You are on page 1of 2

Data Sheet

__________________________________________________________________________________________________________________

SecuriFire
BX-O1
Output module for
SecuriLine eXtended

The BX-O1 has a potential-free relay output for switching loads of


up to 2 A and up to 230 V.

It meets the SecuiLine eXtended specification for operation on the


addressable loop of the SecuriFire fire detection system.
Fig. 1 BX-O1
__________________________________________________________________________________________________________________

Description Interfaces
The BX-O1 can be connected to the SecuriLine eXtended ad-
dressable loop of the SecuriFire fire detection system.

The BX-O1 has a potential-free relay output for switching loads of


up to 2 A and up to 230 V.

An “Fail safe position” can be programmed for the output in the


event of loop voltage failure.

The relay outputs are suitable for outputting pulses.

Addressing and parameter assignment for the BX-O1 is performed


with PC software via the fire alarm control panel.

The module includes a short-circuit isolator. In the event of wire


breakage or a short-circuit, this functionality ensures that the fault
is localised and at the same time maintains the full operability of
the addressable loop.

BX-O1 features
 Power supply via the X-LINE Fig. 2 BX-O1 interfaces
 Addressing and parameter assignment with PC software via
X-LINE
 Up to 62 modules can be connected per loop SecuriLine eXtended (X2)
 1 output, change-over contact 230V Terminal Designation Description
 Fail safe position of the relay output if there is a voltage supply 1 L1 Data A
failure 2 GND GND A
 Integrated short circuit isolators 3 GND GND B
 Robust plastic housing (option) 4 L2 Data B
5 SHLD Screen support point
6 SHLD Screen support point

Relay output (X3)


Terminal Designation Description
1 NC Normally closed
2 COM Common
3 NO Normally open

Securiton AG Alpenstrasse 20 3052 Zollikofen Switzerland T 811 068 en c 1/2


Data Sheet

Power requirement Connection example


When both detectors and modules are operated on an addressable
loop, note that the BX-O1 has a higher power consumption than a When laying a 230 V power cable, make sure that it is
detector. For security reasons a maximum of 62 BX-O1s are per- not conveyed directly over the electronics of the mod-
mitted per addressable loop. ule.

A tool is available for calculating the maximum possible loop length


and the maximum number of participants. Connection output module BX-O1

GND
SHLD
L1
BX-O1
Example:
Actuation as X2
quiescent contact
SHLD
e.g. control electronics
SHLD
X3
L2
Lift control 1 NC
GND
system COM GND

NO L1 1

SHLD

GND
L2
Article numbers / spare parts
Short designation Swiss art. number Art. number
BX-O1 Output module -- 20-2100015-01-xx
Accessories
GEH MOD IP66 Map case IP66 for BX-O1 239 917 FG020234
MM SM M20 M20 step nipple 242 578 MM000181
MM ANB M16 M16 mounting screw union -- MM000185
MM GM M16 M16 counter-nut -- MM000186
MP MOD KL Small mounting plate for loop modules 265 417 30-6800021-01-xx

Technical data
Operating voltage 12 to 30 VDC
Power consumption (module's power consumption only) 0.48 mA
Signal transmission Serial data transmission, 2-line technology
Protection type without housing/with housing 00/66 IP
Ambient temperature -20 to +60 -°C
Connection Screw terminals max. 1.5 mm2
VdS approval G212024
Declaration of performance (DoP) CPR-20-13-013-DE-EN
Dimensions (H x W x D) 67 x 67 x 20 mm
Dimensions with map case (H x W x D) 94 x 94 x 81 mm
Weight xx g

Relay outputs 1
Relay Bistable, one coil
Type of contact Change-over contact
Switching voltage 230 V
Switching current 0.1 – 2000 mA
Breaking capacity 60 (0.25 A @ 230 V) W
Switching frequency max. 3.125 Hz
(a relay can change its state every 160 ms per loop, provided no other command has to be performed)
Impulse output in 100 ms increments, 0.36 to 12 s
(deviation of up to +8 s).
Connection Screw terminals max. 2.5 mm2

2/2 T 811 068 en c, 16.03.2018 Rd BX-O1


First edition: 28.09 2012 Rd
The product specifications contained in this document are subject to change without notice.