Feeder Protection and Control REF630: Product Guide
Feeder Protection and Control REF630: Product Guide
Contents
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors
that may appear in this document.
© Copyright 2019 ABB.
All rights reserved.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks
of their respective holders.
2 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3 Issued: 2019-02-25
Revision: H
1. Description 2. Application
REF630 is a comprehensive feeder management relay for REF630 provides main protection for overhead lines and cable
protection, control, measuring and supervision of utility and feeders of distribution networks. The protection relay fits both
industrial distribution substations. REF630 is a member of isolated neutral networks and networks with resistance or
ABB’s Relion ® product family and a part of its 630 series impedance earthed neutral. Four pre-defined configurations to
characterized by functional scalability and flexible match typical feeder protection and control requirements are
configurability. REF630 also features necessary control available. The pre-defined configurations can be used as such
functions constituting an ideal solution for feeder bay control. or easily adapted or extended with freely selectable add-on
functions, by means of which the protection relay can be fine-
The supported communication protocols including IEC 61850 tuned to exactly satisfy the specific requirements of your
offer seamless connectivity to industrial automation systems. present application.
ABB 3
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
REF630
Preconf. n
Io ANSI IEC
27 3U<
Uo 51BF/51NBF 3I>/Io>BF
3U 51N-1/51N-2 Io>/Io>>
3I 59 3U>
67-1 3I>→
Bus A
Bus B
3U 3U
Uo Uo
3I 3I 3I 3I
Io Io Io Io
21FL FLOC 47O-/59 U2>/3U> 47O-/59 U2>/3U> 21FL FLOC 21FL FLOC 21FL FLOC
46 I2> 47U+/27 U1</3U< 47U+/27 U1</3U< 46 I2> 46 I2> 46 I2>
46PD I2/I1> 59G Uo> 59G Uo> 46PD I2/I1> 46PD I2/I1> 46PD I2/I1>
49F 3Ith>F 81O/81U/81R f</f>/ df/dt 81O/81U/81R f</f>/ df/dt 49F 3Ith>F 49F 3Ith>F 49F 3Ith>F
50N/51N 3Io>>> 50N/51N 3Io>>> 50N/51N 3Io>>> 50N/51N 3Io>>>
50P/51P 3I>>> 50P/51P 3I>>> 50P/51P 3I>>> 50P/51P 3I>>>
51BF/51NBF 3I>/Io>BF 51BF/51NBF 3I>/Io>BF 51BF/51NBF 3I>/Io>BF 51BF/51NBF 3I>/Io>BF
51N-1/51N-2 Io>/Io>> 51N-1/51N-2 Io>/Io>> 51N-1/51N-2 Io>/Io>> 51N-1/51N-2 Io>/Io>>
51P-1/51P-2 3I>/3I>> 51P-1/51P-2 3I>/3I>> 51P-1/51P-2 3I>/3I>> 51P-1/51P-2 3I>/3I>>
60 FUSEF 60 FUSEF 60 FUSEF 60 FUSEF
67N-1 Io>→ 67N-1 Io>→ 67N-1 Io>→ 67N-1 Io>→
68 3I2f> 68 3I2f> 68 3I2f> 68 3I2f>
79 O→I 79 O→I
GUID-2D5D5EDF-BA34-4545-8116-7D4BAB6EFC27 V1 EN
Figure 1. Application example with double busbar switchgear arrangement with one incoming feeder and several outgoing feeders for
overhead line and cable feeders in preconfiguration n
4 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
REF630
Preconf. n
Io ANSI IEC
47O-/59 U2>/3U>
47U+/27 U1</3U<
Uo
51BF/51NBF 3I>/Io>BF
3U 59G Uo>
3I
67-1/67-2 3I>→/3I>>→
81O f>
81LSH UFLS/R
Bus A
Bus B
3I 3I 3I 3I
Io 3U Uo Io 3U Uo Io 3U Uo Io 3U Uo
GUID-E52499B7-DF0A-46D4-B120-97203A34F91A V1 EN
Figure 2. Application example in double busbar, also so called back 2 back, switchgear arrangement with dedicated voltage measurement in
each feeder
ABB 5
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
REF620
Preconf. C
ANSI IEC
27 3U<
51BF/51NBF 3I>/Io>BF
Io 51N-1/51N-2 Io>/Io>>
67-1 3I>→
59 3U>
81O/81U/81R f</f>/ df/dt
Uo
3U
3I
Bus A
Bus B
2U
2U
3I 3I 3I 3I 3I
Io 3U Uo Io 3U Uo Io 3U Uo Io 3U Uo
21, 21P, 21N Z< 21, 21P, 21N Z< 21, 21P, 21N Z< 21, 21P, 21N Z< 25 SYNC
27/59 3U</3U> 27/59 3U</3U> 27/59 3U</3U> 27/59 3U</3U> 47O-/59 U2>/3U>
46 I2> 46 I2> 46 I2> 46 I2> 47U+/27 U1</3U<
46PD I2/I1> 46PD I2/I1> 46PD I2/I1> 46PD I2/I1> 50P/51P 3I>>>
49F 3Ith>F 49F 3Ith>F 49F 3Ith>F 49F 3Ith>F 51BF/51NBF 3I>/Io>BF
50N/51N 3Io>>> 50N/51N 3Io>>> 50N/51N 3Io>>> 50N/51N 3Io>>> 51P-1/51P-2 3I>/3I>>
50P/51P 3I>>> 50P/51P 3I>>> 50P/51P 3I>>> 50P/51P 3I>>>
51BF/51NBF 3I>/Io>BF 51BF/51NBF 3I>/Io>BF 51BF/51NBF 3I>/Io>BF 51BF/51NBF 3I>/Io>BF
51N-1/51N-2 Io>/Io>> 51N-1/51N-2 Io>/Io>> 51N-1/51N-2 Io>/Io>> 51N-1/51N-2 Io>/Io>>
51P-1/51P-2 3I>/3I>> 51P-1/51P-2 3I>/3I>> 51P-1/51P-2 3I>/3I>> 51P-1/51P-2 3I>/3I>>
59G Uo> 59G Uo> 59G Uo> 59G Uo>
60 FUSEF 60 FUSEF 60 FUSEF 60 FUSEF
67N-1/67N-2 Io>→/Io>>→ 67N-1/67N-2 Io>→/Io>>→ 67N-1/67N-2 Io>→/Io>>→ 67N-1/67N-2 Io>→/Io>>→
68 3I2f> 68 3I2f> 68 3I2f> 68 3I2f>
79 O→I 79 O→I 79 O→I 79 O→I
SOFT SOFT SOFT SOFT SOFT SOFT SOFT SOFT
GUID-05EAB48E-56BE-4C20-98D5-24A5643A175B V1 EN
Figure 3. Application example in double busbar arrangement, most typical, for gas insulated switchgear with 3 position disconnector and
voltage measurement in each feeder
The bus sectionalizer with also independent voltage sections. Preconfiguration C with its distance protection is
measurement on both busbars allows switchgear operation preconfigured for ring and meshed type feeders.
while maintenance works are required on one of the busbar
6 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
REF630 REF630
Preconf. n Preconf. n
Io ANSI IEC Io ANSI IEC
25 SYNC 25 SYNC
3U 47O-/59 U2>/3U> 3U 47O-/59 U2>/3U>
Uo 47U+/27 U1</3U< Uo 47U+/27 U1</3U<
50P/51P 3I>>> 50P/51P 3I>>>
3I 3I
51BF/51NBF 3I>/Io>BF 51BF/51NBF 3I>/Io>BF
51P-1/51P-2 3I>/3I>> 51P-1/51P-2 3I>/3I>>
59G Uo> 59G Uo>
67-1 3I>→ 67-1 3I>→
3I 3I 3I 3I
3U Uo 3U Uo
Io Io Io
GUID-D1305B07-E9C9-4353-A69F-253D93273E7D V1 EN
Figure 4. Application example with single busbar switchgear arranged into two bus sections separated with bus coupler
High impedance earthed network with preconfigurations N and functionality is used to prevent unsynchronized connection of
directional overcurrent and directional earth-fault functions are two separate networks into each other.
used. In incoming feeders and bus coupler the synchrocheck
ABB 7
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
8 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
UL1UL2UL3
Uo
2× AND
3I OR
I2> I2/I1> 3Ith>F 3I>>>
46 46PD 49F 50P/51P *) Fixed or detached LHMI is available.
1× 1× 2×
3I>/Io>BF 3I> 3I>>
CONDITION MONITORING COMMUNICATION
51BF/51NBF 51P-1 51P-2
AND SUPERVISION
Protocols: 1 0 1 0 0 0 1 1 0 0 1 1 0 0
2× 1× 1× 1× 1× IEC 61850-8-1 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
3I>→ 3I>>→ 3I2f> FUSEF CBCM E IEC 60870-5-103 1 1 0 0 1 1 1 0 1 1 0 1 0
67-1 67-2 68 60 CBCM E DNP3 1 0 1 1 0 1 1 0 1 1 0 1 0 0
1 0 1 0 0 0 1 1 0 0 1 1 0 0 1 0 1
1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
Interfaces: 1 1 0 0 1 1 1 0 1 1 0 1 0
UL1UL2UL3 1× 1× 3×
Ethernet: TX (RJ45),
1 0FX1(LC)
1 0 1 1 0 1 1 0 1 0 0
MCS 3I OPTS TCS
Serial: Serial glass fiber (ST),
MCS 3I OPTM TCM
Serial plastic fiber
(snap-in connector)
Io 2× 1×
Io>> Io>→ Io>→ Io>→IEF U<>
51N-2 67N-1 67N-2 67NIEF U<>
Uo
CONTROL AND INDICATION 1) MEASUREMENT
3×
Z< FLOC Yo>→ Object Ctrl 2) - I, U, Io, Uo, P, Q, E, pf, f
21, 21P, 21N 21FL 21YN - Symmetrical components
CB 2 - Limit value supervision
3× 3× DC
3U< Po>→ 8
Q>→, 3U< ES Analog interface types B
27 32N 32Q, 27
1)
Check availability of binary inputs/outputs Current transformer 51)
from technical documentation
3× 2× 2× 2× 2)
Control and indication function for Voltage transformer 4
P> U2> U1> U1< primary object
1)
One of available current transformer
32R/32O 47O- 47O+ 47U+ inputs is sensitive (0.1 / 0.5 A)
3× 1× 1×
Io>>> Io> Io>HA 3U> O→I SYNC PQM3I PQM3Upe
50N/51N 51N-1 51NHA 59 79 25 PQM3I PQM3Vpg
3× 6× 5×
Uo> Io>→Y UFLS/R f> PQM3Upp
59G 67YN 81LSH 81O PQM3Vpp
5× 5× 16× 2×
df/dt> f< MAP SOTF PQMUBU PQMU
81R 81U MAP SOTF PQMUBV PQMV
REMARKS
Optional 2× No. of instances
function enabled by default
GUID-973EE09F-BEFA-40C3-AAEE-FB97B84EAA52 V1 EN
ABB 9
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
UL1UL2UL3
Uo
2× AND
3I OR
I2> I2/I1> 3Ith>F 3I>>>
46 46PD 49F 50P/51P *) Fixed or detached LHMI is available.
1× 1× 2×
3I>/Io>BF 3I> 3I>>
CONDITION MONITORING COMMUNICATION
51BF/51NBF 51P-1 51P-2
AND SUPERVISION
Protocols: 1 0 1 0 0 0 1 1 0 0 1 1 0 0
1× 1× 1× 1× IEC 61850-8-1 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
3I2f> FUSEF CBCM E IEC 60870-5-103 1 1 0 0 1 1 1 0 1 1 0 1 0
68 60 CBCM E DNP3 1 0 1 1 0 1 1 0 1 1 0 1 0 0
1 0 1 0 0 0 1 1 0 0 1 1 0 0 1 0 1 0 0
1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
Interfaces: 1 1 0 0 1 1 1 0 1 1 0 1 0
UL1UL2UL3 1× 1× 3×
Ethernet: TX (RJ45),
1 0FX1(LC)
1 0 1 1 0 1 1 0 1 0 0
MCS 3I OPTS TCS
Serial: Serial glass fiber (ST),
MCS 3I OPTM TCM
Serial plastic fiber
(snap-in connector)
Io 1× 2×
Io>>> Io> Io>> Io>→ U<>
50N/51N 51N-1 51N-2 67N-1 U<>
Uo
CONTROL AND INDICATION 1) MEASUREMENT
3×
Z< FLOC Yo>→ Object Ctrl 2) - I, U, Io, Uo, P, Q, E, pf, f
21, 21P, 21N 21FL 21YN - Symmetrical components
CB 2 - Limit value supervision
3× 3× DC
8
3U< Po>→ Q>→, 3U< ES Analog interface types B
27 32N 32Q, 27 1)
Check availability of binary inputs/outputs Current transformer 51)
from technical documentation
3× 2× 2× 2× 2)
Control and indication function for Voltage transformer 4
P> U2> U1> U1< primary object
1)
One of available current transformer
32R/32O 47O- 47O+ 47U+ inputs is sensitive (0.1 / 0.5 A)
3× 3× 2× 1× 1×
Io>HA 3U> Uo> 3I>→ O→I SYNC PQM3I PQM3Upe
51NHA 59 59G 67-1 79 25 PQM3I PQM3Vpg
6× 5× 5× 5×
UFLS/R f> df/dt> f< PQMUBU PQMU
81LSH 81O 81R 81U PQMUBV PQMV
16× 2×
MAP SOTF
MAP SOTF
REMARKS
Optional 2× No. of instances
function enabled by default
GUID-041037E1-4C3F-4F83-BFFB-995BA916B55B V1 EN
10 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
UL1UL2UL3
Uo
3I 2× AND
Z< I2> I2/I1> OR
21, 21P, 21N 46 46PD *) Fixed or detached LHMI is available.
1× 1×
3Ith>F 3I>>> 3I>/Io>BF
CONDITION MONITORING COMMUNICATION
49F 50P/51P 51BF/51NBF
AND SUPERVISION
Protocols: 1 0 1 0 0 0 1 1 0 0 1 1 0 0
2× 1× 1× 1× 1× IEC 61850-8-1 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
3I> 3I>> 3I2f> FUSEF CBCM E IEC 60870-5-103 1 1 0 0 1 1 1 0 1 1 0 1 0
51P-1 51P-2 68 60 CBCM E DNP3 1 0 1 1 0 1 1 0 1 1 0 1 0 0
1 0 1 0 0 0 1 1 0 0 1 1 0 0 1 0 1
1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
Interfaces: 1 1 0 0 1 1 1 0 1 1 0 1 0
UL1UL2UL3 1× 1× 3×
Ethernet: TX (RJ45),
1 0FX1(LC)
1 0 1 1 0 1 1 0 1 0 0
MCS 3I OPTS TCS
Serial: Serial glass fiber (ST),
MCS 3I OPTM TCM
Serial plastic fiber
(snap-in connector)
3×
Io
Io>> Io>→ Io>→ U<>
51N-2 67N-1 67N-2 U<>
Uo
CONTROL AND INDICATION 1) MEASUREMENT
3× 3× 1× 1×
FLOC Yo>→ Po>→ O→I SYNC PQM3I PQM3Upe
21FL 21YN 32N 79 25 PQM3I PQM3Vpg
3× 2×
Q>→, 3U< P> U2> PQM3Upp
32Q, 27 32R/32O 47O- PQM3Vpp
2× 2×
U1> U1< Io>>> Io> PQMUBU PQMU
47O+ 47U+ 50N/51N 51N-1 PQMUBV PQMV
2×
Io>HA 3I>→ 3I>>→ Io>→IEF
51NHA 67-1 67-2 67NIEF
REMARKS
6× 5× 5× Optional 2× No. of instances
Io>→Y UFLS/R f> df/dt> function enabled by default
67YN 81LSH 81O 81R
GUID-A5805D15-8663-4995-B76C-A21248C18FBF V1 EN
ABB 11
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
2× 1× 1× AND
3I OR
I2> 3I>>> 3I>/Io>BF
46 50P/51P 51BF/51NBF *) Fixed or detached LHMI is available.
2×
3I> 3I>> 3I2f>
CONDITION MONITORING COMMUNICATION
51P-1 51P-2 68
AND SUPERVISION
Protocols: 1 0 1 0 0 0 1 1 0 0 1 1 0 0
2× 1× 1× IEC 61850-8-1 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
Io FUSEF CBCM E IEC 60870-5-103 1 1 0 0 1 1 1 0 1 1 0 1 0
60 CBCM E DNP3 1 0 1 1 0 1 1 0 1 1 0 1 0 0
1 0 1 0 0 0 1 1 0 0 1 1 0 0 1 0 1 0 0
1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
Interfaces: 1 1 0 0 1 1 1 0 1 1 0 1 0
2× 3×
Ethernet: TX (RJ45),
1 0FX1(LC)
1 0 1 1 0 1 1 0 1 0 0
Io>>> Io> Io>> MCS 3I OPTS TCS
Serial: Serial glass fiber (ST),
50N/51N 51N-1 51N-2 MCS 3I OPTM TCM
Serial plastic fiber
(snap-in connector)
U<>
U<>
3×
Z< FLOC Yo>→
21, 21P, 21N 21FL 21YN
CONTROL AND INDICATION 1) MEASUREMENT
3× 3×
3U< Po>→ Q>→, 3U< Object Ctrl 2) - I, U, Io, Uo, P, Q, E, pf, f
27 32N 32Q, 27 - Symmetrical components
CB 2 - Limit value supervision
3× 2× 2× DC
8
P> I2/I1> U2> U1> ES Analog interface types B
32R/32O 46PD 47O- 47O+ 1)
Check availability of binary inputs/outputs Current transformer 51)
from technical documentation
2× 3× 2)
Control and indication function for Voltage transformer 4
U1< 3Ith>F Io>HA 3U> primary object 1)
One of available current transformer
47U+ 49F 51NHA 59 inputs is sensitive (0.1 / 0.5 A)
3× 2× 3× 2×
Uo> 3I>→ 3I>>→ Io>→ O→I SYNC PQM3I PQM3Upe
59G 67-1 67-2 67N-1 79 25 PQM3I PQM3Vpg
6×
Io>→ Io>→IEF Io>→Y UFLS/R PQM3Upp
67N-2 67NIEF 67YN 81LSH PQM3Vpp
5× 5× 5× 16×
f> df/dt> f< MAP PQMUBU PQMU
81O 81R 81U MAP PQMUBV PQMV
2×
SOTF
SOTF REMARKS
GUID-46E0483B-5329-418D-944B-5F75F073A12E V1 EN
12 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
UL1UL2UL3
Uo
3× 3× 2× AND
3I
Po>→ Q>→, 3U< P> I2> OR
32N 32Q, 27 32R/32O 46 *) Fixed or detached LHMI is available.
2× 2× 2×
I2/I1> U2> U1> U1< 3Ith>F
CONDITION MONITORING COMMUNICATION
46PD 47O- 47O+ 47U+ 49F
AND SUPERVISION
Protocols: 1 0 1 0 0 0 1 1 0 0 1 1 0 0
2× 2× 2× IEC 61850-8-1 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
Io>>> 3I>>> 3I>/Io>BF Io> FUSEF CBCM E IEC 60870-5-103 1 1 0 0 1 1 1 0 1 1 0 1 0
1 0 1 1 0 1 1 0 1 1 0 1 0 0
50N/51N 50P/51P 51BF/51NBF 51N-1 60 CBCM E DNP3 1 0 1 0 0 0 1 1 0 0 1 1 0 0 1 0
U12 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
Interfaces: 1 1 0 0 1 1 1 0 1 1 0 1 0
2× 3× 2× 3×
Ethernet: TX (RJ45),1 0 1(LC)
FX 1 0 1 1 0 1 1 0 1 0 0
Io>> Io>HA 3I> 3I>> 3U> MCS 3I OPTS TCS
Serial: Serial glass fiber (ST),
51N-2 51NHA 51P-1 51P-2 59 MCS 3I OPTM TCM
Serial plastic fiber
(snap-in connector)
3× 2× 3×
Uo> 3I>→ 3I>>→ Io>→ Io>→ U<>
Io 59G 67-1 67-2 67N-1 67N-2 U<>
6× 5×
Io>→IEF Io>→Y 3I2f> UFLS/R f>
67NIEF 67YN 68 81LSH 81O CONTROL AND INDICATION 1) MEASUREMENT
2×
O→I SYNC PQM3I PQM3Upe
79 25 PQM3I PQM3Vpg
PQM3Upp
PQM3Vpp
PQMUBU PQMU
PQMUBV PQMV
REMARKS
Optional 3× Total nr. of
function instances
GUID-6BE6503A-F28B-43F9-8195-385F14F3A45D V1 EN
Description Preconfiguration
ABB 13
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Description A B C D n
Protection
Distance protection - - 1 - 1
Fault locator - - - - 1
Autoreclosing 1 1 1 - 2
Overfrequency protection - - - - 5
Underfrequency protection - - - - 5
Load shedding - - - - 6
14 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Tripping logic 1 1 1 1 2
Protection-related functions
Control
Bay control 1 1 1 1 1
Interlocking interface 4 4 4 1 10
Circuit breaker 1 1 1 1 2
Disconnector 3 3 3 - 8
Synchrocheck - - - - 1
Event counter - - - - 1
Trip-circuit supervision 3 3 3 3 3
Energy monitoring - - - - 1
Power quality
Voltage variation - - - - 1
Voltage unbalance - - - - 1
Current harmonics - - - - 1
ABB 15
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Measurement
Binary receive - - - - 10
Interlock receive - - - - 59
Integer receive - - - - 32
16 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
ABB 17
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
18 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
The monitoring functions provide operational circuit breaker 18. Inputs and outputs
history data, which can be used for scheduling preventive Depending on the hardware configuration selected, the
circuit-breaker maintenance. protection relay is equipped with three phase-current inputs
and one or two residual-current inputs for earth-fault
protection. The protection relay always includes one residual
13. Trip-circuit supervision
voltage input for directional earth-fault protection or residual
The trip-circuit supervision continuously monitors the
voltage protection. Further, the protection relay includes three
availability and operability of the trip circuit. It provides open-
phase-voltage inputs for overvoltage, undervoltage and
circuit monitoring both when the circuit breaker is in its closed
directional overcurrent protection and other voltage based
and in its open position. It also detects loss of circuit-breaker
protection functions. Depending on the hardware
control voltage.
configuration, the protection relay also includes a dedicated
voltage input for synchrocheck.
14. Self-supervision
The relay’s built-in self-supervision system continuously The phase-current inputs are rated 1/5 A. The protection relay
monitors the state of the relay hardware and the operation of is equipped with one or two alternative residual-current inputs,
the relay software. Any fault or malfunction detected is used for that is 1/5 A or 0.1/0.5 A. The 0.1/0.5 A input is normally used in
alerting the operator. applications requiring sensitive earth-fault protection and
featuring a core-balance current transformer.
Self-supervision events are saved into an internal event list
which can be accessed locally via the user interface on the The three phase-voltage inputs, for either phase-to-phase
protection relay's front panel. The event list can also be voltages or phase-to-earth voltages, and the residual-voltage
accessed using the Web HMI or PCM600. input cover the rated voltages 100 V, 110 V, 115 V and 120 V.
The rated values of the current and voltage inputs are selected
in the relay software.
15. Fuse failure supervision
The fuse failure supervision detects failures between the In addition, the binary input thresholds are selected by
voltage measurement circuit and the relay. The failures are adjusting the protection relay’s parameter settings. The
detected either by the negative sequence-based algorithm or threshold voltage can be set separately for each binary input.
by the delta voltage and delta current algorithm. Upon the
detection of a failure, the fuse failure supervision function The optional RTD/mA module facilitates the measurement of up
activates an alarm and blocks voltage-dependent protection to eight analog signals via the RTD/mA inputs and provides four
functions from unintended operation. mA outputs. With RTD sensors the RTD/mA inputs can for
instance be used for temperature measurement stator
windings, thus extending the functionality of the thermal
16. Current circuit supervision overload protection and preventing premature aging of the
Current circuit supervision is used for detecting faults in the windings. Furthermore, the RTD/mA inputs can be used for
current transformer secondary circuits. On detecting of a fault measuring the ambient air or cooling media temperature, or
the current circuit supervision function can also activate an bearing temperatures. The RTD/mA inputs can be used for
alarm LED and block certain protection functions to avoid supervision of analog mA signals provided by external
unintended operation. The current circuit supervision function transducers. The RTD/mA inputs can be alternatively used also
calculates the sum of the phase currents and compares the as resistance input or as an input for voltage transducer. The
sum with the measured single reference current from a core RTD/mA module enables the use of the multipurpose analog
balance current transformer or from another set of phase protection functions. These protection functions can be used
current transformers. for tripping and alarm purposes based on RTD/mA measuring
data, or analog values communicated via GOOSE messaging.
17. Access control The mA outputs can be used for transferring freely selectable
To protect the protection relay from unauthorized access and to measured or calculated analog values to devices provided with
maintain information integrity, the protection relay is provided mA input capabilities.
with an authentication system including user management.
The enhanced scalability of the 6U variant protection relays are
Using the IED User Management tool in the Protection and
intended for optimized medium voltage metal-clad switchgear
Control IED Manager PCM600, an individual password is
applications where additional binary inputs and outputs are
assigned to each user by the administrator. Further, the user
often required.
name is associated to one or more of the four available user
groups: System Operator, Protection Engineer, Design All binary input and output contacts are freely configurable
Engineer and User Administrator. The user group association using the signal matrix of the application configuration function
for each individual user enables the use of theprotection relay in PCM600.
according to the profile of the user group.
ABB 19
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
AA 4 - 5 - -
AB 4 1 4 - -
AC 3 1 5 - -
BA 4 - 5 8 4
BB 4 1 4 8 4
BC 3 1 5 8 4
Default AA 14 9
Default AA 14 9
19. Communication substations, as defined by the IEC 61850 standard. Further, the
The protection relay supports the IEC 61850 substation protection relay supports the sending and receiving of analog
automation standard including horizontal GOOSE values using GOOSE messaging. Analog GOOSE messaging
communication as well as the well-established DNP3 (TCP/IP) enables fast transfer of analog measurement values over the
and IEC 60870-5-103 protocols. All operational information station bus, thus facilitating for example sharing of RTD input
and controls are available through these protocols. values, such as surrounding temperature values, to other relay
applications. Analog GOOSE messages can also be used in
Disturbance files are accessed using the IEC 61850 or IEC load shedding applications. The protection relay interoperates
60870-5-103 protocols. Disturbance files are also available to with other IEC 61850 compliant devices, tools and systems and
any Ethernet based application in the standard COMTRADE simultaneously reports events to five different clients on the IEC
format. The protection relay can send binary signals to other 61850 station bus. For a system using DNP3 over TCP/IP,
protection relays (so called horizontal communication) using the events can be sent to four different masters. For systems using
IEC 61850-8-1 GOOSE (Generic Object Oriented Substation IEC 60870-5-103, the protection relay can be connected to one
Event) profile. Binary GOOSE messaging can, for example, be master in a station bus with star-topology.
employed for protection and interlocking-based protection
schemes. The protection relay meets the GOOSE performance All communication connectors, except for the front port
requirements for tripping applications in distribution connector, are placed on integrated communication modules.
20 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
IEC 60870-5-103 is available from optical serial port where it is With special time synchronization wiring
possible to use serial glass fibre (ST connector) or serial plastic • IRIG-B (Inter-Range Instrumentation Group - Time Code
fibre (snap-in connector). Format B)
IEC 61850 ● ●
DNP3 ● ●
IEC 60870-5-103 ● ●
● = Supported
1) Please refer to the Selection and ordering data chapter for more information
ABB 21
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Table 7. Dimensions
Description Value
Width 220 mm
Depth 249.5 mm
1) Without LHMI
Uauxnominal 100, 110, 120, 220, 240 V AC, 50 and 60 Hz 48, 60, 110, 125 V DC
Ripple in the DC auxiliary voltage Max 15% of the DC value (at frequency of 100 Hz)
Power supply input must be protected by an For example, type S282 UC-K.
external miniature circuit breaker The rated maximum load of aux voltage which is given as 35 watts. Depending on the voltage
used, select a suitable MCB based on the respective current. Type S282 UC-K has a rated
current of 0.75 A at 400 V AC.
22 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Description Value
• Continuously 4A 20 A
• For 10 s 25 A 100 A
Voltage inputs Rated voltage, Un 100 V AC/ 110 V AC/ 115 V AC/ 120 V AC
Voltage withstand:
• Continuous 425 V AC
• For 10 s 450 V AC
1) Residual current
2) Phase currents or residual current
Description Value
Ripple in the DC auxiliary voltage Max 15% of the DC value (at frequency of 100 Hz)
ABB 23
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Description Value
RTD inputs Supported RTD sensor 100 Ω platinum TCR 0.00385 (DIN 43760)
Operation accuracy ±0.1% ±20 ppm per °C of full-scale Ambient temperature -40°C...
70°C
Operation accuracy ±0.1% ±40 ppm per °C of full-scale Ambient temperature -40°C...
70°C
24 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Description Value
Breaking capacity when the control-circuit time constant L/R<40 ms, at U ≤0.5 A/≤0.1 A/≤0.04 A
< 48/110/220 V DC
Description Value
Breaking capacity when the control-circuit time constant L/R<40 ms, at ≤1 A/≤0.3 A/≤0.1 A
U< 48/110/220 V DC
Description Value
Breaking capacity when the control-circuit time constant L/R<40 ms, at U ≤1 A/≤0.3 A/≤0.1 A
< 48/110/220 V DC
Description Value
Isolation level 4 kV
ABB 25
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Screw terminal, pin row header IRIG-B Shielded twisted pair cable
Recommended: CAT 5, Belden RS-485 (9841- 9844) or Alpha Wire
(Alpha 6222-6230)
660 mm 1 mm Snap-in 10 m
Description Value
Front side IP 40
Description Value
Description Value
Altitude up to 2000 m
26 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
ABB 27
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
100 kHz and 1 MHz burst disturbance test IEC 61000-4-18, level 3
IEC 60255-22-1
• Contact discharge 8 kV
• Air discharge 15 kV
• Conducted, common mode 10 V (rms), f=150 kHz...80 MHz IEC 61000-4-6 , level 3
IEC 60255-22-6
• All ports 4 kV
• Communication 1 kV line-to-earth
• 2s 100 A/m
Power frequency immunity test Binary inputs only IEC 60255-22-7, class A
IEC 61000-4-16
28 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
• Radiated RF-emission
• Resistance <0.1Ω, 4 A, 60 s
ABB 29
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Description Reference
LV directive 2006/95/EC
Description Reference
Description
30 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Protection functions
Characteristic Value
PHHPTOC:
IFault = 2 × set Start value Typically 19 ms (±5 ms)
PHLPTOC:
IFault = 2 × set Start value Typically 23 ms (±15 ms)
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)
1) Set Operate delay time = 0.02 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 × In , fn = 50 Hz, fault current in one phase
with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Includes the delay of the heavy-duty output contact
ABB 31
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
32 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Characteristic Value
DPHLPDOC Current:
±1.5% of the set value or ±0.002 × In
Voltage:
±1.5% of the set value or ±0.002 × Un
Phase angle:
±2°
DPHHPDOC Current:
±1.5% of the set value or ±0.002 × In (at currents in the range of 0.1…10
× In)
±5.0% of the set value (at currents in the range of 10…40 × In)
Voltage:
±1.5% of the set value or ±0.002 × Un
Phase angle:
±2°
Start time1)2) IFault = 2.0 × set Start value Typically 24 ms (±15 ms)
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)
1) Measurement mode = default (depends of stage), current before fault = 0.0 × In, fn = 50 Hz, fault current in one phase with nominal frequency injected from random phase angle, results based
on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 × In, Start value multiples in range of 1.5...20
ABB 33
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Characteristic Value
Current:
±1.5% of the set value or ±0.003 × In
Voltage:
±1.0% of the set value or ±0.003 × Un
Impedance:
±2.0% of the set value or ±0.01 Ω static accuracy
Phase angle: ±2°
34 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
ABB 35
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
36 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Characteristic Value
Characteristic Value
Characteristic Value
ABB 37
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)
1) Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 × In, fn = 50 Hz, earth-fault current with nominal frequency injected from
random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 × In, Start value multiples in range of 1.5...20
38 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Characteristic Value
DEFLPDEF Current:
±1.5% of the set value or ±0.002 × In
Voltage
±1.5% of the set value or ±0.002 × Un
Phase angle: ±2°
DEFHPDEF Current:
±1.5% of the set value or ±0.002 × In
(at currents in the range of 0.1…10 × In)
±5.0% of the set value
(at currents in the range of 10…40 × In)
Voltage:
±1.5% of the set value or ±0.002 × Un
Phase angle: ±2°
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)
1) Set Operate delay time = 0.06 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 × In , fn = 50 Hz, earth-fault current with
nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 × In, Start value multiples in range of 1.5 to 20
ABB 39
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in IDMT mode 3) ±5.0% of the set value or ±20 ms
1) Fundamental frequency current = 1.0 × I n . Harmonics current before fault = 0.0 × In , harmonics fault current 2.0 × Start value. Results based on statistical distribution of 1000 measurement.
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 × In , Start value multiples in range of 2...20
40 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Characteristic Value
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Io varied during the test. Uo = 1.0 × Un = phase to earth voltage during earth-fault in compensated or unearthed network.
2) Includes the delay of the signal output contact. Results based on statistical distribution of 1000 measurements.
ABB 41
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Characteristic Value
1) Includes the delay of the signal output contact. Results based on statistical distribution of 1000 measurements.
42 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the set value or ±20 ms
1) Io varied during the test. Uo = 1.0 × U n = phase to earth voltage during earth-fault in compensated or un-earthed network. The residual power value before fault = 0.0 pu, fn = 50 Hz, results
based on statistical distribution of 1000 measurements.
2) Includes the delay of the signal output contact.
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
ABB 43
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Characteristic Value
Start time 1)2) IFault = 2 × set Start value Typically 23 ms (±15 ms)
IFault = 10 × set Start value Typically 16 ms (±15 ms)
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)
1) Operate curve type = IEC definite time, negative sequence current before fault = 0.0, fn = 50 Hz
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 × In , Start value multiples in range of 1.5 to 20
Characteristic Value
1) Overload current > 1.2 × Operate level temperature, Current reference > 0.50 pu
44 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Table 59. Three-phase thermal overload protection for feeder (T1PTTR) main settings
Characteristic Value
Current measurement:
±1.5% of the set value or ±0.002 × In
Ratio I2f/I1f measurement:
±5.0% of the set value
Characteristic Value
Start time1)2) UFault = 2.0 × set Start value Typically 17 ms (±15 ms)
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)
1) Start value = 1.0 × Un, Voltage before fault = 0.9 × Un, fn = 50 Hz, overvoltage in one phase-to-phase with nominal frequency injected from random phase angle
2) Includes the delay of the signal output contact
3) Maximum Start value = 1.20 × Un, Start value multiples in range of 1.10...2.00
ABB 45
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Characteristic Value
Start time1)2) UFault = 0.9 × set Start value Typically 24 ms (±15 ms)
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)
1) Start value = 1.0 × Un, Voltage before fault = 1.1 × Un, fn = 50 Hz, undervoltage in one phase-to-phase with nominal frequency injected from random phase angle
2) Includes the delay of the signal output contact
3) Minimum Start value = 0.50 × Un, Start value multiples in range of 0.90...0.20
46 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Positive-sequence voltage before fault = 0.0 × Un, fn = 50 Hz, positive-sequence overvoltage of nominal frequency injected from random phase angle
2) Includes the delay of the signal output contact
Characteristic Value
Start time1)2) UFault = 0.9 × set Start value Typically 28 ms (±15 ms)
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Positive-sequence voltage before fault = 1.1 × Un, fn = 50 Hz, positive-sequence undervoltage of nominal frequency injected from random phase angle
2) Includes the delay of the signal output contact
ABB 47
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Negative-sequence voltage before fault = 0.0 × Un, fn = 50 Hz, negative-sequence overvoltage of nominal frequency injected from random phase angle
2) Includes the delay of the signal output contact
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Residual voltage before fault = 0.0 × Un , fn = 50 Hz, residual voltage with nominal frequency injected from random phase angle
2) Includes the delay of the signal output contact
48 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Start value = 0.05 × Sn, Reactive power before fault = 0.8 × Start value. Reactive power overshoot 2 times. Results based on statistical distribution of 1000 measurement.
Table 75. Directional reactive power undervoltage protection (DQPTUV) main settings
Characteristic Value
Start time1)2) Start value = 0.05 Hz/s Typically 110 ms (±15 ms)
df/dtFAULT = ±1.0 Hz/s
Operate time accuracy in definite time mode ±1.0% of the set value or ±30 ms
ABB 49
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Characteristic Value
±0.003 Hz
Operate time accuracy in definite time mode ±1.0% of the set value or ±30 ms
Characteristic Value
±0.003 Hz
Operate time accuracy in definite time mode ±1.0% of the set value or ±30 ms
50 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Characteristic Value
±0.003 Hz
Operate time accuracy in definite time mode ±1.0% of the set value or ±30 ms
Characteristic Value
ABB 51
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Characteristic Value
Characteristic Value
52 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
ABB 53
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Protection-related functions
Characteristic Value
Characteristic Value
Table 94. Communication logic for residual overcurrent (RESCPSCH) main settings
Characteristic Value
54 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Characteristic Value
Table 98. Current reversal and WEI logic (CRWPSCH) main settings
Table 99. Current reversal and WEI logic for residual overcurrent (RCRWPSCH)
Characteristic Value
ABB 55
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Table 100. Current reversal and WEI logic for residual overcurrent (RCRWPSCH) main settings
56 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Control functions
Characteristic Value
ABB 57
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Characteristic Value
Table 103. Runtime counter for machines and devices (MDSOPT) main settings
Characteristic Value
Characteristic Value
Operate time1) • NPS function UFault = 1.1 × set Neg Seq voltage Typically 35 ms (±15 ms)
Lev Typically 25 ms (±15 ms)
UFault = 5.0 × set Neg Seq voltage
Lev
• Delta function ΔU = 1.1 × set Voltage change rate Typically 35 ms (±15 ms)
ΔU = 2.0 × set Voltage change rate Typically 28 ms (±15 ms)
1) Includes the delay of the signal output contact, fn = 50 Hz, fault voltage with nominal frequency injected from random phase angle
Characteristic Value
58 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Characteristic Value
Characteristic Value
Characteristic Value
ABB 59
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Characteristic Value
Operation VPPMHAI On -
Off
60 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Operation VPHMHAI On -
Off
ABB 61
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Measurement functions
Characteristic Value
±0.5% or ±0.002 × In
(at currents in the range of 0.01...4.00 × In)
Characteristic Value
±0.5% or ±0.002 × Un
(at voltages in the range of 0.01...1.15 × Un)
Characteristic Value
±0.5% or ±0.002 × Un
(at voltages in the range of 0.01...1.15 × Un)
Characteristic Value
±0.5% or ±0.002 × In
(at currents in the range of 0.01...4.00 × In)
Characteristic Value
±0.5% or ±0.002 × Un
62 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Characteristic Value
Characteristic Value
±1.0% or ±0.002 × In
at currents in the range of 0.01...4.00 × In
Characteristic Value
±1.0% or ±0.002 × Un
At voltages in range of 0.01…1.15 × Un
ABB 63
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
21. Front panel user interface LED indicators. The 15 programmable alarm LEDs can indicate
The 630 series protection relays can be ordered with a a total of 45 alarms. The local HMI offers full front-panel user-
detached front-panel user interface (HMI). An integrated HMI is interface functionality with menu navigation, menu views and
available for 4U high housing. The local HMI includes a large operational data. In addition, the local HMI can, using PCM600,
graphical monochrome LCD with a resolution of 320 x 240 be configured to show a single-line diagram (SLD). The SLD
pixels (width x height). The amount of characters and rows view displays the status of the primary apparatus such as circuit
fitting the view depends on the character size as the characters' breakers and disconnectors, selected measurement values and
width and height may vary. busbar arrangements.
GUID-5CFD3446-A92F-4A5F-B60D-90025DCFDC61 V2 EN
Mounting methods:
• Flush mounting
• Semi-flush mounting
• Overhead/ceiling mounting
64 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
270
252,5
366
13
101,6
180
ø6,8
GUID-945D3C86-A432-4C1F-927A-A208E0C1F5F6 V2 EN
GUID-AF1BEC0B-A9DC-4E9B-9C89-98F28B1C81DB V1 EN
Figure 11. Flush mounting
Figure 12. Semi-flush mounting
,5 22 0
25
25 8,
177
13
265,9
4
22
GUID-A368C5C3-D4A9-40B7-BD0E-181A6BB7ECA6 V1 EN
Figure 14. 6U half 19" unit wall mounted with two mounting brackets
and detached LHMI
ABB 65
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
23. Selection and ordering data The order code consists of a string of letters and digits
generated from the hardware and software modules of the
The IED type and serial number label identifies the protection protection relay. Use the ordering key information in tables to
and control relay. The label placed is on the side of the generate the order code when ordering protection and control
protection relay's case. The labels include a set of smaller size relays.
labels, one label for each module in the protection relay. The
module labels state the type and serial number of each module.
SBFAABABBBAZAZNBXD
# Description
1 IED
630 series, 4U half 19” housing S
630 series, 6U half 19” housing T
630 series, 4U half 19” housing & connector set U
630 series, 6U half 19” housing & connector set V
2 Standard
IEC B
3 Main application
Feeder protection and control F
GUID-3D6E8ED5-075A-4229-82C7-80A7D126FEC2 V5 EN
66 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
The preconfiguration determines the analog input and binary I/O options. SBFAABABBBAZAZNBXD
The example below shows standard configuration “A” with chosen options.
# Description
4-8 Functional application, preconfigurations:
A = Preconfiguration A for open/closed ring feeder
B = Preconfiguration B for radial overhead/mixed line feeder
C = Preconfiguration C for ring/meshed feeder1)
D = Preconfiguration D for bus sectionalizer
N = None
Pre- Available analog input options Available binary input/
conf. output options
AB = 23 BI + 18 BO
AC = 32 BI + 27 BO
A AB = 4I (I0 1/5 A) + 1I (I0 0.1/0.5 A) + 4U
AD2) = 41 BI + 36 BO
AE2) = 50 BI + 45 BO
AB = 23 BI + 18 BO
AC = 32 BI + 27 BO
B AB = 4I (I0 1/5 A) + 1I (I0 0.1/0.5 A) + 4U
AD2) = 41 BI + 36 BO
AE2) = 50 BI + 45 BO
AB = 23 BI + 18 BO
AC = 32 BI + 27 BO
C1) AB = 4I (I0 1/5 A) + 1I (I0 0.1/0.5 A) + 4U
AD2) = 41 BI + 36 BO
AE2) = 50 BI + 45 BO
AB = 23 BI + 18 BO
AC = 32 BI + 27 BO
D AB = 4I (I0 1/5 A) + 1I (I0 0.1/0.5 A) + 4U
AD2) = 41 BI + 36 BO
AE2) = 50 BI + 45 BO
AA = 4I (I0 1/5 A) + 5U
AB = 4I (I0 1/5 A) + 1I (I0 0.1/0.5 A) + 4U
AA = 14 BI + 9 BO
AC = 3I + 1I (I0 0.1/0.5 A) + 5U
AB = 23 BI + 18 BO
BA = 4I (I0 1/5 A) + 5U +
N 8mA/RTD in + 4mA out AC3) = 32 BI + 27 BO
1) Preconfiguration C requires that the distance protection option is chosen for digit #14 or digit #15
2) Binary input/output options AD and AE require 6U half 19” IED housing (digit #1 = T or V)
3) Binary input/output option AC is not available for 4U high variant (digit #1 = S or U) with RTD card options
(digit #5-6 = BA, BB or BC)
4) Binary input/output option AE is not available for 6U high variant (digit #1 = T or V) with RTD card options
(digit #5-6 = BA, BB or BC)
GUID-D8AAE9B9-CABD-41D3-BBC1-F9377202A589 V5 EN
ABB 67
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
SBFAABABBBAZAZNBXD
# Description
9 Communication modules (Serial)
Serial glass fibre (ST connector) A
Serial plastic fibre (Snap-in connector) B
10 Communication modules (Ethernet)
Ethernet 100Base-FX (LC connector) A
Ethernet 100Base-TX (RJ-45 connector) B
11 Communication (Protocol)
IEC 61850 protocol A
IEC 61850 and DNP3 TCP/IP protocols B
IEC 61850 and IEC 60870-103 protocols C
GUID-28800219-99DA-45EB-919C-C7CBE7B7C69D V5 EN
68 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
SBFAABABBBAZAZNBXD
# Description
12 Language
Language package Z
13 Front panel
Integrated LHM1) A
Detached LHMI + 1 m cable B
Detached LHMI + 2 m cable C
Detached LHMI + 3 m cable D
Detached LHMI + 4 m cable E
Detached LHMI + 5 m cable F
No LHMI2) N
14 Option 13)
Fault locator and synchro-check A
Fault locator and distance protection 4)
B
Fault locator and power quality 5) C
Synchro-check and distance protection 4) D
Synchro-check and power quality5) E
Distance protection and power quality 4,5)
F
All options Z
None N
15 Option 23)
Fault locator A
Synchro-check B
Distance protection4) D
Power quality5) E
None N
16 Power supply
Power supply 48-125 VDC A
Power supply 110-250 VDC, 100-240 VAC B
17 Reserved
Undefined X
18 Version
Version 1.3 D
ABB 69
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Example code: S B F A A B A B B B A Z A Z N B X D
Digit (#) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Code
GUID-05BC330A-4237-4597-B5B0-9FD1B4414DC0 V5 EN
24. Accessories
Flush mounting kit for one 4U half 19” housing the protection relay 1KHL400040R0001
Semi-flush mounting kit for one 4U half 19” housing the protection relay 1KHL400444R0001
Wall-mounting kit (cabling towards the mounting wall) for one 4U half 19” housing the protection relay 1KHL400067R0001
Wall-mounting kit (cabling to the front) for one 4U half 19” housing the protection relay 1KHL400449R0001
19" rack mounting kit for one 4U half 19” housing the protection relay 1KHL400236R0001
19" rack mounting kit for two 4U half 19” housing the protection relays 1KHL400237R0001
Overhead/ceiling mounting kit (with cable space) for one 4U half 19” housing the protection relay 1KHL400450R0001
Wall-mounting kit for direct rear wall mounting (with cabling to the front) of one 6U half 19" housing the protection 1KHL400452R0001
relay
Wall-mounting kit (with cabling towards the mounting wall) for one 6U half 19" housing the protection relay 1KHL400200R0001
Overhead/ceiling mounting kit (with cable space) for one 6U half 19" housing the protection relay 1KHL400464R0001
19" rack mounting kit for one RTXP8 test switch (the test switch is not included in the delivery) 1KHL400465R0001
19" rack mounting kit for one RTXP18 test switch (the test switch is not included in the delivery) 1KHL400467R0001
19" rack mounting kit for one RTXP24 test switch (the test switch is not included in the delivery) 1KHL400469R0001
Connector set for one 4U housing the protection relay including analog input variant 4I + 5U or 5I + 4U 2RCA021735
Connector set for one 6U housing the protection relay including analog input variant 4I + 5U or 5I + 4U 2RCA021736
Connector set for one 4U housing the protection relay including analog input variant 7I + 3U 2RCA023041
Connector set for one 6U housing the protection relay including analog input variant 7I + 3U 2RCA023042
Connector set for one 4U housing the protection relay including analog input variant 8I + 2U 2RCA023039
Connector set for one 6U housing the protection relay including analog input variant 8I + 2U 2RCA023040
70 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
26. Tools using a web browser (IE 7.0 or later). For security reasons, the
The protection relay is delivered either with or without an web-browser based user interface is disabled by default. The
optional factory made preconfiguration. The default parameter interface can be enabled with the PCM600 tool or from the front
setting values can be changed from the front-panel user panel user interface. The functionality of the interface is by
interface, the web-browser based user interface (WebHMI) or default limited to read-only, but can be configured to enable
the PCM600 tool in combination with the relay-specific read and write access by means of PCM600 or the local HMI.
connectivity package.
The relay connectivity package is a collection of software and
PCM600 offers extensive relay configuration functions such as specific protection relay information, which enable system
relay application configuration, signal configuration, DNP3 products and tools to connect and interact with the protection
communication configuration and IEC 61850 communication relay. The connectivity packages reduce the risk of errors in
configuration including horizontal communication, GOOSE. system integration, minimizing device configuration and set-up
times.
When the web-browser based user interface is used, the
protection relay can be accessed either locally or remotely
Description Version
ABB 71
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Parameter setting ● ●
Disturbance handling ● ●
Signal monitoring ● ●
Event viewer ● ●
Hardware configuration - ●
Signal matrix - ●
Communication management - ●
User management - ●
Creating/handling projects - ●
IED Compare - ●
27. Supported ABB solutions substation automation standard, are fast communication
ABB’s 630 series protection and control protection relays capability, continuous supervision of the protection and
together with the Grid Automation controller COM600 communication system's integrity, and an inherent flexibility
constitute a genuine IEC 61850 solution for reliable power regarding reconfiguration and upgrades
distribution in utility and industrial power systems. To facilitate
and streamline the system engineering ABB’s relays are At substation level, COM600 uses the logic processor and data
supplied with connectivity packages. The connectivity content of the bay level devices to enhance substation level
packages include a compilation of software and relay-specific functionality. COM600 features a Web-browser based HMI
information such as single-line diagram templates, manuals which provides a customizable graphical display for visualizing
and a full relay data model including event and parameter lists. single line mimic diagrams for switchgear bay solutions. To
With the connectivity packages, the relays can be readily enhance personnel safety, the Web HMI also enables remote
configured via the PCM600 Protection and Control IED access to substation devices and processes. Furthermore,
Manager and integrated with the Grid Automation controller COM600 can be used as a local data warehouse for technical
COM600 or the MicroSCADA Pro network control and documentation of the substation and for network data collected
management system. by the devices. The collected network data facilitates extensive
reporting and analyzing of network fault situations using the
The 630 series relays offer support for the IEC 61850 standard data historian and event handling features of COM600.
including horizontal GOOSE messaging. Compared to
traditional hard-wired, inter-device signaling, peer-to-peer COM600 also features gateway functionality providing
communication over a switched Ethernet LAN offers an seamless connectivity between the substation devices and
advanced and versatile platform for power system protection. network-level control and management systems such as
Among the distinctive features of the protection system MicroSCADA Pro and System 800xA.
approach, enabled by the full implementation of the IEC 61850
72 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Product Version
ABB 73
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
GUID-88CD16F3-27E5-4657-BDAF-46D27B4970D8 V1 EN
74 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
GUID-5E27DD50-FD15-4824-BDFB-DD52E29730EA V2 EN
Unit BI/BO
4U X319 + X3161)
X324 + X321
6U X324 + X3211)
X329 + X326
X334 + X331
X339 + X336
ABB 75
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
GUID-CB7B1CF8-A0E4-42F5-998C-701641515127 V1 EN
29. References You will find the latest relevant information on the REF630
The www.abb.com/substationautomation portal offers you protection relay on the product page. Scroll down the page to
information about the distribution automation product and find and download the related documentation.
service range.
76 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Protection
Three-phase directional overcurrent protection, low stage DPHLPDOC 3I> -> 67-1
Three-phase directional overcurrent protection, high stage DPHHPDOC 3I>> -> 67-2
ABB 77
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Protection-related functions
Current reversal and WEI logic for residual overcurrent RCRWPSCH CLCRWN 85NCRW
Control
Power quality
78 ABB
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
Measurement
ABB 79
Feeder Protection and Control 1MRS756976 H
REF630
Product version: 1.3
80 ABB
81
—
ABB Distribution Solutions
Distribution Automation
P.O. Box 699
FI-65101 VAASA, Finland
Phone +358 10 22 11
www.abb.com/mediumvoltage
www.abb.com/relion
1MRS756976 H