Professional Documents
Culture Documents
__________________________________________________________________________________________________________________
SecuriFire
BX-O1
Output module for
SecuriLine eXtended
Description Interfaces
The BX-O1 can be connected to the SecuriLine eXtended ad-
dressable loop of the SecuriFire fire detection system.
BX-O1 features
Power supply via the X-LINE Fig. 2 BX-O1 interfaces
Addressing and parameter assignment with PC software via
X-LINE
Up to 62 modules can be connected per loop SecuriLine eXtended (X2)
1 output, change-over contact 230V Terminal Designation Description
Fail safe position of the relay output if there is a voltage supply 1 L1 Data A
failure 2 GND GND A
Integrated short circuit isolators 3 GND GND B
Robust plastic housing (option) 4 L2 Data B
5 SHLD Screen support point
6 SHLD Screen support point
GND
SHLD
L1
BX-O1
Example:
Actuation as X2
quiescent contact
SHLD
e.g. control electronics
SHLD
X3
L2
Lift control 1 NC
GND
system COM GND
NO L1 1
SHLD
GND
L2
Article numbers / spare parts
Short designation Swiss art. number Art. number
BX-O1 Output module -- 20-2100015-01-xx
Accessories
GEH MOD IP66 Map case IP66 for BX-O1 239 917 FG020234
MM SM M20 M20 step nipple 242 578 MM000181
MM ANB M16 M16 mounting screw union -- MM000185
MM GM M16 M16 counter-nut -- MM000186
MP MOD KL Small mounting plate for loop modules 265 417 30-6800021-01-xx
Technical data
Operating voltage 12 to 30 VDC
Power consumption (module's power consumption only) 0.48 mA
Signal transmission Serial data transmission, 2-line technology
Protection type without housing/with housing 00/66 IP
Ambient temperature -20 to +60 -°C
Connection Screw terminals max. 1.5 mm2
VdS approval G212024
Declaration of performance (DoP) CPR-20-13-013-DE-EN
Dimensions (H x W x D) 67 x 67 x 20 mm
Dimensions with map case (H x W x D) 94 x 94 x 81 mm
Weight xx g
Relay outputs 1
Relay Bistable, one coil
Type of contact Change-over contact
Switching voltage 230 V
Switching current 0.1 – 2000 mA
Breaking capacity 60 (0.25 A @ 230 V) W
Switching frequency max. 3.125 Hz
(a relay can change its state every 160 ms per loop, provided no other command has to be performed)
Impulse output in 100 ms increments, 0.36 to 12 s
(deviation of up to +8 s).
Connection Screw terminals max. 2.5 mm2