Professional Documents
Culture Documents
com
Copyright and Trademarks
© 2005 Tyco Safety Products Westminster, Westminster, MA 01441-0001 USA
Information in this document is subject to change without notice. No part of this document may be reproduced or transmitted
in any form or by any means, electronic or mechanical, for any purpose, without the express written consent of Tyco Safety
Products.
Tyco, Simplex, the Simplex logo, IDNet, SmartSync and WALKTEST are registered trademarks of Tyco International Ser-
vices AG or its affiliates in the US and/or other countries.
TrueAlarm analog smoke detection is protected by one or more of the following U.S. Patents: 5,155,468; 5,173,683;
5,543,777. IDNet addressable communications are protected by U.S. Patent No. 4,796,025. IDNet duplicate device detection
is protected under U.S. Patent No. 6,034,601. WALKTEST system test is protected under US Patent No. 4,725,818. Smart-
Sync horn/strobe operation is protected under U.S. Patent No. 6,281,789. Two wire synchronization circuit operation is pro-
tected by U.S. patent No. 5,559,492.
In the event of equipment malfunction, all repairs should be performed by an authorized agent. It is the responsibility of users
requiring service to report the need for service to our company or to one of our authorized agents. Service can be arranged
through our office at:
The Ringer Equivalence Number (REN), which is 01 for the DACT installed in this panel, is used to determine the number of
devices that may be connected to a telephone line. Excessive RENs on a telephone line may result in the devices not ringing in
response to an incoming call. In most, but not all areas, the sum of RENs should not exceed five (5.0). To be certain of the
number of devices that may be connected to a line, as determined by the total number of RENs, contact the local telephone
company. For products approved after July 23, 2001, the REN is part of the product identifier, which uses the format
US:AAAEQ##TXXXX. The digits represented by ## are the REN without a decimal point (e.g. 01 is a REN of 0.1).
If the DACT causes harm to the telephone network, the telephone company will notify you in advance that temporary discon-
tinuance of service may be required. But if advance notice isn’t practical, the telephone company will notify you as soon as
possible. If your service is discontinued, you will be advised of your right to file a complaint with the FCC.
The telephone company may make changes to its facilities, equipment, operations, or procedures that could affect the opera-
tion of the equipment. If this happens the telephone company will provide advance notice in order for you to make the neces-
sary modifications to maintain uninterrupted service.
If trouble is experienced with the DACT, please contact Tyco Safety Products at the location identified above. If the equipment
is causing harm to the telephone network, the telephone company may request that you disconnect the equipment until the
problem is resolved.
Network
Service Unused
Provider's RJ-11 Jack
Facilities
Telephone
Line
Telephone
Network
Demarcation Unused
Point Telephone
Fax RJ-11 Jack
Answering
System
Telephone
Connectors for the DACT are terminal blocks on the DACT module. Refer to DACT Wiring in Chapter 2 of this manual for
specific DACT wiring instructions.
DO NOT INSTALL ANY PRODUCT THAT APPEARS DAMAGED. Upon unpacking your product, inspect the contents of
the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify your distributor.
ELECTRICAL HAZARD - Disconnect electrical field power when making any internal adjustments or repairs. Servicing
should be performed by qualified Simplex Technical Representatives.
STATIC HAZARD - Static electricity can damage components. Therefore, handle as follows:
RADIO FREQUENCY ENERGY - This equipment generates, uses, and can radiate radio frequency energy and if not installed
and used in accordance with the instruction manual, can cause interference to radio communications. It has been tested and
found to comply with the limits for a Class A computing device pursuant to Subpart J of Part 15 of FCC Rules, which are
designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of
this equipment in a residential area may cause interference in which case the user at his own expense will be required to take
whatever measures may be required to correct the interference.
SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES - To ensure proper system operation, this product must
be tested in accordance with NFPA72 after any programming operation or change in site-specific software. Reacceptance test-
ing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to
system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In
addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly
affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
The 4008-9101 and 4008-9121 (includes door mounted annunciator) are In This Chapter
addressable fire alarm control panels capable of monitoring and control-
ling up to 200 initiating devices on an addressable communications cir-
cuit (IDNet). The single-board system and cabinet provide a complete Optional Modules . . . . . . . . . . . . . . . . . . . . . . .1-2
fire alarm for most applications. Initiating Devices . . . . . . . . . . . . . . . . . . . . . . .1-3
Programming Overview . . . . . . . . . . . . . . . . . .1-4
In cases where the installation, wiring, or programming procedure is
identical for both panels, the term 4008 is used. If the procedure applies
only to a specific panel, the complete product name (i.e., 4008-9121 is
used).
The 4008 provides audible and visible indications during alarm, super-
visory, or trouble conditions. Should any of these conditions occur, the
system activates the applicable notification appliances, LEDs, and the
panel’s tone-alert. The indications continue until an operator acknowl-
edges the condition.
The 4008 base system includes the Main System Board (MSB) mounted
in a steel enclosure with locking door. The MSB consists of:
• System power supply (24V filtered @ 3A)
• IDNet loop
• Two, 2A Notification Appliance Circuits (Style Y or Z)
• Two Auxiliary Relay circuits
• One Auxiliary Power tap
• 2 x 20 backlit LCD, LEDs and keypad
• Expansion power supply / NAC connection
• Service port
• DACT
1-1
Technical Manuals Online! - http://www.tech-man.com
Chapter 1. Overview
and 4008-9806 city cards are identical except that the 4006-
9805 provides disconnect switches for each circuit. Model
Specification
4006-9805 must be used for Canadian applications. The City
120 VAC, 60 Hz, 4A; Circuit must be enabled via the panel’s System Options
240 VAC, 50 Hz, 3A before use.
The NACs on the EPS may be configured as AUX 24V Zone 4 Zone 8
NAC 3
NAC 4
power taps. One EPS per system is allowed. The EPS must
be enabled via the panel’s System Options before use.
Figure 1-1 Zone LED Annunciator Module
CITY CIRCUIT CARDS (4006-9805, 4006-9806)
The city circuit card connects to the MSB with a ribbon har- • Remote LED/Switch Module (4610-9111). This
ness to provide connections to either Remote Station module provides the following:
(reverse polarity), or Public Service Fire Communications
- 10 programmable red LEDs
Center (local energy) receiving units. The card has two cir-
cuits - circuit 1 reports alarm or alarm/trouble events - 6 programmable yellow LEDs Green “power on”
(Remote Station only) and circuit 2 can be configured to LED
report trouble events or supervisory events. In the event of a - Yellow “Alarm Silenced” LED
CPU failure, a city card configured for a trouble output - Yellow “Trouble”
sends a trouble to the city circuit. The card is mounted to the
- Yellow “Comm Loss” LED
right of the MSB at the top of the chassis. The 4006-9805
1-2
Technical Manuals Online! - http://www.tech-man.com
Chapter 1. Overview
ZONE 3
Comm Lost
ACK
ZONE 4
ZONE 5
ZONE 6
Reset Trouble
CONTROL
ENABLE addressable heat detector. It has a fixed sensitivity of
ZONE 7
ZONE 8
Lamp
Test
Power 135°F, and may also be programmed for 15°F/minute
rate-of-rise operation. The detector sends a unique iden-
tifier to the control panel so that it may be easily auto-
programmed and verified during normal operation.
Figure 1-2 Remote LED/Switch Annunciator
Module • Combination Photo/Heat Detector (4098-9754,
4098-9754C) is a combination photoelectric detector
• LCD Annunciator. The 4606-9101 Remote LCD and thermal detector in one head. It has the same char-
Annunciator provides remote annunciation of the Fire acteristics as the photo and heat detectors described
Alarm Control Panel (FACP) status. Visual status is pro- above. This device consumes two addresses - one for
vided by a liquid crystal display and LEDs. Audible the photo and one for the heat. The detector sends
annunciation is provided through a piezo sounder. unique identifiers to the control panel so that it may be
Access to the functions of the annunciator can be lim- easily auto-programmed and verified during normal
ited through the use of the annunciator’s keyswitch. operation.
• Duct Detectors. The panel is compatible with any of
For Canadian applications, the LCD annunciator is only the following duct detectors:
suitable for supplementary applications.
- Two-wire detector without relay (4098-9755)
4009-9201 and 4009-9202CA (Canadian) NAC - Two-wire detector without relay, Canadian (4098-
Extender 9755C)
The 4009-9201/4009-9202CA Notification Appliance Cir- - Four-wire detector with relay (4098-9756)
cuit (NAC) Extenders are self-contained adjunct panels. - Four-wire detector with relay, Canadian (4098-
9756C)
The base version of the NAC Extender is a single-board sys-
• Detector Bases. The detectors described above may
tem consisting of four NACs, a power supply and charger,
be installed in the following detector bases:
and two conventional NAC inputs that connect to the host
panel for hardwired control of the NAC extender. - Detector Base w/o Remote Led Connection (4098-
9792)
Option cards are available to provide the following addi- - Detector Base w/o Remote Led Connection, Cana-
tional capabilities: dian, (4098-9792C)
• 4009-9808 Class A Adapter Option Card -- allows fault - Detector Base w/Remote Led Connection (4098-
tolerance in the case of open circuit wiring faults on the 9789)
NACs. - Detector Base w/Remote Led Connection, Cana-
dian (4098-9789C)
• 4009-9807 NAC Option Card -- adds four conventional
Notification Appliance Circuits. - Detector Base w/Relay Drive (4098-9791)
- Detector Base w/Relay Drive, Canadian (4098-
9791C)
Initiating Devices
- Isolator Base (4098-9793)
The 4008 is compatible with the following addressable initi- - Isolator Base, Canadian (4098-9793C)
ating devices. Up to 200 devices (any combination) are
allowed in the system. - Sounder Base (4098-9794)
- Sounder Base, Canadian (4098-9794C)
- Multi Detector Sounder Base (4098-9795)
1-3
Technical Manuals Online! - http://www.tech-man.com
Chapter 1. Overview
- Multi Detector Sounder Base, Canadian (4098- It is recommended that you use the automatic program-
9795C) ming option to perform the following tasks.
- Multi Detector Base w/LED (4098-9796) - Initial programming. After all option cards are
- Multi Detector Base w/LED, Canadian (4098- installed and all devices are addressed and wired,
9796C) use the auto programming feature to add the cards
and devices to the job. After automatic program-
MONITOR MODULES ming the panel will function as a general alarm
panel, assuming all devices are wired correctly. At
• The 4090-9001 Supervised Monitor is a contact closure
that point, you can use manual programming to edit
monitor capable of quad sensing (normal, open, short,
labels, device functions, and alarm groups if neces-
and current-limited conditions). It is a line-powered
sary.
device and consumes one address.
- Adding new cards or points to a previously pro-
• The 4090-9101 (Class B) and 4090-9106(Class A)
grammed job.
Addressable Modules are input devices capable of quad
sensing (normal, open, short, and current -limited condi-
• Manual Programming. This programming option
tions). This device requires separate 24 V power and
allows you to individually change the attributes of each
consumes one loop address.
point, including:
• The 4099-9001 (single action) and 4099-9002/4099-
- Function Type. Determines the way in which the
9003 (dual action) addressable pull stations are latching
point operates (i.e., fire point, trouble point, on til
pull stations that can be reset with a key. They are a line-
silence, etc.).
powered device, consuming one address.
- Custom Label. Automatic programming assigns a
CONTROL MODULES generic label -- such as P1, NAC1, or AUX1 -- to
• 4090-9002 Relay Module is line-powered and contains each point. Manual programming allows you to
a Form-C relay that can be used to control auxiliary assign a 20-character, site-specific label to each
functions (such as elevator recall). point.
• 4090-9116 Isolator Module allows the addressable - Alarm Group. Allows inputs and outputs to be
device loop to continue to function under certain fault associated into groups to implement selective sig-
conditions. naling applications.
• 4090-9007 Signal Zone. System Options
System options are pre-defined modes of operation with a
Programming Overview range of settings from which to choose. System Options
define global operations such as the time and date format,
A job refers to the file containing all of the panel’s program-
door drop timers, and whether the city circuit is enabled, etc.
ming information. A job (also called a CFIG file) can be pro-
System options can be set during either the automatic man-
grammed in one of two ways.
ual programming process.
• Automatic Programming (Chapter 3). The panel’s
auto-program option provides the ability to quickly and Alarm Groups
automatically program the panel’s components and fea-
Alarm groups allow you to implement basic selective signal-
tures. This option does the following:
ling applications. As you program input (smoke detectors,
- Scans the panel’s serial communication channel, monitor zones) and output points (NAC, signal zone, relay),
adding any annunciators. you are given the opportunity to associate the point with an
- Scans the IDNet channel, adding and configuring alarm group number. The number can range from 1-99 and
IDNet devices. each point can be in up to three alarm groups. When pro-
- Adds any installed option cards, such as an AUX gramming is complete, an initiating device can only trigger
relay module or city circuit card. the output devices (relays, NACs) that share its alarm
group(s).
- Performs a duplicate address search, terminating
the operation if a duplicate address is found. Single Station Operation
- DACT information (phone numbers and account Single Station is a mode of operation that applies to IDNet
information) must be manually programmed. devices that use a sounder base (the sensor can be either
photo, heat, or combination photo/heat).
1-4
Technical Manuals Online! - http://www.tech-man.com
Chapter 1. Overview
1-5
Technical Manuals Online! - http://www.tech-man.com
Chapter 1. Overview
Table 1-1 Operator Keys (Continued) Table 1-2 Access Levels and Features
1-6
Technical Manuals Online! - http://www.tech-man.com
Chapter 2. Installation/System Checkout
Expansion
Power Supply
City Connect
Module DACT
AC Voltage Battery
Connection Connection
Battery Battery
2-1
Technical Manuals Online! - http://www.tech-man.com
Chapter 2. Installation/System Checkout
13.250
15.632
Semi-Flush Mounting
Semi-flush mounting involves recessing the cabinet into a
wall and attaching it directly to the wall's studs. At a mini-
mum, 1.5 inches of the cabinet must protrude from the wall
to allow for clearance of the panel door.
2-2
Technical Manuals Online! - http://www.tech-man.com
Chapter 2. Installation/System Checkout
4008
Compatible Bases:
See “Ferrite OR
S
2-3
Technical Manuals Online! - http://www.tech-man.com
Chapter 2. Installation/System Checkout
IDNet Ferrite Bead Compatible Devices for use with IDNet Monitor
IDNet wiring attached to TB 2-1 and 2-2 must pass through ZAMs
a ferrite bead. Wrap the wiring twice through the ferrite A Zone Addressable Module (ZAM) allows the following
bead, as shown in Figure 2-5. non-IDNet devices to be wired to the addressable channel.
Max. #
Head Base(s)
Devices
4098-9685 N/A 20
Max. #
Head Base(s)
Devices
TYPICAL 4-WIRE
DETECT OR
TYPICAL 4-WIRE ZONE 2098-9735 (RELAY SHO WN
24 VDC power 24VDC DEVICES
ENERGIZED)
from listed FACP
E.O.L. RELAY
RED YELLO W
2-4
Technical Manuals Online! - http://www.tech-man.com
Chapter 2. Installation/System Checkout
Class A/Class B NAC Wiring tor from any circuits in use. Leave it installed if circuits
are unused.
The following guidelines and restrictions apply to notifica- • Wiring chart gives maximum distance for 1/4 - 2 A
tion appliance circuits (NACs) located on either the main loads. For Class B circuits, wiring distance is from
system board (MSB) or on the Expansion Power Supply panel terminals to last appliance. For Class A circuits,
(EPS). wiring distance is from panel terminals to last appliance
• All wiring to be 18 AWG (min.) to 12 AWG (max.). and back to terminals. Use of Simplex Model 2081-
• Conductors must test free of all grounds and stray volt- 9044 will reduce the wire distance.
ages before connection to appliances and panel. • When using two-wire audible/visible appliances, maxi-
• All wiring is supervised and power limited. mum wiring capacitance of .22 uF must be considered.
• Wire Class A (Style Z) NACs from B+ and B- to each
appliance as shown. No EOL device is needed. Connect Maximum Wiring Distance in Feet
wires from +/- terminals of the last appliance to the Alarm Line
18 16 14 12
A+/A- terminals as shown. Current
AWG AWG AWG AWG
Resistance
(Amps) (Ohms)
• Voltage Rating: Refer to “NAC Ratings” on Page 2-7
for specific voltage specifications. Maximum ripple: .25 840 1335 2126 3382 12
2-5
Technical Manuals Online! - http://www.tech-man.com
Chapter 2. Installation/System Checkout
NAC - NAC -
733-894
(10K, 1/2W
EOLR NAC+ NAC+
B +
B +
A +
B -
B -
A -
TB1 TB2 TB3
1 2 3 4 5 6 7 8 1 2 3 4 5 1 2 3 4 5 6 7 8
10K, 1/2W
EOLR
NAC+ NAC+
B +
B +
A +
B -
B -
A -
TB1
1 2 3 4 5 6 7 8 9 10
NAC MODULE
2-6
Technical Manuals Online! - http://www.tech-man.com
Chapter 2. Installation/System Checkout
NAC ratings allowed strobe load on either the main or expansion power
supply is 1.35 A. The balance of the 3 A capacity can be
The panel is rated Special Application for 2A maximum per auxiliary loads or audible notification appliances.
NAC with Simplex 4901 and 4906 TrueAlert & TrueAlert
Multi-Candela Notification Appliances. Synchronization of strobes across all NACs in a system is
UL-Listed for the Simplex models noted in the table below.
For all other UL-Listed Notification Appliances, NACs are See the table below for maximum number allowed of each
rated regulated 24 VDC at 1.5 A maximum each. Maximum appliance per NAC.
Rated Max. # per Rated Max. # Rated Max. # per Rated Max. # per
4906-
Current NAC Current per NAC Current NAC Current NAC
2-7
Technical Manuals Online! - http://www.tech-man.com
Chapter 2. Installation/System Checkout
details. 1 2 3 4 5 6 7 8 1 2 3 4 5 1 2 3 4 5 6 7 8
2-8
Technical Manuals Online! - http://www.tech-man.com
Chapter 2. Installation/System Checkout
Digital Alarm Communicating • Wire from TELCO equipment to TB5 using 18 AWG to
24 AWG.
Transmitter (DACT) Wiring
• All wiring is supervised.
• The DACT requires two telephone line connections to • Digital Alarm Communicator Receiver (DACR) com-
meet NFPA72 requirements. Wire from TB5-3/TB5-4 patibility is shown in Table 2-4.
and TB5-7/TB5-8 to an RJ-11 or other Telcom wiring • If wiring is routed outside the building, use of a listed
block for connection to other telephone equipment. The secondary protector is required. Use Simplex Number
DACT will seize control of the telephone line (if neces- 2081-9028 or 2081-9044. A protector must be installed
sary) to transmit emergency messages. When wired as at each building exit/entrance. Each 2081-9028 adds .2
shown, the DACT will properly control access to lines ohm wiring resistance. Each 2081-9044 adds 6 ohms
in an emergency. wiring resistance. Use of the 2081-9044 will signifi-
• Telephone wiring from public telephone network con- cantly reduce wiring distance.
nects to TB5-1/TB5-2 and TB5-5/TB5-6.
1 2 3 4 5 6 7 8 1 2 3 4 5 1 2 3 4 5 6 7 8
DANGER
HIGH VOLTAGE
IN THIS AREA
DACT TELEPHONE
CONNECTIONS
1 2 3 4 5 6 7 8
TB5
R T R T R T R T
I I I I I I I I
N P N P N P N P
G G G G
2-9
Technical Manuals Online! - http://www.tech-man.com
Chapter 2. Installation/System Checkout
Contact ID
(Preferred)
3/1 Standard
1800/2300 Hz TBD
(10 and 20PPS) With 9032
Line Card
3/1 Standard
1900/1400 Hz TBD
(10 and 20PPS) With 9032
Line Card
4/2 Standard
1800/2300 Hz TBD
(10 and 20PPS) With 9032
Line Card
4/2 Standard
1900/1400 Hz TBD
(10 and 20PPS) With 9032
Line Card
Radionics
BFSK TBD
1800/2300 Hz With 9032
Line Card
Radionics
BFSK TBD
1900/1400 Hz With 9032
Line Card
SIA TBD
Notes:
1. With 685-8 Line Card
2. With Rec-11 Line Card
3. These receivers are also Factory Mutual (FM) approved.
2-10
Technical Manuals Online! - http://www.tech-man.com
Chapter 2. Installation/System Checkout
Auxiliary 24V Power Wiring • Compatible with Simplex 4098 Series Peripherals; 2098
Series Relay Modules; all Simplex 4090 Series IDNet
• All wiring is to be 18 AWG (min.) to 12 AWG (max.) Peripherals; and 4610-9111 / 4606-9101 Annunciators.
• Conductors must test free of all grounds and stray volt- • If wiring is routed outside the building, use of a listed
ages before connection to appliances and panel. secondary protector is required. Use Simplex Model
• All wiring is supervised and power limited. 2081-9028 or 2081-9044. A protector must be installed
at each building exit/entrance. Each 2081-9044 adds 6
• Voltage rating (24 VDC special application): 1 V p-p
ohms wiring resistance, and is rated for 200mA. Each
ripple (maximum)
2081-9028 adds .2 ohms wiring resistance, and is rated
- 0.5 A maximum available aux 24 V from EPS
for more than 1/2A Aux. 24V capacity.
- Additional 0.5 A maximum available from Main
System Board (MSB) AUX 24 V • Compatible devices must operate from a range of 19.5
- 3 A total available from MSB NACs and MSB to 28 VDC or greater, and have a total current draw of 1/
AUX 24 V. 2 A or less.
- 3 A total available from EPS NACs and EPS AUX
24 V.
1 / 2 MAX.
1 2 3 4 5 6 7 8 1 2 3 4 5 1 2 3 4 5 6 7 8
MSB AUX 24V
1 / 2 MAX.
EPS
DANGER
1
HIGH VOLTAGE
2
3
IN THIS AREA
NAC MODULE
4
5
6
DACT TELEPHONE
7
CONNECTIONS
8
9
1 2 3 4 5 6 7 8
10
TB5
2-11
Technical Manuals Online! - http://www.tech-man.com
Chapter 2. Installation/System Checkout
City Connect Module Wiring • Conductors must test free of all grounds.
• For specific information about reverse polarity and local
• City connect module mounts to the main system as energy circuits see Figure 2-14.
shown. Refer to City Module Installation Instructions
• If wiring is routed outside the building, use of a listed
for details.
secondary protector is required. Use Simplex Model
• City module consists of two circuits that are jumper- Number 2081-9044. A protector must be installed at
configured. Circuits may be configured for reverse- each location the wiring enters or exits a building. Each
polarity or local energy operation. See jumper setting 2081-9044 adds 6 ohms wiring resistance and is rated
table for details. Modules must also be added to the sys- for 200 mA. Maximum wiring resistance is reduced by
tem configuration. See “System Options” later in this 6 ohms for each 2081-9044 used.
manual.
• Circuits are shipped with 3.3K, 1/2W resistor installed.
• All wiring to be per NFPA-72, NEC, and local codes. Remove resistor before wiring circuit. Leave installed
Minimum 20 AWG for reverse polarity circuits; mini- on unused circuits.
mum 18 AWG for local energy circuits.
• Wiring is supervised for opens and grounds, but not
power-limited.
2
INTENDED FOR CONNECTION TO A POLARITY CITY CONNECT P6 3
HIGH VOLTAGE
WITH 2200 OHM TRIP COIL (6200 OHM TOTAL)
IN THIS AREA
3A 3A
FUSE FUSE
SW SW
1 2 3 4
SEE DETAIL A
P3 P5 CKT 1 CKT 2
10 9 10 9
8 7 8 7 1
2
P6
LE LE
CITY CONNECT 3
6 5 6 5
4
P2 P4
RP
4 3
RP
4 3
MODULE 1
LE LE 2
2 1 2 1 P6
RP RP 3
4
P3 P5
FUSE FUSE
P3: 1 - 2, 3 - 4, 5 - 6 P3: 7 - 8, 9 - 10
CITY 1
P2: 2 - 3 P2: 1 - 2
P5: 1 - 2, 3 - 4, 5 - 6 P5: 7 - 8, 9 - 10 SW SW
CITY 2
P4: 2 - 3 P4: 1 - 2 1 2 3 4
DETAIL A
2-12
Technical Manuals Online! - http://www.tech-man.com
Chapter 2. Installation/System Checkout
AUX. TBL.
RELAY RELAY
J C
U E
M N
P T
E E
R R
1 2 3 4 5 6 7 8 1 2 3 4 5 1 2 3 4 5 6 7 8
JUMPER
CENTER
2-13
Technical Manuals Online! - http://www.tech-man.com
Chapter 2. Installation/System Checkout
1 2 3 4 5 6 7 8 1 2 3 4 5 1 2 3 4 5 6 7 8
EPS
DANGER
1
B+ B-
HIGH VOLTAGE
2
3
IN THIS AREA
NAC MODULE
B+ B- A+ A-
5
6
DACT TELEPHONE
7
CONNECTIONS
8
9
1 2 3 4 5 6 7 8
10
TB5
LINE
734 - 179
WHITE
BLACK
WHITE / BLACK HARNESS 734 - 179
2-14
Technical Manuals Online! - http://www.tech-man.com
Chapter 2. Installation/System Checkout
1 2 3 4 5 6 7 8 1 2 3 4 5 1 2 3 4 5 6 7 8
EPS
DANGER
1
3B+
HIGH VOLTAGE
2
3B-
3
IN THIS AREA
NAC MODULE
3A+
4
3A-
5
4B+
6
4B-
DACT TELEPHONE
7
4A-
CONNECTIONS
8
4A-
9
24V
1 2 3 4 5 6 7 8
10
0V
TB5
R B 734 - 180
BLACK
RED
R B
BATTERY CONNECTOR
CONNECT TO
BATTERY TERMINALS
(FUSED ON PCB)
2-15
Technical Manuals Online! - http://www.tech-man.com
Chapter 2. Installation/System Checkout
SYSTEM NORMAL
12:00 am 03/09/03
+ - + -
LINE NEUTRAL BATT EPS
If other troubles exist in the system, the following is dis-
Figure 2-18 Location of Depleted Battery Jumper played:
Acceptance Testing
When you are finished with the original installation, pro-
gramming and all modifications, conduct a complete opera-
tional test on the entire installation to verify compliance with
applicable NFPA standards and Local Codes. Testing should
be conducted in the presence of a representative of the
Authority Having Jurisdiction (AHJ), and the customer's
representative. Follow procedures outlined in Chapter 10
"Inspection, Testing, and Maintenance" of NFPA standard
72-2002 and as dictated by local codes.
Figure 2-19 Safety Ground and Ferrite Bead
2-16
Technical Manuals Online! - http://www.tech-man.com
Chapter 2. Installation/System Checkout
Testing Circuit Supervision Batteries should be tested by discharging them with a suit-
Use the following procedures to confirm that IDNet and able tester and verifying that battery voltage is at least 21V
NACs and are supervising for opens, shorts and grounds. when fully discharged. Battery discharge tests should be per-
The right column in this table shows the LEDs that illumi- formed annually, and batteries should be replaced no longer
nate when an open, short, or ground occurs on a specific cir- than 4 years from date of installation.
cuit.
The battery charger is temperature-compensated per battery
manufacturer recommendations. There is no charger voltage
Table 2-5 Testing Circuit Supervision adjustment. At normal room temperature, battery voltage
should be 27-27.6V when the battery set is fully charged. At
Condition Corresponding LEDs higher temperatures, the voltage will be lower. At lower
To create an open: Illuminates the System Trouble temperatures, the voltage will be higher. The battery charger
LED. has a negative temperature coefficient. At higher tempera-
Class A or B Circuit. Disconnect the
“out” wiring from any device. tures, the chemical process in the battery is accelerated. This
means that the ideal charger voltage is lower. Likewise, at
To create a short: Illuminates the System Trouble
LED.
lower temperatures, a higher output voltage is required for
Apply a zero ohm jumper across full charge. Control of battery charge voltage relative to
the IDNet terminal blocks, or across
the loop +/- terminals on a device.
ambient temperature prolongs battery life. The chart below
shows the proper range of battery voltage across the speci-
To create an Earth ground: Illuminates the System Trouble fied operating range of the equipment. The chart is for 12-
LED.
Place a 10K or smaller value resis- cell battery sets, with nominal 24V rating.
tor from supervised wiring to Earth If you have programmed a front
ground. panel or annunciator LED to detect
Earth ground conditions, the pro-
grammed LED also illuminates. Table 2-6 Temperature Effect on Batteries
Refer to “Common LED Applica-
tions” in Chapter 6 of this manual
for information on programming an Min. Max.
Temp Temp V/cell V/cell
Earth Fault LED. Battery Battery
(C) (F) (min) (max)
Voltage Voltage
Battery Tests
The batteries used with the 4008 FACP are sealed lead-acid
type. Batteries should be installed within six months of the
date of manufacture.
2-17
Technical Manuals Online! - http://www.tech-man.com
Technical Manuals Online! - http://www.tech-man.com
Chapter 3. Auto-Programming
The Auto-Program option provides the ability to quickly and automati- In This Chapter
cally program the panel’s components and features for general alarm
operation. It automatically scans the serial communication channel, add-
ing any annunciators found, polls the IDNet channel and configures any Configure All. . . . . . . . . . . . . . . . . . . . . . . . . . .3-1
IDNet devices found, and adds any option cards found. Detect New Hardware . . . . . . . . . . . . . . . . . . .3-2
Restore Factory Defaults . . . . . . . . . . . . . . . . .3-2
Edit System Options. . . . . . . . . . . . . . . . . . . . .3-2
Auto-Program can perform the following:
Restore Default System Options . . . . . . . . . . .3-3
• Reconfigure all hardware Saving the Configuration . . . . . . . . . . . . . . . . .3-3
• Add new hardware Default Programming Assignments . . . . . . . . .3-3
• Restore factory defaults
• Edit system option settings
Configure All
This option starts the panel with a new configuration. If a previous con-
figuration is present and this option is selected, it erases the previous
configuration and creates a new one with the currently connected hard-
ware.
1. Press <MENU> to select the main menu.
2. Press <NEXT> or <PREVIOUS> until the [Auto-Program] menu
item is displayed and then press <ENTER>. The following appears:
FIRE ALARM
SUSPENDED
3-1
Technical Manuals Online! - http://www.tech-man.com
Chapter 3. Auto-Programming
3-2
Technical Manuals Online! - http://www.tech-man.com
Chapter 3. Auto-Programming
Table 3-1 System Options (Cont’d) When the configuration is saved, the panel will automati-
cally restart and run through its self-test procedure.
Option Settings
Single Station Selects whether or not sounder base PHOTO SMOKE Smoke Detector
devices operate in single station mode.
SPHOTO SMOKE Smoke Detector with sounder output
Cross Zone Selectable per alarm group. Selects (single-station operation)
whether one alarm or more than one
alarm is required to trigger outputs for RPHOTO SMOKE Smoke Detector with relay (general
that alarm group. alarm operation)
Alarm Groups programmed as Cross IPHOTO SMOKE Smoke Detector with isolator
Zone shall not contain any devices pro-
grammed with the VSMOKE Input HEAT HEAT Heat Detector
Function Type.
SHEAT HEAT Heat Detector with sounder output (sin-
gle-station operation)
Restore Default System Options RHEAT HEAT Heat Detector with relay output (gen-
eral alarm operation)
This option allows the operator to restore the factory-default
options that may have been edited. It will erase any edits that IHEAT HEAT Heat Detector with isolator
were performed in the "Edit System Options" menu, but OHEAT HEAT Rate-of-rise Heat Detector
leave any card/point programming intact.
OSHEAT HEAT Rate-of-rise Heat Detector with
sounder output (single-station opera-
Saving the Configuration tion)
When the Auto-Programming operation is complete, press ORHEAT HEAT Rate-of-rise Heat Detector with relay
the <EXIT/CLEAR> key. The following screen will be dis- output (general alarm operation)
played. OIHEAT HEAT Rate-of-rise Heat Detector with isolator
JOB HAS CHANGED AZONE FIRE Class A General Alarm Fire Monitor
[Cont] Dscrd Save Zone
3-3
Technical Manuals Online! - http://www.tech-man.com
Chapter 3. Auto-Programming
Table 3-2 Default Function Type Assignments, • Tone else pulse dialing
IDNet Devices, NACs, and Relays (Cont’d) • AC Fail reporting delay is 6 hours
Function
• Reporting format is CID
Device Description
Type • Primary and Secondary Phone Number. There are no
values for the primary and secondary phone numbers or
SIGNAL OTS General Alarm Signal (on-til-silence)
account codes.
ISOL ISOL IDNet loop isolator • The CID Group and CID Point Identifier default to the
SIG1-2 OTS General Alarm Signal (on-til-silence)
IDNet device address.
• Default event codes are shown in Table 3-4.
SIG3-4 OTR General Alarm Signal (on-til-reset)
AUX1 OTR General Alarm Relay (on-til-reset) Table 3-4 Default CID Event Codes
AUX2 TRBL Trouble Relay (on-til-clear) Function Type Fire Supervisory Trouble
Table 3-3 Default NAC, Relay, Signal Circuit Output SMOKE 111 - 330
Mode Assignments
SO - 200 330
SIG1-2 (NAC) Temporal Code A three pulse coding pattern SUPV - 200 330
consisting of three ½ second pulses, each sep-
arated by ½ second silence. Each group of UTIL - - 330
three pulses is separated by 1.5 seconds of
TROUBLE - - 330
silence.
VSMOKE 111 - 330
SIG3-4 (NAC Synchronized. Used with visual NACs. Pro-
grams all visuals to flash simultaneously. LATSUPV - 200 330
AUX1 & AUX2 Steady on STYLEC 110 - 330
RELAY Modules Steady on OTHER TRBL* - - 330
SIGNAL Mod- Steady on
ules *Any other trouble not specifically mentioned would have a code of 330.
For example, a trouble on an output device would report an event code of 330.
Annunciator Defaults
Annunciator cards found during the Auto-Program process
are added into the default configuration.
• LCD Annunciators are configured to receive all events.
Refer to Chapter 6 for information on manually pro-
gramming which events are received by the LCD
Annunciator.
• LED Annunciators and 24-I/O modules are not pro-
grammed for default operation.
DACT Defaults
The defaults for the DACT are listed below. Refer to Chap-
ter 5for information on manually programming the DACT.
3-4
Technical Manuals Online! - http://www.tech-man.com
Chapter 4. Manually Programming
IDNet Points
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Stan-
dard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be
limited to specific values or not used at all as indicated below.
Program Feature or Option Permitted in UL 864? (Y/N) Possible Settings Settings Permitted in UL 864
This chapter discusses manually adding, deleting, and editing the In This Chapter
attributes of the panel’s IDNet points.
In most cases, it is recommended that you use the panel’s auto program- Accessing IDNet Programming Menus . . . . . .4-2
ming feature (see Chapter 3) when initially programming the panel, or Adding an IDNet Device. . . . . . . . . . . . . . . . . .4-2
when adding devices to an existing job. Auto programming scans the Editing IDNet Device Attributes . . . . . . . . . . . .4-2
IDNet channel and automatically adds devices that it finds to the job. Deleting an IDNet Point . . . . . . . . . . . . . . . . . .4-8
Once the devices are added, use the manual programming procedures
described in this chapter to adjust the point attributes listed below to
your site-specific needs.
To manually add, edit, or delete a IDNet point, you must first login at
Access Level 4. Refer to Chapter 1 for information on doing this.
4-1
Technical Manuals Online! - http://www.tech-man.com
Chapter 4. Manually Programming IDNet Points
Accessing IDNet Programming Note: Make sure the address shown on the display corre-
sponds to the physical address, set via dip switches, of the
Menus device.
1. Press the <MENU> key. Press <NEXT> or <PREV>
Refer to “Editing IDNet Device” for information on setting
until the [Programming] option is displayed. Press
device attributes.
<ENTER>. The following displays:
4-2
Technical Manuals Online! - http://www.tech-man.com
Chapter 4. Manually Programming IDNet Points
4090-9007
Zone Individual Addressable Module (IAM) for SIGNAL
Class A or B Signal Circuits
4090-9001
IAM
Supervised Individual Addressable Module (IAM)
4090-9002
RIAM
Indiv. Addressable Module with Relay
4-3
Technical Manuals Online! - http://www.tech-man.com
Chapter 4. Manually Programming IDNet Points
4090-9101 IDNet: 1
Class B Zone Addressable Module for monitor MBZAM [PULL]
devices
4-4
Technical Manuals Online! - http://www.tech-man.com
Chapter 4. Manually Programming IDNet Points
Table 4-3 Input Function Types (Continued) Table 4-3 Input Function Types (Continued)
Function Function
Device State = Status Device State = Status
Type Type
4-5
Technical Manuals Online! - http://www.tech-man.com
Chapter 4. Manually Programming IDNet Points
Table 4-3 Input Function Types (Continued) Table 4-4 Output Function Types
Function Function
Device State = Status Description
Type Type
Relay activates steady on general alarm; turns off NAC activates when there is a trouble condition
RRELAY
when system reset occurs. TRBL active in the system. NAC is on until trouble condi-
tion is acknowledged.
Relay activates steady when there is a supervisory
SUPV condition active in the system. Relay is on until AUXPWR Not Applicable - cannot be used with IDNet output.
supervisory condition is acknowledged.
MDL Not Applicable - cannot be used with IDNet output.
Relay activates steady when there is a trouble
TRBL condition active in the system. Relay is on until
trouble condition is acknowledged.
Note: Elevator recall requires the following:
• The relay must have a function type of Primary or Alter-
AUXPWR Not Applicable - cannot be used with IDNet output.
nate and must be wired to the appropriate elevator con-
Relay activates on general alarm. Relay is tied to trol contact.
PRIMARY
Primary Elevator Recall contacts. See Note below. • The initiating devices used to trigger elevator recall
Relay activates on general alarm. Relay is tied to must be associated with the following alarm groups.
ALTERN Alternate Elevator Recall contacts. See Note - Alarm Group 98. Associate all zones used to recall
below.
the elevator to the primary floor in this alarm
Relay provides 24V power to four wire detectors. group.
DRESET Relay turns off for 5 secs on system reset) - Alarm Group 99. Associate all zones used to recall
the elevator to the alternate floor in this alarm
group.
4-6
Technical Manuals Online! - http://www.tech-man.com
Chapter 4. Manually Programming IDNet Points
Editing Point Labels The following is a list of all words in the library.
1. Follow the steps in “Accessing Menus”. Make sure to Table 4-5 Word Library
choose IDNet as the type of device to program.
<ENTER>=Accept
Prg: [IDNet] Default of blanks 5th Floor
2. Press <ENTER>. The top line shows the custom label North Flr_1 Garage
assigned to the first IDNet point. Use the <NEXT> and
South Flr_2 Hallway
<PREV> keys to scroll through the list of points.
3. Press <ENTER> when the appropriate point is dis- East Flr_3 HVAC_Room
played. A prompt appears, asking you to specify the West Flr_4 Kitchen
function type. Use the <NEXT> and <PREV> keys to
scroll through the choices until <Edit Label> appears. Front Flr_5 Lobby
Centr RM __ Office
IDNet1
Fn: [Edit Label] rear Basement Patient
4. Press <ENTER>. A cursor appears beneath the leftmost upper Boiler_RM Restroom
letter of the currently assigned custom label. Use the left
lower Classroom Room
and right arrow keys to move the cursor between letters.
main Closet__ Stairway
You can edit a label in one of three ways:
first Corridor Storeroom
• Using the Keypad. Press the alphanumeric key cor-
responding to the letter you want. For example, for 2nd Elect_RM Wing
the letter “C”, press the “2” key on the keypad three
3rd Elevator Zone
times. Use the left and right arrow keys to move to
the next letter in the label. 4th Entrance
• Use the <NEXT> and <PREV> keys. Each time
you press the <NEXT> key, the display advances to 5. Pressing <ENTER> saves the current label. Pressing
the next character. Likewise, each press of the <EXIT/CLEAR> will quit label editing without saving.
<PREV> key moves backward one character. Use
the left and right arrow keys to move to the next let- Clear Point Label
ter in the label.
• Use the Word Library, which is a stored list of com- The "Clear Point Label" menu performs the same function as
mon words sorted alphabetically. Press the "Edit Point Label" described above except that it clears the
<FUNCTION> key on the front panel. A prompt point's currently assigned label first.
similar to the following appears.
Alarm Group
IDNet1
The Alarm Group programming choice allows you to per-
<FUNC> = Word Library
form input-output (selective signaling) programming in a
To jump to a word, press the alphanumeric key cor- fast, flexible manner. The Alarm Group concept allows the
responding to the first letter in the word. For exam- activation of a particular input to control a specific set of
ple, to use the word Floor, press the “3” key outputs. An IDC can be in up to three different Alarm
repeatedly until Floor appears. Groups. For additional details on Alarm Groups and their
operation, refer to “Programming Overview” in Chapter 1.
IDNet:1
ALM GRP: [00] 00 00
4-7
Technical Manuals Online! - http://www.tech-man.com
Chapter 4. Manually Programming IDNet Points
The right and left arrow keys allow you to move the focus
brackets to a different alarm group, while the <NEXT> and
<PREV> keys allow you to select the desired group number.
Pressing <ENTER> will accept any changes made and exit,
and the <EXIT/CLEAR> key will quit the alarm group edit
without saving.
4-8
Technical Manuals Online! - http://www.tech-man.com
Chapter 5. Manually Programming NACs,
Relays, and DACT
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Stan-
dard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be
limited to specific values or not used at all as indicated below.
Program Feature or Option Permitted in UL 864? (Y/N) Possible Settings Settings Permitted in UL 864
Manually programming NAC, programmable relay, and DACT points In This Chapter
allows you to set the attributes of the point to the specific values
required for the job. You can create a custom label for each point,
change the way in which the NACs, programmable relays, and DACT Accessing Menus . . . . . . . . . . . . . . . . . . . . . . 5-2
operate, or add a NAC or relay to an alarm group for selective signaling. Programming NACs . . . . . . . . . . . . . . . . . . . . 5-2
Programming AUX Relays . . . . . . . . . . . . . . . 5-4
It is recommended that you use the panel’s auto programming feature Programming DACT. . . . . . . . . . . . . . . . . . . . 5-6
Accessing DACT Menu . . . . . . . . . . . . . . . . . 5-6
(see Chapter 3) when initially programming the panel, or when adding
Programming DACT Options . . . . . . . . . . . . . 5-7
devices to an existing job. Auto programming automatically programs
Programming Contact ID (CID) Points . . . . . . 5-9
the NACs, Relays, and DACT with default values. You can then use the Programming Event Codes . . . . . . . . . . . . . 5-10
manual programming procedures described in this chapter to adjust the Saving Changes. . . . . . . . . . . . . . . . . . . . . . 5-11
following values.
To manually add, edit, or delete a point, you must first login at Access
Level 4. Refer to Chapter 1 for information on doing this.
If an Expansion Power Supply Module is installed in the system, you
must first set the Expansion Power Supply system option to ON before
5-1
Technical Manuals Online! - http://www.tech-man.com
Chapter 5. Manually Programming NACs, Relays, and DACT
4. Possible choices for this prompt are listed below. Use NAC1
the <NEXT> and <PREV> keys to scroll to the appro- [SSIG] TEMPRL
priate choice and then press <ENTER>.
• NAC 5. Use the <NEXT> and <PREV> keys to select the
appropriate Function. Use the right and left arrow keys
• RELAY (Use for panel’s on-board AUX relays)
to move the cursor between the function type and the
Select the operation you want to perform and see the appro- coding pattern. Use the <NEXT> and <PREV> keys to
priate section in this chapter. set the pattern to the appropriate choice.
6. Pressing <ENTER> will accept any changes made and
Programming NACs exit, and the <EXIT/CLEAR> key quits editing without
saving
Use the following procedure to edit the programming of the
Note: Refer to the table located at the top of Page 5-1 for UL
two Notification Appliance Circuits (NACs) on the base
864 compliant options.
panel, or the two optional NACs on the expansion power
supply. NACs cannot be added or deleted, only edited.
5-2
Technical Manuals Online! - http://www.tech-man.com
Chapter 5. Manually Programming NACs, Relays, and DACT
Compatible visual-only devices include: Typically used for process monitoring function. For
• 4906-9101, wall-mount, visual-only, red example, a relay on a machine is tied to the IDC.
• 4906-9102, ceiling-mount, visual-only, red When the relay activates, the utility IDC activates
• 4906-9103, wall-mount, visual-only, white and triggers the utility NAC.
• 4906-9104, ceiling-mount, visual-only, white
Table 5-2 NAC Operation Settings
Compatible A/V devices include:
QALERT
• 4906-9127, wall-mount, red
Operation Description
• 4906-9128, ceiling-mount, red
• 4906-9129, wall-mount, white
• 4906-9130, wall-mount, red Standard Temporal coded pattern. A three pulse
coding pattern consisting of three ½ second
Temporal pulses, each separated by ½ second silence. Each
Compatible audible-only devices include:
group of three pulses is separated by 1.5 seconds
of silence.
• 4901-9820, wall-mount, red, horn only. Horn
must be selected for two-wire horn strobe con- Generates synchronization pulse for visual-only
trol. See Horn Instruction manual.
NAC circuits that use the following visual-only
devices.
General Alarm (on til-silence). Use for NAC circuits Synch
containing only audible devices. • 4906-9101, wall-mount, visual-only, red
• 4906-9102, ceiling-mount, visual-only, red
• 4906-9103, wall-mount, visual-only, white
SSIG Compatible audible-only devices include:
• 4906-9104, ceiling-mount, visual-only, white
• 4901-9820, wall-mount, red, horn only.
Steady Steady On
NAC1
Signa1 1/4
5-3
Technical Manuals Online! - http://www.tech-man.com
Chapter 5. Manually Programming NACs, Relays, and DACT
NAC1 NAC1
FN: [Function Type] Fn: [Alarm Groups]
4. Use the <NEXT> and <PREV> keys until <Edit Label> 5. Press <ENTER>. A prompt similar to the following
is displayed. For example: appears.
5. Press <ENTER>. The current custom label for the point 6. Use the <NEXT> and <PREV> keys to scroll the num-
is displayed on the top line of the display. A cursor is ber in the brackets. Use the right and left arrow keys to
shown below the selected character in the label. Use the move between the alarm groups. Press <ENTER> when
right and left arrow keys to move the cursor to a differ- all the values are set correctly.
ent character to edit; use the <NEXT> and <PREV>
keys to scroll through the characters. Programming AUX Relays
6. Pressing the <ENTER> key will save the current label,
and <EXIT/CLEAR> will quit label editing without Aux Relay programming allows you to define the following
saving. options:
• Function, defines the following for a relay.
Clear Point Label - When the Relay activates and deactivates.
The "Clear Point Label" menu performs the same function as - The "output method" that defines how the Relay
"Edit Point Label" described above except that it clears the activates (coded, steady, etc.)
point's currently assigned label first. • Edit or Clear Point Label. Allows you to set a 40 char-
acter label for the relay point.
Editing Alarm Groups • Alarm Group. Allows you to associate the relay with up
Alarm groups allow you to program selective signaling. to 99 groups of initiating devices, providing the ability
Assign the NAC an alarm group number from 1 to 99. to perform selective activation of the relay.
Assign the same alarm group number to the initiating
1. Follow the steps in “Accessing Menus.” Make sure to
device(s) that you want to control the NAC. Each NAC can
choose Relay as the type of device to program.
be in up to three groups.
1. Follow the steps in “Accessing Menus”. Make sure to <ENTER>=Accept
choose NAC as the type of device to program Prg: [Relay]
5-4
Technical Manuals Online! - http://www.tech-man.com
Chapter 5. Manually Programming NACs, Relays, and DACT
6. Pressing <ENTER> will accept any changes made and Standard Temporal coded pattern. A
exit. <EXIT/CLEAR> key will quit the alarm group edit three pulse coding pattern consisting
without saving. of three ½ second pulses, each sepa-
Temporal rated by ½ second silence. Each
Note: Refer to the table located at the top of Page 5-1 for UL group of three pulses is separated by
864 compliant options. 1.5 seconds of
silence.
Table 5-3 Relay Function Types Steady Steady On
AUX1
Alarm 1/2
AUX1
FN: [Hardware Type]
5-5
Technical Manuals Online! - http://www.tech-man.com
Chapter 5. Manually Programming NACs, Relays, and DACT
4. Use the <NEXT> and <PREV> keys until <Edit Label> 2. Press <ENTER>. The Programming menu appears.
is displayed. For example:
<ENTER>=Accept
AUX1 Prg:[Points]
Fn: [Edit Label]
3. Press <NEXT> or <PREV> until DACT is shown.
5. Press <ENTER>. The current custom label for the point
<ENTER>=Accept
is displayed on the top line of the display. A cursor is
Prg: [DACT]
shown below the selected character in the label. Use the
right and left arrow keys to move the cursor to a differ- 4. Press <ENTER>. The following prompt appears.
ent character to edit; use the <NEXT> and <PREV>
keys to scroll through the characters. <ENTER>=Accept
DACT: [Options]
Pressing the <ENTER> key will save the current label, and
5. Use the <NEXT> and <PREV> keys to select one of the
<EXIT/CLEAR> will quit label editing without saving.
following choices.
Clear Point Label • Options. This choice allows you to program a wide
range of DACT parameters. (supervising station
The "Clear Point Label" menu performs the same function as
phone numbers and account codes, dialing mode,
"Edit Point Label" described above except that it clears the
communications format, etc.). Refer to “Program-
point's currently assigned label first.
ming DACT Options” below for specific informa-
tion.
Programming DACT
Note: If no DACT is installed, use this option to
The panel’s DACT (Digital Alarm Communicator Transmit-
disable the DACT. See “Programming DACT
ter) allows the panel to use one or two telephone lines to call
Options,” below for more information.
a supervising station and report a local alarm, trouble, or
supervisory condition. • Event Codes. The 3/1, 4/2, BFSK, and SIA com-
munication formats support per-event reporting of
This section describes programming the DACT options to fire alarms, trouble conditions, etc. With these for-
specify the characteristics of the DACT’s phone connection, mats, the supervising station receives a general
communication format, and the format of the event or CID code for an event type that does not specify the
codes used by the supervising station. activated point.
Login at Level 4 before starting DACT programming. See Use this choice to verify and edit the codes for each
Chapter 1 for information on doing this. event type. Refer to “Programming Event Codes,”
below for more information.
Note: The <Exit/Clear> key is used to back out of menus or
displays and return to the top-level menu structure. Where Note: Only the 3/1 and 4/2 formats allow editing of
possible, the <Exit/Clear> key backs out one level at a time. event codes.
There are cases, however, that the Exit/Clear key will return
• CID Points. The Contact ID communication for-
the operator directly to the top-level menu.
mat supports per-point reporting of system events.
The supervising station receives a code identifying
Accessing DACT Menu the point and the event type (alarm, trouble, etc.).
With this format, the DACT can also send a resto-
1. Press the <MENU> key. Press <NEXT> or <PREV> ral code to the supervising station after the device
until the [Programming] option is displayed. Press experiencing the alarm, trouble, or supervisory
<ENTER>. The following displays: condition is restored to a normal state. Use this
choice to verify and edit the activation and restoral
FIRE ALARM
codes for each point. Refer to “Programming Con-
SUSPENDED
tact ID (CID) Event Codes,” below for more infor-
<ENTER> to Program mation.
<EXIT> to resume
5-6
Technical Manuals Online! - http://www.tech-man.com
Chapter 5. Manually Programming NACs, Relays, and DACT
Programming DACT Options Note: The following special characters are available for
use when setting the primary and secondary phone num-
1. Follow the steps in “Accessing DACT Menu”. Make bers.
sure to choose Options as the type of device to program. • B -- Use if it is necessary to input a DTMF (touch-
tone) asterisk (*) into the phone number.
<ENTER>=Accept
DACT: [Options] • C -- Use if it is necessary to input a DTMF pound
sign (#) into the phone number.
Enabling/Disabling DACT • D -- Inserting this character into the phone number
1. Press <ENTER> at the DACT: [Options] prompt. The causes a 3 second delay at the point at which the D
following prompt appears, allowing you to enable or appears.
disable the DACT. - E -- This character causes the DACT to wait two
seconds for a secondary (outside line) dial tone. It
<ENTER>=Accept may be necessary to use this character if you must
Opt: [Enable DACT] dial a specific number (9, for example) to get an
outside line on the phone system. For example, 9E
2. Press <ENTER>. The following appears.
would cause the DACT to request an outside line
Enable DACT and then wait 2 seconds for the secondary dial tone
[OFF] before proceeding with the rest of the phone num-
ber. If you use the “E” special character, make sure
3. Use the <NEXT> or <PREV> keys to change the set- to set the Dial Mode to Tone; do not use Tone
ting to ON. else Pulse.
By default, the DACT is enabled, but unconfigured. The 3. Press <ENTER>. The prompt shown in Step 1 reap-
DACT will report a configuration trouble until the pears.
phone numbers and account numbers are programmed, 4. Press the <NEXT> key. The prompt for the primary
or until it is disabled if it will not be used. account number appears.
4. Press <ENTER>. A prompt appears, asking you to con-
firm the choice. Setting Primary Account Number
The primary account number is a unique identifier assigned
5. Press <ENTER> to confirm the selection. The prompt
and used by the supervising station.
shown in Step 1 reappears. Use the <NEXT> key to
move to the prompt for primary phone number. Pri Account #
[0] 000
Setting Primary Phone Number
The next prompt allows you to set the Primary Phone Num- 1. Use the arrow keys to move the cursor from one number
ber of the supervising station. This is the number that the to another. Use the NEXT and PREV keys or the key-
DACT dials first. pad to enter each number.
1. Press <ENTER>. The following prompt appears. 3. Press <ENTER>. The prompt shown above Step 1 reap-
pears.
Pri Phone # 4. Press the <NEXT> key. The prompt for the Secondary
[X] XXXXXXXXXXXXXXXX Phone Number appears.
2. Use the arrow keys to move the cursor from one digit to
Setting Secondary Phone Number
another. Use the keypad numbers, or use the NEXT and
PREV keys to enter each number. Press <ENTER> The Secondary Phone Number specifies the alternate phone
when the number is correctly entered. A prompt appears number that the DACT can use if attempts to dial the pri-
asking you to confirm the number that you entered. mary phone number fail.
5-7
Technical Manuals Online! - http://www.tech-man.com
Chapter 5. Manually Programming NACs, Relays, and DACT
Note: You can also use the special characters B, C, D, and E 2. Use the NEXT and PREV keys to move from one
when specifying the Secondary Phone Number. See the choice to another. Choices are tone (touchtone), pulse,
description of these characters in the section “Setting Pri- and tone else pulse (attempt to dial with a touchtone for-
mary Phone Number” above. mat and if that fails, use a pulse format).
1. Press <ENTER>. The following prompt appears. 4. Press <ENTER>. The prompt shown above Step 1 reap-
pears.
Sec Phone # 5. Press the <NEXT> key. The prompt for the Pulse Rate
[X] XXXXXXXXXXXXXXXX appears.
2. Use the arrow keys to move the cursor from one digit to
another. Use the keypad numbers, or use the NEXT and Setting Pulse Rate
PREV keys to enter each number. Press <ENTER> The Pulse Rate option specifies the pulse rate used with
when the number is correctly entered. A prompt appears either the 3/1 or 4/2 pulse format. This option does not apply
asking you to confirm the number that you entered. to other formats.
3. Press <ENTER> again. The prompt shown above Step 1 <ENTER> = Accept
reappears. Pulse Rate
4. Press the <NEXT> key. The prompt for the Secondary
Account Number appears. 1. Press <ENTER>.
The dialing mode specifies the type of phone line being used 1. Press <ENTER>.
by the DACT.
Pulse Freq
<ENTER> = Accept [1.9KHz Data]
Dialing Mode
2. Use the NEXT and PREV keys to move from one
1. Press <ENTER>. choice to another. Choices are
5-8
Technical Manuals Online! - http://www.tech-man.com
Chapter 5. Manually Programming NACs, Relays, and DACT
Report Format 4. Press the <NEXT> key. The prompt for the Test Report
[Contact ID] Time appears.
The DACT can report in any of the following communi- Test Report Time
cation formats. This option specifies the time at which the Test Report Event
• 3/1 pulse = Three-digit account code followed by is sent to the supervising station. Time is set in 24 hour, mil-
one-digit reporting code, double round at 20 pulses itary, format.
per second (PPS). Allows programmable reporting
codes. Refer to “Programming Event Codes” later <ENTER> = Accept
in this chapter. Opt: [Test Rpt Time]
• 4/2 pulse = Four-digit account code followed by 1. Press <ENTER>.
two-digit reporting code, double round at 20 PPS.
Allows programmable reporting codes. Refer to Test Rpt Time
“Programming Event Codes” later in this chapter. [02] : 00
• BFSK = Three-digit account code followed by
two-digit reporting code, single transmission of 2. Use the NEXT and PREV keys to increment or decre-
constant tones. Features built-in error checking and ment the hour setting (two digits on left). Use the right
fixed reporting codes. arrow key to move the cursor to the minutes (two digits
on right). Use the NEXT and PREV keys to increment
• SIA = Level 1 compatibility. Four-digit account
or decrement the minutes setting.
code features tonal acknowledge, basic reports, and
fixed reporting codes. 3. Press <ENTER> to accept the choice. A prompt appears
• Contact ID (Default). Uses a four digit account asking you to confirm the choice.
code, followed by a two- digit group number and 4. Press <ENTER>. The prompt shown above Step 1 reap-
three digit contact number. pears.
2. Use the NEXT and PREV keys to move from one 5. Press the <EXIT/CLEAR> key. The prompt for setting
choice to another. DACT options reappears. Press the <NEXT> key to
3. Press <ENTER> to accept the choice. A prompt appears access either the CID Points or Event Codes menus.
asking you to confirm the choice.
4. Press <ENTER>. The prompt shown above Step 1 reap- Programming Contact ID (CID)
pears. Points
5. Press the <NEXT> key. The prompt for the AC Fail Follow the procedure below only if the DACT is using the
Delay appears. Contact ID (CID) reporting format. CID reporting format
requires you to specify the group and Contact ID for each
5-9
Technical Manuals Online! - http://www.tech-man.com
Chapter 5. Manually Programming NACs, Relays, and DACT
point, but there is no need to specify the type of event with <ENTER>=Accept
the CID format. This information is automatically derived DACT: [Event Codes]
from the point’s function type.
2. Press <ENTER>. A prompt similar to the following
Note: Default CID point values are provided in the panel. appears.
Before changing these values, please contact an authorized
[FIRE ALARM]
representative at the supervising station. Refer to Table 3-4
Code: A1
for information on the default CID codes.
3. For each code, use the right arrow key to move between
1. Follow the steps in “Accessing DACT Menu,” earlier in
the letter/digit of the Code field. Use the <NEXT> and
this chapter. Use the <NEXT> or <PREV> keys to
<PREV> keys to increment or decrement the value of a
choose CID Points.
letter or digit. See Table 5-5 for a list of Event types and
<ENTER>=Accept their corresponding codes.
DACT: [CID Points] 4. To choose another code to edit or verify, press the right
2. Press <ENTER>. A prompt similar to the following arrow key until the cursor is on the top line of the
appears. prompt. Use the <NEXT> and <PREV> keys to scroll
to another code and then repeat Step 3.
[Garage IDC1]
GRP: 01 ID: 001 5. When all points have been configured, press the
<ENTER> key. A prompt similar to the following
This prompt consists of the following fields. appears, asking you to confirm the changes you made.
• Point Custom Label. The top line of the prompt dis-
plays the custom label assigned to the point. <ENTER>=Confirm
Code: A1
• Grp. A 2-digit number used to group associated
devices together. 6. Press <ENTER>. The prompt shown in Step 1 appears.
• ID (Contact ID). a 3-digit number used to identify a
Table 5-5 Event Categories and Codes
specific point/device.
3. For each point, use the right arrow key to move between Event 3/1 BFSK 4/2 SIA
the digits of the GRP and ID fields. Use the <NEXT>
Fire Alarm 1 11 A1 FA1
and <PREV> keys to increment or decrement the value
of a digit. Supervisory 3 33 A3 SS3
4. To choose another point, press the right arrow key until Trouble 4 F4 A4 FT4
the cursor is on the top line (custom label) of the
Fire Restoral E E1 71 FR1
prompt. Use the <NEXT> and <PREV> keys to scroll
to another point and then repeat Step 3. Supervisory E E3 73 SJ3
Restoral
5. When all points have been configured, press the
<ENTER> key. A prompt similar to the following Trouble Restoral E E4 74 FJ4
appears, asking you to confirm the changes you made.
Phone Line 1 F FB 31 LT1
Trouble
<ENTER>=Confirm
GRP: [01] ID:001 Phone Line 1 E EB 35 LR1
Restoral
6. Press <ENTER>. The prompt shown in Step 1 appears.
Phone Line 2 F FC 32 LT2
Trouble
Programming Event Codes
Phone Line 2 E EC 36 LR2
Follow the procedure below only if the DACT is using the Restoral
3/1 or 4/2 reporting format. AC Failure F FA 6A AT0
1. Follow the steps in “Accessing DACT Menu,” earlier in AC Restoral E EA 7A AR0
this chapter. Use the <NEXT> or <PREV> keys to
choose Event Codes. Auto Test Report E EE 3A RP0
5-10
Technical Manuals Online! - http://www.tech-man.com
Chapter 5. Manually Programming NACs, Relays, and DACT
Off-normal at F F8 33 YX0
test
Saving Changes
When DACT programming is complete, press the EXIT/
CLEAR key until the following prompt is shown.
Use the right arrow key to move the cursor to one of the fol-
lowing options and press <ENTER>.
5-11
Technical Manuals Online! - http://www.tech-man.com
Technical Manuals Online! - http://www.tech-man.com
Chapter 6. Manually Programming
Annunciators
6-1
Technical Manuals Online! - http://www.tech-man.com
Chapter 6. Manually Programming Annunciators
Adding an Annunciator 4. Press <ENTER>. Use the <NEXT> and <PREV> keys
to scroll through the choices until “Add” is displayed.
Automatically Adding Annunciator Cards
<ENTER>=Accept
Use the Automatic Programming option to automatically Annuns: [Add]
add annunciator modules to the job. (This option will also
detect and add an Expansion Power Supply and City Card, if 5. Press <ENTER>. A prompt appears, asking you to iden-
installed.) tify the specific type of annunciator.
1. Press the <MENU> key. Press <NEXT> or <PREV> <ENTER>=Accept
until the [Automatic Programming] option is displayed. Add: [LCD]
Press <ENTER>. The following displays:
6. Use the <NEXT> and <PREV> keys to select one of the
FIRE ALARM
following:
SUSPENDED
• Zone Ann
<ENTER> to Program • Remote LED/SW
<EXIT> to resume • LCD. Option not applicable to this panel.
2. Press <ENTER>. The following prompt appears. 7. Press <ENTER>. A prompt appears, asking you to set
the card address for the annunciator. The address you
<ENTER>=Accept specify must match the address set via dip switch on the
AP: [Reconfig All] annunciator. The address must be in the range of 4
through 7.
3. Use the <NEXT> key to select [Detect New]. The fol-
lowing prompt appears. 8. Use the <NEXT> and <PREV> keys to select the
appropriate address and press ENTER.
<ENTER> to Continue
9. A prompt appears asking you to confirm the addition of
*May CHANGE Setting*
the annunciator. Pressing <ENTER> will accept any
4. Press <ENTER> to detect and add annunciators to the changes made and exit. Use the <EXIT/CLEAR> key to
job. quit without saving.
<ENTER>=Accept <ENTER>=Accept
Prg:[Points] Prg:[Points]
3. Use the <NEXT> and <PREV> keys to scroll through 3. Press <ENTER>. A prompt appears, allowing you to
the choices until “Annuns” is displayed. select the type of point to manually edit. By default,
[IDC] is the first choice.
<ENTER>=Accept
Prg: [Annuns]
6-2
Technical Manuals Online! - http://www.tech-man.com
Chapter 6. Manually Programming Annunciators
<ENTER>=Accept
Prg:[IDC
CONTROL
Lamp Power
Default Programming
The LEDs on the Local Zone LED and Remote LED/Switch
annunciators have the pre-defined operations listed in Table
6-1 and Table 6-2.
6-3
Technical Manuals Online! - http://www.tech-man.com
Chapter 6. Manually Programming Annunciators
6-4
Technical Manuals Online! - http://www.tech-man.com
Chapter 6. Manually Programming Annunciators
5. Use the <NEXT> and <PREV> keys to scroll through Output activates when any point is in a
LT
the available modes. As you scroll through the modes, trouble condition.
the default reference address for the mode appears to the
right of the mode. Refer to Table 6-3 for a list of the
available modes. Table 6-4 Common LED Reference Points
6. When the appropriate mode is selected, use the right
Reference
arrow key to move the cursor brackets over to the refer- Description
Point
ence point. Press the <FUNCTION> key. This changes
the numerical designation of the reference point to a Separate reference point for each
text-based description. Refer to Table 6-4 for a list of IDNet initiating device. State moni-
common reference points. For example: IDNet 1-200
tored determined by selected LED
mode.
Type: BZONE Fire
IDC10 Aux Relays 1 Separate reference point for each
and 2 relay. State monitored determined
7. Use the <NEXT> and <PREV> keys to scroll through by selected LED mode.
the list of available reference points.
City/DACT Separate reference point (18-14) for dis-
8. Press <ENTER> when the appropriate reference point is Disconnect
displayed. The prompt shown in Step 4 reappears. connect and trouble. Typical use is to
City Trouble monitor the ON state of either point.
9. Press <ENTER>. A prompt appears, asking you to con-
firm the changes. Control
Bypass
10. Press <ENTER> to confirm the changes. Separate reference point for each type
Elevator of bypass.Typical use is to monitor the
Table 6-3 LED Modes Bypass ON state of any of the points.
6-5
Technical Manuals Online! - http://www.tech-man.com
Chapter 6. Manually Programming Annunciators
Programming Panel and LCD LEDs Alarm Signal Red with unique identifier
Signal Circuit Fault Yellow
This section describes programming the built-in LEDs on
Inhibit Yellow
the front panel and on the LCD annunciator. Programming
Supervisory Inputs Yellow with unique identi-
involves setting the reference point, mode (the point and
fier
point state that triggers the LED to illuminate), and the color
Power - ON Green
of the LED.
Trouble Signal Yellow
Setting LED Color Alarm Signal Silence Yellow
6-6
Technical Manuals Online! - http://www.tech-man.com
Chapter 6. Manually Programming Annunciators
6-7
Technical Manuals Online! - http://www.tech-man.com
Chapter 6. Manually Programming Annunciators
1. Press the <MENU> key. Press <NEXT> or <PREV> Choosing Event Groups to Annunciate
until the [Programming] option is displayed. Press After selecting <NEXT>, as described in Step 6 of the previ-
<ENTER>. The following displays: ous section, you are prompted to specify whether you want
to annunciate Fire events on the LCD.
FIRE ALARM
SUSPENDED <ENTER>=Accept
Send FIRE Events: [Yes]
<ENTER> to Program
<EXIT> to resume 1. Use the <NEXT> and <PREV> keys to toggle between
Yes and No. Press <ENTER> when the correct value
2. Press <ENTER>. The Programming menu appears.
appears. The next prompt asks whether you want to
[Points] is the default selection, which allows you to
annunciate Supervisory Events on the LCD.
make changes to a specific point’s programming.
<ENTER>=Accept
<ENTER>=Accept
Send SUPV Events: [Yes]
Prg:[Points]
2. Use the <NEXT> and <PREV> keys to toggle between
3. Press <ENTER>. A prompt appears, allowing you to
Yes and No. Press <ENTER> when the correct value
select the type of point to manually edit. By default,
appears. The next prompt asks whether you want to
[IDC] is the first choice.
annunciate Trouble Events on the LCD.
<ENTER>=Accept
<ENTER>=Accept
Prg:[Cards]
Send TBL Events: [Yes]
4. Press <ENTER>. The display prompts you for the type
3. Use the <NEXT> and <PREV> keys to toggle between
of operation you want to perform.
Yes and No. Press <ENTER> when the correct value
<ENTER>=Accept appears. The next prompt asks whether you want to
Cards:[Add] annunciate signal silence and system reset messages on
the LCD.
5. Use the <NEXT> and <PREV> keys to scroll through
the choices until Modify is shown. Press <ENTER>. <ENTER>=Accept
The display prompts you to specify the address of the Send Reset/Silence: [Yes]
card you want to modify.
4. Use the <NEXT> and <PREV> keys to toggle between
Card=[11] Yes and No. Press <ENTER> when the correct value
LCD appears. See “Setting Key-Switch Operation” below for
information on the next prompt that appears.
6. Use the <NEXT> and <PREV> keys to scroll to the
address of the LCD annunciator. Press <ENTER> when Setting Key-Switch Operation
the appropriate address is shown. A prompt similar to The key-switch operation selection allows you to select
the following appears. whether or not the LCD's key-switch is required to be
inserted and activated in order for the keypad's operation to
<ENTER>=ALL Events take effect. The first prompt appears as follows.
<NEXT> = Select Events
<ENTER> = Default Key
• Press <ENTER> to annunciate all events generated <NEXT> = Select Key
by the panel and attached devices to the LCD. The
next prompt asks you to specify the operation of the 1. Press <ENTER> to require the use of the key for all
key-switch. See “Setting Key-Switch Operation” LCD operations (system reset, ACK, signal silence).
below for information. Press <NEXT> to see the following prompt, which asks
• Press <NEXT> to select which groups of events are if you want to require the key to use the Fire Ack key.
forwarded to the annunciator. A series of prompts
<ENTER>=Accept
appears, telling you to press ENTER to send a
FIRE ACK: [Yes]
group of events to the annunciator. See “Choosing
Event Groups to Annunciate” below.
6-8
Technical Manuals Online! - http://www.tech-man.com
Chapter 6. Manually Programming Annunciators
<ENTER>=Accept
TROUBLE ACK: [Yes]
<ENTER>=Accept
SYSTEM RESET: [Yes]
<ENTER>=Accept
ALARM SILENCE: [Yes]
<ENTER>=Save
Use the right arrow key to move the cursor to one of the fol-
lowing options and press <ENTER>.
6-9
Technical Manuals Online! - http://www.tech-man.com
Technical Manuals Online! - http://www.tech-man.com
Chapter 7. Manually Programming System
Options
System options are pre-defined modes of operation with a range of set- In This Chapter
tings from which to choose. System Options define global operations
such as the time and date format, door drop timers, and whether the city
circuit is enabled, etc. System options can be set during either the auto- Accessing System Options Menu . . . . . . . . . .7-1
matic (Chapter 3) or manual programming process. Programming Options . . . . . . . . . . . . . . . . . . .7-1
FIRE ALARM
SUSPENDED
<ENTER> to Program
<EXIT> to resume
<ENTER>=Accept
Prg: [OPTIONS]
<ENTER>=Accept
Opt: [Time/Date]
Programming Options
Refer to the appropriate section in the table below for details on each
option. In each case, programming the option involves using the
<NEXT> and <PREV> keys to scroll through the choices and using the
<ENTER> key to set the option to the value you choose.
7-1
Technical Manuals Online! - http://www.tech-man.com
Chapter 7. Manually Programming System Options
Option Settings
Option Settings
The Door Holder Drop on AC Failure allows
Choose 12 (am/pm) or 24-hour (military) for- the 4008 to hold doors open for a set duration
Time/Date during an AC power loss condition. After that
mat. Use <NEXT> and <PREV> to scroll
Format timer has expired, the 4008 turns off the door
between options and <ENTER> to set.
holder relays (all DHOLDER point types). The
The Active Status Reminder option allows AC Doors range for the timer is 0-60 minutes with a
you to set an interval and duration during default setting of 5 minutes. To have the door
which the panel reminds operators that a holders drop the doors immediately upon AC
FIRE, SUPV, or TBL condition still exists. This power loss, set the timer to 0. This option
is accomplished by sounding the front panel applies to all DHOLDER relay function types
tone-alert. regardless of their Alarm Group setting.
• Choose: ON or OFF (default = OFF).
• Set reminder interval This option selects the operation of the 4008 if
Reminder (1-12 hours) an alarm occurs during an AC power loss
• Signal duration. This option sets the while a depleted battery trouble exists. If this
duration of the acknowledge signal. (0- option is selected, the system does the fol-
60 seconds; 0=on until ack; default=5) lowing:
• WILL NOT initiate an alarm if the first
The default for this option is 0, meaning alarm occurs after the depleted battery
an acknowledge is required to silence Depleted Bat- state has been detected. If the hardware
the reminder. tery Cutout jumper for depleted battery cutout has
been clipped, the system will shut down
60 seconds after the depleted battery
While the timer is counting down, the Alarm condition is detected
Silence/Reset Inhibit Timer prevents a sys- • WILL continue sounding the alarm if the
tem operator from using either the Alarm depleted battery state is reached after
Silence or System Reset functions. When the the system is already in the alarm state.
Inhibit inhibit timer expires, the 4008 may be reset/
silenced.
Display 1st When this option is selected, the 4008 will
Choose a timer range from 0-60 minutes Alarm automatically display the first (oldest) alarm
(default=0 - no inhibit) instead of the Alarm Tally abnormal screen.
This allows the first responder to determine
The Alarm Signal Cutout timer allows you to the location of the first alarm in the system
set a duration for how long notification appli- without having to open the door and press the
ances sound after an alarm. In other words, acknowledge key.
when an alarm condition exists, the signals
sound until silenced. With this option set at If an unacknowledged alarm exists, the sys-
Alarm Cutout two minutes, building signals sound on alarm tem displays that alarm. When that alarm is
for two minutes and then stop sounding. acknowledged, the system shall revert to dis-
However, the alarm condition remains active. playing the oldest alarm.
Choose a timer range from 0-60 minutes If no fire alarms exist in the system, the first
(default=0 - no cutout) supervisory event is shown on the display. If
no supervisories exist, the first trouble is
Allows the 4008 to hold doors open for a set shown on the display. If there are no fire
duration during an alarm condition. After that alarms, supervisories, or troubles, the SYS-
duration has expired, the 4008 shuts off the TEM NORMAL screen is displayed.
door holder relays (all DHOLDER point
Alarm Doors types). Choose a timer range from 0-60 min- Enable City Cir- This option activates the 4008 Circuit Module.
utes (default=0 - immediate door drop). This cuit If a city circuit is used in the system this
option applies to all DHOLDER relay function option must be selected or a trouble will be
types, regardless of their Alarm Group set- reported. If this option is selected and the city
ting. module is not connected, the trouble will also
report. There is no other programming
required for the city module. The city type is
configured with jumpers on the city circuit
board.
7-2
Technical Manuals Online! - http://www.tech-man.com
Chapter 7. Manually Programming System Options
Option Settings
7-3
Technical Manuals Online! - http://www.tech-man.com
Technical Manuals Online! - http://www.tech-man.com
Chapter 8. Operating
LAMP Test
Lamp Test is accomplished during normal monitoring (Access Level 1)
by pressing the Function key, then pressing ENTER. All LEDs energize
and all LED segments are written to.
Abnormal Conditions
Abnormal conditions are indicated on the 4008 by flashing the alarm,
supervisory, or trouble LED and sounding the tone-alert. The tone-alert
pulses for an alarm condition, and is on steady for a trouble or supervi-
sory. If the "Display First Alarm" option is selected, the display pro-
vides information about the first, highest-priority alarm in the system
without operator intervention. If "Display First Alarm" is not selected, a
screen showing the overall system status is shown:
02 | 00 | 00
CORE 1 MEZZANINE
FIRE 1/2
8-1
Technical Manuals Online! - http://www.tech-man.com
Chapter 8. Operating
Historical Logs
The 4008 is a Global Acknowledge system meaning that one
press of an Acknowledge key acknowledges every abnormal The 4008 has three separate, non-volatile historical logs:
point in the system within that category. Pressing the Ack Alarm, Supervisory, and Trouble. These logs can be viewed
key allows the operator to scroll through all the abnormal separately, or they can be viewed in chronological order as a
points in that category. The additional information listed single combined log. Each log records information about the
below can be obtained by pressing the <ENTER> key. event and the time the event occurred. The following table
describes the different logs and their stored events.
• The electrical state of the point (open, short circuit, nor-
Table 8-1 Log Events
mal, abnormal)
• Enable/Disable state of the point Historical
Stored Events
• Manual override state (if output) Log
• Assigned Alarm Groups
Alarms
ALOG Alarm Acknowledge
Silencing Alarms Alarm Log Log Cleared
100 Entries Alarm Silence
The "Alarm Silence" key allows the operator to silence System Reset
active Notification Appliance Circuits that are programmed
for "on-til-silence" operation. SLOG Supervisory Conditions
Supervisory Supervisory Acknowledge
Log Log Cleared
Caution: Pressing the Alarm Silence key causes fire alarm
100 Entries
evacuation signals to turn OFF. Follow local procedures to
silence alarm evacuation signals. Trouble Events
TLOG
Login/Logout for Level 2 or higher
Trouble Log
To silence an alarm, press the <ALARM SILENCE> key. Log Cleared
300 Entries
WALKTEST Events
• All "on-til-silence" notification appliance circuits will
turn OFF CLOG All Events in Chronological Order
• The Alarm Silenced indicator LED will turn on Combined Log
8-2
Technical Manuals Online! - http://www.tech-man.com
Chapter 8. Operating
higher. To clear the log you are currently viewing, press 7. Press <ENTER> when the point whose status you want
<ENTER> while viewing any log entry. The following to view is displayed. The Hardware Type and Function
screen will be displayed: Type for the point are shown. For example:
Press <ENTER> to clear the current log. An entry is added 8. Additional information and control options are available
to the log to indicate that it was cleared. as described in the following table.
IDNet1
Viewing Point Information
PHOTO SMOKE
1. Press <MENU>.
a. Press the <NEXT> key to view the
2. Press <NEXT> and <PREV> until the following following information for the device.
IDNet
prompt appears.
• Enable/Disable status
<ENTER>=Accept • Alarm Verification Tally
Menu: [Control/View] • Electrical state (normal, short, open,
abnormal)
3. Press <ENTER>. A prompt similar to the following
appears. • CID Group and ID
• Assigned Alarm Groups
<ENTER>=Accept
Ctrl/View: [IDNet]
a. Press <ENTER> to view the point’s
4. Use the <NEXT> or <PREV> key to select one of the hardware type and assigned function
following. type. For example:
NAC1
- IDNet
NAC
- Relay
- NAC a. Press the <NEXT> key to view the
- Input (Not Applicable) following information for the IDC.
Relay or
- Output (LED) NAC
• Electrical State (open/short/normal)
- System Point - these are logical system points used • Enable/Disable status
for on/off control of system functions. Control of • Output state (on/off/coding)
these points is not allowed. • Automatic/Manual control status. See
5. Press <ENTER> when the appropriate point category “Manually Controlling a NAC/Relay”
(i.e., Relay, NAC) is selected. A display similar to the below for additional information.
following appears. • Function type and output method
• Assigned Alarm Groups
IDNet1
Input N/A
Fire NORMAL
8-3
Technical Manuals Online! - http://www.tech-man.com
Chapter 8. Operating
Table 8-2 Additional Point Information (Continued) 2. Press <NEXT> until Control/View is shown.
Output a. Press <ENTER> to view a descrip- 3. Press <ENTER>. Use the <NEXT> or <PREV> key to
(LED) select IDC, NAC, or Relay.
tion of the first system point in the
list. Press NEXT to scroll through the 4. Press <ENTER>. Use the <NEXT> or <PREV> key to
list of points. scroll through the list of points.
5. Press <DISABLE/ENABLE> when the point you want
System to turn enable/disable is displayed. A prompt similar to
a. Press <ENTER> to view a descrip-
Point the following appears.
tion of the first system point in the
list. Press NEXT to scroll through the
IDNet1
list of points.
FN: [Enable]
8-4
Technical Manuals Online! - http://www.tech-man.com
Chapter 8. Operating
Table 8-3 Control Functions (Continued) a. Connect a 733-794 download cable between the
Service Port on the panel and a serial communica-
Function Description tion port on the PC.
a. Create a connection profile for the serial port. Set
Control Point Bypasses the following control points the serial communication parameters to 9600 baud,
Bypass (causes a trouble): 8 bits, no parity, 1 stop bit, and no flow control.
• On-til-Silence NACs a. Configure the application to capture the informa-
• On-til-Reset NACs/relays tion coming in on the serial port. (Choose Capture
Text in the Hyperterminal Transfer menu.)
Elevator Bypasses Elevator Recall operation
Bypass (causes a trouble)
To generate a report, do the following.
Doorholder Bypasses the door holder operation
Bypass (causes a trouble) 1. Press <MENU>.
2. Press <NEXT> and <PREV> until the following
Lamp Test Illuminates all LEDs and LCD segments
on the operator interface. prompt appears.
Setting the Time and Date 4. Use the <NEXT> or <PREV> key to select one of the
options described in Table 8-4.
Selecting the "Set Time/Date" option from the main menu
allows you to change the system time and date. This opera- Table 8-4 Reports
tion is protected at Access Level 2.
Report Description
<ENTER>=Accept ALOG Displays contents of alarm log.
Reports
5. Press <ENTER>. The panel displays a message noting
Reports, which are either text-based archives of system that the report has been sent to the printer.
activity or a text-based description of the panel configura-
tion, can be archived and printed in the following manner. Diagnostics
• The panel supports an unsupervised, 80-column serial
printer that can be used to record events, or to print his- Use the following procedure to run the panel’s diagnostic
tory log reports. options.
8-5
Technical Manuals Online! - http://www.tech-man.com
Chapter 8. Operating
8-6
Technical Manuals Online! - http://www.tech-man.com
Chapter 8. Operating
1. Press the <MENU> key. Press <NEXT> or <PREV> Restarting the CPU
until the [Walktest] option is displayed. Press This option is used to clear an Access Level 4 Trouble (i.e., a
<ENTER>. The following displays: “Service Mode Trouble”).
<ENTER>=Accept 1. Press <MENU>.
[Off] Lg Sil NoPr
2. Press <NEXT> and <PREV> and choose one of the fol-
2. For each option, use the <NEXT> and <PREV> keys to lowing options.
scroll through the option’s choices. Use the right and • Warm. Clears the Access Level 4 trouble, restarts
left arrow keys to move from one option to another. the panel, but preserves the panel’s non-volatile
Available options include memory, including time/date information, historical
• ON/OFF. Used to enable and disable WalkTest. logs, and all currently disabled points
When set to ON, a WalkTest Enabled trouble is dis- • Cold. Clears the Access Level 4 trouble and re-ini-
played on the panel. tializes the panel’s non-volatile memory, clearing
• LG/NL. Controls whether alarms and troubles gen- all time/date information, historical logs, and dis-
erated by WalkTest are sent to the alarm or trouble abled points.
log. Lg enables logging; NL disables logging. 3. Choose an option and press <ENTER>. System startup
• SIG/SIL. Controls whether the NACs are used to prompts appear on the screen, followed by the system
signal activation of an alarm or trouble condition. status message.
SIG enables NACs for Walktest; SIL disables
NACs for WalkTest. Viewing Software Revision Number and Job Info
• PR/NoPR. Enables (PR) or disables (NoPR) 1. Press <MENU>.
whether WalkTest alarms and troubles are sent to
2. Press <NEXT> or <PREV> until Software Rev is
the locally attached printer.
shown. Press <ENTER>. A message similar to the fol-
3. When the options are set, press the <ENTER> key. The lowing appears, displaying the revision level of the
system prompts you to confirm the settings. Press panel’s software.
<ENTER> again to confirm.
Rev 1.00.11
Advanced Operations <NEXT> = View Job Info
Upload/Download 3. Press <NEXT> to see the job revision number (i.e., the
Uploading and downloading files allows you to transfer the number of times the job has been edited and saved), and
panel’s job file between a service PC and the panel. The term the date on which the panel was edited.
Uploading refers to transferring a job file from the panel to a
PC; whereas, the term Downloading refers to moving a job JOB REV:1
file from the PC to the panel. 12:00:00 am 04/09/04
<ENTER>=Accept
XFER: [Start XFER]
8-7
Technical Manuals Online! - http://www.tech-man.com
Technical Manuals Online! - http://www.tech-man.com
Appendix A. Battery Standby Calculations
Note: Auxiliary power from the system’s AUX 24 V taps must also be included in the calculation, unless that power is
switched off during battery standby. For example, door holders operated from 24 V need not be included if they are discon-
nected via a relay during a battery standby condition. Notification Appliance load must be included in the alarm current total.
2. From previous calculations, locate total Alarm Current (B) in amperes. B = ______
6. Select a battery size LARGER than the number from the Initial Battery Calculation from the following list of batteries
using the 20 Hour Rating value:
A-1
Technical Manuals Online! - http://www.tech-man.com
20 Hour Rating C/20 (Amps) 20 Hour Rating C/20 (Amps)
7. If either the Standby Current or the Alarm Current is greater than the C/20 current for the initial battery size selected, a
Discharge Factor (DF) must be applied. For example, 1 A load on a 10 Ah battery requires a Discharge Factor of 1.08 (10
Ah / 1 A gives discharge time of 10 hours; DF = 1.08). Use the following table to determine Discharge Factor (use the 20
hr value for 24 hr standby):
8. Standby Discharge Factor (SDF) = _________ Alarm Discharge Factor (ADF) = _________
9. Minimum Required Battery Capacity Calculation. (to account for battery aging, a 1.17 multiplier is included)
10. If the battery size initially selected is smaller than the result of step 9 above, repeat the calculations using a larger battery
size.
A-2
Technical Manuals Online! - http://www.tech-man.com
Appendix B. Contact ID Default Values
24hr Test Report, Off Normal GRP:01 ID:235 Test 602, 608
*Any other trouble not specifically mentioned would have a code of 330.
For example, a trouble on an output device would report an event code of 330.
B-1
Technical Manuals Online! - http://www.tech-man.com
Table B-1: Contact ID Default Values (Continued)
*Any other trouble not specifically mentioned would have a code of 330.
For example, a trouble on an output device would report an event code of 330.
B-2
Technical Manuals Online! - http://www.tech-man.com
Technical Manuals Online! - http://www.tech-man.com
Technical Manuals Online! - http://www.tech-man.com