Professional Documents
Culture Documents
Rev. W
Copyright and Trademarks
© 2004-2016 Tyco Fire Protection Products. All rights reserved.
Specifications and other information shown were current as of publication and are subject to change without notice.
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is
strictly prohibited.
No part of this document may be reproduced or transmitted in any form or by any means, electronic or mechanical, for
any purpose, without the express written consent of Tyco Fire Protection Products.
FCC Information
This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the door of this
equipment is a label that contains, among other information, the following product identifier: US:5QWAL01B4008. If
requested, the number must be provided to the telephone company.
In the event of equipment malfunction, all repairs should be performed by an authorized agent. It is the responsibility of
users requiring service to report the need for service to our company or to one of our authorized agents.
The Ringer Equivalence Number (REN), which is 01 for the DACT installed in this panel, is used to determine the
number of devices that may be connected to a telephone line. Excessive RENs on a telephone line may result in the
devices not ringing in response to an incoming call. In most, but not all areas, the sum of RENs should not exceed five
(5.0). To be certain of the number of devices that may be connected to a line, as determined by the total number of
RENs, contact the local telephone company. For products approved after July 23, 2001, the REN is part of the product
identifier, which uses the format US:AAAEQ##TXXXX. The digits represented by ## are the REN without a decimal
point (e.g. 01 is a REN of 0.1).
If the DACT causes harm to the telephone network, the telephone company will notify you in advance that temporary
discontinuance of service may be required. But if advance notice isn’t practical, the telephone company will notify you
as soon as possible. If your service is discontinued, you will be advised of your right to file a complaint with the FCC.
The telephone company may make changes to its facilities, equipment, operations, or procedures that could affect the
operation of the equipment. If this happens the telephone company will provide advance notice in order for you to make
the necessary modifications to maintain uninterrupted service.
If trouble is experienced with the DACT, please contact Tyco Safety Products at the location identified above. If the
equipment is causing harm to the telephone network, the telephone company may request that you disconnect the
equipment until the problem is resolved.
DACT Computer
Network
Service Unused
Provider's RJ-11 Jack
Facilities
Telephone
Line
Telephone
Network
Demarcation Unused
Point Telephone
Fax RJ-11 Jack
Answering
System
Telephone
Connectors for the DACT are terminal blocks on the DACT module. Refer to DACT Wiring in Chapter 2 of this
manual for specific DACT wiring instructions.
Cautions and Warnings
READ AND SAVE THESE INSTRUCTIONS. Follow the instructions in this installation manual. These
instructions must be followed to avoid damage to this product and associated equipment. Product operation
and reliability depends upon proper installation.
DO NOT INSTALL ANY SIMPLEX® PRODUCT THAT APPEARS DAMAGED. Upon unpacking
your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent,
immediately file a claim with the carrier and notify an authorized Simplex product supplier.
ELECTRICAL HAZARD - Disconnect electrical field power when making any internal adjustments or
repairs. All repairs should be performed by a representative or authorized agent of your local Simplex
product supplier.
FCC RULES AND REGULATIONS - Part 15 - This equipment has been tested and found to comply
with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed
to provide reasonable protection against harmful interference when the equipment is operated in a com-
mercial environment. This equipment generates, uses, and can radiate radio frequency energy and if not
installed and used in accordance with the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is likely to cause harmful interference
in which case the user will be required to correct the interference at his own expense.
All components, circuits, system operations, or software functions known to be affected by a change must
be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of
initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be
tested and proper system operation verified.
Table of Contents
Overview ......................................................................................................................1-1
Optional Modules ............................................................................................................................... 1-2
Initiating Devices ................................................................................................................................ 1-3
Programming Overview...................................................................................................................... 1-4
User Interface..................................................................................................................................... 1-5
Logging In and Out............................................................................................................................. 1-6
Programming a Job ............................................................................................................................ 1-7
Installation/System Checkout....................................................................................2-1
Back Box Mounting ............................................................................................................................ 2-1
General Wiring Guidelines ................................................................................................................. 2-2
Safety Ground/Ferrite Bead ............................................................................................................... 2-2
IDNet Wiring ....................................................................................................................................... 2-3
Multiple Notification Zones on a Single Circuit ................................................................................... 2-3
Class A/Class B NAC Wiring.............................................................................................................. 2-5
Remote Annunciator Comm Wiring.................................................................................................... 2-8
DACT Wiring over Telephone Lines................................................................................................... 2-9
DACT Wiring Using Ethernet Line (UL and ULC) ............................................................................ 2-12
Bosch C900V2 DACT using the Ethernet Line (UL only) ................................................................. 2-13
Auxiliary 24V Power Wiring .............................................................................................................. 2-14
City Connect Module Wiring............................................................................................................. 2-14
Auxiliary Relay Wiring ...................................................................................................................... 2-15
AC Supply Wiring ............................................................................................................................. 2-16
Battery Wiring................................................................................................................................... 2-17
Depleted Battery Cutout ................................................................................................................... 2-18
System Power-Up and Checkout ..................................................................................................... 2-19
Replacing Lithium Battery ................................................................................................................ 2-19
Periodic Testing and Maintenance ................................................................................................... 2-20
Auto-Programming ..................................................................................................... 3-1
Configure All ...................................................................................................................................... 3-1
Detect New Hardware ........................................................................................................................ 3-2
Restore Factory Defaults ................................................................................................................... 3-2
Edit System Options .......................................................................................................................... 3-2
Restore Default System Options........................................................................................................ 3-3
Saving the Configuration.................................................................................................................... 3-3
Default Programming Assignments ................................................................................................... 3-3
Manually Programming
IDNet Points ................................................................................................................ 4-1
Accessing IDNet Programming Menus .............................................................................................. 4-2
Adding an IDNet Device..................................................................................................................... 4-2
Editing IDNet Device Attributes.......................................................................................................... 4-2
Deleting an IDNet Point ..................................................................................................................... 4-8
The 4008-9101 line of Fire Alarm Control Panels (FACP) are address- In This Chapter
able fire alarm control panels capable of monitoring and controlling up
to 200 initiating devices on an addressable communications circuit
(IDNet). The single-board system and cabinet provide a complete fire Optional Modules . . . . . . . . . . . . . . . . . . . . . . .1-2
alarm for most applications. Initiating Devices . . . . . . . . . . . . . . . . . . . . . . .1-3
Programming Overview . . . . . . . . . . . . . . . . . .1-4
User Interface. . . . . . . . . . . . . . . . . . . . . . . . . .1-5
The 4008 is available in 6 models, red or beige, with or without door-
Logging In and Out. . . . . . . . . . . . . . . . . . . . . .1-6
mounted annunciator. Two models are available in Canadian French. Programming a Job . . . . . . . . . . . . . . . . . . . . .1-7
• 4008-9101 Red
• 4008-9102 Beige
• 4008-9121 Red with door-mounted annunciator
• 4008-9122 Beige with door-mounted annunciator
• 4008-9123 Red with door-mounted annunciator, Canadian French
• 4008-9124 Beige with door-mounted annunciator, Canadian French
Throughout this document, the term 4008-9101 is intended to include
the beige version also (4008-9102). The term 4008-9121 refers to the
beige version as well (4008-9122).
The 4008 provides audible and visible indications during alarm, super-
visory, or trouble conditions. Should any of these conditions occur, the
system activates the applicable notification appliances, LEDs, and the
panel’s tone-alert. The indications continue until an operator acknowl-
edges the condition.
The 4008 base system includes the Main System Board (MSB) mounted
in a steel enclosure with locking door. The MSB consists of:
• System power supply (24V filtered @ 3A)
• IDNet loop
• Two, 2A Notification Appliance Circuits (Style Y or Z)
• Two Auxiliary Relay circuits
• One Auxiliary Power tap
• 2 x 20 backlit LCD, LEDs and keypad
• Expansion power supply / NAC connection
• Service port
• DACT
1-1
Chapter 1. Overview
• Zone LED Annunciator displays alarm & trouble status Center (local energy) receiving units. The card has two cir-
for each logical zone. cuits - circuit 1 reports alarm or alarm/trouble events
• City Connect Module. (Remote Station only) and circuit 2 can be configured to
report trouble events or supervisory events. In the event of a
• Remote LED annunciators are available. These modules
CPU failure, a city card configured for a trouble output
interface to the system via a serial communication link.
sends a trouble to the city circuit. The card is mounted to the
They mount in separate enclosures, up to 4000 feet from
MSB with standoffs and connects via a ribbon harness. The
the control panel.
4006-9805 and 4008-9806 city cards are identical except
Table 1-1 Specifications that the 4006-9805 provides disconnect switches for each
circuit. Model 4006-9805must be used for Canadian applica-
Specification tions.The City Circuit must be enabled via the panel’s Sys-
tem Options before use.
120 VAC, 60 Hz, 4A;
240 VAC, 50 Hz, 3A AUX RELAY MODULE (4008-9802)
24 VDC, 3A alarm power The auxiliary relay module includes three relays, one each
24 VDC, ½A auxiliary power for system alarm, supervisory and trouble conditions. LEDs
Power Supply Battery charger for up to 25 Ah batter- indicate active relay circuits. Normally Open or Normally
ies, recharge per UL 864 and for up to Closed contact operation is selected by shunt jumper place-
12.7 Ah per S527 (ULC). The 4008 ment. Contacts are rated for 2A, 30VDC, 0.35 power factor.
back box can accommodate up to 12.7
Either an auxiliary relay module or a City Circuit Card may
Ah batteries
be added to the system. Addressable relay modules are avail-
The 4008 operates normally with ambi- able, connecting to the system through IDNet.
ent temperatures from 32° F to 120° F
(0° C to 49° C), inclusive. ANNUNCIATOR MODULES
Environmental
The 4008 operates normally under non- The 4008 supports a variety of annunciator modules. A total
condensing humidity conditions up to of four annunciators may be added to the system, one of
93% relative humidity at 90° F (32° C). which can be located in the panel (door-mounted LED
annunciator).
Optional Modules • 4008-9121 Door-Mounted LED Annunciator. The
Local Zone LED Module provides 24 LEDs for visible
The following is a list of optional modules for the 4008. zone alarm and trouble indication. This module is stan-
Refer to the individual instructions that accompany each dard for ULC-S527 compliant systems (Canada).There
module for more information. Refer to the label inside the are 10 Red and 14 Yellow LEDs. This provides a red
door of the 4008 for the placement of optional modules. alarm and yellow trouble LED for up to 10 groups of
devices. This module also provides 4 Yellow LEDs, one
Note: One AUX relay module or city circuit card is allowed. for each of 4 NACs. The LEDs are programmable, and
can be used for other functions as appropriate per appli-
EXPANSION POWER SUPPLY (4008-9801) cation.
When additional notification appliance circuits are required,
an expansion power supply may be added. The expansion
power supply provides two additional 2A NACs, and fil-
tered/regulated 24 VDC, 3A power. The expansion power
supply is mounted to the right of the MSB at the bottom of
the chassis. It connects to the MSB with a ribbon harness.
1-2
Chapter 1. Overview
• Remote LED/Switch Module (4610-9111). This • 4009-9807 NAC Option Card -- adds four conventional
module provides the following: Notification Appliance Circuits.
- 10 programmable red LEDs
- 6 programmable yellow LEDs Initiating Devices
Green “power on” LED
The 4008 is compatible with the following addressable initi-
- Yellow “Alarm Silenced” LED ating devices. Up to 200 devices (any combination) are
- Yellow “Trouble” LED allowed in the system.
- Yellow “Comm Loss” LED
DETECTOR MODULES
- Tone-Alert
• Photoelectric Detector (4098-9714, 4098-9714C)
- Switches for ACK, Alarm Silence, System Reset,
is an addressable photoelectric smoke detector that pro-
and Lamp Test
vides smoke detection by means of optical sense tech-
- Key switch to enable switch functions nology. The detector sends a unique identifier to the
control panel so that it may be easily auto-programmed
and verified during normal operation. The sensitivity of
the detector is 2.5%/ft. obscuration.
• Heat Detector (4098-9733, 4098-9733C) is an
addressable heat detector. It has a fixed sensitivity of
135°F, and may also be programmed for 15°F/minute
rate-of-rise operation. The detector sends a unique iden-
tifier to the control panel so that it may be easily auto-
programmed and verified during normal operation.
Figure 1-2 Remote LED/Switch Annunciator
• Combination Photo/Heat Detector (4098-9754,
Module
4098-9754C) is a combination photoelectric detector
and thermal detector in one head. It has the same char-
• LCD Annunciator. The 4606-9101 Remote LCD
acteristics as the photo and heat detectors described
Annunciator provides remote annunciation of the Fire
above. This device consumes two addresses - one for
Alarm Control Panel (FACP) status. Visual status is pro-
the photo and one for the heat. The detector sends
vided by a liquid crystal display and LEDs. Audible
unique identifiers to the control panel so that it may be
annunciation is provided through a piezo sounder.
easily auto-programmed and verified during normal
Access to the functions of the annunciator can be lim-
operation.
ited through the use of the annunciator’s keyswitch.
• Duct Detectors. The panel is compatible with any of
For Canadian applications, the LCD annunciator is only the following duct detectors:
suitable for supplementary applications.
- Two-wire detector without relay (4098-9755)Two-
4009-9201 and 4009-9202CA (Canadian)NAC wire detector without relay, Canadian (4098-9755C
Extender - Four-wire detector with relay (4098-9756)Four-
wire detector with relay, Canadian (4098-9756C
The 4009-9201/4009-9202CANotification Appliance Cir-
cuit (NAC) Extender is a self-contained adjunct panel. • Detector Bases. The detectors described above may
be installed in the following detector bases:
The base version of the NAC Extender is a single-board sys- - Detector Base w/o Remote Led Connection (4098-
tem consisting of four NACs, a power supply and charger, 9792)Detector Base w/o Remote Led Connection,
and two conventional NAC inputs that connect to the host Canadian, (4098-9792C)
panel for hardwired control of the NAC extender. - Detector Base w/Remote Led Connection (4098-
9789)Detector Base w/Remote Led Connection,
Option cards are available to provide the following addi- Canadian (4098-9789C)
tional capabilities:
- Detector Base w/Relay Drive (4098-9791)Detector
• 4009-9808 Class A Adapter Option Card -- allows fault Base w/Relay Drive, Canadian (4098-9791C)
tolerance in the case of open circuit wiring faults on the - Isolator Base (4098-9793)Isolator Base, Canadian
NACs. (4098-9793C)
1-3
Chapter 1. Overview
- Sounder Base (4098-9794)Sounder Base, Canadian - DACT information (phone numbers and account
(4098-9794C) information) must be manually programmed.
- Multi Detector Sounder Base (4098-9795)Multi It is recommended that you use the automatic program-
Detector Sounder Base, Canadian (4098-9795C) ming option to perform the following tasks.
- Multi Detector Base w/LED (4098-9796)Multi - Initial programming. After all option cards are
Detector Base w/LED, Canadian (4098-9796C) installed and all devices are addressed and wired,
use the auto programming feature to add the cards
MONITOR MODULES and devices to the job. After automatic program-
• The 4090-9001 Supervised Monitor is a contact closure ming the panel will function as a general alarm
monitor capable of quad sensing (normal, open, short, panel, assuming all devices are wired correctly. At
and current-limited conditions). It is a line-powered that point, you can use manual programming to edit
device and consumes one address. labels, device functions, and alarm groups if neces-
• The 4090-9101 (Class B) and 4090-9106(Class A) sary.
Addressable Modules are input devices capable of quad - Adding new cards or points to a previously pro-
sensing (normal, open, short, and current -limited condi- grammed job.
tions). This device requires separate 24 V power and
consumes one loop address. See 579-832 revision G for • Manual Programming. This programming option
2-Wire Detector Compatibility Chart. allows you to individually change the attributes of each
• The 4099-9001 (single action) and 4099-9002/4099- point, including:
9003 (dual action) addressable pull stations are latching - Function Type. Determines the way in which the
pull stations that can be reset with a key. They are a line- point operates (i.e., fire point, trouble point, on til
powered device, consuming one address. silence, etc.).
- Custom Label. Automatic programming assigns a
CONTROL MODULES
generic label -- such as P1, NAC1, or AUX1 -- to
• 4090-9002 Relay Module is line-powered and contains each point. Manual programming allows you to
a Form-C relay that can be used to control auxiliary assign a 20-character, site-specific label to each
functions (such as elevator recall). point.
• 4090-9116 Isolator Module allows the addressable - Alarm Group. Allows inputs and outputs to be
device loop to continue to function under certain fault associated into groups to implement selective sig-
conditions. naling applications.
• 4090-9007 Signal Zone Module provides addressable - DACT information (phone numbers and account
NAC control to allow notification to be directed where information) must be manually programmed.
desired.
System Options
Programming Overview System options are pre-defined modes of operation with a
range of settings from which to choose. System Options
A job refers to the file containing all of the panel’s program- define global operations such as the time and date format,
ming information. A job (also called a CFIG file) can be pro- door drop timers, and whether the city circuit is enabled, etc.
grammed in one of two ways. System options can be set during either the automatic or
• Automatic Programming (Chapter 3). The panel’s manual programming process.
auto-program option provides the ability to quickly and
automatically program the panel’s components and fea- Alarm Groups
tures. This option does the following: Alarm groups allow you to implement basic selective signal-
- Scans the panel’s serial communication channel, ling applications. As you program input (smoke detectors,
adding any annunciators. monitor zones) and output points (NAC, signal zone, relay),
- Scans the IDNet channel, adding and configuring you are given the opportunity to associate the point with an
IDNet devices. alarm group number. The number can range from 1-99 and
each point can be in up to three alarm groups. When pro-
- Adds any installed option cards, such as an AUX gramming is complete, an initiating device can only trigger
relay module or city circuit card. the output devices (relays, NACs) that share its alarm
- Performs a duplicate address search, terminating group(s).
the operation if a duplicate address is found.
1-4
Chapter 1. Overview
Figure 1-3 User Interface The Menu key always brings you to the
MENU top of the main menu structure unless
you are in the Programming menu.
Table 1-2 Operator Keys The Function Menu is displayed when
the <Function> key is pressed at the
Key Function high-level status screen. Use the <Previ-
FUNCTION ous> and <Next> keys to scroll through
Acknowledges any unacknowledged fire the list of functions. The function key
ALARM alarms in the system, and scrolls provides access to commonly used con-
ACK through the alarms in the active Alarm trol and display functions.
List.
1-5
Chapter 1. Overview
The <Exit/Clear> key is used to back out All Level 1 operations, plus:
of menus or displays and return to the Set Time/Date, Point Control,
top-level menu structure. Where possi- 2 Enable/Disable points,
EXIT/ ble, the <Exit/Clear> key backs out one Passcode = Earth Fault Latch, Manual Evac, Drill,
CLEAR level at a time. There are cases, how- 2000 City Disconnect, Control Point Bypass,
ever, that the Exit/Clear key will return Elevator Bypass, Door Holder Bypass,
the operator directly to the top-level User Key 1 & 2, Clear Historical Logs
menu.
All Level 1 & 2 operations, plus:
3
The <Enter> key is used to confirm Clear Verification Tallies
Passcode =
selections. In a programming screen, Custom Label editing
3000
pressing <Enter> indicates that the infor- WALKTEST, Run Diagnostics, Reports
mation on the display is correct and can
ENTER All Level 1, 2, & 3 operations, plus:
be accepted. The <Enter> key is used in 4
various other places within the menu Programming,
Passcode =
structure, always for this same type of Upload/Download, Cold Start,
4000
operation. Autoprogramming
Access: Level 1
<ENTER>=[Login]
1-6
Chapter 1. Overview
Access: Level 1 ming is complete, an initiating device can only trigger the
Passcode: [0] output devices (relays, NACs) that share its alarm group(s).
Programming a Job
A job refers to the file containing all of the panel’s program-
ming information. This manual describes the process
required to create a job from the front panel of the system.
Creating a job involves:
• Setting the attributes of each Device, NAC, and AUX
relay, including:
- Function Type. Determines the way in which the
Device, NAC, or relay operates (i.e., fire point,
trouble point, on til silence, etc.)
- Custom label. This is a 20-character label that
describes each device, NAC, or relay.
- Alarm Group. Allows inputs and outputs to be
associated into groups to implement selective sig-
naling applications. See “Alarm Groups” below.
• Defining the attributes (phone numbers, account num-
bers, reporting format, etc.) of the panel’s Digital Alarm
Communicator Transmitter (DACT). If the DACT will
not be used, programming consists of disabling the
DACT.
• Programming the operation of the LEDs contained on
the panel and connected annunciators. Programming an
annunciator consists of identifying the point being mon-
itored by the LED and the mode (i.e., fire alarm, trou-
ble, etc.) that will trigger the LED to illuminate.
• Setting values for the panel’s system options, which are
pre-defined modes of operation with a range of settings
from which to choose. System Options define global
operations such as the time and date format, door drop
timers, and whether the city circuit is enabled, etc.
Alarm Groups
Alarm groups allow you to implement basic selective signal-
ling applications. As you program input (N2 Devices) and
output points (N2 output devices, NAC or relay), you are
given the opportunity to associate the point with an alarm
group number. The number can range from 1-100 and each
point can be in up to three alarm groups. When program-
1-7
Chapter 2. Installation/System Checkout
Expansion
Power Supply
City Connect
Module DACT
AC Voltage Battery
Connection Connection
Battery Battery
2-1
Chapter 2. Installation/System Checkout
13.250
15.632
Semi-Flush Mounting
Semi-flush mounting involves recessing the cabinet into a
wall and attaching it directly to the wall's studs. At a mini-
mum, 1.5 inches of the cabinet must protrude from the wall
Figure 2-4 Safety Ground and Ferrite Bead
to allow for clearance of the panel door.
2-2
Chapter 2. Installation/System Checkout
Testing Procedure - 10, 000 feet total cable load (max.) allowed. Resis-
Before connecting circuit wiring to the 4008 system, includ- tance and capacitance limits must be observed.
ing option modules, wires must be tested as follows: • For Class A (Style 6 or Style 7) wiring, adhere to the
following:
1. Using a voltmeter to verify no stray voltages are applied
- Wire from B+/B- terminals to the first addressable
to the field wiring. Test for AC and DC voltages across
device. Wire to each device in succession for a
each pair of wires and from each wire to earth.
Class A loop. From last device, wiring is returned
2. Use an ohmeter to verify that all wiring tests free of to the A+/A- terminals.
grounds. Each conductor should test “open” against - Maximum wiring capacitance is .58uF total. Maxi-
earth (chassis is earth when safety ground is connected mum wiring resistance to any device is 52 ohms.
to grounding stud as shown in Figure 2-4).
- System ships with jumper wires from B+ to A+ and
from B- to A-. Remove jumper wires for Class A
IDNet Wiring wiring.
- T-tapping is not allowed for Class A wiring.
• All wiring is to be 18 AWG (min.) to 12 AWG (max.)
18 TP required, 18 TSP recommended if run together
with Notification Appliance Circuits. Multiple Notification Zones on a Sin-
• Conductors must test free of all grounds and stray volt- gle Circuit
ages before connection to appliances and panel.
If Notification Appliances on a given Class B circuit are to
• All wiring is supervised and power-limited.
be used for multiple Notification Zones for Partial Evacua-
• Refer to installation instructions packed with address- tion (Selective Signalling), then the NAC Riser must be
able detectors for information on wiring detectors to installed in accordance with Survivability From Attack by
IDNet channel. Fire Requirements in NFPA 2002 ED. Section 6.9.4, using
• IDNet voltage is 36.25V (max.) at 3333 bits/second. one or more of the following:
• For shielded wiring, connect shield to TB2-3. Jumper - a 2-hour rated cable assembly;
setting selects shield connection (Earth or 0V). Default - a 2-hour rated shaft or enclosure;
setting is 0V. - a 2-hour rated stairwell in building fully sprinklered in
accordance with NFPA 13.
• To achieve maximum wiring distance, use low capaci-
tance wire, 29 pF/Foot or lower. If shielded wire is used,
If the circuit(s) under consideration are in a Class A loop cir-
be sure to consider shield to conductor capacitance.
cuit configuration, then another option is available. Here,
• Style 7 operation requires use of addressable isolator isolators are used in place of the ‘armored cable’ methods
modules -- 4090-9116, 4098-9793, 4098-9793C. Refer described above, with isolators bounding any wire segment
to 579-872 for information on 4090-9116; refer to 574- that services a Notification zone.
706 for information on 4098-9793.
• If wiring is routed outside the building, use of a listed
secondary protector is required. Use Simplex Number
2081-9028 or 2081-9044. A protector must be installed
at each building exit/entrance. Each 2081-9028 adds .2
ohm wiring resistance. Each 2081-9044 adds 6 ohms
wiring resistance. Use of the 2081-9044 will signifi-
cantly reduce wiring distance.
• For Class B (Style 4) wiring, adhere to the following:
- Wire all addressable detectors to B+ and B- termi-
nals. Do not return wiring to A+/A- terminals.
- Maximum wiring capacitance is .58uF total. Maxi-
mum wiring resistance to any device is 52 ohms.
- System ships with jumper wires from B+ to A+ and
from B- to A-. Leave jumper wires installed for
Class B wiring.
- T-tapping is allowed for Class B wiring.
2-3
Chapter 2. Installation/System Checkout
Compatible ZAMs/IAMs
IDNet Ferrite Bead Compatible Devices for use with IDNet Monitor
IDNet wiring attached to TB 2-1 and 2-2 must pass through ZAMs
a ferrite bead. Wrap the wiring twice through the ferrite A Zone Addressable Module (ZAM) allows the following
bead, as shown in Figure 2-6. non-IDNet devices to be wired to the addressable channel.
Max. #
Head Base(s)
Devices
4098-9685 N/A 20
Max. #
Head Base(s)
Devices
2-4
Chapter 2. Installation/System Checkout
TYPICAL 4-WIRE
DETECT OR
TYPICAL 4-WIRE ZONE
(RELAY SHO WN
24 VDC power 24VDC DEVICES
ENERGIZED)
from listed FACP
E.O.L. RELAY
RED YELLO W
4090-9101
24VDC
ZAM BLACK
YELLO W END-OF-LINE DEVICE
SELECTED PER ZONE
CIRCUIT
2-5
Chapter 2. Installation/System Checkout
NAC - NAC -
NAC+ NAC+
B+
B+
A+
B-
B-
A-
2-6
Chapter 2. Installation/System Checkout
NAC+ NAC+
B+
B+
A+
B-
B-
A-
TB1
1 2 3 4 5 6 7 8 9 10
Rated Max. # per Rated Max. # Rated Max. # per Rated Max. # per
4906-
Current NAC Current per NAC Current NAC Current NAC
2-7
Chapter 2. Installation/System Checkout
All other regulated 24 VDC synchronized notification • Wiring must pass through a ferrite bead. Wrap the wir-
appliances require the use of their associated, listed external ing twice through the ferrite bead, as shown in
synchronization module. Notification Circuit rating is 1.5 A Figure 2-11.
maximum, 1.35 A maximum strobe load per power supply.
Use the UL-rated operating current to determine maximum
number of appliances allowed per NAC.
details.
• Remote Annunciator Modules require power and com-
munications wiring. 0V SHIELD CONN
(IF USED)
• For “bus-style” wiring, maximum wiring limit is 4, 000
feet. Maximum wiring capacitance is .58 uF total, wire-
to-wire plus wire to shield. Attach Simplex Model 733- TB1 TB2 TB3
974) 100 ohm, 1/2 W harness (see “A” in Figure 2-13) 1 2 3 4 5 6 7 8 1 2 3 4 5 1 2 3 4 5 6 7 8
2-8
Chapter 2. Installation/System Checkout
2-9
Chapter 2. Installation/System Checkout
DANGER
HIGH VOLTAGE
IN THIS AREA
1 2 3 4 5 6 7 8
TB5
TB5 EXPLODED
Note: To connect auxiliary telephone equipment to the same telephone lines as the DACT, be sure to wire from the Line
1 and/or Line 2 "AUX" TIP/RING terminals.
2-10
Chapter 2. Installation/System Checkout
Contact ID
(Preferred)
3/1 Standard
1800/2300 Hz TBD
(10 and 20PPS) With 9032
Line Card
3/1 Standard
1900/1400 Hz TBD
(10 and 20PPS) With 9032
Line Card
4/2 Standard
1800/2300 Hz TBD
(10 and 20PPS) With 9032
Line Card
4/2 Standard
1900/1400 Hz TBD
(10 and 20PPS) With 9032
Line Card
Radionics
BFSK TBD
1800/2300 Hz With 9032
Line Card
Radionics
BFSK TBD
1900/1400 Hz With 9032
Line Card
SIA TBD
Notes:
1. With 685-8 Line Card
2. With Rec-11 Line Card
3. These receivers are also Factory Mutual (FM) approved.
4. With or without D6680 Network Ethernet Adapter
5. DSC TL300
2-11
Chapter 2. Installation/System Checkout
T-Link TL300
*See note 5
Network
+ - TX
RX
GND
RED
BLK
YEL
GRN PGM2 GND IN3 IN4 T1
12 - 24VDC PGM1 IN1 IN2 GND Earth R1 #18-#26 awg
EOLR for IDC
#18- 22 awg
150 ma max
1 2 3 4 5 6 7 8
2-12
Chapter 2. Installation/System Checkout
Notes:
1. A Bosch C900V2 in a Bosch
AE2 enclosure must be Bosch AE2 enclosure (See note 1)
mounted within 20 feet of the
FACP and be in the same Panel
P2 C900V2
room as it. The S1
RJ45
wiring to the FACP must be See note 3
P1
enclosed in the conduit or be
equivalently Telco
protected against
mechanical damage. The
cabinet must be grounded.
1 2 3 4 5 6 7 8
TB5
Figure 2-16 Bosch C900V2 DACT using the Ethernet Line (UL only)
2-13
Chapter 2. Installation/System Checkout
Auxiliary 24V Power Wiring • Compatible with Simplex 4098 Series Peripherals; 2098
Series Relay Modules; all Simplex 4090 Series IDNet
• All wiring is to be 18 AWG (min.) to 12 AWG (max.) Peripherals; and 4610-9111 / 4606-9101 Annunciators.
• Conductors must test free of all grounds and stray volt- • If wiring is routed outside the building, use of a listed
ages before connection to appliances and panel. secondary protector is required. Use Simplex Model
• All wiring is supervised and power limited. 2081-9028 or 2081-9044. A protector must be installed
at each building exit/entrance. Each 2081-9044 adds 6
• Voltage rating (24 VDC special application): 1 V p-p
ohms wiring resistance, and is rated for 200mA. Each
ripple (maximum)
2081-9028 adds .2 ohms wiring resistance, and is rated
- 0.5 A maximum available aux 24 V from EPS
for more than 1/2A Aux. 24V capacity.
- Additional 0.5 A maximum available from Main
System Board (MSB) AUX 24 V • Compatible devices must operate from a range of 19.5
- 3 A total available from MSB NACs and MSB to 28 VDC or greater, and have a total current draw of 1/
AUX 24 V. 2 A or less.
- 3 A total available from EPS NACs and EPS AUX
24 V.
City Connect Module Wiring • City module consists of two circuits that are jumper-
configured. Circuits may be configured for reverse-
• City connect module mounts to the main system as polarity or local energy operation. See jumper setting
shown. Refer to City Module Installation Instructions table for details. Modules must also be added to the sys-
for details. tem configuration. See “System Options” later in this
manual.
2-14
Chapter 2. Installation/System Checkout
• All wiring to be per NFPA-72, NEC, and local codes. Number 2081-9044. A protector must be installed at
Minimum 20 AWG for reverse polarity circuits; mini- each location the wiring enters or exits a building. Each
mum 18 AWG for local energy circuits. 2081-9044 adds 6 ohms wiring resistance and is rated
• Wiring is supervised for opens and grounds, but not for 200 mA. Maximum wiring resistance is reduced by
power-limited. 6 ohms for each 2081-9044 used.
• Conductors must test free of all grounds. • Circuits are shipped with 3.3K, 1/2W resistor installed.
Remove resistor before wiring circuit. Leave installed
• For specific information about reverse polarity and local
on unused circuits.
energy circuits see Figure 2-18.
• If wiring is routed outside the building, use of a listed
secondary protector is required. Use Simplex Model
9-10
7-8
5-6
3-4
1-2
O O
N N
O O
N N
Shows ON Position
Auxiliary Relay Wiring • Conductors must test free of all grounds and stray volt-
ages before connection to appliances, devices, and
• All wiring must be 18 AWG (minimum) to 12 AWG panel.
(maximum).
2-15
Chapter 2. Installation/System Checkout
TBL. AUX.
RELAY RELAY
J C
U E
M N
P T
E E
R R
JUMPER
CENTER
MAIN SYSTEM BOARD - ADDRESSABLE (MSB - A)
2-16
Chapter 2. Installation/System Checkout
EPS
POWER SUPPLY MODULE
TB1
EXPANSION POWER SUPPLY ASSY.
DANGER
1 2 3 4 5 6 7 8 9 10
B+ B-
HIGH VOLTAGE
IN THIS AREA
NAC MODULE
B+ B- A+ A-
DACT TELEPHONE
CONNECTIONS
1 2 3 4 5 6 7 8
TB5
LINE
734 - 179
WIRE AC LINE AND NEUTRAL AS SHOWN.
NEUTRAL HOT TO LEFT TERMINAL, NEUTRAL TO RIGHT TERMINAL.
WHITE
BLACK WHITE / BLACK HARNESS 734 - 179
FROM EPS (LOWER MODULES)
TO MAIN SYSTEM BOARD.
2-17
Chapter 2. Installation/System Checkout
EPS
POWER SUPPLY MODULE
TB1
EXPANSION POWER SUPPLY ASSY.
DANGER 3B+
1 2 3 4 5 6 7 8 9 10
HIGH VOLTAGE 3B-
IN THIS AREA 3A+
NAC MODULE
3A-
4B+
4B-
DACT TELEPHONE 4A-
CONNECTIONS 4A-
1 2 3 4 5 6 7 8 24V
0V
TB5
R B 734 - 180
E L ATTACH TO BATTERY CONNECTOR
D K RIGHT - JUSTIFIED, BLACK WIRE TO THE RIGHT
BLACK
RED
R B
E L HARNESS 734 - 180
D K FROM EPS (LOWER MODULES)
TO MAIN SYSTEM BOARD
BATTERY CONNECTOR
CONNECT TO
BATTERY TERMINALS
(FUSED ON PCB)
+ - + -
LINE NEUTRAL BATT EPS
2-18
Chapter 2. Installation/System Checkout
00 00 02
Replacing Lithium Battery
The panel uses a lithium battery to maintain non-volatile
memory on the panel. In the event of a total power-down
Pressing the <TROUBLE ACK> key allows the operator to (AC power and lead-acid battery), the lithium battery allows
acknowledge the troubles (silencing the panel sounder) and the panel to maintain all historical logs, time/date informa-
scroll through the troubles on the active Trouble List. tion, list of disabled points, and the alarm verification tallies.
2-19
Chapter 2. Installation/System Checkout
edition. Local codes may require additional testing and 30 86 2.234 2.277 26.81 27.32
maintenance. All system components must be tested in
35 95 2.224 2.262 26.69 27.14
accordance with governing codes. Specific details on select
system components are provided below. 40 104 2.214 2.247 26.57 26.96
Min. Max.
Temp Temp V/cell V/cell
Battery Battery
(C) (F) (min) (max)
Voltage Voltage
2-20
Chapter 3. Auto-Programming
The Auto-Program option provides the ability to quickly and automati- In This Chapter
cally program the panel’s components and features for general alarm
operation. It automatically scans the serial communication channel, add-
ing any annunciators found, polls the IDNet channel and configures any Configure All. . . . . . . . . . . . . . . . . . . . . . . . . . .3-1
IDNet devices found, and adds any option cards found. Detect New Hardware . . . . . . . . . . . . . . . . . . .3-2
Restore Factory Defaults . . . . . . . . . . . . . . . . .3-2
Edit System Options. . . . . . . . . . . . . . . . . . . . .3-2
Auto-Program can perform the following:
Restore Default System Options . . . . . . . . . . .3-3
• Reconfigure all hardware Saving the Configuration . . . . . . . . . . . . . . . . .3-3
• Add new hardware Default Programming Assignments . . . . . . . . .3-3
• Restore factory defaults
• Edit system option settings
Configure All
This option starts the panel with a new configuration. If a previous con-
figuration is present and this option is selected, it erases the previous
configuration and creates a new one with the currently connected hard-
ware.
1. Press <MENU> to select the main menu.
2. Press <NEXT> or <PREVIOUS> until the [Auto-Program] menu
item is displayed and then press <ENTER>. The following appears:
FIRE ALARM
SUSPENDED
3-1
Chapter 3. Auto-Programming
3-2
Chapter 3. Auto-Programming
Table 3-1 System Options (Continued) Table 3-1 System Options (Continued)
Alarm Cutout Timer Choose a timer range from 0-60 min- Report AC Fail Delay This option is the time delay that the
utes (default=0 - no cutout) system uses before reporting an AC
Failure condition to the central station
Door Drop on Alarm Choose a timer range from 0-60 sec- via the DACT, or before the city trouble
onds (default=0 - immediate) is tripped if the only trouble is AC Fail-
ure.
Door Drop on AC fail Choose a timer range from 0-60 min-
utes (default=5 minutes) Test Report Time Selects the time when the daily System
Test Report is sent to the central sta-
Detector Output Selects IDNet device sounder base
tion. The default is 2 A.M. For system
coding operation. software revision 1.03.07 and above
the test report message will be sent at
Depleted Battery Cut- Choose ON or OFF; default = OFF
out 6 hour intervals beginning at the time
entered.
Display 1st Alarm Choose ON or OFF; default = OFF
Edit Passcodes
Enable City Circuit Choose ON or OFF; default = OFF
Enable Expansion Choose ON or OFF; default = OFF Restore Default System Options
Power
This option allows the operator to restore the factory-default
Single Station Selects whether or not sounder or relay
options that may have been edited. It will erase any edits that
base devices operate in single station
mode. were performed in the "Edit System Options" menu, but
leave any card/point programming intact.
Cross Zone Selectable per alarm group. Selects
whether one alarm or more than one
alarm is required to trigger outputs for Saving the Configuration
that alarm group.
When the Auto-Programming operation is complete, press
Alarm Groups programmed as Cross the <EXIT/CLEAR> key. The following screen will be dis-
Zone shall not contain any devices pro- played.
grammed with the VSMOKE Input
Function Type.
JOB HAS CHANGED
Alarm Groups programmed as Cross [Cont] Dscrd Save
Zones shall include a minimum of 2
detectors in each protected zone and • Continue Edit. Continue editing the configuration.
the spacings between detectors shall
• Discard Changes. Discard changes made during the
be reduced to 0.7 times the recom-
mended linear spacing in accordance programming session and restore the original configura-
with NFPA72-2002. tion (if possible).
AHJ Reset If this option is not selected, a point that
• Save Job. Save the new job configuration.
has alarmed the panel must be dis- When the configuration is saved, the panel will automati-
abled or restored to the normal state cally restart and run through its self-test procedure.
before the panel can be reset. When
this option is selected, the device only
needs to be no longer in the alarm state Default Programming Assignments
for the system to be reset (e.g. point
can be in trouble). IDNet and NAC Default Function Types
NFPA NAC Operation When this option is selected, the Table 3-2 lists the default function types assigned by the auto
strobes on the QALERT NACs will turn programming process to IDNet and NAC devices. The func-
off when alarm silence is activated. If tion type determines the manner in which the device oper-
the option is not selected, the strobes ates (i.e., a function type of SSIG or SRELAY means the
turn off upon completion of system
device is on until an alarm silence is performed). The func-
reset.
tion type is a programmable attribute, and it can be manually
changed, as described in Chapter 4 (IDNet) and Chapter 5
(NAC, Relay, DACT) of this manual.
3-3
Chapter 3. Auto-Programming
HEAT HEAT Heat Detector SIG3-4 (NAC) Synchronized. Used with visual NACs. Pro-
grams all visuals to flash simultaneously.
SHEAT HEAT Heat Detector with sounder output
AUX1 & AUX2 Steady on
RHEAT HEAT Heat Detector with relay output
RELAY Modules Steady on
IHEAT HEAT Heat Detector with isolator
SIGNAL Mod- Steady on
OHEAT HEAT Rate-of-rise Heat Detector ules
OSHEAT HEAT Rate-of-rise Heat Detector with
sounder output Annunciator Defaults
ORHEAT HEAT Rate-of-rise Heat Detector with relay Annunciator cards found during the Auto-Program process
output are added into the default configuration.
OIHEAT HEAT Rate-of-rise Heat Detector with isolator • LCD Annunciators are configured to receive all events.
Refer to Chapter 6 for information on manually pro-
AZONE FIRE Class A General Alarm Fire Monitor
gramming which events are received by the LCD
Zone
Annunciator.
BZONE FIRE Class B General Alarm Fire Monitor • LED and LED/Switch Annunciators are configured
Zone
according to the charts in Chapter 6. Refer to this chap-
MON FIRE General Alarm Fire Monitor Zone ter for full programming information.
PULL PULL Addressable Manual Pull Station • Address 4 is used with 4008-9121 for the Local LED
(door mounted) annunciator. Set the address of LCD
RELAY RRELAY General Alarm Relay (on-til-reset) and LED/Switch annunciators to 5-7 when auto-pro-
SIGNAL SSIG General Alarm Signal (on-til-silence) gramming is used. For the 4008-9101, a remote annun-
ciator may be manually programmed at address 4.
ISOL ISOL IDNet loop isolator
DACT Defaults
SIG1-2 SSIG General Alarm Signal (on-til-silence)
The defaults for the DACT are listed below. Refer to Chap-
SIG3-4 RSIG General Alarm Signal (on-til-reset)
ter 5 for information on manually programming the DACT.
AUX1 RSIG General Alarm Relay (on-til-reset) • Tone else pulse dialing
AUX2 TRBL Trouble Relay (on-til-clear) • AC Fail reporting delay is 2 hours
• Reporting format is CID
NAC, Relay, and Signal Circuit Output Mode • Primary and Secondary Phone Number. There are no
Assignments values for the primary and secondary phone numbers or
Table 3-3 lists the default output mode (steady, temporal, account codes.
etc.) assignments for the NAC, Relay, and Signal circuits. • The CID Group and CID Point Identifier default to the
IDNet device address.
3-4
Chapter 3. Auto-Programming
*Any other trouble not specifically mentioned would have a code of 330.
For example, a trouble on an output device would report an event code of 330.
3-5
Chapter 4. Manually Programming
IDNet Points
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Stan-
dard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be
limited to specific values or not used at all as indicated below.
Program Feature or Option Permitted in UL 864? (Y/N) Possible Settings Settings Permitted in UL 864
This chapter discusses manually adding, deleting, and editing the attri- In This Chapter
butes of the panel’s IDNet points.
In most cases, it is recommended that you use the panel’s auto program- Accessing IDNet Programming Menus . . . . . .4-2
ming feature (see Chapter 3) when initially programming the panel, or Adding an IDNet Device. . . . . . . . . . . . . . . . . .4-2
when adding devices to an existing job. Auto programming scans the Editing IDNet Device Attributes . . . . . . . . . . . .4-2
IDNet channel and automatically adds devices that it finds to the job. Deleting an IDNet Point . . . . . . . . . . . . . . . . . .4-8
Once the devices are added, use the manual programming procedures
described in this chapter to adjust the point attributes listed below to
your site-specific needs.
To manually add, edit, or delete a IDNet point, you must first login at
Access Level 4. Refer to Chapter 1 for information on doing this.
4-1
Chapter 4. Manually Programming IDNet Points
Accessing IDNet Programming Note: Make sure the address shown on the display corresponds to
the physical address, set via dip switches, of the device.
Menus
Refer to “Editing IDNet Device” for information on setting
1. Press the <MENU> key. Press <NEXT> or <PREV> device attributes.
until the [Programming] option is displayed. Press
<ENTER>. The following displays:
Editing IDNet Device Attributes
FIRE ALARM
SUSPENDED Editing Hardware Type
<ENTER> to Program The hardware type identifies the specific device assigned to
<EXIT> to resume the IDNet address. Table 4-1 and Table 4-2 identify the
required hardware types for all IDNet devices and modules.
2. Press <ENTER>. The Programming menu appears: 1. Follow the steps outlined in “Accessing IDNet Pro-
gramming Menus” earlier in this chapter. Select “Edit”
<ENTER>=Accept
and then press <ENTER>. The display shows the first
Prg:[Points]
point in the list. For example:
3. Press Enter again. A prompt appears, allowing you to
Lobby Door
select the type of point to manually edit. By default,
Pull M1
IDNet is the first choice.
2. Use the <NEXT> and <PREV> keys to scroll through
<ENTER>=Accept
the list of points until the appropriate point is displayed.
Prg: [IDNet]
Press <ENTER>. A prompt similar to the following
4. Press <ENTER>. appears.
<ENTER>=Accept IDNet: 1
IDNet: [Add] Fn: [Hardware Type]
5. Use The <NEXT> and <PREV> keys to scroll through 3. Press <ENTER>. A prompt similar to the following
the following choices and then press <ENTER>. appears, allowing you to set the Hardware Type.
4-2
Chapter 4. Manually Programming IDNet Points
4098-9792 4090-9007
4098-9792C Zone Individual Addressable Module (IAM) for SIGNAL
Detector base w/o remote LED Class A or B Signal Circuits
HEAT
4098-9789 OHEAT 4090-9001
IAM
4098-9789C Supervised Individual Addressable Module (IAM)
4098-9733 Detector base with remote LED
4090-9002
4098- RIAM
4098-9791 Indiv. Addressable Module with Relay
9733C RHEAT
4098-9791C
ROHEAT
Detector base with relay 4090-9116
Heat ISOL
Addressable Isolator
Detector 4098-9793
Sensor IHEAT
4098-9793C 4090-9101
IOHEAT
Isolator base Class B Zone Addressable Module for monitor MBZAM
devices
4098-9794
4098-9794C SHEAT 4090-9106
Sounder base SOHEAT Class A Zone Addressable Module (ZAM) for MAZAM
See Note 1 below. monitor devices
4098-9754 4098-9795
4099-9010 Single action pull station
4098- 4098-9795C SPHOTO &
9754C Multi-detector sounder base SHEAT ADRPUL
4099-9012 Dual Action (Push/Pull)
See Note 1 and Note 2 below.
Addressable Pull Stations
Combina-
tion Photo
Electric 4098-9796
Smoke 4098-9796C PHOTO &
Detector Multi-detector base with LED HEAT
and Heat See Note 2 below. Edit IDNet Function Type
Detector
The panel’s addressable channel supports the following
function types.
4-3
Chapter 4. Manually Programming IDNet Points
• Input function types are used with monitor points. 6. <ENTER> will select the function in the display, while
The function type determines the way in which the <EXIT/CLEAR> will return to the previous screen
panel responds to a change in a point’s electrical state. without making any changes
For example, when you assign the SMOKE function
type to a smoke detector, the system interprets an open Note: Refer to table at top of Page 4-1 for UL 864 compliant options.
on the device as a trouble and a short/abnormal state as
a fire. Refer to Table 4-3 for a list of input function Table 4-3 Input Function Types
types and states.
Function
• Output Function Types are used with notification Device State = Status
Type
appliances and relays (connected via a 4090-9007 Sig-
nal IAM). An output point’s function type determines Normal = NORMAL
Current-Limited = FIRE
the operation of the NAC or relay (e.g., on til silence; on
Short = FIRE
til reset, etc.) Refer to Table 4-4 for a list of output func- SMOKE
Open = TROUBLE
tion types. Notification appliances and relays controlled
via a 4090-9007 Signal IAM or 4090-9002 Relay IAM Use with smoke detectors.
activate with a steady output; coding of notification
Normal = NORMAL
appliances and relays attached to IAMs is not allowed. Current-Limited = FIRE
Short = FIRE
Program the input and output function types as follows: HEAT
Open = TROUBLE
1. Follow the steps outlined in “Accessing IDNet Pro- Use with heat detectors.
gramming Menus” earlier in this chapter. Select “Edit”
and then press <ENTER>. The display shows the first Normal = NORMAL
point in the list. For example: Current-Limited = FIRE
Short = FIRE
PULL
Open = TROUBLE
Lobby Door
Pull M1 Use with pull stations.
2. Use the <NEXT> and <PREV> keys to scroll through Normal = NORMAL
the list of points until the appropriate point is displayed. Current-Limited = FIRE
Short = FIRE
Press <ENTER>. A prompt similar to the following DUCT
Open = TROUBLE
appears.
Use with Duct detectors.
IDNet: 1
Fn: [Hardware Type]
IDNet: 1
[PULL]
<ENTER>= Confirm
[PULL]
4-4
Chapter 4. Manually Programming IDNet Points
Table 4-3 Input Function Types (Continued) Table 4-3 Input Function Types (Continued)
Function Function
Device State = Status Device State = Status
Type Type
If a smoke detector with the function type Used to monitor any supervisory type device
VSMOKE enters a current-limited state, the where operator acknowledgment is required.
panel’s alarm verification cycle begins. The panel
starts a delay timer of 30 seconds. When the Normal = NORMAL
timer expires, the zone containing the activated Current-Limited = SUPERVISORY
detector is reset. Following the reset, another 10 Short = SUPERVISORY
second timer starts. When the 10 second timer LATSUPV Open = TROUBLE
expires, the system checks the device for an
alarm. If a current-limited condition exists on the Generic supervisory monitor - latches until a sys-
device, the panel initiates a fire alarm. If no cur- tem reset occurs.
VSMOKE
rent-limited condition exists, the panel starts a 2
Normal = NORMAL
minute timer. While the timer is counting down,
Current-Limited = SUPERVISORY
any current-limited condition on any other device
will trigger a fire alarm. Short = SUPERVISORY
Open = TROUBLE
SO
A short from a pull-station always triggers an
alarm condition, regardless of the alarm verifica- Used to indicate abnormal sprinkler conditions,
such as the opening of a PIV or OS&Y tamper-
tion cycle.
switch. Must be used with normally open contacts
At any stage of the alarm verification cycle, the only.
presence of two devices in alarm triggers an
Normal = NORMAL
alarm condition. Current-Limited = SUPERVISORY
Short = FIRE (water flow)
Note: The VSMOKE function type shall not be
Open = TROUBLE
enabled for Canadian applications.
Combination Waterflow/Sprinkler Monitor (NO).
Normal = NORMAL WSO
Current-Limited = FIRE Where permitted by the AHJ, this circuit
monitors both waterflow sensors and PIV/OS&Y
Short = FIRE
tampers on the same circuit. All tamper switches
Open = TROUBLE
(N.O. contacts) must be connected with a listed
current limiting resistor. A short condition indi-
This is a generic fire alarm point type. A typical
cates waterflow alarms.
FIRE application for this point type is a fire alarm
zone containing more than one type of device.
Normal = NORMAL
For example, when a combination of smoke
Current-Limited = FIRE (water flow)
detectors, pull stations, waterflow monitors, and Short = FIRE (water flow)
heat detectors is connected to an IAM or WATER
Open = TROUBLE
ZAM, this point type allows alarms to report as
originating from a zone. Use with normally open waterflow monitors.
Normal = NORMAL Normal = NORMAL
Current-Limited = FIRE Current-Limited = TROUBLE
Short = TROUBLE
Short = TROUBLE
Open = TROUBLE TROUBLE
STYLEC Open = TROUBLE
Style-C Fire Alarm Monitor. Used when only cur-
Generic trouble monitor.
rent limited devices are connected to the zone. A
short circuit is reported as a Trouble.
4-5
Chapter 4. Manually Programming IDNet Points
Table 4-3 Input Function Types (Continued) Table 4-4 Output Function Types (Continued)
Function Function
Device State = Status Description
Type Type
PRIMARY
Relay activates on general alarm. Relay is tied to - Alarm Group 97. Associate all zones used to recall the ele-
Primary Elevator Recall contacts. See Note below. vator to the alternate floor in this alarm group.
Relay activates on general alarm. Relay is tied to
ALTERN Alternate Elevator Recall contacts. See Note Editing Point Labels
below.
1. Follow the steps in “Accessing Menus”. Make sure to
Relay provides 24V power to four wire detectors. choose IDNet as the type of device to program.
DRESET
Relay turns off for 5 secs on system reset)
<ENTER>=Accept
Prg: [IDNet]
4-6
Chapter 4. Manually Programming IDNet Points
2. Use the <NEXT> and <PREV> keys to scroll through Table 4-5 Word Library
the choices until <EDIT> appears.
3. Press <ENTER>. The top line shows the custom label
assigned to the first IDNet point. Use the <NEXT> and 2ND ELECT. RM WING
<PREV> keys to scroll through the list of points.
3RD ELEVATOR ZONE
4. Press <ENTER> when the appropriate point is dis-
played. A prompt appears, asking you to specify the 4TH ENTRANCE
function type. Use the <NEXT> and <PREV> keys to
CENTR RM __ OFFICE
scroll through the choices until <Edit Label> appears.
EAST FLR_3 HVAC_ROOM
IDNet1
Fn: [Edit Label] FIRST CORRIDOR STOREROOM
The right and left arrow keys allow you to move the focus
5th FLOOR brackets to a different alarm group, while the <NEXT> and
4-7
Chapter 4. Manually Programming IDNet Points
4-8
Chapter 5. Manually Programming NACs,
Relays, and DACT
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Stan-
dard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be
limited to specific values or not used at all as indicated below.
Program Feature or Option Permitted in UL 864? (Y/N) Possible Settings Settings Permitted in UL 864
Manually programming NAC, programmable relay, and DACT points In This Chapter
allows you to set the attributes of the point to the specific values
required for the job. You can create a custom label for each point,
change the way in which the NACs, programmable relays, and DACT Accessing Menus . . . . . . . . . . . . . . . . . . . . . . 5-2
operate, or add a NAC or relay to an alarm group for selective signaling. Programming NACs . . . . . . . . . . . . . . . . . . . . 5-2
Programming AUX Relays . . . . . . . . . . . . . . . 5-5
It is recommended that you use the panel’s auto programming feature Programming DACT. . . . . . . . . . . . . . . . . . . . 5-6
Accessing DACT Menu . . . . . . . . . . . . . . . . . 5-7
(see Chapter 3) when initially programming the panel, or when adding
Programming DACT Options . . . . . . . . . . . . . 5-7
devices to an existing job. Auto programming automatically programs
Programming Contact ID (CID) Points . . . . . 5-10
the NACs, Relays, and DACT with default values. You can then use the Programming Event Codes . . . . . . . . . . . . . 5-11
manual programming procedures described in this chapter to adjust the Saving Changes. . . . . . . . . . . . . . . . . . . . . . 5-11
following values.
To manually add, edit, or delete a point, you must first login at Access
Level 4. Refer to Chapter 1 for information on doing this.
If an Expansion Power Supply Module is installed in the system, you
must first set the Expansion Power Supply system option to ON before
5-1
Chapter 5. Manually Programming NACs, Relays, and DACT
Use the following steps to gain access to the NAC and relay Setting NAC Function Type and Coding Pattern
menus. The Function Type determines the way in which the NAC
operates (whether it is an audible, visual, relay, etc.) and its
1. Press the <MENU> key. Press <NEXT> or <PREV>
output method (steady, etc.)
until the [Programming] option is displayed. Press
<ENTER>. The following displays: 1. Follow the steps in “Accessing Menus”. Make sure to
choose NAC as the type of device to program.
FIRE ALARM
SUSPENDED <ENTER>=Accept
Prg: [NAC]
<ENTER> to Program
<EXIT> to resume 2. Press <ENTER>, and then use <NEXT> and <PREV>
keys to choose the circuit (NAC1, NAC2, NAC3, or
2. Press <ENTER>. The Programming menu appears. NAC4) to program.
[Points] is the default selection, which allows you to
make changes to a specific point’s programming. NAC1
Signal 1/4
<ENTER>=Accept
Prg:[Points] 3. Press <ENTER> when the appropriate NAC is dis-
played. A prompt appears, asking you to specify the
3. Press <ENTER>. A prompt appears, allowing you to NAC function type.
select the type of point to manually edit. By default,
[IDNet] is the first choice. NAC1
Fn: [Function]
<ENTER>=Accept
Prg:[IDNet] 4. Press <ENTER>. As shown in the example below, the
NAC function type is comprised of two parts -- the
4. Possible choices for this prompt are listed below. Use function (On Till Silence, On Till Reset, etc.) and the
the <NEXT> and <PREV> keys to scroll to the appro- coding pattern (temporal, 120 BPM, etc.)
priate choice and then press <ENTER>.
• NAC NAC1
[SSIG] TEMPRL
• RELAY (Use for panel’s on-board AUX relays)
5. Use the <NEXT> and <PREV> keys to select the
Select the operation you want to perform and see the appro-
appropriate Function. Use the right and left arrow keys
priate section in this chapter.
to move the cursor between the function type and the
coding pattern. Use the <NEXT> and <PREV> keys to
Programming NACs set the pattern to the appropriate choice.
Use the following procedure to edit the programming of the 6. Pressing <ENTER> will accept any changes made and
two Notification Appliance Circuits (NACs) on the base exit, and the <EXIT/CLEAR> key quits editing without
panel, or the two optional NACs on the expansion power saving.
supply. NACs cannot be added or deleted, only edited. Note: Refer to the table located at the top of Page 5-1 for UL 864
compliant options.
NAC editing provides the following options:
1. Edit Function, which defines the following for a NAC:
- When the NAC activates and deactivates
- The "output method" used by the NAC when it acti-
vates (coded, steady, etc.)
5-2
Chapter 5. Manually Programming NACs, Relays, and DACT
5-3
Chapter 5. Manually Programming NACs, Relays, and DACT
Operation Description This option allows you to assign a 40-character custom label
to each NAC point.
Steady Steady On
1. Follow the steps in “Accessing NAC and Relay
20 BPM *Slow March Time - 20 beats per minute Menus”. Make sure to choose NAC as the type of
120 BPM *Fast March Time - 120 beats per minute device to program.
<ENTER>=Accept
*NACs programmed as the QALERT function type will
Prg: [NAC]
code at a 60 BPM March-Time rate if either the 20 BPM or
120 BPM NAC coding pattern is selected. 2. Press <ENTER>, and then use <NEXT> and <PREV>
keys to choose the circuit (NAC1, NAC2, NAC3, or
Editing Alarm Groups
NAC4) to program.
Alarm groups allow you to program selective signaling.
Assign the NAC an alarm group number from 1 to 99. NAC1
Assign the same alarm group number to the initiating Signal 1/4
device(s) that you want to control the NAC. Each NAC can
be in up to three groups. 3. Press <ENTER> when the appropriate NAC is dis-
played. A prompt appears, asking you to specify the
1. Follow the steps in “Accessing Menus”. Make sure to NAC function type.
choose NAC as the type of device to program
NAC1
<ENTER>=Accept FN: [Function Type]
Prg: [NAC]
4. Use the <NEXT> and <PREV> keys until <Edit Label>
2. Press <ENTER>, and then use <NEXT> and <PREV> is displayed. For example:
keys to choose the circuit (NAC1, NAC2, NAC3, or
NAC4) to program. NAC1
Fn: [Edit Label]
NAC1
Signal 1/4 5. Press <ENTER>. The current custom label for the point
is displayed on the top line of the display. A cursor is
3. Press <ENTER> when the appropriate NAC is dis- shown below the selected character in the label. Use the
played. A prompt appears, asking you to specify the right and left arrow keys to move the cursor to a differ-
NAC function type. ent character to edit; use the <NEXT> and <PREV>
keys to scroll through the characters.
NAC1
The characters available for labels are:
FN: [Function Type]
A-Z 0-9 , blank space & ( ) * + - . / : ‘ # ! @ $ % ^ = ? ;
4. Use the <NEXT> and <PREV> keys until [Alarm
Groups] is displayed. For example: A label is edited in one of three ways:
• Using the keypad. Press the alphanumeric key corre-
NAC1 sponding to the letter you want. For example, for the let-
Fn: [Alarm Groups] ter “C”, press the “2” key on the keypad four times. Use
the left and right arrow keys to move to the next letter in
5. Press <ENTER>. A prompt similar to the following the label.
appears.
• Use the <NEXT> and <PREV> keys. Each time you
ALARM GROUPS press the <NEXT> key, the display advances to the next
[99] 00 00 character. Each press of the <PREV> key moves back
one character. Use the left and right arrow keys to move
6. Use the <NEXT> and <PREV> keys to scroll the num- between letters in the label.
ber in the brackets. Use the right and left arrow keys to
move between the alarm groups. Press <ENTER> when
all the values are set correctly.
5-4
Chapter 5. Manually Programming NACs, Relays, and DACT
• Use the Word Library, which is a stored list of common 4. Press <ENTER>. The display appears similar to the fol-
words stored alphabetically. Press the <FUNCTION> lowing. As shown in the example below, the function
key on the front panel, and a prompt of the format type is comprised of two parts -- the function (On Till
below is displayed. Trouble Relay, On Till Reset, etc.) and the coding pat-
NAC1 tern (Steady, 120 BPM, etc.)
<FUNC> = Word Library
AUX1
To jump to a word, press the alphanumeric key corre- [RRELAY] STEADY
sponding to the first letter in the word. For example, to
use the word Floor, press the “3” key repeatedly until 5. Use the <NEXT> and <PREV> keys to select the
floor is displayed. to access words beginning with the appropriate Function. Use the right arrow key to move
same letter use the Next/Prev keys to select the word. the cursor to the coding pattern, and then use the
<NEXT> and <PREV> keys to set the pattern.
6. Pressing the <ENTER> key will save the current label,
and <EXIT/CLEAR> will quit label editing without 6. Pressing <ENTER> will accept any changes made and
saving. exit. <EXIT/CLEAR> key will quit the alarm group edit
without saving.
Clear Point Label Note: Refer to the table located at the top of Page 5-1 for UL 864
compliant options.
The "Clear Point Label" menu performs the same function as
"Edit Point Label" described above except that it clears the Table 5-3 Relay Function Types
point's currently assigned label first.
Function
Description
Type
Programming AUX Relays
Relay activates on general alarm;
Aux Relay programming allows you to define the following SRELAY
remains on-til-silence.
options:
Relay activates on general alarm;
• Function, defines the following for a relay. RRELAY
remains on-til-reset.
- When the Relay activates and deactivates.
Relay activates when a Supervisory
- The "output method" that defines how the Relay SUPV condition occurs; remains on-til-
activates (coded, steady, etc.) cleared.
• Edit or Clear Point Label. Allows you to set a 40 char- Relay activates when a Trouble con-
acter label for the relay point. TROUBLE
dition occurs; remains on-till cleared.
• Alarm Group. Allows you to associate the relay with up Relay activates when a utility IDC in
to 99 groups of initiating devices, providing the ability UTILITY
the same alarm group activates.
to perform selective activation of the relay.
PRIMARY Relay activates on general alarm.
1. Follow the steps in “Accessing Menus.” Make sure to See Note Relay is tied to Primary Elevator
choose Relay as the type of device to program. Below Recall contacts.
2. Press <ENTER>, and then use <NEXT> and <PREV> Relay provides 24V power to four
to choose the relay to program. DRESET wire detectors. Relay turns off for 5
secs on system reset.
AUX1 Relay typically provides 24V power to
Alarm 1/1 larger door holder relay with separate
power source. Relay activates on
DHOLDER
3. Press <ENTER> when the appropriate relay is dis- general alarm and signals door
played. A prompt appears, asking you to specify the holder relay to cut power to door
holder magnets.
relay function type.
AUX1
FN: [Function]
5-5
Chapter 5. Manually Programming NACs, Relays, and DACT
5-6
Chapter 5. Manually Programming NACs, Relays, and DACT
5-7
Chapter 5. Manually Programming NACs, Relays, and DACT
5. Press <ENTER> to confirm the selection. The prompt 1. Use the arrow keys to move the cursor from one number
shown in Step 1 reappears. Use the <NEXT> key to to another. Use the NEXT and PREV keys or the key-
move to the prompt for primary phone number. pad to enter each number.
Setting Primary Phone Number 2. Press <ENTER> when the number is correctly entered.
A prompt appears asking you to confirm the number
The next prompt allows you to set the Primary Phone Num- that you entered.
ber of the supervising station. This is the number that the
DACT dials first. 3. Press <ENTER>. The prompt shown above Step 1 reap-
pears.
Note: When connecting to a TL300, enter any telephone number.
4. Press the <NEXT> key. The prompt for the Secondary
<ENTER>=Accept Phone Number appears.
Opt: [Pri Phone #]
Setting Secondary Phone Number
1. Press <ENTER>. The following prompt appears. The Secondary Phone Number specifies the alternate phone
number that the DACT can use if attempts to dial the pri-
Pri Phone #
mary phone number fail.
[X] XXXXXXXXXXXXXXXX
2. Use the arrow keys to move the cursor from one digit to
another. Use the keypad numbers, or use the NEXT and Note: When connecting to a TL300, enter any telephone number.
PREV keys to enter each number. Press <ENTER> You can also use the special characters B, C, D, and E when specify-
ing the Secondary Phone Number. See the description of these char-
when the number is correctly entered. A prompt appears acters in the section “Setting Primary Phone Number” above.
asking you to confirm the number that you entered.
<ENTER>=Accept
Opt: [Sec Phone #]
Note: The following special characters are available for use
when setting the primary and secondary phone numbers. 1. Press <ENTER>. The following prompt appears.
• B -- Use if it is necessary to input a DTMF (touch- Sec Phone #
tone) asterisk (*) into the phone number. [X] XXXXXXXXXXXXXXXX
• C -- Use if it is necessary to input a DTMF pound
sign (#) into the phone number. 2. Use the arrow keys to move the cursor from one digit to
another. Use the keypad numbers, or use the NEXT and
• D -- Inserting this character into the phone number PREV keys to enter each number. Press <ENTER>
causes a 3 second delay at the point at which the D when the number is correctly entered. A prompt appears
appears. asking you to confirm the number that you entered.
• E -- This character allows the DACT to start dialing
as soon as a dial tone is detected. If “E” is not the 3. Press <ENTER> again. The prompt shown above Step 1
first character of the number, the DACT will wait 7 reappears.
additional seconds before dialing. Do not use “E” 4. Press the <NEXT> key. The prompt for the Secondary
after the first digit unless a secondary dial tone is Account Number appears.
expected.
3. Press <ENTER>. The prompt shown in Step 1 reap-
pears.
4. Press the <NEXT> key. The prompt for the primary
account number appears.
Pri Account #
[0] 000
5-8
Chapter 5. Manually Programming NACs, Relays, and DACT
3. Press <ENTER>. The prompt shown above Step 1 reap- Setting Pulse Frequency
pears.
The pulse frequency specifies the frequency (in KHz) of the
4. Press the <NEXT> key. The prompt for setting the dial- pulses used by the DACT.
ing mode appears.
<ENTER> = Accept
Setting Dialing Mode Opt: [Pulse Freq]
The dialing mode specifies the type of phone line being used
1. Press <ENTER>.
by the DACT.
Pulse Freq
<ENTER> = Accept
[1.9KHz Data]
Dialing Mode
2. Use the NEXT and PREV keys to move from one
1. Press <ENTER>.
choice to another. Choices are
Dialing Mode
1.9 KHz
[Tone else Pulse]
1.8 KHz
2. Use the NEXT and PREV keys to move from one 3. Press <ENTER> to accept the choice. A prompt appears
choice to another. Choices are tone (touchtone), pulse, asking you to confirm the choice.
and tone else pulse (attempt to dial with a touchtone for-
mat and if that fails, use a pulse format). 4. Press <ENTER>. The prompt shown above Step 1 reap-
pears.
3. Press <ENTER> to accept the choice. A prompt appears
asking you to confirm the choice. 5. Press the <NEXT> key. The prompt for the Reporting
Format appears.
4. Press <ENTER>. The prompt shown above Step 1 reap-
pears. Reporting Format
5. Press the <NEXT> key. The prompt for the Pulse Rate Before you select the Communications Format Code, deter-
appears. mine, from an authorized person at the supervising station,
the required reporting format.
Setting Pulse Rate
<ENTER> = Accept
The Pulse Rate option specifies the pulse rate used with
Opt: [Report Format]
either the 3/1 or 4/2 pulse format. This option does not apply
to other formats. 1. Press <ENTER>. The following prompt appears.
<ENTER> = Accept Report Format
Pulse Rate [Contact ID]
1. Press <ENTER>. The DACT can report in any of the following communi-
cation formats.
5-9
Chapter 5. Manually Programming NACs, Relays, and DACT
5. Press the <NEXT> key. The prompt for the AC Fail Programming Contact ID (CID)
Delay appears.
Points
AC Fail Delay Follow the procedure below only if the DACT is using the
The AC Fail Delay allows you to specify the interval Contact ID (CID) reporting format. CID reporting format
between power loss at the panel and when the DACT noti- requires you to specify the group and Contact ID for each
fies the supervising station of the power loss. AC fail delay point, but there is no need to specify the type of event with
is selectable from 0-24 hours. the CID format. This information is automatically derived
from the point’s function type.
AC Fail Delay Note: Default CID point values are provided in the panel. Before
[02] Hrs changing these values, please contact an authorized representative
at the supervising station. Refer to Table 3-4 for information on the
1. Use the NEXT and PREV keys to move from one default CID codes.
choice to another ( 0-24 hours).
1. Follow the steps in “Accessing DACT Menu,” earlier in
2. Press <ENTER> to accept the choice. A prompt appears this chapter. Use the <NEXT> or <PREV> keys to
asking you to confirm the choice. choose CID Points.
3. Press <ENTER>. The prompt shown above Step 1 reap- <ENTER>=Accept
pears. DACT: [CID Points]
4. Press the <NEXT> key. The prompt for the Test Report 2. Press <ENTER>. A prompt similar to the following
Time appears. appears.
[Garage IDC1]
GRP: 01 ID: 001
5-10
Chapter 5. Manually Programming NACs, Relays, and DACT
This prompt consists of the following fields. 6. Press <ENTER>. The prompt shown in Step 1 appears.
• Point Custom Label. The top line of the prompt dis-
plays the custom label assigned to the point. Table 5-5 Event Categories and Codes
• Grp. A 2-digit number used to group associated Event 3/1 BFSK 4/2 SIA
devices together.
Fire Alarm 1 11 A1 FA1
• ID (Contact ID). a 3-digit number used to identify a
Supervisory 3 33 A3 SS3
specific point/device.
Trouble 4 F4 A4 FT4
3. For each point, use the right arrow key to move between
the digits of the GRP and ID fields. Use the <NEXT> Fire Restoral E E1 71 FR1
and <PREV> keys to increment or decrement the value Supervisory E E3 73 SJ3
of a digit. Restoral
4. To choose another point, press the right arrow key until Trouble Restoral E E4 74 FJ4
the cursor is on the top line (custom label) of the
Phone Line 1 F FB 31 LT1
prompt. Use the <NEXT> and <PREV> keys to scroll Trouble
to another point and then repeat Step 3.
Phone Line 1 E EB 35 LR1
5. When all points have been configured, press the Restoral
<ENTER> key. A prompt similar to the following Phone Line 2 F FC 32 LT2
appears, asking you to confirm the changes you made. Trouble
<ENTER>=Confirm Phone Line 2 E EC 36 LR2
GRP: [01] ID:001 Restoral
5. When all points have been configured, press the • Save - saves your edit changes
<ENTER> key. A prompt similar to the following
Note: Both discard and save restart the panel.
appears, asking you to confirm the changes you made.
<ENTER>=Confirm
Code: 1
5-11
Chapter 6. Programming Annunciators
Note: The <Exit/Clear> key is used to back out of menus or displays and return to
the top-level menu structure. Where possible, the <Exit/Clear> key backs out one
level at a time. There are cases, however, that the Exit/Clear key will return the
operator directly to the top-level menu.
6-1
Chapter 6. Programming Annunciators
Adding an Annunciator 4. Press <ENTER>. Use the <NEXT> and <PREV> keys
to scroll through the choices until “Add” is displayed.
Automatically Adding Annunciator Cards
<ENTER>=Accept
Use the Automatic Programming option to automatically Annuns: [Add]
add annunciator modules to the job. (This option will also
detect and add an Expansion Power Supply and City Card, if 5. Press <ENTER>. A prompt appears, asking you to iden-
installed.) tify the specific type of annunciator.
1. Press the <MENU> key. Press <NEXT> or <PREV> <ENTER>=Accept
until the [AutoProgram] option is displayed. Press Add: [LCD]
<ENTER>. The following displays:
6. Use the <NEXT> and <PREV> keys to select one of the
FIRE ALARM following:
SUSPENDED
• Zone Ann
<ENTER> to Program • Remote LED/SW
<EXIT> to resume • LCD
2. Press <ENTER>. The following prompt appears. 7. Press <ENTER>. A prompt appears, asking you to set
the card address for the annunciator. The address you
<ENTER>=Accept specify must match the address set via dip switch on the
AP: [Reconfig All] annunciator. The address must be in the range of 4
through 7. Note: A 4008-9121 uses address 4 for the local
3. Use the <NEXT> key to select [Detect New]. The fol- LED annunciator.
lowing prompt appears.
8. Use the <NEXT> and <PREV> keys to select the
<ENTER> to Continue appropriate address and press ENTER.
*May CHANGE Setting*
9. A prompt appears asking you to confirm the addition of
4. Press <ENTER> to detect and add annunciators to the the annunciator. Pressing <ENTER> will accept any
job. changes made and exit. Use the <EXIT/CLEAR> key to
quit without saving.
Manually Adding an Annunciator Module
Use the following procedure to manually add the annuncia- Accessing Annunciator Menus
tor module to the job.
1. Press the <MENU> key. Press <NEXT> or <PREV>
1. Press the <MENU> key. Press <NEXT> or <PREV> until the [Programming] option is displayed. Press
until the [Programming] option is displayed. Press <ENTER>. The following displays:
<ENTER>. The following displays:
FIRE ALARM
FIRE ALARM SUSPENDED
SUSPENDED
<ENTER> to Program
<ENTER> to Program <EXIT> to resume
<EXIT> to resume
2. Press <ENTER>. The Programming menu appears.
2. Press Enter. The Programming menu appears: [Points] is the default selection, which allows you to
make changes to a specific point’s programming.
<ENTER>=Accept
Prg:[Points] <ENTER>=Accept
Prg:[Points]
3. Use the <NEXT> and <PREV> keys to scroll through
the choices until “Annunc” is displayed. 3. Press <ENTER>. A prompt appears, allowing you to
select the type of point to manually edit. By default,
<ENTER>=Accept [IDC] is the first choice.
Prg: [Annunc]
6-2
Chapter 6. Programming Annunciators
<ENTER>=Accept
Prg:[IDC]
Point 17 Point 9 Point 3
Point 20 Point 10 Point 18
4. Use The <NEXT> and <PREV> keys to scroll to the Point 22 Point 11 Point 19
Point 4 Point 12 Point 1
appropriate choice and then press <ENTER>. Point 5 Point 13 Point 21
Point 6 Point 14 Point 2
• LED. Use this selection for programming the fol- Point 7 Point 15 Point 23
Point 8 Point 16 Point 24
lowing:
- LEDs on 4610-9111 Remote LED/Switch
Annunciator. Figure 6-2 24 LED Panel
- LEDs on Local Zone LED Annunciator (door-
mounted annunciator). Programming Overview
• SWITCH. Use this selection to program switches Programming an LED consists of performing the following
on the 4610-9111 Remote LED/Switch Annuncia- tasks
tor. • Identify which point is being monitored by the LED
• USER SWITCH/LED (Panel LEDs). Use this (called the reference point).
option to program the panel’s three LEDs and the • Identify which point state (fire alarm, trouble, etc.) trig-
LCD Annunciator user LEDs. gers the LED to turn on. This is called the mode.
Programming LEDs Located on See “Programming the LED’s Mode and Reference Point”
later in this chapter.
Zone Annunciator and Remote LED/
Switch Modules For example, you can associate an LED with a smoke detec-
tor point and have the LED turn on only when the point
Use the procedures outlined in this section to program any of enters a trouble state.
the following:
• LEDs on Local Zone Annunciator Default Programming
• LEDs on Remote LED/Switch Module The LEDs on the Local Zone LED and Remote LED/Switch
annunciators have the pre-defined operations listed in Table
Note: The three LEDs on the front of the display are programmed in 6-1 and Table 6-2.
a different manner. Refer to ”Programming Panel LEDs” at the end of
this chapter for information.
In both tables, a default function of FIRE means the LED
Mapping LEDs to Software Points illuminates if a fire alarm condition occurs on the corre-
sponding reference point. A default function of TROUBLE
Figure 6-1 identifies the way in which the software points means the LED illuminates if a trouble condition occurs on
map to the LEDs on the annunciators. For example, to con- the corresponding reference point.
trol the LED in the upper left corner of the Local Zone LED
Annunciator, you need to program Point 17. Table 6-1 Default LED Assignments,
Local Zone LED Module
Default Reference
LED/Color Default Function
Point
6-3
Chapter 6. Programming Annunciators
Table 6-1 Default LED Assignments, Table 6-2 Default LED Assignments, Remote LED/
Local Zone LED Module (Continued) Switch Module (Continued)
6-4
Chapter 6. Programming Annunciators
Type: Photo SMOKE IDNet 1-200 Separate reference point for each IDNet
IDC10 (03-01 to initiating device. State monitored deter-
03-200) mined by selected LED mode.
7. Use the <NEXT> and <PREV> keys to scroll through Aux Relays 1 Separate reference point for each relay.
the list of available reference points. and 2 (14-5 State monitored determined by selected
8. Press <ENTER> when the appropriate reference point is and 14-6) LED mode.
displayed. The prompt shown in Step 4 reappears. City/DACT Separate reference point (18-14) for dis-
9. Press <ENTER>. A prompt appears, asking you to con- Disconnect connect and trouble. Typical use is to
firm the changes. City Trouble monitor the ON state of either point.
6-5
Chapter 6. Programming Annunciators
Table 6-4 Common LED Reference Points 2. Press <ENTER>. A scrollable list of points appears.
(Continued) Use the <NEXT> and <PREV> keys to scroll to the
point you want to edit. The display appears similar to
the following.
Reference
Description User LED 1
Point
Y LED 1/5
List contains all zones with WATER or
WSO function type. Monitoring the Fire 3. Press <ENTER>. Use the <NEXT> and <PREV> keys
List - Water- or Trouble state of this list allows you to to scroll through the options until [FUNCTION] is
flow Zones illuminate an LED when any zone in the shown.
(22-101) list enters an alarm or trouble state. Use
output mode to select which state (Fire, User LED 1
Trouble) is monitored. Fn: [Function]
List contains all zones with SO or WSO
4. Press <ENTER>. A prompt similar to the following
function type. Monitoring the Fire, Trou-
ble, or Supervisory state of this list appears, allowing you to set the LED color.
List - Sprinkler
allows you to illuminate an LED when
Zones User LED 1
any zone in the list enters an alarm,
(22-102) [Y LED]
trouble, or supervisory state. Select
either FIRE, TRBL, or SUPV as the
mode. 5. Use the <NEXT> and <PREV> keys to toggle between
the following LED colors
Separate list for each alarm group. Mon-
• Y - Programs LED as a yellow LED.
itoring the Fire, Supervisory, Trouble, or
Alarm Group ON state of an alarm group list allows • RG - Programs LED as a Red / Green LED. If you
1 -99 (22-1 you to illuminate an LED if any point in assign this type to LED1 (top LED), its color will
through 22-99) the group enters the fire, trouble, super- be red. If you assign this type to the LED2 (middle)
visory, or ON state. Use output mode to or LED3 (bottom), its color will be green.
select state monitored.
6. Press <ENTER> to choose a color. A prompt appears
Separate list for each NAC. Monitoring asking you to press <ENTER> to confirm the choice.
the ON or trouble state of a NAC allows
NACs 1 - 4 For Canadian applications, LED colors must comply with
you to illuminate an LED if the NAC
(14-1 through Table 6-5.
enters trouble state or turns on. Use out-
14-4)
put mode to select state (on or trouble)
monitored.
Table 6-5 ULC LED Color Requirements
Note: Refer to complete system point list in Appendix. Function Color
Alarm Inputs Red
Programming Panel and LCD LEDs Alarm Signal Red with unique identifier
Signal Circuit Fault Yellow
This section describes programming the built-in LEDs on
the front panel and on the LCD annunciator. Programming Inhibit Yellow
involves setting the reference point, mode (the point and Supervisory Inputs Yellow with unique identi-
point state that triggers the LED to illuminate), and the color fier
of the LED. Power - ON Green
Trouble Signal Yellow
Setting LED Color
Alarm Signal Silence Yellow
1. Follow Steps 1 through 4 in “Accessing Annunciator
Menus” earlier in this chapter. Choose User SW/LED Setting LED Mode and Reference Point
as the type of device to program.
An LED’s mode allows you to specify which point is being
<ENTER>=Accept monitored by the LED (called the reference point) and what
Prg: [User SW/LED] point state triggers the LED to turn on.
6-6
Chapter 6. Programming Annunciators
1. Follow Steps 1 through 4 in “Accessing Annunciator • Earth Fault Detect LED. This LED tracks whether the
Menus” earlier in this chapter. Choose User SW/LED panel’s Earth fault system point is active or not. If the
as the type of device to program. point enters a trouble state (i.e., there is an Earth fault),
the yellow LED illuminates. Program the LED as fol-
<ENTER>=Accept lows:
Prg: [User SW/LED]
- Make sure the color is yellow
2. Press <ENTER>. A scrollable list of points appears. - Select the "TRBL" mode
Use the <NEXT> and <PREV> keys to scroll to the - Select 17-06 as the reference point
point you want to edit. The display appears similar to • Waterflow LED, which illuminates if a device with the
the following. function type WATER or WSO activates. Program the
LED as follows:
User LED 1
Y LED 1/5 - Make sure the LED color is red
- Select the "FIRE" mode
3. Press <ENTER>. Use the <NEXT> and <PREV> keys
- Select 22-101 as the reference point
to scroll through the options until [Edit Mode] is shown.
• City/DACT Disconnect (required for Canadian panels).
User LED 1 This LED tracks whether the City/DACT Disconnect
Fn: [Mode] system point is active or not. If the point turns ON (i.e.,
either the city circuit or DACT has been disconnected),
4. Press <ENTER>. The next prompt appears similar to the yellow LED illuminates. Program the LED as fol-
the following: lows:
- Make sure the color is yellow
Mode Prg - LED
[NONE] -- - Select the "ON" mode
- Select 18-14 as the reference point
5. Use the <NEXT> and <PREV> keys to scroll through • Signal Silence Inhibit Enabled. This LED tracks
the available modes. As you scroll through the modes, whether the Signal Silence Inhibit Enabled system point
the default reference address for the mode appears to the is active or not. If the point turns ON (i.e., Signal
right of the mode. Refer to Table 6-3 for a list of the Silence Inhibit system option is set to ON), the yellow
available modes. LED illuminates. Program the LED as follows:
6. When the appropriate mode is selected, use the right - Make sure the color is yellow
arrow key to move the cursor brackets over to the refer- - Select the "ON" mode
ence point. Press the <FUNCTION> key. This changes
the numerical designation of the reference point to a - Select 18-35 as the reference point
text-based description. For example:
Programming LCD Annunciator
Type: BZONE Fire
IDC10
Attributes
The following LCD annunciator attributes can be modified.
7. Use the <NEXT> and <PREV> keys to scroll through
the list of available reference points. • The type of events annunciated at the LCD. You can
choose whether to view Fire, Supervisory, or Trouble
8. Press <ENTER> when the appropriate reference point is events at the annunciator.
displayed. The prompt shown in Step 4 reappears.
• Whether the key-switch must be activated to use the
9. Press <ENTER>. A prompt appears, asking you to con- LCD annunciator’s Acknowledge, Signal Silence, and
firm the changes. System Reset keys.
10. Press <ENTER> to confirm the changes. 1. Press the <MENU> key. Press <NEXT> or <PREV>
until the [Programming] option is displayed. Press
<ENTER>. The following displays:
Common LED Applications
Common applications for programmable LEDs are: FIRE ALARM
SUSPENDED
6-7
Chapter 6. Programming Annunciators
2. Press <ENTER>. The Programming menu appears. 1. Use the <NEXT> and <PREV> keys to toggle between
[Points] is the default selection, which allows you to Yes and No. Press <ENTER> when the correct value
make changes to a specific point’s programming. appears. The next prompt asks whether you want to
annunciate Supervisory Events on the LCD.
<ENTER>=Accept
Prg:[Points] <ENTER>=Accept
Send SUPV Events: [Yes]
3. Press <ENTER>. A prompt appears, allowing you to
select the type of point to manually edit. By default, 2. Use the <NEXT> and <PREV> keys to toggle between
[IDC] is the first choice. Yes and No. Press <ENTER> when the correct value
appears. The next prompt asks whether you want to
<ENTER>=Accept annunciate Trouble Events on the LCD.
Prg:[Cards]
<ENTER>=Accept
4. Press <ENTER>. The display prompts you for the type Send TBL Events: [Yes]
of operation you want to perform.
3. Use the <NEXT> and <PREV> keys to toggle between
<ENTER>=Accept Yes and No. Press <ENTER> when the correct value
Cards:[Add] appears. The next prompt asks whether you want to
annunciate signal silence and system reset messages on
5. Use the <NEXT> and <PREV> keys to scroll through the LCD.
the choices until Modify is shown. Press <ENTER>.
The display prompts you to specify the address of the <ENTER>=Accept
card you want to modify. Send Reset/Silence: [Yes]
Choosing Event Groups to Annunciate 2. Use the <NEXT> and <PREV> keys to toggle between
After selecting <NEXT>, as described in Step 6 of the previ- Yes and No. Press <ENTER> when the correct value
ous section, you are prompted to specify whether you want appears. Press <NEXT> to see the following prompt,
to annunciate Fire events on the LCD. which asks if you want to require the key to use the
Supv Ack key.
6-8
Chapter 6. Programming Annunciators
<ENTER>=Accept
TROUBLE ACK: [Yes]
<ENTER>=Accept
SYSTEM RESET: [Yes]
<ENTER>=Accept
ALARM SILENCE: [Yes]
<ENTER>=Save
Use the right arrow key to move the cursor to one of the fol-
lowing options and press <ENTER>.
6-9
Chapter 7. Manually Programming System
Options
System options are pre-defined modes of operation with a range of set- In This Chapter
tings from which to choose. System Options define global operations
such as the time and date format, door drop timers, and whether the city
circuit is enabled, etc. System options can be set during either the auto- Accessing System Options Menu . . . . . . . . . .7-1
matic (Chapter 3) or manual programming process. Programming Options . . . . . . . . . . . . . . . . . . .7-1
FIRE ALARM
SUSPENDED
<ENTER> to Program
<EXIT> to resume
<ENTER>=Accept
Prg: [OPTIONS]
<ENTER>=Accept
Opt: [Time/Date]
Programming Options
Refer to the appropriate section in the table below for details on each
option. In each case, programming the option involves using the
<NEXT> and <PREV> keys to scroll through the choices and using the
<ENTER> key to set the option to the value you choose.
7-1
Chapter 7. Manually Programming System Options
7-2
Chapter 7. Manually Programming System Options
Option Settings
7-3
Chapter 8. Operating
Abnormal Conditions
Abnormal conditions are indicated on the 4008 by flashing the alarm,
supervisory, or trouble LED and sounding the tone-alert. The tone-alert
pulses for an alarm condition, and is on steady for a trouble or supervi-
sory. If the "Display First Alarm" option is selected, the display pro-
vides information about the first, highest-priority alarm in the system
without operator intervention. If "Display First Alarm" is not selected, a
screen showing the overall system status is shown:
02 | 00 | 00
CORE 1 MEZZANINE
FIRE 1/2
8-1
Chapter 8. Operating
through all the abnormal points in that category. The addi- event and the time the event occurred. The following table
tional information listed below can be obtained by pressing describes the different logs and their stored events.
the <ENTER> key.
Table 8-1 Log Events
• The electrical state of the point (open, short circuit, nor-
mal, abnormal)
Historical
• Enable/Disable state of the point Stored Events
Log
• Manual override state (if output)
Alarms
• Assigned Alarm Groups
ALOG Alarm Acknowledge
Alarm Log Log Cleared
Silencing Alarms 100 Entries Alarm Silence
System Reset
The "Alarm Silence" key allows the operator to silence
active Notification Appliance Circuits that are programmed SLOG Supervisory Conditions
for "on-til-silence" operation. Supervisory Supervisory Acknowledge
Log Log Cleared
100 Entries
Caution: Pressing the Alarm Silence key causes fire alarm
evacuation signals to turn OFF. Follow local procedures to Trouble Events
TLOG
silence alarm evacuation signals. Login/Logout for Level 2 or higher
Trouble Log
Log Cleared
300 Entries
To silence an alarm, press the <ALARM SILENCE> key. WALKTEST Events
• All "on-til-silence" notification appliance circuits will CLOG All Events in Chronological Order
turn OFF Combined Log
• The Alarm Silenced indicator LED will turn on
Viewing Logs
If a subsequent alarm occurs, the notification appliance cir-
cuits resound. 1. Press <MENU>.
2. Press <NEXT> and <PREV> until the following
System Reset prompt appears.
8-2
Chapter 8. Operating
8-3
Chapter 8. Operating
8. Use <NEXT> to select one of the following: The table below shows the operations available in the Func-
• ON. Use this option to turn the relay or NAC on. To tion menu. The Roman numeral shows the access level
return the NAC/Relay to automatic operation, first required for each function.
set it to OFF, and then reselect the point and set it to
AUTO. Table 8-3 Control Functions
• OFF. Turns the relay or NAC off.
Function Description
• AUTO. Use this option to return the NAC or Relay
to automatic operation. Manual Evacu- Activates manual evacuation (general
Note: Manually turning a point on or off will cause a “man- ation II alarm)
ual override” trouble condition on that point until it is
Drill II Activates the drill operation (all notifica-
returned to automatic operation.
tion appliances)
8-4
Chapter 8. Operating
User Key 2 II Programmable User-Selected Function 3. Press <ENTER>. A prompt similar to the following
appears.
Display Time I Shows the current time and date.
<ENTER>=Accept
Send DACT Sends the DACT test event to the sta-
Test I tionary station. Rep: [ALOG]
The Right/Left arrow keys allow you to move the focus from TLOG Displays contents of trouble log.
field-to-field for editing. The <NEXT/PREV> keys allow CLOG Combined alarm, supervisory, and trou-
you to change the currently selected fields. The am/pm field ble logs.
can only be changed by scrolling through the hour values to
change from Morning to Afternoon. CONFIG Text description - including custom label,
function type
8-5
Chapter 8. Operating
8-6
Chapter 8. Operating
If the panel senses the trouble condition correctly, one 3. Press <ENTER>. A prompt similar to the following
of two things happen: appears.
- If the WalkTest signaling option is set to SIG, the
<ENTER>=Accept
panel activates the panel’s NACs for four seconds.
XFER: [Start XFER]
- If the WalkTest logging option is set to LG, the
panel logs the alarm activation to the TLOG. Use Restarting the CPU
the History Logs menu option to view the TLOG.
This option is used to clear an Access Level 4 Trouble (i.e., a
Use the Reports menu option to print a copy of the
“Service Mode Trouble”).
TLOG.
• Earth Ground Sensing. To test the panel’s ability to 1. Press <MENU>.
detect an Earth Ground, short one of the panel’s circuits 2. Press <NEXT> and <PREV> and choose one of the fol-
to Earth. If the panel senses the trouble condition cor- lowing options.
rectly, one of two things happen:
• Warm. Clears the Access Level 4 trouble, restarts
- If the WalkTest signaling option is set to SIG, the the panel, but preserves the panel’s non-volatile
panel activates the panel’s NACs for four seconds. memory, including time/date information, historical
- If the WalkTest logging option is set to LG, the logs, and all currently disabled points
panel logs the alarm activation to the TLOG. Use • Cold. Clears the Access Level 4 trouble and re-ini-
the History Logs menu option to view the TLOG. tializes the panel’s non-volatile memory, clearing
Use the Reports menu option to print a copy of the all time/date information, historical logs, and dis-
TLOG. abled points.
• NAC Trouble Sensing. To test the panel’s ability to
3. Choose an option and press <ENTER>. System startup
sense a trouble condition for each NAC, disconnect one
prompts appear on the screen, followed by the system
of the NAC wires at the panel. If the panel senses the
status message.
trouble condition correctly, one of two things happen:
- If the WalkTest signaling option is set to SIG, the Viewing Software Revision Number and Job Info
panel activates the panel’s NACs for four seconds.
1. Press <MENU>.
- If the WalkTest logging option is set to LG, the
panel logs the alarm activation to the TLOG. Use 2. Press <NEXT> or <PREV> until Software Rev is
the History Logs menu option to view the TLOG. shown. Press <ENTER>. A message similar to the fol-
Use the Reports menu option to print a copy of the lowing appears, displaying the revision level of the
TLOG. panel’s software.
Rev 1.02.01
Advanced Operations <NEXT> = View Job Info
Upload/Download 3. Press <NEXT> to see the job revision number (i.e., the
Uploading and downloading files allows you to transfer the number of times the job has been edited and saved), and
panel’s job file between a service PC and the panel. The term the date on which the panel was edited.
Uploading refers to transferring a job file from the panel to a
JOB REV:1 4008JOB
PC; whereas, the term Downloading refers to moving a job
12:00:00 am 04/09/04
file from the PC to the panel.
8-7
Appendix A. Battery Standby Calculations
Note: Auxiliary power from the system’s AUX 24 V taps must also be included in the calculation, unless that power is
switched off during battery standby. For example, door holders operated from 24 V need not be included if they are discon-
nected via a relay during a battery standby condition. Notification Appliance load must be included in the alarm current total.
1. Identify Standby Time (C), in hours. C = ______ (typically 4, 24, 48, or 60 hr)
2. From previous calculations, locate total Standby Current (A) and total Alarm Current (B) in amperes.
A= ______ B = ______
4. Using the values in Steps 1-4, perform an Initial Battery Calculation per the following:
(A x C) + (0.0167 x B x D) = _______ Ah (Ah = ampere hours)
5. Select a battery size LARGER than the number from the Initial Battery Calculation from the following list of batteries
using the 20 Hour Rating value:
A-1
Table A-2: Battery Size
20 Hour Rating C/20 (Amps) 20 Hour Rating C/20 (Amps)
6. If either the Standby Current or the Alarm Current is greater than the C/20 current for the initial battery size selected, a
Discharge Factor (DF) must be applied. For example, 1 A load on a 10 Ah battery requires a Discharge Factor of 1.08 (10
Ah / 1 A gives discharge time of 10 hours; DF = 1.08). Use the following table to determine Discharge Factor (use the 20
hr value for 24 hr standby):
7. Standby Discharge Factor (SDF) = _________ Alarm Discharge Factor (ADF) = _________
8. Minimum Required Battery Capacity Calculation. (to account for battery aging, a 1.17 multiplier is included)
9. If the battery size initially selected is smaller than the result of step 9 above, repeat the calculations using a larger battery
size.
A-2
Appendix B. Contact ID Default Values
*Any other trouble not specifically mentioned would have a code of 330.
For example, a trouble on an output device would report an event code of 330.
B-1
Table B-1: Contact ID Default Values (Continued)
*Any other trouble not specifically mentioned would have a code of 330.
For example, a trouble on an output device would report an event code of 330.
B-2
Appendix C. System Points
Point ID Description
17-01 AC Fail
17-06 Earth
C-1
Table C-1: System Points (Continued)
Point ID Description
18-06 Drill
C-2
Table C-1: System Points (Continued)
Point ID Description
C-3
Appendix D. Compatible Cooper Wheelock
Appliances
This appendix lists the Cooper Wheelock Appliances that are compatible with 4008 Wheelock Protocol for special applica-
tions.
D-1
Table D-2: Synchronizing Strobes
Synchronizing Strobes
RSS-241575W RSS Series Strobe. 24V, 15/75 Cd, Wall Mount
RSSP-241575W RSSP Series Strobe. 12V or 24V, 15/75 Cd, Wall Mount
RSS-24MCW, RSSP-24MCW RSS/RSSP Series Strobe. 24V, Multi-Cd, Wall Mount
RSS-24MCWH, RSSP-24MCWH RSS/RSSP Series Strobe. 24V, Multi-High-Cd, Wall Mount
RSS-24MCC, RSS-24MCCR RSS Series Strobe. 24V, Multi-Cd, Ceiling Mount. (R=Round)
RSS-24MCCH, RSS-24MCCHR RSS Series Strobe. 24V, Multi-High-Cd, Ceiling Mount. (R=Round)
RSSR-2415W, RSSR-2415C RSS Series Strobe. 24V, 15 Cd, Red, Wall or Ceiling Mount
RSSR-2475W, RSSR-2475C RSS Series Strobe. 24V, 75 Cd, Red, Wall or Ceiling Mount
RSSR-24110C RSS Series Strobe. 24V, 110 Cd, Red, Ceiling Mount
RSSA-24110W, RSSB-24110W RSS Series Strobe. 24V, 110 Cd, Wall Mount. Amber/Blue/Green/Red
RSSG-24110W, RSSR-24110W
RSSA-24MCC, RSSB-24MCC RSS Series Strobe. 24V, Multi-Cd, Ceiling Mount. Amber/Blue/Green/Red
RSSG-24MCC, RSSR-24MCC
RSSA-24MCCH, RSSB-24MCCH RSS Series Strobe. 24V, Multi-High-Cd, Ceiling Mount. Amber/Blue/Green/Red
RSSG-24MCCH, RSSR-24MCCH
RSSPA-24MCC RSSP Series Strobe. 24V, Multi-Cd, Ceiling Mount. Amber
RSSWPA-2475W RSS Series WP Strobe. 24V, Wall Mount. Amber
RSSWPA-24MCCH, RSS Series WP Strobe. 24V, Multi-High-Cd, Ceiling Mount. Amber/Blue/Green/
RSSWPB-24MCCH, Red
RSSWPG-24MCCH,
RSSWPR-24MCCH
RSSWP-2475W, RSSWP-2475C RSS Series WP Strobe. 24V, 30 Cd, Wall or Ceiling Mount
RSSWP-24MCWH RSS Series WP Strobe. 24V, Multi-High-Cd, Wall Mount
RSSWP-24MCCH RSS Series WP Strobe. 24V, Multi-High-Cd, Ceiling Mount
STR STR, red, 2-wire, wall, 12/24V, 8CD, 5 mount
STW STR, white, 2-wire, wall, 12/24V, 8CD, 5 mount
STRS STR, silver red, 2-wire, wall, 12/24V, 8CD, 5 mount
STWS STR, silver white, 2-wire, wall, 12/24V, 8CD, 5 mount
STRC STR, red, 2-wire, ceiling mount, 12/24V, 8CD, 5 mount
STWC STR, white, 2-wire, ceiling mount, 12/24V, 8CD, 5 mount
STRCS STR, silver red, 2-wire, ceiling mount, 12/24V, 8CD, 5 mount
STWCS STR, silver white, 2-wire, ceiling mount, 12/24V, 8CD, 5 mount
ZRS-MCW ZRS Series Strobe. 24V, Multi-Cd, Wall Mount
ZRS-MCWH ZRS Series Strobe. 24V, Multi-High-Cd, Wall Mount
ZRS-24MCC ZRS Series Strobe. 24V, Multi-Cd, Ceiling Mount
ZRS-24MCCH ZRS Series Strobe. 24V, Multi-High-Cd, Ceiling Mount
D-2
Table D-3: Appliances with Synchronizing Strobes
(Only Strobe portion compatible with 4008 Wheelock Protocol for Special Applications)
Device Description
AMT-241575W, AMT-241575W-NYC AMT Series Multi-Tone Horn Strobe. 24V, 15/75 Cd, Wall Mount
AMT-24MCW AMT Series Multi-Tone Horn Strobe. 24V, Multi-Cd, Wall Mount
MT-241575W MT Series MT Horn Strobe. 24V, 15/75 Cd, Wall Mount
MT-24MCW MT Series Multi-Tone Horn Strobe. 24V, Multi-Cd, Wall Mount
MTWP-2475W, MTWP-2475C MTWP Series MT Horn Strobe. 24V, 30 Cd, Wall or Ceiling Mount
MTWP-24MCWH MTWP Series MT Horn Strobe. 24V, Multi-High-Cd, Wall Mount
MTWP-24MCCH MTWP Series MT Horn Strobe. 24V, Multi-High-Cd, Ceiling Mount
MTWPA-2475W, MTWPB-2475W, MTWP Series Multi-Tone Horn Strobe. 24V, Wall Mount.
MTWPG-2475W, MTWPR-2475W Amber/Blue/Green/Red
MTA-24MCCH, MTB-24MCCH, MT Series Multi-Tone Horn Strobe. 24V, Multi-High-Cd, Wall Mount.
MTG-24MCCH, MTR-24MCCH Amber/Blue/Green/Red
MTWPA-24MCCH, MTWPB-24MCCH, MTWP Series Multi-Tone Horn Strobe. 24V, Multi-High-Cd, Wall Mount.
MTWPG-24MCCH, MTWPR-24MCCH Amber/Blue/Green/Red
ET70WP-2475W, ET70WP-2475C ET70WP Series Speaker Strobe. 24V, 30 Cd, Wall or Ceiling Mount
ET70WP-24185W ET70WP Series Speaker Strobe. 24V, 185 Cd, Wall Mount
ET70WP-24177C ET70WP Series Speaker Strobe. 24V, 177 Cd, Ceiling Mount
ET70WPA-2475 ET70WP Series Speaker Strobe. 24V, Wall or Ceiling Mt. Amber
CH70-241575W CH70 Series Chime Strobe. 24V, 15/75 Cd, Wall Mount
CH70-24MCW CH70 Series Chime Strobe. 24V, Multi-Cd, Wall Mount
CH90-24MCC CH90 Series Chime Strobe. 24V, Multi-Cd, Ceiling Mount
CH70-24MCWH CH70 Series Chime Strobe. 24V, Multi-High-Cd, Wall Mount
CH90-24MCCH CH90 Series Chime Strobe. 24V, Multi-High-Cd, Ceiling Mount
E50-241575W E50 Series Speaker Strobe. 24V, 15/75 Cd, Wall Mount
E50-24MCW E50 Series Speaker Strobe. 24V, Multi-Cd, Wall Mount
E50-24MCWH E50 Series Speaker Strobe. 24V, Multi-High-Cd, Wall Mount
E50A-24MCC, E50B-24MCC E50 Series Speaker Strobe. 24V, Multi-Cd, Ceiling Mt. Amber/Blue
E60-24MCW E60 Series Speaker Strobe. 24V, Multi-Cd, Wall Mount
E60-24MCWH E60 Series Speaker Strobe. 24V, Multi-High-Cd, Wall Mount
E60-24MCC E60 Series Speaker Strobe. 24V, Multi-Cd, Ceiling Mount
E60-24MCCH E60 Series Speaker Strobe. 24V, Multi-High-Cd, Ceiling Mount
E70-241575W E70 Series Speaker Strobe. 24V, 15/75 Cd, Wall Mount
E70-24MCW E70 Series Speaker Strobe. 24V, Multi-Cd, Wall Mount
E70-24MCWH E70 Series Speaker Strobe. 24V, Multi-High-Cd, Wall Mount
E70-24MCC, E90-24MCC E70/E90 Series Speaker Strobe. 24V, Multi-Cd, Ceiling Mount
E90-24MCCH E90 Series Speaker Strobe. 24V, Multi-High-Cd, Ceiling Mount
E60A-24MCC, E70A-24MCC, E60/E70/E90 Series Speaker Strobe. 24V, Multi-Cd, Ceiling Mount.
E70B-24MCC, E90A-24MCC, Amber/Blue
E90B-24MCC
ET70-241575W, ET90-241575W ET70/E90 Series Speaker Strobe. 24V, 15/75 Cd, Wall Mount
D-3
Table D-3: Appliances with Synchronizing Strobes
(Only Strobe portion compatible with 4008 Wheelock Protocol for Special Applications) (Continued)
Device Description
ET70-24MCW ET70 Series Speaker Strobe. 24V, Multi-Cd, Wall Mount
ET70-24MCWH ET70 Series Speaker Strobe. 24V, Multi-High-Cd, Wall Mount
ET70-24MCC, ET90-24MCC ET70/ET90 Series Speaker Strobe. 24V, Multi-Cd, Ceiling Mount
ET70WPG-2475, ET70WPB-2475W, ET70WP Series Speaker Strobe. 24V, Wall or Ceiling Mt.
ET70WPG-2475W, ET70WPR-2475W Green/Blue/Red
ET90-24MCCH ET90 Series Speaker Strobe. 24V, Multi-High-Cd, Ceiling Mount
ET80-241575W ET80 Series Speaker Strobe. 24V, 15/75 Cd, Wall Mount
ET80-24MCW ET80 Series Speaker Strobe. 24V, Multi-Cd, Wall Mount
ET80-24MCWH ET80 Series Speaker Strobe. 24V, Multi-High-Cd, Wall Mount
S8-24MCC S8 Series Speaker Strobe. 24V, Multi-Cd, Ceiling Mount
S8-24MCCH S8 Series Speaker Strobe. 24V, Multi-High-Cd, Ceiling Mount
SA-S70-24MCW SA-S70 Series Amp-Speaker Strobe. 24V, Multi-Cd, Wall Mount
SA-S90-24MCC SA-S90 Series Amp-Speaker Strobe. 24V, Multi-Cd, Ceiling Mount
Device Description
AH-24 AH Series Horn. 24V
AH-24WP AH Series Weatherproof Horn. 12V or 24V
HNR Horn, red, 2-wire, wall, 12/24V, 3dB, 5 mount
HNW Horn, white, 2-wire, wall, 12/24V, 8CD, 5 mount
HNRS Horn, silver red, 2-wire, wall, 12/24V, 8CD, 5 mount
HNWS Horn, silver white, 2-wire, wall, 12/24V, 8CD, 5 mount
HNRC Horn, red, 2-wire, ceiling mount, 12/24V, 3dB, 5 mount
HNWC Horn, white, 2-wire, ceiling mount, 12/24V, 3dB, 5
mount
HNRCS Horn, silver red, 2-wire, ceiling mount, 12/24V, 3dB, 5
mount
HNWCS Horn, silver white, 2-wire, ceiling mount, 12/24V, 3dB,
5 mount
HS-24 HS Series Horn. 24V
MIZ-24S MIZ Series Horn. 24V
NH-12/24, NH-12/24R NH Series Horn. 12/24V (R=Round)
ZNH ZNH Series Horn. 12/24V
D-4
Table D-5: Coded Audible Appliances
Devices Description
AMT-12/24, AMT-12/24-NYC AMT Series multi-tone horn, 12/24V, wall or ceiling mount
Devices Description
D-5
579-716
Rev. W
© 2004-2016 Tyco Fire Protection Products. All rights reserved. Specifications and other information shown were current as of publication and are subject to change without notice. TYCO,
SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited.