You are on page 1of 4

General CL-530-A3

Specifications
GS48C30A03-00E-N Clock Module (redundant use)

■ GENERAL Figure 1

This clock module generates


A-voltage and B-voltage clock
signals.

CL-530-A3
Clock Module (redundant use)

These system clock signals are required by most of the ProSafe-SLS (Solid-state Logic Solver) modules
and are distributed via an internal bus. The signals are trapezium shaped voltage pulses, inducing low
EMI noise.

The A-voltage and B-voltage signals are based on a stable crystal oscillator with additional circuitry,
producing an output signal with a repetition-time of 1 msec. The A-voltage and B-voltage signals are
extracted from the same oscillator. They have the same frequency and shape. The phase-relation
between the A-voltage and B-voltage signals is 180°.

The pulse frequency is monitored, and the A-voltage and B-voltage signals are switched off when the
pulse frequency speeds up more than 50%. The frequency monitoring circuit also drives a relay.

The module is suited for synchronization or redundancy with other CL-530 modules by means of the
synchronization input/output. In case of synchronization the module with the highest frequency rules the
bus and other modules are synchronized to that frequency.

The module is also equipped with 4 “logic one” current pulse outputs. These outputs can be used to
connect pulse logic inputs.

The module is provided with 6 red LEDs, indicating the A-voltage and B-voltage pulses and the 4 “logic
one” output signals, and 1 green LED, indicating the oscillator output.

The module is also equipped with an on/off switch for switching on and off the module. This must be used
for on-line replacement of the module in case of redundant use.

GS48C30A03-00E-N
Yokogawa Europe B.V.  Copyright 2017
1st Edition January 2017
CL-530-A3 2 of 4

■ FUNCTIONAL DIAGRAM

Inputs Module Outputs

Supply Notes Front

z32 not used The output LEDs 3, 4, 5 and 6 are representing the output current of each logic ‘1’ 1 A voltage pulse
z30 not used output at z06 - z08, z14 - z16, d24 - d26 and z24 - z26. 2 B voltage pulse
b32 20 Vdc logic 3 “1” output
d32 0 Vdc logic * Connect d10-d12 and b10-b12 for current pulses for previous generation products. 4 “1” output
d30 see ‘outputs’ For synchronization interconnect only “A sync”. 5 “1” output
b30 see ‘outputs’ 6 “1” output
For redundancy interconnect “A sync”, “B sync”, “A voltage pulse” and B voltage pulse” 7 Osc. status
and switch off CL-530-Ax for online replacement. 8 switch on off
Connect ‘Dummy Load’ to both A- and B-Voltage pulse outputs if load is < 40 units.

All Rights Reserved.  Copyright Yokogawa Europe B.V. GS48C30A03-00E-N January 2017
CL-530-A3 3 of 4

■ SPECIFICATIONS

Description Data
General Number of channels 1
Width 6HP
Identification CL-530-A on front and more detailed on connector label
Weight 170 gram

Input A / B sync Isolated input and output, voltage pulses


Voltage 20 V
Pulse width 3 µsec.
Frequency 1 kHz
Capacity Max. 10 modules

Output A / B Voltage pulse System clock voltage pulses


Voltage 16 – 20 V
Pulse width 3.6 µsec. @ 10 V level
Frequency 1 kHz (998.5 ± 0.5 Hz)
Capacity Max. 200 modules
Status indication A / B red LED
Logic ‘1’ (A) Current pulses 500 mA
Capacity 10 unit loads
Status indication Red LED per output
Choke at d12 / b12 Current pulses 500 mA (when connected to voltage pulse)
Capacity 10 unit loads
Chokes at z10 - z12 / d20 - z20 Redundancy load
Oscillator status Relay contact SPDT
Voltage 60 Vdc, 48 Vac
Current 0.5 A
Minimum switching load 1 V and 0.5 mA
Status indication Green LED

Supply Logic supply at b26 24 Vdc ± 10%


15 mA
Logic supply 20 Vdc
40 mA with no load
80 mA with full load

Dissipation 1.2 W with no load to full load

All Rights Reserved.  Copyright Yokogawa Europe B.V. GS48C30A03-00E-N January 2017
CL-530-A3 4 of 4
NOTES

All Rights Reserved.  Copyright Yokogawa Europe B.V. GS48C30A03-00E-N January 2017