General CO-920-01

Specifications
GS48D20Z01-00E-N ProSafe-COM Controller

■ GENERAL Figure 1

ProSafe-COM is a generic term for


the functionality that deals with
communication between the external
world and ProSafe-SLS.

The main objectives are:

■ Presentation of the safety system


status and diagnostics to DCS or
other equipment.
■ Ability to write in the safety system
(overrides).
■ Sequence of event recording;
CO-920-01
keep track of all events in
ProSafe-COM Controller
ProSafe-SLS on millisecond basis.
■ Provide power for attached
ProSafe-COM interface modules.
■ Execution of non-safety logic.
■ ModBus Master capability.
■ Analogue value scaling.
■ Local printer.

The module is equipped with 3 serial ports that run the standard and extended ModBus protocol for status
and event retrieval and for override commands. One of the serial communication links (COM 1) is RS-232
and can be used for module configuration and maintenance. The port can also be used as an additional
ModBus port. The other serial communication links (COM 2, COM 3) are RS-485 (2 wire) or RS-422
(4-wire) bus connections.

The module comprises a dedicated Local Network Control interface that interrogates the ProSafe-SLS
network modules for status and events.

The module software is configured and driven using a configuration file and a tag file. Features are soft-
marshalling: use of logical addresses on the DCS interface. Each communication channel can have a
different physical to logical address mapping.

Event filtering: events can be generated per tag and per communication channel.
Every analogue value can be scaled to different scales.
A COM port can be configured as a ModBus Master to communicate with ModBus slaves
A local printer can be connected to a COM port to print system status and events.

The CO-920-01 has the ability to run a logic program, usually for non-safety logic like first failure detection
and for operator’s matrix panel control and annunciation.

GS48D20Z01-00E-N
Yokogawa Europe B.V.  Copyright 2010
2nd Edition January 2017
CO-920-01 2 of 4

■ FUNCTIONAL DIAGRAM
Inputs Module Outputs

Supply Notes Front

z32 24 Vdc field The RS-485 interfaces are 4-wire interfaces. To connect to a 2-wire RS-485 bus, 1 3V3
COM 1

z30 0 Vdc field connect RX-A and TX-A to the A (+) wire and RX-B and TX-B to the B (-) wire. 2 Network com
b32 not used The RS-232 and battery connections are also available at the DIN41612 connector. 3 Watchdog
d32 not used Only to be used without front (custom housing) 4 Error
d30 not used The Y-net terminator (d08, b08) is the passive end-of-line terminator. The active 5
b30 not used terminator is (permanently) connected to d02, b02. 6
d,b,z06 8 Vdc The RS-485 COM 2 and COM 3 terminators (d22, b22 and d16, b16) are passive end of 7
d,b,z04 0 Vdc bus terminators. 8 AA Battery
If the 8V output is not used, connect d04, b04, z04 to the 0V of the power supply
(MC-569) connected to the MC-5xx modules.

All Rights Reserved.  Copyright Yokogawa Europe B.V. GS48D20Z01-00E-N January 2017
CO-920-01 3 of 4

■ SPECIFICATIONS
Description Data
General Interfaces 3 serial ports (COM1 for maintenance)
1 local network controller interface
Width 6HP
Identification CO-920 on front en more detailed on connector label
Weight 265 gram

Input Serial interface COM 1: 4800 – 57600 Baud RS-232


COM 2 and COM 3: 4800 – 57600 Baud RS-485
Local network Enhanced RS-485, 250.000 Baud

Output Serial interface See Input


Supply Communication modules supply
Voltage 8 Vdc ± 0.5 V
Current Max. 1 A
Power indication Red LED
Local network active Red LED
Watchdog Red LED
Error indication Red LED

Supply Field supply 24 Vdc ± 25%


Max. 1 V top-top ripple
110 mA with 24 Vdc, no load
510 mA with 24 Vdc, full load

Dissipation 3W

All Rights Reserved.  Copyright Yokogawa Europe B.V. GS48D20Z01-00E-N January 2017
CO-920-01 4 of 4
NOTES

All Rights Reserved.  Copyright Yokogawa Europe B.V. GS48D20Z01-00E-N January 2017