/Frequency Options
Current Voltage Calibration at Rated Output
Model No. Model No. Description (5 A or 120 V Nominal Input)
(0-1 mAdc Units) Current Voltage
Option Description † You must specify the desired output voltage:
* On 0-1 mAdc Average-Sensing Current -RS† Scaling Resistor
CT510A2* VT110A2* Average Sensing, Single Unit 5A 150 V For 0-1 mAdc units, specify range from 0-10 Vdc. Load impedance
and Voltage units, A2 and A4 refer to -6 400 Hz
CT510A4* VT110A4* Average Sensing, Single Unit 5A 150 V is 1 MΩ/Vdc (minimum).
accuracy. A2 denotes 0.25% accuracy,
-12 50 Hz (not UL Recognized) For P-Option units, specify range from 0-15 Vdc (PAN models)
4044 3588 Average Sensing, Triple Unit 5A 150 V which is the standard/default; A4
or 0-40 Vdc (PA models). Load impedance is 200, 50, or 20 (kΩ/Vdc)
4044A4* 3588A4* Average Sensing, Triple Unit 5A 150 V denotes 0.15% optional accuracy. -6-RS† 400 Hz and Scaling Resistor
-12-RS† 50 Hz and Scaling Resistor (minimum) for units with outputs of 5, 20, or 50 mAdc, respectively.
4074A 3567A True RMS, Single Unit 5A 150 V On P-Option Current and Voltage units,
A2 and A4 refer to auxiliary power (see This information is not part of the model number, but must be
(P-Option Units) provided to the factory when you place your order.
Table 3). Standard accuracy on P-Option
CT510 VT110 Average Sensing, Single Unit 5A 150 V Current and Voltage units is 0.50%.
4044 3588 Average Sensing, Triple Unit 5A 150 V
4074 3567 True RMS, Single Unit 5A 150 V
See Specifications on previous pages Table 6 Other Options
for more detail.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
34 35
SCI Transducer Cat. 1-51(MTD) 34-35 1/9/02, 5:24 PM
Ordering Procedure Ordering Procedure
Exceltronic AC Average-Sensing & Exceltronic AC Average-Sensing &
True-RMS Current or Voltage Transducers True-RMS Current or Voltage Transducers
Specify by base model number and appropriate selection or option suffixes in the order shown in the following example. Option Description Input Range Frequency Range Burden
(0-1 mAdc Units)
Auxiliary Current or -RS/Freq. Option Option Ext. Aux. None required for average-sensing units.
Base Model No. Output Power Voltage Input Option #1 #2 #3 Power A2** (leave blank) External Auxiliary Power (120 Vac std.) 85-135 Vac 50-500 Hz 2 VA
(true-RMS units only)
Table 1 Table 2 Table 3 Table 4 Table 5 Table 6 Table 6 Table 3
0-1 mAdc (P-Option Units)
output VT110A2 A2** (leave blank) External Auxiliary Power (120 Vac std.) 100-130 Vac 50-500 Hz 3 VA
A4 Internal Auxiliary Power (self-powered) 84-108% of Nominal Aux. Power Voltage Equals Input Frequency 3 VA
-1 -RS -SM -SC (voltage units only)
P-Option
outputs VT110 PAN7 A4
Exceltronic
Specify Specify ** For external auxiliary power voltages other than 120 Vac, specify the voltage in the last position of the complete model number. (Example: 240 Vac Aux.)
output input
If A2 is selected, leave space blank; specify voltage value
DC external auxiliary power available; see Special Options on page 128.
ext. aux. power voltage at end of model no.
If other than 120 Vac (std.), specify ext. aux. Table 4 Input Selection
power voltage: 69 Vac Aux., 240 Vac Aux.,
277 Vac Aux., or 480 Vac Aux. Current Units Only Voltage Units Only
Calibration at Rated Output Calibration at Rated
EXAMPLES: VT110A2-1-RS-SM-SC Output
0-1 mAdc Average-Sensing Voltage Transducer with 0.25% accuracy, 240 V input, resistor scaling (converts current Option Nominal Current Range (5 A Nominal Input) Option Nominal Voltage Range (120 V Nominal Input)
output to voltage output), seismic brace, special calibration (example: 360 V). -3 1A 0-2 A 1 A/Element Std.*** 120 V 0-150 V 150 V/Element
Std.*** 5A 0-10 A 5 A/Element -1 240 V 0-300 V 300 V/Element
VT110PAN7A4-1-RS-SM-SC -5 10 A 0-20 A 10 A/Element -2 480 V 0-600 V 600 V/Element
-8**** 25 A 0-30 A 25 A/Element *** Leave "Input" positions blank in the model number.
4-20 mAdc Average-Sensing Voltage Transducer, internal auxiliary power, 240 V input, resistor scaling (converts current
output to voltage output), seismic brace, special calibration (example: 360 V).
**** Option -8 requires a larger case: Style II case for Models CT510A2 and CT510A4; Style I case for Models 4044 and
4074. (See page 132 for case dimensions. Maximum height of terminal strip(s) is 1.07" on units with -8 option.)
Table 1 Base Model Number Selection
Table 5 Scaling Resistor (-RS)/Frequency Options
Current Voltage Calibration at Rated Output
Model No. Model No. Description (5 A or 120 V Nominal Input)
(0-1 mAdc Units) Current Voltage
Option Description † You must specify the desired output voltage:
* On 0-1 mAdc Average-Sensing Current -RS† Scaling Resistor
CT510A2* VT110A2* Average Sensing, Single Unit 5A 150 V For 0-1 mAdc units, specify range from 0-10 Vdc. Load impedance
and Voltage units, A2 and A4 refer to -6 400 Hz
CT510A4* VT110A4* Average Sensing, Single Unit 5A 150 V is 1 MΩ/Vdc (minimum).
accuracy. A2 denotes 0.25% accuracy,
-12 50 Hz (not UL Recognized) For P-Option units, specify range from 0-15 Vdc (PAN models)
4044 3588 Average Sensing, Triple Unit 5A 150 V which is the standard/default; A4
or 0-40 Vdc (PA models). Load impedance is 200, 50, or 20 (kΩ/Vdc)
4044A4* 3588A4* Average Sensing, Triple Unit 5A 150 V denotes 0.15% optional accuracy. -6-RS† 400 Hz and Scaling Resistor
-12-RS† 50 Hz and Scaling Resistor (minimum) for units with outputs of 5, 20, or 50 mAdc, respectively.
4074A 3567A True RMS, Single Unit 5A 150 V On P-Option Current and Voltage units,
A2 and A4 refer to auxiliary power (see This information is not part of the model number, but must be
(P-Option Units) provided to the factory when you place your order.
Table 3). Standard accuracy on P-Option
CT510 VT110 Average Sensing, Single Unit 5A 150 V Current and Voltage units is 0.50%.
4044 3588 Average Sensing, Triple Unit 5A 150 V
4074 3567 True RMS, Single Unit 5A 150 V
See Specifications on previous pages Table 6 Other Options
for more detail.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
34 35
SCI Transducer Cat. 1-51(MTD) 34-35 1/9/02, 5:24 PM
Specifications
Exceltronic AC Expanded-
Harmonics Scale Voltage Transducers
Exceltronic
To determine whether to use an average-sensing device or a true-RMS device, it is important to understand Accuracy ±0.25% of Input Voltage for 60 Hz ±0.5% of Input Voltage for 60 Hz
the difference between the two. An average-sensing device simply keeps a running average of the continu- Temperature Effect on Accuracy ±0.007% / ° C ±0.015% / ° C
Operating Temperature Range -20° C to +60° C -20° C to +50° C
ously varying signal at its input. A true-RMS device actually calculates, in analog circuitry, the root-mean-
Compliance Voltage 10 Vdc
squared value by: (1) Squaring each instantaneous input value, (2) taking the average (or Mean), and then See Table 2 on page 34.
Load 0–10,000 Ω
(3) taking the square Root of the result. In a case where the sine wave is not distorted, both the average-
Output Ripple Peak < 2.5% RO < 2.5% of Span
sensing and the RMS output values would be the same. However, when a wave form is distorted, the
Response Time < 400 ms to 99% < 1 Second to 99%
RMS value reflects a truer measure of the wave form. For example, the self-heating in a transmission line Standard Calibration Gain ±5% of Span ±20% of Span
is directly proportional to the square of the RMS value of the current wave form, not the square of the Adjustments Zero ±5% of Span ±5% of Span
average value of the current wave form. In the presence of a distorted wave form, the average-sensing Frequency Range 55–65 Hz
device provides an averaged answer and disregards some of the effects of distortion. Therefore, an RMS Stability (per year) ±0.25% of Input Voltage, Noncumulative
Operating Humidity 0–95% Noncondensing
device is advantageous when a large harmonic content is present and precise measurement is required
Isolation Complete (Input/Output/Case) Complete (Input/Output/Power/Case)
(i.e., capacitor banking switching).
Dielectric Withstand 1500 VRMS at 60 Hz
Surge Withstand ANSI/IEEE C37.90.1
The harmonic performance for Scientific Columbus watt or var transducers is excellent. The design of Maximum Net Weight 1 lb., 3 oz. (0.5 kg) 3 lbs., 3 oz. (1.4 kg)
the watt transducer makes it an inherently true-RMS device, as the multiplication of current and voltage Approximate Dimensions 3.3" W x 2.1" D x 4.1" H 7.0" W x 3.7" D x 5.6" H
(excluding mounting plate) (84 mm x 53 mm x 104 mm) (178 mm x 94 mm x 142 mm)
results in the “square” term necessary for the computation. In addition, the analog nature of Scientific Style III Case, see page 122 Style I Case, see page 122
Columbus devices gives them an inherently better performance than many digital-sampling devices. Our * P-Option includes 1–5, 4–20, and 10–50 mAdc outputs. Specifications subject to change without notice.
data shows accurate readings by Scientific Columbus watt transducers up to the 15th-order harmonic. **Minimum span must be at least 18% of low-end voltage.
The same holds true for Scientific Columbus var transducers. A var transducer also calculates a true-RMS
value, multiplying the current by the voltage, shifted 90 degrees in phase. As long as the frequency of the
voltage signal remains at 60 Hz and the voltage signal remains clean (i.e., no harmonics), a true-RMS signal
results. Since most harmonic content appears on the current axis, this method produces accurate signals
for most users.
For more information on transducers and their performance in the presence of harmonics, or for
assistance in selecting the proper transducer for your application, please consult the factory at
1-800-274-5368 (U.S. and Canada).
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
36 37
SCI Transducer Cat. 1-51(MTD) 36-37 1/9/02, 5:24 PM
Specifications
Exceltronic AC Expanded-
Harmonics Scale Voltage Transducers
Exceltronic
To determine whether to use an average-sensing device or a true-RMS device, it is important to understand Accuracy ±0.25% of Input Voltage for 60 Hz ±0.5% of Input Voltage for 60 Hz
the difference between the two. An average-sensing device simply keeps a running average of the continu- Temperature Effect on Accuracy ±0.007% / ° C ±0.015% / ° C
Operating Temperature Range -20° C to +60° C -20° C to +50° C
ously varying signal at its input. A true-RMS device actually calculates, in analog circuitry, the root-mean-
Compliance Voltage 10 Vdc
squared value by: (1) Squaring each instantaneous input value, (2) taking the average (or Mean), and then See Table 2 on page 34.
Load 0–10,000 Ω
(3) taking the square Root of the result. In a case where the sine wave is not distorted, both the average-
Output Ripple Peak < 2.5% RO < 2.5% of Span
sensing and the RMS output values would be the same. However, when a wave form is distorted, the
Response Time < 400 ms to 99% < 1 Second to 99%
RMS value reflects a truer measure of the wave form. For example, the self-heating in a transmission line Standard Calibration Gain ±5% of Span ±20% of Span
is directly proportional to the square of the RMS value of the current wave form, not the square of the Adjustments Zero ±5% of Span ±5% of Span
average value of the current wave form. In the presence of a distorted wave form, the average-sensing Frequency Range 55–65 Hz
device provides an averaged answer and disregards some of the effects of distortion. Therefore, an RMS Stability (per year) ±0.25% of Input Voltage, Noncumulative
Operating Humidity 0–95% Noncondensing
device is advantageous when a large harmonic content is present and precise measurement is required
Isolation Complete (Input/Output/Case) Complete (Input/Output/Power/Case)
(i.e., capacitor banking switching).
Dielectric Withstand 1500 VRMS at 60 Hz
Surge Withstand ANSI/IEEE C37.90.1
The harmonic performance for Scientific Columbus watt or var transducers is excellent. The design of Maximum Net Weight 1 lb., 3 oz. (0.5 kg) 3 lbs., 3 oz. (1.4 kg)
the watt transducer makes it an inherently true-RMS device, as the multiplication of current and voltage Approximate Dimensions 3.3" W x 2.1" D x 4.1" H 7.0" W x 3.7" D x 5.6" H
(excluding mounting plate) (84 mm x 53 mm x 104 mm) (178 mm x 94 mm x 142 mm)
results in the “square” term necessary for the computation. In addition, the analog nature of Scientific Style III Case, see page 122 Style I Case, see page 122
Columbus devices gives them an inherently better performance than many digital-sampling devices. Our * P-Option includes 1–5, 4–20, and 10–50 mAdc outputs. Specifications subject to change without notice.
data shows accurate readings by Scientific Columbus watt transducers up to the 15th-order harmonic. **Minimum span must be at least 18% of low-end voltage.
The same holds true for Scientific Columbus var transducers. A var transducer also calculates a true-RMS
value, multiplying the current by the voltage, shifted 90 degrees in phase. As long as the frequency of the
voltage signal remains at 60 Hz and the voltage signal remains clean (i.e., no harmonics), a true-RMS signal
results. Since most harmonic content appears on the current axis, this method produces accurate signals
for most users.
For more information on transducers and their performance in the presence of harmonics, or for
assistance in selecting the proper transducer for your application, please consult the factory at
1-800-274-5368 (U.S. and Canada).
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
36 37
SCI Transducer Cat. 1-51(MTD) 36-37 1/9/02, 5:24 PM
Ordering Procedure Ordering Procedure
Exceltronic AC Expanded- Exceltronic AC Expanded-
Scale Voltage Transducers Scale Voltage Transducers
Specify by base model number and appropriate selection or option suffixes in the order shown in the following example. Option Description Input Range Frequency Range Burden
(0-1 mAdc Units)
Auxiliary External None Required
Base Model No. Output Power Input Range Aux. Power
(P-Option Units)
Table 1 Table 2 Table 3 Table 4
A2* (leave blank) External Auxiliary Power (120 Vac std.) 100-130 Vac 50-500 Hz 3 VA
A4** Internal Auxiliary Power (self-powered) 84-108% of Nominal Aux. Power Voltage Equals Input Frequency 3 VA
0-1 mAdc
output 90–150 V
* For external auxiliary power voltages other than 120 Vac, specify the voltage in the last position of the complete model number. (Example: 240 Vac Aux.)
3545
Exceltronic
** If the A4 option is selected, the voltage measurement range must stay within the Auxiliary Power Input Range of 84-108% of the Nominal Aux. Power
P-Option Voltage. For example, if the Nominal Aux. Power Voltage is 120 Vac, the Auxiliary Power Input Range must be 100-130 Vac in order to be within
outputs 84-108% of 120 Vac.
PAN7 A4 100–130 V
Please consult the factory if you require any options with Expanded-Scale Voltage Transducers.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
38 39
SCI Transducer Cat. 1-51(MTD) 38-39 1/9/02, 5:25 PM
Ordering Procedure Ordering Procedure
Exceltronic AC Expanded- Exceltronic AC Expanded-
Scale Voltage Transducers Scale Voltage Transducers
Specify by base model number and appropriate selection or option suffixes in the order shown in the following example. Option Description Input Range Frequency Range Burden
(0-1 mAdc Units)
Auxiliary External None Required
Base Model No. Output Power Input Range Aux. Power
(P-Option Units)
Table 1 Table 2 Table 3 Table 4
A2* (leave blank) External Auxiliary Power (120 Vac std.) 100-130 Vac 50-500 Hz 3 VA
A4** Internal Auxiliary Power (self-powered) 84-108% of Nominal Aux. Power Voltage Equals Input Frequency 3 VA
0-1 mAdc
output 90–150 V
* For external auxiliary power voltages other than 120 Vac, specify the voltage in the last position of the complete model number. (Example: 240 Vac Aux.)
3545
Exceltronic
** If the A4 option is selected, the voltage measurement range must stay within the Auxiliary Power Input Range of 84-108% of the Nominal Aux. Power
P-Option Voltage. For example, if the Nominal Aux. Power Voltage is 120 Vac, the Auxiliary Power Input Range must be 100-130 Vac in order to be within
outputs 84-108% of 120 Vac.
PAN7 A4 100–130 V
Please consult the factory if you require any options with Expanded-Scale Voltage Transducers.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
38 39
SCI Transducer Cat. 1-51(MTD) 38-39 1/9/02, 5:25 PM
Wiring Diagrams
Exceltronic AC Current or
Voltage Transducers Transducer Accuracy
WIRING DIAGRAMS FOR 0-1 mAdc UNITS (Styles III & II Cases) AND P-OPTION UNITS (Styles I & V Cases) UNDERSTANDING TRANSDUCER ACCURACY
0-1 mAdc Units Accuracy, as defined in this catalog, is “the degree of uncertainty with which a measured value agrees with
Single Current or Voltage, Triple Current or Voltage (Style II Case) the ideal value.” So, to understand accuracy, we must first define uncertainty.
Expanded-Scale Voltage (Style III Case)
AC
INPUT
There are basically two ways to quantify uncertainty in a measured value: as a percentage of the measured
DC
OUTPUT value (reading) that varies with the input, or as a percentage of a fixed value. This fixed value can be
- +
either rated output (RO) or full scale, which results in a constant uncertainty over the range of inputs. The
1 2 3 4 less the absolute value of the uncertainty, the more accurate the device.
Exceltronic
1 2 3 4 It would be ideal if a measurement device could be specified as a percent-of-reading device; then the uncer-
AØ AC
INPUT tainty of any reading would always be known and constant. However, in practical use, a transducer cannot
+
DC
- OUTPUT be specified strictly as a percent-of-reading device. All electronic circuits have an inherent offset error,
1 2 3 4
AC
True-RMS Current or Voltage (Style II Case) BØ
INPUT which is accounted for by adding a constant error term (such as % RO) to the accuracy specification. At
+
DC
EXTERNAL
1 2 3 4
- OUTPUT Scientific Columbus, we express the total accuracy of our transducers as the percent of reading plus the
AUX. POWER
DC AC
CØ AC
INPUT offset error. For example, the accuracy of our typical current transducer (CT510A2) is 0.15% Reading +
+
OUTPUT DC
- +
INPUT
- OUTPUT 0.1% RO.
1 2 3 4 5 6
The chart below depicts the maximum uncertainty for a CT510A2 transducer compared with two com-
petitive units. The operation of the devices is graphed from several input values. Each plot represents a
different method of specifying transducer accuracy. Scientific Columbus’ CT510A2 accuracy is shown in
bold.
Maximum Uncertainty
AC
(% of Input Signal)
EXTERNAL INPUT
AUX. POWER DC
AC OUTPUT
DC INPUT - +
OUTPUT
- +
1 2 3 4
1 2 3 4 5 6
A PHASE
C PHASE B PHASE
1 2 3 4 1 2 3 4 A B
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
40 41
SCI Transducer Cat. 1-51(MTD) 40-41 1/9/02, 5:25 PM
Wiring Diagrams
Exceltronic AC Current or
Voltage Transducers Transducer Accuracy
WIRING DIAGRAMS FOR 0-1 mAdc UNITS (Styles III & II Cases) AND P-OPTION UNITS (Styles I & V Cases) UNDERSTANDING TRANSDUCER ACCURACY
0-1 mAdc Units Accuracy, as defined in this catalog, is “the degree of uncertainty with which a measured value agrees with
Single Current or Voltage, Triple Current or Voltage (Style II Case) the ideal value.” So, to understand accuracy, we must first define uncertainty.
Expanded-Scale Voltage (Style III Case)
AC
INPUT
There are basically two ways to quantify uncertainty in a measured value: as a percentage of the measured
DC
OUTPUT value (reading) that varies with the input, or as a percentage of a fixed value. This fixed value can be
- +
either rated output (RO) or full scale, which results in a constant uncertainty over the range of inputs. The
1 2 3 4 less the absolute value of the uncertainty, the more accurate the device.
Exceltronic
1 2 3 4 It would be ideal if a measurement device could be specified as a percent-of-reading device; then the uncer-
AØ AC
INPUT tainty of any reading would always be known and constant. However, in practical use, a transducer cannot
+
DC
- OUTPUT be specified strictly as a percent-of-reading device. All electronic circuits have an inherent offset error,
1 2 3 4
AC
True-RMS Current or Voltage (Style II Case) BØ
INPUT which is accounted for by adding a constant error term (such as % RO) to the accuracy specification. At
+
DC
EXTERNAL
1 2 3 4
- OUTPUT Scientific Columbus, we express the total accuracy of our transducers as the percent of reading plus the
AUX. POWER
DC AC
CØ AC
INPUT offset error. For example, the accuracy of our typical current transducer (CT510A2) is 0.15% Reading +
+
OUTPUT DC
- +
INPUT
- OUTPUT 0.1% RO.
1 2 3 4 5 6
The chart below depicts the maximum uncertainty for a CT510A2 transducer compared with two com-
petitive units. The operation of the devices is graphed from several input values. Each plot represents a
different method of specifying transducer accuracy. Scientific Columbus’ CT510A2 accuracy is shown in
bold.
Maximum Uncertainty
AC
(% of Input Signal)
EXTERNAL INPUT
AUX. POWER DC
AC OUTPUT
DC INPUT - +
OUTPUT
- +
1 2 3 4
1 2 3 4 5 6
A PHASE
C PHASE B PHASE
1 2 3 4 1 2 3 4 A B
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
40 41
SCI Transducer Cat. 1-51(MTD) 40-41 1/9/02, 5:25 PM
SCIENTIFIC
Exceltronic AC Watt or Var Transducers SCIENTIFIC
Specifications
COLUMBUS COLUMBUS
EXCELTRONIC AC WATT OR VAR TRANSDUCERS
Exceltronic watt and var transducers
Specifications 0 to ±1 mAdc Watts P-Option* Watts 0 to ±1 mAdc Vars P-Option* Vars
provide utility and industrial users with a (Watt Transducer) (Watt Transducer) (Var Transducer) (Var Transducer)
high degree of accuracy for applications Current Nominal 5A
requiring precise measurements. These Input Range** 0–10 A
Overload Continuous 20 A
transducers provide a dc-output signal Overload 1 Second/Hour 250 A
Burden/Element 0.2 VA (maximum) at 5 A
proportional to input watts or vars. All
Voltage Nominal 120 V
models are available with a wide range of Input Range** 0–150 V
input and output options. Overload Continuous 200 V
Exceltronic
Burden/Element 0.035 VA (maximum) at 120 V
External Input Range 85–135 Vac 100–130 Vac 85–135 Vac 100–130 Vac
Auxiliary Frequency Range 50–500 Hz 50–500 Hz 50–500 Hz 50–500 Hz
Power Burden 3 VA Nominal 6 VA Nominal 3 VA Nominal 6 VA Nominal
Rated Output (RO) = ±1 mAdc for 5, 20, or 50 mAdc for ±1 mAdc for 5, 20, or 50 mAdc for
500 Watts or Vars/Element Standard Calibration Std. Calibration, depending on Standard Calibration Std. Calibration, depending on
selected output range* selected output range*
Accuracy ± (0.2% Reading + 0.01% RO) ± (0.2% Reading + 0.05% RO) ± (0.2% Reading + 0.02% RO) ± (0.3% Reading + 0.05% RO)
Features Applications Outputs at 0–200% RO at 0–120% RO at 0–200% RO at 0–120% RO
Temperature Effect on Accuracy ±0.005% / ° C ±0.0075% / ° C ±0.009% / ° C ±0.012% / ° C
Operating Temperature Range -20° C to +70° C -20° C to +50° C -20° C to +60° C -20° C to +50° C
◆ Accuracy to 0.2% of reading ◆ Substation monitoring ◆ 0 to ±1 mAdc
Compliance Voltage 10 Vdc 10 Vdc
See Table 2 on page 40. See Table 2 on page 40.
◆ Exceptional reliability ◆ SCADA ◆ 1–5 or 1–3–5 mAdc Load 0–10,000 Ω 0–10,000 Ω
◆ Excellent long-term stability ◆ Energy-management ◆ 4–20 or 4–12–20 mAdc Output Ripple Peak < 0.5% RO < 0.25% RO < 0.5% RO < 0.25% RO
systems Response Time < 400 ms to 99% < 1 Second to 99% < 400 ms to 99% < 1 Second to 99%
◆ Self- or externally powered ◆ 10–50 or 10–30–50 mAdc
Power Factor Any
◆ Distribution monitoring
◆ No zero adjustment required PF Effect on Accuracy ± 0.1% VA (maximum) ±0.15% VA (maximum)
◆ Process control ±2% of Reading (minimum) ± 20% of Span (minimum) ±2% of Reading (minimum) ± 20% of Span (minimum)
◆ Most popular models are Standard Calibration Gain
Adjustments Zero None Required ±5% of Zero Point (minimum) None Required ±5% of Zero Point (minimum)
UL Recognized
Frequency Range 58–62 Hz 60 Hz
Stability (per year) ±0.1% RO, ± 0.15% of Span, ±0.2% RO, ±0.25% of Span,
Noncumulative Noncumulative Noncumulative Noncumulative
Operating Humidity 0–95% Noncondensing
Isolation Complete (Input/Output/Power/Case)
Dielectric Withstand 2500 VRMS*** at 60 Hz
Surge Withstand ANSI/IEEE C37.90.1
Maximum Net Weight 3 lbs., 5 oz. (1.5 kg) 4 lbs., 8 oz. (2 kg) 3 lbs., 5 oz. (1.5 kg) 4 lbs., 8 oz. (2 kg)
Approximate Dimensions 4.4" W x 3.9" D x 4.7" H 7.0" W x 3.7" D x 5.6" H 4.4" W x 3.9" D x 4.7" H 7.0" W x 3.7" D x 5.6" H
(excluding mounting plate) (112 mm x 99 mm x 119 mm) (178 mm x 94 mm x 142 mm) (112 mm x 99 mm x 119 mm) (178 mm x 94 mm x 142 mm)
Also available in XLP modular, plug-in format for limited- Style II Case, see page 122 Style I Case, see page 122 Style II Case, see page 122 Style I Case, see page 122
space applications requiring large numbers of transducers. Overrange with Linearity 500–1000 Watts/Element 500–600 Watts/Element 500–1000 Vars/Element 500–600 Vars/Element
No additional error within voltage compliance. Reduce load resistance as required.
◆ Two, four, or eight modules in one enclosure * P-Option includes 1–5/1–3–5, 4–20/4–12–20, and 10–50/10–30–50 mAdc outputs. Specifications subject to change without notice.
** Total input not to exceed 200% of standard-calibration watts or vars on units with 0 to ±1 mAdc output.
◆ Easy to install, expand, or repair Total input not to exceed 120% of standard-calibration watts or vars on units with P-Option outputs.
◆ Convenient front-panel access for calibration and output- ***Dielectric levels as indicated for UL Recognized models; levels may vary on non-UL Recognized models.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
42 43
SCI Transducer Cat. 1-51(MTD) 42-43 1/9/02, 5:25 PM
SCIENTIFIC
Exceltronic AC Watt or Var Transducers SCIENTIFIC
Specifications
COLUMBUS COLUMBUS
EXCELTRONIC AC WATT OR VAR TRANSDUCERS
Exceltronic watt and var transducers
Specifications 0 to ±1 mAdc Watts P-Option* Watts 0 to ±1 mAdc Vars P-Option* Vars
provide utility and industrial users with a (Watt Transducer) (Watt Transducer) (Var Transducer) (Var Transducer)
high degree of accuracy for applications Current Nominal 5A
requiring precise measurements. These Input Range** 0–10 A
Overload Continuous 20 A
transducers provide a dc-output signal Overload 1 Second/Hour 250 A
Burden/Element 0.2 VA (maximum) at 5 A
proportional to input watts or vars. All
Voltage Nominal 120 V
models are available with a wide range of Input Range** 0–150 V
input and output options. Overload Continuous 200 V
Exceltronic
Burden/Element 0.035 VA (maximum) at 120 V
External Input Range 85–135 Vac 100–130 Vac 85–135 Vac 100–130 Vac
Auxiliary Frequency Range 50–500 Hz 50–500 Hz 50–500 Hz 50–500 Hz
Power Burden 3 VA Nominal 6 VA Nominal 3 VA Nominal 6 VA Nominal
Rated Output (RO) = ±1 mAdc for 5, 20, or 50 mAdc for ±1 mAdc for 5, 20, or 50 mAdc for
500 Watts or Vars/Element Standard Calibration Std. Calibration, depending on Standard Calibration Std. Calibration, depending on
selected output range* selected output range*
Accuracy ± (0.2% Reading + 0.01% RO) ± (0.2% Reading + 0.05% RO) ± (0.2% Reading + 0.02% RO) ± (0.3% Reading + 0.05% RO)
Features Applications Outputs at 0–200% RO at 0–120% RO at 0–200% RO at 0–120% RO
Temperature Effect on Accuracy ±0.005% / ° C ±0.0075% / ° C ±0.009% / ° C ±0.012% / ° C
Operating Temperature Range -20° C to +70° C -20° C to +50° C -20° C to +60° C -20° C to +50° C
◆ Accuracy to 0.2% of reading ◆ Substation monitoring ◆ 0 to ±1 mAdc
Compliance Voltage 10 Vdc 10 Vdc
See Table 2 on page 40. See Table 2 on page 40.
◆ Exceptional reliability ◆ SCADA ◆ 1–5 or 1–3–5 mAdc Load 0–10,000 Ω 0–10,000 Ω
◆ Excellent long-term stability ◆ Energy-management ◆ 4–20 or 4–12–20 mAdc Output Ripple Peak < 0.5% RO < 0.25% RO < 0.5% RO < 0.25% RO
systems Response Time < 400 ms to 99% < 1 Second to 99% < 400 ms to 99% < 1 Second to 99%
◆ Self- or externally powered ◆ 10–50 or 10–30–50 mAdc
Power Factor Any
◆ Distribution monitoring
◆ No zero adjustment required PF Effect on Accuracy ± 0.1% VA (maximum) ±0.15% VA (maximum)
◆ Process control ±2% of Reading (minimum) ± 20% of Span (minimum) ±2% of Reading (minimum) ± 20% of Span (minimum)
◆ Most popular models are Standard Calibration Gain
Adjustments Zero None Required ±5% of Zero Point (minimum) None Required ±5% of Zero Point (minimum)
UL Recognized
Frequency Range 58–62 Hz 60 Hz
Stability (per year) ±0.1% RO, ± 0.15% of Span, ±0.2% RO, ±0.25% of Span,
Noncumulative Noncumulative Noncumulative Noncumulative
Operating Humidity 0–95% Noncondensing
Isolation Complete (Input/Output/Power/Case)
Dielectric Withstand 2500 VRMS*** at 60 Hz
Surge Withstand ANSI/IEEE C37.90.1
Maximum Net Weight 3 lbs., 5 oz. (1.5 kg) 4 lbs., 8 oz. (2 kg) 3 lbs., 5 oz. (1.5 kg) 4 lbs., 8 oz. (2 kg)
Approximate Dimensions 4.4" W x 3.9" D x 4.7" H 7.0" W x 3.7" D x 5.6" H 4.4" W x 3.9" D x 4.7" H 7.0" W x 3.7" D x 5.6" H
(excluding mounting plate) (112 mm x 99 mm x 119 mm) (178 mm x 94 mm x 142 mm) (112 mm x 99 mm x 119 mm) (178 mm x 94 mm x 142 mm)
Also available in XLP modular, plug-in format for limited- Style II Case, see page 122 Style I Case, see page 122 Style II Case, see page 122 Style I Case, see page 122
space applications requiring large numbers of transducers. Overrange with Linearity 500–1000 Watts/Element 500–600 Watts/Element 500–1000 Vars/Element 500–600 Vars/Element
No additional error within voltage compliance. Reduce load resistance as required.
◆ Two, four, or eight modules in one enclosure * P-Option includes 1–5/1–3–5, 4–20/4–12–20, and 10–50/10–30–50 mAdc outputs. Specifications subject to change without notice.
** Total input not to exceed 200% of standard-calibration watts or vars on units with 0 to ±1 mAdc output.
◆ Easy to install, expand, or repair Total input not to exceed 120% of standard-calibration watts or vars on units with P-Option outputs.
◆ Convenient front-panel access for calibration and output- ***Dielectric levels as indicated for UL Recognized models; levels may vary on non-UL Recognized models.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
42 43
SCI Transducer Cat. 1-51(MTD) 42-43 1/9/02, 5:25 PM
Ordering Procedure Ordering Procedure
Exceltronic AC Watt or Exceltronic AC Watt or
Var Transducers Var Transducers
Exceltronic
DC external auxiliary power available; see Special Options on page 128.
P-Option
Specify Specify If other than 120 Vac Table 4 Input Selection
outputs PAN7 A4 output input (std.), specify ext.
voltage value aux. power voltage: Current Voltage
If A2 is selected, leave this space blank; specify 69 Vac Aux.,
240 Vac Aux., Current Range Calibration at Rated Output Voltage Range Calibration at Rated Output
ext. aux. power voltage at end of model no.
277 Vac Aux., Option Nominal w/ Accuracy (5 A Nominal Input) Option Nominal w/ Accuracy (120 V Nominal Input)
or 480 Vac Aux. -3 1A 0-2 A 100 W or Vars/Element -0 69 V 0-75 V 250 W or Vars/Element
-4 2.5 A 0-5 A 250 W or Vars/Element Std.*** 120 V 0-150 V 500 W or Vars/Element
EXAMPLES: XL342K5A2-5-1-RS-SM-SC Std.*** 5A 0-10 A 500 W or Vars/Element -1 240 V 0-300 V 1000 W or Vars/Element
3-element, 0 to ±1 mAdc Watt Transducer; 120 Vac external auxiliary power; 10 A input; 240 V input; resistor scaling -11 7.5 A 0-15 A 750 W or Vars/Element -9 277 V 0-340 V 1200 W or Vars/Element
(converts current output to voltage output); seismic brace; special calibration (example: 7200 W). -5 10 A 0-20 A 1000 W or Vars/Element -2 480 V 0-600 V 2000 W or Vars/Element -7
15 A 0-20 A1500 W or Vars/Element
-8**** 25 A 0-30 A 2500 W or Vars/Element *** Leave "Input" positions blank in the model number.
XL342K5PAN7A4-5-1-RS-SM-SC
3-element, 4-20 mAdc Watt Transducer; internal auxiliary power; 10 A input; 240 V input; resistor scaling (converts current **** Option -8 requires a Style I case. (See page 122 for case dimensions.
output to voltage output); seismic brace; special calibration (example: 7200 W). Maximum height of terminal strip(s) is 1.07" for units with -8 option.)
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
44 45
SCI Transducer Cat. 1-51(MTD) 44-45 1/9/02, 5:25 PM
Ordering Procedure Ordering Procedure
Exceltronic AC Watt or Exceltronic AC Watt or
Var Transducers Var Transducers
Exceltronic
DC external auxiliary power available; see Special Options on page 128.
P-Option
Specify Specify If other than 120 Vac Table 4 Input Selection
outputs PAN7 A4 output input (std.), specify ext.
voltage value aux. power voltage: Current Voltage
If A2 is selected, leave this space blank; specify 69 Vac Aux.,
240 Vac Aux., Current Range Calibration at Rated Output Voltage Range Calibration at Rated Output
ext. aux. power voltage at end of model no.
277 Vac Aux., Option Nominal w/ Accuracy (5 A Nominal Input) Option Nominal w/ Accuracy (120 V Nominal Input)
or 480 Vac Aux. -3 1A 0-2 A 100 W or Vars/Element -0 69 V 0-75 V 250 W or Vars/Element
-4 2.5 A 0-5 A 250 W or Vars/Element Std.*** 120 V 0-150 V 500 W or Vars/Element
EXAMPLES: XL342K5A2-5-1-RS-SM-SC Std.*** 5A 0-10 A 500 W or Vars/Element -1 240 V 0-300 V 1000 W or Vars/Element
3-element, 0 to ±1 mAdc Watt Transducer; 120 Vac external auxiliary power; 10 A input; 240 V input; resistor scaling -11 7.5 A 0-15 A 750 W or Vars/Element -9 277 V 0-340 V 1200 W or Vars/Element
(converts current output to voltage output); seismic brace; special calibration (example: 7200 W). -5 10 A 0-20 A 1000 W or Vars/Element -2 480 V 0-600 V 2000 W or Vars/Element -7
15 A 0-20 A1500 W or Vars/Element
-8**** 25 A 0-30 A 2500 W or Vars/Element *** Leave "Input" positions blank in the model number.
XL342K5PAN7A4-5-1-RS-SM-SC
3-element, 4-20 mAdc Watt Transducer; internal auxiliary power; 10 A input; 240 V input; resistor scaling (converts current **** Option -8 requires a Style I case. (See page 122 for case dimensions.
output to voltage output); seismic brace; special calibration (example: 7200 W). Maximum height of terminal strip(s) is 1.07" for units with -8 option.)
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
44 45
SCI Transducer Cat. 1-51(MTD) 44-45 1/9/02, 5:25 PM
Wiring Diagrams Wiring Diagrams
Exceltronic AC Watt or Exceltronic AC Watt or
Var Transducers Var Transducers
WIRING DIAGRAMS FOR 0 to ±1 mAdc UNITS (Style II Case) WIRING DIAGRAMS FOR P-OPTION UNITS (Style I Case)
1 Element, Single Phase, 2 Wire LINE 11/2 Element, Single Phase, 3 Wire 1 Element, Single Phase, 2 Wire 11/2 Element, Single Phase, 3 Wire
L1 L2 LINE
LINE
LINE L1 L2
L1 N L2
L1 N L2
DC DC
OUTPUT DC
OUTPUT DC
- + - + -
OUTPUT
+ -
OUTPUT
+
1 2 3 4 5 6
1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
Exceltronic
7 8 9 10 11 12
7 8 9 10 11 12
7 8 9 10 11 12 7 8 9 10 11 12
LOAD
LOAD
EXTERNAL LOAD
EXTERNAL AUX. POWER
NOTES: (1) For units with -8 option, connect AUX. POWER NOTE: For units with -8 option, connect
EXTERNAL
AUX. POWER current input to terminals 7 (•) and 10 . EXTERNAL
LOAD
current input to terminals 7 (•) & 10.
AUX. POWER
(2) Bottom terminal strip (7-12) omitted on A4
models, except with -8 option. 11/2 Element, 3 Phase, 3 Wire, Delta 2 Element, 3 Phase, 3 Wire, Delta
LINE LINE LINE
11/2 Element, 3 Phase, 3 Wire, Delta 2 Element, 3 Phase, 3 Wire, Delta L1 L2 L3 L1 L2 L3 L1 L2 L3
LINE DC DC
L1 L2 OUTPUT OUTPUT
L3
DC DC - + - +
OUTPUT OUTPUT
- + - + 1 2 3 4 5 6 1 2 3 4 5 6
1 2 3 4 5 6 1 2 3 4 5 6
7 8 9 10 11 12 7 8 9 10 11 12
7 8 9 10 11 12 7 8 9 10 11 12
LOAD EXTERNAL LOAD
EXTERNAL
AUX. POWER AUX. POWER
EXTERNAL
AUX. POWER LOAD EXTERNAL LOAD 21/2 Element, 3 Phase, 4 Wire, Wye 3 Element, 3 Phase, 4 Wire, Wye
AUX. POWER
LINE LINE
L1 L2 L3 N L1 L2 L3 N
1 2 3 4 5 6 6A 1 2 3 4 5 6 6A
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
EXT. EXT.
AUX. AUX.
POWER POWER 7 8 9 10 11 12 12A
7 8 9 10 11 12 12A
7 8 9 10 11 12 12A 7 8 9 10 11 12 12A
LOAD LOAD
LOAD LOAD
Adj t
Adjust A2 Models: Shown. A4 Models: External aux. power not required. Adjust A2 Models: Shown. A4 Models: External aux. power not required.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
46 47
SCI Transducer Cat. 1-51(MTD) 46-47 1/9/02, 5:25 PM
Wiring Diagrams Wiring Diagrams
Exceltronic AC Watt or Exceltronic AC Watt or
Var Transducers Var Transducers
WIRING DIAGRAMS FOR 0 to ±1 mAdc UNITS (Style II Case) WIRING DIAGRAMS FOR P-OPTION UNITS (Style I Case)
1 Element, Single Phase, 2 Wire LINE 11/2 Element, Single Phase, 3 Wire 1 Element, Single Phase, 2 Wire 11/2 Element, Single Phase, 3 Wire
L1 L2 LINE
LINE
LINE L1 L2
L1 N L2
L1 N L2
DC DC
OUTPUT DC
OUTPUT DC
- + - + -
OUTPUT
+ -
OUTPUT
+
1 2 3 4 5 6
1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
Exceltronic
7 8 9 10 11 12
7 8 9 10 11 12
7 8 9 10 11 12 7 8 9 10 11 12
LOAD
LOAD
EXTERNAL LOAD
EXTERNAL AUX. POWER
NOTES: (1) For units with -8 option, connect AUX. POWER NOTE: For units with -8 option, connect
EXTERNAL
AUX. POWER current input to terminals 7 (•) and 10 . EXTERNAL
LOAD
current input to terminals 7 (•) & 10.
AUX. POWER
(2) Bottom terminal strip (7-12) omitted on A4
models, except with -8 option. 11/2 Element, 3 Phase, 3 Wire, Delta 2 Element, 3 Phase, 3 Wire, Delta
LINE LINE LINE
11/2 Element, 3 Phase, 3 Wire, Delta 2 Element, 3 Phase, 3 Wire, Delta L1 L2 L3 L1 L2 L3 L1 L2 L3
LINE DC DC
L1 L2 OUTPUT OUTPUT
L3
DC DC - + - +
OUTPUT OUTPUT
- + - + 1 2 3 4 5 6 1 2 3 4 5 6
1 2 3 4 5 6 1 2 3 4 5 6
7 8 9 10 11 12 7 8 9 10 11 12
7 8 9 10 11 12 7 8 9 10 11 12
LOAD EXTERNAL LOAD
EXTERNAL
AUX. POWER AUX. POWER
EXTERNAL
AUX. POWER LOAD EXTERNAL LOAD 21/2 Element, 3 Phase, 4 Wire, Wye 3 Element, 3 Phase, 4 Wire, Wye
AUX. POWER
LINE LINE
L1 L2 L3 N L1 L2 L3 N
1 2 3 4 5 6 6A 1 2 3 4 5 6 6A
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
EXT. EXT.
AUX. AUX.
POWER POWER 7 8 9 10 11 12 12A
7 8 9 10 11 12 12A
7 8 9 10 11 12 12A 7 8 9 10 11 12 12A
LOAD LOAD
LOAD LOAD
Adj t
Adjust A2 Models: Shown. A4 Models: External aux. power not required. Adjust A2 Models: Shown. A4 Models: External aux. power not required.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
46 47
SCI Transducer Cat. 1-51(MTD) 46-47 1/9/02, 5:25 PM
SCIENTIFIC
Exceltronic Combined SCIENTIFIC
Specifications
AC Watt/Var Transducers
COLUMBUS COLUMBUS
EXCELTRONIC COMBINED AC WATT/VAR TRANSDUCERS
Exceltronic combined watt/var transducers provide all the functions Specifications 0 to ±1 mAdc Watts P-Option* Watts 0 to ±1 mAdc Vars P-Option* Vars
of the individual watt and var transducers, but require only half the (Combined Watt/Var (Combined Watt/Var (Combined Watt/Var (Combined Watt/Var
panel space and half the wiring. These transducers use a common Transducer) Transducer) Transducer) Transducer)
power supply and share the input voltage and current transformers. Current Nominal 5A
Input Range** 0–10 A
Because of this unique feature, the burden on the user’s transform- Overload Continuous 20 A
Overload 1 Second/Hour 250 A
ers is the same as when only one watt or var transducer is used. Burden/Element 0.2 VA (maximum) at 5 A
Voltage Nominal 120 V
Input Range** 0–150 V
Exceltronic
Overload Continuous 200 V
Burden/Element 0.035 VA (maximum) at 120 V
External Input Range 85–135 Vac 100–130 Vac 85–135 Vac 100–130 Vac
Auxiliary Frequency Range 50–500 Hz 50–500 Hz 50–500 Hz 50–500 Hz
Power Burden 3 VA Nominal 5 VA Nominal 3 VA Nominal 5 VA Nominal
Rated Output (RO) = ±1 mAdc for 5 or 20 mAdc for ±1 mAdc for 5 or 20 mAdc for
500 Watts or Vars/Element Standard Calibration Std. Calibration, depending on Standard Calibration Std. Calibration, depending on
selected output range* selected output range*
Accuracy ± (0.2% Reading + 0.01% RO) ± (0.2% Reading + 0.05% RO) ± (0.2% Reading + 0.02% RO) ± (0.3% Reading + 0.05% RO)
at 0–200% RO at 0–120% RO at 0–200% RO at 0–120% RO
Temperature Effect on Accuracy ±0.005% / ° C ±0.0075% / ° C ±0.009% / ° C ±0.012% / ° C
Operating Temperature Range -20° C to +60° C -20° C to +50° C -20° C to +60° C -20° C to +50° C
Features Applications Outputs Compliance Voltage 10 Vdc 20 Vdc 10 Vdc 20 Vdc
Load 0–10,000 Ω See Table 2 on page 46. 0–10,000 Ω See Table 2 on page 46.
◆ Accuracy to 0.2% of reading ◆ Substation line monitoring ◆ 0 to ±1 mAdc Output Ripple Peak < 0.5% RO < 0.25% RO < 0.5% RO < 0.25% RO
Response Time < 400 ms to 99% < 1 Second to 99% < 400 ms to 99% < 1 Second to 99%
◆ Two transducers in one ◆ Energy-management ◆ 1–5 or 1–3–5 mAdc Power Factor Any
enclosure systems
◆ 4–20 or 4–12–20 mAdc PF Effect on Accuracy ± 0.1% VA (maximum) ±0.15% VA (maximum)
◆ Excellent long-term stability ◆ Process control Standard Calibration Gain ±2% of Reading (minimum) ± 20% of Span (minimum) ±2% of Reading (minimum) ± 20% of Span (minimum)
Adjustments Zero None Required ±5% of Zero Point (minimum) None Required ±5% of Zero Point (minimum)
◆ Most popular models are
UL Recognized Frequency 60 Hz
Stability (per year) ±0.1% RO, ±0.15% of Span, ±0.2% RO, ± 0.25% of Span,
Noncumulative Noncumulative Noncumulative Noncumulative
Operating Humidity 0–95% Noncondensing
Isolation Complete (Input/Output/Power/Case)
Dielectric Withstand 2500 VRMS*** at 60 Hz
Surge Withstand ANSI/IEEE C37.90.1
Also available in XLP modular, plug-in format for limited- Maximum Net Weight 3 lbs., 10 oz. (1.6 kg) 3 lbs., 14 oz. (1.8 kg) 3 lbs., 10 oz. (1.6 kg) 3 lbs., 14 oz. (1.8 kg)
space applications requiring large numbers of transducers. Approximate Dimensions 4.4" W x 3.9" D x 6.3" H (112 mm x 99 mm x 160 mm) Style IV Case, see page 123
(excluding mounting plate)
◆ Up to three single-phase watt/var transducers in one Overrange with Linearity 500–1000 Watts/Element 500–600 Watts/Element 500–1000 Vars/Element 500–600 Vars/Element
module No additional error within voltage compliance. Reduce load resistance as required.
◆ Two, four, or eight modules in one enclosure * P-Option includes 1–5/1–3–5 and 4–20/4–12–20 mAdc outputs. Specifications subject to change without notice.
** Total input not to exceed 200% of standard-calibration watts and vars on units with 0 to ±1 mAdc output.
◆ Easy to install, expand, or repair Total input not to exceed 120% of standard-calibration watts and vars on units with P-Option outputs.
***Dielectric levels as indicated for UL Recognized models; levels may vary on non-UL Recognized models.
◆ Convenient front-panel access for calibration and output-
current jacks available
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
48 49
SCI Transducer Cat. 1-51(MTD) 48-49 1/9/02, 5:25 PM
SCIENTIFIC
Exceltronic Combined SCIENTIFIC
Specifications
AC Watt/Var Transducers
COLUMBUS COLUMBUS
EXCELTRONIC COMBINED AC WATT/VAR TRANSDUCERS
Exceltronic combined watt/var transducers provide all the functions Specifications 0 to ±1 mAdc Watts P-Option* Watts 0 to ±1 mAdc Vars P-Option* Vars
of the individual watt and var transducers, but require only half the (Combined Watt/Var (Combined Watt/Var (Combined Watt/Var (Combined Watt/Var
panel space and half the wiring. These transducers use a common Transducer) Transducer) Transducer) Transducer)
power supply and share the input voltage and current transformers. Current Nominal 5A
Input Range** 0–10 A
Because of this unique feature, the burden on the user’s transform- Overload Continuous 20 A
Overload 1 Second/Hour 250 A
ers is the same as when only one watt or var transducer is used. Burden/Element 0.2 VA (maximum) at 5 A
Voltage Nominal 120 V
Input Range** 0–150 V
Exceltronic
Overload Continuous 200 V
Burden/Element 0.035 VA (maximum) at 120 V
External Input Range 85–135 Vac 100–130 Vac 85–135 Vac 100–130 Vac
Auxiliary Frequency Range 50–500 Hz 50–500 Hz 50–500 Hz 50–500 Hz
Power Burden 3 VA Nominal 5 VA Nominal 3 VA Nominal 5 VA Nominal
Rated Output (RO) = ±1 mAdc for 5 or 20 mAdc for ±1 mAdc for 5 or 20 mAdc for
500 Watts or Vars/Element Standard Calibration Std. Calibration, depending on Standard Calibration Std. Calibration, depending on
selected output range* selected output range*
Accuracy ± (0.2% Reading + 0.01% RO) ± (0.2% Reading + 0.05% RO) ± (0.2% Reading + 0.02% RO) ± (0.3% Reading + 0.05% RO)
at 0–200% RO at 0–120% RO at 0–200% RO at 0–120% RO
Temperature Effect on Accuracy ±0.005% / ° C ±0.0075% / ° C ±0.009% / ° C ±0.012% / ° C
Operating Temperature Range -20° C to +60° C -20° C to +50° C -20° C to +60° C -20° C to +50° C
Features Applications Outputs Compliance Voltage 10 Vdc 20 Vdc 10 Vdc 20 Vdc
Load 0–10,000 Ω See Table 2 on page 46. 0–10,000 Ω See Table 2 on page 46.
◆ Accuracy to 0.2% of reading ◆ Substation line monitoring ◆ 0 to ±1 mAdc Output Ripple Peak < 0.5% RO < 0.25% RO < 0.5% RO < 0.25% RO
Response Time < 400 ms to 99% < 1 Second to 99% < 400 ms to 99% < 1 Second to 99%
◆ Two transducers in one ◆ Energy-management ◆ 1–5 or 1–3–5 mAdc Power Factor Any
enclosure systems
◆ 4–20 or 4–12–20 mAdc PF Effect on Accuracy ± 0.1% VA (maximum) ±0.15% VA (maximum)
◆ Excellent long-term stability ◆ Process control Standard Calibration Gain ±2% of Reading (minimum) ± 20% of Span (minimum) ±2% of Reading (minimum) ± 20% of Span (minimum)
Adjustments Zero None Required ±5% of Zero Point (minimum) None Required ±5% of Zero Point (minimum)
◆ Most popular models are
UL Recognized Frequency 60 Hz
Stability (per year) ±0.1% RO, ±0.15% of Span, ±0.2% RO, ± 0.25% of Span,
Noncumulative Noncumulative Noncumulative Noncumulative
Operating Humidity 0–95% Noncondensing
Isolation Complete (Input/Output/Power/Case)
Dielectric Withstand 2500 VRMS*** at 60 Hz
Surge Withstand ANSI/IEEE C37.90.1
Also available in XLP modular, plug-in format for limited- Maximum Net Weight 3 lbs., 10 oz. (1.6 kg) 3 lbs., 14 oz. (1.8 kg) 3 lbs., 10 oz. (1.6 kg) 3 lbs., 14 oz. (1.8 kg)
space applications requiring large numbers of transducers. Approximate Dimensions 4.4" W x 3.9" D x 6.3" H (112 mm x 99 mm x 160 mm) Style IV Case, see page 123
(excluding mounting plate)
◆ Up to three single-phase watt/var transducers in one Overrange with Linearity 500–1000 Watts/Element 500–600 Watts/Element 500–1000 Vars/Element 500–600 Vars/Element
module No additional error within voltage compliance. Reduce load resistance as required.
◆ Two, four, or eight modules in one enclosure * P-Option includes 1–5/1–3–5 and 4–20/4–12–20 mAdc outputs. Specifications subject to change without notice.
** Total input not to exceed 200% of standard-calibration watts and vars on units with 0 to ±1 mAdc output.
◆ Easy to install, expand, or repair Total input not to exceed 120% of standard-calibration watts and vars on units with P-Option outputs.
***Dielectric levels as indicated for UL Recognized models; levels may vary on non-UL Recognized models.
◆ Convenient front-panel access for calibration and output-
current jacks available
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
48 49
SCI Transducer Cat. 1-51(MTD) 48-49 1/9/02, 5:25 PM
Ordering Procedure Ordering Procedure
Exceltronic Combined Exceltronic Combined
AC Watt/Var Transducers AC Watt/Var Transducers
Specify by base model number and appropriate selection or option suffixes in the order shown in the following example. Option Description Input Range Frequency Range Burden
(0 to ±1 mAdc Units)
Auxiliary Current Voltage -RS/Freq. Option Option Ext. Aux. A2** External Auxiliary Power (120 Vac std.) 85-135 Vac 50-500 Hz 3 VA
Base Model No. Output Power Input Input Option #1 #2 #3 Power A4 Internal Auxiliary Power (self-powered) 70-112% of Nominal Aux. Power Voltage Equals Input Frequency 3 VA
(P-Option Units)
Table 1 Table 2 Table 3 Table 4 Table 4 Table 5 Table 6 Table 6 Table 3 A2** (leave blank) External Auxiliary Power (120 Vac std.) 100-130 Vac 50-500 Hz 6 VA
A4 Internal Auxiliary Power (self-powered) 84-108% of Nominal Aux. Power Voltage Equals Input Frequency 6 VA
0 to ±1 mAdc
output A2
** For external auxiliary power voltages other than 120 Vac, specify the voltage in the last position of the complete model number. (Example: 240 Vac Aux.)
Exceltronic
DC external auxiliary power available; see Special Options on page 128.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
50 51
SCI Transducer Cat. 1-51(MTD) 50-51 1/9/02, 5:26 PM
Ordering Procedure Ordering Procedure
Exceltronic Combined Exceltronic Combined
AC Watt/Var Transducers AC Watt/Var Transducers
Specify by base model number and appropriate selection or option suffixes in the order shown in the following example. Option Description Input Range Frequency Range Burden
(0 to ±1 mAdc Units)
Auxiliary Current Voltage -RS/Freq. Option Option Ext. Aux. A2** External Auxiliary Power (120 Vac std.) 85-135 Vac 50-500 Hz 3 VA
Base Model No. Output Power Input Input Option #1 #2 #3 Power A4 Internal Auxiliary Power (self-powered) 70-112% of Nominal Aux. Power Voltage Equals Input Frequency 3 VA
(P-Option Units)
Table 1 Table 2 Table 3 Table 4 Table 4 Table 5 Table 6 Table 6 Table 3 A2** (leave blank) External Auxiliary Power (120 Vac std.) 100-130 Vac 50-500 Hz 6 VA
A4 Internal Auxiliary Power (self-powered) 84-108% of Nominal Aux. Power Voltage Equals Input Frequency 6 VA
0 to ±1 mAdc
output A2
** For external auxiliary power voltages other than 120 Vac, specify the voltage in the last position of the complete model number. (Example: 240 Vac Aux.)
Exceltronic
DC external auxiliary power available; see Special Options on page 128.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
50 51
SCI Transducer Cat. 1-51(MTD) 50-51 1/9/02, 5:26 PM
Wiring Diagrams
Exceltronic Combined
AC Watt/Var Transducers Analog Totalizers
WIRING DIAGRAMS FOR 0 to ±1 mAdc AND P-OPTION UNITS (Style IV Case) 9100 SERIES ANALOG TOTALIZERS
1 Element, Single Phase, 2 Wire 11/2 Element, Single Phase, 3 Wire In many applications, the need to sum the output of a series of transducers is necessary to help determine
LINE
DC
L1 L2
DC L1
LINE
N L2
the operation of a total system. Scientific Columbus’ 9100 Series Analog Totalizers meet this requirement.
OUTPUT OUTPUT
COM WATT VAR COM WATT VAR For example, the total watts supplied by six separate watt transducers can be summed
- + + - + + (or totalized) to give a total watts value for all six devices. Other quantities that can be measured and
1 2 2A 3 4 5 6 1 2 2A 3 4 5 6
summed include vars, current, and voltage.
Exceltronic
7 8 9 10 11 12 13 7 8 9 10 11 12 13 u Up to six inputs
u Up to three outputs (one analog and two Form-C pulse outputs)
LOAD
1 2 2A 3 4 5 6 6A 1 2 2A 3 4 5 6 6A
WATT, VAR, CURRENT, OR TOTALIZED FORM-C
EXT. EXT.
output analog input #5
AUX.
VOLTAGE TRANSDUCER PULSE OUTPUTS
AUX.
POWER POWER (Wh, Varh, Ah, or Vh)
7 8 9 10 11 12 13 12A 7 8 9 10 11 12 13 12A
WATT, VAR, CURRENT, OR
output analog input #6
VOLTAGE TRANSDUCER
LOAD LOAD
120 Vac
EXTERNAL
Adjust A2 Models: Shown. A4 Models: External aux. power not required. AUX. POWER
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
52 53
SCI Transducer Cat. 52-89(MTD) 52-53 1/9/02, 5:27 PM
Ametek Transducer Comp MTD1 1/9/02 5:11 PM Page 2
WIRING DIAGRAMS FOR 0 to ±1 mAdc AND P-OPTION UNITS (Style IV Case) 9100 SERIES ANALOG TOTALIZERS
1 Element, Single Phase, 2 Wire 11/2 Element, Single Phase, 3 Wire In many applications, the need to sum the output of a series of transducers is necessary to help determine
LINE
DC
L1 L2
DC L1
LINE
N L2
the operation of a total system. Scientific Columbus’ 9100 Series Analog Totalizers meet this requirement.
OUTPUT OUTPUT
COM WATT VAR COM WATT VAR For example, the total watts supplied by six separate watt transducers can be summed
- + + - + + (or totalized) to give a total watts value for all six devices. Other quantities that can be measured and
1 2 2A 3 4 5 6 1 2 2A 3 4 5 6
summed include vars, current, and voltage.
Exceltronic
7 8 9 10 11 12 13 7 8 9 10 11 12 13 u Up to six inputs
u Up to three outputs (one analog and two Form-C pulse outputs)
LOAD
1 2 2A 3 4 5 6 6A 1 2 2A 3 4 5 6 6A
WATT, VAR, CURRENT, OR TOTALIZED FORM-C
EXT. EXT.
output analog input #5
AUX.
VOLTAGE TRANSDUCER PULSE OUTPUTS
AUX.
POWER POWER (Wh, Varh, Ah, or Vh)
7 8 9 10 11 12 13 12A 7 8 9 10 11 12 13 12A
WATT, VAR, CURRENT, OR
output analog input #6
VOLTAGE TRANSDUCER
LOAD LOAD
120 Vac
EXTERNAL
Adjust A2 Models: Shown. A4 Models: External aux. power not required. AUX. POWER
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
52 53
SCI Transducer Cat. 52-89(MTD) 52-53 1/9/02, 5:27 PM
SCIENTIFIC
Exceltronic AC Watt/Watthour SCIENTIFIC
Specifications
or Var/Varhour Transducers
COLUMBUS COLUMBUS
EXCELTRONIC AC WATT/WATTHOUR OR VAR/VARHOUR TRANSDUCERS
Exceltronic combined watt/ Specifications 0 to ±1 mAdc Watts P-Option* Watts 0 to ±1 mAdc Vars P-Option* Vars
watthour and var/varhour trans- (Watt/Watthour (Watt/Watthour (Var/Varhour (Var/Varhour
Transducer) Transducer) Transducer) Transducer)
ducers provide two simultaneous
outputs: an analog output directly Current Nominal 5A
Input Range** 0–10 A
proportional to instantaneous Overload Continuous 20 A
Overload 1 Second/Hour 250 A
watts or vars, and a digital (pulse) Burden/Element 0.2 VA (maximum) at 5 A
output (Form-C mercury-wetted Voltage Nominal 120 V
Input Range** 0–150 V
relay or solid-state) directly propor-
Exceltronic
Overload Continuous 200 V
tional to watthours or varhours. Burden/Element 0.03 VA (maximum) at 120 V
All models are available in either External Input Range 85–135 Vac 100–130 Vac 85–135 Vac 100–130 Vac
Auxiliary Frequency Range 50–500 Hz 50–500 Hz 50–500 Hz 50–500 Hz
unidirectional or bidirectional configurations. Power Burden 3 VA Nominal 6 VA Nominal 3 VA Nominal 6 VA Nominal
Rated Output (RO) = ±1 mAdc for 5, 20, or 50 mAdc for ±1 mAdc for 5, 20, or 50 mAdc for
500 Watts or Vars/Element Standard Calibration Std. Calibration, depending on Standard Calibration Std. Calibration, depending on
selected output range* selected output range*
±(0.2% Reading + 0.01% RO) ±(0.2% Reading + 0.05% RO) ±(0.2% Reading + 0.02% RO) ±(0.3% Reading + 0.05% RO)
Features Applications Outputs Accuracy
at 0–200% RO at 0–120% RO at 0–200% RO at 0–120% RO
Temperature Effect on Accuracy ± 0.005% / ° C ±0.0075% / ° C ±0.009% / ° C ±0.012% / ° C
◆ Accuracy to 0.2% of reading ◆ Energy-management ◆ 0 to ± 1 mAdc Operating Temperature Range -20° C to +70° C -20° C to +50° C -20° C to +60° C -20° C to +50° C
systems Compliance Voltage 10 Vdc 10 Vdc
◆ Analog & digital outputs ◆ 1–5 or 1–3–5 mAdc See Table 2 on page 52. See Table 2 on page 52.
◆ Distribution monitoring Load 0–10,000 Ω 0–10,000 Ω
◆ Excellent long-term stability ◆ 4–20 or 4–12–20 mAdc Output Ripple Peak < 0.5% RO < 0.25% RO < 0.5% RO < 0.25% RO
◆ Process control
◆ Exceptional reliability ◆ 10–50 or 10–30–50 mAdc Relay Contact Rating (-60XX option) 15 VA at 1 A (maximum) or 150 Vac/15 Vdc (maximum) with resistive load. Contact protection required for inductive loads.
Relay Contact Life (-60XX option) One billion operations when operated within specifications.
◆ Wide selection of current & ◆ Relay and solid-state
voltage input ranges outputs for watthour and Solid-State Output Contact
28 Vdc (maximum) VCESAT: 1 Vdc (maximum) at 7 mAdc
Rating (-62XX option)
varhour functions
Response Time < 400 ms to 99% < 1 Second to 99% < 400 ms to 99% < 1 Second to 99%
Power Factor Any
PF Effect on Accuracy ±0.1% VA (maximum) ±0.15% VA (maximum)
Transducer Accuracy Specsmanship Standard Calibration Gain ± 1% of Reading (minimum) ±20% of Span (minimum) ± 1% of Reading (minimum) ±20% of Span (minimum)
Adjustments Zero None Required ±5% of Zero Point (minimum) None Required ±5% of Zero Point (minimum)
Metrology is the science of measurement for determination of
conformance to technical requirements. Scientific Columbus is Frequency Range 58–62 Hz 60 Hz
dedicated to this science. Scientific Columbus transducers provide Stability (per year) ±0.1% RO, ±0.15% of Span, ± 0.2% RO, ±0.25% of Span,
precise measurements which are rated as “Percent-of-Reading-plus- Noncumulative Noncumulative Noncumulative Noncumulative
Percent-of-RO” devices. Operating Humidity 0–95% Noncondensing
Isolation Complete (Input/Output/Power/Case) All KYZ outputs are isolated.
What does this mean? Aren’t all accuracy specifications the same?
Dielectric Withstand 1500 VRMS at 60 Hz
No. Surge Withstand ANSI/IEEE C37.90.1
Like any specification, what is defined may not be as important as Maximum Net Weight 4 lbs., 12 oz. (2.2 kg) 5 lbs., 2 oz. (2.3 kg) 4 lbs., 14 oz. (2.2 kg) 5 lbs., 4 oz. (2.4 kg)
how it is defined. When a Percent-of-Reading-plus-Percent-of-RO Approximate Dimensions 7.0" W x 3.7" D x 5.6" H 7.2" W x 5.3" D x 5.8" H 7.0" W x 3.7" D x 5.6" H 7.2" W x 5.3" D x 5.8" H
device is used in a measurement, the maximum measurement (excluding mounting plate) (178 mm x 94 mm x 142 mm) (183 mm x 135 mm x 147 mm) (178 mm x 94 mm x 142 mm) (183 mm x 135 mm x 147 mm)
Style I Case, see page 122 Style V Case, see page 123 Style I Case, see page 122 Style V Case, see page 123
tolerance is known. However, many devices are specified as
“Percent of Full Scale.” Full-scale specifications can result in a Overrange with Linearity 500–1000 Watts/Element 500–600 Watts/Element 500–1000 Vars/Element 500–600 Vars/Element
measurement tolerance of 3% or greater, when the tolerance is 0.3% No additional error within voltage compliance. Reduce load resistance as required.
from a Scientific Columbus, Percent-of-Reading-plus-Percent-of-RO * P-Option includes 1–5/1–3–5, 4–20/4–12–20, and 10–50/10–30–50 mAdc outputs. Specifications subject to change without notice.
Transducer. **Total input not to exceed 200% of standard-calibration watts or vars on units with 0 to ±1 mAdc output.
Total input not to exceed 120% of standard-calibration watts or vars on units with P-Option outputs.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
54 55
SCI Transducer Cat. 52-89(MTD) 54-55 1/9/02, 5:27 PM
SCIENTIFIC
Exceltronic AC Watt/Watthour SCIENTIFIC
Specifications
or Var/Varhour Transducers
COLUMBUS COLUMBUS
EXCELTRONIC AC WATT/WATTHOUR OR VAR/VARHOUR TRANSDUCERS
Exceltronic combined watt/ Specifications 0 to ±1 mAdc Watts P-Option* Watts 0 to ±1 mAdc Vars P-Option* Vars
watthour and var/varhour trans- (Watt/Watthour (Watt/Watthour (Var/Varhour (Var/Varhour
Transducer) Transducer) Transducer) Transducer)
ducers provide two simultaneous
outputs: an analog output directly Current Nominal 5A
Input Range** 0–10 A
proportional to instantaneous Overload Continuous 20 A
Overload 1 Second/Hour 250 A
watts or vars, and a digital (pulse) Burden/Element 0.2 VA (maximum) at 5 A
output (Form-C mercury-wetted Voltage Nominal 120 V
Input Range** 0–150 V
relay or solid-state) directly propor-
Exceltronic
Overload Continuous 200 V
tional to watthours or varhours. Burden/Element 0.03 VA (maximum) at 120 V
All models are available in either External Input Range 85–135 Vac 100–130 Vac 85–135 Vac 100–130 Vac
Auxiliary Frequency Range 50–500 Hz 50–500 Hz 50–500 Hz 50–500 Hz
unidirectional or bidirectional configurations. Power Burden 3 VA Nominal 6 VA Nominal 3 VA Nominal 6 VA Nominal
Rated Output (RO) = ±1 mAdc for 5, 20, or 50 mAdc for ±1 mAdc for 5, 20, or 50 mAdc for
500 Watts or Vars/Element Standard Calibration Std. Calibration, depending on Standard Calibration Std. Calibration, depending on
selected output range* selected output range*
±(0.2% Reading + 0.01% RO) ±(0.2% Reading + 0.05% RO) ±(0.2% Reading + 0.02% RO) ±(0.3% Reading + 0.05% RO)
Features Applications Outputs Accuracy
at 0–200% RO at 0–120% RO at 0–200% RO at 0–120% RO
Temperature Effect on Accuracy ± 0.005% / ° C ±0.0075% / ° C ±0.009% / ° C ±0.012% / ° C
◆ Accuracy to 0.2% of reading ◆ Energy-management ◆ 0 to ± 1 mAdc Operating Temperature Range -20° C to +70° C -20° C to +50° C -20° C to +60° C -20° C to +50° C
systems Compliance Voltage 10 Vdc 10 Vdc
◆ Analog & digital outputs ◆ 1–5 or 1–3–5 mAdc See Table 2 on page 52. See Table 2 on page 52.
◆ Distribution monitoring Load 0–10,000 Ω 0–10,000 Ω
◆ Excellent long-term stability ◆ 4–20 or 4–12–20 mAdc Output Ripple Peak < 0.5% RO < 0.25% RO < 0.5% RO < 0.25% RO
◆ Process control
◆ Exceptional reliability ◆ 10–50 or 10–30–50 mAdc Relay Contact Rating (-60XX option) 15 VA at 1 A (maximum) or 150 Vac/15 Vdc (maximum) with resistive load. Contact protection required for inductive loads.
Relay Contact Life (-60XX option) One billion operations when operated within specifications.
◆ Wide selection of current & ◆ Relay and solid-state
voltage input ranges outputs for watthour and Solid-State Output Contact
28 Vdc (maximum) VCESAT: 1 Vdc (maximum) at 7 mAdc
Rating (-62XX option)
varhour functions
Response Time < 400 ms to 99% < 1 Second to 99% < 400 ms to 99% < 1 Second to 99%
Power Factor Any
PF Effect on Accuracy ±0.1% VA (maximum) ±0.15% VA (maximum)
Transducer Accuracy Specsmanship Standard Calibration Gain ± 1% of Reading (minimum) ±20% of Span (minimum) ± 1% of Reading (minimum) ±20% of Span (minimum)
Adjustments Zero None Required ±5% of Zero Point (minimum) None Required ±5% of Zero Point (minimum)
Metrology is the science of measurement for determination of
conformance to technical requirements. Scientific Columbus is Frequency Range 58–62 Hz 60 Hz
dedicated to this science. Scientific Columbus transducers provide Stability (per year) ±0.1% RO, ±0.15% of Span, ± 0.2% RO, ±0.25% of Span,
precise measurements which are rated as “Percent-of-Reading-plus- Noncumulative Noncumulative Noncumulative Noncumulative
Percent-of-RO” devices. Operating Humidity 0–95% Noncondensing
Isolation Complete (Input/Output/Power/Case) All KYZ outputs are isolated.
What does this mean? Aren’t all accuracy specifications the same?
Dielectric Withstand 1500 VRMS at 60 Hz
No. Surge Withstand ANSI/IEEE C37.90.1
Like any specification, what is defined may not be as important as Maximum Net Weight 4 lbs., 12 oz. (2.2 kg) 5 lbs., 2 oz. (2.3 kg) 4 lbs., 14 oz. (2.2 kg) 5 lbs., 4 oz. (2.4 kg)
how it is defined. When a Percent-of-Reading-plus-Percent-of-RO Approximate Dimensions 7.0" W x 3.7" D x 5.6" H 7.2" W x 5.3" D x 5.8" H 7.0" W x 3.7" D x 5.6" H 7.2" W x 5.3" D x 5.8" H
device is used in a measurement, the maximum measurement (excluding mounting plate) (178 mm x 94 mm x 142 mm) (183 mm x 135 mm x 147 mm) (178 mm x 94 mm x 142 mm) (183 mm x 135 mm x 147 mm)
Style I Case, see page 122 Style V Case, see page 123 Style I Case, see page 122 Style V Case, see page 123
tolerance is known. However, many devices are specified as
“Percent of Full Scale.” Full-scale specifications can result in a Overrange with Linearity 500–1000 Watts/Element 500–600 Watts/Element 500–1000 Vars/Element 500–600 Vars/Element
measurement tolerance of 3% or greater, when the tolerance is 0.3% No additional error within voltage compliance. Reduce load resistance as required.
from a Scientific Columbus, Percent-of-Reading-plus-Percent-of-RO * P-Option includes 1–5/1–3–5, 4–20/4–12–20, and 10–50/10–30–50 mAdc outputs. Specifications subject to change without notice.
Transducer. **Total input not to exceed 200% of standard-calibration watts or vars on units with 0 to ±1 mAdc output.
Total input not to exceed 120% of standard-calibration watts or vars on units with P-Option outputs.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
54 55
SCI Transducer Cat. 52-89(MTD) 54-55 1/9/02, 5:27 PM
Ordering Procedure Ordering Procedure
Exceltronic AC Watt/Watthour Exceltronic AC Watt/Watthour
or Var/Varhour Transducers or Var/Varhour Transducers
Specify by base model number and appropriate selection or option suffixes in the order shown in the following example. Option Description Input Range Frequency Range Burden
(0 to ±1 mAdc Units)
Auxiliary Pulse Mounting Current Voltage -RS/Freq. Option Option Ext. Aux. A2*** External Auxiliary Power (120 Vac std.) 85-135 Vac 50-500 Hz 3 VA
Base Model No. Output Power Output Orientation Input Input Option #1 #2 #3 Power A4 Internal Auxiliary Power (self-powered) 70-112% of Nominal Aux. Power Voltage Equals Input Frequency 3 VA
(P-Option Units)
Table 1 Table 2 Table 3 Table 4 Table 4 Table 5 Table 5 Table 6 Table 7 Table 7 Table 3 A2*** (leave blank) External Auxiliary Power (120 Vac std.) 100-130 Vac 50-500 Hz 6 VA
0 to ±1 mAdc A4 Internal Auxiliary Power (self-powered) 84-108% of Nominal Aux. Power Voltage Equals Input Frequency 6 VA
output A2 *** For external auxiliary power voltages other than 120 Vac, specify the voltage in the last position of the complete model number. (Example: 240 Vac Aux.)
-6070 -V -5 -1 -RS -SM -SC DC external auxiliary power available; see Special Options on page 128.
XLV31K521/2 Table 4 Pulse Output Selection
Exceltronic
P-Option Option Description CPH Range**** Mounting Orientation*****
Specify Specify Specify
outputs PAN7 A4 -6070 Form-C Mercury-Wetted Relay, Unidirectional 2-14,000 -V (Vertical) or -H (Horizontal)
counts output input
-6270 Form-C Solid-State, Unidirectional 2-900,000 Not Applicable
per hour voltage value
-6096 Form-C Mercury-Wetted Relay, Bidirectional 2-14,000 -V (Vertical) or -H (Horizontal)
-6296 Form-C Solid-State, Bidirectional 2-900,000 Not Applicable
If A2 is selected, leave this space blank; specify If other than 120 Vac (std.), specify ext. aux. power voltage:
*** Standard cph is one count/watthour or varhour unless otherwise specified.
ext. aux. power voltage at end of model no. 69 Vac Aux., 240 Vac Aux., 277 Vac Aux., or 480 Vac Aux.
***** You must specify the desired mounting orientation for units with mercury-wetted relays.
Table 5 Input Selection
EXAMPLES: XLV31K521/2A2-6070-V-5-1-RS-SM-SC
Current Voltage
21/2-element, 0 to ±1 mAdc Var/Varhour Transducer; 120 Vac external auxiliary power; mercury-wetted relay
(unidirectional); vertical mounting; 10 A input; 240 V input; resistor scaling (converts current output to voltage output); Current Range Calibration at Rated Output Voltage Range Calibration at Rated Output
seismic brace; special calibration (example: 7200 W). Option Nominal w/ Accuracy (5 A Nominal Input) Option Nominal w/ Accuracy (120 V Nominal Input)
-3 1A 0-2 A 100 W or Vars/Element -0 69 V 0-75 V 250 W or Vars/Element
XLV31K521/2PAN7A4-6070-V-5-1-RS-SM-SC -4 2.5 A 0-5 A 250 W or Vars/Element Std.† 120 V 0-150 V 500 W or Vars/Element
Std.† 5A 0-10 A 500 W or Vars/Element -1 240 V 0-300 V 1000 W or Vars/Element
21/2-element, 4-20 mAdc Var/Varhour Transducer; internal auxiliary power; mercury-wetted relay (unidirectional);
-11 7.5 A 0-15 A 750 W or Vars/Element -9 277 V 0-340 V 1200 W or Vars/Element
vertical mounting; 10 A input; 240 V input; resistor scaling (converts current output to voltage output); seismic brace;
-5 10 A 0-20 A 1000 W or Vars/Element -2 480 V 0-600 V 2000 W or Vars/Element
special calibration (example: 7200 W).
-7 15 A 0-20 A 1500 W or Vars/Element † Leave "Input" positions blank in the model number.
-8†† 25 A 0-30 A 2500 W or Vars/Element
Table 1 Base Model Number Selection †† Option -8 requires a Style V case. (See page 123 for case dimensions.
Maximum height of terminal strip(s) is 1.07" for units with -8 option.)
Watt Var Calibration at Rated Output Table 6 Scaling Resistor (-RS)/Frequency Options
Element Model No. Model No. Connection (5 A, 120 V Nominal Input) Option Description ††† You must specify the desired output voltage:
1 XL5C5 XLV5C5 Single Phase 500 W or Vars * 21/2-element units require -RS††† Scaling Resistor For 0 to ±1 mAdc units, specify range from 0 to ±10 Vdc. Load impedance is 1 MΩ/Vdc (minimum).
2 XL31K5 XLV31K5 3 Phase, 3 Wire 1000 W or Vars a balanced voltage. -6 400 Hz For P-Option units, specify range from 0-15 Vdc (PAN models) or 0-40 Vdc (PA models). Load
21/2* XL31K521/2 XLV31K521/2 3 Phase, 4 Wire 1500 W or Vars -12 50 Hz impedance is 200, 50, or 20 (kΩ/Vdc) (minimum) for units with outputs of 5, 20, or 50 mAdc,
3 XL342K5 XLV342K5 3 Phase, 4 Wire 1500 W or Vars -6-RS††† 400 Hz and Scaling Resistor respectively.
-12-RS††† 50 Hz and Scaling Resistor This information is not part of the model number, but must be provided to the factory when you
Table 2 Output Selection place your order.
Table 7 Other Options
0 to ±1 mAdc output is Compliance Voltage/ Maximum Open
standard, and is specified P-Option** Output Range Maximum Load Circuit Voltage Option Description †††† You must specify the desired input value:
by the Base Model PAN6 1-5 mAdc 15 Vdc/3000 Ω 30 Vdc -20 50-200% Calibration Adjustment (current outputs) 0 to ±1 mAdc units can be calibrated within 90-180% of their
Numbers. For outputs other PAN7 4-20 mAdc 15 Vdc/750 Ω 30 Vdc -21 50-200% Calibration Adjustment (voltage outputs) standard-calibration input watts or vars. (Example: A 2-element
than 0 to ±1 mAdc, indicate PAN8 10-50 mAdc 15 Vdc/300 Ω 30 Vdc (available only with 0 to ±1 mAdc units) watt/watthour transducer is calibrated to 1000 W standard. The
-24 24 Vdc Loop-Powered (PA7 and PA7-B models only) -SC option can be added for input levels from 900 W (90%) to 1800 W
the appropriate P-Option in PAN6-B 1-3-5 mAdc 15 Vdc/3000 Ω 30 Vdc (180%).) P-Option units can be calibrated within 60-180% of their
(consult factory for specifications)
the "Output" position of the PAN7-B 4-12-20 mAdc 15 Vdc/750 Ω 30 Vdc standard-calibration input watts or vars.
-CE Analog Output Shorting Relay
complete model number. PAN8-B 10-30-50 mAdc 15 Vdc/300 Ω 30 Vdc This information is not part of the model number, but must be
(available only with 0 to ±1 mAdc units)
provided to the factory when you place your order.
PA6 1-5 mAdc 40 Vdc/8000 Ω 70 Vdc -SC†††† Special Calibration
** PAN and PA models take PA7 4-20 mAdc 40 Vdc/2000 Ω 70 Vdc -SM Seismic Brace (available with 0 to ±1 mAdc units)
-6070 or -6270 unidirectional If you require additional options not shown here, see Special
PA8 10-50 mAdc 30 Vdc/600 Ω 70 Vdc (consult factory if you desire this option with
pulse outputs; PAN-B and Options on page 128. When ordering any special options, or
a P-Option unit)
PA-B models take -6096 or PA6-B 1-3-5 mAdc 40 Vdc/8000 Ω 70 Vdc more than three options, you must first consult the factory for
-Z Zero-Based Output Calibration (ex.: PA7-Z = 0-20 mAdc)
-6296 bidirectional pulse PA7-B 4-12-20 mAdc 40 Vdc/2000 Ω 70 Vdc pricing and delivery estimates.
outputs. (available only with P-Option units, except PAN-B models)
PA8-B 10-30-50 mAdc 30 Vdc/600 Ω 70 Vdc
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
56 57
SCI Transducer Cat. 52-89(MTD) 56-57 1/9/02, 5:27 PM
Ordering Procedure Ordering Procedure
Exceltronic AC Watt/Watthour Exceltronic AC Watt/Watthour
or Var/Varhour Transducers or Var/Varhour Transducers
Specify by base model number and appropriate selection or option suffixes in the order shown in the following example. Option Description Input Range Frequency Range Burden
(0 to ±1 mAdc Units)
Auxiliary Pulse Mounting Current Voltage -RS/Freq. Option Option Ext. Aux. A2*** External Auxiliary Power (120 Vac std.) 85-135 Vac 50-500 Hz 3 VA
Base Model No. Output Power Output Orientation Input Input Option #1 #2 #3 Power A4 Internal Auxiliary Power (self-powered) 70-112% of Nominal Aux. Power Voltage Equals Input Frequency 3 VA
(P-Option Units)
Table 1 Table 2 Table 3 Table 4 Table 4 Table 5 Table 5 Table 6 Table 7 Table 7 Table 3 A2*** (leave blank) External Auxiliary Power (120 Vac std.) 100-130 Vac 50-500 Hz 6 VA
0 to ±1 mAdc A4 Internal Auxiliary Power (self-powered) 84-108% of Nominal Aux. Power Voltage Equals Input Frequency 6 VA
output A2 *** For external auxiliary power voltages other than 120 Vac, specify the voltage in the last position of the complete model number. (Example: 240 Vac Aux.)
-6070 -V -5 -1 -RS -SM -SC DC external auxiliary power available; see Special Options on page 128.
XLV31K521/2 Table 4 Pulse Output Selection
Exceltronic
P-Option Option Description CPH Range**** Mounting Orientation*****
Specify Specify Specify
outputs PAN7 A4 -6070 Form-C Mercury-Wetted Relay, Unidirectional 2-14,000 -V (Vertical) or -H (Horizontal)
counts output input
-6270 Form-C Solid-State, Unidirectional 2-900,000 Not Applicable
per hour voltage value
-6096 Form-C Mercury-Wetted Relay, Bidirectional 2-14,000 -V (Vertical) or -H (Horizontal)
-6296 Form-C Solid-State, Bidirectional 2-900,000 Not Applicable
If A2 is selected, leave this space blank; specify If other than 120 Vac (std.), specify ext. aux. power voltage:
*** Standard cph is one count/watthour or varhour unless otherwise specified.
ext. aux. power voltage at end of model no. 69 Vac Aux., 240 Vac Aux., 277 Vac Aux., or 480 Vac Aux.
***** You must specify the desired mounting orientation for units with mercury-wetted relays.
Table 5 Input Selection
EXAMPLES: XLV31K521/2A2-6070-V-5-1-RS-SM-SC
Current Voltage
21/2-element, 0 to ±1 mAdc Var/Varhour Transducer; 120 Vac external auxiliary power; mercury-wetted relay
(unidirectional); vertical mounting; 10 A input; 240 V input; resistor scaling (converts current output to voltage output); Current Range Calibration at Rated Output Voltage Range Calibration at Rated Output
seismic brace; special calibration (example: 7200 W). Option Nominal w/ Accuracy (5 A Nominal Input) Option Nominal w/ Accuracy (120 V Nominal Input)
-3 1A 0-2 A 100 W or Vars/Element -0 69 V 0-75 V 250 W or Vars/Element
XLV31K521/2PAN7A4-6070-V-5-1-RS-SM-SC -4 2.5 A 0-5 A 250 W or Vars/Element Std.† 120 V 0-150 V 500 W or Vars/Element
Std.† 5A 0-10 A 500 W or Vars/Element -1 240 V 0-300 V 1000 W or Vars/Element
21/2-element, 4-20 mAdc Var/Varhour Transducer; internal auxiliary power; mercury-wetted relay (unidirectional);
-11 7.5 A 0-15 A 750 W or Vars/Element -9 277 V 0-340 V 1200 W or Vars/Element
vertical mounting; 10 A input; 240 V input; resistor scaling (converts current output to voltage output); seismic brace;
-5 10 A 0-20 A 1000 W or Vars/Element -2 480 V 0-600 V 2000 W or Vars/Element
special calibration (example: 7200 W).
-7 15 A 0-20 A 1500 W or Vars/Element † Leave "Input" positions blank in the model number.
-8†† 25 A 0-30 A 2500 W or Vars/Element
Table 1 Base Model Number Selection †† Option -8 requires a Style V case. (See page 123 for case dimensions.
Maximum height of terminal strip(s) is 1.07" for units with -8 option.)
Watt Var Calibration at Rated Output Table 6 Scaling Resistor (-RS)/Frequency Options
Element Model No. Model No. Connection (5 A, 120 V Nominal Input) Option Description ††† You must specify the desired output voltage:
1 XL5C5 XLV5C5 Single Phase 500 W or Vars * 21/2-element units require -RS††† Scaling Resistor For 0 to ±1 mAdc units, specify range from 0 to ±10 Vdc. Load impedance is 1 MΩ/Vdc (minimum).
2 XL31K5 XLV31K5 3 Phase, 3 Wire 1000 W or Vars a balanced voltage. -6 400 Hz For P-Option units, specify range from 0-15 Vdc (PAN models) or 0-40 Vdc (PA models). Load
21/2* XL31K521/2 XLV31K521/2 3 Phase, 4 Wire 1500 W or Vars -12 50 Hz impedance is 200, 50, or 20 (kΩ/Vdc) (minimum) for units with outputs of 5, 20, or 50 mAdc,
3 XL342K5 XLV342K5 3 Phase, 4 Wire 1500 W or Vars -6-RS††† 400 Hz and Scaling Resistor respectively.
-12-RS††† 50 Hz and Scaling Resistor This information is not part of the model number, but must be provided to the factory when you
Table 2 Output Selection place your order.
Table 7 Other Options
0 to ±1 mAdc output is Compliance Voltage/ Maximum Open
standard, and is specified P-Option** Output Range Maximum Load Circuit Voltage Option Description †††† You must specify the desired input value:
by the Base Model PAN6 1-5 mAdc 15 Vdc/3000 Ω 30 Vdc -20 50-200% Calibration Adjustment (current outputs) 0 to ±1 mAdc units can be calibrated within 90-180% of their
Numbers. For outputs other PAN7 4-20 mAdc 15 Vdc/750 Ω 30 Vdc -21 50-200% Calibration Adjustment (voltage outputs) standard-calibration input watts or vars. (Example: A 2-element
than 0 to ±1 mAdc, indicate PAN8 10-50 mAdc 15 Vdc/300 Ω 30 Vdc (available only with 0 to ±1 mAdc units) watt/watthour transducer is calibrated to 1000 W standard. The
-24 24 Vdc Loop-Powered (PA7 and PA7-B models only) -SC option can be added for input levels from 900 W (90%) to 1800 W
the appropriate P-Option in PAN6-B 1-3-5 mAdc 15 Vdc/3000 Ω 30 Vdc (180%).) P-Option units can be calibrated within 60-180% of their
(consult factory for specifications)
the "Output" position of the PAN7-B 4-12-20 mAdc 15 Vdc/750 Ω 30 Vdc standard-calibration input watts or vars.
-CE Analog Output Shorting Relay
complete model number. PAN8-B 10-30-50 mAdc 15 Vdc/300 Ω 30 Vdc This information is not part of the model number, but must be
(available only with 0 to ±1 mAdc units)
provided to the factory when you place your order.
PA6 1-5 mAdc 40 Vdc/8000 Ω 70 Vdc -SC†††† Special Calibration
** PAN and PA models take PA7 4-20 mAdc 40 Vdc/2000 Ω 70 Vdc -SM Seismic Brace (available with 0 to ±1 mAdc units)
-6070 or -6270 unidirectional If you require additional options not shown here, see Special
PA8 10-50 mAdc 30 Vdc/600 Ω 70 Vdc (consult factory if you desire this option with
pulse outputs; PAN-B and Options on page 128. When ordering any special options, or
a P-Option unit)
PA-B models take -6096 or PA6-B 1-3-5 mAdc 40 Vdc/8000 Ω 70 Vdc more than three options, you must first consult the factory for
-Z Zero-Based Output Calibration (ex.: PA7-Z = 0-20 mAdc)
-6296 bidirectional pulse PA7-B 4-12-20 mAdc 40 Vdc/2000 Ω 70 Vdc pricing and delivery estimates.
outputs. (available only with P-Option units, except PAN-B models)
PA8-B 10-30-50 mAdc 30 Vdc/600 Ω 70 Vdc
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
56 57
SCI Transducer Cat. 52-89(MTD) 56-57 1/9/02, 5:27 PM
Wiring Diagrams Wiring Diagrams
Exceltronic AC Watt/Watthour Exceltronic AC Watt/Watthour
or Var/Varhour Transducers or Var/Varhour Transducers
WIRING DIAGRAMS FOR 0 to ±1 mAdc UNITS (Style I Case) WIRING DIAGRAMS FOR 0 to ±1 mAdc UNITS (Style I Case)
DC DC DC DC
Exceltronic
OUTPUT OUTPUT OUTPUT OUTPUT
- + - + - + - +
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H
LOAD LOAD
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
LOAD LOAD
Omitted on -6070 Models Omitted on -6270 Models Omitted on -6070 Models Omitted on -6270 Models
NOTE: For 1-element units with -8 option, connect current input to terminals 7 (•) & 10.
DC DC
OUTPUT OUTPUT
- + - +
DC DC
OUTPUT OUTPUT
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
- + - +
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H
Adjust A2 Models: Shown. A4 Models: External aux. power not required. Adjust A2 Models: Shown. A4 Models: External aux. power not required.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
58 59
SCI Transducer Cat. 52-89(MTD) 58-59 1/9/02, 5:27 PM
Wiring Diagrams Wiring Diagrams
Exceltronic AC Watt/Watthour Exceltronic AC Watt/Watthour
or Var/Varhour Transducers or Var/Varhour Transducers
WIRING DIAGRAMS FOR 0 to ±1 mAdc UNITS (Style I Case) WIRING DIAGRAMS FOR 0 to ±1 mAdc UNITS (Style I Case)
DC DC DC DC
Exceltronic
OUTPUT OUTPUT OUTPUT OUTPUT
- + - + - + - +
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H
LOAD LOAD
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
LOAD LOAD
Omitted on -6070 Models Omitted on -6270 Models Omitted on -6070 Models Omitted on -6270 Models
NOTE: For 1-element units with -8 option, connect current input to terminals 7 (•) & 10.
DC DC
OUTPUT OUTPUT
- + - +
DC DC
OUTPUT OUTPUT
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
- + - +
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H
Adjust A2 Models: Shown. A4 Models: External aux. power not required. Adjust A2 Models: Shown. A4 Models: External aux. power not required.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
58 59
SCI Transducer Cat. 52-89(MTD) 58-59 1/9/02, 5:27 PM
Wiring Diagrams Wiring Diagrams
Exceltronic AC Watt/Watthour Exceltronic AC Watt/Watthour
or Var/Varhour Transducers or Var/Varhour Transducers
WIRING DIAGRAMS FOR P-OPTION UNITS (Style V Case) WIRING DIAGRAMS FOR P-OPTION UNITS (Style V Case)
DC DC DC DC
OUTPUT OUTPUT OUTPUT OUTPUT
- + - + - + - +
Exceltronic
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H
LOAD LOAD
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
LOAD LOAD
Omitted on -6070 Models Omitted on -6270 Models Omitted on -6070 Models Omitted on -6270 Models
NOTE: For 1-element units with -8 option, connect current input to terminals 7 (•) & 10.
DC DC
OUTPUT OUTPUT
- + - +
DC DC
OUTPUT OUTPUT
- + - +
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
EXTERNAL EXTERNAL
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H AUX. POWER AUX. POWER
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H
Adjust A2 Models: Shown. A4 Models: External aux. power not required. Adjust A2 Models: Shown. A4 Models: External aux. power not required.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
60 61
SCI Transducer Cat. 52-89(MTD) 60-61 1/9/02, 5:27 PM
Wiring Diagrams Wiring Diagrams
Exceltronic AC Watt/Watthour Exceltronic AC Watt/Watthour
or Var/Varhour Transducers or Var/Varhour Transducers
WIRING DIAGRAMS FOR P-OPTION UNITS (Style V Case) WIRING DIAGRAMS FOR P-OPTION UNITS (Style V Case)
DC DC DC DC
OUTPUT OUTPUT OUTPUT OUTPUT
- + - + - + - +
Exceltronic
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H
LOAD LOAD
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
LOAD LOAD
Omitted on -6070 Models Omitted on -6270 Models Omitted on -6070 Models Omitted on -6270 Models
NOTE: For 1-element units with -8 option, connect current input to terminals 7 (•) & 10.
DC DC
OUTPUT OUTPUT
- + - +
DC DC
OUTPUT OUTPUT
- + - +
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
1 2 3 4 5 6 A B C D 1 2 3 4 5 6 A B C D
EXTERNAL EXTERNAL
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H AUX. POWER AUX. POWER
7 8 9 10 11 12 E F G H 7 8 9 10 11 12 E F G H
Adjust A2 Models: Shown. A4 Models: External aux. power not required. Adjust A2 Models: Shown. A4 Models: External aux. power not required.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
60 61
SCI Transducer Cat. 52-89(MTD) 60-61 1/9/02, 5:27 PM
SCIENTIFIC
Exceltronic AC Phase Angle SCIENTIFIC
Specifications
(Power Factor) Transducers
COLUMBUS COLUMBUS
EXCELTRONIC PHASE ANGLE (POWER FACTOR) TRANSDUCERS
Scientific Columbus offers a wide selection of phase angle trans-ducers Specifications 0 to ±50 mVdc or 0 to ±0.5 mAdc P-Option*
that can be used to determine power factor. The transducers produce a (Phase Angle (Power Factor) Transducer) (Phase Angle (Power Factor) Transducer)
dc output which is linearly proportional to the phase angle difference Current Nominal 5A
Input Range 0.25–5 A
between the voltage and current in an ac power system. The power Overload Continuous 10 A
factor is equal to the cosine of the phase angle. Therefore, a conversion Overload 1 Second/Hour 250 A
Burden/Element 1 VA (maximum) at 5 A
is required if the linear phase angle output is to be converted to power Nominal PF-1, -2, -3 Models PF-34 Models
factor. (See Conversion Table on page 62.) Voltage Range 120 V 120 V/220 V
Input Overload Continuous 95–135 V 95–135 V/190–250 V
Burden/Element 150 V 150 V/275 V
Exceltronic
5.5 VA (maximum) at 120 V 5.5 VA (maximum) at 120 V
All models have bipolar output; therefore indicating not only the phase
External Input Range 100–130 Vac
angle but also whether it is lead or lag. The transducers provide a Auxiliary Frequency Range None Required 50–500 Hz
meaningful indication of phase angle on a three-phase system, only when Power Burden 3 VA Nominal
Rated Type A & A1 Units ± 50 mVdc for Standard Calibration 5, 20, or 50 mAdc for Standard Calibration,
balanced load conditions prevail. While all models may be used on Output Type A4 Units ±0.5 mAdc for Standard Calibration depending on selected output range*
three-phase, four-wire systems, only the PF-34 models can be used on three-phase, (RO)
three-wire systems. The PF-34 models are recommended if varying line frequency is present. Accuracy See table below.
Temperature Effect on Accuracy See table below.
Operating Temperature Range -20° C to +60° C -20° C to +50° C
Compliance Voltage 5 Vdc for Type A4 Units
See Table 2 on page 61.
Load See Table 1 on page 60.
Features Applications Outputs Output Type A Units 200 mV Peak to Peak
Ripple Type A1 & A4 Units < 1% RMS < 0.25% of Span
Peak
◆ Bipolar output ◆ Generating stations ◆ 0 to ± 50 mVdc
Response Type A Units < 10 ms to 99%
< 1 Second to 99%
◆ Exceptional reliability ◆ Process control ◆ 0 to ± 0.5 mAdc Time Type A1 & A4 Units < 400 ms to 99%
Power Factor See Table 1 on page 60.
◆ High accuracy ◆ Energy-management ◆ 1–3–5 mAdc
Standard Calibration Gain ±10% of Reading (minimum) ±20% of Span (minimum)
systems ±2% of RO (minimum) ±5% of Zero Point (minimum)
◆ 4–12–20 mAdc Adjustments Zero
Frequency PF-1, -2, -3 Models Nominal ± 0.25%
◆ 10–30–50 mAdc Range PF-34 Models Nominal ±5%
Stability (per year) ±1% of Span, Noncumulative
Operating Humidity 0–95% Noncondensing
Isolation Complete (Input/Output/Case) Complete (Input/Output/Power/Case)
Dielectric Withstand 1500 VRMS at 60 Hz
Surge Withstand ANSI/IEEE C37.90.1
Maximum Net Weight 2 lbs., 12 oz. (1.2 kg) 4 lbs., 2 oz. (1.9 kg)
Utility Rate Tariffs and Power Factor
Approximate Dimensions 4.4" W x 3.9" D x 4.7" H 7.0" W x 3.7" D x 5.6" H
(excluding mounting plate) (112 mm x 99 mm x 119 mm) (178 mm x 94 mm x 142 mm)
When utility rate tariffs are predicated on power factor, a Scientific Style II Case, see page 122 Style I Case, see page 122
Columbus Exceltronic Phase Angle (Power Factor) Transducer can
*P-Option includes 1–3–5, 4–12–20, and 10–30–50 mAdc outputs. Specifications subject to change without notice.
be employed to help establish set points or targets. By installing a
Scientific Columbus Exceltronic Phase Angle (Power Factor) Trans- Model No./Accuracy
ducer and a Scientific Columbus Signal Conditioner together, a 25 ° C - 20° C to + 60 ° C (- 25 ° C to + 50 ° C for P-Option Units)
target can be set to give indication or alarm when a specific value is PF-1A, PF-1A1, PF-1A4 PF-1
achieved. ±0.01 PF from 0.8 Lead to 0.8 Lag ± 0.03 PF from 0.3 Lead to 0.3 Lag ±0.02 PF from 0.8 Lead to 0.8 Lag ±0.05 PF from 0.3 Lead to 0.3 Lag
PF-2A, PF-2A1, PF-2A4 PF-2
±0.01 PF from 0.8 Lead to 0.8 Lag ±0.025 PF from 0.5 Lead to 0.5 Lag ±0.02 PF from 0.8 Lead to 0.8 Lag ±0.04 PF from 0.5 Lead to 0.5 Lag
PF-3A, PF-3A1, PF-3A4 PF-3
±0.01 PF from 0.9 Lead to 0.9 Lag ± 0.02 PF from 0.7 Lead to 0.7 Lag ±0.015 PF from 0.9 Lead to 0.9 Lag ±0.03 PF from 0.7 Lead to 0.7 Lag
PF-34A, PF-34A1, PF-34A4 PF-34
±0.01 PF from 0.8 Lead to 0.8 Lag ±0.025 PF from 0.5 Lead to 0.5 Lag ±0.02 PF from 0.8 Lead to 0.8 Lag ±0.04 PF from 0.5 Lead to 0.5 Lag
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
62 63
SCI Transducer Cat. 52-89(MTD) 62-63 1/9/02, 5:28 PM
SCIENTIFIC
Exceltronic AC Phase Angle SCIENTIFIC
Specifications
(Power Factor) Transducers
COLUMBUS COLUMBUS
EXCELTRONIC PHASE ANGLE (POWER FACTOR) TRANSDUCERS
Scientific Columbus offers a wide selection of phase angle trans-ducers Specifications 0 to ±50 mVdc or 0 to ±0.5 mAdc P-Option*
that can be used to determine power factor. The transducers produce a (Phase Angle (Power Factor) Transducer) (Phase Angle (Power Factor) Transducer)
dc output which is linearly proportional to the phase angle difference Current Nominal 5A
Input Range 0.25–5 A
between the voltage and current in an ac power system. The power Overload Continuous 10 A
factor is equal to the cosine of the phase angle. Therefore, a conversion Overload 1 Second/Hour 250 A
Burden/Element 1 VA (maximum) at 5 A
is required if the linear phase angle output is to be converted to power Nominal PF-1, -2, -3 Models PF-34 Models
factor. (See Conversion Table on page 62.) Voltage Range 120 V 120 V/220 V
Input Overload Continuous 95–135 V 95–135 V/190–250 V
Burden/Element 150 V 150 V/275 V
Exceltronic
5.5 VA (maximum) at 120 V 5.5 VA (maximum) at 120 V
All models have bipolar output; therefore indicating not only the phase
External Input Range 100–130 Vac
angle but also whether it is lead or lag. The transducers provide a Auxiliary Frequency Range None Required 50–500 Hz
meaningful indication of phase angle on a three-phase system, only when Power Burden 3 VA Nominal
Rated Type A & A1 Units ± 50 mVdc for Standard Calibration 5, 20, or 50 mAdc for Standard Calibration,
balanced load conditions prevail. While all models may be used on Output Type A4 Units ±0.5 mAdc for Standard Calibration depending on selected output range*
three-phase, four-wire systems, only the PF-34 models can be used on three-phase, (RO)
three-wire systems. The PF-34 models are recommended if varying line frequency is present. Accuracy See table below.
Temperature Effect on Accuracy See table below.
Operating Temperature Range -20° C to +60° C -20° C to +50° C
Compliance Voltage 5 Vdc for Type A4 Units
See Table 2 on page 61.
Load See Table 1 on page 60.
Features Applications Outputs Output Type A Units 200 mV Peak to Peak
Ripple Type A1 & A4 Units < 1% RMS < 0.25% of Span
Peak
◆ Bipolar output ◆ Generating stations ◆ 0 to ± 50 mVdc
Response Type A Units < 10 ms to 99%
< 1 Second to 99%
◆ Exceptional reliability ◆ Process control ◆ 0 to ± 0.5 mAdc Time Type A1 & A4 Units < 400 ms to 99%
Power Factor See Table 1 on page 60.
◆ High accuracy ◆ Energy-management ◆ 1–3–5 mAdc
Standard Calibration Gain ±10% of Reading (minimum) ±20% of Span (minimum)
systems ±2% of RO (minimum) ±5% of Zero Point (minimum)
◆ 4–12–20 mAdc Adjustments Zero
Frequency PF-1, -2, -3 Models Nominal ± 0.25%
◆ 10–30–50 mAdc Range PF-34 Models Nominal ±5%
Stability (per year) ±1% of Span, Noncumulative
Operating Humidity 0–95% Noncondensing
Isolation Complete (Input/Output/Case) Complete (Input/Output/Power/Case)
Dielectric Withstand 1500 VRMS at 60 Hz
Surge Withstand ANSI/IEEE C37.90.1
Maximum Net Weight 2 lbs., 12 oz. (1.2 kg) 4 lbs., 2 oz. (1.9 kg)
Utility Rate Tariffs and Power Factor
Approximate Dimensions 4.4" W x 3.9" D x 4.7" H 7.0" W x 3.7" D x 5.6" H
(excluding mounting plate) (112 mm x 99 mm x 119 mm) (178 mm x 94 mm x 142 mm)
When utility rate tariffs are predicated on power factor, a Scientific Style II Case, see page 122 Style I Case, see page 122
Columbus Exceltronic Phase Angle (Power Factor) Transducer can
*P-Option includes 1–3–5, 4–12–20, and 10–30–50 mAdc outputs. Specifications subject to change without notice.
be employed to help establish set points or targets. By installing a
Scientific Columbus Exceltronic Phase Angle (Power Factor) Trans- Model No./Accuracy
ducer and a Scientific Columbus Signal Conditioner together, a 25 ° C - 20° C to + 60 ° C (- 25 ° C to + 50 ° C for P-Option Units)
target can be set to give indication or alarm when a specific value is PF-1A, PF-1A1, PF-1A4 PF-1
achieved. ±0.01 PF from 0.8 Lead to 0.8 Lag ± 0.03 PF from 0.3 Lead to 0.3 Lag ±0.02 PF from 0.8 Lead to 0.8 Lag ±0.05 PF from 0.3 Lead to 0.3 Lag
PF-2A, PF-2A1, PF-2A4 PF-2
±0.01 PF from 0.8 Lead to 0.8 Lag ±0.025 PF from 0.5 Lead to 0.5 Lag ±0.02 PF from 0.8 Lead to 0.8 Lag ±0.04 PF from 0.5 Lead to 0.5 Lag
PF-3A, PF-3A1, PF-3A4 PF-3
±0.01 PF from 0.9 Lead to 0.9 Lag ± 0.02 PF from 0.7 Lead to 0.7 Lag ±0.015 PF from 0.9 Lead to 0.9 Lag ±0.03 PF from 0.7 Lead to 0.7 Lag
PF-34A, PF-34A1, PF-34A4 PF-34
±0.01 PF from 0.8 Lead to 0.8 Lag ±0.025 PF from 0.5 Lead to 0.5 Lag ±0.02 PF from 0.8 Lead to 0.8 Lag ±0.04 PF from 0.5 Lead to 0.5 Lag
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
62 63
SCI Transducer Cat. 52-89(MTD) 62-63 1/9/02, 5:28 PM
Ordering Procedure Ordering Procedure
Exceltronic AC Phase Angle Exceltronic AC Phase Angle
(Power Factor) Transducers (Power Factor) Transducers
Specify by base model number and appropriate selection or option suffixes in the order shown in the following example. Compliance Voltage/ Maximum Open
P-Option Output Range Maximum Load Circuit Voltage
If one of the bidirectional
-RS/Freq. Option Option External PAN6-B 1-3-5 mAdc 15 Vdc/3000 Ω 30 Vdc
outputs at right is required,
Base Model No. Output Option #1 #2 #3 Aux. Power PAN7-B 4-12-20 mAdc 15 Vdc/750 Ω 30 Vdc
indicate the appropriate
PAN8-B 10-30-50 mAdc 15 Vdc/300 Ω 30 Vdc
0 to ± 50 mVdc or Table 1 Table 2 Table 3 Table 4 Table 4 P-Option in the "Output"
position of the complete PA6-B 1-3-5 mAdc 40 Vdc/8000 Ω 70 Vdc
0 to ± 0.5 mAdc
PF-34A4 model number. PA7-B 4-12-20 mAdc 40 Vdc/2000 Ω 70 Vdc
outputs
PA8-B 10-30-50 mAdc 30 Vdc/600 Ω 70 Vdc
-RS -SM
Exceltronic
P-Option Specify Table 3 Scaling Resistor (-RS)/Frequency Options
outputs PF-34 PA7-B output -24
voltage
Option Description
-RS* Scaling Resistor * You must specify the desired output voltage:
If other than 120 Vac (std.), specify ext. aux. power voltage: -6 400 Hz For 0 to ±50 mVdc or 0 to ±0.5 mAdc units, specify range from 0 to ±5 Vdc. Load
69 Vac Aux., 240 Vac Aux., 227 Vac Aux., or 480 Vac Aux. -12 50 Hz impedance is 2 MΩ/Vdc (minimum).
-6-RS* 400 Hz and Scaling Resistor For P-Option units, specify range from 0-15 Vdc (PAN models) or 0-40 Vdc (PA models).
-12-RS* 50 Hz and Scaling Resistor Load impedance is 200, 50, or 20 (kΩ/Vdc) (minimum) for units with outputs of 5, 20, or
EXAMPLES: PF-34A4-RS-SM 50 mAdc, respectively.
3-phase, 0 to ±0.5 mAdc Phase Angle (PF) Transducer; resistor scaling (converts current output to voltage output); This information is not part of the model number, but must be provided to the factory
seismic brace. when you place your order.
PF-34PA7-B-RS-SM-24
3-phase, 4-12-20 mAdc Phase Angle (PF) Transducer; resistor scaling (converts current output to voltage output);
seismic brace; 24 Vdc loop-powered. Table 4 Other Options
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
64 65
SCI Transducer Cat. 52-89(MTD) 64-65 1/9/02, 5:28 PM
Ordering Procedure Ordering Procedure
Exceltronic AC Phase Angle Exceltronic AC Phase Angle
(Power Factor) Transducers (Power Factor) Transducers
Specify by base model number and appropriate selection or option suffixes in the order shown in the following example. Compliance Voltage/ Maximum Open
P-Option Output Range Maximum Load Circuit Voltage
If one of the bidirectional
-RS/Freq. Option Option External PAN6-B 1-3-5 mAdc 15 Vdc/3000 Ω 30 Vdc
outputs at right is required,
Base Model No. Output Option #1 #2 #3 Aux. Power PAN7-B 4-12-20 mAdc 15 Vdc/750 Ω 30 Vdc
indicate the appropriate
PAN8-B 10-30-50 mAdc 15 Vdc/300 Ω 30 Vdc
0 to ± 50 mVdc or Table 1 Table 2 Table 3 Table 4 Table 4 P-Option in the "Output"
position of the complete PA6-B 1-3-5 mAdc 40 Vdc/8000 Ω 70 Vdc
0 to ± 0.5 mAdc
PF-34A4 model number. PA7-B 4-12-20 mAdc 40 Vdc/2000 Ω 70 Vdc
outputs
PA8-B 10-30-50 mAdc 30 Vdc/600 Ω 70 Vdc
-RS -SM
Exceltronic
P-Option Specify Table 3 Scaling Resistor (-RS)/Frequency Options
outputs PF-34 PA7-B output -24
voltage
Option Description
-RS* Scaling Resistor * You must specify the desired output voltage:
If other than 120 Vac (std.), specify ext. aux. power voltage: -6 400 Hz For 0 to ±50 mVdc or 0 to ±0.5 mAdc units, specify range from 0 to ±5 Vdc. Load
69 Vac Aux., 240 Vac Aux., 227 Vac Aux., or 480 Vac Aux. -12 50 Hz impedance is 2 MΩ/Vdc (minimum).
-6-RS* 400 Hz and Scaling Resistor For P-Option units, specify range from 0-15 Vdc (PAN models) or 0-40 Vdc (PA models).
-12-RS* 50 Hz and Scaling Resistor Load impedance is 200, 50, or 20 (kΩ/Vdc) (minimum) for units with outputs of 5, 20, or
EXAMPLES: PF-34A4-RS-SM 50 mAdc, respectively.
3-phase, 0 to ±0.5 mAdc Phase Angle (PF) Transducer; resistor scaling (converts current output to voltage output); This information is not part of the model number, but must be provided to the factory
seismic brace. when you place your order.
PF-34PA7-B-RS-SM-24
3-phase, 4-12-20 mAdc Phase Angle (PF) Transducer; resistor scaling (converts current output to voltage output);
seismic brace; 24 Vdc loop-powered. Table 4 Other Options
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
64 65
SCI Transducer Cat. 52-89(MTD) 64-65 1/9/02, 5:28 PM
Conversion Table Wiring Diagrams
Exceltronic AC Phase Angle Exceltronic AC Phase Angle
(Power Factor) Transducers (Power Factor) Transducers
CONVERSION TABLE (% Full Scale to Power Factor) WIRING DIAGRAMS FOR 0 to ±50 mVdc AND 0 to ±0.5 mAdc UNITS (Style II Case)
AND P-OPTION UNITS (Style I Case)
Percent Full Scale
Power Angle in (45.57°) (60°) (72.54°)
Factor Angle Decimals FS = 0.7 PF FS = 0.5 PF FS = 0.3 PF
0 to ±50 mVdc and 0 to ±0.5 mAdc Units—PF-1, PF-2, PF-3 Models
1.000 0°0' 0.00° 0.00 0.00 0.00 1 Element, Single Phase, 2 Wire LINE
3 Element, 3 Phase, 4 Wire, Wye LINE
.995 5°44' 5.73° 12.58 9.56 7.90 L1 L2 L1 L2 L3 N
.990 8°6.6' 8.11° 17.80 13.52 11.18
.985 9°56' 9.94° 21.80 16.56 13.70 DC DC
.980 11°29' 11.48° 25.19 19.13 15.82 OUTPUT OUTPUT
Exceltronic
1 2 3 4 5 6 1 2 3 4 5 6
.965 15°12' 15.20° 33.36 25.34 20.96
.960 16°16' 16.26° 35.70 27.10 22.41
.955 17°15' 17.25° 37.86 28.76 23.78
.950 18°12' 18.19° 39.92 30.32 25.08
.940 19°57' 19.95° 43.77 33.25 27.50
.930 21°34' 21.57° 47.32 35.94 29.73
LOAD
.920 23°4.4' 23.07° 50.63 38.46 31.81 LOAD
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
66 67
SCI Transducer Cat. 52-89(MTD) 66-67 1/9/02, 5:28 PM
Conversion Table Wiring Diagrams
Exceltronic AC Phase Angle Exceltronic AC Phase Angle
(Power Factor) Transducers (Power Factor) Transducers
CONVERSION TABLE (% Full Scale to Power Factor) WIRING DIAGRAMS FOR 0 to ±50 mVdc AND 0 to ±0.5 mAdc UNITS (Style II Case)
AND P-OPTION UNITS (Style I Case)
Percent Full Scale
Power Angle in (45.57°) (60°) (72.54°)
Factor Angle Decimals FS = 0.7 PF FS = 0.5 PF FS = 0.3 PF
0 to ±50 mVdc and 0 to ±0.5 mAdc Units—PF-1, PF-2, PF-3 Models
1.000 0°0' 0.00° 0.00 0.00 0.00 1 Element, Single Phase, 2 Wire LINE
3 Element, 3 Phase, 4 Wire, Wye LINE
.995 5°44' 5.73° 12.58 9.56 7.90 L1 L2 L1 L2 L3 N
.990 8°6.6' 8.11° 17.80 13.52 11.18
.985 9°56' 9.94° 21.80 16.56 13.70 DC DC
.980 11°29' 11.48° 25.19 19.13 15.82 OUTPUT OUTPUT
Exceltronic
1 2 3 4 5 6 1 2 3 4 5 6
.965 15°12' 15.20° 33.36 25.34 20.96
.960 16°16' 16.26° 35.70 27.10 22.41
.955 17°15' 17.25° 37.86 28.76 23.78
.950 18°12' 18.19° 39.92 30.32 25.08
.940 19°57' 19.95° 43.77 33.25 27.50
.930 21°34' 21.57° 47.32 35.94 29.73
LOAD
.920 23°4.4' 23.07° 50.63 38.46 31.81 LOAD
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
66 67
SCI Transducer Cat. 52-89(MTD) 66-67 1/9/02, 5:28 PM
SCIENTIFIC
Exceltronic AC Phase Angle SCIENTIFIC
Specifications
or Voltage Angle Transducers
COLUMBUS COLUMBUS
EXCELTRONIC AC PHASE ANGLE OR VOLTAGE ANGLE TRANSDUCERS
Model 6330 Phase Angle Trans- Specifications 0 to ±1 mAdc P-Option* 0 to ±1 mAdc P-Option*
ducers measure the phase angle (Phase Angle (Phase Angle (Voltage Angle (Voltage Angle
between one voltage and one Transducer) Transducer) Transducer) Transducer)
current input. These units are Current Nominal 5A
0.5–5 A
Input Range
more stable and accurate than the Overload Continuous 10 A N/A
Overload 1 Second/Hour 250 A
PF Series Phase Angle Transducers Burden/Element 0.2 VA (maximum) at 5 A
used for determining power factor; Voltage Nominal 120 V
Input Range 95–135 V
they also provide a wider range of
Exceltronic
Overload Continuous 150 V
measurement. Burden/Element 4 VA (maximum) at 120 V
Second Nominal 120 V
Voltage Range N/A 50–135 V
The Model 6314 Voltage Angle Input Overload Continuous 150 V
Burden/Element 2.2 VA (maximum) at 120 V
Transducers measure the angle between two voltage inputs.
External Input Range 100–130 Vac 100–130 Vac
Auxiliary Frequency Range None Required 50–500 Hz None Required 50–500 Hz
All 6330 and 6314 models have a ±180° phase detector which prevents ambiguous readings when Power Burden 3 VA Nominal 3 VA Nominal
Rated Output (RO)** ±1 mAdc for 5, 20, or 50 mAdc for ±1 mAdc for 5, 20, or 50 mAdc for
the input goes beyond full scale. The unique circuits use both zero-crossing times to measure the angle. Standard Calibration Std. Calibration, depending on Standard Calibration Std. Calibration, depending on
They use phase-locked loops to reduce the effects of noise interference and harmonics on the inputs. selected output range* selected output range*
Accuracy ±1° at 25° C
Phase Angle Range 0 to ± 45°, 0 to ±60°, 0 to ±75°, and 0 to ±180°
(without ambiguous readings)
Features Applications Outputs Temperature Effect on Accuracy ± 0.5° over ± 0.6° over ±0.5° over ±0.6° over
Temperature Range Temperature Range Temperature Range Temperature Range
Operating Temperature Range -20° C to +60° C -20° C to +50° C -20° C to +60° C -20° C to +50° C
◆ Angle ranges from ◆ SCADA ◆ 0 to ±1 mAdc
± 45° to ±180° Compliance Voltage 10 Vdc 10 Vdc
See Table 2 on page 66.
◆ Substation monitoring ◆ 1–3–5 mAdc Load 0–10,000 Ω
See Table 2 on page 66.
0–10,000 Ω
◆ Circuits reduce noise &
◆ Generating stations ◆ 4–12–20 mAdc Output Ripple Peak < 1% RO < 0.5% RO < 1% RO < 0.5% RO
harmonic interference
Response Time < 400 ms to 99% < 1 Second to 99% < 400 ms to 99% < 1 Second to 99%
◆ 10–30–50 mAdc
Standard Calibration Gain ±3% of Reading (minimum) ±20% of Span (minimum) ±3% of Reading (minimum) ±20% of Span (minimum)
Adjustments Zero ± 2% RO (minimum) ±5% of Zero Point (minimum) ± 2% RO (minimum) ±5% of Zero Point (minimum)
Frequency Nominal ± 3%
Stability (per year) ±1% RO, ± 1% of Span, ± 1% RO, ±1% of Span,
Noncumulative Noncumulative Noncumulative Noncumulative
Operating Humidity 0–95% Noncondensing
Also available in XLP modular, plug-in format for limited- Isolation Complete Complete Complete Complete
(Input/Output/Case) (Input/Output/Power/Case) (Input/Output/Case) (Input/Output/Power/Case)
space applications requiring large numbers of transducers.
Dielectric Withstand 1500 VRMS at 60 Hz
Surge Withstand ANSI/IEEE C37.90.1
◆ One or two phase angle or voltage angle transducers
Maximum Net Weight 2 lbs., 2 oz. (1 kg) 3 lbs., 8 oz. (1.6 kg) 2 lbs., 2 oz. (1 kg) 3 lbs., 8 oz. (1.6 kg)
in one module
Approximate Dimensions 4.4" W x 3.9" D x 4.7" H 7.0" W x 3.7" D x 5.6" H 4.4" W x 3.9" D x 4.7" H 7.0" W x 3.7" D x 5.6" H
◆ Two, four, or eight modules in one enclosure (excluding mounting plate) (112 mm x 99 mm x 119 mm) (178 mm x 94 mm x 142 mm) (112 mm x 99 mm x 119 mm) (178 mm x 94 mm x 142 mm)
Style II Case, see page 122 Style I Case, see page 122 Style II Case, see page 122 Style I Case, see page 122
◆ Easy to install, expand, or repair
* P-Option includes 1–3–5, 4–12–20, and 10–30–50 mAdc outputs. Specifications subject to change without notice.
◆ Convenient front-panel access for calibration and output- **For Phase Angle units, output is positive when current lags voltage.
current jacks available For Voltage Angle units, output is positive when “B” lags “A”.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
68 69
SCI Transducer Cat. 52-89(MTD) 68-69 1/9/02, 5:28 PM
SCIENTIFIC
Exceltronic AC Phase Angle SCIENTIFIC
Specifications
or Voltage Angle Transducers
COLUMBUS COLUMBUS
EXCELTRONIC AC PHASE ANGLE OR VOLTAGE ANGLE TRANSDUCERS
Model 6330 Phase Angle Trans- Specifications 0 to ±1 mAdc P-Option* 0 to ±1 mAdc P-Option*
ducers measure the phase angle (Phase Angle (Phase Angle (Voltage Angle (Voltage Angle
between one voltage and one Transducer) Transducer) Transducer) Transducer)
current input. These units are Current Nominal 5A
0.5–5 A
Input Range
more stable and accurate than the Overload Continuous 10 A N/A
Overload 1 Second/Hour 250 A
PF Series Phase Angle Transducers Burden/Element 0.2 VA (maximum) at 5 A
used for determining power factor; Voltage Nominal 120 V
Input Range 95–135 V
they also provide a wider range of
Exceltronic
Overload Continuous 150 V
measurement. Burden/Element 4 VA (maximum) at 120 V
Second Nominal 120 V
Voltage Range N/A 50–135 V
The Model 6314 Voltage Angle Input Overload Continuous 150 V
Burden/Element 2.2 VA (maximum) at 120 V
Transducers measure the angle between two voltage inputs.
External Input Range 100–130 Vac 100–130 Vac
Auxiliary Frequency Range None Required 50–500 Hz None Required 50–500 Hz
All 6330 and 6314 models have a ±180° phase detector which prevents ambiguous readings when Power Burden 3 VA Nominal 3 VA Nominal
Rated Output (RO)** ±1 mAdc for 5, 20, or 50 mAdc for ±1 mAdc for 5, 20, or 50 mAdc for
the input goes beyond full scale. The unique circuits use both zero-crossing times to measure the angle. Standard Calibration Std. Calibration, depending on Standard Calibration Std. Calibration, depending on
They use phase-locked loops to reduce the effects of noise interference and harmonics on the inputs. selected output range* selected output range*
Accuracy ±1° at 25° C
Phase Angle Range 0 to ± 45°, 0 to ±60°, 0 to ±75°, and 0 to ±180°
(without ambiguous readings)
Features Applications Outputs Temperature Effect on Accuracy ± 0.5° over ± 0.6° over ±0.5° over ±0.6° over
Temperature Range Temperature Range Temperature Range Temperature Range
Operating Temperature Range -20° C to +60° C -20° C to +50° C -20° C to +60° C -20° C to +50° C
◆ Angle ranges from ◆ SCADA ◆ 0 to ±1 mAdc
± 45° to ±180° Compliance Voltage 10 Vdc 10 Vdc
See Table 2 on page 66.
◆ Substation monitoring ◆ 1–3–5 mAdc Load 0–10,000 Ω
See Table 2 on page 66.
0–10,000 Ω
◆ Circuits reduce noise &
◆ Generating stations ◆ 4–12–20 mAdc Output Ripple Peak < 1% RO < 0.5% RO < 1% RO < 0.5% RO
harmonic interference
Response Time < 400 ms to 99% < 1 Second to 99% < 400 ms to 99% < 1 Second to 99%
◆ 10–30–50 mAdc
Standard Calibration Gain ±3% of Reading (minimum) ±20% of Span (minimum) ±3% of Reading (minimum) ±20% of Span (minimum)
Adjustments Zero ± 2% RO (minimum) ±5% of Zero Point (minimum) ± 2% RO (minimum) ±5% of Zero Point (minimum)
Frequency Nominal ± 3%
Stability (per year) ±1% RO, ± 1% of Span, ± 1% RO, ±1% of Span,
Noncumulative Noncumulative Noncumulative Noncumulative
Operating Humidity 0–95% Noncondensing
Also available in XLP modular, plug-in format for limited- Isolation Complete Complete Complete Complete
(Input/Output/Case) (Input/Output/Power/Case) (Input/Output/Case) (Input/Output/Power/Case)
space applications requiring large numbers of transducers.
Dielectric Withstand 1500 VRMS at 60 Hz
Surge Withstand ANSI/IEEE C37.90.1
◆ One or two phase angle or voltage angle transducers
Maximum Net Weight 2 lbs., 2 oz. (1 kg) 3 lbs., 8 oz. (1.6 kg) 2 lbs., 2 oz. (1 kg) 3 lbs., 8 oz. (1.6 kg)
in one module
Approximate Dimensions 4.4" W x 3.9" D x 4.7" H 7.0" W x 3.7" D x 5.6" H 4.4" W x 3.9" D x 4.7" H 7.0" W x 3.7" D x 5.6" H
◆ Two, four, or eight modules in one enclosure (excluding mounting plate) (112 mm x 99 mm x 119 mm) (178 mm x 94 mm x 142 mm) (112 mm x 99 mm x 119 mm) (178 mm x 94 mm x 142 mm)
Style II Case, see page 122 Style I Case, see page 122 Style II Case, see page 122 Style I Case, see page 122
◆ Easy to install, expand, or repair
* P-Option includes 1–3–5, 4–12–20, and 10–30–50 mAdc outputs. Specifications subject to change without notice.
◆ Convenient front-panel access for calibration and output- **For Phase Angle units, output is positive when current lags voltage.
current jacks available For Voltage Angle units, output is positive when “B” lags “A”.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
68 69
SCI Transducer Cat. 52-89(MTD) 68-69 1/9/02, 5:28 PM
Ordering Procedure Wiring Diagrams
Exceltronic AC Phase Angle Exceltronic AC Phase Angle
or Voltage Angle Transducers or Voltage Angle Transducers
ORDERING PROCEDURE WIRING DIAGRAMS FOR 0 to ±1 mAdc UNITS (Style II Case) AND P-OPTION UNITS (Style I Case)
Specify by base model number and appropriate selection or option suffixes in the order shown in the following example.
Angle Range External
Base Model No. Output Designator Options Aux. Power
0 to ±1 mAdc Units
0 to ± 1 mAdc Table 1 Table 2 Table 1
output 6330 60 Model 6330 Phase Angle Model 6314 Voltage Angle
LINE LINE
LINE L1 L2 L1 L2
P-Option L1 L2
outputs 6330 PA7-B 180
Consult
Exceltronic
factory DC
OUTPUT
DC
OUTPUT
for All P-Option units have 120 Vac - + - +
options external aux. power. Specify
other voltage, if required: 1 2 3 4 5 6 1 2 3 4 5 6
69 Vac Aux., 240 Vac Aux.,
277 Vac Aux., or 480 Vac Aux.
6330PA7-B-180
4-12-20 mAdc Phase Angle Transducer, 0 to ±180° input range.
P-Option Units
Table 1 Base Model Number Selection
Model 6330 Phase Angle Model 6314 Voltage Angle
Phase Angle VoltageAngle Angle Range Standard Calibration LINE LINE
LINE
Model No. Model No. Designator Power Factor Input Output L1 L2
L1 L2 L1 L2
Please consult the factory if you require any options with Phase Angle or Voltage Angle Transducers.
Adjust
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
70 71
SCI Transducer Cat. 52-89(MTD) 70-71 1/9/02, 5:28 PM
Ordering Procedure Wiring Diagrams
Exceltronic AC Phase Angle Exceltronic AC Phase Angle
or Voltage Angle Transducers or Voltage Angle Transducers
ORDERING PROCEDURE WIRING DIAGRAMS FOR 0 to ±1 mAdc UNITS (Style II Case) AND P-OPTION UNITS (Style I Case)
Specify by base model number and appropriate selection or option suffixes in the order shown in the following example.
Angle Range External
Base Model No. Output Designator Options Aux. Power
0 to ±1 mAdc Units
0 to ± 1 mAdc Table 1 Table 2 Table 1
output 6330 60 Model 6330 Phase Angle Model 6314 Voltage Angle
LINE LINE
LINE L1 L2 L1 L2
P-Option L1 L2
outputs 6330 PA7-B 180
Consult
Exceltronic
factory DC
OUTPUT
DC
OUTPUT
for All P-Option units have 120 Vac - + - +
options external aux. power. Specify
other voltage, if required: 1 2 3 4 5 6 1 2 3 4 5 6
69 Vac Aux., 240 Vac Aux.,
277 Vac Aux., or 480 Vac Aux.
6330PA7-B-180
4-12-20 mAdc Phase Angle Transducer, 0 to ±180° input range.
P-Option Units
Table 1 Base Model Number Selection
Model 6330 Phase Angle Model 6314 Voltage Angle
Phase Angle VoltageAngle Angle Range Standard Calibration LINE LINE
LINE
Model No. Model No. Designator Power Factor Input Output L1 L2
L1 L2 L1 L2
Please consult the factory if you require any options with Phase Angle or Voltage Angle Transducers.
Adjust
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
70 71
SCI Transducer Cat. 52-89(MTD) 70-71 1/9/02, 5:28 PM
SCIENTIFIC
Exceltronic AC Frequency Transducers SCIENTIFIC
Specifications
COLUMBUS COLUMBUS
EXCELTRONIC AC FREQUENCY TRANSDUCERS
Frequency transducers have an expanded-scale output. Specifications 0–1 mAdc P-Option*
A variety of calibrations may be ordered, or the user may (Frequency Transducer) (Frequency Transducer)
calibrate the transducer at the installation site to meet specific Voltage Nominal 120 V
requirements. Input Range 90–150 V
Overload Continuous 150 V
Burden/Element 2 VA (maximum) at 120 V
Customers can add series components and devices to the output External Input Range 100–130 Vac
Auxiliary Frequency Range None Required 50–500 Hz
signal circuit without having to recalibrate these transducers. Power Burden 3 VA Nominal
Series components and devices include: indicators, recorders,
Exceltronic
Rated Output (RO) 1 mAdc at Maximum Rated Frequency 5, 20, or 50 mAdc for Standard Calibration,
depending on selected output range*
resistors for alarms, and analog-to-digital pick-off points.
Accuracy ±0.02% of Center Frequency at 25° C ±0.05% of Center Frequency at 25° C
Temperature Effect on Accuracy ±0.0025% / ° C ±0.01% / ° C
Operating Temperature Range -20° C to +60° C -20° C to +50° C
Compliance Voltage 10 Vdc
See Table 2 on page 70.
Load 0–10,000 Ω
Output Ripple Peak < 1% RO < 0.25% of Span
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
72 73
SCI Transducer Cat. 52-89(MTD) 72-73 1/9/02, 5:28 PM
SCIENTIFIC
Exceltronic AC Frequency Transducers SCIENTIFIC
Specifications
COLUMBUS COLUMBUS
EXCELTRONIC AC FREQUENCY TRANSDUCERS
Frequency transducers have an expanded-scale output. Specifications 0–1 mAdc P-Option*
A variety of calibrations may be ordered, or the user may (Frequency Transducer) (Frequency Transducer)
calibrate the transducer at the installation site to meet specific Voltage Nominal 120 V
requirements. Input Range 90–150 V
Overload Continuous 150 V
Burden/Element 2 VA (maximum) at 120 V
Customers can add series components and devices to the output External Input Range 100–130 Vac
Auxiliary Frequency Range None Required 50–500 Hz
signal circuit without having to recalibrate these transducers. Power Burden 3 VA Nominal
Series components and devices include: indicators, recorders,
Exceltronic
Rated Output (RO) 1 mAdc at Maximum Rated Frequency 5, 20, or 50 mAdc for Standard Calibration,
depending on selected output range*
resistors for alarms, and analog-to-digital pick-off points.
Accuracy ±0.02% of Center Frequency at 25° C ±0.05% of Center Frequency at 25° C
Temperature Effect on Accuracy ±0.0025% / ° C ±0.01% / ° C
Operating Temperature Range -20° C to +60° C -20° C to +50° C
Compliance Voltage 10 Vdc
See Table 2 on page 70.
Load 0–10,000 Ω
Output Ripple Peak < 1% RO < 0.25% of Span
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
72 73
SCI Transducer Cat. 52-89(MTD) 72-73 1/9/02, 5:28 PM
Ordering Procedure
Exceltronic AC Frequency Ordering Procedure
Transducers Exceltronic AC Frequency Transducers
-RS -SM ** For external auxiliary power voltages other than 120 Vac, specify the voltage in the last position of the complete model number. (Example: 240 Vac Aux.)
P-Option
outputs 6281 PAN7 A4 -Z DC external auxiliary power available; see Special Options on page 128.
Specify
Exceltronic
voltage
If A2 is selected, leave space range If other than 120 Vac (std.), Table 4 Scaling Resistor (-RS) Option
blank; specify ext. aux. power specify ext. aux. power voltage:
voltage at end of model no. 69 Vac Aux., 240 Vac Aux., Option Description
277 Vac Aux., or 480 Vac Aux. -RS*** Scaling Resistor *** You must specify the desired output voltage:
For 0-1 mAdc units, specify range from 0-10 Vdc. Load impedance is 1 MΩ/Vdc
(minimum).
For P-Option units, specify range from 0-15 Vdc (PAN models) or 0-40 Vdc (PA
models). Load impedance is 200, 50, or 20 (kΩ/Vdc) (minimum) for units with
outputs of 5, 20, or 50 mAdc, respectively.
EXAMPLES: 6281B-RS-SM This information is not part of the model number, but must be provided to the
45-55 Hz, 0-1 mAdc Frequency Transducer; resistor scaling (converts current output to voltage output); seismic brace. factory when you place your order.
EXTERNAL
Table 2 Output Selection AC AUX. POWER
DC INPUT
OUTPUT
Compliance Voltage/ Maximum Open - +
0-1 mAdc output is DC
AC
P-Option Output Range Maximum Load Circuit Voltage INPUT
standard, and is specified OUTPUT
PAN6 1-5 mAdc 15 Vdc/3000 Ω 30 Vdc - +
by the Base Model 1 2 3 4 5 6
PAN7 4-20 mAdc 15 Vdc/750 Ω 30 Vdc
Numbers. For outputs
PAN8 10-50 mAdc 15 Vdc/300 Ω 30 Vdc 1 2 3 4
other than 0-1 mAdc,
indicate the appropriate PA6 1-5 mAdc 40 Vdc/8000 Ω 70 Vdc
P-Option in the "Output" PA7 4-20 mAdc 40 Vdc/2000 Ω 70 Vdc
position of the complete PA8 10-50 mAdc 30 Vdc/600 Ω 70 Vdc
model number.
Adjust
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
74 75
SCI Transducer Cat. 52-89(MTD) 74-75 1/9/02, 5:29 PM
Ordering Procedure
Exceltronic AC Frequency Ordering Procedure
Transducers Exceltronic AC Frequency Transducers
-RS -SM ** For external auxiliary power voltages other than 120 Vac, specify the voltage in the last position of the complete model number. (Example: 240 Vac Aux.)
P-Option
outputs 6281 PAN7 A4 -Z DC external auxiliary power available; see Special Options on page 128.
Specify
Exceltronic
voltage
If A2 is selected, leave space range If other than 120 Vac (std.), Table 4 Scaling Resistor (-RS) Option
blank; specify ext. aux. power specify ext. aux. power voltage:
voltage at end of model no. 69 Vac Aux., 240 Vac Aux., Option Description
277 Vac Aux., or 480 Vac Aux. -RS*** Scaling Resistor *** You must specify the desired output voltage:
For 0-1 mAdc units, specify range from 0-10 Vdc. Load impedance is 1 MΩ/Vdc
(minimum).
For P-Option units, specify range from 0-15 Vdc (PAN models) or 0-40 Vdc (PA
models). Load impedance is 200, 50, or 20 (kΩ/Vdc) (minimum) for units with
outputs of 5, 20, or 50 mAdc, respectively.
EXAMPLES: 6281B-RS-SM This information is not part of the model number, but must be provided to the
45-55 Hz, 0-1 mAdc Frequency Transducer; resistor scaling (converts current output to voltage output); seismic brace. factory when you place your order.
EXTERNAL
Table 2 Output Selection AC AUX. POWER
DC INPUT
OUTPUT
Compliance Voltage/ Maximum Open - +
0-1 mAdc output is DC
AC
P-Option Output Range Maximum Load Circuit Voltage INPUT
standard, and is specified OUTPUT
PAN6 1-5 mAdc 15 Vdc/3000 Ω 30 Vdc - +
by the Base Model 1 2 3 4 5 6
PAN7 4-20 mAdc 15 Vdc/750 Ω 30 Vdc
Numbers. For outputs
PAN8 10-50 mAdc 15 Vdc/300 Ω 30 Vdc 1 2 3 4
other than 0-1 mAdc,
indicate the appropriate PA6 1-5 mAdc 40 Vdc/8000 Ω 70 Vdc
P-Option in the "Output" PA7 4-20 mAdc 40 Vdc/2000 Ω 70 Vdc
position of the complete PA8 10-50 mAdc 30 Vdc/600 Ω 70 Vdc
model number.
Adjust
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
74 75
SCI Transducer Cat. 52-89(MTD) 74-75 1/9/02, 5:29 PM
SCIENTIFIC
Exceltronic Temperature Transducers SCIENTIFIC
Specifications
COLUMBUS COLUMBUS
EXCELTRONIC TEMPERATURE TRANSDUCERS
Scientific Columbus temperature transducers offer an accurate,
inexpensive method of measuring temperature through interface with Specifications 0–1 mAdc P-Option*
(Temperature Transducer) (Temperature Transducer)
a variety of RTD sensor types. These transducers have true current
outputs that will simplify your own calibrating or scaling networks, as External Input Range 90–130 Vac 100–130 Vac
50–500 Hz
Auxiliary Frequency Range 50–500 Hz
well as allow telemetering over long distances without line-drop error. Power Burden 3.5 VA Nominal 6 VA Nominal
To achieve higher accuracy, the true current output is compensated to Rated Output (RO) 1 mAdc at Maximum Calibrated Temperature 5, 20, or 50 mAdc for Standard Calibration,
depending on selected output range*
be proportional to true temperature changes, rather than merely the
Accuracy See Table 1 on page 74.
resistance change of the RTD.
Exceltronic
Temperature Effect on Accuracy ±0.015% / ° F ±0.02% / ° F
Operating Temperature Range -20° C to +60° C (-4° F to +140° F) -20° C to +50° C (-4° F to +122° F)
Compliance Voltage 10 Vdc
Open Circuit Voltage 16 Vdc See Table 2 on page 74.
Load 0–10,000 Ω
Output Ripple Peak < 1% RO < 0.25% of Span
Response Time < 50 ms to 99% < 1 Second to 99%
Standard Calibration Gain ±10% of Span (minimum) ± 20% of Span (minimum)
Adjustments Zero ±3% of Span (minimum) ±5% of Zero Point (minimum)
± 0.4% RO, Noncumulative ± 0.5% of Span, Noncumulative
Features Applications Outputs Stability (per year)
Operating Humidity 0–95% Noncondensing
Isolation Input/Power/Case and Output/Power/Case
◆ Compatible with nickel-iron, ◆ Process control ◆ 0–1 mAdc Dielectric Withstand 1500 VRMS at 60 Hz
platinum, & copper RTDs
◆ Substation monitoring ◆ 1–5 mAdc Surge Withstand ANSI/IEEE C37.90.1
◆ Exceptional reliability Maximum Net Weight 2 lbs., 1 oz. (0.9 kg) 3 lbs., 8 oz. (1.6 kg)
◆ Generating stations ◆ 4–20 mAdc
◆ Wide range of operating Approximate Model 3.3" W x 2.1" D x 4.1" H
◆ 10–50 mAdc Dimensions 9015N (84 mm x 53 mm x 104 mm)
temperatures (excluding Style III Case, see page 122 7.0" W x 3.7" D x 5.6" H
mounting plate) (178 mm x 94 mm x 142 mm)
◆ Excellent long-term stability Models 4.4" W x 3.9" D x 4.7" H Style I Case, see page 122
9016P & (112 mm x 99 mm x 119 mm)
9019C Style II Case, see page 122
*P-Option includes 1–5, 4–20, and 10–50 mAdc outputs. Specifications subject to change without notice.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
76 77
SCI Transducer Cat. 52-89(MTD) 76-77 1/9/02, 5:29 PM
SCIENTIFIC
Exceltronic Temperature Transducers SCIENTIFIC
Specifications
COLUMBUS COLUMBUS
EXCELTRONIC TEMPERATURE TRANSDUCERS
Scientific Columbus temperature transducers offer an accurate,
inexpensive method of measuring temperature through interface with Specifications 0–1 mAdc P-Option*
(Temperature Transducer) (Temperature Transducer)
a variety of RTD sensor types. These transducers have true current
outputs that will simplify your own calibrating or scaling networks, as External Input Range 90–130 Vac 100–130 Vac
50–500 Hz
Auxiliary Frequency Range 50–500 Hz
well as allow telemetering over long distances without line-drop error. Power Burden 3.5 VA Nominal 6 VA Nominal
To achieve higher accuracy, the true current output is compensated to Rated Output (RO) 1 mAdc at Maximum Calibrated Temperature 5, 20, or 50 mAdc for Standard Calibration,
depending on selected output range*
be proportional to true temperature changes, rather than merely the
Accuracy See Table 1 on page 74.
resistance change of the RTD.
Exceltronic
Temperature Effect on Accuracy ±0.015% / ° F ±0.02% / ° F
Operating Temperature Range -20° C to +60° C (-4° F to +140° F) -20° C to +50° C (-4° F to +122° F)
Compliance Voltage 10 Vdc
Open Circuit Voltage 16 Vdc See Table 2 on page 74.
Load 0–10,000 Ω
Output Ripple Peak < 1% RO < 0.25% of Span
Response Time < 50 ms to 99% < 1 Second to 99%
Standard Calibration Gain ±10% of Span (minimum) ± 20% of Span (minimum)
Adjustments Zero ±3% of Span (minimum) ±5% of Zero Point (minimum)
± 0.4% RO, Noncumulative ± 0.5% of Span, Noncumulative
Features Applications Outputs Stability (per year)
Operating Humidity 0–95% Noncondensing
Isolation Input/Power/Case and Output/Power/Case
◆ Compatible with nickel-iron, ◆ Process control ◆ 0–1 mAdc Dielectric Withstand 1500 VRMS at 60 Hz
platinum, & copper RTDs
◆ Substation monitoring ◆ 1–5 mAdc Surge Withstand ANSI/IEEE C37.90.1
◆ Exceptional reliability Maximum Net Weight 2 lbs., 1 oz. (0.9 kg) 3 lbs., 8 oz. (1.6 kg)
◆ Generating stations ◆ 4–20 mAdc
◆ Wide range of operating Approximate Model 3.3" W x 2.1" D x 4.1" H
◆ 10–50 mAdc Dimensions 9015N (84 mm x 53 mm x 104 mm)
temperatures (excluding Style III Case, see page 122 7.0" W x 3.7" D x 5.6" H
mounting plate) (178 mm x 94 mm x 142 mm)
◆ Excellent long-term stability Models 4.4" W x 3.9" D x 4.7" H Style I Case, see page 122
9016P & (112 mm x 99 mm x 119 mm)
9019C Style II Case, see page 122
*P-Option includes 1–5, 4–20, and 10–50 mAdc outputs. Specifications subject to change without notice.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
76 77
SCI Transducer Cat. 52-89(MTD) 76-77 1/9/02, 5:29 PM
Ordering Procedure Ordering Procedure
Exceltronic Temperature Transducers Exceltronic Temperature Transducers
Specify by base model number and appropriate selection or option suffixes in the order shown in the following example. Option Description *** You must specify the desired output voltage:
-RS Scaling Resistor*** For 0-1 mAdc units, specify range from 0-10 Vdc. Load impedance is 1 MΩ/Vdc (minimum).
Scaling External
For P-Option units, specify range from 0-15 Vdc (PAN models) or 0-40 Vdc (PA models). Load
Resistor Option Option Auxiliary impedance is 200, 50, or 20 (kΩ/Vdc) (minimum) for units with outputs of 5, 20, or 50 mAdc, respectively.
Base Model No. Output Option #1 #2 #3 Power
This information is not part of the model number, but must be provided to the factory when you place
Table 1 Table 2 Table 3 Table 4 Table 4 your order.
Exceltronic
(consult factory for specifications) Options on page 128. When ordering any special options, or
P-Option -SM Seismic Brace (available with 0-1 mAdc units) more than three options, you must first consult the factory for
Specify All units have 120 Vac pricing and delivery estimates.
outputs PAN7 output -Z (consult factory if you desire this option with
external aux. power.
voltage Specify other voltage, if a P-Option unit)
required: 69 Vac Aux., -Z Zero-Based Output Calibration (ex.: PA7-Z = 0-20 mAdc)
240 Vac Aux., 277 Vac Aux., (available only with P-Option units)
or 480 Vac Aux.
EXAMPLES: 9019C-RS-SM
0-1 mAdc Temperature Transducer for use with copper RTD, resistor scaling (converts current output to voltage output), WIRING DIAGRAMS FOR 0-1 mAdc UNITS (Styles III & II Cases) AND P-OPTION UNITS (Style I Case)
seismic brace.
* You must specify minimum and maximum input temperature values from within the Temperature Range shown for each RTD type.
The resulting temperature span (maximum temperature value minus minimum temperature value) must fall within the Temperature RTD
RTD
Span shown for each RTD type. (Example: Model 9015N temperature range = -195° F to -110° F and temperature span = 85° F.)
This information is not part of the model number, but must be provided to the factory when you place your order.
** You must specify the Temperature Coefficient of Resistance (TCR) of your 100 Ω platinum RTD probe—whether it is designed to the 9015N Temperature 9016P & 9019C Temperature
American Standard (TCR = .00392 Ω/Ω/°C), U.S. Industrial Standard (TCR = .00391 Ω/Ω/°C), or European Standard (TCR = .00385 Ω/Ω/°C). P-Option Units EXTERNAL
P-Option Units
This information is not part of the model number, but must be provided to the factory when you place your order. (Style I Case) AUX. POWER (Style I Case) EXTERNAL
RTD AUX. POWER
DC DC
OUTPUT OUTPUT
Table 2 Output Selection - + - +
Compliance Voltage/ Maximum Open 1 2 3 4 5 6 1 2 3 4
0-1 mAdc output is
P-Option Output Range Maximum Load Circuit Voltage
standard, and is specified
PAN6 1-5 mAdc 15 Vdc/3000 Ω 30 Vdc
by the Base Model
PAN7 4-20 mAdc 15 Vdc/750 Ω 30 Vdc
Numbers. For outputs
PAN8 10-50 mAdc 15 Vdc/300 Ω 30 Vdc
other than 0-1 mAdc,
indicate the appropriate PA6 1-5 mAdc 40 Vdc/8000 Ω 70 Vdc
P-Option in the "Output" PA7 4-20 mAdc 40 Vdc/2000 Ω 70 Vdc 5 6 7 8
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
78 79
SCI Transducer Cat. 52-89(MTD) 78-79 1/9/02, 5:29 PM
Ordering Procedure Ordering Procedure
Exceltronic Temperature Transducers Exceltronic Temperature Transducers
Specify by base model number and appropriate selection or option suffixes in the order shown in the following example. Option Description *** You must specify the desired output voltage:
-RS Scaling Resistor*** For 0-1 mAdc units, specify range from 0-10 Vdc. Load impedance is 1 MΩ/Vdc (minimum).
Scaling External
For P-Option units, specify range from 0-15 Vdc (PAN models) or 0-40 Vdc (PA models). Load
Resistor Option Option Auxiliary impedance is 200, 50, or 20 (kΩ/Vdc) (minimum) for units with outputs of 5, 20, or 50 mAdc, respectively.
Base Model No. Output Option #1 #2 #3 Power
This information is not part of the model number, but must be provided to the factory when you place
Table 1 Table 2 Table 3 Table 4 Table 4 your order.
Exceltronic
(consult factory for specifications) Options on page 128. When ordering any special options, or
P-Option -SM Seismic Brace (available with 0-1 mAdc units) more than three options, you must first consult the factory for
Specify All units have 120 Vac pricing and delivery estimates.
outputs PAN7 output -Z (consult factory if you desire this option with
external aux. power.
voltage Specify other voltage, if a P-Option unit)
required: 69 Vac Aux., -Z Zero-Based Output Calibration (ex.: PA7-Z = 0-20 mAdc)
240 Vac Aux., 277 Vac Aux., (available only with P-Option units)
or 480 Vac Aux.
EXAMPLES: 9019C-RS-SM
0-1 mAdc Temperature Transducer for use with copper RTD, resistor scaling (converts current output to voltage output), WIRING DIAGRAMS FOR 0-1 mAdc UNITS (Styles III & II Cases) AND P-OPTION UNITS (Style I Case)
seismic brace.
* You must specify minimum and maximum input temperature values from within the Temperature Range shown for each RTD type.
The resulting temperature span (maximum temperature value minus minimum temperature value) must fall within the Temperature RTD
RTD
Span shown for each RTD type. (Example: Model 9015N temperature range = -195° F to -110° F and temperature span = 85° F.)
This information is not part of the model number, but must be provided to the factory when you place your order.
** You must specify the Temperature Coefficient of Resistance (TCR) of your 100 Ω platinum RTD probe—whether it is designed to the 9015N Temperature 9016P & 9019C Temperature
American Standard (TCR = .00392 Ω/Ω/°C), U.S. Industrial Standard (TCR = .00391 Ω/Ω/°C), or European Standard (TCR = .00385 Ω/Ω/°C). P-Option Units EXTERNAL
P-Option Units
This information is not part of the model number, but must be provided to the factory when you place your order. (Style I Case) AUX. POWER (Style I Case) EXTERNAL
RTD AUX. POWER
DC DC
OUTPUT OUTPUT
Table 2 Output Selection - + - +
Compliance Voltage/ Maximum Open 1 2 3 4 5 6 1 2 3 4
0-1 mAdc output is
P-Option Output Range Maximum Load Circuit Voltage
standard, and is specified
PAN6 1-5 mAdc 15 Vdc/3000 Ω 30 Vdc
by the Base Model
PAN7 4-20 mAdc 15 Vdc/750 Ω 30 Vdc
Numbers. For outputs
PAN8 10-50 mAdc 15 Vdc/300 Ω 30 Vdc
other than 0-1 mAdc,
indicate the appropriate PA6 1-5 mAdc 40 Vdc/8000 Ω 70 Vdc
P-Option in the "Output" PA7 4-20 mAdc 40 Vdc/2000 Ω 70 Vdc 5 6 7 8
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
78 79
SCI Transducer Cat. 52-89(MTD) 78-79 1/9/02, 5:29 PM
MAV 2 SCIENTIFIC
Exceltronic XLP Modular
Plug-In Transducers
COLUMBUS
Meter Accuracy Verifier
MAV2 offers The XLP Series of transducers
Simplicity, Safety, and Accuracy — All In One is a family of power instrumenta-
Compact Portable Meter-testing Instrument. tion transducers in a compact,
modular plug-in form. XLP
The MAV2 Meter Accuracy Verifier is a straightforward, transducers are ideal where large
safe, and cost-effective instrument for on-site verification quantities of transducers are
and calibration of self-contained meter accuracy. Every required, but space is limited.
aspect of the MAV2’s design and construction, from its
menu-driven operation to the lightweight and compact XLP transducers feature three
package, is focused on the needs of the customer service enclosure widths to accomodate two, four, or eight modules.
representative or field technician—including accuracy Each module consists of two parts: a plug-in assembly and a back-panel assembly.
assurance traceable to NIST.
For current inputs, the current transformers are located on the back-panel assembly so the current inputs
The small size and light weight of the MAV2 Verifier are not opened when the plug-in assembly is removed. New or additional plug-ins or back panels can be
make it possible for the customer service representative added in the field.
XLP Plug-In
or technician to carry it in their vehicle, and bring it to
distant locations such as apartment building meter rooms, MAV2 SPECIFICATIONS
without any special effort. Full-load testing capability to Watthour Accuracy
Modules Available Features Applications
50 amps eliminates the need for larger test instruments, ±0.1 % of Reading (0.05% typical)
Operating Temperature Range
and the affordability of the MAV2 makes it practical -20° C to +60° C (Temperature Effect on Accuracy is 30 ppm/°C)
◆ Current ◆ Modular concept & ◆ Substations
to have many units in the field. Storage Temperature Range compact design save
-30° C to +80° C ◆ Voltage ◆ Generating stations
transducer panel space
Operating Voltage (Autoranging)
108–264 V (120 Volt L-G Nominal) ◆ Combined Current/Voltage ◆ SCADA
The MAV2 Verifier can be used by relatively “less Test Currents
◆ Up to six transducers in
Full Load 15, 30, or 50 A ◆ Expanded-Scale Voltage one module
technically trained” customer service personnel as Light Load 1.5, 3, or 5 A
well as trained meter technicians. Designed for safety, Meter Power Interlocks ◆ Watt ◆ Two, four, or eight
the MAV2 incorporates an electrically interlocked
Redundant interlocks, activated by meter insertion, provide dead-front
access to MAV2 meter adapter socket. ◆ Var
modules in one enclosure Outputs
Display
deadfront design in the meter socket adapter, insuring ◆ Lower installation costs
Two lines of 16 characters each, 0.3-inch character height, ◆ Combined Watt/Var
that there are no live circuits in the adapter socket Internally backlit
◆ Easy to install ◆ 0 to ±1 mAdc
Keyboard ◆ Phase Angle
until the meter is installed. Anyone qualified to replace Three sealed keys (UP, DOWN, and ENTER) control all operations ◆ 1–5 or 1–3–5 mAdc
including Start and Stop of test. ◆ Convenient front-panel
a meter in the field is capable of using the MAV2. ◆ Voltage Angle
Interconnecting Cable access ◆ 4–20 or 4–12–20 mAdc
Control unit is connected to the meter adapter socket by a spiral cable.
Length range is two to seven feet. ◆ Frequency
Disk Rotation Sensor
Optional photo optical disk rotation sensor uses reflective measurement. ◆ Temperature (RTD)
Connecting the sensor automatically sets up the meter for rotation
sensor operation.
Pendant Snap Switch
Optional snap switch is provided on a 30-inch cord. Plugging in the snap
switch automatically configures the unit for snap-switch operation.
Calibration and Certification
Traceable to NIST. User calibration can be performed using the infrared
optical pulse port. Calibration is digital, via the front-panel display and
Headquarters keyboard, and requires the installation of an internal hardware key as
50 Fordham Road 255 North Union Street well as a special keyboard sequence.
CER
Wilmington, MA 01887 Rochester, NY 14605 Size
TIFIE
XLP Plug-In
or technician to carry it in their vehicle, and bring it to
distant locations such as apartment building meter rooms, MAV2 SPECIFICATIONS
without any special effort. Full-load testing capability to Watthour Accuracy
Modules Available Features Applications
50 amps eliminates the need for larger test instruments, ±0.1 % of Reading (0.05% typical)
Operating Temperature Range
and the affordability of the MAV2 makes it practical -20° C to +60° C (Temperature Effect on Accuracy is 30 ppm/°C)
◆ Current ◆ Modular concept & ◆ Substations
to have many units in the field. Storage Temperature Range compact design save
-30° C to +80° C ◆ Voltage ◆ Generating stations
transducer panel space
Operating Voltage (Autoranging)
108–264 V (120 Volt L-G Nominal) ◆ Combined Current/Voltage ◆ SCADA
The MAV2 Verifier can be used by relatively “less Test Currents
◆ Up to six transducers in
Full Load 15, 30, or 50 A ◆ Expanded-Scale Voltage one module
technically trained” customer service personnel as Light Load 1.5, 3, or 5 A
well as trained meter technicians. Designed for safety, Meter Power Interlocks ◆ Watt ◆ Two, four, or eight
the MAV2 incorporates an electrically interlocked
Redundant interlocks, activated by meter insertion, provide dead-front
access to MAV2 meter adapter socket. ◆ Var
modules in one enclosure Outputs
Display
deadfront design in the meter socket adapter, insuring ◆ Lower installation costs
Two lines of 16 characters each, 0.3-inch character height, ◆ Combined Watt/Var
that there are no live circuits in the adapter socket Internally backlit
◆ Easy to install ◆ 0 to ±1 mAdc
Keyboard ◆ Phase Angle
until the meter is installed. Anyone qualified to replace Three sealed keys (UP, DOWN, and ENTER) control all operations ◆ 1–5 or 1–3–5 mAdc
including Start and Stop of test. ◆ Convenient front-panel
a meter in the field is capable of using the MAV2. ◆ Voltage Angle
Interconnecting Cable access ◆ 4–20 or 4–12–20 mAdc
Control unit is connected to the meter adapter socket by a spiral cable.
Length range is two to seven feet. ◆ Frequency
Disk Rotation Sensor
Optional photo optical disk rotation sensor uses reflective measurement. ◆ Temperature (RTD)
Connecting the sensor automatically sets up the meter for rotation
sensor operation.
Pendant Snap Switch
Optional snap switch is provided on a 30-inch cord. Plugging in the snap
switch automatically configures the unit for snap-switch operation.
Calibration and Certification
Traceable to NIST. User calibration can be performed using the infrared
optical pulse port. Calibration is digital, via the front-panel display and
Headquarters keyboard, and requires the installation of an internal hardware key as
50 Fordham Road 255 North Union Street well as a special keyboard sequence.
CER
Wilmington, MA 01887 Rochester, NY 14605 Size
TIFIE
Specifications 0–1 mAdc Amps P-Option* Amps 0–1 mAdc Volts P-Option* Volts Specifications 0–1 mAdc Volts P-Option* Volts
(Current Transducer) (Current Transducer) (Voltage Transducer) (Voltage Transducer) (Expanded-Scale Voltage Transducer) (Expanded-Scale Voltage Transducer)
Current Nominal 5A 5A Voltage Span/Range Any 20–60 V span between 90–150 V (customer specified)**
Input Calibrating Range 0–5 A 0–5 A Input Overload Continuous 150 V
Range with Linearity 0–10 A 0–6 A Burden/Element 2 VA (maximum) at 120 V
N/A N/A
Overload Continuous 20 A 20 A
Overload 1 Second/Hour 250 A 250 A External Input Range 100–130 Vac
Burden/Element 0.25 VA (maximum) at 5 A 0.25 VA (maximum) at 5 A Auxiliary Frequency Range None Required 50–500 Hz
Power Burden 3 VA Nominal
Voltage Nominal 120 V 120 V
Input Calibrating Range 0–150 V 0–150 V Rated Output (RO) 0 mAdc at low end of range (customer specified) 1 or 4 mAdc at low end of range (customer specified)
Range with Linearity N/A N/A 0–150 V 0–165 V 1 mAdc at high end of range (customer specified) 5 or 20 mAdc at high end of range (customer specified)
Overload Continuous 180 V 180 V Accuracy ±0.25% of Input Voltage for 60 Hz
Burden/Element 2.2 VA (maximum) at 120 V 2.2 VA (maximum) at 120 V
Temperature Effect on Accuracy ±0.007% / ° C ±0.01% / ° C
External Input Range 100–130 Vac 100–130 Vac
Auxiliary Frequency Range None Required 50–500 Hz None Required 50–500 Hz Operating Temperature Range -20° C to +60° C -20° C to +50° C
Power Burden/Element 3 VA Nominal 3 VA Nominal
Compliance Voltage 10 Vdc 25 Vdc
Rated Output (RO) = 1 mAdc for 5 or 20 mAdc for 1 mAdc for 5 or 20 mAdc for 0–10,000 Ω
Load 0–5,000 Ω for 1–5 mAdc units
5 A or 150 V/Element Standard Calibration Std. Calibration, depending on Standard Calibration Std. Calibration, depending on 0–1,250 Ω for 4–20 mAdc units
selected output range* selected output range*
Output Ripple Peak < 2.5% RO < 2.5% of Span
Accuracy Standard ±0.25% RO ±0.25% RO
± 0.25% of Span ± 0.25% of Span
A4 Models ±0.1% RO ±0.1% RO Response Time < 400 ms to 99%
Temperature Effect on Accuracy ± 0.01% / ° C ± 0.015% / ° C ±0.01% / ° C ±0.015% / ° C Standard Calibration Gain ±5% of Span ±20% of Span
XLP Plug-In
Adjustments Zero ±5% of Span ±5% of Span
Operating Temperature Range -20° C to +60° C -20° C to +50° C -20° C to +60° C -20° C to +50° C
Compliance Voltage 10 Vdc 25 Vdc 10 Vdc 25 Vdc Frequency Range 55–65 Hz
Load 0–10,000 Ω 0–5,000 W for 1–5 mAdc units 0–10,000 Ω 0–5,000 W for 1–5 mAdc units Stability (per year) ± 0.25% of Input Voltage, Noncumulative
0–1,250 W for 4–20 mAdc units 0–1,250 W for 4–20 mAdc units Operating Humidity 0–95% Noncondensing
Output Ripple Peak < 0.25% RO < 0.25% of Span < 0.25% RO < 0.25% of Span Isolation Complete (Input/Output/Case) Complete (Input/Output/Power/Case)
Response Time < 400 ms to 99% Dielectric Withstand 1500 VRMS at 60 Hz
Standard Calibration Gain ± 10% of Reading (minimum) ±20% of Span (minimum) ± 10% of Reading (minimum) ±20% of Span (minimum) Surge Withstand ANSI/IEEE C37.90.1
Adjustments Zero None Required ±5% of Zero Point (minimum) None Required ±5% of Zero Point (minimum)
Maximum Net Weight Weights vary by model; consult factory.
Frequency Range 50–500 Hz (specify nominal)
Approximate Dimensions See enclosure diagrams on page 85.
Stability (per year) ±0.1% RO, ±0.15% of Span, ± 0.25% RO, ± 0.3% of Span,
Noncumulative Noncumulative Noncumulative Noncumulative * P-Option includes 1–5 and 4–20 mAdc outputs. Specifications subject to change without notice.
**Minimum span must be at least 18% of low-end voltage.
Operating Humidity 0–95% Noncondensing
Isolation Complete Complete Complete Complete
(Input/Output/Case) (Input/Output/Power/Case) (Input/Output/Case) (Input/Output/Power/Case)
Dielectric Withstand 1500 VRMS at 60 Hz
Surge Withstand ANSI/IEEE C37.90.1
Maximum Net Weight Weights vary by model; consult factory.
Approximate Dimensions See enclosure diagrams on page 85.
*P-Option includes 1–5 and 4–20 mAdc outputs. Not available on all models. Specifications subject to change without notice.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
82 83
SCI Transducer Cat. 52-89(MTD) 82-83 1/9/02, 5:29 PM
Specifications Specifications
Exceltronic XLP AC Average-Sensing Exceltronic XLP AC Expanded-
Current or Voltage Transducers Scale Voltage Transducers
Specifications 0–1 mAdc Amps P-Option* Amps 0–1 mAdc Volts P-Option* Volts Specifications 0–1 mAdc Volts P-Option* Volts
(Current Transducer) (Current Transducer) (Voltage Transducer) (Voltage Transducer) (Expanded-Scale Voltage Transducer) (Expanded-Scale Voltage Transducer)
Current Nominal 5A 5A Voltage Span/Range Any 20–60 V span between 90–150 V (customer specified)**
Input Calibrating Range 0–5 A 0–5 A Input Overload Continuous 150 V
Range with Linearity 0–10 A 0–6 A Burden/Element 2 VA (maximum) at 120 V
N/A N/A
Overload Continuous 20 A 20 A
Overload 1 Second/Hour 250 A 250 A External Input Range 100–130 Vac
Burden/Element 0.25 VA (maximum) at 5 A 0.25 VA (maximum) at 5 A Auxiliary Frequency Range None Required 50–500 Hz
Power Burden 3 VA Nominal
Voltage Nominal 120 V 120 V
Input Calibrating Range 0–150 V 0–150 V Rated Output (RO) 0 mAdc at low end of range (customer specified) 1 or 4 mAdc at low end of range (customer specified)
Range with Linearity N/A N/A 0–150 V 0–165 V 1 mAdc at high end of range (customer specified) 5 or 20 mAdc at high end of range (customer specified)
Overload Continuous 180 V 180 V Accuracy ±0.25% of Input Voltage for 60 Hz
Burden/Element 2.2 VA (maximum) at 120 V 2.2 VA (maximum) at 120 V
Temperature Effect on Accuracy ±0.007% / ° C ±0.01% / ° C
External Input Range 100–130 Vac 100–130 Vac
Auxiliary Frequency Range None Required 50–500 Hz None Required 50–500 Hz Operating Temperature Range -20° C to +60° C -20° C to +50° C
Power Burden/Element 3 VA Nominal 3 VA Nominal
Compliance Voltage 10 Vdc 25 Vdc
Rated Output (RO) = 1 mAdc for 5 or 20 mAdc for 1 mAdc for 5 or 20 mAdc for 0–10,000 Ω
Load 0–5,000 Ω for 1–5 mAdc units
5 A or 150 V/Element Standard Calibration Std. Calibration, depending on Standard Calibration Std. Calibration, depending on 0–1,250 Ω for 4–20 mAdc units
selected output range* selected output range*
Output Ripple Peak < 2.5% RO < 2.5% of Span
Accuracy Standard ±0.25% RO ±0.25% RO
± 0.25% of Span ± 0.25% of Span
A4 Models ±0.1% RO ±0.1% RO Response Time < 400 ms to 99%
Temperature Effect on Accuracy ± 0.01% / ° C ± 0.015% / ° C ±0.01% / ° C ±0.015% / ° C Standard Calibration Gain ±5% of Span ±20% of Span
XLP Plug-In
Adjustments Zero ±5% of Span ±5% of Span
Operating Temperature Range -20° C to +60° C -20° C to +50° C -20° C to +60° C -20° C to +50° C
Compliance Voltage 10 Vdc 25 Vdc 10 Vdc 25 Vdc Frequency Range 55–65 Hz
Load 0–10,000 Ω 0–5,000 W for 1–5 mAdc units 0–10,000 Ω 0–5,000 W for 1–5 mAdc units Stability (per year) ± 0.25% of Input Voltage, Noncumulative
0–1,250 W for 4–20 mAdc units 0–1,250 W for 4–20 mAdc units Operating Humidity 0–95% Noncondensing
Output Ripple Peak < 0.25% RO < 0.25% of Span < 0.25% RO < 0.25% of Span Isolation Complete (Input/Output/Case) Complete (Input/Output/Power/Case)
Response Time < 400 ms to 99% Dielectric Withstand 1500 VRMS at 60 Hz
Standard Calibration Gain ± 10% of Reading (minimum) ±20% of Span (minimum) ± 10% of Reading (minimum) ±20% of Span (minimum) Surge Withstand ANSI/IEEE C37.90.1
Adjustments Zero None Required ±5% of Zero Point (minimum) None Required ±5% of Zero Point (minimum)
Maximum Net Weight Weights vary by model; consult factory.
Frequency Range 50–500 Hz (specify nominal)
Approximate Dimensions See enclosure diagrams on page 85.
Stability (per year) ±0.1% RO, ±0.15% of Span, ± 0.25% RO, ± 0.3% of Span,
Noncumulative Noncumulative Noncumulative Noncumulative * P-Option includes 1–5 and 4–20 mAdc outputs. Specifications subject to change without notice.
**Minimum span must be at least 18% of low-end voltage.
Operating Humidity 0–95% Noncondensing
Isolation Complete Complete Complete Complete
(Input/Output/Case) (Input/Output/Power/Case) (Input/Output/Case) (Input/Output/Power/Case)
Dielectric Withstand 1500 VRMS at 60 Hz
Surge Withstand ANSI/IEEE C37.90.1
Maximum Net Weight Weights vary by model; consult factory.
Approximate Dimensions See enclosure diagrams on page 85.
*P-Option includes 1–5 and 4–20 mAdc outputs. Not available on all models. Specifications subject to change without notice.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
82 83
SCI Transducer Cat. 52-89(MTD) 82-83 1/9/02, 5:29 PM
Specifications Specifications
Exceltronic XLP AC Watt Exceltronic XLP Combined
or Var Transducers AC Watt/Var Transducers
Specifications 0 to ±1 mAdc Watts P-Option* Watts 0 to ±1 mAdc Vars P-Option* Vars Specifications 0 to ±1 mAdc Watts P-Option* Watts 0 to ±1 mAdc Vars P-Option* Vars
(Watt Transducer) (Watt Transducer) (Var Transducer) (Var Transducer) (Combined Watt/Var (Combined Watt/Var (Combined Watt/Var (Combined Watt/Var
Transducer) Transducer) Transducer) Transducer)
Current Nominal 5A
Input Range** 0–10 A Current Nominal 5A
Overload Continuous 20 A Input Range** 0–10 A
Overload 1 Second/Hour 250 A Overload Continuous 20 A
Burden/Element 0.2 VA (maximum) at 5 A Overload 1 Second/Hour 250 A
Burden/Element 0.2 VA (maximum) at 5 A
Voltage Nominal 120 V
Input Range** 0–150 V Voltage Nominal 120 V
Overload Continuous 200 V Input Range** 0–150 V
Burden/Element 0.02 VA (maximum) at 120 V Overload Continuous 200 V
Burden/Element 0.02 VA (maximum) at 120 V
External Input Range 85–135 Vac 100–130 Vac 85–135 Vac 100–130 Vac
Auxiliary Frequency Range 50–500 Hz 50–500 Hz 50–500 Hz 50–500 Hz External Input Range 85–135 Vac 100–130 Vac 85–135 Vac 100–130 Vac
Power Burden 3 VA Nominal 5 VA Nominal 3 VA Nominal 5 VA Nominal Auxiliary Frequency Range 50–500 Hz 50–500 Hz 50–500 Hz 50–500 Hz
Power Burden 3 VA Nominal 7 VA Nominal 3 VA Nominal 7 VA Nominal
Rated Output (RO) = ±1 mAdc for 5 or 20 mAdc for ±1 mAdc for 5 or 20 mAdc for
500 Watts or Vars/Element Standard Calibration Std. Calibration, depending on Standard Calibration Std. Calibration, depending on Rated Output (RO) = ±1 mAdc for 5 or 20 mAdc for ±1 mAdc for 5 or 20 mAdc for
selected output range* selected output range* 500 Watts or Vars/Element Standard Calibration Std. Calibration, depending on Standard Calibration Std. Calibration, depending on
selected output range* selected output range*
Accuracy ±(0.2% Reading + 0.01% RO) ±(0.2% Reading + 0.05% RO) ±(0.2% Reading + 0.02% RO) ±(0.3% Reading + 0.05% RO)
at 0–200% RO at 0–120% RO at 0–200% RO at 0–120% RO Accuracy ±(0.2% Reading + 0.01% RO) ±(0.2% Reading + 0.05% RO) ±(0.2% Reading + 0.02% RO) ±(0.3% Reading + 0.05% RO)
at 0–200% RO at 0–120% RO at 0–200% RO at 0–120% RO
Temperature Effect on Accuracy ± 0.005% / ° C ±0.0075% / ° C ±0.009% / ° C ±0.012% / ° C
Temperature Effect on Accuracy ±0.005% / ° C ± 0.0075% / ° C ± 0.009% / ° C ± 0.012% / ° C
Operating Temperature Range -20° C to +70° C -20° C to +50° C -20° C to +60° C -20° C to +50° C
XLP Plug-In
Operating Temperature Range -20° C to +60° C -20° C to +50° C -20° C to +60° C -20° C to +50° C
Compliance Voltage 10 Vdc 25 Vdc 10 Vdc 25 Vdc
Compliance Voltage 10 Vdc 25 Vdc 10 Vdc 25 Vdc
Load 0–10,000 Ω 0–5,000 Ω for 0–10,000 Ω 0–5,000 Ω for
1–5/1–3–5 mAdc units 1–5/1–3–5 mAdc units Load 0–10,000 Ω 0–5,000 Ω for 0–10,000 Ω 0–5,000 Ω for
0–1,250 Ω for 0–1,250 Ω for 1–5/1–3–5 mAdc units 1–5/1–3–5 mAdc units
4–20/4–12–20 mAdc units 4–20/4–12–20 mAdc units 0–1,250 Ω for 0–1,250 Ω for
4–20/4–12–20 mAdc units 4–20/4–12–20 mAdc units
Output Ripple Peak < 0.5% RO
Output Ripple Peak < 0.5% RO
Response Time < 400 ms to 99%
Response Time < 400 ms to 99%
Power Factor Any
Power Factor Any
PF Effect on Accuracy ±0.1% VA (maximum) ±0.15% VA (maximum)
PF Effect on Accuracy ±0.1% VA (maximum) ±0.15% VA (maximum)
Standard Calibration Gain ± 2% of Reading (minimum) ±20% of Span (minimum) ± 2% of Reading (minimum) ±20% of Span (minimum)
Adjustments Zero None Required ±5% of Zero Point (minimum) None Required ±5% of Zero Point (minimum) Standard Calibration Gain ±2% of Reading (minimum) ±20% of Span (minimum) ±2% of Reading (minimum) ±20% of Span (minimum)
Adjustments Zero None Required ±5% of Zero Point (minimum) None Required ±5% of Zero Point (minimum)
Frequency Range 58–62 Hz 60 Hz
Frequency 60 Hz
Stability (per year) ±0.1% RO, ±0.15% of Span, ± 0.2% RO, ±0.25% of Span,
Noncumulative Noncumulative Noncumulative Noncumulative Stability (per year) ±0.1% RO, ± 0.15% of Span, ±0.2% RO, ±0.25% of Span,
Noncumulative Noncumulative Noncumulative Noncumulative
Operating Humidity 0–95% Noncondensing
Operating Humidity 0–95% Noncondensing
Isolation Complete (Input/Output/Power/Case)
Isolation Complete (Input/Output/Power/Case)
Dielectric Withstand 1500 VRMS at 60 Hz
Dielectric Withstand 1500 VRMS at 60 Hz
Surge Withstand ANSI/IEEE C37.90.1
Surge Withstand ANSI/IEEE C37.90.1
Maximum Net Weight Weights vary by model; consult factory.
Maximum Net Weight Weights vary by model; consult factory.
Approximate Dimensions See enclosure diagrams on page 85.
Approximate Dimensions See enclosure diagrams on page 85.
Overrange with Linearity 500–1000 Watts/Element 500–600 Watts/Element 500–1000 Vars/Element 500–600 Vars/Element
Overrange with Linearity 500–1000 Watts/Element 500–600 Watts/Element 500–1000 Vars/Element 500–600 Vars/Element
No additional error within voltage compliance. Reduce load resistance as required.
No additional error within voltage compliance. Reduce load resistance as required.
* P-Option includes 1–5/1–3–5 and 4–20/4–12–20 mAdc outputs. Specifications subject to change without notice.
* P-Option includes 1–5/1–3–5 and 4–20/4–12–20 mAdc outputs. Not available on XLPWV10-30 model. Specifications subject to change without notice.
**Total input not to exceed 200% of standard-calibration watts or vars on units with 0 to ±1 mAdc output.
**Total input not to exceed 200% of standard-calibration watts and vars on units with 0 to ±1 mAdc output.
Total input not to exceed 120% of standard-calibration watts or vars on units with P-Option outputs.
Total input not to exceed 120% of standard-calibration watts and vars on units with P-Option outputs.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
84 85
SCI Transducer Cat. 52-89(MTD) 84-85 1/9/02, 5:29 PM
Specifications Specifications
Exceltronic XLP AC Watt Exceltronic XLP Combined
or Var Transducers AC Watt/Var Transducers
Specifications 0 to ±1 mAdc Watts P-Option* Watts 0 to ±1 mAdc Vars P-Option* Vars Specifications 0 to ±1 mAdc Watts P-Option* Watts 0 to ±1 mAdc Vars P-Option* Vars
(Watt Transducer) (Watt Transducer) (Var Transducer) (Var Transducer) (Combined Watt/Var (Combined Watt/Var (Combined Watt/Var (Combined Watt/Var
Transducer) Transducer) Transducer) Transducer)
Current Nominal 5A
Input Range** 0–10 A Current Nominal 5A
Overload Continuous 20 A Input Range** 0–10 A
Overload 1 Second/Hour 250 A Overload Continuous 20 A
Burden/Element 0.2 VA (maximum) at 5 A Overload 1 Second/Hour 250 A
Burden/Element 0.2 VA (maximum) at 5 A
Voltage Nominal 120 V
Input Range** 0–150 V Voltage Nominal 120 V
Overload Continuous 200 V Input Range** 0–150 V
Burden/Element 0.02 VA (maximum) at 120 V Overload Continuous 200 V
Burden/Element 0.02 VA (maximum) at 120 V
External Input Range 85–135 Vac 100–130 Vac 85–135 Vac 100–130 Vac
Auxiliary Frequency Range 50–500 Hz 50–500 Hz 50–500 Hz 50–500 Hz External Input Range 85–135 Vac 100–130 Vac 85–135 Vac 100–130 Vac
Power Burden 3 VA Nominal 5 VA Nominal 3 VA Nominal 5 VA Nominal Auxiliary Frequency Range 50–500 Hz 50–500 Hz 50–500 Hz 50–500 Hz
Power Burden 3 VA Nominal 7 VA Nominal 3 VA Nominal 7 VA Nominal
Rated Output (RO) = ±1 mAdc for 5 or 20 mAdc for ±1 mAdc for 5 or 20 mAdc for
500 Watts or Vars/Element Standard Calibration Std. Calibration, depending on Standard Calibration Std. Calibration, depending on Rated Output (RO) = ±1 mAdc for 5 or 20 mAdc for ±1 mAdc for 5 or 20 mAdc for
selected output range* selected output range* 500 Watts or Vars/Element Standard Calibration Std. Calibration, depending on Standard Calibration Std. Calibration, depending on
selected output range* selected output range*
Accuracy ±(0.2% Reading + 0.01% RO) ±(0.2% Reading + 0.05% RO) ±(0.2% Reading + 0.02% RO) ±(0.3% Reading + 0.05% RO)
at 0–200% RO at 0–120% RO at 0–200% RO at 0–120% RO Accuracy ±(0.2% Reading + 0.01% RO) ±(0.2% Reading + 0.05% RO) ±(0.2% Reading + 0.02% RO) ±(0.3% Reading + 0.05% RO)
at 0–200% RO at 0–120% RO at 0–200% RO at 0–120% RO
Temperature Effect on Accuracy ± 0.005% / ° C ±0.0075% / ° C ±0.009% / ° C ±0.012% / ° C
Temperature Effect on Accuracy ±0.005% / ° C ± 0.0075% / ° C ± 0.009% / ° C ± 0.012% / ° C
Operating Temperature Range -20° C to +70° C -20° C to +50° C -20° C to +60° C -20° C to +50° C
XLP Plug-In
Operating Temperature Range -20° C to +60° C -20° C to +50° C -20° C to +60° C -20° C to +50° C
Compliance Voltage 10 Vdc 25 Vdc 10 Vdc 25 Vdc
Compliance Voltage 10 Vdc 25 Vdc 10 Vdc 25 Vdc
Load 0–10,000 Ω 0–5,000 Ω for 0–10,000 Ω 0–5,000 Ω for
1–5/1–3–5 mAdc units 1–5/1–3–5 mAdc units Load 0–10,000 Ω 0–5,000 Ω for 0–10,000 Ω 0–5,000 Ω for
0–1,250 Ω for 0–1,250 Ω for 1–5/1–3–5 mAdc units 1–5/1–3–5 mAdc units
4–20/4–12–20 mAdc units 4–20/4–12–20 mAdc units 0–1,250 Ω for 0–1,250 Ω for
4–20/4–12–20 mAdc units 4–20/4–12–20 mAdc units
Output Ripple Peak < 0.5% RO
Output Ripple Peak < 0.5% RO
Response Time < 400 ms to 99%
Response Time < 400 ms to 99%
Power Factor Any
Power Factor Any
PF Effect on Accuracy ±0.1% VA (maximum) ±0.15% VA (maximum)
PF Effect on Accuracy ±0.1% VA (maximum) ±0.15% VA (maximum)
Standard Calibration Gain ± 2% of Reading (minimum) ±20% of Span (minimum) ± 2% of Reading (minimum) ±20% of Span (minimum)
Adjustments Zero None Required ±5% of Zero Point (minimum) None Required ±5% of Zero Point (minimum) Standard Calibration Gain ±2% of Reading (minimum) ±20% of Span (minimum) ±2% of Reading (minimum) ±20% of Span (minimum)
Adjustments Zero None Required ±5% of Zero Point (minimum) None Required ±5% of Zero Point (minimum)
Frequency Range 58–62 Hz 60 Hz
Frequency 60 Hz
Stability (per year) ±0.1% RO, ±0.15% of Span, ± 0.2% RO, ±0.25% of Span,
Noncumulative Noncumulative Noncumulative Noncumulative Stability (per year) ±0.1% RO, ± 0.15% of Span, ±0.2% RO, ±0.25% of Span,
Noncumulative Noncumulative Noncumulative Noncumulative
Operating Humidity 0–95% Noncondensing
Operating Humidity 0–95% Noncondensing
Isolation Complete (Input/Output/Power/Case)
Isolation Complete (Input/Output/Power/Case)
Dielectric Withstand 1500 VRMS at 60 Hz
Dielectric Withstand 1500 VRMS at 60 Hz
Surge Withstand ANSI/IEEE C37.90.1
Surge Withstand ANSI/IEEE C37.90.1
Maximum Net Weight Weights vary by model; consult factory.
Maximum Net Weight Weights vary by model; consult factory.
Approximate Dimensions See enclosure diagrams on page 85.
Approximate Dimensions See enclosure diagrams on page 85.
Overrange with Linearity 500–1000 Watts/Element 500–600 Watts/Element 500–1000 Vars/Element 500–600 Vars/Element
Overrange with Linearity 500–1000 Watts/Element 500–600 Watts/Element 500–1000 Vars/Element 500–600 Vars/Element
No additional error within voltage compliance. Reduce load resistance as required.
No additional error within voltage compliance. Reduce load resistance as required.
* P-Option includes 1–5/1–3–5 and 4–20/4–12–20 mAdc outputs. Specifications subject to change without notice.
* P-Option includes 1–5/1–3–5 and 4–20/4–12–20 mAdc outputs. Not available on XLPWV10-30 model. Specifications subject to change without notice.
**Total input not to exceed 200% of standard-calibration watts or vars on units with 0 to ±1 mAdc output.
**Total input not to exceed 200% of standard-calibration watts and vars on units with 0 to ±1 mAdc output.
Total input not to exceed 120% of standard-calibration watts or vars on units with P-Option outputs.
Total input not to exceed 120% of standard-calibration watts and vars on units with P-Option outputs.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
84 85
SCI Transducer Cat. 52-89(MTD) 84-85 1/9/02, 5:29 PM
Specifications
Exceltronic XLP AC Phase Angle Specifications
or Voltage Angle Transducers Exceltronic XLP AC Frequency Transducers
XLP Plug-In
Accuracy ±1° at 25° C Standard Calibration Gain ±5% of Span (minimum) ± 20% of Span (minimum)
Adjustments Zero ±10% of Span (minimum) ±5% of Zero Point (minimum)
Phase Angle Range 0 to ± 45°, 0 to ±60°, 0 to ±75°, and 0 to ±180° Stability (per year) ±0.02% of Center Frequency ±0.04% of Center Frequency
(without ambiguous readings)
Temperature Effect on Accuracy ± 0.5° ± 0.6° ±0.5° ±0.6° Operating Humidity 0–95% Noncondensing
Operating Temperature Range -20° C to +60° C -20° C to +50° C -20° C to +60° C -20° C to +50° C Isolation Complete (Input/Output/Case) Complete (Input/Output/Power/Case)
Compliance Voltage 10 Vdc 25 Vdc 10 Vdc 25 Vdc Dielectric Withstand 1500 VRMS at 60 Hz
Load 0–10,000 Ω 0–5,000 Ω for 1–3–5 mAdc units 0–10,000 Ω 0–5,000 Ω for 1–3–5 mAdc units Surge Withstand ANSI/IEEE C37.90.1
0–1,250 Ω for 0–1,250 Ω for Maximum Net Weight Weights vary by model; consult factory.
4–12–20 mAdc units 4–12–20 mAdc units
Approximate Dimensions See enclosure diagrams on page 85.
Output Ripple Peak < 1% RO
*P-Option includes 1–5 and 4–20 mAdc outputs. Specifications subject to change without notice.
Response Time < 400 ms to 99%
Standard Calibration Gain ±3% of Reading (minimum) ±20% of Span (minimum) ±3% of Reading (minimum) ±20% of Span (minimum)
Adjustments Zero ± 2% RO (minimum) ±5% of Zero Point (minimum) ±2% RO (minimum) ±5% of Zero Point (minimum)
Frequency Nominal ± 3%
Stability (per year) ±1% RO, ± 1% of Span, ± 1% RO, ±1% of Span,
Noncumulative Noncumulative Noncumulative Noncumulative
Operating Humidity 0–95% Noncondensing
Isolation Complete Complete Complete Complete
(Input/Output/Case) (Input/Output/Power/Case) (Input/Output/Case) (Input/Output/Power/Case)
Dielectric Withstand 1500 VRMS at 60 Hz
Surge Withstand ANSI/IEEE C37.90.1
Maximum Net Weight Weights vary by model; consult factory.
Approximate Dimensions See enclosure diagrams on page 85.
*P-Option includes 1–3–5 and 4–12–20 mAdc outputs. Specifications subject to change without notice.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
86 87
SCI Transducer Cat. 52-89(MTD) 86-87 1/9/02, 5:29 PM
Specifications
Exceltronic XLP AC Phase Angle Specifications
or Voltage Angle Transducers Exceltronic XLP AC Frequency Transducers
XLP Plug-In
Accuracy ±1° at 25° C Standard Calibration Gain ±5% of Span (minimum) ± 20% of Span (minimum)
Adjustments Zero ±10% of Span (minimum) ±5% of Zero Point (minimum)
Phase Angle Range 0 to ± 45°, 0 to ±60°, 0 to ±75°, and 0 to ±180° Stability (per year) ±0.02% of Center Frequency ±0.04% of Center Frequency
(without ambiguous readings)
Temperature Effect on Accuracy ± 0.5° ± 0.6° ±0.5° ±0.6° Operating Humidity 0–95% Noncondensing
Operating Temperature Range -20° C to +60° C -20° C to +50° C -20° C to +60° C -20° C to +50° C Isolation Complete (Input/Output/Case) Complete (Input/Output/Power/Case)
Compliance Voltage 10 Vdc 25 Vdc 10 Vdc 25 Vdc Dielectric Withstand 1500 VRMS at 60 Hz
Load 0–10,000 Ω 0–5,000 Ω for 1–3–5 mAdc units 0–10,000 Ω 0–5,000 Ω for 1–3–5 mAdc units Surge Withstand ANSI/IEEE C37.90.1
0–1,250 Ω for 0–1,250 Ω for Maximum Net Weight Weights vary by model; consult factory.
4–12–20 mAdc units 4–12–20 mAdc units
Approximate Dimensions See enclosure diagrams on page 85.
Output Ripple Peak < 1% RO
*P-Option includes 1–5 and 4–20 mAdc outputs. Specifications subject to change without notice.
Response Time < 400 ms to 99%
Standard Calibration Gain ±3% of Reading (minimum) ±20% of Span (minimum) ±3% of Reading (minimum) ±20% of Span (minimum)
Adjustments Zero ± 2% RO (minimum) ±5% of Zero Point (minimum) ±2% RO (minimum) ±5% of Zero Point (minimum)
Frequency Nominal ± 3%
Stability (per year) ±1% RO, ± 1% of Span, ± 1% RO, ±1% of Span,
Noncumulative Noncumulative Noncumulative Noncumulative
Operating Humidity 0–95% Noncondensing
Isolation Complete Complete Complete Complete
(Input/Output/Case) (Input/Output/Power/Case) (Input/Output/Case) (Input/Output/Power/Case)
Dielectric Withstand 1500 VRMS at 60 Hz
Surge Withstand ANSI/IEEE C37.90.1
Maximum Net Weight Weights vary by model; consult factory.
Approximate Dimensions See enclosure diagrams on page 85.
*P-Option includes 1–3–5 and 4–12–20 mAdc outputs. Specifications subject to change without notice.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
86 87
SCI Transducer Cat. 52-89(MTD) 86-87 1/9/02, 5:29 PM
Specifications Enclosure Drawings
Exceltronic XLP Temperature Exceltronic XLP Modular
Transducers Plug-In Transducers
ENCLOSURE DRAWINGS
Specifications 0–1 mAdc P-Option*
(Temperature Transducer) (Temperature Transducer)
2-Module Enclosure 4-Module Enclosure
External Input Range 90–130 Vac 100–130 Vac
Auxiliary Frequency Range 50–500 Hz 50–500 Hz
Power Burden 3.5 VA Nominal 5.5 VA Nominal
6.57"
Rated Output (RO) 1 mAdc at Maximum Calibrated Temperature 5 or 20 mAdc for Standard Calibration, (166.89 mm) 10.70" (271.78 mm)
depending on selected output range* 5.82"
(147.83 mm) 9.94" (252.48 mm)
Accuracy Nickel-Iron 0.8% of Span
Platinum 0.5% of Span
Copper 0.8% of Span
Temperature Effect on Accuracy ± 0.015% / ° F ± 0.017% / ° F
4.00" 7.00" 4.00" 7.00"
Operating Temperature Range -20° C to +60° C (-4° F to +140° F) -20° C to +50° C (-4° F to +122° F) (101.60 mm) (177.80 mm) (101.60 mm) (177.80 mm)
Compliance Voltage 10 Vdc 25 Vdc
Open Circuit Voltage 16 Vdc 30 Vdc
Load 0–10,000 Ω 0–5,000 Ω for 1–5 mAdc units 4.52" 1.50"
0–1,250 Ω for 4–20 mAdc units MAX. (38.10 mm)
8.65" MAX. 1.50"
(38.10 mm)
(114.81 mm) (219.71 mm)
Output Ripple Peak < 1% RO < 1% of Span (WIDTH BEHIND FRONT)
(WIDTH BEHIND FRONT)
Response Time < 50 ms to 99%
Standard Calibration Gain ± 5% of Span (minimum) ±20% of Span (minimum)
Adjustments Zero ± 3% of Span (minimum) ± 5% of Zero Point (minimum)
Stability (per year) ±0.4% RO, Noncumulative ±0.5% of Span, Noncumulative
Operating Humidity 0–95% Noncondensing 8-Module Enclosure (front view)
Isolation Input/Power/Case and Output/Power/Case
Dielectric Withstand 1500 VRMS at 60 Hz
Surge Withstand ANSI/IEEE C37.90.1 18.95" (481.33 mm)
Maximum Net Weight Weights vary by model; consult factory. 18.19" (462.03 mm)
Approximate Dimensions See enclosure diagrams on page 85.
*P-Option includes 1–5 and 4–20 mAdc outputs. Specifications subject to change without notice.
Instrumentation
4.00" 7.00"
(101.60 mm) (177.80 mm)
Enclosure
Module FRONT OF MODULE
0.061" (1.55 mm)
(side view) BEHIND THIS LINE
1.19"
(30.23 mm)
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
88 89
SCI Transducer Cat. 52-89(MTD) 88-89 1/9/02, 5:29 PM
Specifications Enclosure Drawings
Exceltronic XLP Temperature Exceltronic XLP Modular
Transducers Plug-In Transducers
ENCLOSURE DRAWINGS
Specifications 0–1 mAdc P-Option*
(Temperature Transducer) (Temperature Transducer)
2-Module Enclosure 4-Module Enclosure
External Input Range 90–130 Vac 100–130 Vac
Auxiliary Frequency Range 50–500 Hz 50–500 Hz
Power Burden 3.5 VA Nominal 5.5 VA Nominal
6.57"
Rated Output (RO) 1 mAdc at Maximum Calibrated Temperature 5 or 20 mAdc for Standard Calibration, (166.89 mm) 10.70" (271.78 mm)
depending on selected output range* 5.82"
(147.83 mm) 9.94" (252.48 mm)
Accuracy Nickel-Iron 0.8% of Span
Platinum 0.5% of Span
Copper 0.8% of Span
Temperature Effect on Accuracy ± 0.015% / ° F ± 0.017% / ° F
4.00" 7.00" 4.00" 7.00"
Operating Temperature Range -20° C to +60° C (-4° F to +140° F) -20° C to +50° C (-4° F to +122° F) (101.60 mm) (177.80 mm) (101.60 mm) (177.80 mm)
Compliance Voltage 10 Vdc 25 Vdc
Open Circuit Voltage 16 Vdc 30 Vdc
Load 0–10,000 Ω 0–5,000 Ω for 1–5 mAdc units 4.52" 1.50"
0–1,250 Ω for 4–20 mAdc units MAX. (38.10 mm)
8.65" MAX. 1.50"
(38.10 mm)
(114.81 mm) (219.71 mm)
Output Ripple Peak < 1% RO < 1% of Span (WIDTH BEHIND FRONT)
(WIDTH BEHIND FRONT)
Response Time < 50 ms to 99%
Standard Calibration Gain ± 5% of Span (minimum) ±20% of Span (minimum)
Adjustments Zero ± 3% of Span (minimum) ± 5% of Zero Point (minimum)
Stability (per year) ±0.4% RO, Noncumulative ±0.5% of Span, Noncumulative
Operating Humidity 0–95% Noncondensing 8-Module Enclosure (front view)
Isolation Input/Power/Case and Output/Power/Case
Dielectric Withstand 1500 VRMS at 60 Hz
Surge Withstand ANSI/IEEE C37.90.1 18.95" (481.33 mm)
Maximum Net Weight Weights vary by model; consult factory. 18.19" (462.03 mm)
Approximate Dimensions See enclosure diagrams on page 85.
*P-Option includes 1–5 and 4–20 mAdc outputs. Specifications subject to change without notice.
Instrumentation
4.00" 7.00"
(101.60 mm) (177.80 mm)
Enclosure
Module FRONT OF MODULE
0.061" (1.55 mm)
(side view) BEHIND THIS LINE
1.19"
(30.23 mm)
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
88 89
SCI Transducer Cat. 52-89(MTD) 88-89 1/9/02, 5:29 PM
Ordering Procedure Ordering Procedure
Exceltronic XLP Modular Exceltronic XLP Modular
Plug-In Transducers Plug-In Transducers
Instrumentation
Position 8 Quantity of Blanks 10184-001 XLPZ260 Two 60 Hz Frequency Units XLP26 Two Platinum Temperature Units
XLPZ2400 Two 400 Hz Frequency Units XLP29 Two Copper Temperature Units
Table 1 Current or Voltage Base Model Numbers Table 6 Output Selection See Table 1 on page 74 for additional ordering information.
CURRENT OR VOLTAGE TRANSDUCERS IN ONE PLUG-IN MODULE COMBINED CURRENT/VOLTAGE TRANSDUCERS IN ONE PLUG-IN MODULE
P-Option Output Range Compliance Voltage Maximum Load Max. Open Circuit Voltage
0 to ±1 mAdc output is standard,
Current Model No. Description Combined Current/ P6** 1-5 mAdc 25 Vdc 5000 Ω 30 Vdc
and is specified by the Base
XLPC One Current Unit Voltage Model No. Description Model Numbers. For outputs P7** 4-20 mAdc 25 Vdc 1250 Ω 30 Vdc
XLPC2 Two Current Units XLPCE One Current Unit/One Voltage Unit other than 0 to ±1 mAdc, P6-B*** 1-3-5 mAdc 25 Vdc 5000 Ω 30 Vdc
XLPC3 Three Current Units XLPC2E Two Current Units/One Voltage Unit indicate the appropriate P7-B*** 4-12-20 mAdc 25 Vdc 1250 Ω 30 Vdc
XLPC3E* Three Current Units/One Voltage Unit P-Option in the "Output" position
Voltage Model No. Description XLPCE2 One Current Unit/Two Voltage Units ** P6 and P7 options are available for all XLP types except Phase Angle and Voltage Angle.
of the complete model number.
XLPE One Voltage Unit XLPCE3* One Current Unit/Three Voltage Units
XLPE2 Two Voltage Units XLPCE4* One Current Unit/Four Voltage Units
*** P6-B and P7-B options are available for all XLP types except Current, Voltage, Frequency, and Temperature.
XLPE3 Three Voltage Units Table 7 Options
XLPC2E2* Two Current Units/Two Voltage Units
XLPE4* Four Voltage Units XLPC2E3* Two Current Units/Three Voltage Units Option Description **** Most XLP transducers come standard with internal auxiliary power (A4 option).
Expanded-Scale XLPC2E4* Two Current Units/Four Voltage Units -1 240 V Input If you require external auxiliary power, the A2 option designator should come
Voltage Model No. Description XLPC3E2* Three Current Units/Two Voltage Units -5 10 A Input before any other options in the complete model number.
XLPEX One Voltage Unit (with 90-150 V XLPC3E3* Three Current Units/Three Voltage Units A2**** External Auxiliary Power (120 Vac std.)
expanded-scale option) -FA Front Access If you require additional options not shown here, please consult the factory.
XLPEX2 Two Voltage Units (with 90-150 V
expanded-scale option) Combined Watt/Watthour or Var/Varhour and Combined Phase/Voltage Angle transducers are available in XLP format on special order.
XLPEX3 Three Voltage Units (with 90-150 V Please consult the factory for more information.
* Not available with 1-5 or 4-20 mAdc outputs.
expanded-scale option)
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
90 91
SCI Transducer Cat 90-134(MTD) 90-91 1/9/02, 5:32 PM
Ordering Procedure Ordering Procedure
Exceltronic XLP Modular Exceltronic XLP Modular
Plug-In Transducers Plug-In Transducers
Instrumentation
Position 8 Quantity of Blanks 10184-001 XLPZ260 Two 60 Hz Frequency Units XLP26 Two Platinum Temperature Units
XLPZ2400 Two 400 Hz Frequency Units XLP29 Two Copper Temperature Units
Table 1 Current or Voltage Base Model Numbers Table 6 Output Selection See Table 1 on page 74 for additional ordering information.
CURRENT OR VOLTAGE TRANSDUCERS IN ONE PLUG-IN MODULE COMBINED CURRENT/VOLTAGE TRANSDUCERS IN ONE PLUG-IN MODULE
P-Option Output Range Compliance Voltage Maximum Load Max. Open Circuit Voltage
0 to ±1 mAdc output is standard,
Current Model No. Description Combined Current/ P6** 1-5 mAdc 25 Vdc 5000 Ω 30 Vdc
and is specified by the Base
XLPC One Current Unit Voltage Model No. Description Model Numbers. For outputs P7** 4-20 mAdc 25 Vdc 1250 Ω 30 Vdc
XLPC2 Two Current Units XLPCE One Current Unit/One Voltage Unit other than 0 to ±1 mAdc, P6-B*** 1-3-5 mAdc 25 Vdc 5000 Ω 30 Vdc
XLPC3 Three Current Units XLPC2E Two Current Units/One Voltage Unit indicate the appropriate P7-B*** 4-12-20 mAdc 25 Vdc 1250 Ω 30 Vdc
XLPC3E* Three Current Units/One Voltage Unit P-Option in the "Output" position
Voltage Model No. Description XLPCE2 One Current Unit/Two Voltage Units ** P6 and P7 options are available for all XLP types except Phase Angle and Voltage Angle.
of the complete model number.
XLPE One Voltage Unit XLPCE3* One Current Unit/Three Voltage Units
XLPE2 Two Voltage Units XLPCE4* One Current Unit/Four Voltage Units
*** P6-B and P7-B options are available for all XLP types except Current, Voltage, Frequency, and Temperature.
XLPE3 Three Voltage Units Table 7 Options
XLPC2E2* Two Current Units/Two Voltage Units
XLPE4* Four Voltage Units XLPC2E3* Two Current Units/Three Voltage Units Option Description **** Most XLP transducers come standard with internal auxiliary power (A4 option).
Expanded-Scale XLPC2E4* Two Current Units/Four Voltage Units -1 240 V Input If you require external auxiliary power, the A2 option designator should come
Voltage Model No. Description XLPC3E2* Three Current Units/Two Voltage Units -5 10 A Input before any other options in the complete model number.
XLPEX One Voltage Unit (with 90-150 V XLPC3E3* Three Current Units/Three Voltage Units A2**** External Auxiliary Power (120 Vac std.)
expanded-scale option) -FA Front Access If you require additional options not shown here, please consult the factory.
XLPEX2 Two Voltage Units (with 90-150 V
expanded-scale option) Combined Watt/Watthour or Var/Varhour and Combined Phase/Voltage Angle transducers are available in XLP format on special order.
XLPEX3 Three Voltage Units (with 90-150 V Please consult the factory for more information.
* Not available with 1-5 or 4-20 mAdc outputs.
expanded-scale option)
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
90 91
SCI Transducer Cat 90-134(MTD) 90-91 1/9/02, 5:32 PM
Wiring Diagrams Wiring Diagrams
Exceltronic XLP Modular Exceltronic XLP Modular
Plug-In Transducers Plug-In Transducers
OUTPUTS
8 * OUTPUT LOAD RANGE
9 + OUTPUT 1 0-1 mAdc
1 1 OUTPUT 1 *
OUTPUTS
OUTPUT LOAD RANGE LOAD 0-10K OHMS
+ 1-5 mA 0-5K OHMS
OUTPUT 2 * 2 8 8 * OUTPUT LOAD RANGE
OUTPUTS
OUTPUTS
2 1-5 mA 0-5K OHMS
LOAD 0-10K OHMS 9 9
10 11 + OUTPUT 4 0-1 mAdc
4-20 mA 0-1250 OHMS
*
4
LOAD 0-10K OHMS
2 OUTPUT 2 *
XLP Plug-In
OUTPUT 3
11
+ 12
3 10 10
OUTPUT 3 0-1 mAdc
3
11
+
LOAD 0-10K OHMS
13 11
12 EXTERNAL OUTPUT 5 0-1 mAdc
AUX. PWR. 5
AUX. POWER LOAD 0-10K OHMS
-007 14 12 12
-005
-008 -013
Models E, E2, E3 Voltage Models EP7A2, E2P7A2, E3P7A2 Voltage with External Aux. Power
Models EX, EX2, EX3 Expanded-Scale Voltage Models Z1P7A2, Z2P7A2 Frequency with External Aux. Power Models CE3, C2E, C2E2, C2E3, C3E, C3E2, C3E3 Current/Voltage Models CE4, C2E4, Current/Voltage
Models Z1, Z2 Frequency (Consult factory for drawing of Expanded-Scale Voltage with External Aux. Power) Model E4 Voltage
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
92 93
SCI Transducer Cat 90-134(MTD) 92-93 1/9/02, 5:32 PM
Wiring Diagrams Wiring Diagrams
Exceltronic XLP Modular Exceltronic XLP Modular
Plug-In Transducers Plug-In Transducers
OUTPUTS
8 * OUTPUT LOAD RANGE
9 + OUTPUT 1 0-1 mAdc
1 1 OUTPUT 1 *
OUTPUTS
OUTPUT LOAD RANGE LOAD 0-10K OHMS
+ 1-5 mA 0-5K OHMS
OUTPUT 2 * 2 8 8 * OUTPUT LOAD RANGE
OUTPUTS
OUTPUTS
2 1-5 mA 0-5K OHMS
LOAD 0-10K OHMS 9 9
10 11 + OUTPUT 4 0-1 mAdc
4-20 mA 0-1250 OHMS
*
4
LOAD 0-10K OHMS
2 OUTPUT 2 *
XLP Plug-In
OUTPUT 3
11
+ 12
3 10 10
OUTPUT 3 0-1 mAdc
3
11
+
LOAD 0-10K OHMS
13 11
12 EXTERNAL OUTPUT 5 0-1 mAdc
AUX. PWR. 5
AUX. POWER LOAD 0-10K OHMS
-007 14 12 12
-005
-008 -013
Models E, E2, E3 Voltage Models EP7A2, E2P7A2, E3P7A2 Voltage with External Aux. Power
Models EX, EX2, EX3 Expanded-Scale Voltage Models Z1P7A2, Z2P7A2 Frequency with External Aux. Power Models CE3, C2E, C2E2, C2E3, C3E, C3E2, C3E3 Current/Voltage Models CE4, C2E4, Current/Voltage
Models Z1, Z2 Frequency (Consult factory for drawing of Expanded-Scale Voltage with External Aux. Power) Model E4 Voltage
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
92 93
SCI Transducer Cat 90-134(MTD) 92-93 1/9/02, 5:32 PM
Wiring Diagrams Wiring Diagrams
Exceltronic XLP Modular Exceltronic XLP Modular
Plug-In Transducers Plug-In Transducers
1-Element Watt, Var, Watt/Var 1-Element Watt, Var, Watt/Var with External Aux. Power 2-Element Watt, Var, Watt/Var 2-Element Watt, Var, Watt/Var with External Aux. Power
LINE LINE LINE LINE
A B A B A B C A B C
1
1 1 1 AMPS IA
IA AMPS IA AMPS IA AMPS
2
2 2 2
3
3 3 3 AMPS IC
IC AMPS 4
4 4 4
5
5 5 VOLTS E AB
5
EA E AB 6
VOLTS EA VOLTS VOLTS
6 6 6
7
VOLTS E CB
7 7 LOAD 7 8
AUX. PWR. EXTERNAL E CB VOLTS
AUX. POWER LOAD
8 8 8 9
LOAD EXTERNAL AUX. PWR.
LOAD AUX. POWER
9 9 9 10
VAR VAR OUTPUT * * OUTPUT LOAD RANGE VAR VAR OUTPUT * * OUTPUT LOAD RANGE VAR VAR OUTPUT * * OUTPUT LOAD RANGE
+ +
OUTPUTS
OUTPUTS
+
OUTPUTS
10 OUTPUT LOAD RANGE OUTPUT LOAD RANGE 10 OUTPUT LOAD RANGE
10 11
0 to + 1 mA 0-10K OHMS 0 to + 1 mA 0 to + 1 mA 0-10K OHMS
* OUTPUT LOAD RANGE
XLP Plug-In
0-10K OHMS
1-5 mA 0-5K OHMS 1-5 mA 0-5K OHMS 1-5 mA 0-5K OHMS VAR OUTPUT * VAR
OUTPUTS
11
+ 1-3-5 mA 0-5K OHMS + 1-3-5 mA 0-5K OHMS
11
+ 1-3-5 mA 0-5K OHMS OUTPUT
0 to + 1 mA
LOAD RANGE
12 +
4-20 mA 0-1250 OHMS 11 4-20 mA 0-1250 OHMS 4-20 mA 0-1250 OHMS 0-10K OHMS
4-12-20 mA 0-1250 OHMS 4-12-20 mA 0-1250 OHMS 1-5 mA 0-5K OHMS
WATT WATT OUTPUT * WATT WATT OUTPUT * 4-12-20 mA 0-1250 OHMS WATT WATT OUTPUT * 1-3-5 mA 0-5K OHMS
+
12 12 12 4-20 mA 0-1250 OHMS 13
4-12-20 mA 0-1250 OHMS WATT OUTPUT * WATT
-001 -004 -003 14
-001
11/2-Element Watt, Var, Watt/Var 11/2-Element Watt, Var, Watt/Var with External Aux. Power 21/2-Element Watt, Var, Watt/Var 21/2-Element Watt, Var, Watt/Var with External Aux. Power
LINE
LINE LINE LINE
A B C N
A B C A B C A B C N
1 1 13
1 1 IA
AMPS AMPS IA
IA AMPS IA AMPS
2
2 2 2 14
3
3 15
3 3 AMPS IB
AMPS IB * OUTPUT LOAD RANGE
IC AMPS IC AMPS 4 OUTPUT LOAD RANGE
4 16 0 to + 1 mA 0-10K OHMS
4 4 1-5 mA 0-5K OHMS
5 1-3-5 mA 0-5K OHMS
OUTPUTS
OUTPUTS
11
+ 1-3-5 mA 0-5K OHMS
11
1-3-5 mA 0-5K OHMS OUTPUT LOAD RANGE
12 + WATT OUTPUT * VAR OUTPUT *
4-20 mA 0-1250 OHMS 4-20 mA 0-1250 OHMS 0 to + 1 mA 0-10K OHMS
12 24
WATT WATT OUTPUT * 4-12-20 mA 0-1250 OHMS WATT WATT OUTPUT * 4-12-20 mA 0-1250 OHMS 1-5 mA 0-5K OHMS
12 12
1-3-5 mA
4-20 mA
0-5K OHMS
0-1250 OHMS
13 +
4-12-20 mA 0-1250 OHMS WATT OUTPUT * WATT
-011
-002 -005 14
-002
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
94 95
SCI Transducer Cat 90-134(MTD) 94-95 1/9/02, 5:32 PM
Wiring Diagrams Wiring Diagrams
Exceltronic XLP Modular Exceltronic XLP Modular
Plug-In Transducers Plug-In Transducers
1-Element Watt, Var, Watt/Var 1-Element Watt, Var, Watt/Var with External Aux. Power 2-Element Watt, Var, Watt/Var 2-Element Watt, Var, Watt/Var with External Aux. Power
LINE LINE LINE LINE
A B A B A B C A B C
1
1 1 1 AMPS IA
IA AMPS IA AMPS IA AMPS
2
2 2 2
3
3 3 3 AMPS IC
IC AMPS 4
4 4 4
5
5 5 VOLTS E AB
5
EA E AB 6
VOLTS EA VOLTS VOLTS
6 6 6
7
VOLTS E CB
7 7 LOAD 7 8
AUX. PWR. EXTERNAL E CB VOLTS
AUX. POWER LOAD
8 8 8 9
LOAD EXTERNAL AUX. PWR.
LOAD AUX. POWER
9 9 9 10
VAR VAR OUTPUT * * OUTPUT LOAD RANGE VAR VAR OUTPUT * * OUTPUT LOAD RANGE VAR VAR OUTPUT * * OUTPUT LOAD RANGE
+ +
OUTPUTS
OUTPUTS
+
OUTPUTS
10 OUTPUT LOAD RANGE OUTPUT LOAD RANGE 10 OUTPUT LOAD RANGE
10 11
0 to + 1 mA 0-10K OHMS 0 to + 1 mA 0 to + 1 mA 0-10K OHMS
* OUTPUT LOAD RANGE
XLP Plug-In
0-10K OHMS
1-5 mA 0-5K OHMS 1-5 mA 0-5K OHMS 1-5 mA 0-5K OHMS VAR OUTPUT * VAR
OUTPUTS
11
+ 1-3-5 mA 0-5K OHMS + 1-3-5 mA 0-5K OHMS
11
+ 1-3-5 mA 0-5K OHMS OUTPUT
0 to + 1 mA
LOAD RANGE
12 +
4-20 mA 0-1250 OHMS 11 4-20 mA 0-1250 OHMS 4-20 mA 0-1250 OHMS 0-10K OHMS
4-12-20 mA 0-1250 OHMS 4-12-20 mA 0-1250 OHMS 1-5 mA 0-5K OHMS
WATT WATT OUTPUT * WATT WATT OUTPUT * 4-12-20 mA 0-1250 OHMS WATT WATT OUTPUT * 1-3-5 mA 0-5K OHMS
+
12 12 12 4-20 mA 0-1250 OHMS 13
4-12-20 mA 0-1250 OHMS WATT OUTPUT * WATT
-001 -004 -003 14
-001
11/2-Element Watt, Var, Watt/Var 11/2-Element Watt, Var, Watt/Var with External Aux. Power 21/2-Element Watt, Var, Watt/Var 21/2-Element Watt, Var, Watt/Var with External Aux. Power
LINE
LINE LINE LINE
A B C N
A B C A B C A B C N
1 1 13
1 1 IA
AMPS AMPS IA
IA AMPS IA AMPS
2
2 2 2 14
3
3 15
3 3 AMPS IB
AMPS IB * OUTPUT LOAD RANGE
IC AMPS IC AMPS 4 OUTPUT LOAD RANGE
4 16 0 to + 1 mA 0-10K OHMS
4 4 1-5 mA 0-5K OHMS
5 1-3-5 mA 0-5K OHMS
OUTPUTS
OUTPUTS
11
+ 1-3-5 mA 0-5K OHMS
11
1-3-5 mA 0-5K OHMS OUTPUT LOAD RANGE
12 + WATT OUTPUT * VAR OUTPUT *
4-20 mA 0-1250 OHMS 4-20 mA 0-1250 OHMS 0 to + 1 mA 0-10K OHMS
12 24
WATT WATT OUTPUT * 4-12-20 mA 0-1250 OHMS WATT WATT OUTPUT * 4-12-20 mA 0-1250 OHMS 1-5 mA 0-5K OHMS
12 12
1-3-5 mA
4-20 mA
0-5K OHMS
0-1250 OHMS
13 +
4-12-20 mA 0-1250 OHMS WATT OUTPUT * WATT
-011
-002 -005 14
-002
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
94 95
SCI Transducer Cat 90-134(MTD) 94-95 1/9/02, 5:32 PM
Wiring Diagrams Wiring Diagrams
Exceltronic XLP Modular Exceltronic XLP Modular
Plug-In Transducers Plug-In Transducers
VOLTS
8 EB EA L L
I 2A AMPS E 2B VOLTS SYSTEM B
VOLTS
8 20 8 LOAD 2 8 LB 2
9 EC EB
VOLTS + +
9 21
VOLTS
9 9
10 N EC EXTERNAL
AUX. POWER
CH. 1 CHANNEL 1 OUTPUT * * OUTPUT LOAD RANGE CH. 1 CHANNEL 1 OUTPUT * * OUTPUT LOAD RANGE
OUTPUTS
OUTPUTS
10 OUTPUT LOAD RANGE 10 OUTPUT LOAD RANGE
11 N
10 22 0 to + 1 mA 0-10K OHMS 0 to + 1 mA 0-10K OHMS
XLP Plug-In
VAR 1-3-5 mA 0-5K OHMS 1-3-5 mA 0-5K OHMS
VOLTS
+ + + +
OUTPUTS
Three 1-Element Watt/Vars in One Module with or without External Aux. Power Models T1, T2 Temperature
LINE
A B C N
1
COM
1 13
VAR A O 2
AMPS IA VA OUTPUT U RTD1 RTD1
2 14 + T
P 3
3 15
+ U
WATT A T 4
AMPS IB WA OUTPUT S
4 16 COM
5
COM
5 17 O
AMPS IC VB VAR B 6
OUTPUT U RTD2 RTD2
6 18 + T
P 7
7 19
+ U
EA
VOLTS
WATT B T
WB OUTPUT S
8
8 20 COM +
EB 9
COM CH. 1
9 21 CHANNEL 1 OUTPUT *
VOLTS
OUT
EC
VC VAR C O * OUTPUT LOAD RANGE
10
OUTPUT U OUTPUT LOAD RANGE
N
10 22 + T 0-1 mA 0-10K OHMS
+
P 1-5 mA 0-5K OHMS 11
+
VOLTS
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
96 97
SCI Transducer Cat 90-134(MTD) 96-97 1/9/02, 5:32 PM
Wiring Diagrams Wiring Diagrams
Exceltronic XLP Modular Exceltronic XLP Modular
Plug-In Transducers Plug-In Transducers
VOLTS
8 EB EA L L
I 2A AMPS E 2B VOLTS SYSTEM B
VOLTS
8 20 8 LOAD 2 8 LB 2
9 EC EB
VOLTS + +
9 21
VOLTS
9 9
10 N EC EXTERNAL
AUX. POWER
CH. 1 CHANNEL 1 OUTPUT * * OUTPUT LOAD RANGE CH. 1 CHANNEL 1 OUTPUT * * OUTPUT LOAD RANGE
OUTPUTS
OUTPUTS
10 OUTPUT LOAD RANGE 10 OUTPUT LOAD RANGE
11 N
10 22 0 to + 1 mA 0-10K OHMS 0 to + 1 mA 0-10K OHMS
XLP Plug-In
VAR 1-3-5 mA 0-5K OHMS 1-3-5 mA 0-5K OHMS
VOLTS
+ + + +
OUTPUTS
Three 1-Element Watt/Vars in One Module with or without External Aux. Power Models T1, T2 Temperature
LINE
A B C N
1
COM
1 13
VAR A O 2
AMPS IA VA OUTPUT U RTD1 RTD1
2 14 + T
P 3
3 15
+ U
WATT A T 4
AMPS IB WA OUTPUT S
4 16 COM
5
COM
5 17 O
AMPS IC VB VAR B 6
OUTPUT U RTD2 RTD2
6 18 + T
P 7
7 19
+ U
EA
VOLTS
WATT B T
WB OUTPUT S
8
8 20 COM +
EB 9
COM CH. 1
9 21 CHANNEL 1 OUTPUT *
VOLTS
OUT
EC
VC VAR C O * OUTPUT LOAD RANGE
10
OUTPUT U OUTPUT LOAD RANGE
N
10 22 + T 0-1 mA 0-10K OHMS
+
P 1-5 mA 0-5K OHMS 11
+
VOLTS
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
96 97
SCI Transducer Cat 90-134(MTD) 96-97 1/9/02, 5:32 PM
Test Equipment
Exceltronic XLP Modular
Plug-In Transducers
SCIENTIFIC
Exceltronic II XLG AC Transducers
AVAILABLE TEST EQUIPMENT
COLUMBUS
Scientific Columbus offers three testing devices for use with XLP transducers: The Exceltronic II XLG is a lower-priced line
of transducers that meets all common energy-
Test Fixture (Model XLP 6329B) measurement needs. Its 0.2% accuracy level
This device is used for bench calibrating and troubleshooting XLP permits measurement or monitoring of any circuit at
transducer modules. The test fixture contains all of the various types
minimal cost. Smaller can size with 4–20 mAdc
of current transformers necessary to cover all of the different transducer
output makes these transducers ideal for industrial
configurations. Special switching selects the transducer configuration for
the unit under test. All calibration is performed using the single-phase applications and generating stations.
method.
The XLG is available in current, voltage, watt,
This fixture is intended as a method of making electrical connections to the modules; it does not contain the var, and combined watt/var units with 5 A or
necessary power source and reference standards. The Model 6444 Calibrator (see pages 120–121) is available 120 V input levels on all units. The current and
for that purpose. voltage units also have options for 10 A and
240 V inputs. Frequency levels of 50 or 60 Hz are available on
Output Loop Tester (Model XLP 6304) all units. The 60 Hz XLG line is UL Recognized, and both
This test module uses internal batteries to generate a very accurate 0.1 or 1 mAdc signal for testing equipment 50 and 60 Hz models meet the ANSI/IEEE C37.90.1-1989 surge-
connected to the output loops of any of the XLP modules. A self-contained voltmeter measures the voltage withstand test.
across the loop under test to check for loop resistance or intermittent open circuits.
XLG
◆ Isolated outputs on ◆ Substation monitoring ◆ Unidirectional &
Consult the factory for complete information on these test devices. combined watt/var units bidirectional outputs
on combination watt/var
◆ 2500 VRMS isolation
® units
JEM MULTIFUNCTION TRANSDUCER
Scientific Columbus XLG Transducers provide precise measurement of voltage, current, watts (real power),
Consult the factory for specifications and ordering information. and vars (reactive power), and can be utilized in many ways as inputs to your process-control system.
Applications include early detection of machinery failure and electrical balance of the power system.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
98 99
SCI Transducer Cat 90-134(MTD) 98-99 1/9/02, 5:33 PM
Test Equipment
Exceltronic XLP Modular
Plug-In Transducers
SCIENTIFIC
Exceltronic II XLG AC Transducers
AVAILABLE TEST EQUIPMENT
COLUMBUS
Scientific Columbus offers three testing devices for use with XLP transducers: The Exceltronic II XLG is a lower-priced line
of transducers that meets all common energy-
Test Fixture (Model XLP 6329B) measurement needs. Its 0.2% accuracy level
This device is used for bench calibrating and troubleshooting XLP permits measurement or monitoring of any circuit at
transducer modules. The test fixture contains all of the various types
minimal cost. Smaller can size with 4–20 mAdc
of current transformers necessary to cover all of the different transducer
output makes these transducers ideal for industrial
configurations. Special switching selects the transducer configuration for
the unit under test. All calibration is performed using the single-phase applications and generating stations.
method.
The XLG is available in current, voltage, watt,
This fixture is intended as a method of making electrical connections to the modules; it does not contain the var, and combined watt/var units with 5 A or
necessary power source and reference standards. The Model 6444 Calibrator (see pages 120–121) is available 120 V input levels on all units. The current and
for that purpose. voltage units also have options for 10 A and
240 V inputs. Frequency levels of 50 or 60 Hz are available on
Output Loop Tester (Model XLP 6304) all units. The 60 Hz XLG line is UL Recognized, and both
This test module uses internal batteries to generate a very accurate 0.1 or 1 mAdc signal for testing equipment 50 and 60 Hz models meet the ANSI/IEEE C37.90.1-1989 surge-
connected to the output loops of any of the XLP modules. A self-contained voltmeter measures the voltage withstand test.
across the loop under test to check for loop resistance or intermittent open circuits.
XLG
◆ Isolated outputs on ◆ Substation monitoring ◆ Unidirectional &
Consult the factory for complete information on these test devices. combined watt/var units bidirectional outputs
on combination watt/var
◆ 2500 VRMS isolation
® units
JEM MULTIFUNCTION TRANSDUCER
Scientific Columbus XLG Transducers provide precise measurement of voltage, current, watts (real power),
Consult the factory for specifications and ordering information. and vars (reactive power), and can be utilized in many ways as inputs to your process-control system.
Applications include early detection of machinery failure and electrical balance of the power system.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
98 99
SCI Transducer Cat 90-134(MTD) 98-99 1/9/02, 5:33 PM
Specifications Ordering Procedure & Case Dimensions
Exceltronic II XLG AC Average-Sensing Exceltronic II XLG AC Average-Sensing
Current or Voltage Transducers Current or Voltage Transducers
ORDERING PROCEDURE
Specifications 0–1 mAdc Amps 4–20 mAdc Amps 0–1 mAdc Volts 4–20 mAdc Volts XLG Model Number: XLG V 10 S 1 - 1
(Current Transducer) (Current Transducer) (Voltage Transducer) (Voltage Transducer)
Current Nominal Option A Option D Transducer Type EXAMPLE: XLGV10S1-1
Input Calibrating Range 5A 10 A V = Voltage
Range with Linearity 0–5 A 0–10 A Voltage Transducer, 1 element,
Overload Continuous 0–7.5 A 0–15 A N/A I = Current self-powered (internal auxiliary
Overload 1 Second/Hour 15 A 20 A power), 0-1 mAdc output, 120 V input.
Burden/Element 250 A 250 A Elements
0.25 VA (maximum) at 5 A 0.35 VA (maximum) at 10 A 10 = 1 Element (single)
Voltage Nominal Option 1 Option 3 30 = 3 Element (triple)
Input Calibrating Range 120 V 240 V
Range with Linearity 0–150 V 0–300 V Auxiliary Power
Overload Continuous N/A 0–150 V 0–300 V
Burden/Element 180 V 300 V S = Self-Powered (internal auxiliary power)—0-1 mAdc units only
2.2 VA (maximum) at 120 V 2.2 VA (maximum) at 120 V E = External Auxiliary Power (120 Vac std.)—4-20 mAdc units only 50-60 Hz is standard on all XLG
85–150 Vac
Current and Voltage Transducers.
External Input Range 85–150 Vac
Auxiliary Frequency Range None Required 50–500 Hz None Required 50–500 Hz Output
Power Burden/Element 2.5 VA (maximum) at 120 V 2.5 VA (maximum) at 120 V 1 = 0-1 mAdc
Rated Output (RO) = 1 mAdc for 20 mAdc for 1 mAdc for 20 mAdc for 4 = 4-20 mAdc (unidirectional)
5 A or 150 V/Element Standard Calibration Standard Calibration Standard Calibration Standard Calibration
Input
Accuracy ± 0.2% RO
Current Units Voltage Units
Temperature Effect on Accuracy ± 0.0075% / ° C (typical) - 0.015% / ° C (typical) A=5A 1 = 120 V
Operating Temperature Range -20° C to +60° C -20° C to +50° C -20° C to +60° C -20° C to +50° C D = 10 A 3 = 240 V
Compliance Voltage 10 Vdc 15 Vdc 10 Vdc 15 Vdc
Load Any load from 0–10,000 Ω Any load from 0–750 Ω Any load from 0–10,000 Ω Any load from 0–750 Ω
at 1 mAdc at 20 mAdc at 1 mAdc at 20 mAdc CASE DIMENSIONS (Styles III & II Cases)
XLG
Output Ripple Peak < 0.5% RO
Response Time < 400 ms to 99% < 500 ms to 99% < 400 ms to 99% < 500 ms to 99%
Single Current or Voltage
(Style III Case)
±10% of Reading (minimum) ± 20% of Reading (minimum) ±10% of Reading (minimum) ± 20% of Reading (minimum)
SCREW HEAD PROTRUDES .25"
Standard Calibration Gain .09" (2.29 mm) (TYP.) (6.35 mm) .75"
Adjustments Zero None Required ±5% of Zero Point (minimum) None Required ±5% of Zero Point (minimum) .46" FROM CASE - .094" RAD. (19.05 mm)
(11.68 mm) 2 SCREWS (2.39 mm)
Frequency Range 48–62 Hz .23"
(52.07 mm)
(38.10 mm)
3.53"
±0.25% RO, Noncumulative
(5.84 mm)
Stability (per year)
2.05"
(89.66 mm)
1.50"
.36" DIA.
Operating Humidity 0–95% Noncondensing (9.14 mm)
2 KEYSLOTS
Isolation Complete Complete Complete Complete
(Input/Output/Case) (Input/Output/Power/Case) (Input/Output/Case) (Input/Output/Power/Case) 3.07" .187" DIA.
.25" (77.98 mm)
(6.35 mm) (4.75 mm)
3.50" .07"
Dielectric Withstand 2500 VRMS at 60 Hz (88.90 mm)
2 MOUNTING
(1.78 mm)
HOLES
Surge Withstand ANSI/IEEE C37.90.1-1989 4.00"
(101.60 mm)
Maximum Single 1 lb., 1 oz. (0.5 kg)
Net Weight Triple 2 lbs., 9 oz. (1.2 kg)
Triple Current or Voltage
Approximate Single 3.3" W x 2.1" D x 4.3" H (Style II Case)
Dimensions (84 mm x 53 mm x 109 mm) SCREW HEAD PROTRUDES .09" (2.29 mm) (TYP.)
.75"
FROM CASE - 4 SCREWS
(excluding Style III Case, see page 122 1.14" .43" (19.05 mm)
Triple (10.92 mm)
mounting plate) (28.96 mm) .25"
(6.35 mm)
4.4" W x 3.9" D x 4.9" H
(112 mm x 99 mm x 124 mm) .094" RAD.
(2.39 mm)
Style II Case, see page 122
3.77" .23" 4.15"
(50.80 mm)
(95.76 mm) (5.84 mm) (105.41 mm)
Specifications subject to change without notice.
2.00"
.36" DIA.
1.50" (9.14 mm)
(38.10 mm) 2 KEYSLOTS
4.75"
(120.65 mm) Terminal strips shown for illustration purposes only. For exact terminal-
5.25" strip configuration on specific units, see connection diagrams on page 98.
(133.35 mm) Drawings not to scale.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
100 101
SCI Transducer Cat 90-134(MTD) 100-101 1/9/02, 5:33 PM
Specifications Ordering Procedure & Case Dimensions
Exceltronic II XLG AC Average-Sensing Exceltronic II XLG AC Average-Sensing
Current or Voltage Transducers Current or Voltage Transducers
ORDERING PROCEDURE
Specifications 0–1 mAdc Amps 4–20 mAdc Amps 0–1 mAdc Volts 4–20 mAdc Volts XLG Model Number: XLG V 10 S 1 - 1
(Current Transducer) (Current Transducer) (Voltage Transducer) (Voltage Transducer)
Current Nominal Option A Option D Transducer Type EXAMPLE: XLGV10S1-1
Input Calibrating Range 5A 10 A V = Voltage
Range with Linearity 0–5 A 0–10 A Voltage Transducer, 1 element,
Overload Continuous 0–7.5 A 0–15 A N/A I = Current self-powered (internal auxiliary
Overload 1 Second/Hour 15 A 20 A power), 0-1 mAdc output, 120 V input.
Burden/Element 250 A 250 A Elements
0.25 VA (maximum) at 5 A 0.35 VA (maximum) at 10 A 10 = 1 Element (single)
Voltage Nominal Option 1 Option 3 30 = 3 Element (triple)
Input Calibrating Range 120 V 240 V
Range with Linearity 0–150 V 0–300 V Auxiliary Power
Overload Continuous N/A 0–150 V 0–300 V
Burden/Element 180 V 300 V S = Self-Powered (internal auxiliary power)—0-1 mAdc units only
2.2 VA (maximum) at 120 V 2.2 VA (maximum) at 120 V E = External Auxiliary Power (120 Vac std.)—4-20 mAdc units only 50-60 Hz is standard on all XLG
85–150 Vac
Current and Voltage Transducers.
External Input Range 85–150 Vac
Auxiliary Frequency Range None Required 50–500 Hz None Required 50–500 Hz Output
Power Burden/Element 2.5 VA (maximum) at 120 V 2.5 VA (maximum) at 120 V 1 = 0-1 mAdc
Rated Output (RO) = 1 mAdc for 20 mAdc for 1 mAdc for 20 mAdc for 4 = 4-20 mAdc (unidirectional)
5 A or 150 V/Element Standard Calibration Standard Calibration Standard Calibration Standard Calibration
Input
Accuracy ± 0.2% RO
Current Units Voltage Units
Temperature Effect on Accuracy ± 0.0075% / ° C (typical) - 0.015% / ° C (typical) A=5A 1 = 120 V
Operating Temperature Range -20° C to +60° C -20° C to +50° C -20° C to +60° C -20° C to +50° C D = 10 A 3 = 240 V
Compliance Voltage 10 Vdc 15 Vdc 10 Vdc 15 Vdc
Load Any load from 0–10,000 Ω Any load from 0–750 Ω Any load from 0–10,000 Ω Any load from 0–750 Ω
at 1 mAdc at 20 mAdc at 1 mAdc at 20 mAdc CASE DIMENSIONS (Styles III & II Cases)
XLG
Output Ripple Peak < 0.5% RO
Response Time < 400 ms to 99% < 500 ms to 99% < 400 ms to 99% < 500 ms to 99%
Single Current or Voltage
(Style III Case)
±10% of Reading (minimum) ± 20% of Reading (minimum) ±10% of Reading (minimum) ± 20% of Reading (minimum)
SCREW HEAD PROTRUDES .25"
Standard Calibration Gain .09" (2.29 mm) (TYP.) (6.35 mm) .75"
Adjustments Zero None Required ±5% of Zero Point (minimum) None Required ±5% of Zero Point (minimum) .46" FROM CASE - .094" RAD. (19.05 mm)
(11.68 mm) 2 SCREWS (2.39 mm)
Frequency Range 48–62 Hz .23"
(52.07 mm)
(38.10 mm)
3.53"
±0.25% RO, Noncumulative
(5.84 mm)
Stability (per year)
2.05"
(89.66 mm)
1.50"
.36" DIA.
Operating Humidity 0–95% Noncondensing (9.14 mm)
2 KEYSLOTS
Isolation Complete Complete Complete Complete
(Input/Output/Case) (Input/Output/Power/Case) (Input/Output/Case) (Input/Output/Power/Case) 3.07" .187" DIA.
.25" (77.98 mm)
(6.35 mm) (4.75 mm)
3.50" .07"
Dielectric Withstand 2500 VRMS at 60 Hz (88.90 mm)
2 MOUNTING
(1.78 mm)
HOLES
Surge Withstand ANSI/IEEE C37.90.1-1989 4.00"
(101.60 mm)
Maximum Single 1 lb., 1 oz. (0.5 kg)
Net Weight Triple 2 lbs., 9 oz. (1.2 kg)
Triple Current or Voltage
Approximate Single 3.3" W x 2.1" D x 4.3" H (Style II Case)
Dimensions (84 mm x 53 mm x 109 mm) SCREW HEAD PROTRUDES .09" (2.29 mm) (TYP.)
.75"
FROM CASE - 4 SCREWS
(excluding Style III Case, see page 122 1.14" .43" (19.05 mm)
Triple (10.92 mm)
mounting plate) (28.96 mm) .25"
(6.35 mm)
4.4" W x 3.9" D x 4.9" H
(112 mm x 99 mm x 124 mm) .094" RAD.
(2.39 mm)
Style II Case, see page 122
3.77" .23" 4.15"
(50.80 mm)
(95.76 mm) (5.84 mm) (105.41 mm)
Specifications subject to change without notice.
2.00"
.36" DIA.
1.50" (9.14 mm)
(38.10 mm) 2 KEYSLOTS
4.75"
(120.65 mm) Terminal strips shown for illustration purposes only. For exact terminal-
5.25" strip configuration on specific units, see connection diagrams on page 98.
(133.35 mm) Drawings not to scale.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
100 101
SCI Transducer Cat 90-134(MTD) 100-101 1/9/02, 5:33 PM
Wiring Diagrams Specifications
Exceltronic II XLG AC Average-Sensing Exceltronic II XLG
Current or Voltage Transducers AC Watt or Var Transducers
WIRING DIAGRAMS FOR 0-1 mAdc AND 4-20 mAdc UNITS (Styles III & II Cases)
Specifications 0 to ±1 mAdc Watts 4–20 mAdc Watts 0 to ±1 mAdc Vars 4–20 mAdc Vars
(Watt Transducer) (Watt Transducer) (Var Transducer) (Var Transducer)
Current Nominal 5A
0-1 mAdc Units Input Range* 0–10 A
Overload Continuous 15 A
Overload 1 Second/Hour 250 A
Burden/Element 0.3 VA (maximum) at 5 A
Single Current or Voltage Triple Current or Voltage
(Style III Case) (Style II Case) Voltage Nominal 120 V
Input Range* 0–150 V
Overload Continuous 180 V
Burden/Element 0.035 VA (maximum) at 120 V
AO BO CO External Input Range 85–150 Vac 85–150 Vac
DC DC DC Auxiliary Frequency Range 50–500 Hz 50–500 Hz
OUTPUT OUTPUT OUTPUT Power Burden 4 VA (maximum) at 120 V 4.5 VA (maximum) at 120 V
AC
DC INPUT - + - + - + Rated Output (RO) = ±1 mAdc for 20 mAdc for ±1 mAdc for 20 mAdc for
OUTPUT
- + 500 Watts or Vars/Element Standard Calibration Standard Calibration Standard Calibration Standard Calibration
1 2 3 4 5 6 Accuracy ± (0.1% Reading + 0.05% RO) ± 0.2% of Output Range ± (0.1% Reading + 0.1% RO) ± 0.2% of Output Range
1 2 3 4 at 0–200% RO at 0–200% RO
Temperature Effect on Accuracy ±0.005% / ° C (typical) ±0.0075% / ° C (typical) ±0.0075% / ° C (typical) ±0.008% / ° C (typical)
Operating Temperature Range -20° C to +70° C -20° C to +50° C -20° C to +60° C -20° C to +50° C
7 8 9 10 11 12 Compliance Voltage 10 Vdc 15 Vdc 10 Vdc 15 Vdc
Load Any load from 0–10,000 Ω Any load from 0–750 Ω Any load from 0–10,000 Ω Any load from 0–750 Ω
at 1 mAdc at 20 mAdc at 1 mAdc at 20 mAdc
AO BO CO
Output Ripple Peak < 0.5% RO
AC AC AC
INPUT INPUT INPUT Response Time < 400 ms to 99% < 500 ms to 99% < 400 ms to 99% < 500 ms to 99%
XLG
Power Factor Any
PF Effect on Accuracy ± 0.2% RO (maximum)
Standard Calibration Gain ±2% of Reading (minimum) ± 20% of Reading (minimum) ±2% of Reading (minimum) ± 20% of Reading (minimum)
Adjustments Zero None Required ±5% of Zero Point (minimum) None Required ±5% of Zero Point (minimum)
4-20 mAdc Units
Frequency Range 58–62 Hz 60 Hz
Stability (per year) ±0.25% RO, Noncumulative
Single Current or Voltage Triple Current or Voltage
Operating Humidity 0–95% Noncondensing
(Style III Case) (Style II Case)
Isolation Complete (Input/Output/Power/Case)
Dielectric Withstand 2500 VRMS at 60 Hz
AO BO CO
Surge Withstand ANSI/IEEE C37.90.1-1989
EXTERNAL
AUX. POWER DC DC DC Maximum Net Weight 2 lbs., 11 oz. (1.2 kg)
OUTPUT OUTPUT OUTPUT
AC
INPUT - + - + - + Approximate Dimensions
(excluding mounting plate)
4.4" W x 3.9" D x 4.9" H (112 mm x 99 mm x 124 mm) Style II Case, see page 122
DC
OUTPUT Overrange with Linearity 500–1000 Watts/Element 500–600 Watts/Element 500–1000 Vars/Element 500–600 Vars/Element
- + 1 2 3 4 5 6 6A
No additional error within voltage compliance. Reduce load resistance as required.
1 2 3 4 5 6
*Total input not to exceed 200% of standard-calibration watts or vars on units with 0 to ±1 mAdc output. Specifications subject to change without notice.
EXTERNAL
AUX. POWER Total input not to exceed 120% of standard-calibration watts or vars on units with 4–20 mAdc output.
7 8 9 10 11 12 12A
AO BO CO
AC AC AC
INPUT INPUT INPUT
Adjust
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
102 103
SCI Transducer Cat 90-134(MTD) 102-103 1/9/02, 5:33 PM
Wiring Diagrams Specifications
Exceltronic II XLG AC Average-Sensing Exceltronic II XLG
Current or Voltage Transducers AC Watt or Var Transducers
WIRING DIAGRAMS FOR 0-1 mAdc AND 4-20 mAdc UNITS (Styles III & II Cases)
Specifications 0 to ±1 mAdc Watts 4–20 mAdc Watts 0 to ±1 mAdc Vars 4–20 mAdc Vars
(Watt Transducer) (Watt Transducer) (Var Transducer) (Var Transducer)
Current Nominal 5A
0-1 mAdc Units Input Range* 0–10 A
Overload Continuous 15 A
Overload 1 Second/Hour 250 A
Burden/Element 0.3 VA (maximum) at 5 A
Single Current or Voltage Triple Current or Voltage
(Style III Case) (Style II Case) Voltage Nominal 120 V
Input Range* 0–150 V
Overload Continuous 180 V
Burden/Element 0.035 VA (maximum) at 120 V
AO BO CO External Input Range 85–150 Vac 85–150 Vac
DC DC DC Auxiliary Frequency Range 50–500 Hz 50–500 Hz
OUTPUT OUTPUT OUTPUT Power Burden 4 VA (maximum) at 120 V 4.5 VA (maximum) at 120 V
AC
DC INPUT - + - + - + Rated Output (RO) = ±1 mAdc for 20 mAdc for ±1 mAdc for 20 mAdc for
OUTPUT
- + 500 Watts or Vars/Element Standard Calibration Standard Calibration Standard Calibration Standard Calibration
1 2 3 4 5 6 Accuracy ± (0.1% Reading + 0.05% RO) ± 0.2% of Output Range ± (0.1% Reading + 0.1% RO) ± 0.2% of Output Range
1 2 3 4 at 0–200% RO at 0–200% RO
Temperature Effect on Accuracy ±0.005% / ° C (typical) ±0.0075% / ° C (typical) ±0.0075% / ° C (typical) ±0.008% / ° C (typical)
Operating Temperature Range -20° C to +70° C -20° C to +50° C -20° C to +60° C -20° C to +50° C
7 8 9 10 11 12 Compliance Voltage 10 Vdc 15 Vdc 10 Vdc 15 Vdc
Load Any load from 0–10,000 Ω Any load from 0–750 Ω Any load from 0–10,000 Ω Any load from 0–750 Ω
at 1 mAdc at 20 mAdc at 1 mAdc at 20 mAdc
AO BO CO
Output Ripple Peak < 0.5% RO
AC AC AC
INPUT INPUT INPUT Response Time < 400 ms to 99% < 500 ms to 99% < 400 ms to 99% < 500 ms to 99%
XLG
Power Factor Any
PF Effect on Accuracy ± 0.2% RO (maximum)
Standard Calibration Gain ±2% of Reading (minimum) ± 20% of Reading (minimum) ±2% of Reading (minimum) ± 20% of Reading (minimum)
Adjustments Zero None Required ±5% of Zero Point (minimum) None Required ±5% of Zero Point (minimum)
4-20 mAdc Units
Frequency Range 58–62 Hz 60 Hz
Stability (per year) ±0.25% RO, Noncumulative
Single Current or Voltage Triple Current or Voltage
Operating Humidity 0–95% Noncondensing
(Style III Case) (Style II Case)
Isolation Complete (Input/Output/Power/Case)
Dielectric Withstand 2500 VRMS at 60 Hz
AO BO CO
Surge Withstand ANSI/IEEE C37.90.1-1989
EXTERNAL
AUX. POWER DC DC DC Maximum Net Weight 2 lbs., 11 oz. (1.2 kg)
OUTPUT OUTPUT OUTPUT
AC
INPUT - + - + - + Approximate Dimensions
(excluding mounting plate)
4.4" W x 3.9" D x 4.9" H (112 mm x 99 mm x 124 mm) Style II Case, see page 122
DC
OUTPUT Overrange with Linearity 500–1000 Watts/Element 500–600 Watts/Element 500–1000 Vars/Element 500–600 Vars/Element
- + 1 2 3 4 5 6 6A
No additional error within voltage compliance. Reduce load resistance as required.
1 2 3 4 5 6
*Total input not to exceed 200% of standard-calibration watts or vars on units with 0 to ±1 mAdc output. Specifications subject to change without notice.
EXTERNAL
AUX. POWER Total input not to exceed 120% of standard-calibration watts or vars on units with 4–20 mAdc output.
7 8 9 10 11 12 12A
AO BO CO
AC AC AC
INPUT INPUT INPUT
Adjust
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
102 103
SCI Transducer Cat 90-134(MTD) 102-103 1/9/02, 5:33 PM
Ordering Procedure & Case Dimensions Wiring Diagrams
Exceltronic II XLG Exceltronic II XLG
AC Watt or Var Transducers AC Watt or Var Transducers
ORDERING PROCEDURE WIRING DIAGRAMS FOR 0-1 mAdc AND 4-20 mAdc UNITS (Style II Case)
XLG Model Number: XLG W 20 E 4 - A1 -
XLG
Option
NOTE: Bottom terminal strip (7-12) omitted on S models.
5 = 50 Hz (not UL Recognized)
1.14" .43"
FROM CASE - 4 SCREWS - + - +
(28.96 mm) (10.92 mm) .25" .75"
(6.35 mm) (19.05 mm)
1 2 3 4 5 6 6A 1 2 3 4 5 6 6A
.094" RAD.
(2.39 mm) EXT. EXT.
AUX. AUX.
3.77" .23" POWER
(50.80 mm)
POWER
(95.76 mm) (5.84 mm)
2.00"
4.15"
.36" DIA. (105.41 mm) 7 8 9 10 11 12 12A 7 8 9 10 11 12 12A
1.50" (9.14 mm)
(38.10 mm) 2 KEYSLOTS
.187" DIA.
(4.75 mm) LOAD LOAD
2 MOUNTING .07"
4.40"
(111.76 mm) HOLES (1.78 mm)
4.75"
(120.65 mm)
5.25"
(133.35 mm)
Terminal strips shown for illustration purposes only. For exact terminal-strip configuration on specific units, see connection diagrams on page 101.
Drawings not to scale. Adjust E Models: Shown. S Models: External aux. power not required.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
104 105
SCI Transducer Cat 90-134(MTD) 104-105 1/9/02, 5:33 PM
Ordering Procedure & Case Dimensions Wiring Diagrams
Exceltronic II XLG Exceltronic II XLG
AC Watt or Var Transducers AC Watt or Var Transducers
ORDERING PROCEDURE WIRING DIAGRAMS FOR 0-1 mAdc AND 4-20 mAdc UNITS (Style II Case)
XLG Model Number: XLG W 20 E 4 - A1 -
XLG
Option
NOTE: Bottom terminal strip (7-12) omitted on S models.
5 = 50 Hz (not UL Recognized)
1.14" .43"
FROM CASE - 4 SCREWS - + - +
(28.96 mm) (10.92 mm) .25" .75"
(6.35 mm) (19.05 mm)
1 2 3 4 5 6 6A 1 2 3 4 5 6 6A
.094" RAD.
(2.39 mm) EXT. EXT.
AUX. AUX.
3.77" .23" POWER
(50.80 mm)
POWER
(95.76 mm) (5.84 mm)
2.00"
4.15"
.36" DIA. (105.41 mm) 7 8 9 10 11 12 12A 7 8 9 10 11 12 12A
1.50" (9.14 mm)
(38.10 mm) 2 KEYSLOTS
.187" DIA.
(4.75 mm) LOAD LOAD
2 MOUNTING .07"
4.40"
(111.76 mm) HOLES (1.78 mm)
4.75"
(120.65 mm)
5.25"
(133.35 mm)
Terminal strips shown for illustration purposes only. For exact terminal-strip configuration on specific units, see connection diagrams on page 101.
Drawings not to scale. Adjust E Models: Shown. S Models: External aux. power not required.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
104 105
SCI Transducer Cat 90-134(MTD) 104-105 1/9/02, 5:33 PM
Specifications Ordering Procedure & Case Dimensions
Exceltronic II XLG Combined Exceltronic II XLG Combined
AC Watt/Var Transducers AC Watt/Var Transducers
ORDERING PROCEDURE
Specifications 0 to ±1 mAdc Watts 4–20 mAdc Watts 0 to ±1 mAdc Vars 4–20 mAdc Vars
(Combined Watt/Var (Combined Watt/Var (Combined Watt/Var (Combined Watt/Var XLG Model Number: XLG C 30 E 1 - A1 - N
Transducer) Transducer) Transducer) Transducer)
Transducer Type EXAMPLE: XLGC30E1-A1-N
Current Nominal 5A
Input Range* 0–10 A C = Combined Watt/Var Combined Watt/Var Transducer,
Overload Continuous 15 A 3 element, 120 Vac external
Overload 1 Second/Hour 250 A Elements
Burden/Element 0.3 VA (maximum) at 5 A auxiliary power, 0-1 mAdc output,
10 = 1 Element 5 A/120 V input, nonisolated.
Voltage Nominal 120 V 20 = 2 Element
Input Range* 0–150 V 25 = 21/2 Element
Overload Continuous 180 V
Burden/Element 0.035 VA (maximum) at 120 V 30 = 3 Element
External Input Range 85–150 Vac Auxiliary Power
Auxiliary Frequency Range 50–500 Hz
Power Burden 8 VA (maximum) at 120 V S = Self-Powered (internal auxiliary power)
E = External Auxiliary Power (120 Vac std.)
Rated Output (RO) = ±1 mAdc for 20 mAdc for ±1 mAdc for 20 mAdc for
500 Watts or Vars/Element Standard Calibration Standard Calibration Standard Calibration Standard Calibration
Output
Accuracy ±(0.1% Reading + 0.05% RO) ±0.2% of Output Range ±(0.1% Reading + 0.1% RO) ±0.2% of Output Range 1 = 0-1 mAdc
at 0–200% RO at 0–200% RO
4 = 4-20 mAdc (unidirectional)
Temperature Effect on Accuracy ± 0.005% / ° C (typical) ± 0.0075% / ° C (typical) ±0.0075% / ° C (typical) ±0.008% / ° C (typical) 12 = 4-12-20 mAdc (bidirectional)
Operating Temperature Range -20° C to +60° C -20° C to +50° C -20° C to +60° C -20° C to +50° C 15 = 4-20 mAdc Unidirectional (watts)/4-12-20 mAdc Bidirectional (vars)
Compliance Voltage 10 Vdc 15 Vdc 10 Vdc 15 Vdc
Load Any load from 0–10,000 Ω Any load from 0–750 Ω Any load from 0–10,000 Ω Any load from 0–750Ω
Input
at 1 mAdc at 20 mAdc at 1 mAdc at 20 mAdc A=5A
Output Ripple Peak < 0.5% RO 1 = 120 V
XLG
Response Time < 400 ms to 99% < 500 ms to 99% < 400 ms to 99% < 500 ms to 99% Options
Power Factor Any N = Nonisolated Outputs
PF Effect on Accuracy ±0.2% RO (maximum) 5 = 50 Hz (not UL Recognized)
Standard Calibration Gain ± 2% of Reading (minimum) ±20% of Reading (minimum) ± 2% of Reading (minimum) ±20% of Reading (minimum)
Adjustments Zero None Required ±5% of Zero Point (minimum) None Required ±5% of Zero Point (minimum)
Frequency 60 Hz
Stability (per year) ±0.25% RO, Noncumulative
Operating Humidity 0–95% Noncondensing CASE DIMENSIONS (Style IV Case)
Isolation Complete (Input/Output/Power/Case)
Dielectric Withstand 2500 VRMS at 60 Hz
SCREW HEAD PROTRUDES .09" (2.29 mm) (TYP.)
Surge Withstand ANSI/IEEE C37.90.1-1989 FROM CASE - 4 SCREWS .75"
1.14" .43" (19.05 mm)
Maximum Net Weight 3 lbs., 5 oz. (1.5 kg) (28.96 mm) (10.92 mm) .25"
(6.35 mm)
Approximate Dimensions 4.4" W x 3.9" D x 6.5" H (112 mm x 99 mm x 165 mm) Style IV Case, see page 123 .094" RAD.
(excluding mounting plate) (2.39 mm)
Overrange with Linearity 500–1000 Watts/Element 500–600 Watts/Element 500–1000 Vars/Element 500–600 Vars/Element 3.77" .23"
(50.80 mm)
(95.76 mm) (5.84 mm)
2.00"
No additional error within voltage compliance. Reduce load resistance as required.
.36" DIA. 5.78"
*Total input not to exceed 200% of standard-calibration watts and vars on units with 0 to ±1 mAdc output. Specifications subject to change without notice. 1.50" (9.14 mm) (146.81 mm)
Total input not to exceed 120% of standard-calibration watts and vars on units with 4–20 mAdc output. (38.10 mm) 2 KEYSLOTS
.187" DIA.
(4.75 mm)
2 MOUNTING
4.40"
(111.76 mm) HOLES
4.75"
(120.65 mm)
.07"
5.25" (1.78 mm)
(133.35 mm)
Terminal strips shown for illustration purposes only. For exact terminal-strip configuration on specific units, see connection diagrams on page 104.
Drawings not to scale.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
106 107
SCI Transducer Cat 90-134(MTD) 106-107 1/9/02, 5:33 PM
Specifications Ordering Procedure & Case Dimensions
Exceltronic II XLG Combined Exceltronic II XLG Combined
AC Watt/Var Transducers AC Watt/Var Transducers
ORDERING PROCEDURE
Specifications 0 to ±1 mAdc Watts 4–20 mAdc Watts 0 to ±1 mAdc Vars 4–20 mAdc Vars
(Combined Watt/Var (Combined Watt/Var (Combined Watt/Var (Combined Watt/Var XLG Model Number: XLG C 30 E 1 - A1 - N
Transducer) Transducer) Transducer) Transducer)
Transducer Type EXAMPLE: XLGC30E1-A1-N
Current Nominal 5A
Input Range* 0–10 A C = Combined Watt/Var Combined Watt/Var Transducer,
Overload Continuous 15 A 3 element, 120 Vac external
Overload 1 Second/Hour 250 A Elements
Burden/Element 0.3 VA (maximum) at 5 A auxiliary power, 0-1 mAdc output,
10 = 1 Element 5 A/120 V input, nonisolated.
Voltage Nominal 120 V 20 = 2 Element
Input Range* 0–150 V 25 = 21/2 Element
Overload Continuous 180 V
Burden/Element 0.035 VA (maximum) at 120 V 30 = 3 Element
External Input Range 85–150 Vac Auxiliary Power
Auxiliary Frequency Range 50–500 Hz
Power Burden 8 VA (maximum) at 120 V S = Self-Powered (internal auxiliary power)
E = External Auxiliary Power (120 Vac std.)
Rated Output (RO) = ±1 mAdc for 20 mAdc for ±1 mAdc for 20 mAdc for
500 Watts or Vars/Element Standard Calibration Standard Calibration Standard Calibration Standard Calibration
Output
Accuracy ±(0.1% Reading + 0.05% RO) ±0.2% of Output Range ±(0.1% Reading + 0.1% RO) ±0.2% of Output Range 1 = 0-1 mAdc
at 0–200% RO at 0–200% RO
4 = 4-20 mAdc (unidirectional)
Temperature Effect on Accuracy ± 0.005% / ° C (typical) ± 0.0075% / ° C (typical) ±0.0075% / ° C (typical) ±0.008% / ° C (typical) 12 = 4-12-20 mAdc (bidirectional)
Operating Temperature Range -20° C to +60° C -20° C to +50° C -20° C to +60° C -20° C to +50° C 15 = 4-20 mAdc Unidirectional (watts)/4-12-20 mAdc Bidirectional (vars)
Compliance Voltage 10 Vdc 15 Vdc 10 Vdc 15 Vdc
Load Any load from 0–10,000 Ω Any load from 0–750 Ω Any load from 0–10,000 Ω Any load from 0–750Ω
Input
at 1 mAdc at 20 mAdc at 1 mAdc at 20 mAdc A=5A
Output Ripple Peak < 0.5% RO 1 = 120 V
XLG
Response Time < 400 ms to 99% < 500 ms to 99% < 400 ms to 99% < 500 ms to 99% Options
Power Factor Any N = Nonisolated Outputs
PF Effect on Accuracy ±0.2% RO (maximum) 5 = 50 Hz (not UL Recognized)
Standard Calibration Gain ± 2% of Reading (minimum) ±20% of Reading (minimum) ± 2% of Reading (minimum) ±20% of Reading (minimum)
Adjustments Zero None Required ±5% of Zero Point (minimum) None Required ±5% of Zero Point (minimum)
Frequency 60 Hz
Stability (per year) ±0.25% RO, Noncumulative
Operating Humidity 0–95% Noncondensing CASE DIMENSIONS (Style IV Case)
Isolation Complete (Input/Output/Power/Case)
Dielectric Withstand 2500 VRMS at 60 Hz
SCREW HEAD PROTRUDES .09" (2.29 mm) (TYP.)
Surge Withstand ANSI/IEEE C37.90.1-1989 FROM CASE - 4 SCREWS .75"
1.14" .43" (19.05 mm)
Maximum Net Weight 3 lbs., 5 oz. (1.5 kg) (28.96 mm) (10.92 mm) .25"
(6.35 mm)
Approximate Dimensions 4.4" W x 3.9" D x 6.5" H (112 mm x 99 mm x 165 mm) Style IV Case, see page 123 .094" RAD.
(excluding mounting plate) (2.39 mm)
Overrange with Linearity 500–1000 Watts/Element 500–600 Watts/Element 500–1000 Vars/Element 500–600 Vars/Element 3.77" .23"
(50.80 mm)
(95.76 mm) (5.84 mm)
2.00"
No additional error within voltage compliance. Reduce load resistance as required.
.36" DIA. 5.78"
*Total input not to exceed 200% of standard-calibration watts and vars on units with 0 to ±1 mAdc output. Specifications subject to change without notice. 1.50" (9.14 mm) (146.81 mm)
Total input not to exceed 120% of standard-calibration watts and vars on units with 4–20 mAdc output. (38.10 mm) 2 KEYSLOTS
.187" DIA.
(4.75 mm)
2 MOUNTING
4.40"
(111.76 mm) HOLES
4.75"
(120.65 mm)
.07"
5.25" (1.78 mm)
(133.35 mm)
Terminal strips shown for illustration purposes only. For exact terminal-strip configuration on specific units, see connection diagrams on page 104.
Drawings not to scale.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
106 107
SCI Transducer Cat 90-134(MTD) 106-107 1/9/02, 5:33 PM
Wiring Diagrams
Exceltronic II XLG Combined
AC Watt/Var Transducers
How Accurate
WIRING DIAGRAMS FOR 0-1 mAdc AND 4-20 mAdc ISOLATED UNITS (Style IV Case)
Nonisolated units have the same connections as the Exceltronic Combined Watt/Var Transducers on page 48.
is your Cash
Register?
1 Element, Single Phase, 2 Wire 2 Element, 3 Phase, 3 Wire, Delta
In this industry an error rate as low as a fraction of a
percent can mean the loss of hundreds of thousands of
LINE
LINE
L1 L2 L3 dollars. If you think of your meter as the “cash register”
L1 L2
of your utility, you can envision the money you are
DC DC
OUTPUT OUTPUT losing through inaccurate measurements. Deregulation
WATT WATT
- + - + makes accurate metering your responsibility and even
more important than ever before.
1 2 3 4 5 6 6A 1 2 3 4 5 6 6A
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
7 8 9 10 11 12 12A 7 8 9 10 11 12 12A
The New Cash Register
for the Industry!
- DC
OUTPUT + LOAD - DC
OUTPUT + LOAD
JemStar is the metering solution for the new era of deregulation. At a time when old metering
VAR VAR
standards just won’t do, JemStar provides accuracy you can take to the bank. Put profit and
loss control at your fingertips. A powerful meter, that exceeds industry standards, JEMSTAR
is the new “cash register” for the industry. Accurate
monitoring provides more data, and it allows you to
21/2 Element, 3 Phase, 4 Wire, Wye 3 Element, 3 Phase, 4 Wire, Wye provide customers with additional services and infor-
mation. JEMSTAR can help turn your profits around.
Instrumentation
LINE LINE
L1 L2 L3 N L1 L2 L3 N
DC
OUTPUT
WATT
DC
OUTPUT
WATT
Metering for Today and for the Future
- + - + 1-888-880-JEM1
1 2 3 4 5 6 6A 6B 1 2 3 4 5 6 6A 6B
EXT.
AUX.
EXT.
AUX.
Simply Powerful SCIENTIFIC COLUMBUS
Watthour Accuracy: 0.07% Reading exceeds Thermal Demand Emulation, Contact Inputs
POWER POWER IEC 687 Class 0.2 The JEMSTAR accuracy is Demand Prediction (2) Channels Programmable
unparalleled in the industry. for Pulse counter, Demand
Transformer Loss Compensation—TLC Synchronization, Status Input
7 8 9 10 11 12 12A 12B 7 8 9 10 11 12 12A 12B Graphical Display or TOU Rate Override.
Simultaneous Communications
Bi-Directional and 4 Quadrant Metering I/R Port, RS-232, RS-485, Modem S-Base, A-base, Switchboard
Per Phase and System Measurements Inputs and Outputs: Auto-ranging Voltage:
Watts, Vars, VA, Q, Voltage, Current, PF, THD, Analog Outputs are fully Programmable for any 55-530 VAC
- + LOAD - + LOAD
Watthours, Varhours, VAhours, Qhours, Amphours
Registers:
instantaneous measurement. (3) channels of either
0-1 or 4-20 mA.
Contact Outputs
Site Diagnostics include
installation verification and
DC DC
OUTPUT Instantaneous, Consumption, Demand (Sliding & (4) Channels Programmable as Threshold Alarms, on-going monitoring.
OUTPUT Fixed), Time of Peak, Average Power Factor, Site Monitoring Alarms, Energy Pulses, EOD
VAR VAR Coincident Demand, Coincident Power Factor, Output or Demand Prediction Alarm
Cumulative Demand, Continuous Cumulative
Demand,
www.rochester.com
E Models: Shown. S Models: External aux. power not required.
Adjust NOTE: Dynamic separation between the two analog outputs is limited to ±10 Vdc (±15 Vdc separation on E1 & S1 units). Headquarters
50 Fordham Road 255 North Union Street
Wilmington, MA 01887 Rochester, NY 14605
Tel: 978-988-4101 Tel: 585-263-7700
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 Fax: 978-988-4179 Fax: 585-454-7805
E-Mail: power.industrial@ametek.com E-Mail: info@rochester.com
108 109
SCI Transducer Cat 90-134(MTD) 108-109 1/9/02, 5:33 PM
Wiring Diagrams
Exceltronic II XLG Combined
AC Watt/Var Transducers
How Accurate
WIRING DIAGRAMS FOR 0-1 mAdc AND 4-20 mAdc ISOLATED UNITS (Style IV Case)
Nonisolated units have the same connections as the Exceltronic Combined Watt/Var Transducers on page 48.
is your Cash
Register?
1 Element, Single Phase, 2 Wire 2 Element, 3 Phase, 3 Wire, Delta
In this industry an error rate as low as a fraction of a
percent can mean the loss of hundreds of thousands of
LINE
LINE
L1 L2 L3 dollars. If you think of your meter as the “cash register”
L1 L2
of your utility, you can envision the money you are
DC DC
OUTPUT OUTPUT losing through inaccurate measurements. Deregulation
WATT WATT
- + - + makes accurate metering your responsibility and even
more important than ever before.
1 2 3 4 5 6 6A 1 2 3 4 5 6 6A
EXTERNAL EXTERNAL
AUX. POWER AUX. POWER
7 8 9 10 11 12 12A 7 8 9 10 11 12 12A
The New Cash Register
for the Industry!
- DC
OUTPUT + LOAD - DC
OUTPUT + LOAD
JemStar is the metering solution for the new era of deregulation. At a time when old metering
VAR VAR
standards just won’t do, JemStar provides accuracy you can take to the bank. Put profit and
loss control at your fingertips. A powerful meter, that exceeds industry standards, JEMSTAR
is the new “cash register” for the industry. Accurate
monitoring provides more data, and it allows you to
21/2 Element, 3 Phase, 4 Wire, Wye 3 Element, 3 Phase, 4 Wire, Wye provide customers with additional services and infor-
mation. JEMSTAR can help turn your profits around.
Instrumentation
LINE LINE
L1 L2 L3 N L1 L2 L3 N
DC
OUTPUT
WATT
DC
OUTPUT
WATT
Metering for Today and for the Future
- + - + 1-888-880-JEM1
1 2 3 4 5 6 6A 6B 1 2 3 4 5 6 6A 6B
EXT.
AUX.
EXT.
AUX.
Simply Powerful SCIENTIFIC COLUMBUS
Watthour Accuracy: 0.07% Reading exceeds Thermal Demand Emulation, Contact Inputs
POWER POWER IEC 687 Class 0.2 The JEMSTAR accuracy is Demand Prediction (2) Channels Programmable
unparalleled in the industry. for Pulse counter, Demand
Transformer Loss Compensation—TLC Synchronization, Status Input
7 8 9 10 11 12 12A 12B 7 8 9 10 11 12 12A 12B Graphical Display or TOU Rate Override.
Simultaneous Communications
Bi-Directional and 4 Quadrant Metering I/R Port, RS-232, RS-485, Modem S-Base, A-base, Switchboard
Per Phase and System Measurements Inputs and Outputs: Auto-ranging Voltage:
Watts, Vars, VA, Q, Voltage, Current, PF, THD, Analog Outputs are fully Programmable for any 55-530 VAC
- + LOAD - + LOAD
Watthours, Varhours, VAhours, Qhours, Amphours
Registers:
instantaneous measurement. (3) channels of either
0-1 or 4-20 mA.
Contact Outputs
Site Diagnostics include
installation verification and
DC DC
OUTPUT Instantaneous, Consumption, Demand (Sliding & (4) Channels Programmable as Threshold Alarms, on-going monitoring.
OUTPUT Fixed), Time of Peak, Average Power Factor, Site Monitoring Alarms, Energy Pulses, EOD
VAR VAR Coincident Demand, Coincident Power Factor, Output or Demand Prediction Alarm
Cumulative Demand, Continuous Cumulative
Demand,
www.rochester.com
E Models: Shown. S Models: External aux. power not required.
Adjust NOTE: Dynamic separation between the two analog outputs is limited to ±10 Vdc (±15 Vdc separation on E1 & S1 units). Headquarters
50 Fordham Road 255 North Union Street
Wilmington, MA 01887 Rochester, NY 14605
Tel: 978-988-4101 Tel: 585-263-7700
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 Fax: 978-988-4179 Fax: 585-454-7805
E-Mail: power.industrial@ametek.com E-Mail: info@rochester.com
108 109
SCI Transducer Cat 90-134(MTD) 108-109 1/9/02, 5:33 PM
SCIENTIFIC
DC Watt Transducers SCIENTIFIC
Specifications, Ordering Procedure,
COLUMBUS COLUMBUS & Wiring Diagram
DC WATT TRANSDUCERS
box is supplied for line-to-line voltages from 600 –1000 Rated Output (RO) ±1 mAdc at Nominal Inputs
Output Range 0 to ±1 mAdc
Vdc.
Accuracy 50 mVdc Shunt ±0.75% RO
100 mVdc Shunt ±0.5% RO
Scientific Columbus DC Watt Transducers have the Temperature Effect on Accuracy ± 0.015% / ° C (excluding shunts)
same three-year warranty as the Exceltronic line. Operating Temperature Range -20° C to +60° C
Compliance Voltage 10 Vdc
Load 0–10,000 Ω
Output Ripple Peak < 0.5% RO
Instrumentation
DC Rail Systems Model No.
Please consult the factory if you require any options with the 6268 DC Watt Transducer.
6268
Scientific Columbus DC Watt Transducers perform well for WIRING DIAGRAM (Style I Case)
monitoring dc power on electric rail systems. In a dc rail system,
the catenary is energized to a specified dc level for operating the Model 6268 DC Watt Transducer LINE
DC
train. A Scientific Columbus DC Watt Transducer can derive an OUTPUT
- +
analog output signal proportional to watts to reflect the dc power
1 2 3 4 5 MV
delivered to the train. SHUNT
7 8 9 10 11 12 12A
EXTERNAL
AUX. POWER LOAD
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
110 111
SCI Transducer Cat 90-134(MTD) 110-111 1/9/02, 5:33 PM
SCIENTIFIC
DC Watt Transducers SCIENTIFIC
Specifications, Ordering Procedure,
COLUMBUS COLUMBUS & Wiring Diagram
DC WATT TRANSDUCERS
box is supplied for line-to-line voltages from 600 –1000 Rated Output (RO) ±1 mAdc at Nominal Inputs
Output Range 0 to ±1 mAdc
Vdc.
Accuracy 50 mVdc Shunt ±0.75% RO
100 mVdc Shunt ±0.5% RO
Scientific Columbus DC Watt Transducers have the Temperature Effect on Accuracy ± 0.015% / ° C (excluding shunts)
same three-year warranty as the Exceltronic line. Operating Temperature Range -20° C to +60° C
Compliance Voltage 10 Vdc
Load 0–10,000 Ω
Output Ripple Peak < 0.5% RO
Instrumentation
DC Rail Systems Model No.
Please consult the factory if you require any options with the 6268 DC Watt Transducer.
6268
Scientific Columbus DC Watt Transducers perform well for WIRING DIAGRAM (Style I Case)
monitoring dc power on electric rail systems. In a dc rail system,
the catenary is energized to a specified dc level for operating the Model 6268 DC Watt Transducer LINE
DC
train. A Scientific Columbus DC Watt Transducer can derive an OUTPUT
- +
analog output signal proportional to watts to reflect the dc power
1 2 3 4 5 MV
delivered to the train. SHUNT
7 8 9 10 11 12 12A
EXTERNAL
AUX. POWER LOAD
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
110 111
SCI Transducer Cat 90-134(MTD) 110-111 1/9/02, 5:33 PM
SCIENTIFIC
DC Voltage Isolation Amplifiers SCIENTIFIC
Specifications
COLUMBUS COLUMBUS
DC VOLTAGE ISOLATION AMPLIFIERS
The output circuit is a hybrid amplifier operating in the Voltage Nominal 0 to ± 100 mVdc†
Input Ranges Available 0 to ±50 mVdc thru 0 to ± 1000 Vdc (customer specified)†
transconductance mode to provide true current output. Load Units Impedance
Only 0–20 Vdc 5000 Ohms/Volt
resistance variations from 0 –10,000 Ω have less than 0.1% effect 21–1000 Vdc 1400 Ohms/Volt
on the output current. External Input Range 108–132 Vac 108–132 Vac
Auxiliary Frequency Range 58–62 Hz 58–62 Hz
Power Burden 2 VA Nominal 5 VA Nominal
Scientific Columbus DC Voltage Isolation Amplifiers have the Rated Output (RO) 0 to ±1 mAdc for Standard Calibration 5, 20, or 50 mAdc for Standard Calibration,
depending on selected output range*
same three-year warranty as the Exceltronic line.
Accuracy ±0.5% RO at 25° C ±0.7% of Span
Temperature Effect on Accuracy ±0.04% / ° C ±0.05% / ° C
Operating Temperature Range -10° C to +70° C -10° C to +50° C
Features Applications Outputs Compliance Voltage 10 Vdc
See Table 2 on page 110.
Load 0–10,000 Ω
Output Ripple Peak 6271A unit contributes < 0.25% RO 6271 unit contributes < 0.25% of Span
◆ Complete isolation ◆ Telemetering ◆ 0 to ±1 mAdc at steady-state dc input at steady-state dc input
◆ DC shunt inputs or dc ◆ Recording devices ◆ 1–5 or 1–3–5 mAdc Response Time < 400 ms to 99% < 1 Second to 99%
voltage from 0–50 mV thru ◆ A/D converters Standard Calibration Gain ± 15% RO (minimum) ±20% of Span (minimum)
◆ 4–20 or 4–12–20 mAdc Adjustments Zero ± 1% RO (minimum) ±5% of Zero Point (minimum)
0–1000 V
◆ 10–50 or 10–30–50 mAdc Stability (per year) ±0.25% RO, Noncumulative ±0.4% of Span, Noncumulative
◆ 4000 Vdc input isolation
Operating Humidity 0–95% Noncondensing
◆ Filtered output Isolation Input to Input to
Output/Power/Case Output/Power/Case
(Output/Power/Case) (Output/Power/Case)
Dielectric Withstand 4000 Vdc 1500 VRMS at 60 Hz 4000 Vdc 1500 VRMS at 60 Hz
Maximum Net Weight 2 lbs., 2 oz. (1 kg) 3 lbs., 8 oz. (1.6 kg)
Approximate Dimensions 4.4" W x 3.9" D x 4.7" H 7.0" W x 3.7" D x 5.6" H
(excluding mounting plate) (112 mm x 99 mm x 119 mm) (178 mm x 94 mm x 142 mm)
Neutral-Current Sensor Warns of Magnetic Storms Style II Case, see page 122 Style I Case, see page 122
* P-Option includes 1–5/1–3–5, 4–20/4–12–20, and 10–50/10–30–50 mAdc outputs. Specifications subject to change without notice.
Off-the-shelf electronic components are used by a large investor- **Other input ranges available; consult factory.
Instrumentation
owned utility to measure quasi-direct currents flowing in the neutrals † All inputs are zero-based spans.
of key transformers during solar-magnetic storms. The primary aim is
to collect field data confirming the accuracy of recently developed
models of dc current during geomagnetic activity. The geomagnetic
current sensors interface with the utility’s SCADA system, so dis-
patchers can act accordingly when magnetic activity occurs.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
112 113
SCI Transducer Cat 90-134(MTD) 112-113 1/9/02, 5:33 PM
SCIENTIFIC
DC Voltage Isolation Amplifiers SCIENTIFIC
Specifications
COLUMBUS COLUMBUS
DC VOLTAGE ISOLATION AMPLIFIERS
The output circuit is a hybrid amplifier operating in the Voltage Nominal 0 to ± 100 mVdc†
Input Ranges Available 0 to ±50 mVdc thru 0 to ± 1000 Vdc (customer specified)†
transconductance mode to provide true current output. Load Units Impedance
Only 0–20 Vdc 5000 Ohms/Volt
resistance variations from 0 –10,000 Ω have less than 0.1% effect 21–1000 Vdc 1400 Ohms/Volt
on the output current. External Input Range 108–132 Vac 108–132 Vac
Auxiliary Frequency Range 58–62 Hz 58–62 Hz
Power Burden 2 VA Nominal 5 VA Nominal
Scientific Columbus DC Voltage Isolation Amplifiers have the Rated Output (RO) 0 to ±1 mAdc for Standard Calibration 5, 20, or 50 mAdc for Standard Calibration,
depending on selected output range*
same three-year warranty as the Exceltronic line.
Accuracy ±0.5% RO at 25° C ±0.7% of Span
Temperature Effect on Accuracy ±0.04% / ° C ±0.05% / ° C
Operating Temperature Range -10° C to +70° C -10° C to +50° C
Features Applications Outputs Compliance Voltage 10 Vdc
See Table 2 on page 110.
Load 0–10,000 Ω
Output Ripple Peak 6271A unit contributes < 0.25% RO 6271 unit contributes < 0.25% of Span
◆ Complete isolation ◆ Telemetering ◆ 0 to ±1 mAdc at steady-state dc input at steady-state dc input
◆ DC shunt inputs or dc ◆ Recording devices ◆ 1–5 or 1–3–5 mAdc Response Time < 400 ms to 99% < 1 Second to 99%
voltage from 0–50 mV thru ◆ A/D converters Standard Calibration Gain ± 15% RO (minimum) ±20% of Span (minimum)
◆ 4–20 or 4–12–20 mAdc Adjustments Zero ± 1% RO (minimum) ±5% of Zero Point (minimum)
0–1000 V
◆ 10–50 or 10–30–50 mAdc Stability (per year) ±0.25% RO, Noncumulative ±0.4% of Span, Noncumulative
◆ 4000 Vdc input isolation
Operating Humidity 0–95% Noncondensing
◆ Filtered output Isolation Input to Input to
Output/Power/Case Output/Power/Case
(Output/Power/Case) (Output/Power/Case)
Dielectric Withstand 4000 Vdc 1500 VRMS at 60 Hz 4000 Vdc 1500 VRMS at 60 Hz
Maximum Net Weight 2 lbs., 2 oz. (1 kg) 3 lbs., 8 oz. (1.6 kg)
Approximate Dimensions 4.4" W x 3.9" D x 4.7" H 7.0" W x 3.7" D x 5.6" H
(excluding mounting plate) (112 mm x 99 mm x 119 mm) (178 mm x 94 mm x 142 mm)
Neutral-Current Sensor Warns of Magnetic Storms Style II Case, see page 122 Style I Case, see page 122
* P-Option includes 1–5/1–3–5, 4–20/4–12–20, and 10–50/10–30–50 mAdc outputs. Specifications subject to change without notice.
Off-the-shelf electronic components are used by a large investor- **Other input ranges available; consult factory.
Instrumentation
owned utility to measure quasi-direct currents flowing in the neutrals † All inputs are zero-based spans.
of key transformers during solar-magnetic storms. The primary aim is
to collect field data confirming the accuracy of recently developed
models of dc current during geomagnetic activity. The geomagnetic
current sensors interface with the utility’s SCADA system, so dis-
patchers can act accordingly when magnetic activity occurs.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
112 113
SCI Transducer Cat 90-134(MTD) 112-113 1/9/02, 5:33 PM
Ordering Procedure Ordering Procedure
DC Voltage Isolation Amplifiers DC Voltage Isolation Amplifiers
Specify by base model number and appropriate selection or option suffixes in the order shown in the following example. Option Description * You must specify the desired output voltage:
-RS* Scaling Resistor For 0 to ±1 mAdc units, specify range from 0 to ±10 Vdc. Load impedance is 1 MΩ/Vdc
Scaling External
(minimum).
Resistor Option Auxiliary For P-Option units, specify range from 0-15 Vdc (PAN models) or 0-40 Vdc (PA models). Load
Base Model No. Output Option #1 #2 Input Power impedance is 200, 50, or 20 (kΩ/Vdc) (minimum) for units with outputs of 5, 20, or 50 mAdc,
respectively.
Table 1 Table 2 Table 3 Table 4 Table 5
This information is not part of the model number, but must be provided to the factory when
you place your order.
0 to ±1 mAdc
output 6271A
Table 4 Other Options
-RS -SM 100 mVdc
Option Description
-24 24 Vdc Loop-Powered (PA7 and PA7-B models only) If you require additional options not shown here, see Special
P-Option Options on page 128. When ordering any special options, or
Specify All units have 120 Vac external aux. (consult factory for specifications)
outputs 6271 more than three options, you must first consult the factory for
PAN7 output power. Specify other voltage, if -SM Seismic Brace (available with 0 to ±1 mAdc units)
voltage required: 69 Vac Aux., 240 Vac Aux., (consult factory if you desire this option with pricing and delivery estimates.
277 Vac Aux., or 480 Vac Aux. a P-Option unit)
-Z Zero-Based Output Calibration (ex.: PA7-Z = 0-20 mAdc)
(available only with P-Option units, except PAN-B
EXAMPLES: 6271A-RS-SM-100 mVdc models)
0 to ±1 mAdc output DC Voltage Isolation Amplifier, resistor scaling (converts current output to voltage output),
seismic brace, 0 to ±100 mVdc (std.) input calibration. Table 5 Input Selection
6271PAN7-RS-SM-100 mVdc Type of Input Input Span
4-20 mAdc output DC Voltage Isolation Amplifier, resistor scaling (converts current output to voltage output), Current 0 to ±1 mAdc All inputs for these units are zero-based spans. The standard
seismic brace, 0-100 mVdc (std.) input calibration. Voltage 0 to ±50 mVdc thru 0 to ±1000 Vdc input span is 0 to ±100 mVdc. All 0 to ±1 mAdc output units are
inherently bidirectional; P-Option units are unidirectional or
bidirectional as indicated in Table 2.
Table 1 Base Model Number Selection
Model No. WIRING DIAGRAMS FOR 0 to ±1 mAdc UNITS (Style II Case) AND P-OPTION UNITS (Style I Case)
(0 to ±1 mAdc Units)
6271A 6271A DC Voltage Isolation Amplifier 6271 DC Voltage Isolation Amplifier
(P-Option Units) 0 to ±1 mAdc Units P-Option Units
6271 EXTERNAL
EXTERNAL AUX. POWER
AUX.
AUX. PWR. GAIN
Table 2 Output Selection AUX.
GAIN
DC
OUTPUT
DC
+
Instrumentation
OUTPUT
Compliance Voltage/ Maximum Open + REF.
P-Option Output Range Maximum Load Circuit Voltage 1 2 3 4 5 6
PAN6 1-5 mAdc 15 Vdc/3000 Ω 30 Vdc 1 2 3 4 5 6
0 to ±1 mAdc output is
PAN7 4-20 mAdc 15 Vdc/750 Ω 30 Vdc
standard, and is specified
PAN8 10-50 mAdc 15 Vdc/300 Ω 30 Vdc
by the Base Model
Numbers. For outputs PAN6-B 1-3-5 mAdc 15 Vdc/3000 Ω 30 Vdc
7 8
other than 0 to ±1 mAdc, PAN7-B 4-12-20 mAdc 15 Vdc/750 Ω 30 Vdc
indicate the appropriate PAN8-B 10-30-50 mAdc 15 Vdc/300 Ω 30 Vdc DC
7 8
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
114 115
SCI Transducer Cat 90-134(MTD) 114-115 1/9/02, 5:34 PM
Ordering Procedure Ordering Procedure
DC Voltage Isolation Amplifiers DC Voltage Isolation Amplifiers
Specify by base model number and appropriate selection or option suffixes in the order shown in the following example. Option Description * You must specify the desired output voltage:
-RS* Scaling Resistor For 0 to ±1 mAdc units, specify range from 0 to ±10 Vdc. Load impedance is 1 MΩ/Vdc
Scaling External
(minimum).
Resistor Option Auxiliary For P-Option units, specify range from 0-15 Vdc (PAN models) or 0-40 Vdc (PA models). Load
Base Model No. Output Option #1 #2 Input Power impedance is 200, 50, or 20 (kΩ/Vdc) (minimum) for units with outputs of 5, 20, or 50 mAdc,
respectively.
Table 1 Table 2 Table 3 Table 4 Table 5
This information is not part of the model number, but must be provided to the factory when
you place your order.
0 to ±1 mAdc
output 6271A
Table 4 Other Options
-RS -SM 100 mVdc
Option Description
-24 24 Vdc Loop-Powered (PA7 and PA7-B models only) If you require additional options not shown here, see Special
P-Option Options on page 128. When ordering any special options, or
Specify All units have 120 Vac external aux. (consult factory for specifications)
outputs 6271 more than three options, you must first consult the factory for
PAN7 output power. Specify other voltage, if -SM Seismic Brace (available with 0 to ±1 mAdc units)
voltage required: 69 Vac Aux., 240 Vac Aux., (consult factory if you desire this option with pricing and delivery estimates.
277 Vac Aux., or 480 Vac Aux. a P-Option unit)
-Z Zero-Based Output Calibration (ex.: PA7-Z = 0-20 mAdc)
(available only with P-Option units, except PAN-B
EXAMPLES: 6271A-RS-SM-100 mVdc models)
0 to ±1 mAdc output DC Voltage Isolation Amplifier, resistor scaling (converts current output to voltage output),
seismic brace, 0 to ±100 mVdc (std.) input calibration. Table 5 Input Selection
6271PAN7-RS-SM-100 mVdc Type of Input Input Span
4-20 mAdc output DC Voltage Isolation Amplifier, resistor scaling (converts current output to voltage output), Current 0 to ±1 mAdc All inputs for these units are zero-based spans. The standard
seismic brace, 0-100 mVdc (std.) input calibration. Voltage 0 to ±50 mVdc thru 0 to ±1000 Vdc input span is 0 to ±100 mVdc. All 0 to ±1 mAdc output units are
inherently bidirectional; P-Option units are unidirectional or
bidirectional as indicated in Table 2.
Table 1 Base Model Number Selection
Model No. WIRING DIAGRAMS FOR 0 to ±1 mAdc UNITS (Style II Case) AND P-OPTION UNITS (Style I Case)
(0 to ±1 mAdc Units)
6271A 6271A DC Voltage Isolation Amplifier 6271 DC Voltage Isolation Amplifier
(P-Option Units) 0 to ±1 mAdc Units P-Option Units
6271 EXTERNAL
EXTERNAL AUX. POWER
AUX.
AUX. PWR. GAIN
Table 2 Output Selection AUX.
GAIN
DC
OUTPUT
DC
+
Instrumentation
OUTPUT
Compliance Voltage/ Maximum Open + REF.
P-Option Output Range Maximum Load Circuit Voltage 1 2 3 4 5 6
PAN6 1-5 mAdc 15 Vdc/3000 Ω 30 Vdc 1 2 3 4 5 6
0 to ±1 mAdc output is
PAN7 4-20 mAdc 15 Vdc/750 Ω 30 Vdc
standard, and is specified
PAN8 10-50 mAdc 15 Vdc/300 Ω 30 Vdc
by the Base Model
Numbers. For outputs PAN6-B 1-3-5 mAdc 15 Vdc/3000 Ω 30 Vdc
7 8
other than 0 to ±1 mAdc, PAN7-B 4-12-20 mAdc 15 Vdc/750 Ω 30 Vdc
indicate the appropriate PAN8-B 10-30-50 mAdc 15 Vdc/300 Ω 30 Vdc DC
7 8
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
114 115
SCI Transducer Cat 90-134(MTD) 114-115 1/9/02, 5:34 PM
SCIENTIFIC
DC Instrument Amplifiers SCIENTIFIC
Ordering Procedure & Wiring Diagrams
COLUMBUS COLUMBUS
ORDERING PROCEDURE FOR DC INSTRUMENT AMPLIFIERS
The Model 6181A DC Instrument Amplifier is a non-isolated Model No.
6181A Please consult the factory if you require any options with the 6181A DC Instrument Amplifier.
unit with unmatched stability which provides a direct interface
to low-level signals.
DC INPUT
DC + -
DC
EXTERNAL INPUT EXTERNAL OUTPUT
DC OUTPUT
AUX. POWER + - + - AUX. POWER + -
R1
5
SPECIFICATIONS 1 2 3 4 5 6 7
3 IS IL 5
1 2 3 4 5 6 7
3
R2
CURRENT CURRENT VOLTAGE
6181 6181 7 EL
INPUT 6 OUTPUT 4 OUTPUT
R1 VOLTAGE R1
4 R1 7 INPUT ES
Specifications DC Instrument Amplifier R2
6
R2 R2
External Input Range 100–130 Vac IL
=
R1 + R2 6
EL R1 + R2
IS R1 =
Auxiliary Frequency Range 50–500 Hz ES R1
Power Burden 5 VA (maximum)
LOW INPUT IMPEDANCE (CURRENT INPUT) HIGH INPUT IMPEDANCE (VOLTAGE INPUT)
DC Input Limits Current 0–10 µA thru 0–5 mA HIGH OUTPUT IMPEDANCE (CURRENT OUTPUT) LOW OUTPUT IMPEDANCE (VOLTAGE OUTPUT)
(zero-based span) Voltage 0–10 mV thru 0–8 V
DC Output Limits Current 0–10 mA (maximum)
(zero-based span) Voltage 0–8 V (maximum)
Effective Input Current < 10 Ω
Impedance Voltage >10 MΩ
DC Linearity ± 0.5% of Maximum Output*
Transresistance Mode Transconductance Mode
Gain Stability ± 0.5% of Maximum Output*
Zero Stability 20 µV / ° C (maximum), 5 µV / ° C (typical)
Referenced to Input
DC INPUT
Accuracy/Temperature Effect/ DC
Instrumentation
Long-Term Stability Dependent on externally selected components EXTERNAL INPUT EXTERNAL DC
AUX. POWER + - DC
OUTPUT
AUX. POWER + OUTPUT -
Operating Temperature Range -10° C to +50° C + - - +
IS 3 IL 5
3 5
Response Time < 100 ms to 99% 1 2 3 4 5 6 7 1 2 3 4 5 6 7
CURRENT VOLTAGE 6181 CURRENT
6181 EL OUTPUT 4 6
Maximum Net Weight 1 lb., 14 oz. (0.9 kg) INPUT
VOLTAGE
OUTPUT
4 6 INPUT RK 4
RK
Approximate Dimensions 4.4" W x 3.9" D x 4.7" H RK ES
(excluding mounting plate) (112 mm x 99 mm x 119 mm) RK
ES
Style II Case, see page 122 EL
= RK 6
IL
= RK
IS
* Must fall within input, output, and feedback resistance limits listed. Specifications subject to change without notice.
LOW INPUT IMPEDANCE (CURRENT INPUT) HIGH INPUT IMPEDANCE (VOLTAGE INPUT)
LOW OUTPUT IMPEDANCE (VOLTAGE OUTPUT) HIGH OUTPUT IMPEDANCE (CURRENT OUTPUT)
Zero Adjust
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
116 117
SCI Transducer Cat 90-134(MTD) 116-117 1/9/02, 5:34 PM
SCIENTIFIC
DC Instrument Amplifiers SCIENTIFIC
Ordering Procedure & Wiring Diagrams
COLUMBUS COLUMBUS
ORDERING PROCEDURE FOR DC INSTRUMENT AMPLIFIERS
The Model 6181A DC Instrument Amplifier is a non-isolated Model No.
6181A Please consult the factory if you require any options with the 6181A DC Instrument Amplifier.
unit with unmatched stability which provides a direct interface
to low-level signals.
DC INPUT
DC + -
DC
EXTERNAL INPUT EXTERNAL OUTPUT
DC OUTPUT
AUX. POWER + - + - AUX. POWER + -
R1
5
SPECIFICATIONS 1 2 3 4 5 6 7
3 IS IL 5
1 2 3 4 5 6 7
3
R2
CURRENT CURRENT VOLTAGE
6181 6181 7 EL
INPUT 6 OUTPUT 4 OUTPUT
R1 VOLTAGE R1
4 R1 7 INPUT ES
Specifications DC Instrument Amplifier R2
6
R2 R2
External Input Range 100–130 Vac IL
=
R1 + R2 6
EL R1 + R2
IS R1 =
Auxiliary Frequency Range 50–500 Hz ES R1
Power Burden 5 VA (maximum)
LOW INPUT IMPEDANCE (CURRENT INPUT) HIGH INPUT IMPEDANCE (VOLTAGE INPUT)
DC Input Limits Current 0–10 µA thru 0–5 mA HIGH OUTPUT IMPEDANCE (CURRENT OUTPUT) LOW OUTPUT IMPEDANCE (VOLTAGE OUTPUT)
(zero-based span) Voltage 0–10 mV thru 0–8 V
DC Output Limits Current 0–10 mA (maximum)
(zero-based span) Voltage 0–8 V (maximum)
Effective Input Current < 10 Ω
Impedance Voltage >10 MΩ
DC Linearity ± 0.5% of Maximum Output*
Transresistance Mode Transconductance Mode
Gain Stability ± 0.5% of Maximum Output*
Zero Stability 20 µV / ° C (maximum), 5 µV / ° C (typical)
Referenced to Input
DC INPUT
Accuracy/Temperature Effect/ DC
Instrumentation
Long-Term Stability Dependent on externally selected components EXTERNAL INPUT EXTERNAL DC
AUX. POWER + - DC
OUTPUT
AUX. POWER + OUTPUT -
Operating Temperature Range -10° C to +50° C + - - +
IS 3 IL 5
3 5
Response Time < 100 ms to 99% 1 2 3 4 5 6 7 1 2 3 4 5 6 7
CURRENT VOLTAGE 6181 CURRENT
6181 EL OUTPUT 4 6
Maximum Net Weight 1 lb., 14 oz. (0.9 kg) INPUT
VOLTAGE
OUTPUT
4 6 INPUT RK 4
RK
Approximate Dimensions 4.4" W x 3.9" D x 4.7" H RK ES
(excluding mounting plate) (112 mm x 99 mm x 119 mm) RK
ES
Style II Case, see page 122 EL
= RK 6
IL
= RK
IS
* Must fall within input, output, and feedback resistance limits listed. Specifications subject to change without notice.
LOW INPUT IMPEDANCE (CURRENT INPUT) HIGH INPUT IMPEDANCE (VOLTAGE INPUT)
LOW OUTPUT IMPEDANCE (VOLTAGE OUTPUT) HIGH OUTPUT IMPEDANCE (CURRENT OUTPUT)
Zero Adjust
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
116 117
SCI Transducer Cat 90-134(MTD) 116-117 1/9/02, 5:34 PM
SCIENTIFIC
Analog-to-Pulse Converters
SCIENTIFIC
Specifications
COLUMBUS COLUMBUS
ANALOG-TO-PULSE CONVERTERS
(see pages 118–119), pulse recorders, or other Form-A (2-wire) Rated Models 6070, 6370 2–14,000 cph
Output 6096, & 6396
or Form-C (3-wire) receiving devices. A second, isolated Form-C (RO) Models 6270, 6296 2–900,000 cph
6570, 6596, & SAF
relay may be added on some models. Isolated inputs are also available
Accuracy Models 6070, 6270, ±(0.05% Reading + 0.005% RO)
as an option on some models. 6096, 6296, & SAF
Models 6370, 6396, ±(0.09% Reading + 0.01% RO)
6570, & 6596
Scientific Columbus analog-to-pulse converters have the same three-year warranty as the Exceltronic line. Temperature Models 6070, 6270, ±0.003% / ° C (maximum)
Effect on 6096, 6296, & SAF
Accuracy Models 6370, 6396, ±0.005% / ° C (maximum)
6570, & 6596
Operating Temperature Range -20° C to +70° C
Features Applications Outputs Output Models 6070, 6370, Form-C, SPDT, 3-Wire, Mercury-Wetted Relays
6096, & 6396
Models 6270, 6296, Form-C, SPDT, 3-Wire, Solid-State
◆ Accuracy to ± 0.1% of ◆ Converting any analog ◆ 2–14,000 cph (relay) 6570, 6596, & SAF
reading signal into a pulse signal Relay Contact Rating 15 VA at 1 A (maximum) or 150 Vac/15 Vdc (maximum) with resistive load.
◆ 2–900,000 cph (solid-state) Contact protection required for inductive loads. Relay maintains its position under power-failure conditions.
◆ Unidirectional or ◆ Substations
Relay Contact Life One billion operations when operated within specifications.
bidirectional
◆ Generating stations Solid-State Output Contact Rating 28 Vdc (maximum). VCESAT: 1 Vdc (maximum) at 7 mAdc
◆ Form-C mercury-wetted Standard Calibration Adjustment ±1% (minimum)
relay or solid-state output Stability (per year) ± 0.1% RO, Noncumulative
◆ Multichannel units available Operating Humidity 0-95% Noncondensing
Isolation Input/Power/Case and Output/Power Case Input/Output (except counter-drive output)
Dielectric Withstand 1500 VRMS 1000 VRMS on KYZ Output
Instrumentation
Surge Withstand ANSI/IEEE C37.90.1
Orientation Models 6070, 6370, Within 30° of Vertical/Horizontal
6096, & 6396
Models 6270, 6296, Unlimited
6570, 6596, & SAF
Maximum Net Weight 3 lbs., 2 oz. (1.4 kg)
Approximate Dimensions 7.0" W x 3.7" D x 5.8" H
(excluding mounting plate) (178 mm x 94 mm x 147 mm)
Style I Case, see page 122
Specifications subject to change without notice.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
118 119
SCI Transducer Cat 90-134(MTD) 118-119 1/9/02, 5:34 PM
SCIENTIFIC
Analog-to-Pulse Converters
SCIENTIFIC
Specifications
COLUMBUS COLUMBUS
ANALOG-TO-PULSE CONVERTERS
(see pages 118–119), pulse recorders, or other Form-A (2-wire) Rated Models 6070, 6370 2–14,000 cph
Output 6096, & 6396
or Form-C (3-wire) receiving devices. A second, isolated Form-C (RO) Models 6270, 6296 2–900,000 cph
6570, 6596, & SAF
relay may be added on some models. Isolated inputs are also available
Accuracy Models 6070, 6270, ±(0.05% Reading + 0.005% RO)
as an option on some models. 6096, 6296, & SAF
Models 6370, 6396, ±(0.09% Reading + 0.01% RO)
6570, & 6596
Scientific Columbus analog-to-pulse converters have the same three-year warranty as the Exceltronic line. Temperature Models 6070, 6270, ±0.003% / ° C (maximum)
Effect on 6096, 6296, & SAF
Accuracy Models 6370, 6396, ±0.005% / ° C (maximum)
6570, & 6596
Operating Temperature Range -20° C to +70° C
Features Applications Outputs Output Models 6070, 6370, Form-C, SPDT, 3-Wire, Mercury-Wetted Relays
6096, & 6396
Models 6270, 6296, Form-C, SPDT, 3-Wire, Solid-State
◆ Accuracy to ± 0.1% of ◆ Converting any analog ◆ 2–14,000 cph (relay) 6570, 6596, & SAF
reading signal into a pulse signal Relay Contact Rating 15 VA at 1 A (maximum) or 150 Vac/15 Vdc (maximum) with resistive load.
◆ 2–900,000 cph (solid-state) Contact protection required for inductive loads. Relay maintains its position under power-failure conditions.
◆ Unidirectional or ◆ Substations
Relay Contact Life One billion operations when operated within specifications.
bidirectional
◆ Generating stations Solid-State Output Contact Rating 28 Vdc (maximum). VCESAT: 1 Vdc (maximum) at 7 mAdc
◆ Form-C mercury-wetted Standard Calibration Adjustment ±1% (minimum)
relay or solid-state output Stability (per year) ± 0.1% RO, Noncumulative
◆ Multichannel units available Operating Humidity 0-95% Noncondensing
Isolation Input/Power/Case and Output/Power Case Input/Output (except counter-drive output)
Dielectric Withstand 1500 VRMS 1000 VRMS on KYZ Output
Instrumentation
Surge Withstand ANSI/IEEE C37.90.1
Orientation Models 6070, 6370, Within 30° of Vertical/Horizontal
6096, & 6396
Models 6270, 6296, Unlimited
6570, 6596, & SAF
Maximum Net Weight 3 lbs., 2 oz. (1.4 kg)
Approximate Dimensions 7.0" W x 3.7" D x 5.8" H
(excluding mounting plate) (178 mm x 94 mm x 147 mm)
Style I Case, see page 122
Specifications subject to change without notice.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
118 119
SCI Transducer Cat 90-134(MTD) 118-119 1/9/02, 5:34 PM
Ordering Procedure Wiring Diagrams
Analog-to-Pulse Converters Analog-to-Pulse Converters
Specify by base model number and appropriate selection or option suffixes in the order shown in the following example. Models 6070 & 6370 Model 6270 & 6570
DC EXTERNAL DC EXTERNAL
Add'l. Form-C Counter Isolated INPUT AUX. POWER INPUT AUX. POWER
Mounting Output(s) Drive Input - + - +
Base Model No. Orientation Option #1 Option #2 Option #3
1 2 3 4 5 6 6A 1 2 3 4 5 6 6A
SAF-2
Table 1 -VTable 2 -ATable 3 -CTable 3 -ISTable 4
7 8 9 10 11 12 12A 7 8 9 10 11 12 12A
EXAMPLES: SAF-2-V-A-C-IS
0 to -1 mAdc, 2-channel Analog-to-Pulse Converter with two standard Form-C solid-state outputs; vertical mounting;
OUTPUT RELAY SOLID-STATE OUTPUT
two additional Form-C mercury-wetted relays; two counter-drive outputs; isolated inputs. (FORM-C) (FORM-C)
Table 1 Base Model Number Selection Models 6096 & 6396 Model 6296 & 6596
DC EXTERNAL DC EXTERNAL
Model No. Input Configuration Input Impedance Output CPH Range* INPUT AUX. POWER INPUT AUX. POWER
** Standard SAF-2 and SAF-3 units have common positive input terminals.
OUTPUT RELAYS SOLID-STATE OUTPUTS
Table 2 Mounting Orientation Selection (FORM-C) (FORM-C)
Instrumentation
SOLID-STATE
-V Vertical Mounting (wall mounting with vertical OUTPUTS (FORM-C) DC INPUTS
terminal blocks)
-+-+-+ EXTERNAL
Table 3 Output Options AUX. POWER Model SAF-3 is shown with options -A (additional
mercury-wetted relays) and -C (counter drives).
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Option Description SAF-1 models have only the Channel "A" connec-
These options apply only to SAF models. The number of relays, solid-state A B C tions; SAF-2 models have only the Channel "A" and
-A Add'l. Form-C Mercury-Wetted Relay(s)
outputs, or counter drives corresponds to the number of channels in the "B" connections.
-B Add'l. Form-C Solid-State Output(s) C B A
unit. (Example: An SAF-3-A unit has three additional Form-C mercury-
-C Counter-Drive Output(s) A B C
wetted relays in addition to the three standard solid-state outputs.) A B C
Terminals 9, 11, & 13 (positive current input) are
Table 4 Isolated Input Option commoned internally. Requires negative current
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
input for proper operation.
Option Description
This option applies only to SAF-model units and requires a Style V case.
-IS Isolated Inputs
(See page 123 for case dimensions.)
OPTIONAL OPTIONAL
COUNTER-DRIVE OUTPUT RELAYS
Gain Adjust
Please consult the factory if you require any additional options with Analog-to-Pulse Converters. OUTPUTS (FORM-C)
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
120 121
SCI Transducer Cat 90-134(MTD) 120-121 1/9/02, 5:34 PM
Ordering Procedure Wiring Diagrams
Analog-to-Pulse Converters Analog-to-Pulse Converters
Specify by base model number and appropriate selection or option suffixes in the order shown in the following example. Models 6070 & 6370 Model 6270 & 6570
DC EXTERNAL DC EXTERNAL
Add'l. Form-C Counter Isolated INPUT AUX. POWER INPUT AUX. POWER
Mounting Output(s) Drive Input - + - +
Base Model No. Orientation Option #1 Option #2 Option #3
1 2 3 4 5 6 6A 1 2 3 4 5 6 6A
SAF-2
Table 1 -VTable 2 -ATable 3 -CTable 3 -ISTable 4
7 8 9 10 11 12 12A 7 8 9 10 11 12 12A
EXAMPLES: SAF-2-V-A-C-IS
0 to -1 mAdc, 2-channel Analog-to-Pulse Converter with two standard Form-C solid-state outputs; vertical mounting;
OUTPUT RELAY SOLID-STATE OUTPUT
two additional Form-C mercury-wetted relays; two counter-drive outputs; isolated inputs. (FORM-C) (FORM-C)
Table 1 Base Model Number Selection Models 6096 & 6396 Model 6296 & 6596
DC EXTERNAL DC EXTERNAL
Model No. Input Configuration Input Impedance Output CPH Range* INPUT AUX. POWER INPUT AUX. POWER
** Standard SAF-2 and SAF-3 units have common positive input terminals.
OUTPUT RELAYS SOLID-STATE OUTPUTS
Table 2 Mounting Orientation Selection (FORM-C) (FORM-C)
Instrumentation
SOLID-STATE
-V Vertical Mounting (wall mounting with vertical OUTPUTS (FORM-C) DC INPUTS
terminal blocks)
-+-+-+ EXTERNAL
Table 3 Output Options AUX. POWER Model SAF-3 is shown with options -A (additional
mercury-wetted relays) and -C (counter drives).
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Option Description SAF-1 models have only the Channel "A" connec-
These options apply only to SAF models. The number of relays, solid-state A B C tions; SAF-2 models have only the Channel "A" and
-A Add'l. Form-C Mercury-Wetted Relay(s)
outputs, or counter drives corresponds to the number of channels in the "B" connections.
-B Add'l. Form-C Solid-State Output(s) C B A
unit. (Example: An SAF-3-A unit has three additional Form-C mercury-
-C Counter-Drive Output(s) A B C
wetted relays in addition to the three standard solid-state outputs.) A B C
Terminals 9, 11, & 13 (positive current input) are
Table 4 Isolated Input Option commoned internally. Requires negative current
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
input for proper operation.
Option Description
This option applies only to SAF-model units and requires a Style V case.
-IS Isolated Inputs
(See page 123 for case dimensions.)
OPTIONAL OPTIONAL
COUNTER-DRIVE OUTPUT RELAYS
Gain Adjust
Please consult the factory if you require any additional options with Analog-to-Pulse Converters. OUTPUTS (FORM-C)
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
120 121
SCI Transducer Cat 90-134(MTD) 120-121 1/9/02, 5:34 PM
SCIENTIFIC
Registers SCIENTIFIC
Ordering Procedure & Wiring Diagrams
COLUMBUS COLUMBUS
ORDERING PROCEDURE FOR REGISTERS
The Models 6152 and 6153 Registers are used to display pulse outputs. Specify by base model number and appropriate option or selection suffixes in the order shown in the following example.
They are designed for use with all Scientific Columbus pulse-output Auxiliary Mounting External
Output Configuration Mounting Auxiliary
transducers and analog-to-pulse converters. They can also be used as Base Model No. Option #1 Option #2 Orientation Power
remote registers for our JEM meters. Models 6172 and 6173 Registers are 6152R D P -V
Table 1 Table 2 Table 3 Table 4
available for remote mounting of the can away from the counter. Consult
the factory for more information on these products. All units have 120 Vac external aux. power. Specify other voltage, if
required: 69 Vac Aux., 240 Vac Aux., 277 Vac Aux., or 480 Vac Aux.
Scientific Columbus registers have the same three-year warranty as the
Exceltronic line.
EXAMPLE: 6152RDP-V
FEATURES Single 6-digit Resettable Register, single auxiliary relay output, panel mounting, vertical mounting.
◆ Unidirectional or ◆ 6-digit resettable or ◆ Optional auxiliary relays
bidirectional 7-digit nonresettable display and panel mounting
Table 1 Base Model Number Selection Table 2 Auxiliary Output Options
SPECIFICATIONS Model No. Description Configuration Option Description
6152 Single 7-digit Register Nonresettable D Single Auxiliary Relay Output
Specifications Registers 6152R Single 6-digit Register Resettable (one relay per register)
6153 Dual 7-digit Register Nonresettable DD Dual Auxiliary Relay Output
Input Single or Dual 3-Wire, SPDT, Dry Contact 6153R Dual 6-digit Register Resettable (two relays per register)
Form-C Relays
Maximum Input Rate 15,000 cph
Open Contact Voltage VOC Maximum ≤ 15 Vdc Table 3 Mounting Configuration Options Table 4 Mounting Orientation Selection
Closed Contact Current ISC ≤ 10 mAdc Maximum
Closed Contact Voltage VSC Closed ≤ 2.5 Vdc
Option Description Option Description
External Input Range 108–132 Vac You must specify mounting
Std. (leave blank) Wall or Shelf Mounting -H Horizontal Mounting
Auxiliary Frequency Range 50–500 Hz orientation (vertical or
Power Burden 1.5 VA Nominal at 120 V P Panel Mounting -V Vertical Mounting
horizontal) on units with D
Accuracy Exact (1 output for 1 input) or DD options.
Operating Temperature Range -20° C to +60° C WIRING DIAGRAMS FOR REGISTERS (Style I Case)
Visual Output Single or Dual Registers, Figure Size 3/16" High, 6-Digit Resettable or 7-Digit Nonresettable Display
Models 6152, 6152R, 6152D, 6152RD, Models 6153, 6153R, 6153D, & Models 6153DD & 6153RDD
Electrical Output (optional) Single or Dual Isolated Relay Output: Form-C, 3-Wire, SPDT
6152DD, & 6152RDD 6153RD
Relay Contact Rating 15 VA at 1 A (maximum) or 150 Vac/15 Vdc (maximum) with resistive load. Contact protection required for inductive loads.
Y'F
Relay Contact Life One billion operations when operated within specifications. **
F F
REGISTER
Instrumentation
REGISTER REGISTER K'F
Register One count is registered for each transfer of the Form-C, 3-wire input. INPUT PULSE INPUT PULSE INPUT PULSE
Characteristics The register holds counts indefinitely under power-failure conditions and does not give false counts when the power is restored. CONTACT SOURCE CONTACT SOURCE CONTACT SOURCE Z'F
Y YF YF
Y' Y'F
Output Relay Characteristics The normally open and normally closed contacts transfer their previous position for each transfer of the corresponding input relay. * * Y''F
Z F ZF F ZF
Response Time < 250 ms K' K'F
K''F
YR YR
Operating Humidity 0–95% Noncondensing Z' Z'F Z''F
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
122 123
SCI Transducer Cat 90-134(MTD) 122-123 1/9/02, 5:34 PM
SCIENTIFIC
Registers SCIENTIFIC
Ordering Procedure & Wiring Diagrams
COLUMBUS COLUMBUS
ORDERING PROCEDURE FOR REGISTERS
The Models 6152 and 6153 Registers are used to display pulse outputs. Specify by base model number and appropriate option or selection suffixes in the order shown in the following example.
They are designed for use with all Scientific Columbus pulse-output Auxiliary Mounting External
Output Configuration Mounting Auxiliary
transducers and analog-to-pulse converters. They can also be used as Base Model No. Option #1 Option #2 Orientation Power
remote registers for our JEM meters. Models 6172 and 6173 Registers are 6152R D P -V
Table 1 Table 2 Table 3 Table 4
available for remote mounting of the can away from the counter. Consult
the factory for more information on these products. All units have 120 Vac external aux. power. Specify other voltage, if
required: 69 Vac Aux., 240 Vac Aux., 277 Vac Aux., or 480 Vac Aux.
Scientific Columbus registers have the same three-year warranty as the
Exceltronic line.
EXAMPLE: 6152RDP-V
FEATURES Single 6-digit Resettable Register, single auxiliary relay output, panel mounting, vertical mounting.
◆ Unidirectional or ◆ 6-digit resettable or ◆ Optional auxiliary relays
bidirectional 7-digit nonresettable display and panel mounting
Table 1 Base Model Number Selection Table 2 Auxiliary Output Options
SPECIFICATIONS Model No. Description Configuration Option Description
6152 Single 7-digit Register Nonresettable D Single Auxiliary Relay Output
Specifications Registers 6152R Single 6-digit Register Resettable (one relay per register)
6153 Dual 7-digit Register Nonresettable DD Dual Auxiliary Relay Output
Input Single or Dual 3-Wire, SPDT, Dry Contact 6153R Dual 6-digit Register Resettable (two relays per register)
Form-C Relays
Maximum Input Rate 15,000 cph
Open Contact Voltage VOC Maximum ≤ 15 Vdc Table 3 Mounting Configuration Options Table 4 Mounting Orientation Selection
Closed Contact Current ISC ≤ 10 mAdc Maximum
Closed Contact Voltage VSC Closed ≤ 2.5 Vdc
Option Description Option Description
External Input Range 108–132 Vac You must specify mounting
Std. (leave blank) Wall or Shelf Mounting -H Horizontal Mounting
Auxiliary Frequency Range 50–500 Hz orientation (vertical or
Power Burden 1.5 VA Nominal at 120 V P Panel Mounting -V Vertical Mounting
horizontal) on units with D
Accuracy Exact (1 output for 1 input) or DD options.
Operating Temperature Range -20° C to +60° C WIRING DIAGRAMS FOR REGISTERS (Style I Case)
Visual Output Single or Dual Registers, Figure Size 3/16" High, 6-Digit Resettable or 7-Digit Nonresettable Display
Models 6152, 6152R, 6152D, 6152RD, Models 6153, 6153R, 6153D, & Models 6153DD & 6153RDD
Electrical Output (optional) Single or Dual Isolated Relay Output: Form-C, 3-Wire, SPDT
6152DD, & 6152RDD 6153RD
Relay Contact Rating 15 VA at 1 A (maximum) or 150 Vac/15 Vdc (maximum) with resistive load. Contact protection required for inductive loads.
Y'F
Relay Contact Life One billion operations when operated within specifications. **
F F
REGISTER
Instrumentation
REGISTER REGISTER K'F
Register One count is registered for each transfer of the Form-C, 3-wire input. INPUT PULSE INPUT PULSE INPUT PULSE
Characteristics The register holds counts indefinitely under power-failure conditions and does not give false counts when the power is restored. CONTACT SOURCE CONTACT SOURCE CONTACT SOURCE Z'F
Y YF YF
Y' Y'F
Output Relay Characteristics The normally open and normally closed contacts transfer their previous position for each transfer of the corresponding input relay. * * Y''F
Z F ZF F ZF
Response Time < 250 ms K' K'F
K''F
YR YR
Operating Humidity 0–95% Noncondensing Z' Z'F Z''F
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
122 123
SCI Transducer Cat 90-134(MTD) 122-123 1/9/02, 5:34 PM
SCIENTIFIC
Calibrator
SCIENTIFIC
Specifications & Ordering Procedure
COLUMBUS COLUMBUS
CALIBRATOR
ORDERING PROCEDURE
Features Applications Outputs Model No. Description
6444 6444 Calibrator, 60 Hz
◆ Multifunction calibrator/tester ◆ Transducer calibration ◆ 0–150 V 6444-50 6444 Calibrator, 50 Hz
6444-240V Aux. 6444 Calibrator, 60 Hz, 240 Vac External Auxiliary Power
◆ Digitally programmable ◆ Receiving inspection ◆ 0–5 or 0–10 A 6444-50 240V Aux. 6444 Calibrator, 50 Hz, 240 Vac External Auxiliary Power
◆ Self-contained ◆ 0–750 or 0–1500 W 6444-EX 6444 Calibrator, 60 Hz, Expanded Scale
◆ Field testing
Reference
6444-P Calibrator with Internal Offset Adapter for Calibrating Transducers with 1–5/1–3–5 mAdc, 4–20/4–12–20 mAdc,
◆ Portable ◆ 0–750 or 0–1500 Vars or 10–50/10–30–50 mAdc Outputs
6242B Offset Adaptor (to be used with 6444 Calibrator) for Calibrating Transducers with 1–5/1–3–5 mAdc,
◆ One-person operation 4–20/4–12–20 mAdc, or 10–50/10–30–50 mAdc Outputs
◆ No external loads required
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
124 125
SCI Transducer Cat 90-134(MTD) 124-125 1/9/02, 5:34 PM
SCIENTIFIC
Calibrator
SCIENTIFIC
Specifications & Ordering Procedure
COLUMBUS COLUMBUS
CALIBRATOR
ORDERING PROCEDURE
Features Applications Outputs Model No. Description
6444 6444 Calibrator, 60 Hz
◆ Multifunction calibrator/tester ◆ Transducer calibration ◆ 0–150 V 6444-50 6444 Calibrator, 50 Hz
6444-240V Aux. 6444 Calibrator, 60 Hz, 240 Vac External Auxiliary Power
◆ Digitally programmable ◆ Receiving inspection ◆ 0–5 or 0–10 A 6444-50 240V Aux. 6444 Calibrator, 50 Hz, 240 Vac External Auxiliary Power
◆ Self-contained ◆ 0–750 or 0–1500 W 6444-EX 6444 Calibrator, 60 Hz, Expanded Scale
◆ Field testing
Reference
6444-P Calibrator with Internal Offset Adapter for Calibrating Transducers with 1–5/1–3–5 mAdc, 4–20/4–12–20 mAdc,
◆ Portable ◆ 0–750 or 0–1500 Vars or 10–50/10–30–50 mAdc Outputs
6242B Offset Adaptor (to be used with 6444 Calibrator) for Calibrating Transducers with 1–5/1–3–5 mAdc,
◆ One-person operation 4–20/4–12–20 mAdc, or 10–50/10–30–50 mAdc Outputs
◆ No external loads required
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
124 125
SCI Transducer Cat 90-134(MTD) 124-125 1/9/02, 5:34 PM
Case Dimensions for Case Dimensions for
Styles I, II, & III Cases Styles IV & V Cases
SCREW HEAD PROTRUDES .09" (2.29 mm) (TYP.) SCREW HEAD PROTRUDES .09" (2.29 mm) (TYP.)
1.02" .53"
(25.91 mm) .44" FROM CASE - 4 SCREWS .25" FROM CASE - 4 SCREWS .53"
(13.46 mm) 1.14" .43"
(11.18 mm) (6.35 mm) (10.92 mm) (13.46 mm)
(28.96 mm) .25"
(6.35 mm)
.094" RAD.
(2.39 mm) .094" RAD.
.23" (2.39 mm)
3.54"
(50.80 mm)
(50.80 mm)
2.00"
2.00"
5.02"
(9.14 mm) (127.51 mm) .36" DIA.
1.50"
(38.10 mm) 2 KEYSLOTS (9.14 mm) 5.78"
1.50"
(38.10 mm) 2 KEYSLOTS (146.81 mm)
.187" DIA.
(4.75 mm) .187" DIA.
6.95" 2 MOUNTING (4.75 mm)
(176.53 mm) HOLES 2 MOUNTING
7.31" 4.40"
(185.67 mm) (111.76 mm) HOLES
7.83" .07"
(198.88 mm) 4.75"
(1.78 mm)
(120.65 mm)
5.25" .07"
(133.35 mm)
Style I (1.78 mm)
Style IV
(2.39 mm)
.36" DIA. 4.15"
(9.14 mm) (105.41 mm) 5.15"
1.50" .23"
(76.20 mm)
(130.81 mm)
(38.10 mm) 2 KEYSLOTS (5.84 mm)
3.00"
.36" DIA. 5.28"
.187" DIA. (9.14 mm)
(4.75 mm) (134.11 mm)
2 KEYSLOTS
2 MOUNTING 1.50"
4.40"
(111.76 mm) HOLES .07" (38.10 mm) .187" DIA.
(1.78 mm)
4.75" (4.75 mm)
(120.65 mm) 2 MOUNTING
HOLES
5.25"
(133.35 mm)
7.16"
(181.86 mm) .10"
Style II 7.31"
(185.67 mm)
(2.54 mm)
7.83"
(198.88 mm)
Instrumentation
.09" (2.29 mm) (TYP.) (6.35 mm)
.46" FROM CASE - .094" RAD.
(11.68 mm) 2 SCREWS (2.39 mm) .53"
(13.46 mm)
.23"
(52.07 mm)
(38.10 mm)
(5.84 mm)
2.05"
1.50"
Style III
Terminal strips shown for illustration purposes only. For exact terminal-strip configuration on specific units, see connection diagrams. Terminal strips shown for illustration purposes only. For exact terminal-strip configuration on specific units, see connection diagrams.
Drawings not to scale. Drawings not to scale.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
126 127
SCI Transducer Cat 90-134(MTD) 126-127 1/9/02, 5:34 PM
Case Dimensions for Case Dimensions for
Styles I, II, & III Cases Styles IV & V Cases
SCREW HEAD PROTRUDES .09" (2.29 mm) (TYP.) SCREW HEAD PROTRUDES .09" (2.29 mm) (TYP.)
1.02" .53"
(25.91 mm) .44" FROM CASE - 4 SCREWS .25" FROM CASE - 4 SCREWS .53"
(13.46 mm) 1.14" .43"
(11.18 mm) (6.35 mm) (10.92 mm) (13.46 mm)
(28.96 mm) .25"
(6.35 mm)
.094" RAD.
(2.39 mm) .094" RAD.
.23" (2.39 mm)
3.54"
(50.80 mm)
(50.80 mm)
2.00"
2.00"
5.02"
(9.14 mm) (127.51 mm) .36" DIA.
1.50"
(38.10 mm) 2 KEYSLOTS (9.14 mm) 5.78"
1.50"
(38.10 mm) 2 KEYSLOTS (146.81 mm)
.187" DIA.
(4.75 mm) .187" DIA.
6.95" 2 MOUNTING (4.75 mm)
(176.53 mm) HOLES 2 MOUNTING
7.31" 4.40"
(185.67 mm) (111.76 mm) HOLES
7.83" .07"
(198.88 mm) 4.75"
(1.78 mm)
(120.65 mm)
5.25" .07"
(133.35 mm)
Style I (1.78 mm)
Style IV
(2.39 mm)
.36" DIA. 4.15"
(9.14 mm) (105.41 mm) 5.15"
1.50" .23"
(76.20 mm)
(130.81 mm)
(38.10 mm) 2 KEYSLOTS (5.84 mm)
3.00"
.36" DIA. 5.28"
.187" DIA. (9.14 mm)
(4.75 mm) (134.11 mm)
2 KEYSLOTS
2 MOUNTING 1.50"
4.40"
(111.76 mm) HOLES .07" (38.10 mm) .187" DIA.
(1.78 mm)
4.75" (4.75 mm)
(120.65 mm) 2 MOUNTING
HOLES
5.25"
(133.35 mm)
7.16"
(181.86 mm) .10"
Style II 7.31"
(185.67 mm)
(2.54 mm)
7.83"
(198.88 mm)
Instrumentation
.09" (2.29 mm) (TYP.) (6.35 mm)
.46" FROM CASE - .094" RAD.
(11.68 mm) 2 SCREWS (2.39 mm) .53"
(13.46 mm)
.23"
(52.07 mm)
(38.10 mm)
(5.84 mm)
2.05"
1.50"
Style III
Terminal strips shown for illustration purposes only. For exact terminal-strip configuration on specific units, see connection diagrams. Terminal strips shown for illustration purposes only. For exact terminal-strip configuration on specific units, see connection diagrams.
Drawings not to scale. Drawings not to scale.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
126 127
SCI Transducer Cat 90-134(MTD) 126-127 1/9/02, 5:34 PM
Transducer Glossary Transducer Glossary
Accuracy conversion is 500 W in to 5 Vdc out, the unit could be adjusted Front Access (-FA) 15 A Input (-7)
The degree of uncertainty with which a measured value to equate any output from 2.5 Vdc to 10 Vdc, for a 500 W input. The -FA option allows for external calibration or access to test The unit operates from 0–20 A. The standard calibration is
agrees with the ideal value. The drawback to using the wide adjustment is that it makes jack points on XLP transducers. 1500 W or vars per element input for 1 mAdc output.
precision calibration of the unit more difficult (a small turn of
Analog Output Shorting Relay (-CE) the potentiometer results in a large change in the output). Frequency 25 A Input (-8)
The shorting relay monitors the external auxiliary power signal These units have true voltage outputs, versus a milliamp A measure of the number of complete cycles of a waveform The unit operates from 0–30 A. The standard calibration is
on a watt, var, or watt/var unit. If the external auxiliary power output applied across a scaling resistor. per unit of time, specified in Hertz (Hz), or cycles per second. 2500 W or vars per element input for 1 mAdc output. The
deviates from a prespecified range (i.e., below 85 V), a relay The following options refer to signal input frequency only: 25 A option requires a larger case and is not available on all
contact closes, shorting the analog output. This helps prevent Combination Unidirectional/Bidirectional Unit (-UB) transducers.
erroneous signals from the analog output due to low external The -UB option applies only to P-Option combined watt/var 50 Hz Operation (-12)
auxiliary power. transducers. This option specifies a unidirectional output for Internal Auxiliary Power (self-powered) (A4)
400 Hz Operation (-6) The power required for correct operation of a transducer is
watts (example: 4–20 mAdc) and a bidirectional output for vars
Apparent Power (volt-amps) (example: 4–12–20 mAdc). supplied via the line being measured, and adds additional
Full Scale (F.S.) burden to the input.
The product of the applied voltage and current in an ac circuit. The specified maximum magnitude of the input quantity being
Apparent power, or volt-amps, is not the true power of the Compliance Voltage measured that can be applied to a transducer without causing Exception: For average-sensing current and voltage
circuit because the power factor is not considered in the The specified maximum voltage that a transducer current a change in performance beyond specified tolerance. transducers with 0–1 mAdc output, the A4 option specifies
calculation. output must be able to supply while maintaining the specified optional accuracy of 0.1%.
accuracy. Full Scale Output
Auxiliary Power The specified maximum output value for which the stated Isolated Inputs (-IS)
See External Auxiliary Power and Internal Auxiliary Power. Current Transformer (CT) accuracy condition applies. The -IS option applies only to Models SAF-2 and SAF-3 analog-
Transformer used to accurately scale ac currents up or down, to-pulse converters. This option specifies that the positive
Balanced Load or to provide isolation. Generally used to scale large primary Impedance current inputs are electrically isolated from each other.
Refers to an equal loading of the phases in a polyphase or bus currents to usable values for measuring purposes. The total opposing force to the flow of current in an ac circuit.
system (current and phase angle). Isolated Outputs (for units with external auxiliary power) (-C2)
Current Transformer Ratio (CTR) Input Complete isolation between the watt and var outputs of
Bidirectional (-B) The ratio of primary amps divided by secondary amps. The standard transducer input is 5 A and 120 V; however, combined watt/var transducers. The -C2 replaces A2 in the
A bidirectional unit allows measurements of inputs which many other inputs are available: model number. Units with the -C2 option require a Style I case.
flow in two directions, forward and reverse. A typical Dielectric This does not apply to XLG transducers.
4–12–20 mAdc device would have a zero setting at 12 and The medium used to provide electrical isolation or separation. 69 V Input (-0)
minimum and maximum settings at 4 and 20, respectively. The unit operates from 0–75 V. The standard calibration is Isolated Outputs (for units with internal auxiliary power) (-C4)
The -B option applies only to P-Option units. Add -B to the Dielectric Withstand 250 W or vars per element input for 1 mAdc output.
Complete isolation between the watt and var outputs of
PAN or PA designator to specify a bidirectional unit (for The ability of a medium that is providing electrical isolation in 240 V Input (-1) combined watt/var transducers. The -C4 replaces A4 in the
example, 4–12–20 mAdc versus 4–20 mAdc). a transducer to withstand an applied voltage for a specified The unit operates from 0–300 V. The standard calibration is model number. Units with the -C4 option require a Style I case.
time without flashover or puncture. 1000 W or vars per element input for 1 mAdc output. This does not apply to XLG transducers.
Burden
Load imposed by a transducer on the measured input circuit, Dielectric Withstand Voltage Test 277 V Input (-9)
The unit operates from 0–340 V. The standard calibration is Isolation
expressed in volt-amps. Test used to determine the ability of insulating materials and To be electrically separate. A measure of the strength of the
spacings to withstand specified overvoltages for a specified 1200 W or vars per element input for 1 mAdc output.
dielectric providing the electrical division or separation.
Calibration time (one minute unless otherwise stated) without flashover or 480 V Input (-2)
Adjustment of a transducer so the output is within a specified puncture. The unit operates from 0–600 V. The standard calibration is KYZ
range for particular values of the input. 2000 W or vars per element input for 1 mAdc output. A designator for the Form-C pulse initiator output from a
Effective Power (watts) transducer.
50–200% Calibration Adjustment (current outputs) (-20) In ac measurements, effective power (measured in watts) 1 A Input (-3)
The common gain adjustment is ± 2%. When the wide-range equals the product of voltage, current, and power factor (the The unit operates from 0–2 A. The standard calibration is
100 W or vars per element input for 1 mAdc output. Lag
adjustment is specified, the current output can be adjusted cosine of the phase angle between the current and the The condition where the current is delayed in time with respect
from 50–200% of its normal value. For example, the normal voltage). (Watts = EI cos(ø)) 2.5 A Input (-4) to the voltage in an ac circuit (for example, an inductive load).
output for a 500 W input is 1 mAdc when using a 1-element The unit operates from 0–5 A. The standard calibration is
watt transducer. This unit could be adjusted to equate any External Auxiliary Power (A2) 250 W or vars per element input for 1 mAdc output. Lead
output from 0.5 mAdc to 2 mAdc, for a 500 W input. The The power required for correct operation of a transducer is The condition where the current precedes in time with respect
drawback to using the wide adjustment is that it makes supplied via an external auxiliary power source, rather than 7.5 A Input (-11)
to the voltage in an ac circuit (for example, a capacitive load).
precision calibration of the unit more difficult (a small turn of the line being measured. Unless otherwise specified, external The unit operates from 0–15 A. The standard calibration is
the potentiometer results in a large change in the output). 750 W or vars per element input for 1 mAdc output.
Reference
auxiliary power is 120 Vac, 50–500 Hz. Load
10 A Input (-5) The total impedance of all the items in the output circuit.
50–200% Calibration Adjustment (voltage outputs) (-21) Exception: For average-sensing current and voltage The unit operates from 0–20 A. The standard calibration is
The common gain adjustment is ± 2%. When the wide-range transducers with 0–1 mAdc output, the A2 option 1000 W or vars per element input for 1 mAdc output.
adjustment is specified, the voltage output can be adjusted specifies standard accuracy of 0.25% (default accuracy).
from 50–200% of its normal value. For example, if the normal
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
128 129
SCI Transducer Cat 90-134(MTD) 128-129 1/9/02, 5:34 PM
Transducer Glossary Transducer Glossary
Accuracy conversion is 500 W in to 5 Vdc out, the unit could be adjusted Front Access (-FA) 15 A Input (-7)
The degree of uncertainty with which a measured value to equate any output from 2.5 Vdc to 10 Vdc, for a 500 W input. The -FA option allows for external calibration or access to test The unit operates from 0–20 A. The standard calibration is
agrees with the ideal value. The drawback to using the wide adjustment is that it makes jack points on XLP transducers. 1500 W or vars per element input for 1 mAdc output.
precision calibration of the unit more difficult (a small turn of
Analog Output Shorting Relay (-CE) the potentiometer results in a large change in the output). Frequency 25 A Input (-8)
The shorting relay monitors the external auxiliary power signal These units have true voltage outputs, versus a milliamp A measure of the number of complete cycles of a waveform The unit operates from 0–30 A. The standard calibration is
on a watt, var, or watt/var unit. If the external auxiliary power output applied across a scaling resistor. per unit of time, specified in Hertz (Hz), or cycles per second. 2500 W or vars per element input for 1 mAdc output. The
deviates from a prespecified range (i.e., below 85 V), a relay The following options refer to signal input frequency only: 25 A option requires a larger case and is not available on all
contact closes, shorting the analog output. This helps prevent Combination Unidirectional/Bidirectional Unit (-UB) transducers.
erroneous signals from the analog output due to low external The -UB option applies only to P-Option combined watt/var 50 Hz Operation (-12)
auxiliary power. transducers. This option specifies a unidirectional output for Internal Auxiliary Power (self-powered) (A4)
400 Hz Operation (-6) The power required for correct operation of a transducer is
watts (example: 4–20 mAdc) and a bidirectional output for vars
Apparent Power (volt-amps) (example: 4–12–20 mAdc). supplied via the line being measured, and adds additional
Full Scale (F.S.) burden to the input.
The product of the applied voltage and current in an ac circuit. The specified maximum magnitude of the input quantity being
Apparent power, or volt-amps, is not the true power of the Compliance Voltage measured that can be applied to a transducer without causing Exception: For average-sensing current and voltage
circuit because the power factor is not considered in the The specified maximum voltage that a transducer current a change in performance beyond specified tolerance. transducers with 0–1 mAdc output, the A4 option specifies
calculation. output must be able to supply while maintaining the specified optional accuracy of 0.1%.
accuracy. Full Scale Output
Auxiliary Power The specified maximum output value for which the stated Isolated Inputs (-IS)
See External Auxiliary Power and Internal Auxiliary Power. Current Transformer (CT) accuracy condition applies. The -IS option applies only to Models SAF-2 and SAF-3 analog-
Transformer used to accurately scale ac currents up or down, to-pulse converters. This option specifies that the positive
Balanced Load or to provide isolation. Generally used to scale large primary Impedance current inputs are electrically isolated from each other.
Refers to an equal loading of the phases in a polyphase or bus currents to usable values for measuring purposes. The total opposing force to the flow of current in an ac circuit.
system (current and phase angle). Isolated Outputs (for units with external auxiliary power) (-C2)
Current Transformer Ratio (CTR) Input Complete isolation between the watt and var outputs of
Bidirectional (-B) The ratio of primary amps divided by secondary amps. The standard transducer input is 5 A and 120 V; however, combined watt/var transducers. The -C2 replaces A2 in the
A bidirectional unit allows measurements of inputs which many other inputs are available: model number. Units with the -C2 option require a Style I case.
flow in two directions, forward and reverse. A typical Dielectric This does not apply to XLG transducers.
4–12–20 mAdc device would have a zero setting at 12 and The medium used to provide electrical isolation or separation. 69 V Input (-0)
minimum and maximum settings at 4 and 20, respectively. The unit operates from 0–75 V. The standard calibration is Isolated Outputs (for units with internal auxiliary power) (-C4)
The -B option applies only to P-Option units. Add -B to the Dielectric Withstand 250 W or vars per element input for 1 mAdc output.
Complete isolation between the watt and var outputs of
PAN or PA designator to specify a bidirectional unit (for The ability of a medium that is providing electrical isolation in 240 V Input (-1) combined watt/var transducers. The -C4 replaces A4 in the
example, 4–12–20 mAdc versus 4–20 mAdc). a transducer to withstand an applied voltage for a specified The unit operates from 0–300 V. The standard calibration is model number. Units with the -C4 option require a Style I case.
time without flashover or puncture. 1000 W or vars per element input for 1 mAdc output. This does not apply to XLG transducers.
Burden
Load imposed by a transducer on the measured input circuit, Dielectric Withstand Voltage Test 277 V Input (-9)
The unit operates from 0–340 V. The standard calibration is Isolation
expressed in volt-amps. Test used to determine the ability of insulating materials and To be electrically separate. A measure of the strength of the
spacings to withstand specified overvoltages for a specified 1200 W or vars per element input for 1 mAdc output.
dielectric providing the electrical division or separation.
Calibration time (one minute unless otherwise stated) without flashover or 480 V Input (-2)
Adjustment of a transducer so the output is within a specified puncture. The unit operates from 0–600 V. The standard calibration is KYZ
range for particular values of the input. 2000 W or vars per element input for 1 mAdc output. A designator for the Form-C pulse initiator output from a
Effective Power (watts) transducer.
50–200% Calibration Adjustment (current outputs) (-20) In ac measurements, effective power (measured in watts) 1 A Input (-3)
The common gain adjustment is ± 2%. When the wide-range equals the product of voltage, current, and power factor (the The unit operates from 0–2 A. The standard calibration is
100 W or vars per element input for 1 mAdc output. Lag
adjustment is specified, the current output can be adjusted cosine of the phase angle between the current and the The condition where the current is delayed in time with respect
from 50–200% of its normal value. For example, the normal voltage). (Watts = EI cos(ø)) 2.5 A Input (-4) to the voltage in an ac circuit (for example, an inductive load).
output for a 500 W input is 1 mAdc when using a 1-element The unit operates from 0–5 A. The standard calibration is
watt transducer. This unit could be adjusted to equate any External Auxiliary Power (A2) 250 W or vars per element input for 1 mAdc output. Lead
output from 0.5 mAdc to 2 mAdc, for a 500 W input. The The power required for correct operation of a transducer is The condition where the current precedes in time with respect
drawback to using the wide adjustment is that it makes supplied via an external auxiliary power source, rather than 7.5 A Input (-11)
to the voltage in an ac circuit (for example, a capacitive load).
precision calibration of the unit more difficult (a small turn of the line being measured. Unless otherwise specified, external The unit operates from 0–15 A. The standard calibration is
the potentiometer results in a large change in the output). 750 W or vars per element input for 1 mAdc output.
Reference
auxiliary power is 120 Vac, 50–500 Hz. Load
10 A Input (-5) The total impedance of all the items in the output circuit.
50–200% Calibration Adjustment (voltage outputs) (-21) Exception: For average-sensing current and voltage The unit operates from 0–20 A. The standard calibration is
The common gain adjustment is ± 2%. When the wide-range transducers with 0–1 mAdc output, the A2 option 1000 W or vars per element input for 1 mAdc output.
adjustment is specified, the voltage output can be adjusted specifies standard accuracy of 0.25% (default accuracy).
from 50–200% of its normal value. For example, if the normal
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
128 129
SCI Transducer Cat 90-134(MTD) 128-129 1/9/02, 5:34 PM
Transducer Glossary Transducer Glossary
24 Vdc Loop-Powered (-24) Power Factor (PF) Special Calibration (-SC) True RMS Amps
This is a variation to the normal 4–20 mAdc output unit (PA7) The ratio of the effective power (watts) to the apparent power All units can be calibrated to within a specified range. This The effective value of an ac signal. For an amp signal, true
or 4–12–20 mAdc output unit (PA7-B) that requires a 24 Vdc (volt-amps). Equal to the cosine of the phase angle for single- information can be found in the “Other Options” table under RMS is a precise method of stating the amp value regardless
power supply to power the analog output. The transducer phase or 3-phase, 3-wire or 4-wire systems. the Ordering Procedure for most types of transducers. For of waveform distortion. An ac measurement which is equal in
does not supply any current; it only controls the current flow in some types of transducers, the information is in the Special power transfer capability to a corresponding dc current.
the output circuit. All -24 option units are self-powered, unless Range Options section on page 128.
otherwise specified. Nominal operating limits, specified by the lowest calibration True RMS Volts
point to the highest calibration point. Stability The effective value of an ac signal. For a voltage
Nominal The ability of a transducer to maintain its performance signal, true RMS is a precise method of stating the voltage
The normal operating value. Rated Output (RO) characteristics over a specified period of time. value regardless of the waveform distortion. An ac measure-
The output at standard calibration. ment which is equal in power transfer capability to a
Overload Standard Calibration corresponding dc voltage.
The specified maximum magnitude of the input quantity being Reactive Power (var) The nominal point at which a transducer is adjusted.
measured that can be applied to a transducer for a specified A component of apparent power (volt-amps) which does not Unbalanced Loads
period of time without causing damage. produce any real power (watt) transfer (the sine of the phase Surge Withstand Refers to an unequal loading of the phases in a polyphase
angle between the current and the voltage). (Var = VA2 - W 2 A measure of a transducer’s ability to withstand high-voltage, system (current and/or phase angle).
Overrange or Var = EI sin (ø)) high-frequency transients of short duration without damage.
The specified maximum operating point for which the stated Unidirectional Unit
accuracy condition applies. Reading Surge Withstand Capability (SWC) Test A unidirectional unit allows inputs to be measured in
The expected output at a given input value. (Ref. ANSI/IEEE C37.90.1) one direction only. The stated output range (for example,
Peak to Peak The SWC test wave is an oscillatory wave, frequency range of 4–20 mAdc) indicates the minimum and maximum input levels.
The amplitude of the ac waveform from its positive peak to its Real Power (in an ac circuit) 1-1.5 MHz, voltage range of 2.5-3 kV crest value of first peak,
negative peak. The average value of the instantaneous product of volts and envelope decaying to 50% of the crest value of the first peak Voltage Transformer (VT)
amps over a fixed period of time. in not less than 6 µs from the start of the wave. The source Transformer used to accurately scale ac voltages up
Phase Angle impedance is from 150-200 Ω. The test wave is to be applied or down, or to provide isolation. Generally used to scale large
The angular displacement between a current and voltage Response Time to a test specimen at a repetition rate of not less than 50 tests primary or bus voltages to usable values for measuring
waveform, measured in degrees or radians. The time for a transducer output signal to reach 99% of its per second for a period of not less than two seconds. purposes.
final value after a step change in the applied input. Typically (All voltage and time values refer to the open circuit condition
P-Option the response is an exponential curve. of the generator.) Voltage Transformer Ratio (VTR)
P-Option refers to model number designators that specify The ratio of primary volts divided by secondary volts.
certain outputs required for process control applications: Ripple Transducer
The magnitude of ac fluctuations in a dc signal, after filtering. A device for converting an electrical signal into a usable Zero-Based Output Calibration (-Z)
1–5 mAdc Output Usually expressed as a percentage of rated output. direct current or voltage for measurement purposes. The -Z option applies only to P-Option units. The normal zero
(-PAN6) Where a compliance rating of 3000 Ω or 15 Vdc is point—1, 4, or 10 mAdc—is replaced with a 0 mAdc zero
required. Root-Mean-Square (RMS) Transformer Factor point. For example, when a PAN7-Z unit is specified, the
(-PA6) Where a compliance rating of 8000 Ω or 40 Vdc is The effective value of alternating current or voltage. The RMS The product of the current transformer ratio (CTR) and the output range of the unit will be 0–20 mAdc instead of
required. value equates an ac signal to a dc signal that provides the voltage transformer ratio (VTR). Also called the power ratio. 4–20 mAdc. The -Z option is not available with PAN-B models.
same power transfer.
(-P6 for XLP models) Where a compliance rating of 5000 Ω
or 25 Vdc is required. Scaling Resistor (-RS)
4–20 mAdc Output The -RS option provides a scaled voltage output by the
(-PAN7) Where a compliance rating of 750 Ω or 15 Vdc is attachment of an external resistor to the transducer. The
required. output is not a “true” voltage output and may be susceptible
to loading errors. The resistor can be attached internally if
(-PA7) Where a compliance rating of 2000 Ω or 40 Vdc is specified by the user when ordering.
required.
(-P7 for XLP models) Where a compliance rating of 1250 Ω Seismic Brace (-SM)
or 25 Vdc is required. The seismic brace is added to the transducer to keep its
printed circuit boards stable. These are not seismically rated
10–50 mAdc Output units.
(-PAN8) Where a compliance rating of 300 Ω or 15 Vdc is
Reference
required. Self-Powered
See Internal Auxiliary Power.
(-PA8) Where a compliance rating of 600 Ω or 30 Vdc is
required.
Span
The algebraic difference between the upper and lower values
of a range.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
130 131
SCI Transducer Cat 90-134(MTD) 130-131 1/9/02, 5:35 PM
Transducer Glossary Transducer Glossary
24 Vdc Loop-Powered (-24) Power Factor (PF) Special Calibration (-SC) True RMS Amps
This is a variation to the normal 4–20 mAdc output unit (PA7) The ratio of the effective power (watts) to the apparent power All units can be calibrated to within a specified range. This The effective value of an ac signal. For an amp signal, true
or 4–12–20 mAdc output unit (PA7-B) that requires a 24 Vdc (volt-amps). Equal to the cosine of the phase angle for single- information can be found in the “Other Options” table under RMS is a precise method of stating the amp value regardless
power supply to power the analog output. The transducer phase or 3-phase, 3-wire or 4-wire systems. the Ordering Procedure for most types of transducers. For of waveform distortion. An ac measurement which is equal in
does not supply any current; it only controls the current flow in some types of transducers, the information is in the Special power transfer capability to a corresponding dc current.
the output circuit. All -24 option units are self-powered, unless Range Options section on page 128.
otherwise specified. Nominal operating limits, specified by the lowest calibration True RMS Volts
point to the highest calibration point. Stability The effective value of an ac signal. For a voltage
Nominal The ability of a transducer to maintain its performance signal, true RMS is a precise method of stating the voltage
The normal operating value. Rated Output (RO) characteristics over a specified period of time. value regardless of the waveform distortion. An ac measure-
The output at standard calibration. ment which is equal in power transfer capability to a
Overload Standard Calibration corresponding dc voltage.
The specified maximum magnitude of the input quantity being Reactive Power (var) The nominal point at which a transducer is adjusted.
measured that can be applied to a transducer for a specified A component of apparent power (volt-amps) which does not Unbalanced Loads
period of time without causing damage. produce any real power (watt) transfer (the sine of the phase Surge Withstand Refers to an unequal loading of the phases in a polyphase
angle between the current and the voltage). (Var = VA2 - W 2 A measure of a transducer’s ability to withstand high-voltage, system (current and/or phase angle).
Overrange or Var = EI sin (ø)) high-frequency transients of short duration without damage.
The specified maximum operating point for which the stated Unidirectional Unit
accuracy condition applies. Reading Surge Withstand Capability (SWC) Test A unidirectional unit allows inputs to be measured in
The expected output at a given input value. (Ref. ANSI/IEEE C37.90.1) one direction only. The stated output range (for example,
Peak to Peak The SWC test wave is an oscillatory wave, frequency range of 4–20 mAdc) indicates the minimum and maximum input levels.
The amplitude of the ac waveform from its positive peak to its Real Power (in an ac circuit) 1-1.5 MHz, voltage range of 2.5-3 kV crest value of first peak,
negative peak. The average value of the instantaneous product of volts and envelope decaying to 50% of the crest value of the first peak Voltage Transformer (VT)
amps over a fixed period of time. in not less than 6 µs from the start of the wave. The source Transformer used to accurately scale ac voltages up
Phase Angle impedance is from 150-200 Ω. The test wave is to be applied or down, or to provide isolation. Generally used to scale large
The angular displacement between a current and voltage Response Time to a test specimen at a repetition rate of not less than 50 tests primary or bus voltages to usable values for measuring
waveform, measured in degrees or radians. The time for a transducer output signal to reach 99% of its per second for a period of not less than two seconds. purposes.
final value after a step change in the applied input. Typically (All voltage and time values refer to the open circuit condition
P-Option the response is an exponential curve. of the generator.) Voltage Transformer Ratio (VTR)
P-Option refers to model number designators that specify The ratio of primary volts divided by secondary volts.
certain outputs required for process control applications: Ripple Transducer
The magnitude of ac fluctuations in a dc signal, after filtering. A device for converting an electrical signal into a usable Zero-Based Output Calibration (-Z)
1–5 mAdc Output Usually expressed as a percentage of rated output. direct current or voltage for measurement purposes. The -Z option applies only to P-Option units. The normal zero
(-PAN6) Where a compliance rating of 3000 Ω or 15 Vdc is point—1, 4, or 10 mAdc—is replaced with a 0 mAdc zero
required. Root-Mean-Square (RMS) Transformer Factor point. For example, when a PAN7-Z unit is specified, the
(-PA6) Where a compliance rating of 8000 Ω or 40 Vdc is The effective value of alternating current or voltage. The RMS The product of the current transformer ratio (CTR) and the output range of the unit will be 0–20 mAdc instead of
required. value equates an ac signal to a dc signal that provides the voltage transformer ratio (VTR). Also called the power ratio. 4–20 mAdc. The -Z option is not available with PAN-B models.
same power transfer.
(-P6 for XLP models) Where a compliance rating of 5000 Ω
or 25 Vdc is required. Scaling Resistor (-RS)
4–20 mAdc Output The -RS option provides a scaled voltage output by the
(-PAN7) Where a compliance rating of 750 Ω or 15 Vdc is attachment of an external resistor to the transducer. The
required. output is not a “true” voltage output and may be susceptible
to loading errors. The resistor can be attached internally if
(-PA7) Where a compliance rating of 2000 Ω or 40 Vdc is specified by the user when ordering.
required.
(-P7 for XLP models) Where a compliance rating of 1250 Ω Seismic Brace (-SM)
or 25 Vdc is required. The seismic brace is added to the transducer to keep its
printed circuit boards stable. These are not seismically rated
10–50 mAdc Output units.
(-PAN8) Where a compliance rating of 300 Ω or 15 Vdc is
Reference
required. Self-Powered
See Internal Auxiliary Power.
(-PA8) Where a compliance rating of 600 Ω or 30 Vdc is
required.
Span
The algebraic difference between the upper and lower values
of a range.
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
130 131
SCI Transducer Cat 90-134(MTD) 130-131 1/9/02, 5:35 PM
Special Options & Abbreviations AC & Calibration Formulas
AC FORMULAS
When ordering any Special Options, or more than three options,
you must first consult the factory for pricing and delivery estimates. Alternating Current Formulas
Direct Current
To Find Single-Phase Two-Phase* Four-Wire Three-Phase Formulas
DC External Auxiliary Power Frequency– 25 Hz Operation (-25)
If dc external auxiliary power is required, the following levels A measure of the number of complete cycles of a waveform I x E x PF I x E x 2 x PF I x E x 1.73 x PF IxE
are available: per unit of time, specified in Hertz (Hz), or cycles per second. Kilowatts
1000 1000 1000 1000
This option refers to signal input frequency only.
24 Vdc external auxiliary power (-JB)
48 Vdc external auxiliary power (-JC) Isolated VT Inputs (-AY) IxE IxEx2 I x E x 1.73
125 Vdc external auxiliary power (-JD) The -AY option specifies that the voltage inputs are isolated Kilovolt-Amps
from each other on 3-element watt or var transducers. 1000 1000 1000
Extended Range (-ER)
Special calibration levels that fall outside the normal Special Calibration (Frequency Transducers) I x E x % Eff. x PF I x E x 2 x % Eff. x PF I x E x 1.73 x % Eff. x PF I x E x % Eff.
calibration range. Frequency transducers can be calibrated within a specific Horsepower (output)
range. Please consult the factory for special calibration 746 746 746 746
Fast Response (-FR) requirements.
With fast response, the analog output responds faster to the
Amps when Kilowatts kW x 1000 kW x 1000 kW x 1000 kW x 1000
change in input. The normal response time is 400 ms to 99%, Test Jack (-TJ)
are known
but with the fast response option this changes to 50 ms or The test jack is connected in series with the analog output to E x PF 2 x E x PF 1.73 x E x PF E
100 ms to 99%. The change in response time results in an allow testing without disconnecting the unit. The transducer is
inversely proportional increase in output ripple. Consult connected to the standard via the test jack to verify the circuit
Amps when Kilovolt-Amps kVA x 1000 kVA x 1000 kVA x 1000
factory for other response time requirements. is working and to test the accuracy of the unit. The total
are known
resistance on the test jack plus the analog output cannot E 2xE 1.73 x E
Sepia Drawings (-DG) exceed the maximum load resistance of the transducer per its
Drawings that can be used to reproduce blueprints. specification. The test jack is shorted when it is not in use.
Amps when Horsepower hp x 746 hp x 746 hp x 746 hp x 746
is known
E x % Eff. x PF 2 x E x % Eff. x PF 1.73 x E x % Eff. x PF E x % Eff.
STANDARD ABBREVIATIONS
I = Line Current (Amps) % Eff. = Percent Efficiency kW = Kilowatts hp = Horsepower
E = Volts Line to Line PF = Power Factor kVA = Kilovolt-Amps x = Multiply
*For three-wire, two-phase circuits the current in the common conductor is 1.41 times that in either of the other two conductors.
Symbol or Symbol or Symbol or
Abbreviation Unit or Term Abbreviation Unit or Term Abbreviation Unit or Term
Reference
F.S. full scale ohm VT voltage transformer
h hour PF power factor VTR voltage transformer ratio
hp horsepower PKe primary constant of W watt
HV high voltage energy (watthours**/pulse) Wh watthour
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
132 133
SCI Transducer Cat 90-134(MTD) 132-133 1/9/02, 5:35 PM
Special Options & Abbreviations AC & Calibration Formulas
AC FORMULAS
When ordering any Special Options, or more than three options,
you must first consult the factory for pricing and delivery estimates. Alternating Current Formulas
Direct Current
To Find Single-Phase Two-Phase* Four-Wire Three-Phase Formulas
DC External Auxiliary Power Frequency– 25 Hz Operation (-25)
If dc external auxiliary power is required, the following levels A measure of the number of complete cycles of a waveform I x E x PF I x E x 2 x PF I x E x 1.73 x PF IxE
are available: per unit of time, specified in Hertz (Hz), or cycles per second. Kilowatts
1000 1000 1000 1000
This option refers to signal input frequency only.
24 Vdc external auxiliary power (-JB)
48 Vdc external auxiliary power (-JC) Isolated VT Inputs (-AY) IxE IxEx2 I x E x 1.73
125 Vdc external auxiliary power (-JD) The -AY option specifies that the voltage inputs are isolated Kilovolt-Amps
from each other on 3-element watt or var transducers. 1000 1000 1000
Extended Range (-ER)
Special calibration levels that fall outside the normal Special Calibration (Frequency Transducers) I x E x % Eff. x PF I x E x 2 x % Eff. x PF I x E x 1.73 x % Eff. x PF I x E x % Eff.
calibration range. Frequency transducers can be calibrated within a specific Horsepower (output)
range. Please consult the factory for special calibration 746 746 746 746
Fast Response (-FR) requirements.
With fast response, the analog output responds faster to the
Amps when Kilowatts kW x 1000 kW x 1000 kW x 1000 kW x 1000
change in input. The normal response time is 400 ms to 99%, Test Jack (-TJ)
are known
but with the fast response option this changes to 50 ms or The test jack is connected in series with the analog output to E x PF 2 x E x PF 1.73 x E x PF E
100 ms to 99%. The change in response time results in an allow testing without disconnecting the unit. The transducer is
inversely proportional increase in output ripple. Consult connected to the standard via the test jack to verify the circuit
Amps when Kilovolt-Amps kVA x 1000 kVA x 1000 kVA x 1000
factory for other response time requirements. is working and to test the accuracy of the unit. The total
are known
resistance on the test jack plus the analog output cannot E 2xE 1.73 x E
Sepia Drawings (-DG) exceed the maximum load resistance of the transducer per its
Drawings that can be used to reproduce blueprints. specification. The test jack is shorted when it is not in use.
Amps when Horsepower hp x 746 hp x 746 hp x 746 hp x 746
is known
E x % Eff. x PF 2 x E x % Eff. x PF 1.73 x E x % Eff. x PF E x % Eff.
STANDARD ABBREVIATIONS
I = Line Current (Amps) % Eff. = Percent Efficiency kW = Kilowatts hp = Horsepower
E = Volts Line to Line PF = Power Factor kVA = Kilovolt-Amps x = Multiply
*For three-wire, two-phase circuits the current in the common conductor is 1.41 times that in either of the other two conductors.
Symbol or Symbol or Symbol or
Abbreviation Unit or Term Abbreviation Unit or Term Abbreviation Unit or Term
Reference
F.S. full scale ohm VT voltage transformer
h hour PF power factor VTR voltage transformer ratio
hp horsepower PKe primary constant of W watt
HV high voltage energy (watthours**/pulse) Wh watthour
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805 AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
132 133
SCI Transducer Cat 90-134(MTD) 132-133 1/9/02, 5:35 PM
Terms & Conditions
Call us: 8 AM to 5 PM EST, Monday through Friday, 1-800-274-5368 (U.S. and Canada)
Fax us: 24 hours a day, seven days a week, 585-454-7805
◆ Quotes
Contact your local representative for pricing and delivery estimates.
◆ Payment Terms
Standard terms of payment are net thirty (30) days from date of invoice.
◆ Warranty
Seller warrants its Equipment to meet applicable specifications, if any, and to be free from defects in material
and workmanship for a period of one (1) year from date of shipment to the original Purchaser, provided that such
warranty shall be for a period of (a) two (2) years from the date of shipment for the Exceltronic® II XLG product and
(b) three (3) years from the date of shipment for the Exceltronic® XL and Digilogic™ DL products. Upon receipt of
prompt notice from Purchaser, referencing the order number and detailing the claimed nonconformity or defect,
Seller shall, at its option, repair or replace the Equipment. Equipment returned to Seller will only be accepted with
a Returned Materials Authorization number (“RMA”) issued by Seller or one of its authorized representatives.
Inbound shipping charges to Seller’s factory in Rochester, New York, or other designated facility, are the
responsibility of Purchaser. Normal shipping charges for the return to Purchaser of repaired or replacement
Equipment shall be the responsibility of the Seller (North American points only).
Repair or replacement of the Equipment in the manner described above is the exclusive warranty remedy and shall
constitute complete fulfillment of all Seller’s liabilities for breach of this Warranty. Seller assumes no responsibility
hereunder for any Equipment damage or failure caused by (a) improper installation, operation, and maintenance of
the Equipment, or (b) normal wear and tear on disposable and/or consumable parts. This Warranty shall be void in
the event of unauthorized modification or servicing of the Equipment.
THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ANY OTHER WARRANTIES OF QUALITY, WHETHER
EXPRESSED OR IMPLIED (INCLUDING ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR
PURPOSE). In no event shall Seller be liable hereunder for any special, indirect, incidental, or consequential
damages including but not limited to loss of revenue or production.
Exceltronic® is a Registered Trademark of Scientific Columbus Co.
Copyright © 1995 Scientific Columbus Co. All rights reserved.
◆ Delivery
Standard delivery is via UPS, F.O.B. shipping point (Rochester, New York). Express delivery can be made via
either UPS or Federal Express. Shipments over 150 pounds are made via Yellow Freight or Overnight Transportation.
All delivery charges are automatically added to your invoice.
◆ Returns
If it is necessary to return Scientific Columbus products for repair or calibration, contact either your local
representative or the factory at 1-800-274-5368 (U.S. and Canada).
AMETEK® Power Instruments 255 North Union Street Rochester, New York 14605 Phone: 1-800-274-5368 Fax: 585-454-7805
134
SCI Transducer Cat 90-134(MTD) 134 1/9/02, 5:35 PM