REPLY TO CONSULTANT COMMENTS

PROJECT : ELAN TOWNHOUSES


LOCATION : TILAL AL GHAF @ DUBAI
CLIENT : M/s. MAJID AL FUTTAIM
CONSULTANT : M/s. ARIF & BINTOAK
MAIN CONTRACTOR : M/s. UNITED ENGINEERING CONSTRUCTION
MEP CONTRACTOR : M/s. VERGER DELPORTE
SUPPLIER : M/s. EMIRATES INTERNATIONAL EQUIPMENTS MACHINERY LLC

S/N CONSULTANT COMMENTS REPLY REMARKS


Submit a detailed pump Head & Flow calculation
in excel format with all the supporting
1 Comply Kindly refer to Annexure -1
documents, schematic layout showing dimensions
and references for approval
Laboratory test certificates of the proposed
pumps material and coating thickness which are
locally assembled (each items below) at supplier
factory to be provided for review and
Not applicable pumps are
2 approval
factory assembled
a. Counter flange of pump
b. Foundation Nuts-Bolts-Washers of pump
c. Counter flanges joining bolts and nuts.
d. Tie rods of both pump sets
Submit sample of complete booster pump with
Sample is already available with
3 inbuilt VFD and microprocessor controller Comply
the Consultant
assembly for consultant approval
Submit confirmation letter from manufacturer
/supplier that the IP rating of the proposed
Kindly refer to attached
4 pump with inbuilt VFD and microprocessor-based comply
annexure -2
controller is capable to withstand the UAE
weather condition (Temperature and humidity).
Attached sequence of operation is not suitable
Kindly refer to revised sequence
5 with inbuilt VFD and microprocessor-based comply
of operation “section-9”
Control
Submit confirmation letter from the supplier that
the proposed pump installation including
6 inbuilt VFD, and microprocessor-based controller Comply Kindly refer to annexure -3
is suitable of available space for future easy
maintenance
Submit WRAS certificates ACS is equivalent to WRAS
WRAS from UK and ACS from
Proposed pumps are with
7 FRANCE
ACS appprovals
ACS certificate attached in
“section-11”
Provide ESMA (Emirates Authority for ESMA not applicable for
8
Standardization and Metrology) approval boosting pumps
Submit the VFD make and details for consultant The proposed pumps with
review and approval inbilt VFD is an integral part
of Tecnoplus series, the
9
whole pump set along with
the VFD is manufactured by
ESPA- SPAIN as a single unit
Provide a clear certificate (Third party) that the
assembly including the VFD part is capable to Kindly refer to attached
10 Comply
withstand GCC conditions (temperature, annecxure-4
humidity, etc.)
Attached ISO certificate to be applicable for the ISO certification is for the
proposed pump model ESPA factory, separate ISO
11
certificate for each product is
not applicable
Submit PDI (Plumbing and drainage institute) for The proposed pump with
the proposed inbuilt water hammer damper Presskit(Water hammer
arrestor) is an integral part of
12 TECNOPLUS Series, no
separate test certificate
required, ACS is applicable
for kitpress as well
Pump maximum operating pressure should not Maximum system working
be less than 10 bar pressure is only 3.5 bar and
maximum operating pressure
is 4.5 bar, hence pump with
pressure rating 8 bar is
13
sufficient as project
requirement and
specification(more than
150% of maximum working
pressure)
Isolation valve to be provided on suction and
14 comply
discharge of pump
Motor bearing shall be sized to allow a 20,000- Refer Letter attached
15 Comply
minimum hour B10 calculated life. Annexure -5
Submit details of the valves, pressure gauge, VFD
and header pipe arrangement (Such as,
16 Comply Kindly refer to section 10 & 11
material, pressure rating, type, and related
certificates)
Submit detail of accessories along with pumps to
17 Comply Kindly refer to section 10 & 11
be supplied
Complete installation to be as per specification
Kindly refer to revised
and project requirements. Contractor to
18 Noted compliance statement “section
comply items which are under M/s. Verger
4”
Delporte
Submit inertia base and concrete foundation Concrete foundation details kindly refer to the attached
19
details of the pump sets for review and approval will be provided on the shop Annexure-6
drawings. Inertia Base is not
applicable for booster pumps
as per IFC drawings
Provide details about pump cycling/running Proposed single pump with
duration for continuous operation inbuilt VFD , pump is suitable
20
for contionous operation as
per the demand
Provide country of origin of the attached list of Complete pump with
electrical components electrical components are
Researched and developed
21
by ESPA-spain
Country of origin certificate
attached
Contractor to arrange local factory visit for pump Comply, pumps are factory
assembling & testing upon material approval assembled by ESPA-spain,
prior to pump delivery to site how ever visit to factory
approved service center for
22
set assembly (valves &
accessories will be arranged
prior to pump delivery to the
site