Professional Documents
Culture Documents
7 9 11
Relevant materials Maximum power demands must be known before details of supply
1. Overview configuration can be determined and designed for a new building,
either factory or residential or office building.
Lecture notes This includes power estimation for the following three types of
Requirements on electrical supply systems: demand
Standards
more energy efficient, better energy management manufacturing equipment requirements (for factory)
AS/NZS 3000:2007 Wiring Rules
IET BS 7671: 2008, Requirements for safer (including personnel safety, fire and equipment safety) fixed wiring infrastructure requirements
Electrical Installations general purpose outlets (GPOs)
adequate power quality (harmonics and over-voltages)
Other Australia standards able to handle modern information technology systems
IEEE Gray Book compliant with electromagnetic compatibility (EMC) and
Service and Installation Rules (S.I.R.) electromagnetic interference (EMI) regulations for electrical
systems
Publications from manufacturers
etc provide monitoring systems to assess condition of installation
8 10 12
In estimation of maximum demand, one should make
Two methods for Maximum Demand Calculation
allowance for future growth in power usage. Calculation of maximum demand
calculation using Appendix C of AS/NZS3000 Wiring Rules to
determine demand for domestic and commercial type loads.
Typically: using Appendix C of AS/NZS 3000:2007
residential premises, 10% 100kVA 110kVA
when exact load details are unknown, use an estimate
technique called After Diversity Maximum Demand (ADMD) fully air-conditioned offices, 15-20% domestic installation (use Table C1)
Based on results from similar installations, typical load density values commercial premises, 20-25% single
(VA/m2) are derived for different types of floor area usage. shopping centres, light/medium industrial, 25% multiple
Data available for commercial (e.g. offices, shopping centres, hotels,
theatres) and light industrial premises non-domestic installation (use Table C2)
Such allowance for future growth should be residential type (e.g. hotel, hospital)
considered at the planning stage in the selection of
others (e.g. factory, shop, business office)
switchboard circuits
transformer capacity
cable sizes for feeder circuits and network of power
13 15 17
g Floodlighting, swimming pool lighting, tennis court lighting and the like.
h For the purpose of determining maximum demand, a multiple combination socket-outlet shall be
regarded as the same number of points as the number of integral socket-outlets in the combination.
i Each item of permanently connected electrical equipment not exceeding 10 A may be included in
load group B(i) as an additional point.
j Where an electrical installation contains 15 A or 20 A socket-outlets covered by load group B(ii) or Table
B(iii), the base loading of load group B is increased by 10 A or 15 A respectively. If both 15 A and 20
A socket-outlets are installed, the increase is 15 A. C2
k Where an electrical installation includes an air-conditioning system for use in hot weather and a (cont.)
heating system for use in cool weather, only the system that has the greater load shall be taken into
account.
l Instantaneous water heaters including quick recovery heaters having element ratings greater
than 100 W/L.
m Storage-type water heaters, including quick recovery heaters not referred to in footnote l.
n This load group is not applicable to socket-outlets installed in communal areas but connected to
the individual living units. Such socket-outlets should be included in load group B.
Table C1 (cont.)
20 22 24
Example 2:
Example 1:
3. Means & Requirements
A(i)
d.Notes_C1: A(i)
of Electricity Supply
3.1 Voltage levels
e.Notes_C1: A(i)
i.Notes_C1: B(i)
3.2 Quality of supply
3.3 Method of supply
3.4 Type of supply connection
(B-N) (C-N)
(A-N)
3.5 Safety
Note: Assume supply voltage and equipment rating of 230V 3.6 Reliability of supply
3.7 Maintenance
3.8 Backup supply
3.9 DC supply
25 27 29
High voltage:
i.Notes_C1 26=20+6 11 kV, 3-phase supply
[by cable or overhead line]
Low voltage:
(a) 230/400V, 3-phase, 4-wire system
(b) single-phase, 230V, 2-wire system
[underground/aerial cable, or overhead line]
26 28 30
3.2 Quality of supply 3.3 Method of supply
What is an energy distributor? Point of supply
Up to ~200 kVA in demand:
An important consideration because:
Distributors own and manage high and low voltage incoming supply would be obtained directly from
network of 'poles', 'wires' or pipes that deliver electricity or distributor’s LV mains. It is commonly a low
increasing use of power electronics has introduced a
gas to your home or business. They are responsible for the
higher harmonic level into supply voltage supply of 3-phase 415/240V.
quality and reliability of your energy service.
much of equipment now in use, especially IT devices, by either overhead or underground connection.
How is that different to an energy retailer? is more susceptible to voltage variation, transient over-
voltages and harmonics.
Energy retailer on the other hand sells you the electricity
and gas for your home or business and bills you for what
you use.
37 Ref.: NSW Service and Installation Rules 39 Ref.: NSW Service and Installation Rules 41
43 45 47 47
S1 S1 S2
Tie C.B.
Load break fused switch (Normally open)
Transformer
4.1.2. Expanded radial system 4.1.4. Primary loop system 4.1.6. Secondary spot network
S1
Medium or high-voltage
C/B (draw-out type)
transformer(s),
transformer 11kV/415V nominal
Dyn11 winding
switchgear, 25kVA up to 400kVA
600A/phase (400kVA)
protection system, LV fuse
Pad-mounted substation
61 63 65
62 64 66
4.5 Voltage regulation 5.2 Voltage drop determination for cables
and power factor For typical length of 50 Hz building power-supplying cables,
5. Voltage Drop the effect of their shunt capacitive reactance is negligible.
For LV supply, nominal voltage is 230/400V +10% / -6%
at 50Hz (AS 60038-2000 Standard Voltages). Calculation of voltage drop along the cables can be done
adequately by use of short line approximation represented
Deviation from nominal voltage can cause problems: 5.1 Voltage drop determination methods
equipment overheating, light dimming or flickering etc. by equivalent circuit:
5.2 Voltage drop determination for cables
AS3000 requires voltage drop between point of supply 5.3 Voltage drop determination for transformers
and any point in electrical installation not to exceed
5% of nominal voltage when conductors are carrying 5.4 Parallel operations
maximum demand.
Voltage drop in utility service line should not exceed 3%
of nominal voltage when at maximum demand. This is
mainly a requirement applied to distributors and their
service cable impedance.
67 69 71
point
of supply main
switchboard
MSB
distribution
board DB
73 75 77
74 76 78
5.4 Parallel operation of transformers and
feeders Taipei 101
The University of New South Wales
SWITCHBOARDS
79 81 1
OVERVIEW
Switchboard is also called “Switchgear and Controlgear
Assembly” (SCA).
3 5 7
10 12 14
60 mm busbar system
PARTS OF A SWITCHBOARD (CONT’D) PARTS OF A SWITCHBOARD (CONT’D)
Metering equipment Over-voltage surge protection
The metering of SWB will include: Modern switchboards also have some over-voltage surge
protection designed into both HV and LV sides to protect
line and phase voltage, equipment against effects of any over-voltage transients that
line current in each phase, may be generated within the system or conducted in from
total power, external sources.
power factor metering.
15 17 19
16 18 20
SPECIFICATIONS AS/NZS 3000:2000 Electrical Installations IP number uses two numerals to represent specific
Purchaser should specify:
Service and Installation Rules 2005 (Victoria) design requirements to prevent ingress:
Voltage, power, current ratings
Required fault level and protection operating time NS 0112 Design Standards for Industrial / 1st numeral = degree of protection against ingress
Internal structure, segregation of compartments Commercial Developments (EnergyAustralia) of solid objects and thus protection of personnel
Ingress Protection (IP) numbers for protection against dust and against access to hazardous parts.
moisture MORE USEFUL DOCUMENTS
Arc containment requirements … 2nd numeral = degree of protection against harmful
Low voltage electrical work – Code of Practice 2001
ingress of water.
Earthing requirements (NSW WorkCover)
Electrodynamic forces and insulator mechanical strength NSW Service and Installation Rules additional letter (optional) = degree of protection of
requirements
personnel against access to hazardous parts
Thermal features - maximum temperature rises etc.
Testing requirements (Type tests and Routine tests). supplementary letter (optional) = other information
21 23 25
7.09E04(V/m) 4.09E05(V/m)
27 29 31
IP21 typical for commercial buildings Arcing involves significant energy and thus damage is
very destructive.
IP65 for industrial manufacturing or outdoor SWBs IEEE 1584-2002 provides method to calculate incident
energy and arc-flash protection boundaries.
Segregation of internal parts limits spreading of
Electrical installations at UNSW: IP?? damage.
28 30 32
NILSEN can have high voltage switchboards tested to 31.5kA.
Switchboard
compartment
forms of segregation
http://www.nilsen.com.au/
enclosure busbar
internal
separation
functional
unit
terminals
Fig. D2 AS3439.1:2002
33 35 37
34 36 38
The University of New South Wales
SWITCHBOARD DESIGN
Testing of Switchboards
• Two test categories:
• Type Tests: done only on one unit representative of
the design School of Electrical Engineering
• Routine Tests: done on every manufactured unit and Telecommunications
Olex MV cables
UNSW HV Electrical Services (3.8/6.6 – 19/33kV single core screened and PVC sheathed)
40 42 http://www.olex.com.au
2
2C: Two-core cable
Olex MV cables
3
(3.8/6.6 – 19/33kV three core individually screened and PVC sheathed)
3 5 7
http://www.olex.com.au
STANDARD SPECIFICATIONS
4 6 8
CABLE CONDUCTOR (CONTD) Major considerations in selecting cables:
STANDARD SPECIFICATIONS Cu has higher conductivity than Al. To achieve same current carrying as Cu
conductor, Al needs 1.6 times cross section area. This results in more space current carrying capacity [determined by maximum
required to terminate Al conductor.
AS/NZS 1125:2001 Conductors in insulated electric permissible steady state temperature rise].
Termination of Al conductor requires great care to avoid formation of Al oxide
cables and flexible cords on metal surface, which could deteriorate conductivity of the termination.
AS 1531:1991 Conductors - Bare overhead -- voltage drop and regulation at full load
Aluminium and aluminium alloy Al conductors cost less.
AS 1746:1991 Conductors - Bare overhead - Hard-
drawn copper
.
Al conductors have about half specific gravity as Cu conductors
short circuit rating [determined by maximum permissible
transient temperature rise]
AS 3158:2004 Electric cables - Glass fibre insulated - insulation requirements and associated factors [jointing and
For working voltages up to and including 0.6/1 (1.2) kV termination].
AS/NZS 3560.1:2000 Electric cables - Cross-linked
polyethylene insulated - Aerial bundled - For working required level of fire resistance of cable and busbar systems .
voltages up to and including 0.6/1(1.2)kV - Aluminium
conductors
AS/NZS 3187:1995 Approval and test specification -
Mineral-insulated metal-sheathed cables
9 11 13
CURRENT-CARRYING CAPACITY
CABLE CONDUCTOR Very important criterion
Mainly copper (Cu) and aluminium (Al).
Al conductors of cross section < 16 mm2 are difficult to terminate due to its
tendency to 'cold flow'. Therefore below 16 mm2, Al cables are not generally
Requirements Temperature of cable insulation must be kept
below well-defined values to limit ageing
used.
of Minimum rating for cables of consumer mains
Cold flow characteristic of aluminium metal: The common problem with
aluminium wiring occurs as the aluminium wire is screwed to a wall receptacle
or switch plate and becomes loose due to expansion and contraction caused
cable system design is 32A; for cables of sub-mains it is 25A.
by the flow or non flow of electric current.
This produces an illumination oxidation layer as it breathes. Oxide, being an
insulator of high resistance, produces enormous heat that deteriorates the
contact and eventually breaks down.
Copper, on the other hand, does not have cold flow properties.
10 12
14
CURRENT-CARRYING CAPACITY (CONTD)
17 19
15
Limiting temperatures for insulated cables IET standard BS 7671:2008 – Table 4C4: de-rating factor for cable
EXTERNAL INFLUENCES ON CABLE CAPACITY group applications
Table 1 AS3008.1.1
Grouping of cables
Ambient temperature
Depth of laying
0.84
Thermal resistivity of soil
Varying load conditions 0.75
Effect of thermal insulation
Effect of direct sunlight . 0.72
Table 29 AS3008.1.1
21 25
23
Table 27 AS3008.1.1 22 24 26
Definition of unit value of voltage drop in mV/(A m) Definition of unit value of voltage drop in mV/(A m) VOLTAGE DROP AND REGULATION (CONTD)
for single-phase cable for three-phase cable (Contd) L
Calculation of voltage drop along the cable under different loading
+ V1 -
where rpm and xpm are per meter values referred to each
conductor and can be calculated from the values given
where zpm is the equivalent per-meter impedance of each of two in Tables 30 39.
conductors in the single-phase cable and zpm= rpm + jxpm. +
L
+ One can see that the voltage drop depends on
Given unit value of voltage drop in mV/(A m) for single-phase VS VR Load power factor
cable, the voltage drop across it is given by - -
29 Current level
Cable or conductor resistance and reactance
27 29
Length of cable. 31
-
Definition of unit value of voltage drop in mV/(A m) + V1 IET Wiring Regulations, BS 7671_2008: See T3_18
for three-phase cable L
- V2 +
+ V1 -
Three-phase voltage drop: +
IA
+
VS VR V1 -
IB IA +
- -
- +
V2 IB
(m /m)
IC V1+V2 - V2 +
IC
V2
where Z is the equivalent impedance of each -IB One can see from the last two columns of the table below that such
IC
conductor or in the one-phase equivalent circuit. V1
relationship holds.
IA
IB
Definition of unit value of voltage drop in mV/(A m) given in
standard for three-phase cable:
where zpm is the equivalent per-meter impedance referred to Per unit length impedance for the chosen cable referred to each conductor :
each conductor of the cable and zpm= rpm + jxpm. Single phase:
28 30
Three phase: 32
For a chosen three-phase cable under certain operating condition, the voltage drop is
calculated by L
V1
SHORT CIRCUIT TEMPERATURE RISE
+ -
+ +
VOLTAGE DROP AND REGULATION (CONTD) IA
where V
-
IB V
-
S
-
V2 +
R Maximum permissible short-circuit temperatures (duration
Unbalanced 3-phase circuits:
IC up to 5 seconds) are detailed in Tables 52-54 of AS3008.1.
rpm and xpm are per meter values referred to each conductor.
Voltage drop calculations performed on 1 basis by Both r and x can be found from Table 4D1B.
geometrically summing voltage drop in heaviest loaded
is load power factor angle. It is always positive no matter for lagging or
phase and voltage drop in neutral conductor. leading load.
Alternatively, assume balanced 3 load conditions and or
Table 52
perform calculations using current in heaviest loaded where
phase.
Maximum voltage drop across a three-phase cable with a given current:
where Vc(3 ) or z can be found from Table 4D1B for 3 cable, and 35
33
Maximum occurs when load power factor angle is equal to , lagging. 37
Summary For a chosen single-phase cable under certain operating condition, the voltage
L
drop is calculated by L
Unit value of voltage drop in mV/(A m) for three-phase +
+ V1 -
+ where
cable IA
VS IB VR
- -
- +
V2
IC Table 53
zpm is per-meter impedance of each conductor. rpm and xpm are per meter values referred to each conductor.
z is the value found from Table 4D1B for three-phase
cable. Both r and x can be found from Table 4D1B.
is load power factor angle. It is always positive no matter for lagging or
Unit value of voltage drop in mV/(A m) for single-phase leading load.
cable Maximum voltage drop across a single-phase cable with a given current:
+ V1 - + V1 -
+ + + +
I I
VS VR VS VR
zpm is per-meter impedance of each conductor. -
- + -
-
- + -
Table 54
V2 V2
z is the value found from Table 4D1B for single-phase
cable. L where Vc(1 ) or z can be found from Table 4D1B for L
single-phase cable, and
34 36
Maximum occurs when load power factor angle is equal to , lagging.
Limited by material in contact
34 36 38
Calculation of permissible short-circuit current for the CABLE TYPES IN USE
cables CABLE INSULATION
Aerial cables or lines
where: The particular type and thickness of insulation of cables and They are used between buildings or as service lines to buildings
I = short-circuit current (rms over duration), in amps conductors will depend on the voltage of operation and also on the They could be bare lines with no insulation covering; or insulated
t = duration of short circuit, in secs application. overhead cables, which may be either aerial bundled cables
S = cross-sectional area of conductor, in mm2 (ABC) or simply covered conductors.
For modern high voltage distribution systems, cross-linked For those used outdoors, their insulation degrades due to
K = constant depending on the material of the current-carrying
polyethylene (XLPE) is almost exclusively used. ultraviolet (UV) radiation.
conductor, the initial temperature and the final temperature;
For low voltage applications, there are many insulation types in use. Indoor distribution cables
independent of conductor dimension.
These include: paper, XLPE(cross-linked polyethylene), PVC (polyvinyl
chloride), EPR (ethylene propylene rubber )
PVC (polyvinyl chloride) 44-53
c = specific heat conductivity of the conductor material PVC or PE (polyethylene) sheathing
XLPE (cross-linked polyethylene) Fire resistant cables
20 = electrical resistivity of conductor at 20oC Elastomeric (ethylene propylene rubber [EPR]) mineral insulated metal sheathed (MIMS) cables
= conductor material density Mineral insulated metal sheathed (MIMS) cables Radox (Radox is a halogen free polyolefin-copolymer based
compound crosslinked by e-beam technology to eliminate melt
0, 1 = initial and final temperatures Other factors that need to be considered in the insulation choice and flow of the material when subjected to extreme heat such as
overload, short circuit or high ambient temperatures.)
= temperature coefficient of resistance are flexibility, hardness, resistance to mechanical effects, effects Firestop: It is fire resistant cables which can resist the effects of
of moisture and contamination etc. A major factor in the choice fires.
Values for the constant K can be readily obtained from Table 51
of insulation used is the effects of fire on the cable insulation. Other types of cables for control and communication applications
of AS3008.1. 39 41 43
FIRE HAZARDS
I2t=K2S2 CABLE ENCLOSURES AND CONDUITS
1. The cables may provide substantial flammable material in the
chemical structure of their insulation. Conduits: steel, rigid PVC, corrugated
2. They generate significant smoke and soot when they burn and this flexible PVC
can cause considerable damage to equipment otherwise unaffected
by the fire heat. Tubes and pipes: metal, non-metal plastic,
earthenware etc
3. Many of the fire products from insulation combustion are toxic
V75 and thus represent a significant health hazard. Ducts: metal or non-metal
4. Many products of the insulation combustion are corrosive and can Cable support systems: cable trays, cable
substantially damage electronic equipment for example. ladders troughs etc
5. The cables should ideally be able to operate after significant Trunking systems: mainly for busbars.
damage by a fire; however this is not possible if the polymeric
insulation burns away. There may be total loss of insulation integrity
in this case. -
47
45 49
dbts™
48
Ref.: General Cable Australia catalogue 46
50
Example 1:
3 load
consumer 30A
Flexible copper straps mains
1 loads
easily shaped on site to match installation requirements Point of
supply MSB
1 load
Example: Simel bars which consist of a number of 30A
adjacent conducting bare copper laminates coated with a
90m
black self-extinguishable PVC compound
final subcircuit
Three-phase circuit:
EXAMPLES
(See T3_19) 2) From Table 12, one can see that 35mm2 cable can carry 110A.
As there are two circuits in parallel and ambient temperature is 500C, (Col. 6)
different from standard 400C,
Derating factor for cable bunching = 0.8 (Table 22, col.5)
Derating factor for 50oC ambient = 0.82 (Table 27.1, col.9)
60
Hence the maximum current that can be carried by each cable without
58 exceeding 750C temperature limit: 110A X 0.8 X 0.82=72.16A 60 62
Formula for calculating permissible short-circuit current of cable: Solution:
Example 4: From question, one can see that the cable size is 95mm 2 and cable type belongs to column 4.
Then one can find
r=0.47mV/(A m)=0.47m /m; x=0.18mV/(A m)=0.18m /m; z=0.50mV/(A m)=0.50m /m.
where K=111, t=1s and I=10kA. • Per-meter impedance, per-meter resistance and per-meter reactance of each conductor
where K=143, t=1s and I=10kA. • Voltage regulation along the cable L
65
Kraft paper wound around winding conductors essentially a polychlorinated biphenyl (PCB)
paper impregnated with liquid dielectric to exclude air
1 bubbles and to provide good thermal circulation for heat
artificial insulating oil which is almost non-
dissipation. flammable.
LIQUID INSULATION Use mineral oil in most applications toxic effects, particularly if heated or burnt
Such oil is highly flammable. Transformers are generally now banned from use in most countries
limited to Class A materials temperature rise limits of
about 60-70oC. Outdoor use only. some PCB insulated transformers still in service
Moisture is a major problem.
5 7 9
Refined from petroleum Mixtures of synthetic organic chemicals with same basic
chemical structure and similar physical properties ranging
Hydrocarbon compounds: paraffinic, napthenic, aromatic. from oily liquids to waxy solids.
Additives sometimes added: Non-flammable, chemically stable, high boiling point and
Inhibitors to retard oxidation of oil electrical insulating properties.
Passivators to retard formation of copper sludge Used in many industrial and commercial applications
including electrical, heat transfer, and hydraulic
Examples: equipment; as plasticizers in paints, plastics and rubber
Shell Diala Oil B: straight mineral napthenic solvent refined oil products; in pigments, dyes and carbonless copy paper
Shell Diala Oil BX: Diala B with added oxidation inhibitor and many other applications
Health effects: carcinogenic (cancer) and non-
carcinogenic (effects on immune system, nervous
system)
Oil insulated distribution transformer
ONAN cooled type (Oil Natural Air Natural) 6 8 10
Silicone oil Open winding type
convective heat dissipation coefficient not so good problem with moisture ingress
electrical properties very similar to mineral oil increase dielectric losses in insulation (dielectric
dissipation factor)
more expensive reduce insulation strength
Ester
a b c
a b c
A B C A B C
a b c a b c
Parallel Operation
If transformers are used in parallel, ensure they have:
same voltage ratios
If not, will cause circulating current, overheating
same tap points in use (i.e. same voltage)
1
same vector diagram (same phase shift)
If not, line and phase voltages will be intermixed.
Overstress insulation. CONSTRUCTION
same internal impedance (preferable)
If not, will cause unequal loading Types of transformer winding
(a) Concentric, (b) Sandwich made up of disc sections.
30 32 34
Equivalent circuit:
2
Lumped equivalent circuit referred to the primary side:
EQUIVALENT CIRCUITS Equivalent circuit referred to the primary side:
35 37 39
Equivalent circuit:
Phasor diagram
36 38 40
(iv) Core loss and winding (load) loss in case b) of (iii)
Solution: (iii) b) I2=25A at 0.8 lagging PF
Thus
When the secondary side is short-circuited, impedance Z determines the Total loss = 1616 W
fault current. This is the method to determine transformer impedance Z
(Short Circuit Test). (v) Efficiency at full load at unity power factor
Secondary is shorted and primary volts are raised until rated current I2 flows
in secondary. Then
Full load |S|=10kVA
Unity power factor p.f.=1
Since I1 is rated current value [1 per unit or 100%], then Z%=V1(test) [p.u.]
X value can be found from
The transformer nameplate normally gives a percentage value for Z, which 4000/400V
is termed the Impedance Voltage. 10 kVA transformer
R is total winding resistance and can be measured with a resistance meter.
Very temperature dependent. Thus it should be measured at normal Normally V2=400V, V2=4000V.
operating temperature. Difference between R at ambient and operating
temperature may be as much as 30%. 41 43 45
Example: (iii) Input current a) Secondary is open-circuit; b) I2=25A at 0.8 lagging PF.
4000/400V 10kVA transformer:
Primary winding resistance: Rp=13 (in phase with V1) (lag V1 by 90o)
Secondary winding resistance: Rs=0.15
Total leakage reactance referred to primary: X=45
Magnetizing reactance referred to primary: X m=6k Hence
Core loss resistance referred to primary: Rc=12k
Determine:
When
3
Thus, referred to primary:
Normally V2=400V.
4000/400V
10 kVA transformer
42 44 46
Core loss:
Two components of transformer losses:
load (copper) loss in resistance of windings
load-dependent
scales as square of load current 4
temperature-dependent
TRANSFORMER EFFICIENCY
core (iron) loss in the core material
comprise hysteresis and eddy current losses
constant whenever transformer is energised
and independent of load
47 49 51
Efficiency
Copper loss: Power efficiency
For a load with voltage V2, current I2 and power factor cos ,
48 50 52
MEPS Harmonics problem from
Efficiency (Cont’d) AS2374.1.2-2003 Power Transformer Part 1.2: non-sinusoidal supply voltage;
Minimum Energy Performance Standard (MEPS) non-sinusoidal current due to non-linear loads.
Very efficient, typically 95 – 99% requirement for distribution transformers. Both core loss and copper loss in transformer are frequency
Varies with load dependent.
Power efficiency determined at 50% of rated load
For a given power factor, maximum efficiency occurs when at unity power factor. Effect of load current harmonics on voltage across transformer
core loss =copper loss. is negligible. Hence core loss is still treated as constant. Pure
Apply to dry-type and oil- sinusoidal supply voltage is assumed in the analysis.
immersed type, 1 and 3
power transformers, 10kVA Only copper loss increase is considered when de-rating
to 2.5MVA, used in 11kV calculations are performed for the transformer.
and 22kV networks. 2 methods can be used to calculate de-rating factor:
Standard also defines Computer and Business Equipment Manufacturers Association
minimum efficiency levels (CBMEA) Crest Factor method. CBEMA crest factor method is
for "High Power Efficiency not widely used as it is not very accurate.
Transformers". IEEE K-factor method: more accurate; normally adopted.
53 55 57
59 61 63
Example:
100kW of personal
100kW of personal computers are supplied from transformer rated
computers are supplied Amorphous metal. Very low loss.
at 150kVA and with a typical value of PEC(R) =10%. Calculate Eg. HB1 from Metglass
from transformer rated
maximum permissible current and power by the transformer.
at 150kVA
Fault types
There are two major problems that can occur in electrical The prospective fault current varies at different points in the
1) Single line-to-ground fault (70% to 80%) (unsymmetrical fault)
systems: open circuits and short circuits. supply
2) Line-to-line fault (unsymmetrical fault)
3) Double line-to-ground fault (unsymmetrical fault)
Short circuit is the most dangerous because it can lead to very
4) Three-phase short-circuit fault (symmetrical fault) etc
high fault currents, which could cause equipment damage, fire,
injury, etc.
Type 2
Type 1
Fault calculation is necessary for the following purposes:
To choose equipment with proper short-circuit current ratings;
To design protection system for clearing the fault when it occurs. Example:
An 11kV-to-400/230V transformer has a prospective fault current
Type 3 Type 4 of 32kA at the secondary terminals. The consumers mains circuit
has a route length of 25m, using single-core 120mm2 active
conductors and 70mm2 neutral. The submains circuit has a
Zf = 0 route length of 35m, using 16mm2 multi-core cables.
We consider only bolted 3-phase faults. This type gives Determine prospective fault current at main switch board (MSB)
maximum fault current level at any location compared with other and distribution board (DB).
2 types of faults and represents worst case situations. 4 6
Solution:
When the cable size is not very
large, its reactance is small
compared with its resistance.
Hence reactance is ignored.
Total upstream impedance seen from secondary side of transformer is normalize electrical quantities
express voltage, current, kVA and impedance as
Assume cable temperature is 45oC. From Table 34 of percentages (per unit values) of their base values
AS3008.1, impedance of consumers mains (1 phase) is
simplify calculations substantially.
Prospective fault current at main switchboard: transformer treated as a simple impedance (no
Assume cable temperature is 45oC. From Table 35 of AS3008.1, impedance of need for ratio).
the submains (1 phase) is
7 9 11
11-17
8 10 12
Three-phase systems
13 15 17
Example: Example:
14 16 18
j0.24 Vb=33kV j0.24 Vb=33kV
Vb=11kV j0.2 j0.575 Vb=11kV j0.2 j0.575
19 21 23
Vb=132kV
Sb=100MVA
20 22 24
Multiplier due to DC component in the fault current
Sources of fault currents:
electrical utility supply grid system
: the total fault current is addition of DC and AC components.
any in-house generation systems operating at
time of the fault
any motors operating within the system at time of We can see that the rms value of asymmetrical fault current i(t) or
the fault total fault current equals the rms value of ac component iac(t) of the
fault current times an “asymmetry factor” K(t). -
any electrical storage elements in the system (e.g X/R or L/R ratio is relatively small at distribution side or consumer side
capacitors) - due to relatively large resistance seen towards the source. Then the time-
varying term in the K(t) expression decays fast to zero. Hence DC
component has small influence on overall fault current. That is to say, in the
fault current, DC component can be ignored.
25 27 29
But when the fault occurs close to large generators, X/R ratio is very large
Fault impedance variation: DC offset: due to small resistance in the generators, the time-varying term decays
slowly in the K(t) expression. In such case, the influence of DC component
on total fault current must be taken into account.
For the utility supply, source impedance is Offset can increase initial current levels substantially
Within our concern, fault occurs at the distribution side. Hence
constant (a stiff source) influence of DC component is ignored and K is equal to 1.
For in-house generators or motors, impedance is Magnitude of DC offset level is governed primarily
Therefore, when calculating fault current at distribution side, one only needs
time-varying, depending on the time after the by X/R ratio of faulted circuit to calculate the rms value of ac component in the fault current or Iac.
short circuit:
sub-transient reactance (Xd” ) It is also dependent on angle of voltage waveform
at which fault occurs X
transient reactance (Xd’ )
synchronous reactance (Xs ) X
26 28 30
Example
Procedure: A three phase power system is shown below, where Bus 1 is connected to a utility supply with a
fault level of 100MVA and a pure inductive internal impedance.
Convert all impedances to per unit values Three phase four wire cables between Bus 2 and Bus 3 are 4X 300 mm2 Cu/pvc/pvc as given in
the column 7 of Table 4D1B and its length is 150m.
Draw one-phase equivalent circuit in per unit,
including all possible sources modeled as ideal
3 voltage source with their source impedance
Simplify the circuit and reduce it to
FAULT CALCULATION METHODS
Choose a power base of 1MVA and voltage base of 22kV at Bus 1 for the following computation.
s.c. Calculate maximum fault current in amperes for fault at 1) Bus 2; 2) Bus 3 respectively.
Ignore contribution by loads to fault currents. Use both approximate and exact methods to
compute fault currents. Compare the results.
Normally Vth=1, taken as reference phasor.
31 33 35
Assumptions: Then fault current and fault power in per unit value are:
IET Wiring Regulations, BS 7671_2008: See T3_18
(m /m)
and
RG
Source fault level: 100MVA and inductive internal impedance. rpm xpm
4X70 mm2 0.3175 0.09238
4X 120 mm2 0.1848 0.0866
4X 300 mm2 0.0751 0.0808
O.C. 4X 400 mm2 0.0606 0.0808
Current base in The motors in group M1 are identical, so are motors in group M2. Use the average sub-
cable region: transient reactance of 25% and a typical X/R ratio of 6 to calculate impedance of the
motor in the fault analysis.
ZLoad Calculate the maximum symmetrical component or ac component of fault current, if a
bolted three-phase symmetrical fault occurs at (1) point F1, (2) point F2.
Solution:
Thevenin impedance as viewed from bus 3: Common base values
The base MVA is selected as 1MVA and the base kV at load side as 0.4 kV. The base
impedance and base current can then be obtained as follows:
Generally, ZLoad is very large compared with addition of cable, transformer and source Exact method:
impedances. So it can be treated as open circuit unless its impedance is given and is required to
be used in calculation. Approximate method:
In this case, it is not given. So it is treated as open circuit. Utility fault level
The utility fault level is given as 800 MVA with a X/R ratio of 15. The values for the
common base of the equivalent utility resistance Ru and Xu can be obtained as follows:
where If is the fault current resulting from bolted three-phase symmetrical fault.
38 40 42
Base impedance on the utility side: Fault at location F1 or at bus 2: Fault at location F2 or at bus 3
(P.34)
Transformer impedance
The 1000 kVA transformer has an impedance of 5.75% on 1000 kVA and the value of
resistance is 1.21%. The reactance can be obtained by
So X/R ratio for the fault at F1 or bus 2 is 0.04817/0.01021=4.72, the corresponding time
As the transformer rating of 1000 kVA is the same as the base MVA, the percentage
values of the transformer resistance (RT) and reactance (XT) remain the same. constant is 4.72/(2*3.14159*50)=0.015s.
The bolted three-phase symmetrical fault current at F1 is calculated as follows:
43 45 47
70 mm2 cable with a length of 30m IEEE standard on fault calculation allows the following simplified calculation of Thevenin Fault at location F2 or at bus 3
impedance:
The per unit values of the resistance and reactance of the 70 mm2 cable for a length of
30 m can be obtained as follows:
Motor groups
The average sub-transient reactance is 25% based on the total rating of a group of
motors. Based on a typical X/R ratio of 6, the resistance is 25%/6=4.167%.
The values of the equivalent resistances and reactances converted to the common base
for the motor groups M1 and M2 are:
So X/R ratio for the fault at F3 or bus 3 is 0.0896/0.0445=2.01, the corresponding time
(P. 17) constant is 2.01/(2*3.14159*50)=0.0064s.
The bolted three-phase symmetrical fault current at F2 is calculated as follows:
300 mm2 cable with a length of 100m or 10*1443=14.43 kA.
Exact solution:
Since the X/R is well less than 15, the multiplying factor calculated by
One can see that these two methods produce very close results for this case.
44 46 48
Use IEEE recommended method to calculate Thevenin impedance as viewed from bus Transient in R-L circuit (Cont’d) Exercise: Prove the solution given on the earlier page.
3:
(1)
The transient term is zero right from the beginning and the current waveform is or
symmetrical;
In this case, there is a discrepancy between these two methods, but negligible one. (4)
where
In the above analysis, the resistance load and other unknown loads such as loads
from third branch in the circuit diagram are normally ignored when calculating fault The transient term attains its maximum amplitude. By comparing two sides of equation (4), one can obtain
current at each bus.
From (3)
So the solution is
49 51 53
Multiplier due to DC component in the fault current Example of zero and maximum DC component: Definition of unit value of voltage drop in mV/(m A) for three-phase
cable
Switch is turned on at t=0. Determine the current flowing through the circuit Zero DC component
for t 0. Three-phase voltage drop: V1+V2
V1 - V2
+ IA + +
V- S IB VR IC -IB
- V2 + -
IC V1
IA
IB
where
50 52 54
Appendix D FAULT CALCULATION DATA AND EXAMPLE
where
Z is the impedance in referred to each conductor or the impedance
in one phase equivalent circuit of the three phase cable;
zpm is per meter impedance referred to each conductor of the three
phase cable;
Vc(3 ) is the unit value of voltage drop for the three phase cable given
in Table 4D1B.
V1+V2
V1 - V2
+ IA + +
VS IB VR IC -IB
- - + -
V2 V1
IC IA
IB
55 57 59
56 58 60
CT selection 750A
The University of New South Wales =6.25A
Standard CT current rating at the secondary side is 5 A. 600:5 X
Standard CT ratios
50:5 100:5 150:5 200:5 250:5 300:5 400:5 450:5 750A
500:5 600:5 800:5 900:5 1000:5 1200:5 1500:5 1600:5 =4.69A
800:5
2000:5 2400:5 2500:5 3000:5 3200:5 4000:5 5000:5 6000:5
CT Equivalent Circuit:
61 1 3
6.1 Basic components of an overcurrent protection system Fault clearing time by a protection system:
An overcurrent protection system has three basic components: tclear=trelay+tbreaker=ttrip+tbreaker AB A++B-
1.Current transformers
It is defined as the time difference between the
2.Relays (Electro-mechanic relaying and microprocessor based relaying)
moment fault occurs and the moment fault is cleared.
3.Circuit breakers
Breaker’s contacts parting
An example of protection system: An induction-disc-type electromechanical relay:
CT
X X X
trelay tbreaker
time, the circuit breaker opens the main circuit. than that of the inverse-time
relay.
tclear=trelay+tbreaker
tclear=ttrip+tbreaker
I/Ipickup
trelay 0 tclear tbreaker 3.3) Extremely-inverse-time:
An extremely-inverse relay gives the steepest time-current characteristic.
tclear=ttrip+tbreaker
trelay tbreaker
trelay tbreaker
tclear
5 7 9
2) Definite-time or fixed-time relays, which operate after a definite or fixed 3.4) Inverse definite minimum time (IDMT) relays, which have inverse Tap setting or pick-up current setting or plug setting (PS) of an
time delay. time/current characteristics. overcurrent relay
For this relay, when the detected current is equal to Typical IDMT time-delay over-current relay can be described mathematically
or greater than Ipickup, the relay sends a trip signal to by:
circuit breaker after a delay time of ttrip. Then the
circuit breaker opens the main circuit after a delay of
its interrupting time. where IPS=tap setting or pick-up current setting or plug setting (PS) of the
X X
Both Ipickup and ttrip are set values. relay;
k=time-dial setting(TDS) or time multiplier setting (TMS);
tclear=ttrip+tbreaker
I=Current level in secondary side of CT in amps;
t=relay operating time in seconds; Two methods of tap setting or plug setting for phase overcurrent
and are constants for a given relay. protection:
tclear=ttrip+tbreaker 1) A percentage of the CT secondary rated current (5A).
PS=200% Ipickup=200%X5A=10A
6 8 10
Typical commercial overcurrent relay 6.2 Instantaneous and time-delay over-current protection scheme
design
Example 6.2 The one-line diagram of a power system is shown in Figure
Current tap
6.1a. The neutrals of the generator and two transformers are solidly
setting:
grounded. The system data expressed in per unit on a common 100-MVA 1.0
For a multiples of 10,
base is tabulated below. 1.2
TDS 1 results in trelay 1.5
Item MVA Voltage X1
=0.2s delay; Item Base Voltage X1 rating Rating
2.0
2.5
TDS 7 1.9s delay; MVA Rating X X Xs T1 100 20/220 kV 0.10 3.0
GEN 100 20 kV 0.05 0.15 1.0 T2 100 220/20 kV 0.10 3.5
TDS 11 2.9s delay. TL 100 220 kV 0.125 4.0
5.0
X
6.0
Figure 6.1a Single-line 7.0
diagram of the power
8.0
system under study
X 10.0
12.0
The system base values are 100MVA and 20 kV in the generator region.
Figure 6.1b Relay time
X The load level is 100MVA with a rated voltage of 20kV and a lagging power versus current curve
factor of 0.95.
trelay tbreaker Design an overcurrent protection scheme at bus 4 with the circuit breaker
installed close to load as shown in Figure 6.1a.
11 13 15
Example 6.1 A relay is selected to protect a distribution feeder. The fault 1) Three identical CTs are used for three phases. Choose a proper CT ratio Solution: Base:100MVA and 20 kV
current through CT primary side is 2000A and CT ratio is 200:5. PS=200%. from the table below. So CT ratio is 3000:5.
1) Load current
Find the operating times for the time dial settings of 2, 50:5 100:5 150:5 200:5 250:5 300:5 400:5 450:5
if a CO-8 relay is selected and the time current curve is shown in figure 500:5 600:5 800:5 900:5 1000:5 1200:5 1500:5 1600:5 2) Use 90% of the rms value of the ac component of bolted three-phase
below; 2000:5 2400:5 2500:5 3000:5 3200:5 4000:5 5000:5 6000:5 symmetrical fault current during transient period to determine the
if an IDMT relay is selected and the time current curve is represented by current tap setting of the instantaneous relay;
2) Use 90% of the rms value of the ac component of bolted three-phase
Thevenin equivalent impedance as
symmetrical fault current during transient period to determine the
viewed towards source side at the
current tap setting of the instantaneous relay.
place where circuit breaker is
installed:
Solution: 3) A time-delay protection scheme is installed as well to protect the system
The current through the for less severe faults. The time-delay relay has a time/current
relay=2000/40=50A. characteristic shown in Figure 6.1b. The pickup current of the relay is set Fault current during transient period
For PS=200%, the pickup current equal to 150% of the nominal operating current referred to the secondary
is 200%×5=10A of CT. Determine the relay current tap setting and time dial setting.
and the multiples of current tap The selected time dial settings of the relay should result in minimum
setting is 50/10=5. delay time. So the primary side fault current is 6.0768 kA. The chosen CT has a ratio of
For the CO-8: the operating time
4) Draw the three-phase connection diagram including CT, relays and trip coil 3000:5. Thus the secondary current of the CT is 6077 /(3000:5)=10.13 A.
from figure is 0.75s.
of circuit breaker and circuit breaker for the protection schemes in 2) and The current tap setting of the instantaneous relay is set as 90%* 10.13 A or
3) above. Also include a manual trip function. 9.12 A.
For the IDMT: 100MVA Item MVA Voltage X1
X
the operating time from using The rated interrupting time of the circuit breaker is 4 cycles. 20 kV rating Rating
equation is 8.6s. Ignore the contribution by the load to the fault current. The system T1 100 20/220 kV 0.10
frequency is 50Hz. T2 100 220/20 kV 0.10
12 14 TL 100 220 kV 0.125 16
3) The current base at load side is The coordination time interval (CTI) or discrimination time is the time
interval between the primary and remote backup protective devices.
Load current is also equal to 2.887 kA. The pickup current is 2.887 kA X It is the difference between the time t2 that the backup relaying operates
150%/(3000:5)=7.22 A. So the current tap setting of the time-delay relay is and the time t1 that circuit breakers clear the fault under primary relaying.
chosen as 8.0 A. t0: the instant that fault occurs;
CTI
The selected time dial settings of the relay should result in minimum delay t1: the instant that fault is supposed to be cleared
time. So 0.5 or 1/2 time dial setting is chosen. t by primary protection;
t2: the instant that backup protection relay contacts
t0 t1 t2 close and breaker trip coil is energized due to the
same fault in case that primary protection fails;
Current tap setting: t2-t1: the discrimination time or CTI.
1.0
1.2 Example: For the fault below at F1, t1 is fault clearing moment by the
1.5 protection at bus B. t2 is the time moment for the relay at bus A to send out
2.0 trip signal to C.B.1.
2.5 F1
3.0 51:Time-delay
overcurrent relay
X
3.5
4.0 51B:
5.0
t1-t0(clear)=ttripB+tbreaker2
6.0
100MVA
7.0
20 kV 8.0 51A:
10.0 t2-t0=ttripA
12.0
17 19 21
4) The circuit connection diagram is shown as below: 6.3 Radial system protection and relay coordination
Many radial systems are protected by time-delay overcurrent relays. When the protection at bus B acts properly to clear fault at F1, the relay at
bus A will drop off or be de-activated and ready for next fault.
Adjustable time delays can be selected such that the breaker closest to the
fault opens, while other upstream breakers with longer time delays remain
closed. That is, the relays can be coordinated to operate in sequence so as to F1
CTI
18 20 22
Coordination (or grading) methods Example 6-3
Time/current discrimination method Data for the 50-Hz radial system of Fig. 6.2 are given in Tables 6.4, 6.5 and
The inverse-time relays have the characteristics that the smaller the fault 6.6. Select current tap setting (CTSs or plug settings) and time-dial settings
current, the longer the trip time. (TDSs) to protect the system from faults. Use B1 as backup protection if B2
fails to operate.
1) t2-t1 CTI; F1 Assume three CO-8 relays for each breaker whose curve is given in Fig. 6.3,
2) t2 is minimum. X one for each phase, with a 0.3-second coordination time interval (CTI) or Figure 6.4 Circuit
discrimination time. The relays for each breaker are connected as shown in diagram of protection
t Figure 6.4, so that all three phases of the breaker open when a fault is system
detected on any one phase. Assume a 34.5-kV (line-to-line) voltage at buses
t0 t1 t2 1 and 2 during normal operation. Also, future load growth is already included
in Table 6.4, such that maximum loads over the operating life of the radial
By choosing proper values of time dial
system are given in this table.
setting and current tap setting for 51B and
51A, 51B can be designed to be the primary When selecting the current tap settings of relays, ensure that the ratio of Table 6.4 Maximum loads Table 6.5 Fault currents
protection for fault on Line2 and 51A be the pickup current to normal operating current is higher than but closest to Load S (MVA) Lagging p.f. Bus Maximum fault current Minimum fault current
back-up protection for the fault on Line2. In 150%. L1 10.0 0.95 (bolted three phase) (A) (L G or L L) (A)
the meantime, 51A serves as the primary L2 10.0 0.95 1 3000 2200
protection for faults on Line1. 2 2000 1500
51A
X Table 6.6 Breaker, CT, and relay data
Breaker Breaker operating time CT ratio Relay
51B
X
(Rated interrupting time)
B1 5 cycles 400:5 CO 8
Figure 6.2 Single line diagram of a power system
B2 5 cycles 200:5 CO 8
23 25 27
X
Bus Maximum fault current
(bolted three phase) (A)
1 3000
2 2000 tclear=ttrip+tbreaker
To meet coordination requirement: c) A time-delay protection scheme is designed for these eight feeder circuits
with the current-limiting reactor determined in (b). Three identical CO-8
Ttrip1-Tclear2 0.3s (CTI); So 1) Ttrip1 0.49s; 2) Ttrip1 is minimum. relays are used in the scheme with a time dial setting of 2. Select a CT
For the same fault at bus 2, the ratio of fault-to-pickup currents by B1 relay from Table below with the secondary current closest to 5 A under normal
is working condition. Then determine the current tap settings or plug
settings of the relays to ensure a ratio of pickup current to normal
TDS=0.5: Ttrip1=0.25s; working current larger than or equal to and closest to 140%. Determine
TDS=1: Ttrip1=0.61s; TDS=2: Ttrip1=1.10s.
the fault clearing time for bolted fault that results in maximum fault
So 1 is a suitable time dial setting for the relay at bus 1 as this results in a currents.
trip time of 0.61s, longer than 0.49s and being minimum. 20X200A
Standard CT ratios
50:5 100:5 150:5 200:5 250:5 300:5 400:5 450:5
500:5 600:5 800:5 900:5 1000:5 1200:5 1500:5 1600:5
Bus Maximum fault current Minimum fault current 2000:5 2400:5 2500:5 3000:5 3200:5 4000:5 5000:5 6000:5
(bolted three phase) (A) (L G or L L) (A)
1 3000 2200 When calculating fault current at one feeder branch, ignore current
2 2000 1500 contribution by other feeder branches to it.
TDS
Breaker Breaker operating time CT ratio Relay
(Rated interrupting time) Assume that the rated interrupting time of each circuit breaker is 4 cycles.
B1 5 cycles 400:5 CO 8 The system frequency is 50 Hz.
B2 5 cycles 200:5 CO 8
30 32 34
Solution: X
c)
(a) and (b) Select 100MVA and 220kV as Since the rated load current of each feeder branch is 200 A, in order to have Residual current devices (RCD)
the base values on the source side. a secondary current of CT equal to 5 A, the CT with a ratio of 200:5 is
The fault level of a source is defined as follows selected. It is also called earth leakage circuit breakers (ELCB)
According to the requirement that the ratio of pickup current to normal It prevents electrocution when current leaks through body to
where If is the value resulting from bolted three-phase working current is at least 140%, the current tap setting or plug setting or general ground mass earth
symmetrical fault at the source terminal. pickup current setting of the relays is 140%*5A=7A, which is selectable from It provides protection by tripping when earth leakage current
current tap settings of the CO-8 relays (see graph in the question). exceeds limit
For the given source,
From solutions (a) and (b), the maximum fault current with the current- 30mA 0.3s RCDs required for
Then the source internal positive-sequence impedance or reactance here is limiting reactor is 20 times continuous load current, thus the multiples of the
circuits supplying lighting and socket outlets in domestic
current tap setting for this bolted three-phase fault that results in maximum
installations
fault current is
Given the chosen bases, the per-unit source reactance is socket outlet circuits in residential sections of other electrical
installations
problem of nuisance tripping
Alternatively, since voltage base in the source region is the same as voltage
rating of the source
The per-unit transformer reactance
If,pu=Sf,pu , if Vs=1pu.
Without the current-limiting reactor, the maximum fault current flowing
through the circuit breaker, which results from bolted three-phase
symmetrical fault, is determined by
35 37 39
Its value in amperes is The fault clearing time by the circuit breaker for tclear=ttrip+tbreaker
the fault with maximum fault current is
This is the fault current flowing through the circuit breaker without current- approximately equal to 0.35+4*0.02=0.43s.
limiting reactor.
so the fault current without current-limiting reactor is almost
70 times the normal operating current.
To limit the fault current to 20 times rated continuous current of 200A, the
per-unit reactance of the current-limiting reactor can be found by
36 38 40
RCD level of sensitivity
• Type 1: rated tripping current < 10mA, mainly for protection of single
appliances and in various hospital situations
• Type 2: rated tripping current between 10mA - 30mA protect final sub-
circuits where a group of appliances require protection against direct
contact (resulting in ventricular fibrillation)
• Type 3: rated tripping current > 30mA, protect heavier equipment where
protection against indirect contact only is required.
AS/NZS 60898.1:2004
Electrical accessories – circuit breakers for
overcurrent protection for household and
similar installations.
41 43 45
Preferred values of rated continuous current for miniature circuit breaker (MCB)
or fuses: 6, 8, 10, 13, 16, 20, 25 32, 40, 50, 63, 80, 100, 125A.
42 44 46
The University of New South Wales
General requirements:
low impedance path (resistance and reactance) to
earth conductor of local supply system and thence
to earth of supply at main substation
items that need earthing (eg metal casings) must be
School of Electrical Engineering connected to main earth by conductors of low
and Telecommunications
enough impedance to provide equipotential
bonding between all equipment items. Avoid earth
loops
earth potential rise (EPR) or ground potential rise
(GPR) associated with any fault current must be
limited to safe levels
earth conductors capable of handling fault current
without thermal or mechanical damage
47
1 3
48 2 4
MEN system:
2
3
METHODS OF
POWER SYSTEM EARTHING SYSTEMS OF EARTHING
IN LOW-VOLTAGE INSTALLATIONS
earth connections to neutral at consumers
installation and along route to supply substation
neutral provides the return path
balancing of load to utilize phase current cancellation
in return neutral to minimize voltage drop
5 7 9
6 8 10
Common Multiple Earthed Neutral (CMEN) system: Equipotential bonding
Equipotential bonding is an electrical connection intended to
prevent the occurrence of dangerous touch voltages between
simultaneously accessible conductive parts.
Such parts may be exposed conductive parts, in other words
metal casings for electrical equipment, or extraneous conductive
parts, such as conductive structures or pipes in buildings. 4
For safety and protective purposes the equipotential bonding
should have a potential approaching that of earth potential.
In each building a main equipotential bonding conductor shall TYPES OF EARTHING SYSTEMS
Stobie Poles incorporate steel H-bars with
concrete core.
interconnect at the entrance point of the supplies for the following IN CONSUMER’S INSTALLATIONS
conductive parts:
Main protective conductor; Main earthing conductor or main
earthing terminal; PEN conductor in TN-C system; Water pipes;
gas pipes; risers of central heating and air conditioning systems
as well as metallic parts of building structure and other metal
pipework.
11 13 15
12 14 16
1st letter (I or T) gives relationship of supply to earth TN systems: one point of supply is directly earthed; Exposed TT system: one point of supply is directly earthed; Exposed
conductive parts of loads are electrically connected to that point conductive parts of loads are connected to earth via separate
T (terra): direct connection of one point of supply by protective earth (PE) conductor. earth electrode.
system to earth TN systems can be divided into:
I (insulation): all live parts of supply isolated from 1) TN-S system;
earth or one point connected to earth through a very 2) TN-C system;
large impedance 3) TN-C-S system.
T T
TN-S
Y T I 17 Y
19 21
2nd letter (T or N) gives relationship of exposed TN-C system: Neutral conductor (N) and protective earth (PE) IT system: There is either no direct connection or very large
conductive parts of the general installation to earth conductor are combined into a single conductor throughout impedance between supply and earth; exposed conductive parts
of loads are connected to earth through independent earth
T (terra): direct connection of exposed conductive electrode.
parts to earth, independent of earthing of supply TN-C
system
N (neutral): direct connection of exposed conductive Large
N N TN-CS
T
Load Loads
18 20 22
Summary on earthing systems Resistance of a grounding or earthing system with
hemisphere electrode in homogeneous soil
Earth resistance determined by:
shape of electrode(s)
Y extent of electrode(s)
electrical resistivity of the soil
Mud (compressed coal): 1 m,
Wet soil: 10 m,
Moist soil: 100 m,
Dry soil: 1000 m, The current density at radius r is expressed as follows
Rock: 10000 m.
23 25 27
Resistance of a grounding or earthing system with The potential on the electrode can be determined by
hemisphere electrode in homogeneous soil
5
So the resistance of the grounding system is
EARTH RESISTANCE OF
A GROUNDING SYSTEM WITH BURIED Alternatively, consider each individual shell with a radius x and a thickness dx,
ELECTRODES the total resistance R up to a large radius r would be
When
24 26 28
Potential rise at point X on the surface of a ground due to current flowing 2. Transferred Voltage: if person touches a conductor connected
into a hemisphere electrode to potential zero, he/she is subject to voltage
Transferred voltage
soil
29 31 33
1. Touch Voltage: if person touches tower conductor, he/she is 3. Step Voltage: if person walks nearby, he/she is subject to
subject to voltage voltage
(Usually r3-r2=1m)
30 32 34
A single rod grounding system can be replaced by a Two-hemisphere grounding system that is equivalent to two-rod
hemisphere electrode grounding system with equal system:
grounding resistance:
7
The potential on the left hemisphere is
EARTH RESISTANCE OF
TYPICAL GROUNDING SYSTEMS where or
The radius r0 of the hemisphere is calculated by
Since the left-hand side hemisphere is connected electrically with the right-hand side
hemisphere,
35 37 39
where d is the diameter of the rod, r is its radius and is its Solution:
length. Each rod is first replaced by a hemispherical electrode of radius r0, Soil
which has the same earth resistance as one-rod system.
Example Radius of the hemisphere of the equivalent hemispheresystem can
Calculate the resistance to earth of a 0.016 m diameter rod, 2.4 m be found from
long, with soil resistivity as 100 m. where R is the grounding resistance of one-rod system and is equal
to
36 38 40
Grounding grid at substation: A grounding system that consists Solution:
of a number of interconnected, bare conductors buried in the In terms of potential calculation
earth, providing a common ground for electrical devices or on the first conductor E1, the
metallic structures, usually in one specific location, such as original grounding structure can
be decomposed into the
distribution substation.
following four as shown below.
MEASUREMENT OF
EARTH RESISTANCE
Exercise: Solution:
A grounding system is composed of four Due to the symmetry of the system, the currents
identical conductive rods, each of which is flowing into four rods are the same. Assume that
planted in the earth vertically, and has a the current flowing into each rod is I.
diameter of 2r (m) and an effective grounding The voltage at electrode E1 is given by:
length of l (m). The cross sections of the four
rods form a square as shown in the R.H.S.
figure and they are electrically connected
above the earth. The distance between any
two neighboring rods is D (m). The resistivity The terminals of the four electrodes above the earth are electrically
of the earth is (ohm m). connected, so
Each rod can be replaced by an equivalent hemisphere with its radius
equal to r0 (m). r0 is calculated by the following expression:
Thus the resistance of the grounding system is
Derive an expression that can be used to calculate the effective where r0 is determined by or
resistance of this grounding system.
Assume that D is much larger than r0, and the earth soil is Given that r=0.016(m), l=2.4(m), D=5 (m) and =100 (ohm m), the
homogeneous. numerical value of the resistance of the grounding system is
Given that r=0.016(m), l=2.4(m), D=5 (m) and =100 (ohm m),
calculate the numerical value of the resistance of the grounding
system. 42 44 46
Fall-of-potential method to measure resistance of a grounding system
Fall-of-potential method to measure resistance of a grounding system (cont’d) The University of New South Wales
When the ratio of V to I is plotted as a function of the potential probe distance x, curves
similar to those shown below are produced.
R D1<D2
RG
48 2
Aim is to protect:
People
2
Buildings and Contents
against damaging effects of lightning strikes. PHYSICS OF LIGHTNING
3 5 7
Storms
Lightning is very common event. Worldwide, some
30 lightning flashes occur in every second on Collision among ice crystals
average. and water droplets
Frequency of occurrence of lightning and
thunderstorms varies significantly with location. Charge separation
www.erico.com
4 6 8
Lightning protection systems (LPS) are
designed to ensure that lightning terminates
on an air terminal (lightning rod) instead of on
some other parts of building.
Lightning Detectors: storm-tracking instruments, which Ground flash consists of a sequence of high-
analyze storm and lightning activity.
amplitude short-duration current impulses
e.g. The THUNDERBOLT “Lightningman” and (strokes).
“Stormchaser”: handheld portable device can detect
electromagnetic signal from lightnings, from as far as Currents are uni-directional, and usually negative
120 km away. (negative charge injected into struck object).
Electrical. 3
Thermal ELEMENTS OF
Mechanical A LIGHTNING PROTECTION SYSTEM
15 17 19
Cause death or serious injury in various ways : Lightning protection system (LPS) components:
Direct strikes to person causing heart Air terminals
failure, brain damage, suspension of
breathing, burns, etc. Down conductors
22 24
Combined utilities enclosure [Fig E2, AS/NZS1768:2003] 26
Products of interception of lightning by lightning protection system
ERICO company
STANDARDS ON
1.2/50 s unidirectional pulse 8/20 s unidirectional pulse
LIGHTNING PROTECTION
33 35 37
39 41 43
40 42 44
5.2 Protection of structures
45 47
Typical LPS using metal in or on a building [Fig 4.4 AS1768:2007] 49
46 48 50
5.3 Voltage calculation
52 54 56
Crowbar devices
Air spark gaps or gas discharge tubes
SCR and triacs
Clamping devices
Metal oxide varistors (MOV)
Avalanche diodes (Zener diodes)
Switching and rectifier silicon diodes
Isolators
Opto-isolators
Isolation transformers
Common-mode filters
57 59 61
OVERVOLTAGE PROTECTION
IN LOW-VOLTAGE SYSTEMS
58 60 62
1. Cone of Protection Method
Appendix
An improved Electrogeometric
model developed by Eriksson.
School of Electrical Engineering
and Telecommunications
Allows for computation of
parabolic-like lightning
collection volumes for all
Industrial and Commercial Power Systems
potential strike points on a
Topic 9
building .
Volume protected with vertical rod near building’s edge.
POWER QUALITY, REACTIVE POWER
AND POWER FACTOR CORRECTION
www.erico.com
69 71 1
Simplified classification of quality of supply by EnergyAustralia Summary of power quality problems [Ref: R.C. Dugan]
(ENOS Electricity Network Operation Standards, June 2006)
9 11 13
10 12 14
Waveform distortion: Inter-harmonics Waveform distortion – Notching Voltage fluctuation:
Caused by waveforms that have frequency components Rapid changes in voltage within allowable limits of
that are not integral multiples of fundamental (50Hz) nominal voltage
Main causes are static frequency converters, cyclo- AS60038-2000 specifies new standard nominal voltage
converters, induction motors, arcing devices. to be 230V (reduced from 240V). Tolerance is +10% to -
6% which means actual supply voltage range will not
Can cause light flicker, audible noise in audio equipment,
necessarily be lowered.
vibration in induction machines.
EnergyAustralia aim to maintain steady-state voltage
Allowable limits specified in IEC Std 1000.3.9
Voltage notching caused by three-phase converter (ten-minute average) within +/-10% of nominal voltage of
Mains signaling voltages, injected onto network by the 240V (i.e. between 264V and 216V), at consumer’s
utility, e.g. 492, 750 and 1050 Hz. terminals. If possible, it will aim for 226-253V range.
15 17 19
Periodic voltage disturbance caused by switching Any unwanted signals that cannot be classified as
operation of power electronic devices (current harmonic distortion or transients and have spectral
commutation) content < 200 kHz
Extent of distortion determined by depth and width of Caused by power electronic devices, control circuits,
notch arcing equipment, switching power supplies.
Frequency components due to notching can be quite Improper grounding exacerbates problem.
high
In Australia, acceptable limits set by Spectrum
Present Australian standards limit notch depth to 20% of Management Agency.
peak supply voltage at point of common coupling. Voltage flicker caused by arc furnace operation
Note: Flicker can cause lamps to blink rapidly, and is visible to human
eyes at flickering frequencies of 6-8Hz.
16 18 20
Power frequency variation:
Power frequency variation: • Very little distortion in sine wave voltage generated at power stations
Fourier Analysis
• Caused by non-linear loads at the end-users Any periodic waveform can be expressed as a Fourier series.
• Harmonic distortion = periodic distortion in every AC cycle Advantage of using Fourier series analysis
22 24 26
Effects of harmonics on power factor
Equipment for PQ investigations
27 29 31
For voltage:
(IEEE definition)
Note: IEC defines THD as % of total rms. The first component is called the displacement power factor :
Fluke 43 power quality Fluke 430 power quality
THDV is a meaningful parameter but THDI may not be. Analyzer (single phase) Analyzer (three phase)
A small current may have a high THDI but not be a problem. However it can be The second component resulting from harmonic distortions is
mis-interpreted as a serious power quality problem. This can be avoided by
called the distortion power factor :
referring THDI to the fundamental of the peak demand current rather than
fundamental of present sample. This is called total demand distortion (TDD).
The total power factor (also called true power factor) is:
33 35 37
Equivalent circuits:
REACTIVE POWER AND POWER FACTOR
CORRECTION
Most loads are net inductive and so they require reactive power to be supplied
by the source. Similarly overhead lines are net absorbers of reactive power.
The presence of inductive reactive power in a load means that the power factor
is reduced from unity.
The impedance seen by the n-th harmonic current source is: In principle the solution of the reactive power problem is obvious: it is to install
capacitors as required to alleviate the burden on supply for handling the
reactive power. This is the general principle of power factor correction.
34
where FL = fault level at pcc; Qc = VAr rating of capacitor. 36 38
POWER FACTOR CORRECTION
Use of unloaded synchronous motors to
Series connection:
power factor correction (PFC) installations or
compensate reactive power static VAR compensators (SVCs).
when over-excited, synchronous motor operates modular and separately switchable capacitor
at leading power factor and generates VARs banks, ranging from 7.5kVAR to 100kVAR or
higher
Advantages and disadvantages:
Reduction in total current I is small so improvement in loss in the line is
when under-excited, motor operates at lagging conventional automatic PFC system: switching
very small.
power factor and absorbs VARs using mechanical contactors
Series capacitance is very good for voltage regulation and for smoothing
voltage fluctuations.
solid-state switching systems: faster switching
Series capacitance helps to improve stability if line reactance is high.
Much less flexible in that capacitance value is not easily able to be with thyristors, typically ~20ms
changed.
resonance problem
39 41 43
Shunt connection:
45