Product Configuration Specification

Order number: 4200436610-010 Serial number: I1127055 - I1127060

Date: 2018-07-09 Page 1 / 3

Product

RET670 Transformer protection IED


1MRK002816-AB

Basic data

Country: India
Customer's reference: 3269/4200137507-PUNJ LLOYD
Product version: 1p1
Terminal diagram: 1MRK002801-AB, Terminal diagram IED670, IEC symbols
Terminal diagram: 1MRK002802-AA, Terminal diagram IED670, ANSI symbols
DC voltage, EL: 90-250 VDC

Tool interface version: 1.1.01

Customized marking line 1: YN1M251228-SJ,RL=220 VDC,Ir=1A


Customized marking line 2: 3269/4200137507-PUNJ LLOYD

Functions

- Differential protection -

1 pc 1MRK002901-CB Transformer differential protection, three winding (T3WPDIF, 87T) [basic, selected
alternative]
3 pcs 1MRK002901-HA 1Ph High impedance differential protection (HZPDIF, 87X) [selected option]
3 pcs 1MRK002901-EA Restricted earth fault protection, low impedance (REFPDIF, 87N) [selected option]

- Impedance protection -

2 pcs 1MRK002904-AB Phase selection with load enchroachment, quadrilateral characteristic (FDPSPDIS, 21)
[basic]
3 pcs 1MRK002925-EA Full-scheme distance protection, mho characteristic (ZMHPDIS, 21) [selected option]
3 pcs 1MRK002925-GA Full-scheme distance protection, quadrilateral for earth faults (ZMMPDIS, 21) [selected
option]
1 pc 1MRK002924-PA Directional impedance element for mho characteristic (ZDMRDIR, 21) [selected option]
1 pc 1MRK002908-VA Additional distance protection directional function for earth faults (ZDARDIR) [selected
option]
1 pc 1MRK002908-UA Mho Impedance supervision logic (ZSMGAPC) [selected option]
2 pcs 1MRK002925-BA Faulty phase identification with blinder and load enchroachment (FMPSPDIS, 21) [basic]

- Current protection -

3 pcs 1MRK002906-AB Instantaneous phase overcurrent protection (PHPIOC, 50) [selected option]
3 pcs 1MRK002906-BB Four step phase overcurrent protection (OC4PTOC, 51/67) [selected option]
3 pcs 1MRK002906-CB Instantaneous residual overcurrent protection (EFPIOC, 50N) [selected option]
3 pcs 1MRK002906-DB Four step residual overcurrent protection (EF4PTOC, 51N/67N) [selected option]
2 pcs 1MRK002906-NA Thermal overload protection, two time constants (TRPTTR, 49) [selected option]
3 pcs 1MRK002906-RB Breaker failure protection (CCRBRF, 50BF) [selected option]
1 pc 1MRK002902-DA Broken conductor check (BRCPTOC, 46) [basic]

- Voltage protection -

2 pcs 1MRK002908-AB Two step undervoltage protection (UV2PTUV, 27) [selected option]
2 pcs 1MRK002908-DB Two step overvoltage protection (OV2PTOV, 59) [selected option]
3 pcs 1MRK002908-GB Two step residual overvoltage protection (ROV2PTOV, 59N) [selected option]
2 pcs 1MRK002908-MB Overexcitation protection (OEXPVPH, 24) [selected option]

2017-04-11
SPEC.dotx
Product Configuration Specification
Order number: 4200436610-010 Serial number: I1127055 - I1127060

Date: 2018-07-09 Page 2 / 3

1 pc 1MRK002902-EA Loss of voltage check (LOVPTUV, 27) [basic]

- Frequency protection -

2 pcs 1MRK002908-NB Underfrequency function (SAPTUF, 81) [selected option]


2 pcs 1MRK002908-RB Overfrequency function (SAPTOF, 81) [selected option]
2 pcs 1MRK002908-SA Rate-of-change frequency protection (SAPFRC, 81) [selected option]

- Multipurpose protection -

3 pcs 1MRK002902-AA General current and voltage protection (CVGAPC) [selected option]

- Secondary system supervision -

3 pcs 1MRK002914-AA Current circuit supervision (CCSRDIF) [selected option]


3 pcs 1MRK002914-GB Fuse failure supervision (SDDRFUF) [selected option]

- Logic -

3 pcs 1MRK002917-AA Tripping logic (SMPPTRC, 94) [basic]


1 pc 1MRK002917-MA Configurable logic blocks [basic]

- Monitoring -

1 pc 1MRK002923-LB Function block for service values presentation of the analog inputs [basic]
20 pcs 1MRK002918-FA Event function [basic]
1 pc 1MRK002918-GB Disturbance report [basic]

Hardware

- Casing -

1MRK000151-NE 3/4 x 19" rack casing max 5 I/O mod, 2 TRM (Rack) [basic, selected alternative]
1MRK001434-NA Combined backplane module max 5 I/O mod, 2 TRM, 3/4x19" (CBM) [basic, selected alternative]
Location pCBM
1MRK002252-BA Universal backplane module 2 ADM, 2 TRM (UBM) [basic, selected alternative]
Location pUBM
1MRK002239-BB Power supply module 90-250 VDC (PSM) [basic, selected alternative]
Location P1
1MRK002246-BC Numeric processing module 600 MHz with 512kB cache (NUM) [basic]
Location P30

- Connection type -

1MRK002960-AA Compression terminals [basic, selected alternative]


Location P1-P16

- Human Machine Interface -

1MRK000008-PB Human machine interface, small size - text only, IEC symbols 3/4 x 19" (SHMI) [basic, selected
alternative]
Location HMI

- Analog system -

1MRK002133-AB Analog digital conversion module with time synchronization 12 channels (ADM) [basic]
Location P32
1MRK002133-AB Analog digital conversion module with time synchronization 12 channels (ADM) [basic]
Location P31
1MRK002247-AG Transformer input module, compression terminals 6I +6U, 1A, 110/220V, 50/60Hz (TRM) [basic,
selected alternative]

2017-04-11
SPEC.dotx
Product Configuration Specification
Order number: 4200436610-010 Serial number: I1127055 - I1127060

Date: 2018-07-09 Page 3 / 3

Location P41
1MRK002247-CG Transformer input module, compression terminals 12I, 1A, 50/60Hz (TRM) [basic, selected
alternative]
Location P40

- Binary input/output module -

1MRK000508-CB Binary input module, 16 inputs RL220, 220-250VDC, 30mA (BIM) [selected option]
Location P3
1MRK000614-AB Binary output module 24 output relays (BOM) [selected option]
Location P4

- Station communication ports -

1MRK002266-AA Optical ethernet module 1 glass interface, IEC61850-8-1 / IEC61850-9-2 (OEM) [selected option]
Location P31:1

Engineering facilities

- First HMI language -

1MRK002930-AA HMI language, English IEC (lHMI-IEC en) [basic, selected alternative]

- Mounting details with IP40 of protection from the front -

1MRK000020-Y Flush mounting kit [selected option]

Efficient engineering

ABB make available files that can be used with our engineering tools to facilitate the engineering process.

To obtain these files related to this order item, send an e-mail:

To: SE-mets.service@abb.com
Cc: any recipient added here will also receive the response
Subject: 4200436610-010

More information can be obtained at www.abb.com/substationautomation

2017-04-11
SPEC.dotx