LOCATION : TILAL AL GHAF @ DUBAI CLIENT : M/s. MAJID AL FUTTAIM CONSULTANT : M/s. ARIF & BINTOAK MAIN CONTRACTOR : M/s. UNITED ENGINEERING CONSTRUCTION MEP CONTRACTOR : M/s. VERGER DELPORTE SUPPLIER : M/s. EMIRATES INTERNATIONAL EQUIPMENTS MACHINERY LLC
S/N CONSULTANT COMMENTS REPLY REMARKS
Submit a detailed pump Head & Flow calculation in excel format with all the supporting 1 Comply Kindly refer to Annexure -1 documents, schematic layout showing dimensions and references for approval Laboratory test certificates of the proposed pumps material and coating thickness which are locally assembled (each items below) at supplier factory to be provided for review and Not applicable pumps are 2 approval factory assembled a. Counter flange of pump b. Foundation Nuts-Bolts-Washers of pump c. Counter flanges joining bolts and nuts. d. Tie rods of both pump sets Submit sample of complete booster pump with Sample is already available with 3 inbuilt VFD and microprocessor controller Comply the Consultant assembly for consultant approval Submit confirmation letter from manufacturer /supplier that the IP rating of the proposed Kindly refer to attached 4 pump with inbuilt VFD and microprocessor-based comply annexure -2 controller is capable to withstand the UAE weather condition (Temperature and humidity). Attached sequence of operation is not suitable Kindly refer to revised sequence 5 with inbuilt VFD and microprocessor-based comply of operation “section-9” Control Submit confirmation letter from the supplier that the proposed pump installation including 6 inbuilt VFD, and microprocessor-based controller Comply Kindly refer to annexure -3 is suitable of available space for future easy maintenance Submit WRAS certificates ACS is equivalent to WRAS WRAS from UK and ACS from Proposed pumps are with 7 FRANCE ACS appprovals ACS certificate attached in “section-11” Provide ESMA (Emirates Authority for ESMA not applicable for 8 Standardization and Metrology) approval boosting pumps Submit the VFD make and details for consultant The proposed pumps with review and approval inbilt VFD is an integral part of Tecnoplus series, the 9 whole pump set along with the VFD is manufactured by ESPA- SPAIN as a single unit Provide a clear certificate (Third party) that the assembly including the VFD part is capable to Kindly refer to attached 10 Comply withstand GCC conditions (temperature, annecxure-4 humidity, etc.) Attached ISO certificate to be applicable for the ISO certification is for the proposed pump model ESPA factory, separate ISO 11 certificate for each product is not applicable Submit PDI (Plumbing and drainage institute) for The proposed pump with the proposed inbuilt water hammer damper Presskit(Water hammer arrestor) is an integral part of 12 TECNOPLUS Series, no separate test certificate required, ACS is applicable for kitpress as well Pump maximum operating pressure should not Maximum system working be less than 10 bar pressure is only 3.5 bar and maximum operating pressure is 4.5 bar, hence pump with pressure rating 8 bar is 13 sufficient as project requirement and specification(more than 150% of maximum working pressure) Isolation valve to be provided on suction and 14 comply discharge of pump Motor bearing shall be sized to allow a 20,000- Refer Letter attached 15 Comply minimum hour B10 calculated life. Annexure -5 Submit details of the valves, pressure gauge, VFD and header pipe arrangement (Such as, 16 Comply Kindly refer to section 10 & 11 material, pressure rating, type, and related certificates) Submit detail of accessories along with pumps to 17 Comply Kindly refer to section 10 & 11 be supplied Complete installation to be as per specification Kindly refer to revised and project requirements. Contractor to 18 Noted compliance statement “section comply items which are under M/s. Verger 4” Delporte Submit inertia base and concrete foundation Inertia Base for Booster 19 details of the pump sets for review and approval Pumps is not required as per supplier's recommendations
Provide details about pump cycling/running Proposed single pump with
duration for continuous operation inbuilt VFD , pump is suitable 20 for contionous operation as per the demand Provide country of origin of the attached list of Complete pump with electrical components electrical components are Researched and developed 21 by ESPA-spain Country of origin certificate attached Contractor to arrange local factory visit for pump Comply, pumps are factory assembling & testing upon material approval assembled by ESPA-spain, prior to pump delivery to site how ever visit to factory approved service center for 22 set assembly (valves & accessories will be arranged prior to pump delivery to the site