NEO – PRM-2W 2-Wire Smoke Setup

NEO HS2016 / HS2032 / HS2064 / HS20128 v1.0+

Equipment List (for example shown below):


(1) DSC NEO Control Panel
(1) DSC PRM-2W Polarity Reversal Module
(1) DSC RM-1UL Relay or equivalent
(1) HSM2204 Aux Power Supply
(1) PC5003C Enclosure
(1) 7 Amp Battery
(1) PT1640 Transformer
(3) FSA210BST Two Wire Smokes with built in sounders and heat detectors

HSM2204

To the AUX+ and PGM X (-)


of the HSM2204 Power Supply.

1 of 4
August 2016

NEO – PRM-2W 2-Wire Smoke Setup

HSM2204 Mod. 1
PGM5 – PGM8

I/O 1 I/O 2
PGM5 PGM6

Tech Tip: The T1 and T2 connection can be used in any application that the
control panel or 3rd party application can provide a latched closure.

Tech Tip: The use of the T1 and T2 connection is required in the NEO v1.0 –
v1.2 panels due to the changes that were made in the voltage
patterns of the bell circuit of those panels.

Assumed parameters:
The HSM2204 is module #1 (representing PGM's 5 - 8)
PGM5 will be set up as power (resettable power) to the PRM-2W
PGM6 will be used as the fire alarm trigger for the PRM-2W
Zone 1 of the main panel is programmed as Standard 24-Hour Fire

2 of 4
August 2016

NEO – PRM-2W 2-Wire Smoke Setup

Panel Programming:

[ ] = NEO Panel Section / Solid ~ Red Lock light in programming /


{ } = NEO Subsection / Flashing Steady ~ Red Lock light in programming /
( ) = Data / Solid ~ Green Check light in programming /

Section [001] Zone Definition Programming


{001} (008) Program Zone 1 as (008) 24-Hour Standard Fire

Section [009] PGM Definition Programming


{005} (103) Program PGM5 as (103) Sensor Reset [*][7][2]
{006} (156) Program PGM6 as (156) Latched System Event

Section [010] PGM Attribute Programming


{006} Program PGM5 Toggle options 5 – 15 ‘OFF’

3 of 4
August 2016

NEO – PRM-2W 2-Wire Smoke Setup

Tech Tip: Quick programming hint:


In the Toggle Sections, you can press the toggle number to
advance to the desired question and automatically change the
answer.

For Example: Enter Section [010] Subsection {006} and press:


5, 6, 7, 8, 9, 1, 2, 3, 4, 5, 6, 7

Each number entered will drop you to the question and change
the answer automatically to the opposite status.
(e.g. ‘N’ to ‘Y’ or ‘Y’ to ‘N’)

Verify each questions is ‘N’ as you toggle through the list of


event options; leaving True Output (1) and Fire Alarm (3) as ‘Y’.

Pressing ‘9’ while in the Toggle Section changes the screen to Toggle Options 9 – 16;

Where option (1) = Option 9, (2) = Option 10, (3) = Option 11, (4) = Option, etc.

Tech Tip: The HSM2204 will support up to 1000mA of supervised power.

Tech Tip: The HSM2204 PGM’s will support up to 500mA per PGM.

Tech Tip: The HSM2204 supervises the AC and DC of the unit and will
produce a trouble if the AC is lost or DC is low/lost.

HS2016 - supports 1 HSM2204 Power Supply (PGM5 – PGM8)

HS2032 - supports 1 HSM2204 Power Supply (PGM5 – PGM8)

HS2064 - supports 3 HSM2204’s Power Supply (PGM5 – PGM16)

HS2128 - supports 4 HSM2204’s Power Supply (PGM5 – PGM20)