You are on page 1of 72

Floatless Level Controller 61F

Automatic Water Supply and Drainage


Control
Ideal for level control of any conductive liquid
Both general-purpose and panel-use models
available
Incorporates an arrester for surge and induced
lightning protection
Wide range of models: Long-distance, high- and
low-sensitivity, two-wire, etc.
LED indicator for quick operation check
Conforms to EMC/IEC standards
(61F-GP-N/-N8/-GPN-V50) RC
UL/CSA approved (61F-GP-N8/-GPN-V50)

Operating Principle
Unlike ordinary level switches that use a float for level detection, the A pump is usually connected to a contactor, which in turn is con-
61F Floatless Level Controller uses electrodes to electrically detect nected to the Controller contact outputs. The Level Controller would
the liquid level. The following figures illustrate this simple operating automatically operate the pump, to control the liquid level in the
principle. tank.
However, in practice, with only two electrodes, ripples on the sur-
face of the liquid cause the Controller to jump and start, shortening
8 VAC X
Relay pump (and other equipment) life. This problem can be solved by ad-
X ding another electrode to form a self-holding circuit. The additional
Relay contacts electrode, E2, is connected in parallel with E1, as shown below.
b a

c2
E1 X a2
b2
Magnetic contactor (To) E3
X
No current flows between E1 and E3. Relay contacts
b1 a1
c1
When electrode E1 is not in contact with the conductive liquid, the PUMP OFF
electrical circuit is open, and no current flows between electrodes E1
PUMP ON
E1 and E3. Magnetic contactor (To) E3 E2

Consequently, relay X does not operate. Relay X’s NC contacts


(normally closed, b in the figure) remain closed. However, when liq- As shown in the above figure, when the holding circuit relay is ener-
uid is supplied to the tank, so that the liquid contacts or immerses gized, contact a2, its NO contact, is closed. The electrical circuit
E1, the circuit closes. Relay X operates, and electrical devices con- made through the liquid and the electrodes is then retained by E2
nected to the NO (normally open, a in the figure) contacts of the and E3, even when the liquid level falls below E1, as long as contact
relay begin operation. a2 is closed.
When the liquid level falls below E2, the circuit made through the
electrode circuit opens, which de-energizes relay X, thus closing
8 VAC X
Relay the NC contact of X.
X Operating as simply as it does, possible applications of the Float-
Relay contacts less Level Controller are virtually endless. Not only liquid level con-
b a
trol is possible, but such applications as leakage detection, object
size discrimination, and many other problems may be solved by one
E1 of the reliable 61F Floatless Level Controllers.
Magnetic contactor (To) E3
Current flows between E1 and E3.
61F 61F

Model Selection
Basic Configuration of 61F Conductive Level Controller
To use a 61F Conductive Level Controller, the 61F itself, Electrode Holders, and Electrodes are required.

Select from the capability, function, and size to suit the application.
61F
Refer to the following Controller selection guidelines.

Basic configuration
Select from the characteristics, application examples, and shape.
Electrode Holders
Refer to page 66 for cautions about the Electrode Holders.

Select according to operating conditions and shape.


Electrodes
Refer to pages 65 to 67 for cautions about the Electrodes.

Typical Application Example


LED Indicator
Convenient for maintenance and checking operations

61F Controller Relay Unit


Cermet wire is used in the transformer to prevent Incorporates a transistor-based control circuit and output relay. One to
accidents by short-circuiting. five Relay Units are used, depending on the application.

Electrode Holder/Electrodes
Many materials, sensitivities and mounting variations are available.

Water
supply
source

M: Electrical Motor
P: Fluid Pump

M P

Ordering Information
61F Controller Selection Guide by Installation Method
Plug-in Model
Standard Model Compact Plug-in Model

• When there is sufficient mounting space. • When using socket mounting.


• When monitoring operation through LEDs.
61F 61F

61F Controller Selection Guide by Application


Item G G1
A t
Automatic
ti water
t supply
l and
d drainage
d i control
t l Automatic water Automatic water
supply (idling supply (abnormal
prevention) shortage alarm)
Function Automatic pump Water supply Water drainage Water supply Water tank Water supply Water tank
operation P
Pump
P P

(constant water Pump ON Pump Pump


OFF OFF OFF
level) Pump
Pump OFF Pump Pump
ON P
ON ON

Water level --- Water supply Water tank


source
indication
abnormal alarm

Pump OFF
(idling pre- Short-
vention) Short- B L age
age

B L

Appearance Compact Plug-in Model

Standard Model Standard Model Plug-in Model

61F-GP-N
(Pages 18 to 20, 53)

61F-G 61F-G1 61F-G1P


(Pages 6 to 10, 52) (Pages 6 to 8, 11 to 12, 52) (Pages 25 to 28, 54)

61F-GP-N8
(Pages 21 to 24, 53)

Item G2 G3
Automatic water supply and drainage control Automatic water supply and
(abnormal water increase alarm) drainage control (abnormal
filling/shortage alarm)
Function Automatic pump Water supply
Water drainage
Water supply Water drainage
operation P P

(constant water Pump Pump Pump Pump


level) ON OFF ON
OFF
Pump Pump Pump Pump
ON OFF ON OFF
P P

Water level B L B LH
indication Upper
Full
abnormal alarm limit

Short-
B LL age

Appearance Standard Model Plug-in Model Standard Model

61F-G2P
61F-G2 (Pages 25 to 26, 29, 30, 54) 61F-G3
(Pages 6 to 8, 13, 52) (Pages 6 to 8, 14, 53)
61F 61F

Item G4 I Alternative
Water source level indication, Liquid level indication and alarm operation of two
prevention of pump idling due pumps
to water shortage, automatic
water supply control, and
indication of water level in tank
Function Automatic pump Elevated water tank
Water
--- ---
operation supply
Water supply souse
(constant water P

level) Pump
OFF
Pump
ON Pump
ON

Pump
OFF

Water level Elevated water tank


B LH
---
Upper
indication B LH limit

abnormal alarm Full


Water supply souse
Middle

B LH LM

Upper
limit
Lower
B LL limit
Short-
B LL age

Lower
B LL
limit

Appearance Standard Model

Standard Model Plug-in Model

Compact plug-in Model

61F-APN2
61F-IP (Pages 34 to 43, 54)
61F-I (Pages 25 to 26, 31, 54)
(Pages 6, 17, 52)
61F-G4
(Pages 6 to 8, 15, 53)

Related Products
Relay Unit for standard Surge Suppressor Unit (for 61F-WLA Water 61F-GPN-V50 Water
models (Page 8) protecting against induced Leakage Alarm Leakage Detector
voltage) (Pages 44, 54) (Pages 68 to 71) (Pages 68 to 71)
61F 61F

Accessories
Electrode Holders
Applications General Applications Liquid with low Applications Applications Applications Applications
applications where only a specific where high where high where high where
such as water small space is resistance mounting temperature/ corrosion distance to the
supply lines available strength is high pressure resistance is water surface
required conditions are required is long
severe
Models PS-3S/-4S/-5S PS-31 BF-1 BF-3/-4/-5 BS-1 BS-1T PH-1/-2
(Two-wire
models are
also
available.)
Appearance PH-2
SUS

Hastelloy PH-1
titanium

Electrodes
Sets of Electrodes, connecting nuts, lock nuts, and spring washers are available. When ordering individual parts, refer to page 45.

Applications Purified city water, Purified city water, Sodium hydroxide, Sea water, ammonia Acetic acid, dilute
industrial water, industrial water, acetic acid, dilute water, nitric acid sulfuric acid,
sewage sewage, dilute sulfuric acid, dilute sea water
alkaline solution hydrochloric acid
Models F03-60-SUS201 F03-60-SUS316 F03-60 HAS B F03-60 HAS C F03-60 Titanium

Others
Item Model
Protective Cover F03-11
(for PS or BF electrode holders)

Spring Clamp F03-12


(for PS electrode holders)

Electrode Separators (for preventing long electrodes from F03-14 1P (for 1 pole)
contacting with each other) F03-14 3P (for 3 poles)
F03-14 5P (for 5 poles)
61F-Gj 61F-Gj

Specifications
Standard Models
Specifications
Items General-purpose High-tempera- Long-distance High-sensitiv- Low-sensitiv- Two-wire
Controller ture Controller Controllers ity Controllers ity Controller Controller
61F-j (TDL) 61F-jT 61F-jL 2KM 61F-jH 61F-jD 61F-jR
(see note (see note 1) (for 2 km) (see note 1) (see note 1) (see note 1)
1 and 2) 61F-jL 4KM
(for 4 km)
(see note 1)
Controlling materials For control of or- For control of For control of For control of For control of For control of
and operating dinary purified ordinary puri- ordinary puri- liquids with high liquids with low ordinary puri-
conditions water or sewage fied water or fied water in specific resis- specific resis- fied water or
water sewage water cases where tance such as tance such as sewage water
in cases where the distance distilled water salt water, sew- used in com-
the ambient between sew- age water, acid bination with
temperature is age pumps and chemicals, al- Two-wire Elec-
high. water tanks or kali chemicals trode Holder
between receiv- (incorporating a
er tanks and resistor of
supply tanks is 6.8 kΩ)
long or where
remote control
is required.
Supply voltage 100, 110, 120, 200, 220, 230 or 240 VAC; 50/60 Hz
Operating voltage 85% to 110% of rated voltage
range
Interelectrode 8 VAC 24 VAC 8 VAC
voltage
Interelectrode Approx. 1 mA AC max.
current
Power consumption Approx. 3.2 VA max. (One unit)
Interelectrode 0 to approx. 4 kΩ 0 to approx. 0 to approx. Approx. 15 kΩ 0 to approx. 0 to approx. 1.1
operate resistance 5 kΩ 1.8 kΩ (for to 70 kΩ 1.8 kΩ kΩ
2 km) (see note 5)
0 to approx.
0.7 kΩ (for
4 km)
Interelectrode Approx. 15 k to Approx. 15 k to 4 k to ∞ Ω (for Approx. 300 k Approx. 5 k to Approx. 15 k to
release resistance ∞Ω ∞Ω 2 km) to ∞ Ω ∞Ω ∞Ω
2.5 k to ∞ Ω
(for 4 km)
Cable length 1 km max. 600 m max. 2 km max. 50 m max. 1 km max. 800 m max.
(see note 3) 4 km max.
Control output 2 A, 220 VAC (Inductive load: cosφ = 0.4)
5 A, 220 VAC (Resistive load)
Ambient temperature Operating: --10°C to 55°C (--10°C to 70°C for 61F-jT)
Ambient humidity Operating: 45% to 85% RH
Insulation resistance 100 MΩ min. (at 500 VDC)
(see note 4)
Dielectric strength 2000 VAC, 50/60 Hz for 1 min.
(see note 4)
Life expectancy Electrical: 500,000 operations min.
Mechanical:5,000,000 operations min.
Note: 1. The j in the model name represents G, G1, G2, G3, G4, and I.
2. The suffix “TDL” attached to the model name represents models designed for tropical regions (storage humidity of 45 to 90% RH).
3. The length when using completely-insulated, 600-V, 3-conductor (0.75 mm2) cabtire cables. Usable cable lengths will become
shorter as the cable diameter or number of conductors becomes larger.
4. The insulation resistance and dielectric strength indicate values between power terminals and Electrode terminals, between power
terminals and contact terminals, and between Electrode terminals and contact terminals.
5. Possible to use with 15 kΩ or less, however, this may cause reset failure.
61F-Gj 61F-Gj

Internal Circuit Diagrams


The schematic diagrams shown below typify the internal connections of the various 61F models. The designations Ta, Tb, and Tc (sometimes
referred to collectively as “U”) may occur more than once in a product, however, the “a” terminal is always an NO contact, a “b” terminal is an NC
contact, and the “c” terminal is the common terminal.

61F-G 61F-GT 61F-GL


0V 0V 0V
61F-11 61F-11T 100, 110 61F-11L U
100, 110 24 V U 100, 110 U 24 V Relay Unit
Relay Unit 24 V Relay Unit or 120 V
or 120 V or 120 V
200, 220 200, 220 200, 220
8V 8V or 240 V 8V
or 240 V or 240 V

U U U

U U U

Ta Tc Tb E2 E1 Ta Tc Tb E2 E1 Ta Tc Tb E2 E1

S0 S1 S2 E3 S0 S1 S2 E3 S0 S1 S2 E3

61F-GH 61F-GD 61F-GR


(See note.) 0V
0V
100, 110 61F-11R U
0V 61F-11D U 24 V
61F-11H 100, 110 24 V or 120 V Relay Unit
100, 110 U or 120 V Relay Unit
24 V Relay Unit 200, 220
or 120 V 200, 220 8V
200, 220 8V or 240 V
24 V or 240 V
or 240 V
U

U
U
U
U
U
Ta Tc Tb E1
Ta Tc Tb E2 E1
Ta Tc Tb E2 E1

S0 S1 S2 E3
S0 S1 S2 E3
S0 S1 S2 E3
61F-Gj 61F-Gj

Note: The 61F-11H relay de-energizes when there is water present across the Electrodes, whereas the 61F relay energizes when there is
water present across the Electrodes.
Also, the terminal connections of those Controllers provided with LED indicators differ from those which have no indicators.
61F-11 Relay Units
Item 61F-11 61F-11T 61F-11L 61F-11H 61F-11D 61F-11R
Interchangeable with --- Provided Provided Not provided Provided Not provided
general-purpose
model (61F-11)
Color of band on --- Red Yellow Blue Black Green
name plate

61F-11 61F-11T 61F-11L


E S S S E S S S E S S S

8 7 6 5 8 7 6 5 8 7 6 5 4
4 4
8V 24 V 24 V 8V 24 V 24 V 8V 24 V 24 V

Tr2 Tr2 Tr1 Tr2


Tr1 Tr1 X
X X

x x x x
x x

9 10 11 1 2 3 9 10 11 1 2 3 9 10 11 1 2 3

Tb2 Ta2 Tc2 Tc1 Ta1 Tb1 Tb2 Ta2 Tc2 Tc1 Ta1 Tb1 Tb2 Ta2 Tc2 Tc1 Ta1 Tb1

61F-11H Tr2 61F-11D 61F-11R


(see note)
E S S S E S S S E S S S

8 7 6 5 8 7 6 5 8 7 6 5 4
4 4
24 V 24 V 24 V 8V 24 V 24 V 8V 24 V 24 V

Tr2 Tr2 Tr1 Tr2


Tr1 Tr1 X
X X

x x x x
x x

9 10 11 1 2 3 9 10 11 1 2 3 9 10 11 1 2 3

Ta2 Tb2 Tc2 Tc1 Tb1 Ta1 Tb2 Ta2 Tc2 Tc1 Ta1 Tb1 Tb2 Ta2 Tc2 Tc1 Ta1 Tb1
61F-Gj 61F-Gj

Connections
61F-G
Automatic Water Supply and Drainage Control

1. Water Supply 2. Drainage

Water supply Water drainage


P
(U indicator ON) (U indicator ON)
Pump OFF E1 E1
Pump ON

Pump ON (U indicator OFF) (U indicator OFF)


E2 E2 P

E3 E3 Pump OFF

• Connect electromagnetic switch coil terminal A to Tb. • Connect the electromagnetic switch coil terminal A to Ta.
• The pump stops (indicator ON) when the water level reaches E1 • The pump starts (indicator ON) when the water level reaches E1
and starts (indicator OFF) when the water level drops below E2. and stops (indicator OFF) when the water level drops below E2.

200-VAC power supply 61F-G


R S T Transformer
0V
61F-11 U
100 V 24 V
Relay Unit
200 V U
MCCB 8V

Ta Tc Tb E2 E1

S0 S1 S2 E3

(See note 1)

Rated voltage:
*
S0--S1: 100 or 110 or 120 VAC
A S0--S2: 200 or 220 or 240 VAC

Electromagnetic switch
Water tank
PS-3S

Stop
THR E1
Start
E2
Water supply source E3

P
M

Note: 1. The diagram shows the connections for the water supply. When draining, change the connection from terminal Tb to terminal Ta.
2. Be sure to ground terminal E3.
61F-Gj 61F-Gj

61F-GR
Two-wire Automatic Water Supply and Drainage Control
1. Water Supply 2. Drainage
Water supply Water drainage
P
(U indicator ON) (U indicator ON)
Pump OFF E1
Pump ON

Pump ON (U indicator OFF) (U indicator OFF)


E2 P
E3 Pump OFF

• Connect electromagnetic switch coil terminal A to Tb. • Connect the electromagnetic switch coil terminal A to Ta.
• The pump stops (indicator ON) when the water level reaches E1 • The pump starts (indicator ON) when the water level reaches E1
and starts (indicator OFF) when the water level drops below E2. and stops (indicator OFF) when the water level drops below E2.
Note: 1. The two-wire models require two cables for connecting
the 61F-GR and electrode holders and three electrodes.
2. The electrode holders must be special ones for two-wire
models. (The resistance R is built into the electrode
holder for the two-wire models.)
61F-GR
200-VAC power supply
R S T Transformer
0V
61F-11R U
100 V 24 V
Relay Unit
200 V
8V

MCCB

U
U

Ta TC Tb E1

S0 S1 S2 E3

(See note 1)

Rated voltage:
S0--S1: 100 or 110 or 120 VAC
A S0--S2: 200 or 220 or 240 VAC

Electromagnetic switch
Water tank
R PS-3SR

Stop
E1
THR Start
E2
Water supply source E3

P
M

Note: 1. The diagram shows the connections for the water supply. When draining, change the connection from terminal Tb to terminal Ta.
2. Be sure to ground terminal E3.
61F-Gj 61F-Gj

61F-G1

Application 1:Automatic Water Supply Control with Pump Idling Prevention

Water tank
• The pump stops (U2 indicator ON) when the water level reaches
E1 and the pump starts (U2 indicator OFF) when the water level
in the tank drops below E2.
(U1 indicator ON) • When the level of the water supply source drops below E2’, the
E1’
(U1 indicator OFF) pump stops (U1 indicator OFF). Pump idling is prevented and the
E2’
Short- alarm sounds.
age E3’

B L
• Insert a pushbutton switch (NO contact) between E1’ and E3 as
shown by the dotted line. When starting the pump or after
Water supply recovering from a power failure, if the water supply source level
Water
source has not yet reached E1’, press the pushbutton switch to start the
supply pump by momentarily short-circuiting E1’ and E3. When the
pump stops during normal operation subsequent to an alarm
P
(U2 indicator ON) issued for a low water level (e.g., the water level does not reach
Pump OFF E1
E2’), do not press the pushbutton switch.

Pump ON (U2 indicator OFF)


E2
E3

61F-G1
200-VAC power supply
0V Transformer
R S T U1
61F-11
24 V
Relay Unit
100 V
61F-11 U2
24 V
Relay Unit
200 V
MCCB 8V
U1

U2
U1
U2

S0 Tb1 Ta1 Tc2 Tb2

E1’
S1 S2 E3 E2 E1 E2’ (E4)

B Alarm Push-
button
switch
Rated voltage:
S0--S1: 100 or 110 or 120 VAC
S0--S2: 200 or 220 or 240 VAC

Electromagnetic
switch
*
PS-3S

THR E1
Water tank
E2
Water supply E3
source

E1’
P E2’
E3
M

Note: Be sure to ground terminal E3.


61F-Gj 61F-Gj

61F-G1

Application 2: Automatic Water Supply Control with Abnormal Water Shortage Alarm
Water tank • The pump stops (U2 indicator ON) when the water level reaches
Water supply
P
E1 and starts (U2 indicator OFF) when the water level drops
Pump OFF (U2 indicator ON) below E2.
E1
• If the water level drops below E4 for any reason, the pump stops
Pump ON (U2 indicator OFF) (U1 indicator OFF) and the alarm sounds.
E2

E4
(U1 indicator OFF) • Insert a pushbutton switch (NO contact) between E3 and E4.
B L
E3
When starting the pump or after recovering from a power failure,
Shortage if the water level has not yet reached E4, press the pushbutton
switch to start the pump by short-circuiting E3 and E4. If the
pump stops upon releasing the pushbutton switch, keep
pressing the pushbutton switch.
61F-G1
200-VAC power supply
0V Transformer
R S T U1
61F-11
24 V
Relay Unit
100 V
61F-11 U2
24 V
Relay Unit
200 V
8V
U1
MCCB
U2
U1
U2

S0 Tb1 Ta1 Tc2 Tb2

E1’
S1 S2 E3 E2 E1 E2’ (E4)

Alarm

* Pushbutton
Electromagnetic
switch
switch
Rated voltage:
S0--S1: 100 or 110 or 120 VAC
S0--S2: 200 or 220 or 240 VAC PS-4S

E1
Water tank E2
THR
Water supply source E4
E3

P
M

Note: Be sure to ground terminal E3.


61F-Gj 61F-Gj

61F-G2

Automatic Drainage Control and Water Supply with Abnormal Water Increase Alarm
1. Drainage 2. Water Supply

Water drainage Water supply


B L L B
P
Upper
Upper (U1 indicator ON) limit
limit
E4 (U1 indicator ON)
(U2 indicator ON) E4
E1 Pump OFF E1 (U2 indicator ON)
Pump ON
(U2 indicator OFF)
E2 Pump OFF Pump ON (U2 indicator OFF)
P E2
E3 E3

• Connect the electromagnetic switch terminal (T phase) to Ta1. • Connect the electromagnetic switch terminal (T phase) to Tb1.
• The pump starts (U2 indicator ON) when the water level reaches • The pump starts (U2 indicator OFF) when the water level
E1 and stops (U2 indicator OFF) when the water level drops reaches E2 and stops (U2 indicator ON) when the water level
below E2. rises to E1.
• If the water level reaches E4 for any reason, the alarm sounds • If the water level reaches E4 for any reason, the alarm sounds
(U1 indicator ON). (U1 indicator ON).

61F-G2 for drainage control


0V
Transformer
200-VAC power supply
R S T 61F-11 U1
24 V
Relay Unit
100 V
61F-11
24 V
Relay Unit U2
200 V

8V
U2
MCCB

U2 U1

S0
Ta1 Tc1 Tb1 Ta2 Tc2

S1 S2 E3 E2 E1 E4

(See note 1) B

Rated voltage:
S0--S1: 100 or 110 or 120 VAC
S0--S2: 200 or 220 or 240 VAC

*
Electromagnetic
switch
Reservoir

THR

Water supply PS-4S


source

E1 E4
E2
P E3
M

Note: 1. The diagram shows the connections for the water supply. When draining, change the connection from terminal Tb1 to terminal Ta1.
2. Be sure to ground terminal E3.
61F-Gj 61F-Gj

61F-G3

Automatic Water Supply and Drainage Control with Abnormal Water Shortage Alarm and Water Tank Repletion

1. Water Supply 2. Drainage


Water supply B LH
LH B
P
Upper
Upper
Water drainage
limit
limit
(U1 indicator ON) (U1 indicator ON)
E1 E1
Pump OFF (U2 indicator ON) (U2 indicator ON)
E2 E2
Pump ON
Pump ON (U2 indicator OFF)
E3 (U2 indicator OFF)
(U2 indicator OFF) (U3 indicator OFF) Pump OFF
E4 E4 P
LL B
B LL
E5 Lower limit E5
Lower limit

• Connect electromagnetic switch coil terminal A with Tb. • Connect the electromagnetic switch coil terminals A with Ta.
• The pump stops (U2 indicator ON) when the water level reaches • The pump starts (U2 indicator ON) when the water level reaches
E2 and starts (U2 indicator OFF) when the water level drops E2 and stops (U2 indicator OFF) when the water level drops
below E3. below E3.
• If the water level rises to E1 for any reason, the upper-limit • If the water level rises to E1 for any reason, the upper-limit
indicator turns ON and the alarm sounds (U1 indicator ON). indicator turns ON and the alarm sounds (U1 indicator ON).
• If the water level drops below E4 for any reason, the lower-limit • If the water level drops below E4 for any reason, the lower-limit
indicator turns ON and the alarm sounds (U3 indicator OFF). indicator turns ON and the alarm sounds (U3 indicator OFF).
61F-G3 for water supply
200-VAC power supply 0V Transformer
R S T 61F-11
24 V
Relay Unit U1
100 V
24 V
61F-11
Relay Unit U2

24 V
61F-11
Relay Unit U3
200 V

MCCB 8V

U2

U1 U3 U3
U1
U2
Ta Tc Tb B1 B2 Lc E1 E3 E5

S0 S1 S2 LH LL E2 E4

Alarm *
Upper Lower
B limit PL PL limit
(See note 1)
Power Power
source source

Rated voltage:
S0--S1: 100 or 110 or 120 VAC
Electromagnetic S0--S2: 200 or 220 or 240 VAC
switch
PS-5S
Water repletion
THR
E1
Water tank E2
E3
Water supply source E4
E5 Water shortage

P
M

Note: 1. The diagram shows the connections for the water supply. When draining, change the connection from terminal Tb to terminal Ta.
2. Be sure to ground terminal E5.
61F-Gj 61F-Gj

61F-G4

Water Source Level Indication, Prevention of Pump Idling Due to Water Shortage, Automatic Water Supply Control, and Indica-
tion of Water Level in Tank
• Insert four Electrodes in the water supply source and five • The pump stops (U5 indicator ON) when the water level reaches
Electrodes in the elevated water tank. E5 and starts (U5 indicator OFF) when the water level drops
below E6.
• The lower-limit indicator for the water supply source remains ON
while the water source level is below E3 (U2 indicator OFF). • If the water level reaches E4 for any reason, the tank repletion
indicator for the elevated tank turns ON (U4 indicator ON).
• When the water level rises to E2, the lower-limit indicator turns
OFF (U2 indicator ON) and the pump is ready for operation. • Insert a pushbutton switch (NO contact) between E2 and E8 as
shown by the dotted line. When starting the pump and after
• When the water level reaches E1, the upper-limit indicator turns recovering from a power failure, if the water source level has not
ON (U3 indicator ON). yet reached E2 (U2 indicator OFF), press the pushbutton switch
• The water-shortage indicator for the elevated tank remains ON to start the pump by momentarily short-circuiting E2 and E8.
while the water level in the elevated tank is below E7. The When the pump stops during normal operation subsequent to an
indicator turns OFF (U1 indicator ON) when the water level rises alarm issued for low water level (i.e., the water level has not
to E7. reached E3), do not press the pushbutton switch.

61F-G4
0V 24 V 61F-11 Relay Unit U5

24 V 61F-11 Relay Unit U


100 V 1

200 V

0V
MK3P U2
24 V 61F-11 Relay Unit U2
Relay

X
24 V 61F-11 Relay Unit U3
100 V

24 V 61F-11 Relay Unit U4

8V

200 V
X U4 U3 X U1 U5 X U4 U3 U2 U5
200-VAC power supply U1

RST

MCCB LL1 LL2 LH1 LH2 BL1 BL2 BH1 BH2 E4 E3 E2 E1

S0 S1 S2 Tc TC2 B TA E8 E7 E6 E5
Water supply source

Water supply source

Water supply source

Water supply source


Elevated tank water

water shortage

LL1 LL2 LH1 LH2 BL1 BL2 BH1 BH2


Elevated tank

Elevated tank

Elevated tank
lower limit

lower limit
upper limit

upper limit
shortage

repletion

repletion

Pushbutton
switch

Electromagnetic
switch *
Water tank PS-5S
Rated voltage:
S0--S1: 100 or 110 or 120 VAC
S0--S2: 200 or 220 or 240 VAC E4 Water repletion
THR
OFF
Water supply PS-4S E5
ON
E6
source E7
E8
Upper limit Water shortage
E1
ON
E2
OFF
E8 E3 Lower limit
P
M

Note: 1. Be sure to ground terminal E8.


61F-Gj 61F-Gj

Connection with Three-phase Four-line Circuit


When supplying power from N-phase to the Controller in three-phase four-line circuit, refer to the following diagrams.
Line voltage (R-S, S-T, or R-T): 380 or 415 VAC
Phase voltage (N-R, N-S, or N-T): 220 or 240 VAC
61F-Gj, 220 or 240 VAC
Water Supply
Power source
380 or 415 VAC
R S T N * Transformer
61F-11 U
24 V
Relay Unit

8V

Ta Tc Tb E2 E1

S0 S1 S2 S3

*
Rated voltage:
A S0--S2: 220 or 240 VAC

Electromagnetic switch
Water tank

Stop
E1
Start
E2
E3
Water supply source

P
M

Note: Be sure to ground terminal E3.


61F-I 61F-I

61F-I

Liquid Level Indication and Alarm

B LH Upper
• When the water level drops below E2, the lower-limit indicator
(U1 indicator ON)
limit
turns ON and the alarm sounds (U2 indicator OFF).
E1
(U1 indicator OFF)
• When the water level reaches E2, the alarm turns OFF and the
intermediate indicator turns ON (U2 indicator ON).
LM
Middle

Lower
(U2 indicator ON) • When the water level rises to E1, the upper-limit indicator turns
B LL limit
E2
(U2 indicator OFF) ON and the alarm sounds (U1 indicator ON).
E3

61F-I
Transformer
200-VAC power supply 0V
61F-11 U1
R S T 24 V
100 V
Relay Unit

61F-11
24 V
Relay Unit U2
200 V
MCCB 8V

U1
U2 U1 U2
L1
Tc B L3 L2

S0 S1 S2 E3 E2 E1

Intermediate

Alarm B PL PL PL *
Lower
Upper limit limit

Rated voltage:
S0--S1: 100 or 110 or 120 VAC
S0--S2: 200 or 220 or 240 VAC
PS-3S

Upper alarm
E1 Intermediate
Water tank
E2 Lower alarm
Water supply source E3

P
M

Note: Be sure to ground terminal E3.


61F-GP-Nj 61F-GP-Nj

Compact Plug-in Models (11-pin Type)


Specifications
Item General-pur- High-tempera- Long-distance High-sensitiv- Low-sensitiv- Two-wire
pose ture Controller Controllers ity Controller ity Controller Controller
Controller
61F-GP-NT 61F-GP-NL 61F-GP-NH 61F-GP-ND 61F-GP-NR
61F-GP-N 2KM (for 2 km) (see note 1)
61F-GP-NL
4KM (for 4 km)
Controlling materials For control of For control of For control of For control of For control of For control of
and operating ordinary purified ordinary purified ordinary purified liquids with high liquids with low ordinary purified
conditions water or sew- water or sewage water in cases specific resis- specific resis- water or sew-
age water where operating where the dis- tance such as tance such as age water used
ambient temper- tance between distilled water salt water, sew- in combination
ature is high. sewage pumps age water, acid with Two-wire
and water tanks chemicals, alka- Electrode
or between re- li chemicals Holder (incorpo-
ceiver tanks and rating a resistor
supply tanks is of 6.8 kΩ)
long or where
remote control
is required.
Supply voltage 24, 100, 110, 120, 200, 220, 230 or 240 VAC; 50/60 Hz
Operating voltage 85% to 110% of rated voltage
range
Interelectrode 8 VAC
voltage
Interelectrode Approx. 1 mA AC max. Approx. Approx. 1 mA AC max.
current 0.12 mA AC
max.
Power consumption Approx. 3.2 VA max.
Interelectrode 0 to approx. 0 to approx. 0 to approx. Approx. 10 kΩ 0 to approx. 0 to
operate resistance 4 kΩ 4 kΩ 1.3 kΩ (for to approx. 1.3 kΩ approx. 2 kΩ
2 km) 40 kΩ
0 to approx. (see note 4)
0.5 kΩ (for
4 km)
Interelectrode Approx. 15 k to Approx. 15 k to 4 k to ∞ Ω (for Approx. 100 k Approx. 4 k to Approx. 15 k to
release resistance ∞Ω ∞Ω 2 km) to ∞ Ω ∞Ω ∞Ω
0.5 k to ∞ Ω
(for 4 km)
Response time Operate: 80 ms max.
Release: 160 ms max.
Cable length 1 km max. 600 m max. 2 km max. 50 m max. 1 km max. 800 m max.
(see note 2) 4 km max.
Control output 1 A, 250 VAC (Inductive load: cosφ = 0.4)
3 A, 250 VAC (Resistive load)
Ambient temperature Operating: --10°C to 55°C (--10°C to 70°C for high-temperature controller)
Ambient humidity Operating: 45% to 85% RH
Insulation resistance 100 MΩ min. (at 500 VDC)
(see note 3)
Dielectric strength 2000 VAC, 50/60 Hz for 1 min.
(see note 3)
Life expectancy Electrical: 100,000 operations min.
Mechanical:5,000,000 operations min.
Note: 1. The relay in the 61F-GP-NH de-energizes when there is water present across the Electrodes, whereas the relay in the 61F-GP-
N8HY energizes when there is water present across the Electrodes.
2. The length when using completely-insulated, 600-V, 3-conductor (0.75 mm2) cabtire cables. Usable cable lengths will become
shorter as the cable diameter or number of conductors becomes larger.
3. The insulation resistance and dielectric strength indicate values between power terminals and Electrode terminals, between power
terminals and contact terminals, and between Electrode terminals and contact terminals.
4. Possible to use with 10 kΩ or less, however, this may cause reset failure.
61F-GP-Nj 61F-GP-Nj

Internal Circuit Diagrams


61F-GP-N/-NT/-NL/-ND 61F-GP-NH 61F-GP-NR
Power supply Power supply Power supply

24 V Control circuit 24 V Control circuit 24 V Control circuit

8V 8V 8V

U
U U U U U

3 9 4 5 11 10 1 7 6 8 3 9 4 5 11 10 1 7 6 8 3 9 4 5 11 10 1
S0 S1 E3 E1 Ta1 Tc1 Tb1 Ta2 Tc2 Tb2 S0 S1 E3 E1 Ta1 Tc1 Tb1 Ta2 Tc2 Tb2 S0 S1 E3 E1 Ta1 Tc1 Tb1

Note: When applying a self-holding circuit, short between terminals 5 and 6 and use terminal 7 as E2.
Connections
61F-GP-N

Automatic Water Supply and Drainage Control


1. Water Supply 2. Drainage
Water supply Water drainage
P
Indicator ON Indicator ON
Pump OFF E1 E1
Pump ON

Pump ON Indicator OFF Indicator OFF


E2 E2 P
E3 E3 Pump OFF

• Connect electromagnetic switch coil terminal A to terminal 1. • Connect the electromagnetic switch coil terminal to terminal 11.
• The pump stops when the water level reaches E1 (indicator ON) • Pump starts when the water level reaches E1 (indicator ON) and
and starts when the water level drops below E2 (indicator OFF). stops when the water level drops below E2 (indicator OFF).

61F-GP-N
200-VAC power supply
R S T
8 7 6 5

MCCB
U 4
0V 24 V Control circuit
U

8V

200 V
U
3 9
10 11 1 2
(See note 1
below.)
(See note 2
Contactor below.)

THR PS-3S
Water tank

Stop
Water supply source E1
Start
E2
E3
M P

Note: 1. The diagram shows the connections for the water supply. When draining, change the connection from terminal 1 to terminal 11.
2. Be sure to ground terminal 4.
61F-GP-Nj 61F-GP-Nj

Connection with Three-phase Four-line Circuit


When supplying power from N-phase to the Controller in three-phase four-line circuit, refer to the following diagrams.
Line voltage (R-S, S-T, or R-T): 380 or 415 VAC
Phase voltage (N-R, N-S, or N-T): 220 or 240 VAC
61F-GP-Nj 220 or 240 VAC

61F-GP-N

8 7 6 5
U 4
Power source
380 or 415 VAC 0V 24 V Control circuit
R S T N * U

8V
220 or
Source voltage: 240 V
between 3 and 9 U
3 9
10 11 1 2
A (See note 1)

Electromagnetic switch
*(See note 2 )
Stop
Water E1
tank Start
E2
Water supply source E3

P
M

Note: 1. The diagram shows the connections for the water supply. When draining, change the connection from terminal 1 to terminal 11.
2. Be sure to ground terminal 4.
61F-GP-N8j 61F-GP-N8j

Compact Plug-in Models (8-pin Type)


Specifications
Item General-pur- Long-distance High-sensitivity Low-sensitivity Two-wire Variable
pose Controller Controllers Controllers Controller Controller Sensitivity
Controller
61F-GP-N8 61F-GP-N8L 61F-GP-N8H 61F-GP-N8D 61F-GP-N8R
61F-GP-N8Y 2KM (for 2 km) 61F-GP-N8HY 61F-GP-N8-V50
(see note 1) 61F-GP-N8L (see note 1)
4KM (for 4 km)
Controlling For control of or- For control of or- For control of liq- For control of liq- For control of or- For control of
materials and dinary purified dinary purified uids with high uids with low dinary purified cases where
operating water or sewage water in cases specific resis- specific resis- water or sewage variable sensitiv-
conditions water where the dis- tance such as tance such as water used in ity control is re-
tance between distilled water salt water, sew- combination with quired such as
sewage pumps age water, acid Two-wire Elec- detection of froth
and water tanks chemicals, alkali trode Holder (in- on the surface of
or between re- chemicals corporating a re- a liquid, control
ceiver tanks and sistor of 6.8 kΩ) of soil moisture
supply tanks is content, or
long or where re- detection of de-
mote control is gree of water
required. pollution
Supply voltage 24, 100, 110, 120, 200, 220, 230 or 240 VAC; 50/60 Hz 24, 110, 220 or
240 VAC;
50/60 Hz
Operating 85% to 110% of rated voltage
voltage range
Interelectrode 8 VAC 24 VAC 8 VAC 24 VAC
voltage
Interelectrode Approx. 1 mA AC max. Approx. Approx. 1 mA AC max. Approx. 3 mA
current 0.4 mA AC max. AC max.
Power Approx. 3.5 VA max.
consumption
Interelectrode 0 to approx. 0 to 1.3 kΩ (for Approx. 15 kΩ to 0 to approx. 0 to approx. 0 to 50 kΩ
operate 4 kΩ 2 km) approx. 70 kΩ 1.3 kΩ 2 kΩ (Variable)
resistance 0 to 0.5 kΩ (for (see note 4)
4 km)
Interelectrode Approx. 15 k to 4 k to ∞ Ω Approx. 300 k to Approx. 4 k to Approx. 15 k to Operating
release ∞Ω (for 2 km) ∞Ω ∞Ω ∞Ω resistance
resistance 0.5 k to ∞ Ω +50 kΩ max.
(for 4 km)
Response time Operate: 80 ms max.
Release: 160 ms max.
Cable length 1 km max. 2 km max. 50 m max. 1 km max. 800 m max. 50 m max.
(see note 2) 4 km max.
Control output 1 A, 250 VAC (Inductive load: cosφ = 0.4)
3 A, 250 VAC (Resistive load)
Ambient Operating: --10°C to 55°C
temperature
Ambient Operating: 45% to 85% RH
humidity
Insulation 100 MΩ min. (at 500 VDC)
resistance
(see note 3)
Dielectric 2000 VAC, 50/60 Hz for 1 min.
strength
(see note 3)
Life expectancy Electrical: 100,000 operations min.
Mechanical:5,000,000 operations min.

Note: 1. The relay in the 61F-GP-N8H/-N8Y de-energizes when there is water present across the Electrodes, whereas the relay in the
61F-GP-N8HY energizes when there is water present across the Electrodes.
2. The length when using completely-insulated, 600-V, 3-conductor (0.75 mm2) cabtire cables. Usable cable lengths will become
shorter as the cable diameter or number of conductors becomes larger.
3. The insulation resistance and dielectric strength indicate values between power terminals and Electrode terminals, between power
terminals and contact terminals, and between Electrode terminals and contact terminals.
4. Possible to use with 10 kΩ or less, however, this may cause reset failure.
61F-GP-N8j 61F-GP-N8j

Internal Circuit Diagrams


61F-GP-N8/-N8L/-N8D/-N8HY 61F-GP-N8H 61F-GP-N8R
Power supply Power supply Power supply

24 V Control circuit 24 V Control circuit 24 V Control circuit

8 V (see note) 8V
24 V

Note: 24 V for the 61F-GP-N8HY.

61F-GP-N8Y 61F-GP-N8-V50
Power supply Power supply
24 V Control circuit
24 V Control circuit

8V 24 V

3 4 2
61F-GP-N8j 61F-GP-N8j

Connections
61F-GP-N8

Automatic Water Supply and Drainage Control


1. Water Supply 2. Drainage
Water supply Water drainage
P
Indicator ON Indicator ON
Pump OFF E1 E1
Pump ON

Pump ON Indicator OFF Indicator OFF


E2 E2 P

E3 E3 Pump OFF

• Connect electromagnetic switch coil terminal A to terminal 2. • Connect the electromagnetic switch coil terminal A to terminal 3.
• The pump stops when the water level reaches E1 (indicator ON) • The pump starts when the water level reaches E1 (indicator ON)
and starts when the water level drops below E2 (indicator OFF). and stops when the water level drops below E2 (indicator OFF).

200-VAC power supply 61F-GP-N8


R S T

2 1 8 7
MCCB U
0V 8V

24 V Control circuit U
200 V

(See note 1 U
below.)
3 4 5 6

Contactor
(See note 2
below.) PS-3S

Stop
THR E1
Water tank Start
E2
E3

Reservoir

M P

Note: 1. The diagram shows the connections for the water supply. When draining, change the connection from terminal 2 to terminal 3.
2. The ground terminal must be grounded.
61F-GP-N8j 61F-GP-N8j

Connection with Three-phase Four-line Circuit


When supplying power from N-phase to the Controller in three-phase four-line circuit, refer to the following diagrams.
Line voltage (R-S, S-T, or R-T): 380 or 415 VAC
Phase voltage (N-R, N-S, or N-T): 220 or 240 VAC
61F-GP-N8j, 220 or 240 VAC
Power source
380 to 415 VAC
R S T N *

6 5 4 3

U Control 24 V
circuit

8V
U Transformer

7 8 1 2
A

*
Electromagnetic switch

E1 Stop
Water tank
E2
Start
Water supply source E3

P
M

Note: Be sure to ground terminal 1.


61F-GjP 61F-GjP

Plug-in Models
Specifications
Item General-purpose Long-distance High-sensitivity Low-sensitivity
Controller Controllers Controllers Controller
61F-G1P 61F-G1PL 61F-G1PH 61F-G1PD
61F-G2P 61F-G2PL 61F-G2PH 61F-G2PD
61F-IP 61F-IPL 61f-IPH 61F-IPD
(see note 2) (see note 1)
Controlling materials For control of ordinary For control of ordinary For control of liquids with For control of liquids with
and operating purified water or sewage purified water in cases high specific resistance low specific resistance
conditions water where the distance be- such as distilled water such as salt water, sew-
tween sewage pumps age water, acid chemi-
and water tanks or be- cals, alkali chemicals
tween receiver tanks
and supply tanks is long
or where remote control
is required.
Supply voltage 100, 110, 120, 200, 220, 230 or 240 VAC; 50/60 Hz
Operating voltage range 85% to 110% of rated voltage
Interelectrode voltage 8 VAC 24 VAC 8 VAC
Interelectrode current Approx. 1 mA AC max. Approx. Approx. 1.2 mA AC max.
0.4 mA AC max.
Power consumption Approx. 6.4 VA max.
Interelectrode operate 0 to approx. 4 kΩ 0 to 1.8 kΩ (for 2 km) Approx. 15 kΩ to 0 to approx. 1.8 kΩ
resistance 0 to 0.7 kΩ (for 4 km) approx. 70 kΩ
(see note 5)
Interelectrode release Approx. 15 k to ∞ Ω 4 k to ∞ Ω (for 2 km) Approx. 300 k to ∞ Ω Approx. 5 k to ∞ Ω
resistance 2.5 k to ∞ Ω (for 4 km)
Response time Operate: 80 ms max.
Release: 160 ms max.
Cable length 1 km max. 2 km max. 50 m max. 1 km max.
(see note 3) 4 km max.
Control output 2 A, 200 VAC (Inductive load: cosφ = 0.4)
5 A, 200 VAC (Resistive load)
Ambient temperature Operating: --10°C to 55°C
Ambient humidity Operating: 45% to 85% RH
Insulation resistance 100 MΩ min. (at 500 VDC)
(see note 4)
Dielectric strength 2000 VAC, 50/60 Hz for 1 min.
(see note 4)
Life expectancy Electrical: 500,000 operations min.
Mechanical:5,000,000 operations min.

Note: 1. The relay in the 61F-G1H/-G2H/-IPH de-energizes when there is water present across the Electrodes, whereas the relay in the
61F-GP-N8HY energizes when there is water present across the Electrodes.
2. Models are available for 2 km and 4 km.
3. The length when using completely-insulated, 600-V, 3-conductor (0.75 mm2) cabtire cables. Usable cable lengths will become
shorter as the cable diameter or number of conductors becomes larger.
4. The insulation resistance and dielectric strength indicate values between power terminals and Electrode terminals, between power
terminals and contact terminals, and between Electrode terminals and contact terminals.
5. Possible to use with 15 kΩ or less, however, this may cause reset failure.
61F-GjP 61F-GjP

Internal Circuit Diagrams


61F-G1P/-G1PL/-G1PD 61F-G1PH 61F-G2P/-G2PL/-G2PD
7 14 6 5 12 4 3 7 14 6 5 12 4 3 7 14 6 5 12 4 3
U2
U1
U1
U2 U2 U1
U1 U1 U1
24 V Control circuit 24 V Control circuit 24 V Control circuit
Power Power Power
supply 24 V Control circuit U2 supply 24 V Control circuit U2 supply 24 V Control circuit U2
8V 24 V 8V
U2 U1 U2 U1

8 9 15 10 1 11 2 8 U2
9 15 10 1 11 2 8 9 15 10 1 11 2

61F-G2PH 61F-IP/-IPL/-IPD 61F-IPH


7 14 6 5 12 4 3 7 14 6 5 12 4 3
7 14 6 5 12 4 3
U2

U1 U1 U1
U1 U2 U2 U1 U2 U2 U1
24 V Control circuit U1
U1
Power 24 V Control circuit 24 V Control circuit
supply 24 V Control circuit U2 Power Power
supply 24 V Control circuit U2 supply 24 V Control circuit U2
24 V
8V 24 V
U2
8 9 15 10 1 11 2
8 9 15 10 1 11 2 8 9 15 10 1 11 2
61F-GjP 61F-GjP

Connections
61F-G1P

Application 1: Automatic Water Supply Control with Pump Idling Prevention


Water supply
Water tank source
• The pump stops when the water level reaches E1 and the pump
Water starts when the water level in the tank drops below E2.
supply
P • When the level of water supply source drops below E2’, the
Pump pump stops. Pumping idling is prevented and the alarm sounds.
E1
OFF
E1’ • Insert a pushbutton switch (NO contact) between 11 and 15 as
E2’
Short-
Pump
shown by the dotted line below. When starting the pump and
age
E3’
ON E2 after recovering from a power failure, if the water supply source
B
L E3 level has not yet reached E1’, press the pushbutton switch to
start the pump by momentarily short-circuiting E1’ and E3. When
the pump stops during normal operation subsequent to an alarm
issued for a low water level, do not press the pushbutton switch.
Alarm
61F-G1P
200-VAC power supply B
R S T
7 14 6 5 12 4 3
U2
U1
Transformer
0V Control U1
MCCB 24 V
circuit
24 V Control
circuit U2
200 V
8V
U2 U1

8 9 15 10 1 11 2

A Pushbutton switch

*
Electromagnetic
switch PS-3S

E1
Water tank
Water supply E2
THR source E3
PS-3S

E1’
E2’
P E3
M

Note: Be sure to ground terminal 15.


61F-GjP 61F-GjP

61F-G1P
Application 2: Automatic Water Supply Control with Abnormal Water Shortage Alarm
Water tank
Water supply • The pump stops when the water level reaches E1 and starts
Water drainage when the water level drops below E2.
P

Pump OFF E1 • If the water level drops below E4 for any reason, the pump stops
and the alarm sounds.
Pump ON
E2 • Insert a pushbutton switch (NO contact) between 11 and 15.
B L
E4 • When starting the pump and after recovering from a power
Shortage
E3 failure, if the water level has not yet reached E4, press the
pushbutton switch to start the pump by short-circuiting E3 and
E4.
• If the pump stops upon release of the pushbutton switch, keep
pressing the pushbutton switch.

200-VAC power supply


R S T 61F-G1P B Alarm
7 14 U26 5 12 4 3
U1
Transformer
0V Control U1
24 V
MCCB circuit
24 V Control
circuit U2
200 V
8V
U2 U1

8 9 15 10 1 11 2
Pushbutton switch

A
* PS-4S
Electromagnetic switch

Water tank E1
E2
Water supply E3 E4
THR
source

P
M

Note: Be sure to ground terminal 15.


61F-GjP 61F-GjP

61F-G2P
Automatic Drainage Control with Abnormal Water Increase Alarm

Application 1: Drainage
Water drainage
B L • Connect terminal 8 to power supply terminal 9.
Upper
limit
E4 • The pump starts when the water level reaches E1 and stops
E1
Pump ON when the water level drops below E2.
• If the water level reaches E4 for any reason, the alarm sounds.
Pump OFF
E2
P
E3

Alarm
B
61F-G2P

U2 7 14 6 5 12 4 3
200-VAC power supply
R S T
Transformer U1
0V
24 V
Control U1
circuit

24 V Control U
2
circuit
200 V
8V

U2
Electromagnetic 8 9 15 10 1 11 2
switch

Reservoir
THR
PS-4S
Water supply
source
E1 E4
E2
P E3
M

Note: Be sure to ground terminal 15.


61F-GjP 61F-GjP

61F-G2P
Application 2: Water Supply
Water supply
L B
• Connect the terminal 6 to terminal 9 (power supply line).
P
Upper
limit
• The pump starts when the water level reaches E2, and stops
E4
Pump OFF
when the water level rises to E1.
E1
• If the water level reaches E4 for any reason, the alarm sounds.
Pump ON
E2
E3

B
Alarm
61F-G2P
200-VAC power supply
R S T
7 14 6 5 12 4 3
U2 U1
MCCB
U1
0V 24 V Control circuit

24 V Control circuit U2

200 V 8V

U2
8 9 15 10 1 11 2

Contactor

Water tank
THR PS-4S

E
E1 4
E3 E2
Reservoir

M P

Note: Be sure to ground terminal 15.


61F-IPj 61F-IPj

61F-IP

Liquid Level Indication and Alarm


B LH Upper
• When the water level drops below E2, the lower-limit indicator
limit
turns ON and the alarm sounds.
E1

• When the water level reaches E2, the indicator turns OFF and
LM
Middle the intermediate indicator turns ON.
• When the water level rises to E1, the upper-limit indicator turns
Lower
B LL limit
E2 ON and the alarm sounds.
E3

Intermediate
Lower limit

Upper limit
200-VAC power supply
Alarm B PL PL PL
RST
61F-IP

7 14 6 5 12
MCCB U1 4 3
U2 U1
U2
Transformer
0V Control U1
24 V
circuit

Control
24 V
circuit U2
200 V
8V

8 9 15 10 1 11 2

* PS-3S
Water tank Upper alarm
Water supply E1 Intermediate
source E3 E2 Lower alarm

P
M

Note: Be sure to ground terminal 15.


61F-UHS/HSL 61F-UHS/HSL

Ultra High-sensitivity Models


Use these models for sensing objects such as ice, high-purity distilled water, moisture, or other objects with low electrical conductivity.
Specifications
Item High-sensitivity 61F-UHS Variable high-sensitivity 61F-HSL
Supply voltage 100, 200, or 220 VAC; 50/60 Hz 24, 100, 110, 200, or 220 VAC; 50/60 Hz
Operating voltage range 85% to 110% of rated voltage
Interelectrode voltage 24 VAC 13 VDC max.
Interelectrode current Approx. 1 mA AC max. Approx. 1 mA DC max.
Power consumption 3.2 VA max.
Interelectrode operate resistance 0 to approx. 1 MΩ (see note 1) 0 to approx. 5 MΩ (variable)
Interelectrode release resistance Approx. 5 M to ∞ Ω Operate resistance + 2.5 MΩ max.
Cable length 5 m (see note 2) Note 3
Control output 0.3 A, 220 VAC (Inductive load: cosφ = 0.4) 2 A, 220 VAC (Inductive load: cosφ = 0.4)
1 A, 220 VAC (Resistive load) 5 A, 220 VAC (Resistive load)
Ambient temperature Operating: --10°C to 55°C
Ambient humidity Operating: 45% to 85% RH
Insulation resistance 100 MΩ max. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min
Life expectancy Electrical: 50,000 operations min. Electrical: 500,000 operations min.
Mechanical: 5,000,000 operations min. Mechanical: 5,000,000 operations min.
Note: 1. Use 61F-UHS for detecting water leakage with high specific resistance. Connect a sensor cable (page 69) between terminals 1 and
7.
2. Two Electrodes can be connected to the 61F-HSL. Use them for an alarm, not for creating a self-holding circuit.
3. The length when using completely-insulated, 600-V, 3-conductor (0.75 mm2) cabtire cables. Usable cable lengths will become
shorter as the cable diameter or number of conductors becomes larger. For more details, refer to Short Wiring in Electrode Circuit on
page 65.
4. it is recommended that the cable length be kept as short as possible since the Electrode circuit current is at DC micro-current level.
Moreover, the Electrodes will corrode rapidly if the current is allowed to constantly flow between the Electrodes.
Be careful with the electrode polarity and grounding when wiring.
Internal Circuit Diagrams
61F-UHS 61F-HSL

S1 6 Relay
power supply

Rectification/ S1 5
Operation

smoothing To each circuit


circuit
Constant voltage
smoothing circuit

Power
supply
Rectification
power supply

Power To each circuit


smoothing circuit

Operation
Power circuit
Level detection

circuit

supply
Rectification

S2 5 Relay
S2 6
circuit

E3 1
Surge--absorbing

7
Power circuit
Level detection

E1 7
1 Relay
E2 8
circuit
circuit

X/a Ground 8
Tb 2
Tb 2
Tc 4 X/c
Tc 4 X/c
Ta 3
Ta 3
61F-UHS/HSL 61F-UHS/HSL

External Circuit Diagrams (Example)


61F-UHS 61F-HSL

Power Power
4 5 4 5
source source
3 6 3 6

2 7 2 7
1 8 1 8

E3 E2 E1
(--) (+)

Socket: 8PFA1 (track mounted)/ Socket: 8PFA (track mounted)/


PL08 (back connecting) PL08 (back connecting)

61F-UHS
Automatic Operation for Water Supply and Drainage
1. Water Supply 2. Water Drainage

Water supply Water drainage


P

Pump OFF Pump ON


E1 E1

Pump ON Pump OFF


E2 E2 P
E3 E3

• Operation: When the water level reaches E1, the pump stops • Operation: When the water level reaches E1, the pump starts
and, when the water level reaches E2 or below, the pump starts. and, when the water level reaches E2 or below, the pump stops.
• Connection: Connect the contactor coil terminal to terminal 2 of • Connection: Connect the contactor coil terminal to terminal 3 of
the plug-in model. (Terminal 3 is not used.) the plug-in model. (Terminal 2 is not used.)

61F-UHS
200-VAC power supply
R S T
6 5 4 3

MCCB U

0V 24 V Control circuit U

24 V
200 V

7 8 1 2

Note: The diagram shows the connections for the water supply.
Contactor When draining, change the connection from terminal 2 to
terminal 3.

THR PS-3S

Stop
E1
Water tank
E2 Start
E3
Reservoir

M P

Be sure to ground terminal 1.


61F-APN2 61F-APN2

61F-APN2 Solid-state Alternate Operation Relay


When operating two pumps alternately for controlling the one-point liquid level, use the Relay in combination with 61F Controller.

61F-APN2 Compact Plug-in Model

Specifications
Ratings
Supply voltage 100, 110, 200, 220 VAC; 50/60 Hz
Operating voltage range 85% to 110% of rated voltage
Power consumption 3 VA

Contact Ratings (With G2RK Keep Relay)


Item Resistive load (cosφ = 1) Inductive load (cosφ = 0.4, L/R = 7 ms)
Max. load 3 A at 250 VAC 1.5 A at 250 VAC
Carry contact 3A
Max. operating current 3A
Max. switching capacity 750 VA 375 VA
Characteristics
Response time Operate: 25 ms max.
Release: 30 ms max.
Minimum pulse width Min. ON time: 40 ms min.
Min. OFF time: 200 ms min.
Insulation resistance 100 MΩ min. at 500 VDC (between each terminal and power supply)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min (between each terminal and power supply)
Vibration resistance 10 to 55 Hz, 1-mm double amplitude
Shock resistance 10 G (approx. 98 m/s2)
Life expectancy Mechanical: 1,000,000 operations (at operating frequency of 1,800 operations/hour)
Electrical: 100,000 operations min.
(rated load)
Ambient temperature Operating: --10°C to 55°C
Ambient humidity Operating: 45% to 85% RH
When power is applied to the input terminals 2 and 7, the power will The above operation repeats each time power is applied to the input
be transmitted through the alternate operation control circuit and terminals (power application pulse response system). Refer to the
output circuit to turn ON the contacts (NO condition) between 1 and following internal circuit diagram.
3 and between 6 and 8. This state will be held by a magnetic lock
even when the power to the input terminals is turned OFF.
When power is again applied to the input terminals, the contact (NO
condition) will turn OFF and the contacts (NC condition) between 1
and 4 and between 5 and 8 will turn ON. This state will be held even
when the power to the input terminals is turned OFF.

Internal Circuit Diagram 4


X/c1
3
2
1
Alternate operation
control circuit

Output circuit
Power circuit

5
X/c2
7 G2RK (61F-APN2) 6

8
61F-APN2 61F-APN2

Connect the output terminal Ta of the 61F-Gj to input terminal 2 of the 61F-APN2.
Connection
Connect the contactor coil terminal A to the switching contact terminals 3 and 4 of the 61F-APN2.
Operation of the two pumps can be displayed using the switching contact terminals 5 and 6 of the 61F-APN2.

Output contact between


1 and 3 and 6 and 8

Output contact between


1 and 4 and 5 and 8

Power supply voltage


between 2 and 7

40 ms min. 200 ms min.

Timing Chart of Water Supply Alternate Operation

Ta
61F
Tb

Power

Output
61F-APN2 1-3
Output
1-4
Contact 1

Contact 2

When the 61F-APN2 Alternate Operation Relay is used in combina- In case of water supply operation, the output contacts of the Alter-
tion with a 61F Controller, the output contacts of the Alternate nate Operation Relay will be switched after the normally closed con-
Operation Relay will not be switched (OFF) while the contactor is tacts of the 61F turn OFF upon reaching the control level, and the
being excited, and the contactor will not be excited (ON) at the mo- output contacts will be already switched when the normally closed
ment when the output contacts are switched. That is, loads such as contacts of the 61F turn OFF next time.
contactors will not be directly turned ON or OFF by the actions of the Therefore, only the continuous line current needs to be considered
output contacts of the 61F-APN2 Alternate Operation Relay. as the load capacity of the 61F-APN2 and the current can be applied
Instead, they will be turned ON or OFF by the actions of the 61F up to the rated line current of 3 A.
Controller.
61F-APN2 61F-APN2

Connections
At 200 VAC
Water Supply (When Combined with 61F-G)
The relay operation can be monitored if
indicators are connected as shown by
the dotted line.
To power source T
200-VAC power source L2 L1
R S T 61F-G
61F-APN2
U
6 5 4 3 0V 61F-11
24 V Relay Unit
MCCB
100 V
8V U
200 V
Electronic
circuit U

Ta Tc Tb E2 E1
7 8 1 2
S0 S1 S2 E3

Contactor 1 Contactor 2

PS-3S
THR THR Water tank

E1
Water supply resource Water supply resource E2
E3

P1 P2
M1 M2

*Be sure to ground terminal E3.


Note: When controlling drainage, change the connections as shown by dotted lines in the following illustration.

61F-APN2

1 2

Tb Ta

61F-G
61F-APN2 61F-APN2

Water Supply (When Combined with 61F-G1)

The relay operation can be monitored if


indicators are connected as shown by
the dotted line.
To power source T
200-VAC power source L2 L1 61F-G1
R S T
61F-APN2 U1
61F-11
0V 24 V
6 5 4 3 Relay Unit
100 V U2
MCCB 24 V 61F-11
Relay Unit
200 V 8V
Electronic U2 U1
circuit U2
U1

S0 Tb1 Ta1 Tc2 Tb2

S1 S2 E3 E2 E1 E2’ E1’
7 8 1 2 (E4)

B
Alarm

Contactor 1 Contactor 2

PS-3S
THR THR Water tank
Water supply source
PS-3S
Water supply source E1
E2
E3
E1’
E2’
E3

M1 P1

M2 P2

*Be sure to ground terminal E3.


Note: The 61F-G1 is to be used only for supplying water and cannot be used for alternate operation for controlling drainage.
61F-APN2 61F-APN2

Water Drainage (When Combined with 61F-G2)

The relay operation can be monitored if


indicators are connected as shown by
the dotted line.
To power source T
200-VAC power source L2 L1 61F-G2
R S T 61F-APN2
U1
0V 24 V 61F-11
6 5 4 3 Relay Unit
100 V U2
MCCB 24 V 61F-11
Relay Unit
200 V 8V
Electronic U2
circuit
U2 U1

S0 Ta1 TC1 Tb1 Ta2 TC2

S1 S2 E3 E2 E1 E4
7 8 1 2

Alarm

*
Contactor 1 Contactor 2

THR THR

PS-4S
Water supply source Water supply source

E
E1 4
E2
E3
M1 P1

M2 P2

*Be sure to ground terminal E3.


Note: When supplying water, change the two connections as shown by dotted lines in the following illustration.

61F-APN2

1 2

Tb1 Ta1

61F-G2
61F-APN2 61F-APN2

Water Supply (When Combined with 61F-G3)

The relay operation can be monitored if


indicators are connected as shown by
the dotted line. 61F-G3
To power source T
200-VAC power source 61F-11 U1
L2 L1 24 V
R S T 61F-APN2 Relay Unit
0V U2
61F-11
24 V
6 5 4 3 100 V Relay Unit
MCCB 61F-11 U3
24 V
Relay Unit
200 V
Electronic 8V
circuit

U2 U1 U3 U1 U3 U2

Ta Tc Tb B1 B2 Lc E1 E3 E5

7 8 1 2 S0 S1 S2 LH LL E2 E4

B Upper Upper

Alarm
PL limit
indi- PL limit
indi-
cator cator

Power source

Contactor 1 Contactor 2
PS-5S *
THR THR Water tank

E1
E2
Water supply source E3
E4
E5

M1 P1

M2 P2

*Be sure to ground terminal E3.


Note: When discharging water, change the two connections as shown by dotted lines in the following illustration.

61F-APN2

1 2

Tb Ta

61F-G3
61F-APN2 61F-APN2

Water Supply (When Combined with 61F-G4)

61F-G4

0V 61F-11 U5
24 V
Relay Unit
The relay operation can be monitored
100 V 61F-11 U1
if indicators are connected as shown 24 V
by the dotted line. Relay Unit
200 V
To power source T U2
61F-11
24 V
200-VAC power supply L2 L1 U2 Relay Unit
R S T MK3P
61F-APN2 relay 61F-11 U3
X 24 V
Relay Unit
6 5 4 3 100 V U4
24 V 61F-11
MCCB Relay Unit

200 V 8V
Electronic
circuit X U3
X U4 U3 U1 U5 X U4 U2 U5

U1

LL1 LL2 LH1 LH2 BL1 BL2 BH1 BH2 E4 E3 E2 E1

7 8 1 2 S1 S2 TA E6
S0 TC TC2 B E8 E7 E5

LL1 LL2 LH1 LH2 BL1 BL2 BH1 BH2


Shortage Lower Full in Upper Shortage Lower Full in Upper
in elevated limit of elevated limit of in limit of elevated limit of
tank supply
supply tank supply elevated supply tank source
source source tank source

Contactor 1
Contactor 2

PS-5S
THR THR * Water tank

E4
PS-4S E
Water supply source E 5
E7 6
E8
E
E 1
E3 2
E8

M1 P1

M2 P2

*Be sure to ground terminal E3.


Note: The 61F-G4 is to be used only for supplying water and cannot be used alternately for controlling drainage.
61F-APN2 61F-APN2

At 220 VAC
Water Supply (When Combined with 61F-G1P)

For example, operation indication is


possible by the connection as
shown by the dotted line. Alarm
Power B
source
220 VAC L2 L1 61F-G1P
R S T
61F-APN2
7 14 6 5 12 4 3
6 5 4 3
Knife
switch U1
U2

Electronic U1
circuit 0V 24 V Control circuit

24 V Control circuit U2

220 V 8V
U2 U1

7 8 1 2 8 9 15 10 1 11 2

Pushbutton switch
A A

Electromagnetic
*
Electromagnetic switch 1
switch 2 PS-3S

THR THR
Water
PS-3S
tank
Water supply source E1
E2
E3
E1
E2
E3

M1 P1

M2 P2

*Be sure to ground terminal 15.


61F-APN2 61F-APN2

Water Supply (When Combined with 61F-GP-N)


For example, operation indication is
possible by the connection as
shown by the dotted line. 61F-GP-N
Power
source
220-VAC L2 L1 8 7 6 5
R S T
61F-APN
4
U
6 5 4 3
Knife 0V 24 V Control circuit U
switch

Electronic 8V
220 V
circuit
U
9 3

10 11 1 2

7 8 1 2

A A

*
Electromagnetic switch 1 Electromagnetic switch 2
THR PS-3S
THR Water tank

E1
Water supply source Water supply source E2
E3

P1 P2
M1 M2

*Be sure to ground terminal 4.


61F-APN2 61F-APN2

Water Drainage (When Combined with 61F-G2P)


Alarm
For example, operation indication is B
possible by the connection as shown
by the dotted line.
Power 61F-G2P
source
220-VAC L2 L1
61F-ANP2 7 14 6 5 12 4 3
R S T

U2 U1
6 5 4 3
Knife U1
switch 0V 24 V Control circuit

Electronic
circuit 24 V Control circuit U2

8V
220 V

U2

7 8 1 2 8 9 15 10 1 11 2

A A
*
Electromagnetic switch 1 Electromag-
netic switch 2

THR
THR

PS-4S
Water supply source

E
E1 4
E2
E3
M1 P1

M2 P2

*Be sure to ground terminal 15.


61F-03B/04B 61F-03B/04B

61F-03B/04B Surge Suppressor Unit


A high-capacity protective device is available which protects 61F-series Floatless Level Controllers against faults arising from electrical surges
(such as indirect strokes of lightning) when the Controllers are employed in elevated water tanks or in high-altitude locations.
Specifications
Discharge start voltage 90 V ±20 VDC
Impulse withstand voltage 200,000 V (1 x 40 µs)
Impulse withstand current 6,000 A (1 x 40 µs)

Internal Connections
61F-03B 61F-04B

Precautions
1. Mount the Surge Suppressor Unit as close to the Controller
as possible. Adequate results may not be obtained if mounted
close to the Electrode Holder.
2. When grounding the Surge Suppressor Unit in the vicinity of
the Controller, connect the ground side of the Surge
Suppressor Unit to Electrode E3, E5, or E8 (ground terminal).

Long distance

61F-03B

Ground

Connection Sockets
PF113A-E Track-mounted Socket
PL11 Back-connecting Socket
61F 61F

Accessories (Order Separately)


Electrode Holders
Applications For city water and other When mounting space is For low specific liquids. When secure installation
General-use Electrodes. limited. Special 3-pole Used for sewage, sea is required.
Easy-to-replace separate holder of small size and water, etc., having a low For sewage, city water
versions facilitate light weight. Ideal for soft specific resistance. In and other general use. 3-,
maintenance of drink vendors, etc., where sewage use, Electrode 4-, and 5-pole models are
Electrodes. only limited space is Holders must be installed available. In outdoor or
available. 10 to 20 cm apart from dusty locations, or
one another. For acids, locations subject to water
alkalis and sea water, splashes, adherence of
Electrode Holders may be water, dust, dirt, or other
as much as 1 meter apart foreign matter to the
to operate properly. Electrode insulator may
cause Controller
malfunctioning due to
leakage. Be sure to use
the Protective Cover.
Mounting style Flange Screw Flange
Insulator material Phenol resin Ceramics
Max. temperature 70°C max. 150°C max. (without water 150°C max.
drips or vapor on the
surface of the Electrode
Holder)
Appearance PS-3S(R) PS-31 BF-1 BF-3(R) Heat re-
PS-4S(R) BF-4(R) sisting
PS-5S(R) BF-5(R) temp.

Heat re-
sisting
temp.
(see note 2)
No. of 1 --- --- BF-1 ---
El t d
Electrodes 3 PS-3S(-3SR) (see note 1) PS-31 --- BF-3(-3R) (see note 2)
4 PS-4S(-4SR) (see note 1) --- --- BF-4(-4R) (see note 2)
5 PS-5S(-5SR) (see note 1) --- --- BF-5(-5R) (see note 2)
Note: 1. Those with the suffix R in their model name are for 2-wire circuits.
2. The Electrode material for PS-31 is SUS304. (Length: 300 mm)
Applications When resistance to high When corrosion When Electrode positions When Electrode positions
pressure is required. Ideal resistance is required. are distant from water are distant from water
for use in tanks where Since Teflon is used as surface. surface.
temperature or pressure the main part, the For deep well, especially For deep well and
inside the tank is high, Electrode is free from rust sewage. Several underwater pump. 2 sets
e.g. 250°C, 1.96 MPa and corrosion. Ideal for Electrodes are used in of special Electrodes
{20 kg/cm2} liquid level control in food combination. attached to cabtire cables
processing, level control Cable length: 100 m max. for upper- and lower-limit
of strong alkaline liquids, Single-core cord of control are to be
etc. 0.75 mm2 (30/0.18) suspended in water.
Withstand pressure: provided. Cable length: 100 m max.
981 kPa {10 kg/cm2} Two-core cord of
0.75 mm2 (30/0.18)
provided.
Mounting style Screw ---
Insulator material Teflon ---
Max. temperature 250°C max. (without water 150°C max. With vinyl cord: --10°C to 60°C
drips or vapor on the With chloroprene cord: --30°C to 70°C (without frost
surface of the Electrode formation)
Holder)
Appearance Heat re-
sisting
Maximum tightening
Hastelloy
torque at the terminal:
temp.:
150 _C
SUS titanium
14 kgDcm (137.2 N)

Material at tightening sec- Heat re-


tion: iron (standard), sisting
SUS304, SUS316 temp.:
250 _C

No. of 1 BS-1 BS-1T PH-1 ---


El t d
Electrodes 2 --- --- --- PH-2
61F 61F

Note: 1. The BS-1 and BS-1T are pressure-proof models. The rest of models are not pressure-proof.
2. The BS-1 that uses SUS304 for clamping sections and screws of PT1/2 specifications is called BS-1S1.
3. The BS-1 that uses SUS304 for clamping sections is called BS-1S and one that uses SUS316 is called BS-1S2.
4. When using the BS-1T in liquids with low specific resistance, provide a large clearance between Electrodes. This clearance must be
varied depending on the specific resistance, for example, approximately 1 m for acid or alkali liquids.
Electrodes, Connecting Nuts, and Lock Nuts
Applicable
pp Material Electrode Models for individual Electrode assembly components
li id
liquids assembly
bl Electrode (1 m long) Connecting nut Lock nut Spring
washer
Model Model Indication Model Inscrip- Model Inscrip- Model
mark tion tion
Purified city Equivalent F03-60 F03-01 1 line F03-02 --- F03-03 --- F03-04
water, to SUS SUS201 SUS201 SUS201 SUS201 SUS201
industrial 304
water, (AISI-304)
sewage
Purified city SUS316 F03-60 F03-01 2 lines F03-02 6 F03-03 316 F03-04
water, (AISI-316) SUS316 SUS316 SUS316 SUS316 SUS316
industrial
water,
sewage,
dilute alkaline
solution
Sodium Hastelloy F03-60 F03-01 3 lines F03-02 B F03-03 B ---
hydroxide, B HASB HASB HASB HASB
acetic acid,
dilute sulfuric
acid, dilute
hydrochloric
acid
Sea water, Hastelloy F03-60 F03-01 4 lines F03-02 C F03-03 C ---
ammonia C HASC HASC HASC HASC
water, nitric
acid
Acetic acid, Titanium F03-60 F03-01 5 lines F03-02 T F03-03 T ---
dilute sulfuric CHITAN CHITAN CHITAN CHITAN
acid, sea
water
Note: 1. An Electrode assembly consists of the following parts:
One Electrode (1 m)
One connecting nut
Two lock nuts
Two spring washers
2. The material indication mark(s) are inscribed near the screw threads, and represent the material composition of the Electrode.
3. Standard Electrodes are made of stainless steel and usable in purified water, sea water, sewage, acid (except acetic acid, sulfuric
acid, etc.) and alkaline liquids. They may corrode depending upon the temperature and working conditions.
4. Corrosion-resisting Electrodes made of SUS316 (AISI-316) and acid-resisting Electrodes made of titanium or hastelloy are also
available.
Electrode

Material
indication
mark

5. When long Electrodes are required, connect them with connecting nuts and lock nuts (2 pieces) every 1 m.
61F 61F

Electrode Separators
No. of Electrodes Model When the required length of Electrode is more than 1 m, use a Sepa-
rator at each joint of two Electrodes so as to prevent the Electrodes
1 F03-14 1P from contacting one another.
3 F03-14 3P Use a one-pole type for BF Electrodes. The five-pole type can be
5 F03-14 5P used for PS-5S and PS-4S Electrodes.
Material: Ceramic

Electrode Holder
Separator

Connecting nut
Separator
Spring washer
Lock nut

Electrode

Electrode Band
• The Electrode Band consists of polyvinyl-chloride-covered
F03-05 3P, 4P, and 5P (PVC) stainless-steel wires SUS304 (AISI-304) which are free
from mutual contact. As the Electrode Band can be cut,
mounted, and removed with ease, it is most suitable for deep
wells.
Sheath: Vinyl chloride
Core: 0.3 dia. x 21, straight wire, SUS304 • Applicable Electrode Holders:
Length: 50 m max. (When ordering, specify the length by meters.) PS-3S, PS-4S, PS-5S, BF-3, BF-4, BF-5

The Electrodes come in three types: 3P, 4P, and 5P. Each of them
• Ambient operating temperature: --10°C to 60°C (with no icing)
require the following accessories that are separately sold. • The Electrode Band cannot be used in flowing water, liquids over
60°C, or liquids which corrode PVC or stainless steel.
Accessories Weight
g Electrode
(
(per 1) Application Example
3P 4P 5P
Connecting Approx. 3 4 5 Electrode Band connecting nut
nut 20 g
Weight Approx. 3 to 4 4 to 6 5 to 8
50 g
End cap Approx. 3 4 5
1g
Insulation Approx. 2 3 4
Cap 10 g
Adhesive Approx. 1 1 1 Weight
5g
Electrode Band
Electrode --- Approx. Approx. Approx.
Band weight 110 g 140 g 180 g End cap
(1m)
61F 61F

Other Accessories
F03-11 Protective Cover F03-12 Spring Clamp F03-13 Mounting Frame for installing in
concrete
Use this Cover for PS-series Electrode Used to clamp an Electrode Holder with Useful frame for burying in concrete. Cut
Holders with Mounting Frames (upper one ease, as shown in the illustrations, when as required based on the concrete depth.
in the following illustration), This Cover can the Electrode Holder is applied to a tank
also be used when installing the BF-series without a coupling. 115 dia.
Electrode Holders outdoors. Since this Squeeze the mounting frame into the 96
Cover is not water-proof, water or dust may Holder as shown below.
enter through the wire hole (lower one
Applicable Electrode Holders:
below). 80
PS-3S(R), PS-4S(R), PS-5S
100 60
Applicable Electrode Holders:
10 70
BF-3, BF-4, BF-5, PS-3S(R), PS-4S(R),
PS-5S(R)

96 72 dia.
Weight: Four, M5 x 25
112 dia. 82 dia.
mounting
60 approx. 65g screws
Operating
temp.: --10°C
to 70°C
120 dia.

Mounting Frame em-


bedded into concrete
Electrode

Two, M5 x 25 Commonly used with


mounting screws Mounting Frame
Electrode

Electrode

Mounting
PS-3S Electrode Holders
1. Mounting Electrode Holder 2. Attaching Electrode(s) to Electrode 3. Inserting Electrode section into
section Electrode Holder
• Screw the Electrode Holder into the • Insert each Electrode into the connecting • Fit the Electrode section into the
coupling secured at the installation nut, secure the Electrode with the clamp Electrode Holder and secure it with the
location. screws, and then tighten the lock nut. two screws.
• Connect the leads, inserted through the • Check the Electrode section for proper
hole of the rubber bushing, into the wiring, fit the rubber bushing in position,
respective terminals. and then cover the Electrode Holder with
the drip-proof cover.
Electrode section Drip-proof
Twin Electrode housing cover
clockwise Holder

Electrode
section
Rubber housing
bushing

Electrode
Electrode
Lock nut
Holder

Coupling

Note: 1. OMRON does not sell couplings.


2. Screw in the Electrode until it reaches the bottom of the nut. Insufficient insertion will cause a faulty connection.
61F 61F

Installing PS-jS Electrode Holder on Tank


1. For tanks with thin walls combined with the F03-12 Spring Clamps
1. Using the F03-12 as a nut

PS-jS
Tank

F03-12
Electrode

2. Using the F03-12 as a flange

PS-jS

F03-12

Tank
Electrode

Screw (attached to F03-12)

2. For tanks with thick metal walls


1. Fabricate screw threads of the same size as for the PS-jS in
the tank

PS-jS

Tank Electrode

3. For concrete tanks

PS-jS

F03-12

F03-13

Concrete
Electrode
61F 61F

Electrode Holder and Electrodes


How to Mount Electrodes
Connecting Electrodes to Electrode Holders Connecting One Electrode to Another
When a long Electrode is required, use two or more Electrodes by
Electrode Holder jointing them with a connecting nut and two lock nuts at intervals of
1 m.
Clamp screw
Electrode
3. Tighten the Electrode with the
Connecting nut two clamp screws. (see note) Lock nut
2. Fit each Electrode into the
1. Spin a locknut and a spring Spring washer connecting nut so that the
washer onto the Electrode. Spring washer (see note) ends of the two respective
Connecting nut Electrodes contact with one
another at the center of the
4. Secure the connecting nut by connecting nut.
tightening the lock nut and
spring washer. 3. Tighten the Electrodes with
Spring the two clamp screws.
washer
Lock nut 2. Fully fit the Electrode into the 4. Secure the connecting nut
connecting nut attached to with the two lock nuts and
the Electrode Holder. two spring washers. at both
Electrode ends of the connecting nut.

Note: Clamp screw and spring washer are not 1. Spin a locknut and a spring
provided for the BS-1T Electrode Holder washer onto each Electrode
(titanium, hastelloy B, or hastelloy C). end.

PH-1/PH-2 Electrodes
PH-1 PH-2
(See Notes 1 and 2) E2
(white)
E3 E1
(black) (white)

Control range

200 mm max. Control range

5 mm

Note: 1. When the distance between E1 and E3 exceeds 1 m for supplying purified city water, for example, locate a second E3 within 200 mm
of E1.
2. Even when the distance is less than 1 m, the product may not operate due to the water quality.
61F 61F

Electrode Bands
Connecting Electrode Holder and Electrode Band Mounting Weight(1)
Connect the connecting nut to the Electrode section as shown in the illustration below To mount an Electrode Band Weight on an
and secure the connecting nut with the clamp screw. Insert the Electrode Band into the Electrode Band, firmly tighten the two
lower hold of the connecting nut, and tighten the two clamp screws so that the screws A or B. The needle screws will
conductor in the Electrode Band will come into contact with the connecting nut. Then come into contact with the electrode wire
mount the Electrode Holder to the Electrode section and secure them with two (conductor) allowing the Electrode Band
mounting screws, which are provided with the model. Weight to become an electrode plate. (Be
sure to use screw holes A or B.). The
Electrode has guides for connecting
Drip-proof
cover screws as shown by the arrows below so
Electrode Connecting nut that connecting screws can be properly
section (SUS304) inserted into the conductor.
housing Securing A
screws
Connecting
Electrode Band
nut

Electrode
Band
Electrode
Holder Electrode
band

Guides

B F03-07 Weight (SIS304)

Mounting Weight (2) Mounting Insulation Cap Mounting End Cap


Install Electrode Band Weights in three Cover each Electrode Band Weight with an Cover the Electrode Band end and apply
positions. The Electrode Band Weights Insulation Cap so as to prevent false the Adhesive sold separately to prevent
work as short, medium, and long detection due to contact between the water from entering between the sheath
Electrodes, allowing the Electrode Band to Electrode and tank. Deform the Insulation and the the End Cap.
detect high, medium, and low levels of Cap to an ellipsoid before installing it on
liquid. the Electrode Band Weight.

F03-10
Adhesive

F03-09 End Cap (rubber)


F03-09 Insulation Cap (PVC)

In purified city water, if the distance between the long Electrode (E3) and short Electrode (E1) is more than 50 cm, install another
Electrode Band Weight as E3 in the vicinity of E1 at intervals of 15 to 20 cm, referring to Mounting Weight (2) above. An Insulation Cap
is not needed for the long Electrode.

Connect the Electrode


wire to the connecting nut.
Secure the Weight
with needle screws.

E1 (short)
Insulation Cap

E3 (long)
Control range

Add another E3 (long Electrode)


Weight if this distance is more than 50
E2 (medium) cm.

Insulation Cap

E3 (long)
End cap
61F 61F

Mounting the Protective Cover on the Mounting the Protective Cover on the
PS-series Electrode Holder BF-series Electrode Holder (BF-3/4/5)
Attach the F03-12 Mounting Frame to the bottom of the PS-series Remove the two mounting screws (M5 x 25) of the BF-series Elec-
Electrode Holder as shown below. Next, place the F03-11 Protec- trode Holder and attach the two cap screws (M5 x 25) supplied with
tive Cover on top of the Electrode Holder and press on it until a click- the F03-11 Protective Cover.
ing sound is heard. For mounting purposes, the cap screw attached Next, put the Protective Cover over the top of the BF-series Elec-
to the Protective Cover is not required. trode Holder, and then tighten the supplied two screws (M3 x 20 with
washers). Refer to the following illustration.
Protective Cover

M3 x 20
Tighten here
PS-series Electrode Washer
Secure with the Holder
claw of the cover

Protective Cover

Cross-section of the tank

Cap screw M5 x 25

BF-series Electrode Holder

Dimensions
Note: All units are in millimeters unless otherwise indicated.

Standard Models
61F-G
Mounting Holes
M3 screw

Four, 6-dia mounting holes

Four, 6-dia holes

61F-G1 Mounting Holes


61F-G2 M3 screw
61F-I
Four, 6-dia mounting holes

Four, 6-dia holes


61F 61F

61F-G3 M3 screw
Mounting Holes

Four, 6-dia mounting holes

Four, 6-dia holes

61F-G4
M3 screw Mounting Holes

Four, 6-dia mounting holes

Four, 6-dia holes

Plug-in Models
61F-GP-N

61F-
GP-N

PF113A-E

61F-GP-N8

61F-
GP-N8
91

PF083A-E
61F 61F

61F-G1P
61F-G2P
61F-IP

61F-G1P
61F-G2P
61F-IP

14PFA

Ultra High-sensitivity Models


61F-UHS

8PFA1

61F-HSL

8PFA

Solid-state Alternate Operation Relay


61F-APN2

61F-
APN2

PF083A-E

Surge Suppressor Unit


61F-03B
61F-04B
61F-03B
61F-04B

PF0113A-E
61F 61F

Electrode Holders
PS-3S/-4S/-5S
PS-3SR/-4SR/-5SR
Mounting Holes
(see note) PF2 parallel thread Used with
(effective dia.: 58.135) coupling
9-dia. rubber
bushing (inner) 34 dia.

With
Mounting
Bracket
65 dia.
hole

PS-3S (approx. 150 g) PS-4S (approx. 170 g) PS-5S (approx. 185 g)


PS-3SR (approx. 155 g) PS-4SR (approx. 175 g) PS-5SR (approx. 190 g)
Mounting Screw Holes

Note: The PS-3SR, PS-4SR, and PS-5SR have built-in resistor of 6.8 kΩ and used for the two-wire 61F models.

PS-31 PF1/2 Parallel thread

11 dia.
Mounting Holes
Weight: approx. 325 g

Electrode Rubber
SUS304 3 packing
M3 29.5 dia.
F03-31 Dust-preventive rubber cap (optional)
Weight: approx. 20 g Note: Standard holder construction includes three integral
300-mm-long Electrodes. However, a model having
1,000-mm-long Electrodes is available on request.

BF-1 Mounting Holes


Two M5 x 25
Weight: approx. 125 g Terminal bolt Cast iron mounting screws
SUS201 (M6)
Nut (M6)

26-dia. hole

20 dia.

Two, 6-dia. holes


61F 61F

BF-3/-3R
BF-4/-4R BF-3
Weight: approx. 420 g
BF-5/-5R
BF-3R
Weight: approx. 425 g
Mounting Holes
Two, 6-dia. holes

64-dia. hole
Three, 26-dia.
holes

Two, 6-dia. holes

BF-4
Weight: approx. 520 g
BF-4R
Weight: approx. 525 g Mounting Holes

Two, M5 x 25
Cast iron mounting holes

Terminal bolt
Nut M6
SUS201
Four, 26-dia.
holes
Two, 6-dia. holes Two, 6-dia. holes

BF-5
Weight: approx. 710 g
BF-5R
Weight: approx. 715 g Mounting Holes
Two, 6-dia. holes
Five, 26-dia.
holes

110 dia.

BS-1
Weight: approx. 70 g
Width across flats: 20
Terminal bolt Mounting Holes
SUS304 (M4) P=0.7 Two, M4

24 dia.

Nut (iron)

M18 P=1.5
(fine screw thread)

Terminal bolt
SUS304
BS-1T SUS316 Mounting Holes
Titanium
Hastelloy B
Hastelloy C M4 nut Width between
SUS304 flats: 20.5 Two, M4∗∗

24 dia. M18 P=1.5


Hastelloy (fine screw thread)
titanium
∗This nut is made of Teflon
∗∗A connecting nut made of Hastelloy B, Hastelloy
C, or titanium is not supplied with two M4 screws
and thus has no holes for such screws.

Material SUS304 SUS316 Titanium HAS B HAS C


Weight Approx. 55 g Approx. 55 g Approx. 45 g Approx. 65 g Approx. 60 g
61F 61F

PH-1 PH-2
(Approx. 140 g with a 1-m cord) (Approx. 235 g with a 1-m cord)

Two, 6-dia. holes PVC resin (black)


Resin
5 dia.
26 21.7
19 dia. dia dia.
. Two-core
Single-core cable
cable

Cable OD: Vinyl 5.0 dia., Chloroprene 6.5 dia. Cable OD: Vinyl, Hypalon 6.8 dia.

Note: Cable is supplied in lengths of 1, 5, 10, 15, 20, 30, 40,


50, 60, 70, 80, 90, or 100 meters.

Electrode Separators
F03-14 1P for one pole F03-14 3P for three poles F03-14 5P for five poles
6.5 dia. Three, 7 dia. Five, 7 dia.

20 20

28 dia.
41 46
Weight: Approx. 15 g
Weight: Approx. 30 g Weight: Approx. 30 g

Electrode Bands
F03-05 3P, 4P, 5P
Black printing
F03-06 Electrode Band Connecting Nut
Outer sheath: PVC
(1 mm wide) Core: SUS304, 0.3 dia. x 21 twisted (SUS304)
5.5 dia.

F03-07 U-shaped Electrode Band Weight


(SUS304)
M4

5 dia.

Four M4 needle screw

F03-08 End Cap (Neoprene Rubber)

10 dia. 4 dia. 8 dia.


61F 61F

Connecting Sockets
Available Models
Model No. of Controller Unit Track-mounted Socket Back-connecting Socket
61F-UHS 8PFA1 PL08
61F-HSL 8PFA PL08
61F-APN2 PF083A-E PL08
61F-G1P 14PFA PL15
61F-G2P
61F-IP
61F-GP-N PF113A-E PL11
61F-GPN-V50
61F-GP-N8 PF083A-E PL08
61F-03B PF113A-E PL11
61F-04B

Track-mounted Sockets
PF083A-E Eight, M3.5 x 7 Terminal Arrangement/
sems screws
Internal Connections
Two, 4.2-dia. (Top View)
holes Mounting Holes
52 max. 25 dia.
Two, M4 or 4.5-dia. holes

21 max.
41 max.

8PFA
Terminal Arrangement/ Mounting Holes
Internal Connections
Eight, M3.5 x 7 (Top View)
sems screws

Two M4 or 4.5 dia. holes


Two, 4.5 dia.
holes
118 max.
81 max.

51 max.
24 max.

8PFA1 Eight, M3.5 x 7 Terminal Arrangement/ Mounting Holes


sems screws
Internal Connections
(Top View)

Two M4 or 4.5 dia. holes


Two, 4.5 dia.
holes
93 max. 130 max.

51 max.
24 max.
61F 61F

Terminal Arrangement/ Mounting Holes


14PFA Internal Connections
Fourteen, M3.5 x 7
sems screws (Top View)

Two 4.5 dia. or M4 mounting holes


Two, 4.5 dia.
holes
52 max. 118 max.

72 max.
31 max.
M3.5 x 11.5 sems screws for terminal screws

Terminal Arrangement/
PF113A-E Eleven, M3.5 x 5 Internal Connections
sems screws (Top View)
Mounting Holes

52 max.
Two, M4 or 4.5-dia. holes

31 max.

Back-connecting Sockets
PL08 Terminal Arrangement/ Mounting Holes
Internal Connections Two, 3.5-dia. or M3 Controller
(Top View) Unit mounting holes

Two, 2-dia. holes Two, 3.5-dia. or M3 Socket


50.5 max. mounting holes
30 dia.

31 dia.
hole

35 max. Approx. 20.5

PL11 Terminal Arrangement/ Mounting Holes


Internal Connections
(Top View) Two, 3.5-dia. or M3 Socket
mounting holes
Two, 2-dia. holes

31 dia.
51 max. hole

35 max.
Approx. 20.5
61F 61F

PL15 Terminal Arrangement/ Mounting Holes


Internal Connections
Two, 3.5 dia. or M3 Controller
16 max. (Top View) Unit mounting holes

Two, 3.5-dia. or M3 Socket


mounting holes
Two 2-dia. holes
66 max. 41 max.

45 max. 22 max.
61F 61F

Mounting Brackets
When the 61F-G1P/-G2P/-IP/-UHS/-HSL is mounted with a Track-mounted Socket, the Controller is held secure by Mounting Brackets at-
tached to the Socket.
61F-GP-N 61F-03B/-04B
To mount the 61F-GP-N or 61F-GPN-V50 on the PF113A-E Track- When mounting the 61F-03B/-04B on the PF113A-E Track-
mounted Socket, use the PFC-N8 Mounting Brackets attached to mounted Socket, use the PFC-A1 Mounting Bracket.
the Socket as accessories.
PFC-A1
PCF-N8

Approx.
80

To mount the 61F-03B/-04B Unit to the PL11 Back-connecting


Socket, use the PLC-1 Mounting Brackets.
To mount the 61F-GP-N or 61F-GPN-V50 on the PL11 Back-con- PLC-1
necting Socket, use the PHC-5 Mounting Brackets.
PHC-5

61F-GP-N8/61F-APN2
To mount the 61F-GP-N8/61F-APN2 on the PF083A-E, use the
PFC-N8 Mounting Bracket.
PFC-N8

Approx.
80
61F 61F

DIN Track Mounting Accessories


DIN Track End Plate
PFP-100N PFP-M
PFP-50N

M4 x 8
Round
head
screw

(see note 1) (see note 1)

(see note 2)
M4 spring washer

DIN Track Spacer


PFP-100N2 PFP-S

(see note 2)

Note: 1. The PFP-100N is 15 mm on both ends, while the PFP50N


is 15 mm on one end and 5 mm on the other end.
2. Indicates total DIN Track length.

1 m: PFP-100N
50 cm: PFP-50N
1 m: PFP-100N2
61F 61F

Connection with SE Motor Protective Relay


Prevents Burnouts in Motors and Pumps
Static relay for protection of motors and pumps against problems
due to overload, open phase, reverse phase, etc.
Applicable to all 61F-series Controllers except for 61F-I (indicator
model).

Connection Example (When Combined with 61F-G)


Power source
R S T
61F-G

Ta 0V Transformer
S0 61F-11N E1
24 V
Tc Relay Unit
S1 100 V
U E2
Tb 220 V 8V

S2
E3

Ground
Electromagnetic switch

Model SET-3 E1
current converter
+ Ta Tc Tb W E2
Model SE motor relay E3
-- C+ C-- U V
Water tank
61F 61F

Application Examples
• Level control in tanks, reservoirs, sewage plants, underground • Dispensing of liquids by volume.
wells, mixing plants etc.
• Indication of liquid buildup due to filter blockages.
• Level control for element protection in pipes, channels, and • Pollution/foul water detection for rivers, drains, etc.
irrigation systems.
• Flow detection in pipes, channels, and irrigation systems. • Alarm control warning of abnormal or dangerously high or low
levels.
• Ice bank control in cold drink dispensers, ice makers, water
chillers, bulk milk tanks, etc.

61F Selection Guidelines


• The limit of specific resistivity of a fluid controlled by the Table 2 Detectable Resistivity Ranges
general-purpose model at an immersion depth not exceeding
Model Resistivity (recommended
30 mm is 30 Ω-cm, using PS-3S Electrode Holders. Use the
values)
high-sensitivity models (H type) for liquids with higher resistivity
(see note 1). Refer to the resistivity values listed for water and Long-distance models (4 km) 5 kΩ S cm max.
other liquids in Table 1 and Table 3 when selecting the unit Long-distance models (2 km) 10 kΩ S cm max.
specification. The resistivity range detectable by the 61F is
shown in Table 2. Refer to the information on the units and the Low-sensitivity models 10 kΩ S cm max.
fluid to be controlled when selecting the appropriate model. 2-wire models 10 kΩ S cm max.
Note: 1. The high-sensitivity models may suffer from resetting General-purpose models 10 to 30 kΩ S cm
problems when used with certain types of water. In
some cases it cannot substitute for the general-purpose High-temperature models 10 to 30 kΩ S cm
models or low-sensitivity models. Be sure to select the High-sensitivity models 30 to 200 kΩ S cm
model appropriate for the application. (compact plug-in models)
2. The circuit configuration of the 61F-jH high-sensitivity High-sensitivity models 30 to 300 kΩ S cm
model is designed so that the relay de-energizes when (standard models)
there is water present across the Electrodes. When
power supply voltage is applied, the internal relay turns Ultra High-sensitivity models 100 to 10 kΩ S cm
to the NO contact and, when the electrode between E1 Note: The specific resistivity ranges of fluids to be controlled are
and E3 becomes conductive, the relay is reset to the NC given for the PS-3S at an immersion depth not exceeding
contact. This contact operation is reverse for models 30 mm.
other than the high-sensitivity models. Although the in-
ternal relay operates (and operation indicator turns ON) Table 1A Conductance Values of Water
simply when the power supply voltage is applied, this
operation is not abnormal. (The relay in the 61F-jNH Water type Conductance
energizes when there is water present across the Elec- City water 100 to 200 µS/cm
trodes.)
Well water 200 to 500 µS/cm
! Caution River water 67 to 200 µS/cm
In case of the 61F-HSL ultra high-sensitivity variable model, Rain water 40 to 67 µS/cm
malfunction due to electric corrosion may occur in the DC elec-
trode circuit. Be careful not to use the product in such a way Sea water 33,300 µS/cm
where current constantly flows between electrodes. Sewage 500 to 2,000 µS/cm
Distilled water 3.3 to 4 µS/cm max.
Table 1 Water Resistivity Values
(Japanese Reference Values)
Water type Resistivity
City water 5 to 10 kΩ S cm
Well water 2 to 5 kΩ S cm
River water 5 to 15 kΩ S cm
Rain water 15 to 25 kΩ S cm
Sea water 0.03 kΩ S cm
Sewage 0.5 to 2 kΩ S cm
Distilled water 250 to 300 kΩ S cm min.
61F 61F

Precautions
! WARNING Consider the Response Times
Never touch any of the terminals. Doing so may result in elec- The 61F requires a response time not exceeding 80 ms for opera-
tric shock. tion or 160 ms for reset. Take these response times into account in
cases where precise sequence control is required.
Never attempt to disassemble the 61F or touch the inside of
the 61F while the power is being supplied. Doing so may result Consider the Liquids to Be Controlled
in electric shock. The 61F cannot be used for any liquid that has almost no conductiv-
ity such as sewage containing oil.
The 61F cannot be used for any flammable liquid such as gasoline,
Correct Use kerosene, or heavy oil.
Use a Power Supply with Minimal Voltage Fluc- Do Not Share Electrodes
tuation
Do not connect a single Electrode to more than one 61F. If the
Avoid connection to a power supply with a voltage fluctuation great- phases of the 8-VAC Electrode-circuit power supplies are opposite
er than or equal to +10% or --15%. to each other, as shown in Fig. 1, an internal close circuit (return cir-
Consider the Ambient Temperature cuit) is created (indicated by the arrows). The 61F may malfunction
Do not install the 61F where it may be exposed to a temperature of regardless of the liquid level when the 61F power is turned ON. This
55°C or more and a humidity of 85% or more. In particular, install the problem can be overcome by matching the power supply phases, as
61F away from heat-generating equipment incorporating coils or shown in Fig. 2, but in this configuration the internal impedance of
windings. Also avoid locations subject to high humidity or corrosive the 61F calculated from the Electrode will be approximately half as
gases. large as the internal impedance of a single 61F. The same phenom-
enon can occur if multiple (not shared) Electrodes, connected to
Avoid Vibration and Shocks separate 61F units, are installed close together inside a single tank.
Do not subject the 61F to vibration or shocks which can cause chat- Maintain sufficient clearance between Electrodes connected to
tering problems. Do not install the 61F near contactors that gener- separate 61F units so that they do not interfere with each other.
ate severe shocks while the contactors are in operation. Common leads, however, can be connected to the ground Elec-
trode.
Do Not Test with a Megaohmmeter
During insulation resistance measurements, never apply the me- Fig. 1 Internal Closed Circuit
gaohmmeter across the Electrode terminals.
Use Self-holding Electrodes
Use Self-holding (E2) Electrodes when contactor open/close con-
trol is carried out. If E1 Electrodes are used, ripples on the liquid sur-
face can cause incorrect contactor operation and damage to the
contacts.
Be sure to turn OFF the power supply before replacing the plug-in 8 VAC
8 VAC
models.
Short Wiring in Electrode Circuit
Keep the wires connecting the 61F to Electrode Holders as short as
possible. If long leads are used, the floating capacity of the leads,
and abnormal surges or noise in the Electrode circuit can cause
malfunctions.
The thicker the cables, the shorter the permitted wiring length. The
length of the cable connecting the 61F and Electrode described in
the 61F datasheet will be available if a 600-V VCT0.75-mm2, 3-core
cabtire cable is used. Test results indicate that the actual wiring
length using VCT 3.5-mm2, 3-core cable laid over the ground is 50%
of the indicated length for general-purpose applications and 80% of Fig. 2 Match Phases
the indicated length for long-distance applications. When selecting T S R
the cable specification, remember that the wiring length is further
decreased for underground cables and larger diameter cables be-
61F
cause of the increased floating capacity with the ground.
Keep Power Cables Separate from the Electrode So S2
Circuit
Do not pass the leads for the Electrode circuit through the same
duct, or near to, high-tension cables or power cables. This can
cause noise which leads to malfunctions.
61F
Ground Correctly
Ground the common Electrode terminal to reduce the effects of So S2
noise.
Use a Surge Suppressor
Connect a 61F-03B(-04B) Surge Suppressor with the 61F Elec-
trode terminals to protect the circuit from surges. This is particularly
important in lightning-prone areas. To further improve protection,
install a commercial surge suppressor in the power supply to elimi-
nate surges in the power system.
61F 61F

Cautions on Electrodes Keep Electrodes Clean


Be sure to disconnect the 61F before conducting a insulation test on Lift the Electrodes and remove the surface film with fine sandpaper
the Electrode circuit for inspection purposes. about 6 months after installation. Subsequently, repeat this cleaning
once or twice per year.
When cutting an Electrode, be sure to chamfer cut surfaces of the
electrode. Cleaning is particularly important for Electrodes used in a liquid con-
taining large amounts of dirt or slime, which can build up into an in-
Maintain a Clearance Between Electrodes sulating film on the Electrode surface and cause malfunctions.
Maintain sufficient clearance (normally 1 m) between Electrodes in Clean the surface insulating film from Electrodes used in this envi-
sea water or contaminated water. Use the 61F-jD (or -jND) low- ronment once every three months. Use a pipe, as shown in the dia-
sensitivity models if this clearance is difficult to maintain. gram below in situations where the water contains large amounts of
dirt.
Use a pipe as shown to keep dirt and oil films from the Electrode in
situations where the liquid is highly contaminated with dirt and oil,
such as sewage holding tanks.

1m 1m PS-jS

Long Ground Electrode Approx. 10-dia. air vent hole

The Electrodes are mounted in sets of three. Connect the shortest


Electrode to E1, the medium Electrode to E2 and the longest Elec- 4 dia. min. pipe
trode to E3. The longest Electrode, E3, must be at least 50 mm long-
er than the other Electrodes.

E1 Thickness of contaminants
Bottom of tank collected between cleanings
E2 50 mm min.
E3
Use a pipe at least 4 inches in diameter.
Consider the Operating Level Cut off the end of the pipe at an angle to clear the estimated amount
of contaminants accumulating at the bottom of the tank.
Due to the liquid type and fluctuations in the power supply voltage,
the operating level may fluctuate to a small degree from the level at Drill an approximately 10-dia. vent hole at the top of the pipe.
which the liquid surface makes contact with the Electrode tip. Using an Anti-ripple Pipe:
Use an anti-ripple pipe as shown below in cases where large ripples
Use Separators are produced by a rapid fluid flow rate.
If the Electrode length reaches 1 m min., insert Separators at the
joint positions to prevent the Electrodes touching each other in the PS-jS
liquid.
Approx. 10-dia. air vent hole
4-dia. min. pipe
Electrode Holder

Drill at least four 6 to 10-dia. holes


as opposing pairs at the tip position
Separator of each Electrode.

Use a pipe at least 4 inches in diameter.


Take Care When Taping the Electrodes
When applying vinyl tape to the Electrodes to prevent them touching To improve liquid circulation inside the pipe, drill at least four 6 to
each other in the liquid, leave at least 100 mm at the end of the rod 10-dia. holes as opposing pairs at the tip position of each Electrode.
untaped. Do not tape to the very tip. Drill an approximately 10-dia. vent hole at the top of the pipe.
Follow the information above with regard to using Electrodes.
Cautions on Electrode Holders
Do not mount horizontally or a malfunction may occur.
BS and BF Electrode Holders
When installing the Electrodes, first tighten the connection nut with
Tape a wrench before tightening the Electrodes and lock nut. Tightening
100 mm the terminals or other parts can lead to damage of the insulating
parts due to tightening torque.
When mounting a BS-1 Electrode Holder to a boiler, wrap Teflon
tape 2 or 3 times around the mounting position and use the gasket
supplied.
Mount Electrodes Vertically Always apply the F03-11 Protective Cover if the BF-3 (-4 or -5) is
Install the Electrodes vertically to avoid the accumulation of slime used outside or in a position subject to water splashes or where dust
which can form an insulating layer on the Electrode surface. or dirt can settle. Foreign matter on the Electrode insulation can
cause electrical leakage and malfunctions.
61F 61F

Inspecting the Electrode Circuits Measuring the Resistance Between


In cases where the Electrodes cannot be withdrawn to test the Elec- Electrodes
trode circuit, a tester can be used to measure the resistance be- Measure the resistance between the Electrodes if the wiring is cor-
tween the Electrode and ground, as shown in the diagram below. rect but the 61F does not operate. Measure with a voltmeter using
The measured resistance value indicates the length, contact condi- the voltage drop method, as shown below.
tion, and mounting condition of the Electrode. For example, the se-
quence of Electrodes ordered from low measured resistance to high E1
is E3 (long), E2 (medium), and E1 (short).
Follow the guidelines below to use this test method. E3 mA

1. Detach the leads from the 61F.


V
2. Measure the conducting status with the tank full. (The water
level must be at E1 minimum.)
3. Measure the insulating status with the tank empty. (The water
level must be at E3 maximum.)
E1
E1 E2 E3
E3

Tester
Ground
mA An ammeter able to read approximately 1 mA
with as low an impedance as possible.
V A voltmeter able to read a value of several volts
with as high an impedance as possible.
E1 E2 E3

The resistance between Electrodes (resistance of liquid between


E1 and E3) is given by the following equation.
R = V/I
Where,
Tester
Ground
R: resistance of liquid between Electrodes (Ω)
V: voltmeter indicated voltage (V)
I: ammeter indicated current (mA)
Select the 61F model according to the R (resistance) value.
Inspecting the 61F-11N Relay Unit
Apply the specified power supply voltage with the Relay Units con-
nected to the 61F. Refer to the connection diagrams (internal wiring
diagrams) and short the 61F ground terminal to the operating termi-
nal of each Relay Unit. Check the operation of the relay output con-
tacts with a tester. With the 61F-11 models, the indicator will be lit
when the Relay Unit operates.
Water Leak Alarm/Detector 61F-WLA/-GPN-V50

Eliminate Problems Caused from Water


Leakage
0 to 50 kΩ variable operating resistance to detect
virtually any liquid.
Two types available: Water Leak Alarm (61F-WLA)
and plug-in Water Leak Detector (61F-GPN-V50).
24 VAC interelectrode voltage causes no electrolyt-
ic corrosion.
Suggested applications include computer room,
power plant, factory, library, warehouse, and
basement use.
Conforms to EMC/IEC Standards (61F-GPN-V50).
Approved by UL/CSA (61F-GPN-V50)
RC

Ordering Information
Water Leak Alarm 61F-WLA When ordering, to complete the part number, be sure to specify the
desired operating voltage.
Water Leak Detector 61F-GPN-V50
Example: 61F-WLA [120/240 VAC]
Desired supply voltage

Specifications
Ratings/Characteristics
Item Water Leak Alarm Water Leak Detector
Model 61F-WLA 61F-GPN-V50
Supply voltage 100/200, 110/220, 120/240 VAC 100, 110, 120, 200, 220, 240 VAC
Interelectrode voltage 24 VAC
Operating current 3 mA (AC) max.
Power consumption 8.0 VA max. 3.2 VA max.
Sensitivity Variable (0 to 50 kΩ)
Error (against the scale) Scale 0: 10 kΩ Scale 0: 10 kΩ
Scale 50: ±10 kΩ (see note 2) Scale 50: ±10 kΩ (see note 2)
Contact ratings 3 A 250 VAC, SPDT cosφ=1 3 A 250 VAC, DPDT cosφ=1
1 A 250 VAC, SPDT cosφ=0.4 1 A 250 VAC, DPDT cosφ=0.4
Indicator Provided (Power and Leak indicators) Provided (Operation indicator)
Alarm buzzer Provided Not provided
Test switch Provided Not provided
Ambient temperature --10°C to 55°C

Note: 1. For detecting leakage of water with high resistivity, use 61F-UHS or 61F-HSL ultra high-sensitivity models. (Refer to page 32.)
2. The Detector may not operate around the setting value of “0.” Adjust the sensitivity depending on the actual application.
61F-WLA/-GPN-V50 61F-WLA/-GPN-V50

Operation
Internal Circuit
61F-GPN-V50 Water Leak Detector

Rectifier/ Level
smoothing detector
24 VAC Amplifier
circuit switching
circuit

AC power source

Rectifier/
24 VAC smoothing Relay
circuit

Sensitivity
adjuster

Sensor cable

Operating Principle
When the two conductive cores of the Sensor Cable are contacted
by a liquid, a weak alternating current (as small as 3 mA max.) flows Core
across the cores. This current is amplified to operate a relay.
In practice, leakage will be detected if water drops are present be- Core
tween the core wire and the Electrode (F03-15 Sensor Cable) or de-
tecting section (F03-16 Sensor Cable). (Refer to the specifications Liquid
on page 70)
Sensor Cable Protective Cover
Item F03-25 F03-26
Appearance

Suggested use

Construction Adhesive
Adhesive

Comments Fixes the F03-15 Sensor Cable on the floor Fixes the F03-16 Sensor Cable on the floor
surface. Attach the sticker on a smooth surface. To surface. Attach the sticker on a smooth surface. To
attach it on a concrete floor, use a concrete attach it on a concrete floor, use a concrete
bonding agent. bonding agent.
61F-WLA/-GPN-V50 61F-WLA/-GPN-V50

Dimensions
Note: All units are in millimeters unless otherwise indicated.

61F-WLA Water Leak Alarm

Three, M5 or
6-dia. mount-
ing holes

61F-GPN-V50 Water Leak Detector

Accessories (Order Separately)


Connecting Sockets (for 61F-GPN-V50 Water Leak Detector)
PF113A-E Track-mounted Socket

Eleven, M3.5 x 5 Top view


sems screws

61F-
Two, M4 or 4.5 dia. holes
GPN-V50
52 max.

34±1

PF113A-E
31 max. PFC-N8 Holding
Bracket

PL11 Back-connecting Socket

Two, 3.5 dia. or M3


Two, 2 dia.
mounting holes
holes

61-
GPN-V50 Approx. 75
51 max.

31 dia. hole

35 max.
Approx. 20.5 PL11 Approx. 16

Important: Install the Water Leak Detector socket with the keyway facing down.

Sensor Cable
F03-15 Crimped electrode pair Stainless steel core
(0.3 x 12 braided)

Sheath: Transparent vinyl chloride Transparent vinyl chloride


Core: Stainless steel SUS304 333 mm
(3 electrode pairs per meter)

F03-16
Transparent vinyl chloride Detecting cutaway

Sheath: Transparent vinyl chloride


Core: Stainless steel SUS304
61F-WLA/-GPN-V50 61F-WLA/-GPN-V50

Installation
Connections
61F-WLA Water Leak Alarm 61F-GPN-V50 Water Leak Detector
Power
Fuse supply
LED Alarm LED
To Sensor
Rectifica- Cable
Level detec-
tion/ tion switch- Amplifica-
smoothing ing circuit tion circuit
circuit Alarm buzzer
Bottom view

Rectifica- AC power source


tion/
smoothing
circuit

Test switch

100, 110, 120 VAC


power source
200, 220, 240 VAC Sensor cable
power source

Precautions
Correct Use
(1) Use only F03-15 or F03-16 Sensor Cable. Other water conduc- (8) When measuring insulation resistance, do not conduct a meg-
tors may cause the Water Leak Alarm/Detector to malfunction, ger test between the electrode terminals.
or not operate at all because of mismatched sensitivity.
IV Cable Sensor Cable
(2) Place the Sensor Cable at a location where water leakage is
most likely to occur. For example, consider the following loca- 0m 200 m
tions: 10 to 150 m 150 m
• Under a raised floor; on the highest floor of a building; on the 200 to 300 m 100 m
ceiling
350 to 400 m 50 m
• In the vicinity of an air conditioner, or on the floor near a
humidifier Note: IV cable: 2 mm2
• On the floor near a feed-water pipe, conduit; hot-water pipe.
• On top of a power, or control panel
(3) Secure the Sensor Cable so that they touch the floor surface or
the wall near a pipe arrangement. Cover the Sensor Cable with
a F03-25 or F03-26 Protective Cover if they are installed at a
location crowed with people. However, place the cover such a
manner that water can easily reach the Sensor Cable.
(4) Keep the temperature at the installation site to within 55°C. Do
not install the Water Leak Alarm/Detector/Sensor cable in the
proximity of heat-generating equipment (such as that having a
coil or wire winding). Also, do not use it in a highly humid loca-
tion, or at a location that is subjected to corrosive gases. Do not
place the Water Leak Alarm/Detector side-by-side with a high-
capacity contactor that produces an inrush current when it oper-
ates, as such arrangement may cause chattering to occur, con-
sequently causing a malfunction of the Water Leak Alarm/De-
tector.
(5) Wiring distance of the Sensor Cable varies depending on the
water quality. When using IV cables, wire the Sensor Cable to
the length specified in the following table.
(6) Mount the 61F-WLA Water Leak Alarm/Detector on a sturdy
wall surface which is not subjected to vibration or shock. Do not
use double-sided adhesive tape, otherwise, the Detector may
detach when the adhesive tape deteriorates due to aging.
(7) When wiring the Sensor on conductive objects like metal
objects, use the F03-16.
61F-WLA/-GPN-V50 61F-WLA/-GPN-V50

NOTE: DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters to inches divide by 25.4.

R
OMRON ELECTRONICS LLC OMRON ON--LINE OMRON CANADA, INC.
One East Commerce Drive Global -- http://www.omron.com 885 Milner Avenue
Schaumburg, IL 60173 USA -- http://www.omron.com/oei Toronto, Ontario M1B 5V8
1-800-55-OMRON Canada -- http://www.omron.com/oci 416-286-6465

Cat. No. F030-E1-8 Specifications subect to change without notice Printed in U.S.A.

You might also like