TEMPERATURE-PRESSURE RELATIONSHIPS
Superheated
vapor
2
The temperature above 212°F is called 68 70
superheat. It is still measured in degrees.
Pressure, psig
Figure 2 shows an example. The tempera- 60
Pressure, Temperature,
ture of the steam at atmospheric pressure psig °F
50
is 232°F, which means that it has been
68 40
superheated 20°F (232°F – 212°F = 20°F). 28 5 40 Curve shows refrigerant
pressure-temperature
9 –22
characteristics
The principles are the same when you ana- 28 30
lyze the effect of superheat on a refriger-
ant. Figure 3 shows the effect of superheat 20
on 1 lb of liquid R-22. At atmospheric pres-
sure, the addition of heat makes it boil at 9 10
–41°F. After all the refrigerant vaporizes, –22
any added heat will raise its temperature
–40 –20 5 10 20 40
above –41°F, or superheat it. Note that it
Temperature, °F
takes 100 Btu (latent heat of vaporization)
to vaporize the entire pound of liquid R-22.
Adding more heat will superheat the vapor. Figure 4. Boiling points of R-22 at various pressures
If the temperature is raised to –21°F, the
vapor has been superheated 20°F.
Figure 4 above shows the boiling points of R-22 at
Figure 3 is only an example of the principle of super- various pressures. Note the curved line. It shows how
heat. In fact, service technicians do not work with any the saturation or boiling temperature changes as
refrigerant at atmospheric pressure. You already pressure changes. As the pressure increases, it
know that reducing pressure on a liquid lowers its takes a higher temperature for the refrigerant to boil.
boiling point. It then takes less heat to vaporize it. The curved line also represents the R-22 pressure-
Conversely, increasing the pressure on a liquid raises temperature characteristics. The horizontal line
the boiling temperature. shows the temperature in degrees Fahrenheit. The
20
Superheated
vapor
10
0
Temperature, °F
–10
20°F superheat [(–21°F) – (–41°F) = 20°F]
–20
Boiling point Point of complete
–30 vaporization
Saturated R-22 @ 14.7 psia
–40
–60
0* 10 20 30 40 50 60 70 80 90 100
Enthalpy, Btu/lb
3
vertical line shows pressure in psig. The dotted lines tubing wall, it causes the refrigerant in the coil to heat
in Figure 4 show some of the coordinates on the up and boil. Assume that the refrigerant flow is at a
curve at which the refrigerant will boil. relatively slow rate. If this is the case, all the liquid
boils into vapor close to the entry point. You can see
Follow this relationship up and down the pressure- an example of this at point A in Figure 5, where the
temperature scale in Figure 4. You can determine a temperature is 20°F.
series of boiling points—for example, 40°F at 68 psig,
5°F at 28 psig, –22°F at 9 psig, etc. The curve itself From this point on, the boiling vapor picks up super-
is simply a line drawn through all of these points. heat. The farther the vapor travels and the longer it is
Other refrigerants have different curves. No two exposed to heat, the greater the superheat becomes.
refrigerants have identical pressure-temperature At point B, the vapor’s temperature is 30°F with 10°F
characteristics. superheat. At the fifth return bend, the temperature is
40°F with 20°F superheat.
THE EFFECTS OF SUPERHEAT ON A
REFRIGERATION SYSTEM Now look at point C. The difference between vapor
temperature (50°F) and boiling temperature (20°F)
Now that the basic principle of superheat has been equals 30°F of superheat. At this point, the suction
covered, let’s relate the various factors to a simple pressure of the compressor is 43 psig.
refrigeration system. Assume that the system consists
of a bare tube evaporator, compressor, condenser, Opening the hand expansion valve farther increases
and receiver. It also has the most basic of refrigerant the flow of refrigerant. Figure 6 shows the result. The
control devices, the hand-operated expansion valve. increased flow rate means that the refrigerant must
Figure 5 shows such a basic system. reach point B before complete vaporization takes
place. This reduces the evaporator coil surface that is
Opening the hand expansion valve slightly allows a available for building up superheat. As a result, there
small amount of refrigerant to enter the exposed coil. is only 20°F superheat at point C. Higher suction
Air around the coil is at a higher temperature than the pressure results from the greater load placed on the
refrigerant. When the heat from the air penetrates the compressor by the additional refrigerant.
Liquid line
Hand
expansion
valve Condenser
20°F Receiver
20°F
Point of complete
43 psig vaporization
A
30°F Head
10°F superheat pressure
B
40°F
20°F superheat
Compressor
43 psig suction pressure
50°F gas temperature
30°F superheat
4
Liquid line
Hand
expansion
valve Condenser
21°F Receiver
21°F
44 psig
A
21°F
Point of complete Head
B vaporization pressure
31°F
10°F superheat
Compressor
44 psig suction pressure
41°F gas temperature
20°F superheat
Now look at Figure 7. The hand expansion valve is damage to the compressor. The compressor is
open even farther. So much refrigerant flows that it designed to compress a gas, not a liquid.
cannot completely vaporize in the evaporator. This
causes liquid to flood back to the compressor. The These examples demonstrate the ideal evaporator
result is wasted refrigerant and greatly reduced com- condition. The goal is to keep the point of complete
pressor capacity. The greatest concern is possible vaporization at the outlet of the evaporator. Note in
Liquid line
Hand
expansion
valve Condenser
25°F Receiver
25°F
49 psig
A
25°F
Head
B pressure
Flood back
25°F
Compressor
49 psig suction pressure
25°F gas temperature
0°F superheat
5
Liquid line
Hand
expansion
valve Condenser
24°F Receiver
24°F
47.6 psig
A
24°F Head
Point of
B pressure
complete
vaporization
24°F
V
29°F
5°F superheat C
Compressor
47.6 psig suction pressure
34°F gas temperature
10°F superheat
Figure 8 that superheat is 0°F at point V. Ideally, the to open the valve. The addition of several degrees
entire surface of the evaporator performs its refriger- produces a steady, rated flow of refrigerant.
ation function. Only dry, superheated vapor reaches
the compressor. Figure 9 shows the level of efficiency achieved with
the TEV. You have seen that low superheat at the out-
In practice, it is impossible to obtain this condition. let of the evaporator is desired. Thus, you place the
However, the TEV allows you to reach a level close to TEV bulb at this point to measure this condition. In
the ideal. It takes only several degrees of superheat the proper position, its temperature will be about
equal to suction gas temperature.
Thermostatic
expansion valve
Before examining TEV operation in
Refrigerant saturation depth, first review the following terms.
temperature
They are closely associated with valve
operation:
6
SPORLAN VALVE COMPANY
Diaphragm case
Superheat. The heat added to vapor beyond the Capillary
point of complete vaporization. tube
Principal parts
Seat
Figure 10 shows the essential parts of a typical
Pin carrier
thermostatic expansion valve—the diaphragm
case, capillary tube, bulb, seat, pin carrier,
spring, spring guide, adjusting stem packing, Spring Bulb
adjusting stem, push rods, and inlet strainer. Spring
guide
Note that there is no direct mechanical linkage Inlet strainer
between the adjustment stem and the pin. The Adjusting
adjusting stem serves only to vary the spring stem
pressure. packing
Operation
➁
three fundamental pressures that affect the opening
and closing of this control device:
Bulb temperature = Evaporator pressure
saturation temperature
ª bulb pressure + superheat
ª spring pressure
ª
➂
evaporator pressure.
7
Point of complete
vaporization to determine the final pressure—that of the bulb. Bulb
pressure is applied through the capillary tube to the
top of the valve diaphragm. This pressure opposes
the sum of the evaporator pressure and the spring
Refrigerant saturation pressure. It acts to open the valve. When a system is
temperature operating, the bulb charge is part liquid refrigerant
Diaphragm and part saturated vapor. Bulb temperature equals
suction gas temperature. Suction gas temperature is
higher than refrigerant saturation temperature. The
Evaporator pressure increase is produced by superheat.
8
Superheat
by evaporator saturation temperature. They become
equal and opposing, canceling each other out. You
can see, then, that pressures induced by refrigerant Bulb
saturation temperature exert equal force. They act on
both sides of the diaphragm. This leaves superheat
and spring pressure the two factors that regulate the
valve. These two opposing factors maintain a delicate
pressure balance on both sides of the valve
Refrigerant saturation
diaphragm. This permits the valve to operate over a temperature
wide range of evaporator pressures. It can handle Bulb
pressure
light as well as heavy loads on the evaporator. The
thermostatic expansion valve is, in effect, a super-
heat regulator. Evaporator pressure
9
In a system idle for a long period of time, pressure in diaphragm. When this pressure can overcome the
the bulb and above the diaphragm will be almost combined evaporator pressure and spring tension
enough to overcome spring pressure and open the below the diaphragm, the valve opens. This restores
valve. Compressor start-up will immediately lower the or increases refrigerant flow into the evaporator.
refrigerant pressure under the diaphragm. The bulb
pressure will then be enough to oppose the spring When the system’s pressure or temperature control
pressure. It will force the diaphragm down and open stops the compressor, evaporator pressure immedi-
the valve. ately increases. This is because it is no longer sub-
ject to the compressor suction effect. It will increase
Liquid refrigerant will then flow through the open until the combined evaporator pressure and spring
valve as a spray. It will fill the evaporator with wet and tension pressure can overcome vapor pressure in the
saturated vapor. If all of the liquid refrigerant evapo- bulb and above the diaphragm. When it does, the
rates and becomes superheated vapor before it diaphragm raises and the TEV closes.
reaches the suction line, the thermal expansion valve
remains open. PRESSURE DROP ACROSS THE EVAPORATOR
The evaporator continues to absorb heat. The sur- This discussion of TEV operation has not yet consid-
rounding temperature will decrease until wet and sat- ered pressure drop through the evaporator. It was
urated vapor extends to the point in the suction line omitted for simplification. In actual system operation,
where the capillary tube bulb is clamped. When this however, pressure drop will exist and is a factor. To
occurs, the reduced degree of superheat cools the overcome the effect of pressure drop, inlet pressure
suction line and bulb. As a result, vapor pressure in is used to operate the valve.
the bulb and above the diaphragm decreases. This
permits spring pressure to close the valve, either Inlet evaporator pressure acts on the underside of
wholly or partially. the diaphragm. It feeds through a passageway from
the low-pressure side of the valve. This passageway
Refrigerant flow is now stopped or reduced. It is called an “internal equalizer,” shown in Figure 16.
remains so until superheat at the bulb location (A thermostatic expansion valve also may have an
increases vapor pressure in the bulb and above the external equalizer connection, which will be covered
in greater detail later in this chapter.)
10
The gas charge
applications.
+
e
ur
Pressure
s
e)
es
ur
g
in
re
of the other. You can see that, with the same refrig- pr p
(s b
ul
erant in both the bulb and the evaporator, pressure- fo rc e (b
r ce
temperature relationships are identical. Now apply in g fo
os in g
Cl
these curves to system operation. They show that en
Op
there is always a direct relationship, across the
diaphragm, of bulb pressure changes to evaporator
pressure changes. Thermostatic expansion valves
with liquid remote bulb charges normally are used
when there is a very narrow or limited evaporator Temperature
temperature range. This is a condition outside the
scope of other remote bulb charges. Figure 18. Conventional liquid charge
11
P1
Bulb pressure the evaporator, but it will not produce enough pressure
in the remote bulb to open the valve.
Figure 20. Assume that the system pictured has an You should always install a gas-charged valve in a
R-22 gas-charged expansion valve. It has a 100-psig location warmer than that of the remote bulb. The
maximum operating pressure and a 10°F superheat reason for this is that a gas-charged power element
setting. Now, assume that the evaporator pressure contains liquid up to the MOP point. It is very impor-
increases to 100 psig. The total force under the tant for this liquid to remain in the remote bulb, as
diaphragm will be 100 psig plus 11.5 psig (the spring shown in Figure 21. The remote bulb tubing must
pressure setting for 10°F superheat). This equals never contact a surface colder than the remote bulb.
111.5 psig. Remember that the charge in the gas- If it does, the charge will condense at the coldest
charged remote bulb and tube is limited. When the point and the valve will not function properly.
remote bulb reaches the saturation temperature that
corresponds to 111.5 psig, the entire charge has Generally, the application of gas-charged thermosta-
evaporated. Only vapor exists in the bulb. There will tic expansion valves is not limited. However, they
be some added superheat of refrigerant gas leaving work most efficiently in such applications as water
Liquid is
completely
Evaporator pressure
evaporated
100 psig
at 65°F and Spring pressure
111.5 psig 11.5 psig
Evaporator pressure (also suction pressure) must be less than 100 psig
before valve pin will open, regardless of remote bulb temperature
12
chillers and air conditioning units that oper- P1
ate in a 30°F to 50°F evaporator temperature
range. Bulb
Remote bulb loses
The cross charge control if charge
condenses at P2
these points
With a cross-charged remote bulb, the pres-
sure-temperature curve of the refrigerant in P3
the bulb crosses that of the refrigerant in the
system.
The difference between evaporator temperatures Surrounding temperature is not important to the loca-
and bulb temperatures create the operating super- tion of a vapor cross-charged valve. This is because
heats of the cross-charged TEV. It is apparent, then, it cannot lose control if the valve is colder than the
that a cross-charged valve must be adjusted for the remote bulb.
best superheat setting at the lowest evaporator tem-
perature of the system in order to prevent floodback You also can use a vapor cross-charged valve with a
of liquid refrigerant to the compressor. compressor, which requires motor overload protec-
tion. It is also available without MOP, when motor
Liquid cross charge. Cross charges may be either overload protection is not required. When there is no
liquid or vapor. There are three types of liquid cross requirement for starting or overload protection, use
charges. One is designed for use in the commercial the non pressure-limiting type. This may be the case
temperature range (from 40°F to 0°F). Another is for with smaller commercial units or window air condi-
the low temperature range (from 0°F to –40°F). The tioners. When maximum operating pressure is
third is designed for the ultra-low temperature range required, you must consider correct MOP in selecting
(from –40°F to –100°F). a replacement valve.
13
16° SH
Superheat, °F
Liquid charge
9° SH
1. Maintains control under cross-ambient conditions
4° SH
2. Tends to allow floodback on start-up
3. MOP is not available
Normal range
–40 0 50
Evaporator temperature, °F
16° SH
Superheat, °F
Gas charge
20° SH
Superheat, °F
Liquid cross-charge
14
Comparing the types of remote bulb charges ª undersized evaporator tubing
Each of the four remote bulb charges discussed—the ª extreme length of tubing per pass
liquid charge, the gas charge, the liquid cross charge,
and the vapor cross charge—has its own superheat ª improper joints
characteristics. The curves in Figure 22 show the
operating limits of each type based on a superheat of ª restrictive return bends
6°F.
ª distribution headers of various types.
These curves may not reflect true values. They are
presented here simply to show the general advan- Certain pressure drops through the evaporator are of
tages and disadvantages of each. From Figure 22, consequence:
you can see why the vapor cross charge is a major
development. It has the potential to maintain almost ª above 3.0 psi in the air conditioning range
constant superheat. This makes it possible to get
maximum refrigeration effect from an evaporator with ª 2.0 psi in the commercial range
temperatures ranging from +50°F to –40°F. You can
expect consistent superheat adjustments for the full ª 0.75 psi in the low-temperature or food freezer
range of evaporator operation. This eliminates con- range.
cern for floodback or starving of the evaporator at the
extreme ends of the temperature range. These pressure drops will hold a TEV in a relatively
“restricted” position. This will reduce system capacity
THE EXTERNAL EQUALIZER unless a valve with an external equalizer is used. The
evaporator should be designed or selected for the
Look back at Figure 16, which shows a TEV with an operating conditions. The valve should be selected
internal equalizer. Pressure at the valve outlet to the and applied accordingly.
evaporator is applied through the bottom of the
diaphragm. It is applied through a hole drilled in the The valve in Figure 24 on the next page has an inter-
valve or through the space around the valve push nal equalizer. Pressure at the valve outlet is on the
rods. Now look at Figure 23. It shows a TEV
with an external equalizer. Note that packing Valve with external equalizer
around the push rods keeps valve outlet pres-
sure away from the evaporator side of the
diaphragm.
External
Instead, suction pressure is applied to the equalizer
evaporator side of the diaphragm through tub- Push rod
fitting
packing
ing. It is either soldered into an opening in the
suction line near the evaporator outlet or into
a reducing tee located there. This tubing is Evaporator
connected to the external equalizer fitting on outlet
pressure
the valve, as shown in Figure 23. The pre-
ferred tubing location in the suction line is
downstream from the bulb. Push rods
15
bottom of the diaphragm. It is also assumed that the of evaporator surface available for the absorption of
evaporator shown has a negligible pressure drop. latent heat of vaporization of the refrigerant is
Any large pressure drop through the evaporator will reduced. The evaporator is said to be “starved.”
cause the valve to restrict refrigerant flow unless a
valve with an external equalizer is used. The thermostatic expansion valve is being held in a
somewhat “restricted” position. The pressure under-
To understand this, look at Figure 25, which shows neath the diaphragm (at the evaporator inlet) is
an example of an evaporator fed by a TEV with an higher than the pressure at the remote bulb, point C.
internal equalizer. As you can see, there is a sizable Remember that the pressure drop across the evapo-
pressure drop of 16 psig. rator, which causes this condition, increases with the
load. Thus, the “restricting” or “starving” effect is
The pressure at point C is 52.5 psig. This is 16 psig increased when the demand on the expansion valve
lower than at the valve outlet, point A. The 68.5 psig capacity is greatest.
at point A is the pressure acting on the lower side of
the diaphragm. The valve spring is set at a compres- USING AN EXTERNAL EQUALIZER
sion equal to a pressure of 15.5 psig. Thus, the
required pressure above the diaphragm is 68.5 psig The external equalizer type of valve must be used to
plus 15.5 psig, or 84 psig. This pressure corresponds compensate for an excessive pressure drop through
to a saturation temperature of 50°F. Obviously, the an evaporator. The equalizer line can be connected in
refrigerant temperature at point C must be 50°F for one of two ways:
the valve to be in equilibrium.
ª It can connect into the evaporator at a point
But the pressure at this point is only 52.5 psig. The beyond the greatest pressure drop.
corresponding saturation temperature is 28°F. As a
result, a superheat of 22°F (50°F – 28°F = 22°F) is ª It can connect into the suction line at a point on
required to open the valve. An increase in superheat the compressor side of the remote bulb.
from 10°F to 22°F is needed. More of the evaporator
surface must be used to produce this higher super- As a general rule of thumb, the equalizer line should
heated refrigerant gas. This means that the amount be connected to the suction line at the evaporator
P1 = 84 psig
P2 = 68.5 psig
P3 = 15.5 psig
84 psig = 50°F
C 68.5 psig and 50°F
Figure 24. TEV with internal equalizer on evaporator with no pressure drop
16
P1 = 84 psig
P2 = 68.5 psig
P3 = 15.5 psig
84 psig = 50°F
52.5 psig and 50°F C
Figure 25. TEV with internal equalizer on evaporator with 16-psig pressure drop
outlet. When this arrangement is used, true evapora- Look again at the system shown in Figure 25. Now
tor outlet pressure is imposed under the valve assume that there are the same pressure conditions
diaphragm. Pressure drop through the evaporator in a system using a valve with the external equalizer
does not affect operating pressures on the diaphragm. feature, as shown below in Figure 26. The same
The thermostatic expansion valve will respond to pressure drop still exists through the evaporator.
the superheat of the refrigerant gas leaving the Pressure under the diaphragm is now the same as
evaporator. the pressure at the end of the evaporator (point C, or
P1 = 68.5 psig
P2 = 52.5 psig
P3 = 16 psig
Figure 26. TEV with external equalizer on evaporator with 16-psig pressure drop
17
52.5 psig). The pressure required above the dia- ª 2.0 psi in the commercial temperature range
phragm for equilibrium is 52.5 psig plus 16 psig, or
68.5 psig. (Note the increase in the spring pressure— ª over 0.75 psi in the low freezer temperature
from 15.5 psig to 16 psig—needed to bring the TEV range.
into equilibrium.) The 68.5-psig pressure corresponds
to a saturation temperature of 40°F. Therefore, the The recommendations in Table 1 adequately cover
superheat required is now 40°F – 28°F, or 12°F. The the requirements for most field-installed systems. In
use of an external equalizer has reduced the super- general, install an externally equalized valve when
heat from 22°F to 12°F. As you can see, the operating pressure drop between the evaporator inlet and the
superheat has changed from 10°F to 12°F. This is the suction-line bulb location exceeds the maximums
result of the change in the pressure-temperature listed in Table 1.
characteristics of R-22 at the lower suction pressure
of 52.5 psig. DUAL-DIAPHRAGM THERMOSTATIC
EXPANSION VALVES
However, in an operating system, where more evap-
orator surface is made available for boiling the liquid So far, this chapter has assumed that both sides of
refrigerant, the evaporator outlet pressure will an expansion valve’s diaphragm are of equal area.
increase. It will be above 52.5 psig. Thus, you can This is the case when the valve has a single
see the advantage of using a TEV with an external diaphragm. However, there are valves with two
equalizer, as opposed to one with an internal equal- diaphragms. One is subject to pressure developed in
izer. Capacity will increase in a system that has an the remote valve, the other is subject to pressure
evaporator with a sizable pressure drop. developed in the evaporator and by the adjusting
spring. The two diaphragms can be of different sizes,
A thermostatic expansion valve must be equipped as shown in Figure 27.
with the external equalizer feature in order to provide
the best performance in the following cases: There is an advantage in using two diaphragms, one
acted upon by evaporator pressure and the other by
ª when the pressure drop through an evaporator is remote bulb pressure. By proportioning their size, a
in excess of the limits previously defined valve can operate at the same superheat at 5°F as at
25°F. Constant superheat can be maintained. This is
ª when a pressure drop type of refrigerant not possible with a single-diaphragm valve.
distributor is used at the evaporator inlet.
ª 3.0 psi in the comfort air conditioning Table 1. Greater evaporator pressure drop requires
evaporator temperature range external equalizer
18
Power element bulb
Power element
diaphragm
(Power element charge)
Evaporator
pressure
diaphragm
Push rod Out
In Needle Seat
Spring
Adjustment screw
A typical application of a pilot-operated TEV is shown A reduction in suction gas superheat reflects the
in Figure 28 on the next page. This assembly has a need for reduced refrigerant flow. In response, the
primary regulator and a conventional direct-operated pilot valve moves in a closing direction. This action
valve, which acts as a pilot. The pressure and tem- reduces the pressure on top of the piston. As the pis-
perature of suction gas leaving the evaporator oper- ton moves to close the primary regulator, the volume
ate the pilot valve—which, in turn, modulates the of refrigerant flow is reduced. In normal operation,
primary regulator in response to changes in suction and in response to system load, the pilot valve and
gas superheat. The primary regulator opens when regulator assume intermediate or throttling positions.
19
Remote External equalizer line Pilot thermal
bulb well expansion valve
Pilot solenoid
liquid valve
AMMONIA EXPANSION VALVES bulb to become chilled. The result is total or at least
partial closing of the valve.
Thermostatic expansion valves for ammonia refriger-
ant operate much the same as those used with other You might be led to think that valve response to
refrigerants. Characteristics of liquid ammonia, how- changes in bulb temperature is almost instant, so
ever, differ from those of fluorocarbon refrigerants. that superheat stays constant. This is not the case,
Even small quantities of ammonia vapor have a great however. It takes time for refrigerant to travel from the
erosive effect on the expansion device used. High- valve outlet through the evaporator to the remote
velocity refrigerant and contaminants like dirt or scale bulb. There is some delay before the remote bulb
compound this erosive effect. As with other parts of reacts to any change in valve seat position. Under
ammonia systems, valves are made of steel and this condition, the valve “overshoots” on both opening
steel alloys to combat the erosive effect. and closing. This condition is called hunting. With an
exceptionally long evaporator, this may be very unde-
EVAPORATOR LENGTH sirable. It could create alternate cycles, in which the
evaporator would be overfed when there is not
To simplify this chapter, several assumptions have enough superheat, and then starved when superheat
been made up to this point. When a TEV opens, is too high.
refrigerant almost immediately travels through the
evaporator. There, it boils and superheats to a level There should be little hunting by a TEV with an evap-
of, for example, 10°F. Then it proceeds to the remote orator that has short passes from the inlet to the out-
bulb location on the suction line. let. Hunting will be most pronounced in evaporators
with long tubes. Avoid this type of evaporator in the
The subsequent increase in remote bulb temperature interest of efficient valve operation. If a large evapora-
then develops pressure. This pressure bears against tor surface is required, it is better to use several short
the diaphragm, opening the valve. Opening the valve tubes in parallel than one long tube. This reduces the
allows more refrigerant to flow into the evaporator, travel time of refrigerant. If possible, the total length of
decreasing the superheat and causing the remote evaporator tubing should not exceed 100 ft.