You are on page 1of 82

FIRE ALARM

4008-9101/4008-9121
Fire Alarm Control Panel

Installation,
Programming,
and Operating
Instructions

579-716
Rev A
Copyright and Trademarks
© 2004 Tyco Safety Products Westminster, Westminster, MA 01441-0001 USA

Printed in the United States of America.

Information in this document is subject to change without notice. No part of this document may be reproduced or transmitted
in any form or by any means, electronic or mechanical, for any purpose, without the express written consent of Tyco Safety
Producs.

Tyco, Simplex, the Simplex logo, IDNet, SmartSync and WALKTEST are registered trademarks of Tyco International Ser-
vices AG or its affiliates in the US and/or other countries.

TrueAlarm analog smoke detection is protected by one or more of the following U.S. Patents: 5,155,468; 5,173,683;
5,543,777. IDNet addressable communications are protected by U.S. Patent No. 4,796,025. IDNet duplicate device detection
is protected under U.S. Patent No. 6,034,601. WALKTEST system test is protected under US Patent No. 4,725,818. Smart-
Sync horn/strobe operation is protected under U.S. Patent No. 6,281,789. Two wire synchronization circuit operation is pro-
tected by U.S. patent No. 5,559,492.
FCC Information
This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the door of this equip-
ment is a label that contains, among other information, the following product identifier: US:5QWAL01B4008. If requested,
the number must be provided to the telephone company.

In the event of equipment malfunction, all repairs should be performed by an authorized agent. It is the responsibility of users
requiring service to report the need for service to our company or to one of our authorized agents. Service can be arranged
through our office at:

Tyco Safety Products


91 Technology Drive
Westminster, MA 01473
978-731-2500

The Ringer Equivalence Number (REN), which is 01 for the DACT installed in this panel, is used to determine the number of
devices that may be connected to a telephone line. Excessive RENs on a telephone line may result in the devices not ringing in
response to an incoming call. In most, but not all areas, the sum of RENs should not exceed five (5.0). To be certain of the
number of devices that may be connected to a line, as determined by the total number of RENs, contact the local telephone
company. For products approved after July 23, 2001, the REN is part of the product identifier, which uses the format
US:AAAEQ##TXXXX. The digits represented by ## are the REN without a decimal point (e.g. 01 is a REN of 0.1).

If the DACT causes harm to the telephone network, the telephone company will notify you in advance that temporary discon-
tinuance of service may be required. But if advance notice isn’t practical, the telephone company will notify you as soon as
possible. If your service is discontinued, you will be advised of your right to file a complaint with the FCC.

The telephone company may make changes to its facilities, equipment, operations, or procedures that could affect the opera-
tion of the equipment. If this happens the telephone company will provide advance notice in order for you to make the neces-
sary modifications to maintain uninterrupted service.

If trouble is experienced with the DACT, please contact Tyco Safety Products at the location identified above. If the equipment
is causing harm to the telephone network, the telephone company may request that you disconnect the equipment until the
problem is resolved.

Alarm Dialing Equipment


This equipment must be able to seize the telephone line and place a call in an emergency situation. It must be able to do this
even if other equipment (telephone, answering system, computer modem, etc.) already has the telephone line in use. To do so,
the DACT must be electrically in series with and ahead of all other equipment attached to the same telephone line. Proper
installation is depicted in the figure below. If you have any questions concerning these instructions you should consult your
telephone company or a qualified installer about connecting the alarm dialing equipment for you.
DACT Computer

Network
Service Unused
Provider's RJ-11 Jack
Facilities

Telephone
Line

Telephone

Network
Demarcation Unused
Point Telephone
Fax RJ-11 Jack

Answering
System

Telephone

Connectors for the DACT are terminal blocks on the DACT module. Refer to DACT Wiring in Chapter 2 of this manual for
specific DACT wiring instructions.
Cautions and Warnings
READ AND SAVE THESE INSTRUCTIONS. Follow the instructions in this installation manual. These instructions must be
followed to avoid damage to this product and associated equipment. Product operation and reliability depends upon proper
installation.

DO NOT INSTALL ANY PRODUCT THAT APPEARS DAMAGED. Upon unpacking your product, inspect the contents of
the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier.

ELECTRICAL HAZARD - Disconnect electrical field power when making any internal adjustments or repairs. Servicing
should be performed by qualified Simplex Technical Representatives.

STATIC HAZARD - Static electricity can damage components. Therefore, handle as follows:

• Ground yourself before opening or installing components.


• Prior to installation, keep components wrapped in anti-static material at all times.

RADIO FREQUENCY ENERGY - This equipment generates, uses, and can radiate radio frequency energy and if not installed
and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and
found to comply with the limits for a Class A computing device pursuant to Subpart J of Part 15 of FCC Rules, which are
designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of
this equipment in a residential area may cause interference in which case the user at his own expense will be required to take
whatever measures may be required to correct the interference.

SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES - To ensure proper system operation, this product must
be tested in accordance with NFPA72-2002 after any programming operation or change in site-specific software. Reaccep-
tance testing is required after any change, addition or deletion of system components, or after any modification, repair or
adjustment to system hardware or wiring.

All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In
addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly
affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
Table of Contents

Copyright and Trademarks .................................................................................................................1-ii


FCC Information.................................................................................................................................1-iii
Cautions and Warnings...................................................................................................................... 1-v

Chapter 1. Overview ................................................................................................... 1-1


Optional Modules ............................................................................................................................... 1-2
Initiating Devices ................................................................................................................................ 1-3
Programming Overview ..................................................................................................................... 1-4
User Interface .................................................................................................................................... 1-5
Logging In and Out ............................................................................................................................ 1-6
Back Box Mounting ............................................................................................................................ 2-1

Chapter 2. Installation/System Checkout ................................................................. 2-1


General Wiring Guidelines ................................................................................................................. 2-2
IDNet Wiring....................................................................................................................................... 2-3
Class A/Class B NAC Wiring ............................................................................................................. 2-5
Remote Annunciator Comm Wiring ................................................................................................... 2-8
Digital Alarm Communicating Transmitter (DACT) Wiring ................................................................. 2-9
Auxiliary 24V Power Wiring.............................................................................................................. 2-11
City Connect Module Wiring ............................................................................................................ 2-12
Auxiliary Relay Wiring ...................................................................................................................... 2-13
AC Supply Wiring ............................................................................................................................. 2-14
Battery Wiring .................................................................................................................................. 2-15
Depleted Battery Cutout................................................................................................................... 2-16
Safety Ground/Ferrite Bead ............................................................................................................. 2-16
Replacing Lithium Battery ................................................................................................................ 2-17
Periodic Testing and Maintenance................................................................................................... 2-17
Configure ALL .................................................................................................................................... 3-1

Chapter 3. Auto-Programming .................................................................................. 3-1


Detect New Hardware ........................................................................................................................ 3-2
Restore Factory Defaults ................................................................................................................... 3-2
Edit System Options .......................................................................................................................... 3-2
Restore Default System Options........................................................................................................ 3-3
Saving the Configuration.................................................................................................................... 3-3
Default Programming Assignments ................................................................................................... 3-3

Chapter 4. Manually Programming


IDNet Points ................................................................................................................ 4-1
Accessing IDNet Programming Menus .............................................................................................. 4-2
Adding an IDNet Device..................................................................................................................... 4-2
Editing IDNet Device Attributes.......................................................................................................... 4-2
Deleting an IDNet Point ..................................................................................................................... 4-8

Chapter 5. Manually Programming NACs, Relays, and DACT................................ 5-1


Accessing Menus ............................................................................................................................... 5-2
Programming NACs ........................................................................................................................... 5-2
Programming AUX Relays ................................................................................................................. 5-4
Programming DACT........................................................................................................................... 5-6
Accessing DACT Menu ...................................................................................................................... 5-6
Programming DACT Options ............................................................................................................. 5-7
Programming Contact ID (CID) Points ............................................................................................... 5-9
Programming Event Codes .............................................................................................................. 5-10
Saving Changes............................................................................................................................... 5-11
Chapter 6. Manually Programming
Annunciators .............................................................................................................. 6-1
Adding an Annunciator ...................................................................................................................... 6-2
Accessing Annunciator Menus........................................................................................................... 6-2
Programming LEDs Located on Zone Annunciator and Remote LED/Switch Modules..................... 6-3
Programming Panel and LCD LEDs .................................................................................................. 6-6
Common LED Applications ................................................................................................................ 6-7
Programming LCD Annunciator Attributes......................................................................................... 6-7
Saving Changes to the Job................................................................................................................ 6-9
Accessing System Options Menu ...................................................................................................... 7-1
Programming Options ........................................................................................................................ 7-1

Chapter 7. Manually Programming System Options............................................... 7-1


Normal Operation............................................................................................................................... 8-1
LAMP Test ......................................................................................................................................... 8-1
Abnormal Conditions.......................................................................................................................... 8-1

Chapter 8. Operating .................................................................................................. 8-1


Silencing Alarms ................................................................................................................................ 8-2
System Reset .................................................................................................................................... 8-2
Historical Logs ................................................................................................................................... 8-2
Viewing and Controlling Points .......................................................................................................... 8-3
Manually Activating a NAC/Relay ...................................................................................................... 8-4
Enabling or Disabling Points .............................................................................................................. 8-4
Control Functions............................................................................................................................... 8-4
Setting the Time and Date ................................................................................................................. 8-5
Reports .............................................................................................................................................. 8-5
Diagnostics ........................................................................................................................................ 8-5
WalkTest ............................................................................................................................................ 8-6
Advanced Operations ........................................................................................................................ 8-7
Appendix A. Current Draw for System Components ............................................ A-1
Chapter 1. Overview

The 4008-9101 and 4008-9121 (includes door mounted annunciator) are In This Chapter
addressable fire alarm control panels capable of monitoring and control-
ling up to 200 initiating devices on an addressable communications cir-
cuit (IDNet). The single-board system and cabinet provide a complete Optional Modules . . . . . . . . . . . . . . . . . . . . . . .1-2
fire alarm for most applications. Initiating Devices . . . . . . . . . . . . . . . . . . . . . . .1-3
Programming Overview . . . . . . . . . . . . . . . . . .1-4
In cases where the installation, wiring, or programming procedure is
identical for both panels, the term 4008 is used. If the procedure applies
only to a specific panel, the complete product name (i.e., 4008-9121 is
used).

The 4008 provides audible and visible indications during alarm, super-
visory, or trouble conditions. Should any of these conditions occur, the
system activates the applicable notification appliances, LEDs, and the
panel’s tone-alert. The indications continue until an operator acknowl-
edges the condition.

The 4008 base system includes the Main System Board (MSB) mounted
in a steel enclosure with locking door. The MSB consists of:
• System power supply (24V filtered @ 3A)
• IDNet loop
• Two, 2A Notification Appliance Circuits (Style Y or Z)
• Two Auxiliary Relay circuits
• One Auxiliary Power tap
• 2 x 20 backlit LCD, LEDs and keypad
• Expansion power supply / NAC connection
• Service port
• DACT

The following optional modules mount to the chassis, providing addi-


tional capability.
• Additional NACs and signal power are supplied with an optional
expansion power supply.
• Auxiliary relay module with three sets of user-programmable con-
tacts.
• Zone LED Annunciator displays alarm & trouble status for each
logical zone.
• City Connect Module.
• Remote LED annunciators are available. These modules interface
to the system via a serial communication link. They mount in sepa-
rate enclosures, up to 4000 feet from the control panel.

1-1
Chapter 1. Overview

9805 provides disconnect switches for each circuit. Model


4006-9805 must be used for Canadian applications. The City
Specification
Circuit must be enabled via the panel’s System Options
120 VAC, 60 Hz, 4A; before use.
240 VAC, 50 Hz, 3A
AUX RELAY MODULE (4008-9802)
24 VDC, 3A alarm power
The auxiliary relay module includes three relays, one each
Power Supply 24 VDC, ½A auxiliary power
Battery charger for 12.7 Ah batteries, for system alarm, supervisory and trouble conditions. LEDs
recharge per ULC-S527 & UL 864. The indicate active relay circuits. Normally Open or Normally
4008 back box can accommodate up to Closed contact operation is selected by shunt jumper place-
12.7 Ah batteries ment. Contacts are rated for 2A, 30VDC, 0.35 power factor.
Either an auxiliary relay module or a City Circuit Card may
The 4008 operates normally with ambi-
be added to the system. Addressable relay modules are avail-
ent temperatures from 32° F to 120° F
(0° C to 49° C), inclusive. able, connecting to the system through IDNet.
Environmental
The 4008 operates normally under non- ANNUNCIATOR MODULES
condensing humidity conditions up to The 4008 supports a variety of annunciator modules. A total
93% relative humidity at 90° F (32° C).
of four annunciators may be added to the system, one of
which can be located in the panel (door-mounted LED
Optional Modules annunciator).
• Door-Mounted LED Annunciator. The Local Zone
The following is a list of optional modules for the 4008. LED Module provides 24 LEDs for visible zone alarm
Refer to the individual instructions that accompany each and trouble indication. This module is standard for
module for more information. Refer to the label inside the ULC-S527 compliant systems (Canada). There are 10
door of the 4008 for the placement of optional modules. Red and 14 Yellow LEDs. This provides a red alarm and
yellow trouble LED for up to 10 groups of devices. This
Note: One AUX relay module or city circuit card is module also provides 4 Yellow LEDs, one for each of 4
allowed. NACs. The LEDs are programmable, and can be used
for other functions as appropriate per application.
EXPANSION POWER SUPPLY (4008-9801)
When additional notification appliance circuits are required,
an expansion power supply may be added. The expansion
Zone 1 Z one 5 Z one 9
power supply provides two additional 2A NACs, and fil-
tered/regulated 24 VDC, 3A power. The expansion power Zone 2 Z one 6 Zone 10
supply is mounted to the right of the MSB at the bottom of
the chassis. It connects to the MSB with a ribbon harness. Zone 3 Z one 7
NAC 1

NAC 2

NAC 3
The NACs on the EPS may be configured as AUX 24V Zone 4 Z one 8
NAC 4
power taps. One EPS per system is allowed. The EPS must
be enabled via the panel’s System Options before use.
Figure 1-1 Zone LED Annunciator Module
CITY CIRCUIT CARDS (4006-9805, 4006-9806)
The city circuit card connects to the MSB with a ribbon har- • Remote LED/Switch Module (4610-9111). This
ness to provide connections to either Remote Station module provides the following:
(reverse polarity), or Public Service Fire Communications - 10 programmable red LEDs (default programming
Center (local energy) receiving units. The card has two cir- tracks alarm state of Alarm Groups 1-10)
cuits - circuit 1 reports alarm or alarm/trouble events
- 6 programmable yellow LEDs (no default opera-
(Remote Station only) and circuit 2 can be configured to
tion)
report trouble events or supervisory events. In the event of a
CPU failure, a city card configured for a trouble output - Green “power on” LED
sends a trouble to the city circuit. The card is mounted to the - Yellow “Alarm Silenced” LED
right of the MSB at the top of the chassis. The 4006-9805 - Yellow “Trouble”
and 4008-9806 city cards are identical except that the 4006-

1-2
Chapter 1. Overview

- Yellow “Comm Loss” LED DETECTOR MODULES


- Tone-Alert • Photoelectric Detector (4098-9714, 4098-9714C)
- Switches for ACK, Alarm Silence, System Reset, is an addressable photoelectric smoke detector that pro-
and Lamp Test vides smoke detection by means of optical sense tech-
- Key switch to enable switch functions nology. The detector sends a unique identifier to the
control panel so that it may be easily auto-programmed
and verified during normal operation. The sensitivity of
the detector is 2.5%/ft. obscuration.
Fire Alarm Annunciator
ZONE 1 Z ONE 9 Alarm
• Heat Detector (4098-9733, 4098-9733C) is an
Alarm S ilenced
ZONE 2

Z ONE 3
ZONE 10 S ilence

Comm Los t
addressable heat detector. It has a fixed sensitivity of
ACK
Z ONE 4

ZONE 5
T rouble
CONTROL
ENABLE
135°F, and may also be programmed for 15°F/minute
R eset
Z ONE 6

ZONE 7
L amp Power
rate-of-rise operation. The detector sends a unique iden-
Z ONE 8 T est

tifier to the control panel so that it may be easily auto-


programmed and verified during normal operation.
• Combination Photo/Heat Detector (4098-9754,
Figure 1-2 Remote LED/Switch Annunciator 4098-9754C) is a combination photoelectric detector
Module and thermal detector in one head. It has the same char-
acteristics as the photo and heat detectors described
• LCD Annunciator. The 4606-9101 Remote LCD above. This device consumes two addresses - one for
Annunciator provides remote annunciation of the Fire the photo and one for the heat. The detector sends
Alarm Control Panel (FACP) status. Visual status is pro- unique identifiers to the control panel so that it may be
vided by a liquid crystal display and LEDs. Audible easily auto-programmed and verified during normal
annunciation is provided through a piezo sounder. operation.
Access to the functions of the annunciator can be lim-
ited through the use of the annunciator’s keyswitch. • Duct Detectors. The panel is compatible with any of
the following duct detectors:
For Canadian applications, the LCD annunciator is only - Two-wire detector without relay (4098-9755)
suitable for supplementary applications.
- Two-wire detector without relay, Canadian (4098-
4009-9201 and 4009-9202CA (Canadian) NAC 9755C)
Extender - Four-wire detector with relay (4098-9756)
The 4009-9201/4009-9202CA Notification Appliance Cir- - Four-wire detector with relay, Canadian (4098-
cuit (NAC) Extenders are self-contained adjunct panels. 9756C)
• Detector Bases. The detectors described above may
The base version of the NAC Extender is a single-board sys- be installed in the following detector bases:
tem consisting of four NACs, a power supply and charger,
- Detector Base w/o Remote Led Connection (4098-
and two conventional NAC inputs that connect to the host
9792)
panel for hardwired control of the NAC extender.
- Detector Base w/o Remote Led Connection, Cana-
Option cards are available to provide the following addi- dian, (4098-9792C)
tional capabilities: - Detector Base w/Remote Led Connection (4098-
9789)
• 4009-9808 Class A Adapter Option Card -- allows fault
tolerance in the case of open circuit wiring faults on the - Detector Base w/Remote Led Connection, Cana-
NACs. dian (4098-9789C)
- Detector Base w/Relay Drive (4098-9791)
• 4009-9807 NAC Option Card -- adds four conventional
Notification Appliance Circuits. - Detector Base w/Relay Drive, Canadian (4098-
9791C)
- Isolator Base (4098-9793)
Initiating Devices
- Isolator Base, Canadian (4098-9793C)
The 4008 is compatible with the following addressable initi- - Sounder Base (4098-9794)
ating devices. Up to 200 devices (any combination) are
allowed in the system. - Sounder Base, Canadian (4098-9794C)
- Multi Detector Sounder Base (4098-9795)

1-3
Chapter 1. Overview

- Multi Detector Sounder Base, Canadian (4098- It is recommended that you use the automatic program-
9795C) ming option to perform the following tasks.
- Multi Detector Base w/LED (4098-9796) - Initial programming. After all option cards are
- Multi Detector Base w/LED, Canadian (4098- installed and all devices are addressed and wired,
9796C) use the auto programming feature to add the cards
and devices to the job. After automatic program-
MONITOR MODULES ming the panel will function as a general alarm
panel, assuming all devices are wired correctly. At
• The 4090-9001 Supervised Monitor is a contact closure
that point, you can use manual programming to edit
monitor capable of quad sensing (normal, open, short,
labels, device functions, and alarm groups if neces-
and current-limited conditions). It is a line-powered
sary.
device and consumes one address.
- Adding new cards or points to a previously pro-
• The 4090-9101 (Class B) and 4090-9106(Class A)
grammed job.
Addressable Modules are input devices capable of quad
sensing (normal, open, short, and current -limited condi-
• Manual Programming. This programming option
tions). This device requires separate 24 V power and
allows you to individually change the attributes of each
consumes one loop address.
point, including:
• The 4099-9001 (single action) and 4099-9002/4099-
- Function Type. Determines the way in which the
9003 (dual action) addressable pull stations are latching
point operates (i.e., fire point, trouble point, on til
pull stations that can be reset with a key. They are a line-
silence, etc.).
powered device, consuming one address.
- Custom Label. Automatic programming assigns a
CONTROL MODULES generic label -- such as P1, NAC1, or AUX1 -- to
• 4090-9002 Relay Module is line-powered and contains each point. Manual programming allows you to
a Form-C relay that can be used to control auxiliary assign a 20-character, site-specific label to each
functions (such as elevator recall). point.
• 4090-9116 Isolator Module allows the addressable - Alarm Group. Allows inputs and outputs to be
device loop to continue to function under certain fault associated into groups to implement selective sig-
conditions. naling applications.
• 4090-9007 Signal Zone. System Options
System options are pre-defined modes of operation with a
Programming Overview range of settings from which to choose. System Options
define global operations such as the time and date format,
A job refers to the file containing all of the panel’s program-
door drop timers, and whether the city circuit is enabled, etc.
ming information. A job (also called a CFIG file) can be pro-
System options can be set during either the automatic man-
grammed in one of two ways.
ual programming process.
• Automatic Programming (Chapter 3). The panel’s
auto-program option provides the ability to quickly and Alarm Groups
automatically program the panel’s components and fea-
Alarm groups allow you to implement basic selective signal-
tures. This option does the following:
ling applications. As you program input (smoke detectors,
- Scans the panel’s serial communication channel, monitor zones) and output points (NAC, signal zone, relay),
adding any annunciators. you are given the opportunity to associate the point with an
- Scans the IDNet channel, adding and configuring alarm group number. The number can range from 1-10 and
IDNet devices. each point can be in up to three alarm groups. When pro-
- Adds any installed option cards, such as an AUX gramming is complete, an initiating device can only trigger
relay module or city circuit card. the output devices (relays, NACs) that share its alarm
group(s).
- Performs a duplicate address search, terminating
the operation if a duplicate address is found. Single Station Operation
- DACT information (phone numbers and account Single Station is a mode of operation that applies to IDNet
information) must be manually programmed. devices that use a sounder base (the sensor can be either
photo, heat, or combination photo/heat).

1-4
Chapter 1. Overview

Table 1-1 Operator Keys


Photo and heat sensors mounted on sounder bases can be
installed and programmed to act as single station smoke Key Function
detectors. The sounder activates when the smoke or heat
sensor crosses its alarm threshold and turns off when the Acknowledges any unacknowledged
smoke level goes below its threshold. (A general alarm fire TROUBLE troubles in the system, and scrolls
ACK through the trouble conditions in the
condition also occurs when the detector goes into alarm.)
active Trouble List.
Single Station programming allows you to set whether all Silences any silenceable output types
ALARM
the other sounder bases turn on and turn off along with the (generally all audible notification appli-
SILENCE
activated device. ances).

Allows the operator to reset all alarm


User Interface notification appliances and controls,
remove alarms from the Alarm List,
The user interface consists of control keys, LEDs, a 2-line silence all silenceable outputs, reset
by 20-character, backlit LCD, and a sounder mounted in the detectors, and return the system to a
control panel. The purpose of the Operator and Menu keys is normal state (provided that no alarm,
listed below. supervisory or trouble conditions are
present). The display indicates that a
reset is in progress and whether or not a
reset completes successfully.
Pressing the <SYSTEM RESET> key
SYSTEM will only attempt to return the system to
RESET a normal, non-alarm state. All outputs
that were activated by the alarm will
remain active until all alarm inputs have
been restored and the reset was able to
successfully complete.
An open circuit fault on a Class A NAC
does not require a System Reset to
restore to normal.
Open circuit faults on the optional City
Connect module are cleared with a sys-
tem reset after the circuit has been
repaired.
Figure 1-3 User Interface The Menu key always brings you to the
MENU top of the main menu structure unless
you are in the Programming menu.
Table 1-1 Operator Keys
The Function Menu is displayed when
Key Function the <Function> key is pressed at the
high-level status screen. Use the <Previ-
Acknowledges any unacknowledged fire FUNCTION ous> and <Next> keys to scroll through
ALARM alarms in the system, and scrolls the list of functions. The function key
ACK through the alarms in the active Alarm provides access to commonly used con-
List. trol and display functions.

Acknowledges any unacknowledged The <Disable/Enable> key allows the


SUPV supervisories in the system, and scrolls operator to quickly disable or enable any
ACK through the supervisory conditions in the point that is currently displayed. This key
DISABLE/
active Supervisory List. is passcode protected. A confirmation
ENABLE
screen is displayed requesting <Enter>
be pressed before the actual enable or
disable is performed.

1-5
Chapter 1. Overview

Table 1-1 Operator Keys Table 1-2 Access Levels and Features

Key Function Access


Operation
Level
The <Exit/Clear> key is used to back out
of menus or displays and return to the All Level 1 & 2 operations, plus:
top-level menu structure. Where possi- 3 Clear Historical Logs,
EXIT/ ble, the <Exit/Clear> key backs out one Passcode = Clear Verification Tallies
CLEAR level at a time. There are cases, how- 3000 Custom Label editing
ever, that the Exit/Clear key will return WALKTEST
the operator directly to the top-level
menu. 4 All Level 1, 2, & 3 operations, plus:
Passcode = Programming,
The <Enter> key is used to confirm 4000 Upload/Download
selections. When pressed, this key pro-
vides additional information about the Login/Logout Procedure
point shown on the display. In a pro-
gramming screen, pressing <Enter> To perform any of the functions protected at Level 2 or
ENTER above, you must login to the panel using a passcode. After
indicates that the information on the dis-
play is correct and can be accepted. The completing a task at a certain access level, you should then
<Enter> key is used in various other logout to return the access level to Level 1 to prevent unau-
places within the menu structure, always thorized operation. When logged in at Level 2 or above and
for this same type of operation. no panel keys are pressed for more than 10 minutes, the
panel automatically returns the system to Level 1.
The right and left arrows are used in
RIGHT/LEFT screens with multiple choices. The keys
ARROWS advance the focus (square brackets [ ]) All passcodes consist of a 4-digit number. Logging in at
from field to field. Level 4 causes a Service Mode trouble that may only be
cleared by restarting the panel.
The Previous & Next keys are used to
scroll through the system lists, historical To login, perform the following steps:
log, point database, etc. The <Next> key
selects the next display screen in 1. Obtain the passcode information for the desired level.
PREVIOUS/
sequence, and the <Previous> key
NEXT 2. Press <MENU>
selects the previous screen. These keys
are also used to view additional informa- 3. Press <NEXT> until [Login/Logout] is displayed, then
tion about abnormal points or in viewing press <ENTER>. A prompt similar to the following
historical logs.
appears.

Logging In and Out Access: Level 1


<ENTER>=[Login]
Certain operator functions are passcode-protected at differ-
ent levels. This section describes the operator functions, 4. Press <NEXT> until [Login] is displayed, then press
their default access level, and the login/logout procedure. <ENTER>. A prompt similar to the following appears.

Table 1-2 Access Levels and Features Access: Level 1


Passcode: [0]
Access
Operation 5. Use the Keypad to enter the appropriate passcode.
Level
6. When the passcode is correct, press the <ENTER> key
Acknowledge, Silence, System Reset,
to login.
1 View Historical Logs, Lamp Test
View Point Information, A “Login Accepted” message, which indicates your current
access level, is displayed briefly upon a successful login
2 All Level 1 operations, plus: attempt.
Passcode = Set Time/Date, Point Control,
2000 Enable/Disable points To logout, perform steps 1-4 above, but select Logout
instead of Login.

1-6
Chapter 2. Installation/System Checkout

Back Box Mounting In This Chapter


The back box can be surface-mounted or semi-flush mounted to the
wall. Use separate conduit entrances for power-limited and non-power Back Box Mounting . . . . . . . . . . . . . . . . . . . . .2-1
limited wiring. General Wiring Guidelines . . . . . . . . . . . . . . . .2-2
IDNet Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . .2-3
Class A/Class B NAC Wiring . . . . . . . . . . . . . .2-5
AC supply, battery supply, and City Connect wiring are all non-power
Remote Annunciator Comm Wiring . . . . . . . . .2-8
limited wiring.
Digital Alarm Communicating Transmitter (DACT)
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-9
Removing Electronics Assembly
Auxiliary 24V Power Wiring . . . . . . . . . . . . . . 2-11
Use either a #6 Torx or a slot-head screwdriver to remove the four City Connect Module Wiring. . . . . . . . . . . . . .2-12
screws that secure the electronics assembly to the back box. Auxiliary Relay Wiring . . . . . . . . . . . . . . . . . .2-13
AC Supply Wiring . . . . . . . . . . . . . . . . . . . . . .2-14
Conduit Entrances and Wire Routing Battery Wiring. . . . . . . . . . . . . . . . . . . . . . . . .2-15
Depleted Battery Cutout. . . . . . . . . . . . . . . . .2-16
• Nine knockouts are provided for conduit connection. Refer to Fig-
Safety Ground/Ferrite Bead . . . . . . . . . . . . . .2-16
ure 2-1 for knockout locations. Replacing Lithium Battery . . . . . . . . . . . . . . .2-17
• Power limited wiring must be located only in the shaded area of Periodic Testing and Maintenance . . . . . . . . .2-17
the cabinet.
• AC power (non-power limited) wiring must be run in separate con-
duit from all other wiring, as shown in Figure 2-1. Non-power lim-
ited wiring must be separated from power limited wiring by a
minimum of 1/4".

TB1 TB2 TB3

Expansion
Power Supply

City Connect
Module DACT

AC Voltage Battery
Connection Connection

Battery Battery

Figure 2-1 Power-Limited (Shaded) and


Non-Power Limited Wiring Areas

2-1
Chapter 2. Installation/System Checkout

• All Aux Relay loads must be powered from the AUX


power circuit or from a regulated, 24 VDC, power-lim-
ited power supply that is UL-listed for fire protective
signaling service.

Guidelines for Locating Backbox


Always refer to engineering drawings/site installation plans
before beginning installation. Choose a site for each cabinet
that is:
• Located near a dedicated AC individual branch circuit
with Earth ground (to maintain a consistent supply volt-
age).
• Mount the cabinet to the wall so that the top of the
enclosure is no more than six feet above the floor.
• Well-ventilated, clean, and dust free.
1.5”
• Away from sources of heat, including direct sunlight.
• Away from sources of vibration or physical shock.
Figure 2-3 Semi-Flush Mounting
• Away from sources of Radio Frequency Interference
(RFI), such as a radio transceiver base station or hand
held unit. General Wiring Guidelines
• Isolated from sources of strong electromagnetic fields, All wiring to the 4008 and its peripherals must be performed
such as air conditioners, large fans, and electric motors. in accordance with NFPA 70, NFPA 72, all local codes, and
per the technical requirements listed below.
Surface Mounting
Refer to the figure below for hole dimensions. Testing Procedure
Before connecting any wires to the 4008 system, including
1.000 11.250
option modules, wires must be tested as follows:
1. Using a voltmeter (VOM) to verify no stray voltages are
applied to the field wiring. Test for AC and DC voltages
across each pair of wires and from each wire to earth.
2. Use a VOM to verify that all wiring tests free of
13.500 16.000 grounds. Each conductor should test “open” against
earth (chassis).

13.250
15.632

Figure 2-2 Surface Mounting Hole Dimensions

Semi-Flush Mounting
Semi-flush mounting involves recessing the cabinet into a
wall and attaching it directly to the wall's studs. At a mini-
mum, 1.5 inches of the cabinet must protrude from the wall
to allow for clearance of the panel door.

2-2
Chapter 2. Installation/System Checkout

IDNet Wiring • For Class B (Style 4) wiring, adhere to the following:


- Wire all addressable detectors to B+ and B- termi-
• All wiring is to be 18 AWG (min.) to 12 AWG (max.). nals. Do not return wiring to A+/A- terminals.
• Conductors must test free of all grounds and stray volt- - Maximum wiring capacitance is .58uF total. Maxi-
ages before connection to appliances and panel. mum wiring resistance to any device is 52 ohms.
• All wiring is supervised and power-limited. - System ships with jumper wires from B+ to A+ and
• Refer to installation instructions packed with address- from B- to A-. Leave jumper wires installed for
able detectors for information on wiring detectors to Class B wiring.
IDNet channel. - T-tapping is allowed for Class B wiring.
• IDNet voltage is 36.25V (max.) at 3333 bits/second. - 10, 000 feet total cable load (max.) allowed. Resis-
• For shielded wiring, connect shield to TB2-3. Jumper tance and capacitance limits must be observed.
setting selects shield connection (Earth or 0V). Default • For Class A (Style 6 or Style 7) wiring, adhere to the
setting is 0V. following:
• To achieve maximum wiring distance, use low capaci- - Wire from B+/B- terminals to the first addressable
tance wire, 29 pF/Foot or lower. If shielded wire is used, device. Wire to each device in succession for a
be sure to consider shield to conductor capacitance. Class A loop. From last device, wiring is returned
• Style 7 operation requires use of addressable isolator to the A+/A- terminals.
modules -- 4090-9116, 4098-9793, 4098-9793C. Refer - Maximum wiring capacitance is .58uF total. Maxi-
to 579-872 for information on 4090-9116; refer to 574- mum wiring resistance to any device is 52 ohms.
706 for information on 4098-9793. - System ships with jumper wires from B+ to A+ and
• If wiring is routed outside the building, use of a listed from B- to A-. Remove jumper wires for Class A
secondary protector is required. Use Simplex Number wiring.
2081-9028 or 2081-9044. A protector must be installed - T-tapping is not allowed for Class A wiring.
at each building exit/entrance. Each 2081-9028 adds .2
Compatible Detectors:
ohm wiring resistance. Each 2081-9044 adds 6 ohms
wiring resistance. Use of the 2081-9044 will signifi- Photo Detector 4098-9714
Photo Detector (Canadian) 4098-9714C
cantly reduce wiring distance. Photo Detector w/Heat 4098-9754
Photo Detector w/Heat (Canadian) 4098-9754C
Heat Detector 4098-9733
Note: If wiring Heat Detector (Canadian) 4098-9733C
Class B, do not 2 Wire Duct Detector w/o Relay 4098-9755
2 Wire Duct Detector w/o Relay (Canadian) 4098-9755C
return wiring to A+/ 4 Wire Duct Detector w/Relay 4098-9756
CLS B
A- terminals. 4 Wire Duct Detector w/Relay (Canadian) 4098-9756C

4008 Compatible Bases:


See “Ferrite S
OR H
Bead” on next UNIMMODE AE I Detector Base w/o Remote Led Connection 4098-9792
OR E Detector Base w/o Remote Led Connection, Canadian,
page for informa- L 4098-9792C
2008 D
tion on looping TB Detector Base w/Remote Led Connection 4098-9789
Detector Base w/Remote Led Connection, Canadian 4098-
2-1 and TB 2-2 9789C
200 DEVICE Detector Base w/Relay Drive 4098-9791
through Ferrite 12 - 18 AWG CLS A
Detector Base w/Relay Drive, Canadian 4098-9791C
bead. 250mA @ 35V Isolator Base 4098-9793
Isolator Base, Canadian 4098-9793C
Sounder Base 4098-9794
Sounder Base, Canadian 4098-9794C
TB1 TB2 TB3
Multi Detector Sounder Base 4098-9795
1 2 3 4 5 6 7 8 1 2 3 4 5 1 2 3 4 5 6 7 8 Multi Detector Sounder Base, Canadian 4098-9795CA
Multi Detector Base w/LED 4098-9796
Multi Detector Base w/LED, Canadian 4098-9796CA

MAIN SYSTEM BOARD - ADDRESSABLE (MSB - A) Compatible ZAMs/IAMs

4090-9106 Class A ZAM


4090-9101 Class B ZAM
4090-9001 Supervised IAM
4090-9002 Relay IAM

Figure 2-4 IDNet Wiring

2-3
Chapter 2. Installation/System Checkout

IDNet Ferrite Bead Compatible Devices for use with IDNet Monitor
IDNet wiring attached to TB 2-1 and 2-2 must pass through ZAMs
a ferrite bead. Wrap the wiring twice through the ferrite A Zone Addressable Module (ZAM) allows the following
bead, as shown in Figure 2-5. non-IDNet devices to be wired to the addressable channel.

Table 2-1 Two Wire Devices for use with 4090-9106


Class A ZAM and 4090-9101 Class B ZAM

Max. #
Head Base(s)
Devices

4098-9685 N/A 20

4098-9612 to - 4098-9788, -9683,


20
9615 -9684

4098-9601, -9602, 4098-9788, -9683


20
-9605

Figure 2-5 Ferrite Bead


Table 2-2 Four Wire Devices for use with 4090-9101
Class B ZAM

Max. #
Head Base(s)
Devices

4098-9612 to - 4098-9682 (See


20
9615 below for wiring.)

4098-9601, -9602, 4098-9682 (See


20
-9605 below for wiring.)

Wiring 4098-9682 Four-Wire Base


When the 4098-9682 base is used, the auxiliary 24V power
must be routed through TEPG-US Model Number 2098-
9735 end-of-line relay, as shown in Figure 2-6.

TYPICAL 4-WIRE
DETECT OR
TYPICAL 4-WIRE ZONE 2098-9735 (RELAY SHO WN
24 VDC power 24VDC DEVICES
ENERGIZED)
from listed FACP
E.O.L. RELAY
RED YELLO W

24VDC END-OF-LINE DEVICE


4090-9101 BLACK
YELLO W
SELECTED PER ZONE
ZAM CIRCUIT

Figure 2-6 Wiring 4098-9682 Four Wire Base

2-4
Chapter 2. Installation/System Checkout

Class A/Class B NAC Wiring tor from any circuits in use. Leave it installed if circuits
are unused.
The following guidelines and restrictions apply to notifica- • Wiring chart gives maximum distance for 1/4 - 2 A
tion appliance circuits (NACs) located on either the main loads. For Class B circuits, wiring distance is from
system board (MSB) or on the Expansion Power Supply panel terminals to last appliance. For Class A circuits,
(EPS). wiring distance is from panel terminals to last appliance
• All wiring to be 18 AWG (min.) to 12 AWG (max.). and back to terminals. Use of Simplex Model 2081-
• Conductors must test free of all grounds and stray volt- 9044 will reduce the wire distance.
ages before connection to appliances and panel. • When using two-wire audible/visible appliances, maxi-
• All wiring is supervised and power limited. mum wiring capacitance of .22 uF must be considered.
• Wire Class A (Style Z) NACs from B+ and B- to each
appliance as shown. No EOL device is needed. Connect Maximum Wiring Distance in Feet
wires from +/- terminals of the last appliance to the A+/ Alarm Line
18 16 14 12
A- terminals as shown. Current
AWG AWG AWG AWG
Resistance
(Amps) (Ohms)
• Voltage Rating: Refer to “NAC Ratings” on Page 2-7
for specific voltage specifications. Maximum ripple: .25 840 1335 2126 3382 12

1/2 V peak-to-peak. .50 420 667 1063 1691 6


• Current rating 2A max. for either circuit. 3A total
.75 280 445 709 1127 4
between both NAC circuits and AUX 24V load.
1.0 210 334 532 845 3
• When using the following SimplexMulti-Candela appli-
ances, each NAC is rated for 2A max. 1.25 168 267 425 676 2.4

- 4906-9101 1.50 140 222 354 564 2


- 4906-9102
1.75 120 191 304 483 1.71
- 4906-9103
2.0 105 167 266 423 1.5
- 4906-9104
- 4906-9127
• Terminate Class B (Style Y) NACs as shown using Sim-
- 4906-9128
plex 733-894 (4081-9008) 10K 1/2 W resistor harness.
- 4906-9129 For Canadian applications, mount end-of-line resistor to
- 4906-9130 TEPG-US Model 431537 EOL plate in accordance with
- 4906-9151 ULC-S527.
- 4906-9153
• The Expansion Power Supply (if used) mounts next to
- 4906-9154
the MSB. NAC wiring is routed within the cabinet as
• For all other UL-listed notification appliances, each shown below.
NAC is rated at 1.5A max.
• Synchronization of strobes across all NACs in a system
is UL-listed for all of the above SimplexMulti-Candela
models, with a maximum of 34 appliances on a NAC
(15 Cd setting).
• Terminal designations are for the alarm state (+/-). Main
• If wiring is routed outside the building, use of a listed System
secondary protector is required. Use Simplex Number Board EPS
NACs
2081-9028 or 2081-9044. A protector must be installed
at each building exit/entrance. Each 2081-9028 adds .2
ohm wiring resistance. Each 2081-9044 adds 6 ohms
wiring resistance. Use of the 2081-9044 will signifi-
cantly reduce wiring distance.
• System is shipped with 10K, 1/2W resistors connected
across NAC B+/B- for each circuit. Remove this resis-

2-5
Chapter 2. Installation/System Checkout

TYPICAL AUDIBLE / VISIBLE APPLIANCES

NAC - NAC - NAC -

NAC+ NAC+ NAC+

TYPICAL AUDIBLE / VISIBLE APPLIANCES

NAC - NAC -
733-894
(10K, 1/2W
EOLR NAC+ NAC+

B +

B +

A +
B -

B -

A -
TB1 TB2 TB3
1 2 3 4 5 6 7 8 1 2 3 4 5 1 2 3 4 5 6 7 8

MAIN SYSTEM BOARD - ADDRESSABLE (MSB - A)

Figure 2-7 NAC Wiring -- Main System Board

TYPICAL AUDIBLE / VISIBLE APPLIANCES

NAC - NAC - NAC -

NAC+ NAC+ NAC+

TYPICAL AUDIBLE / VISIBLE APPLIANCES

733-894 NAC - NAC -


10K, 1/2W
EOLR
NAC+ NAC+
B +

B +

A +
B -

B -

A -

TB1
1 2 3 4 5 6 7 8 9 10

EXPANSION POWER SUPPLY ASSY.
NAC MODULE

Figure 2-8 NAC Wiring -- Expansion Power Supply NACs

2-6
Chapter 2. Installation/System Checkout

NAC ratings allowed strobe load on either the main or expansion power
supply is 1.35 A. The balance of the 3 A capacity can be
The panel is rated Special Application for 2A maximum per auxiliary loads or audible notification appliances.
NAC with Simplex 4901 and 4906 TrueAlert & TrueAlert
Multi-Candela Notification Appliances. Synchronization of strobes across all NACs in a system is
UL-Listed for the Simplex models noted in the table below.
For all other UL-Listed Notification Appliances, NACs are See the table below for maximum number allowed of each
rated regulated 24 VDC at 1.5 A maximum each. Maximum appliance per NAC.

Table 2-3 NAC Ratings

15Cd 30Cd 75Cd 110Cd

Rated Max. # per Rated Max. # Rated Max. # per Rated Max. # per
4906-
Current NAC Current per NAC Current NAC Current NAC

9101 0.060 33 0.094 21 0.186 10 0.252 7

9102 0.075 26 0.125 16 0.233 8 0.316 6

9103 0.060 33 0.094 21 0.186 10 0.252 7

9104 0.075 26 0.125 16 0.233 8 0.316 6

9127 0.075 26 0.116 17 0.221 9 0.285 7

9128 0.086 23 0.132 15 0.250 8 0.320 6

9129 0.075 26 0.116 17 0.221 9 0.285 7

9130 0.086 23 0.132 15 0.250 8 0.320 6

9151 0.060 33 0.094 21 0.186 10 0.252 7

9154 0.075 26 0.125 16 0.233 8 0.316 6

9153 0.060 33 0.094 21 0.186 10 0.252 7

All other regulated 24 VDC synchronized notification


appliances require the use of their associated, listed external
synchronization module. Notification Circuit rating is 1.5 A
maximum, 1.35 A maximum strobe load per power supply.
Use the UL-rated operating current to determine maximum
number of appliances allowed per NAC.

2-7
Chapter 2. Installation/System Checkout

Remote Annunciator Comm Wiring


• All remote annunciator wiring to be 18 AWG (min.) to N2 COMMS
12 AWG (max.), twisted-pair or shielded twisted pair.
• Conductors must test free of all grounds and stray volt-
ages before connection to appliances and panel.
0V SHIELD CONN
• All wiring is supervised and power limited. (IF USED)

• Refer to installation instructions packed with each


Remote Annuciator Module (RAM) for connection TB1 TB2 TB3
details. 1 2 3 4 5 6 7 8 1 2 3 4 5 1 2 3 4 5 6 7 8

• Remote Annunciator Modules require power and com-


munications wiring. MAIN SYSTEM BOARD - ADDRESSABLE (MSB - A)
• For “bus-style” wiring, maximum wiring limit is 4, 000
feet. Maximum wiring capacitance is .58 uF total, wire-
to-wire plus wire to shield. Attach Simplex Model 733- Figure 2-10 Remote Annunciator
974) 100 ohm, 1/2 W harness (see “A” in figure below) Wiring Connections
for line matching. Wire remote devices “daisy-chain”
style, using the in/out terminals on each device.
• For “T-Tap” style wiring, total cable limit is 10, 000
RAM
feet, 2, 500 feet to the furthest device. Maximum wiring
capacitance is .58uF total, wire-to-wire plus wire-to-
shield. Attach Simplex Model 733-974 100 ohm, 1/2W
harness (see “A” in figure below) for line matching. MSB A RAM RAM A
• Shielded wire is not required for most installations. If
communications wiring is not in conduit with strobes,
T-Tap Style Wiring RAM
voice speaker circuits, or signaling line circuits,
shielded wire is not required. Use shielded wiring if in
same conduit as those circuits. Terminate shield to 0V
(Aux 24V negative terminal) or to chassis.
• If wiring is routed outside the building, use of a listed
secondary protector is required. Use Simplex Number
2081-9028 or 2081-9044. A protector must be installed
MSB A RAM

at each building exit/entrance. Each 2081-9028 adds .2


ohm wiring resistance. Each 2081-9044 adds 6 ohms Bus Style Wiring
wiring resistance. Use of the 2081-9044 will signifi- RAM RAM
cantly reduce wiring distance.
• Wiring must pass through a ferrite bead. Wrap the wir- RAM = Remote Annunciator Module
ing twice through the ferrite bead, as shown in MSB = Main System Board
Figure 2-9.
Figure 2-11 Bus Style and T-Tap Wiring

Figure 2-9 Ferrite Bead

2-8
Chapter 2. Installation/System Checkout

Digital Alarm Communicating • Wire from TELCO equipment to TB5 using 18 AWG to
24 AWG.
Transmitter (DACT) Wiring
• All wiring is supervised.
• The DACT requires two telephone line connections to • Digital Alarm Communicator Receiver (DACR) com-
meet NFPA72 requirements. Wire from TB5-3/TB5-4 patibility is shown in Table 2-4.
and TB5-7/TB5-8 to an RJ-11 or other Telcom wiring • If wiring is routed outside the building, use of a listed
block for connection to other telephone equipment. The secondary protector is required. Use Simplex Number
DACT will seize control of the telephone line (if neces- 2081-9028 or 2081-9044. A protector must be installed
sary) to transmit emergency messages. When wired as at each building exit/entrance. Each 2081-9028 adds .2
shown, the DACT will properly control access to lines ohm wiring resistance. Each 2081-9044 adds 6 ohms
in an emergency. wiring resistance. Use of the 2081-9044 will signifi-
• Telephone wiring from public telephone network con- cantly reduce wiring distance.
nects to TB5-1/TB5-2 and TB5-5/TB5-6.

TB1 TB2 TB3


1 2 3 4 5 6 7 8 1 2 3 4 5 1 2 3 4 5 6 7 8

MAIN SYSTEM BOARD - ADDRESSABLE (MSB - A)

DANGER
HIGH VOLTAGE
IN THIS AREA

DACT TELEPHONE
CONNECTIONS
1 2 3 4 5 6 7 8
TB5
R T R T R T R T
I I I I I I I I
N P N P N P N P
G G G G
WIRE TO MODULAR JACK
LINE 2 TELCO SERVICE IN TO USE LINE 1 FOR
OTHER TELCO EQUIP.
WIRE TO MODULAR JACK
TO USE LINE 1 FOR LINE 1 TELCO SERVICE IN
OTHER TELCO EQUIP.

Figure 2-12 DACT Wiring

2-9
Chapter 2. Installation/System Checkout

Table 2-4 Compatible DACRs

Digital Alarm Communicator Receiver (DACR)


Simplex Osbourne/
FBII ADEMCO Silent Silent
Central Hoffman Surgard Radionics Surgard
CP220FB 685 Knight Knight
Station QuickAlert MLR2-DG D6600 MLR2000
Note 2, 3 Note 1, 3 9000 9500
Services II

Contact ID
Preferred • • • • • • •

3/1 Standard
1800/2300 Hz • • • • • • • • •
10 and 20PPS With 9032
Line Card

3/1 Standard

1900/1400 Hz • • • • • • With 9032
• •
10 and 20PPS
Line Card
Communication Format

4/2 Standard
1800/2300 Hz • • • • • • • • •
10 and 20PPS With 9032
Line Card

4/2 Standard
1900/1400 Hz • • • • • • • • •
10 and 20PPS With 9032
Line Card

Radionics BFSK
1800/2300 Hz • • • • • • • • •
With 9032
Line Card

Radionics BFSK
1900/1400 Hz • • • • • • • • •
With 9032
Line Card

SIA • • • • •
With 9004
Line Card

Notes:
1. With 685-8 Line Card
2. With Rec-11 Line Card
3. These receivers are also Factory Mutual (FM) approved.

2-10
Chapter 2. Installation/System Checkout

Auxiliary 24V Power Wiring • Compatible with Simplex 4098 Series Peripherals; 2098
Series Relay Modules; all Simplex 4090 Series IDNet
• All wiring is to be 18 AWG (min.) to 12 AWG (max.) Peripherals; and 4610-9111 / 4606-9101 Annunciators.
• Conductors must test free of all grounds and stray volt- • If wiring is routed outside the building, use of a listed
ages before connection to appliances and panel. secondary protector is required. Use Simplex Model
• All wiring is supervised and power limited. 2081-9028 or 2081-9044. A protector must be installed
at each building exit/entrance. Each 2081-9044 adds 6
• Voltage rating (24 VDC special application): 1 V p-p
ohms wiring resistance, and is rated for 200mA. Each
ripple (maximum)
2081-9028 adds .2 ohms wiring resistance, and is rated
- 0.5 A maximum available aux 24 V from EPS
for more than 1/2A Aux. 24V capacity.
- Additional 0.5 A maximum available from Main
System Board (MSB) AUX 24 V • Compatible devices must operate from a range of 19.5
- 3 A total available from MSB NACs and MSB to 28 VDC or greater, and have a total current draw of 1/
AUX 24 V. 2 A or less.
- 3 A total available from EPS NACs and EPS AUX
24 V.

MSB AUX 24V
1 / 2 MAX.

TB1 TB2 TB3


1 2 3 4 5 6 7 8 1 2 3 4 5 1 2 3 4 5 6 7 8
MSB AUX 24V
1 / 2 MAX.

MAIN SYSTEM BOARD - ADDRESSABLE (MSB - A)

EPS
POWER SUPPLY MODULE
TB1
EXPANSION POWER SUPPLY ASSY.

DANGER
1 2 3 4 5 6 7 8 9 10

HIGH VOLTAGE
IN THIS AREA
NAC MODULE

DACT TELEPHONE
CONNECTIONS
1 2 3 4 5 6 7 8
TB5

Figure 2-13 Auxiliary 24V Power Wiring

2-11
Chapter 2. Installation/System Checkout

City Connect Module Wiring • Conductors must test free of all grounds.
• For specific information about reverse polarity and local
• City connect module mounts to the main system as energy circuits see Figure 2-14.
shown. Refer to City Module Installation Instructions
• If wiring is routed outside the building, use of a listed
for details.
secondary protector is required. Use Simplex Model
• City module consists of two circuits that are jumper- Number 2081-9044. A protector must be installed at
configured. Circuits may be configured for reverse- each location the wiring enters or exits a building. Each
polarity or local energy operation. See jumper setting 2081-9044 adds 6 ohms wiring resistance and is rated
table for details. Modules must also be added to the sys- for 200 mA. Maximum wiring resistance is reduced by
tem configuration. See “System Options” later in this 6 ohms for each 2081-9044 used.
manual.
• Circuits are shipped with 3.3K, 1/2W resistor installed.
• All wiring to be per NFPA-72, NEC, and local codes. Remove resistor before wiring circuit. Leave installed
Minimum 20 AWG for reverse polarity circuits; mini- on unused circuits.
mum 18 AWG for local energy circuits.
• Wiring is supervised for opens and grounds, but not
power-limited.

TB1 TB2 TB3


REVERSE POLARITY LOCAL ENERGY
1 2 3 4 5 6 7 8 1 2 3 4 5 1 2 3 4 5 6 7 8

MAIN SYSTEM BOARD - ADDRESSABLE (MSB - A)

15mA MAX. AT 24VDC 24V DC NORMAL
4mA SUPERVISION CURRENT
500mA MAX. ALARM CURRENT (PULSED) 1
INTENDED FOR CONNECTION TO A POLARITY CITY CONNECT P6 2
3
4
REVERSAL CIRCUIT OF A REMOTE STATION MODULE
Employ a 14.5 Ohm Trip Coil
RECEIVING UNIT HAVING COMPATIBLE RATINGS INTENDED FOR CONNECTION TO A 14 . 5 OHM
20 . 4V - 28VDC, 1/2 p - p RIPPLE (MAX.) TRIP COIL. DACT TELEPHONE
CONNECTIONS
MAXIMUM WIRING RESISTANCE: 4000 OHMS DANGER
WITH 2200 OHM TRIP COIL (6200 OHM TOTAL) HIGH VOLTAGE
IN THIS AREA
POLARITY MARKED ON TERMINALS REFLECTS
THE ALARM STATE.

3A 3A
FUSE FUSE

SW SW
1 2 3 4

SEE DETAIL  A

P3 P5 CKT 1 CKT 2
10 9 10 9
8 7 8 7 1

LE 6 5 LE 6 5 CITY CONNECT P6 2
3
4
P2 P4
RP 4 3 RP 4 3 MODULE 1
2 1 LE 2 1 LE P6 2
RP RP 3
4

P6 SELECTS CITY CIRCUIT 2 OPERATION.

POS. 1 - 2 AND 3 - 4 FOR CITY 2 TO
ACTIVATE ON SUPERVISORY CONDITION
P3 P5
POS. 1 - 3 FOR CITY 2 TO
LE P2 LE P4
RP RP ACTIVATE ON TROUBLE CONDITION
JUMPER POSITIONS LE LE
RP RP

REVERSE POLARITY LOCAL ENERGY 3A 3A
FUSE FUSE
P3: 1 - 2, 3 - 4, 5 - 6 P3: 7 - 8, 9 - 10
CITY 1
P2: 2 - 3 P2: 1 - 2
P5: 1 - 2, 3 - 4, 5 - 6 P5: 7 - 8, 9 - 10 SW SW
CITY 2
P4: 2 - 3 P4: 1 - 2 1 2 3 4

DETAIL  A

Figure 2-14 City Connect Module Wiring

2-12
Chapter 2. Installation/System Checkout

Auxiliary Relay Wiring • Each relay is selected for normally-closed or normally-


open operation. Shunt jumper setting selects desired
• All wiring must be 18 AWG (minimum) to 12 AWG contact.
(maximum). • Relay 1 is programmable. Default operation is -- On
• Conductors must test free of all grounds and stray volt- Until Reset.
ages before connection to appliances, devices, and • Relay 2 is a normally energized trouble relay. The
panel. jumper settings shown account for the relay being nor-
• All wiring is unsupervised. mally energized. When the panel is completely powered
• Contact rating: 30VDC @ 2A (pilot duty, .35 power fac- “Off”, the trouble relay will be in the “Off Normal”
tor). state.

AUX. TBL.
RELAY RELAY

J C
U E
M N
P T
E E
R R

TB1 TB2 TB3


1 2 3 4 5 6 7 8 1 2 3 4 5 1 2 3 4 5 6 7 8

JUMPER
CENTER
MAIN SYSTEM BOARD - ADDRESSABLE (MSB - A)

JUMPERS TO SELECT NORMALLY OPEN
OR CLOSED RELAY CONTACTS.

NORMALLY OPEN (JMPR LEFT)

NORMALLY CLOSED (JMPR RIGHT)

Figure 2-15 Auxiliary Relay Wiring

2-13
Chapter 2. Installation/System Checkout

AC Supply Wiring • The Expansion Power Supply (EPS) is an option, and


requires AC power when used. Connect the Black/
Adhere to the following guidelines when wiring AC Power. White AC harness from the EPS to the TB4 AC input
• AC power must be wired from a dedicated circuit terminals on the MSB. Wire Black to the left terminal of
breaker or fuse, rated 20 A, per NFPA-72, NEC, and TB4. Wire White to the right terminal of TB4.
local codes. • AC wiring is supervised. Safety ground wire is not
• Before handling AC feed, verify that it is not live using supervised.
a voltmeter. Make sure the circuit is de-energized and • Supply Power Requirements
tagged to prevent injury. - 120 VAC 60 Hz, 4A maximum
• AC supply wiring must be 14 AWG minimum to 12 - 240 VAC 50 Hz, 3A maximum
AWG maximum. • AC feed must be routed in the wiring area below the
• Connect a 12 AWG copper ground wire from safety MSB, in the area designated "not power limited".
ground in the electrical distribution panel to the panel • Before applying AC power to the system, connect the
safety ground stud. batteries per the instructions on the following page and
• Input voltage range: replace the protective cover.
- 120 VAC, 60 Hz • Wire “LINE” to the left terminal of TB4. Wire “Neu-
- 240 VAC, 50Hz tral” to the right terminal of TB4.
- No configuration settings required to select.

TB1 TB2 TB3


1 2 3 4 5 6 7 8 1 2 3 4 5 1 2 3 4 5 6 7 8
THE POWER SUPPLY MODULE, PART OF THE EPS
ASSEMBLY, IS MOUNTED BENEATH THE NAC MODULE
PORTION OF THE EPS ASSEMBLY.
MAIN SYSTEM BOARD - ADDRESSABLE (MSB - A)

EPS
POWER SUPPLY MODULE TB1
EXPANSION POWER SUPPLY ASSY.

DANGER
1 2 3 4 5 6 7 8 9 10

B+ B-

HIGH VOLTAGE
IN THIS AREA
NAC MODULE

B+ B- A+ A-

DACT TELEPHONE
CONNECTIONS
1 2 3 4 5 6 7 8
TB5

LINE
734 - 179
WIRE AC LINE AND NEUTRAL AS SHOWN.
NEUTRAL HOT TO LEFT TERMINAL, NEUTRAL TO RIGHT TERMINAL.

WHITE
BLACK WHITE / BLACK HARNESS 734 - 179
FROM EPS (LOWER MODULES)
TO MAIN SYSTEM BOARD.

Figure 2-16 AC Supply Wiring

2-14
Chapter 2. Installation/System Checkout

Battery Wiring • Connect the main battery harness to the four-position


header, located approximately in the center of the bot-
• The main battery harness connects the MSB to the bat- tom edge on the MSB. Insert the connector left-justi-
tery set in the same cabinet. fied, with the red wire to the left.
• The system requires 24V battery backup. Use two 12V • The EPS connects to the battery header next to the bat-
batteries, connected in series. The main battery harness tery harness described in the previous bullet. Install the
connects to the .250” fast-on battery terminals, as fol- EPS red/black harness right-justified to the battery
lows: header, with the black wire to the right.
1. Connect black wire to the negative battery terminal • For depleted battery cutout operation, remove jumper
of Battery 1. per installation instructions. Separate jumper removal
2. Connect white wire from the positive battery termi- required for MSB and EPS. System programming
nal of Battery 1 to the negative battery terminal of option “Depleted Battery Cutout” must also be selected.
Battery 2. ULC-S527 depleted battery operation requires jumper
removal.
3. Connect the red wire to the positive battery termi-
nal of Battery 2. • Battery Wire is supervised, but not power-limited.
• For 18 Ah batteries, the 4009-9801 external battery cab-
inet must be used. Mount the battery box within 20 feet
of the control panel, in accordance with the mounting
instruction label in the box. All interconnecting wiring
must be enclosed in conduit.

TB1 TB2 TB3


1 2 3 4 5 6 7 8 1 2 3 4 5 1 2 3 4 5 6 7 8
THE POWER SUPPLY MODULE, PART OF THE EPS
ASSEMBLY, IS MOUNTED BENEATH THE NAC MODULE
PORTION OF THE EPS ASSEMBLY.
MAIN SYSTEM BOARD - ADDRESSABLE (MSB - A)

EPS
POWER SUPPLY MODULE
TB1
EXPANSION POWER SUPPLY ASSY.

DANGER 3B+
1 2 3 4 5 6 7 8 9 10

HIGH VOLTAGE 3B-
IN THIS AREA 3A+
NAC MODULE

3A-
4B+
4B-
DACT TELEPHONE 4A-
CONNECTIONS 4A-
1 2 3 4 5 6 7 8 24V
0V
TB5

R B 734 - 180
E L ATTACH TO BATTERY CONNECTOR
D K RIGHT - JUSTIFIED, BLACK WIRE TO THE RIGHT

BLACK
RED
R B
E L HARNESS 734 - 180
D K FROM EPS (LOWER MODULES)
TO MAIN SYSTEM BOARD
BATTERY CONNECTOR

CONNECT TO
BATTERY TERMINALS
(FUSED ON PCB)

Figure 2-17 Battery Wiring

2-15
Chapter 2. Installation/System Checkout

Depleted Battery Cutout System Power-Up and


For depleted battery cutout, remove the jumper shown in Checkout
Figure 2-18 from the MSB. If you are using an Expansion Use the following procedure to apply AC and battery power
Power Supply (EPS), you must also remove the depleted to the 4008.
battery cutout jumper from the EPS. (When programming
the panel, make sure to enable the Depleted Battery Cutout On power up, the 4008 performs the following:
system option.) • Displays revision of boot-loader software
• CPU self test
Remove this • Link Scan - checking for a programming unit connec-
Jumper tion
• Memory Test - Verifying system and job-specific soft-
ware
• Startup - 4008 Exec startup

If the 4008 successfully completes its start up self-test, it


will indicate a warm or cold start trouble, which clears when
acknowledged. If there are no other troubles in the system, a
message similar to the following is displayed:

SYSTEM NORMAL
12:00 am 03/09/03
+ - + -
LINE NEUTRAL BATT EPS
If other troubles exist in the system, the following is dis-
Figure 2-18 Location of Depleted Battery Jumper played:

Safety Ground/Ferrite Bead


FIRE SUPV TRBL
Proper operation and protection against transient energy per
UL 864 and ULC-S527 requires connection of safety ground
wire to cabinet chassis as shown in Figure 2-19. 00 00 02

In addition, a ferrite bead must be attached to the incoming


AC power line as shown in the figure. Wrap the Line and
Neutral legs of the power line twice through the ferrite bead. Pressing the <TROUBLE ACK> key allows the operator to
acknowledge the troubles (silencing the panel sounder) and
scroll through the troubles on the active Trouble List.

If the 4008 self-test fails, the panel displays an error code


and waits 30 seconds before attempting a restart.

Acceptance Testing
When you are finished with the original installation, pro-
gramming and all modifications, conduct a complete opera-
tional test on the entire installation to verify compliance with
applicable NFPA standards and Local Codes. Testing should
be conducted in the presence of a representative of the
Authority Having Jurisdiction (AHJ), and the customer's
representative. Follow procedures outlined in Chapter 10
"Inspection, Testing, and Maintenance" of NFPA standard
72-2002 and as dictated by local codes.
Figure 2-19 Safety Ground and Ferrite Bead

2-16
Chapter 2. Installation/System Checkout

Testing Circuit Supervision Batteries should be tested by discharging them with a suit-
Use the following procedures to confirm that IDNet and able tester and verifying that battery voltage is at least 21V
NACs and are supervising for opens, shorts and grounds. when fully discharged. Battery discharge tests should be per-
The right column in this table shows the LEDs that illumi- formed annually, and batteries should be replaced no longer
nate when an open, short, or ground occurs on a specific cir- than 4 years from date of installation.
cuit.
The battery charger is temperature-compensated per battery
manufacturer recommendations. There is no charger voltage
Table 2-5 Testing Circuit Supervision adjustment. At normal room temperature, battery voltage
should be 27-27.6V when the battery set is fully charged. At
Condition Corresponding LEDs higher temperatures, the voltage will be lower. At lower
To create an open: Illuminates the System Trouble temperatures, the voltage will be higher. The battery charger
LED. has a negative temperature coefficient. At higher tempera-
Class A or B Circuit. Disconnect the
“out” wiring from any device. tures, the chemical process in the battery is accelerated. This
means that the ideal charger voltage is lower. Likewise, at
To create a short: Illuminates the System Trouble
LED.
lower temperatures, a higher output voltage is required for
Apply a zero ohm jumper across full charge. Control of battery charge voltage relative to
the IDNet terminal blocks, or across
the loop +/- terminals on a device.
ambient temperature prolongs battery life. The chart below
shows the proper range of battery voltage across the speci-
To create an Earth ground: Illuminates the System Trouble fied operating range of the equipment. The chart is for 12-
LED.
Place a 10K or smaller value resis- cell battery sets, with nominal 24V rating.
tor from supervised wiring to Earth If you have programmed a front
ground. panel or annunciator LED to detect
Earth ground conditions, the pro-
grammed LED also illuminates. Table 2-6 Temperature Effect on Batteries
Refer to “Common LED Applica-
tions” in Chapter 6 of this manual
for information on programming an Min. Max.
Temp Temp V/cell V/cell
Earth Fault LED. Battery Battery
(C) (F) (min) (max)
Voltage Voltage

0 32 2.294 2.367 27.53 28.40


Replacing Lithium Battery
5 41 2.284 2.352 27.41 28.22
The panel uses a lithium battery to maintain non-volatile
10 50 2.274 2.337 27.29 28.04
memory on the panel. In the event of a total power-down
(AC power and lead-acid battery), the lithium battery allows 15 59 2.264 2.322 27.17 27.86
the panel to maintain all historical logs, time/date informa-
22.2 72 2.250 2.300 27.00 27.60
tion, list of disabled points, and the alarm verification tallies.
25 77 2.244 2.292 26.93 27.50
Important Note: The lithium battery must be replaced only 30 86 2.234 2.277 26.81 27.32
by a qualified service technician.
35 95 2.224 2.262 26.69 27.14

Periodic Testing and Maintenance 40 104 2.214 2.247 26.57 26.96

45 113 2.204 2.232 26.45 26.78


The minimum requirements for periodic testing of the fire
alarm system are outlined in chapter 10 of NFPA-72, 2002 49 120.2 2.196 2.220 26.36 26.64
edition. Local codes may require additional testing and
maintenance. All system components must be tested in
accordance with governing codes. Specific details on select
system components are provided below.

Battery Tests
The batteries used with the 4008 FACP are sealed lead-acid
type. Batteries should be installed within six months of the
date of manufacture.

2-17
Chapter 3. Auto-Programming

The Auto-Program option provides the ability to quickly and automati- In This Chapter
cally program the panel’s components and features for general alarm
operation. It automatically scans the serial communication channel, add-
ing any annunciators found, polls the IDNet channel and configures any Configure ALL . . . . . . . . . . . . . . . . . . . . . . . . .3-1
IDNet devices found, and adds any option cards found. Detect New Hardware . . . . . . . . . . . . . . . . . . .3-2
Restore Factory Defaults . . . . . . . . . . . . . . . . .3-2
Edit System Options. . . . . . . . . . . . . . . . . . . . .3-2
Auto-Program can perform the following:
Restore Default System Options . . . . . . . . . . .3-3
• Reconfigure all hardware Saving the Configuration . . . . . . . . . . . . . . . . .3-3
• Add new hardware Default Programming Assignments . . . . . . . . .3-3
• Restore factory defaults
• Edit system option settings

Understand the following when using Auto-Program:


• The panel does not operate as a fire alarm system during Auto-Pro-
gramming.
• Auto-Program performs a IDNet duplicate address search and ter-
minates if duplicate addresses are found.
• DACT information must be manually programmed (i.e. phone
numbers, account information, etc.). Refer to Chapter 5 for infor-
mation on doing this.

Note: Auto-Program is protected at Access Level 4. In order to


perform an Auto-Program operation, the operator must first login
at Access Level 4. Refer to Chapter 1 for information on logging
in to the system.

Refer to “Default Programming Assignments” in this chapter for a


description the default programming assigned to each type of
point.

Configure ALL
This option starts the panel with a new configuration. If a previous con-
figuration is present and this option is selected, it erases the previous
configuration and creates a new one with the currently connected hard-
ware.
1. Press <MENU> to select the main menu.
2. Press <NEXT> or <PREVIOUS> until the [Auto-Program] menu
item is displayed and then press <ENTER>. The following appears:

FIRE ALARM
SUSPENDED

3-1
Chapter 3. Auto-Programming

3. Press <NEXT> or <PREVIOUS> until [CONFIGURE FIRE ALARM


ALL] is displayed, then select it by pressing <ENTER>. SUSPENDED
A warning message appears, indicating that the current
configuration will be deleted. 2. Press <NEXT> or <PREVIOUS> until [RESTORE
4. The display indicates the progress of the Auto Program FACTORY DEFAULT] is displayed, then select it by
operation. When the process is complete, the total num- pressing <ENTER>. A warning message appears, indi-
ber of IDNet devices found during Auto Program dis- cating that the current configuration will be deleted.
plays. 3. The LCD indicates that the factory default configuration
is being recreated, and then the panel automatically
AutoProgram Complete restarts.
Total Devices: 200
RESTORING DEFAULT
5. When <EXIT/CLEAR> is pressed, you are prompted to
save the new configuration or continue editing. Refer to Edit System Options
“Saving the Configuration” later in this chapter.
System Options allow you to set the panel’s automatic func-
Detect New Hardware tions.
1. Press <MENU> to select the main menu and press
This option adds newly found devices and cards to the exist-
<NEXT> or <PREVIOUS> until the [Auto-Program]
ing configuration. It will also change any devices in the con-
menu item is displayed and then press <ENTER>.
figuration that have changed (e.g. photo device changed to a
sounder base photo). FIRE ALARM
1. Press <MENU> to select the main menu and press SUSPENDED
<NEXT> or <PREVIOUS> until the [Auto-Program]
menu item is displayed. Press <ENTER>. 2. Press <NEXT> or <PREVIOUS> until [SYS
OPTIONS] is displayed, then select it by pressing
FIRE ALARM <ENTER>. The first prompt appears similar to the fol-
SUSPENDED lowing:

2. Press <NEXT> or <PREVIOUS> until [DETECT <ENTER>=Accept


NEW] is displayed, then select it by pressing Opt:[Time/Date]
<ENTER>. A warning message appears, indicating that
the current configuration will be changed. 3. For each option, press <ENTER> and then use the
<NEXT> and <PREV> keys to review the options.
3. The display will indicate the progress of the Auto Pro-
Press <ENTER> when the option is set to the appropri-
gram operation. When the process is complete, the total
ate value. Refer to Table 3-1 for information on each
number of IDNet devices found during the Auto Pro-
option.
gram is displayed:
Note: Detailed descriptions for all system options are
AutoProgram Complete
located in Chapter 7 of this manual.
Total Devices: 200
Table 3-1 System Options
4. When <EXIT/CLEAR> is pressed, you are prompted to
save the new configuration or continue editing. Option Settings

Restore Factory Defaults Time/Date Format Choose 12- or 24-hour format

Active Status Choose:


This option restores the 4008 to its original, factory default
Reminder • ON or OFF (default = OFF).
configuration. All custom programming and devices are
• Set reminder interval (1-12 hours;
erased from the configuration.
default = 8)
1. Press <MENU> to select the main menu and press • Set Signal duration (0-60 sec-
<NEXT> or <PREVIOUS> until the [Auto-Program] onds; 0=on until ack; default=5)
menu item is displayed and then press <ENTER>. Alarm Silence/Reset Choose a timer range from 0-60 min-
Inhibit utes (default=0 - no inhibit)

3-2
Chapter 3. Auto-Programming

Table 3-1 System Options When the configuration is saved, the panel will automati-
cally restart and run through its self-test procedure.
Option Settings

Alarm Cutout Timer Choose a timer range from 0-60 min- Default Programming Assignments
utes (default=0 - no cutout)
IDNet and NAC Default Function Types
Door Drop on Alarm Choose a timer range from 0-60 min-
utes (default=0 - immediate) Table 3-2 lists the default function types assigned by the auto
programming process to IDNet and NAC devices. The func-
Door Drop on AC fail Choose a timer range from 0-60 min-
tion type determines the manner in which the device oper-
utes (default=0 - immediate)
ates (i.e., a function type of OTS means the device is on until
Detector Output Selects IDNet device sounder base an alarm silence is performed). The function type is a pro-
coding operation. grammable attribute, and it can be manually changed, as
Depleted Battery Cut- Choose ON or OFF; default = OFF described in Chapter 4 (IDNet) and Chapter 5 (NAC, Relay,
out DACT) of this manual.
Display 1st Alarm Choose ON or OFF; default = OFF Table 3-2 Default Function Type Assignments,
Enable City Circuit Choose ON or OFF; default = OFF IDNet Devices, NACs, and Relays

Enable Expansion Choose ON or OFF; default = OFF Function


Power Device Description
Type

Single Station Selects whether or not sounder base PHOTO SMOKE Smoke Detector
devices operate in single station mode.
SPHOTO SMOKE Smoke Detector with sounder output
Cross Zone Selectable per alarm group. Selects (single-station operation)
whether one alarm or more than one
alarm is required to trigger outputs for RPHOTO SMOKE Smoke Detector with relay (general
that alarm group. alarm operation)

Alarm Groups programmed as Cross IPHOTO SMOKE Smoke Detector with isolator
Zone shall not contain any devices pro-
grammed with the VSMOKE Input HEAT HEAT Heat Detector
Function Type.
SHEAT HEAT Heat Detector with sounder output (sin-
gle-station operation)
Restore Default System Options RHEAT HEAT Heat Detector with relay output (gen-
eral alarm operation)
This option allows the operator to restore the factory-default
options that may have been edited. It will erase any edits that IHEAT HEAT Heat Detector with isolator
were performed in the "Edit System Options" menu, but OHEAT HEAT Rate-of-rise Heat Detector
leave any card/point programming intact.
OSHEAT HEAT Rate-of-rise Heat Detector with
sounder output (single-station opera-
Saving the Configuration tion)

When the Auto-Programming operation is complete, press ORHEAT HEAT Rate-of-rise Heat Detector with relay
the <EXIT/CLEAR> key. The following screen will be dis- output (general alarm operation)
played. OIHEAT HEAT Rate-of-rise Heat Detector with isolator

JOB HAS CHANGED AZONE FIRE Class A General Alarm Fire Monitor
[Cont] Dscrd Save Zone

BZONE FIRE Class B General Alarm Fire Monitor


• Continue Edit. Continue editing the configuration. Zone
• Discard Changes. Discard changes made during the
MON FIRE General Alarm Fire Monitor Zone
programming session and restore the original configura-
tion (if possible). PULL PULL Addressable Manual Pull Station
• Save Job. Save the new job configuration. RELAY OTR General Alarm Relay (on-til-reset)

3-3
Chapter 3. Auto-Programming

Table 3-2 Default Function Type Assignments, • Tone else pulse dialing
IDNet Devices, NACs, and Relays • AC Fail reporting delay is 6 hours
Function
• Reporting format is CID
Device Description
Type • Primary and Secondary Phone Number. There are no
values for the primary and secondary phone numbers or
SIGNAL OTS General Alarm Signal (on-til-reset)
account codes.
ISOL ISOL IDNet loop isolator • The CID Group and CID Point Identifier default to the
SIG1-2 OTS General Alarm Signal (on-til-silence)
IDNet device address.
• Default event codes are shown in Table 3-4.
SIG3-4 OTR General Alarm Signal (on-til-reset)

AUX1 OTR General Alarm Relay (on-til-reset) Table 3-4 Default Event Codes

AUX2 TRBL Trouble Relay (on-til-clear) Default CID


Function Type
Event Code
NAC, Relay, and Signal Circuit Output Mode
SMOKE 111
Assignments
VSMOKE 111
Table 3-3 lists the default output mode (steady, temporal,
etc.) assignments for the NAC, Relay, and Signal circuits. PULL 115
The output mode is a programmable attribute and it can be
FIRE 110
manually changed, as described in Chapter 5 of this manual.
STYLEC 110
Table 3-3 Default NAC, Relay, Signal Circuit Output
Mode Assignments SUPV 200

LATSUPV 200
Circuit Default Output Method
WSO 113
SIG1-2 (NAC) Temporal Code A three pulse coding pattern
consisting of three ½ second pulses, each sep- WATER 113
arated by ½ second silence. Each group of
three pulses is separated by 1.5 seconds of TROUBLE 330
silence.

SIG3-4 (NAC Synchronized. Used with visual NACs. Pro-


grams all visuals to flash simultaneously.

AUX1 & AUX2 Steady on

RELAY Modules Steady on

SIGNAL Mod- Steady on


ules

Annunciator Defaults
Annunciator cards found during the Auto-Program process
are added into the default configuration.
• LCD Annunciators are configured to receive all events.
Refer to Chapter 6 for information on manually pro-
gramming which events are received by the LCD
Annunciator.
• LED Annunciators and 24-I/O modules are not pro-
grammed for default operation.

DACT Defaults
The defaults for the DACT are listed below. Refer to Chap-
ter 5for information on manually programming the DACT.

3-4
Chapter 4. Manually Programming
IDNet Points

NOTICE TO INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES

This product incorporates field-programmable software. In order for the product to comply with the requirements in the Stan-
dard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be
limited to specific values or not used at all as indicated below.

Program Feature or Option Permitted in UL 864? (Y/N) Possible Settings Settings Permitted in UL 864

SMOKE, HEAT, PULL, SMOKE, HEAT, PULL,


DUCT, VSMOKE, FIRE, DUCT, VSMOKE, FIRE,
Input Function Type Y STYLEC, SUPV, LATSUPV, STYLEC, SUPV, LATSUPV,
SO, WSO, WATER, SO, WSO, WATER,
TROUBLE, UTIL TROUBLE

This chapter discusses manually adding, deleting, and editing the In This Chapter
attributes of the panel’s IDNet points.

In most cases, it is recommended that you use the panel’s auto program- Accessing IDNet Programming Menus . . . . . .4-2
ming feature (see Chapter 3) when initially programming the panel, or Adding an IDNet Device. . . . . . . . . . . . . . . . . .4-2
when adding devices to an existing job. Auto programming scans the Editing IDNet Device Attributes . . . . . . . . . . . .4-2
IDNet channel and automatically adds devices that it finds to the job. Deleting an IDNet Point . . . . . . . . . . . . . . . . . .4-8
Once the devices are added, use the manual programming procedures
described in this chapter to adjust the point attributes listed below to
your site-specific needs.

• Hardware Type. Identifies the specific type of device. If auto pro-


gramming was used, the hardware type was automatically set and
does not need to be changed.
• Function Type. Determines the operation of the device by speci-
fying the way in which the system responds when changes occur to
the electrical state of the device. For example, one function type
might define a fire alarm as a current-limited state and another
might define a fire alarm as a short.
• Label. Up to 20 characters can be used to create a custom label for
the point.
• Alarm Group. Allows you to define selective signaling groups if
necessary. Each point can be associated with up to three alarm
groups. An initiating device can only activate outputs (NACs,
relays, etc.) that share the same alarm group assignment.

To manually add, edit, or delete a IDNet point, you must first login at
Access Level 4. Refer to Chapter 1 for information on doing this.

4-1
Chapter 4. Manually Programming IDNet Points

Accessing IDNet Programming Note: Make sure the address shown on the display corre-
sponds to the physical address, set via dip switches, of the
Menus device.
1. Press the <MENU> key. Press <NEXT> or <PREV>
Refer to “Editing IDNet Device” for information on setting
until the [Programming] option is displayed. Press
device attributes.
<ENTER>. The following displays:

FIRE ALARM Editing IDNet Device Attributes


SUSPENDED
Editing Hardware Type
<ENTER> to Program
<EXIT> to resume The hardware type identifies the specific device assigned to
the IDNet address. Table 4-1 and Table 4-2 identify the
2. Press <ENTER>. The Programming menu appears: required hardware types for all IDNet devices and modules.
<ENTER>=Accept 1. Follow the steps outlined in “Accessing IDNet Pro-
Prg:[Points] gramming Menus” earlier in this chapter. Select “Edit”
and then press <ENTER>. The display shows the first
3. Press Enter again. A prompt appears, allowing you to point in the list. For example:
select the type of point to manually edit. By default,
IDNet is the first choice. IDNet: 1
Pull Lobby Door
<ENTER>=Accept
Prg: [IDNet] 2. Use the <NEXT> and <PREV> keys to scroll through
the list of points until the appropriate point is displayed.
4. Press <ENTER>. Press <ENTER>. A prompt similar to the following
appears.
<ENTER>=Accept
IDNet: [Add] IDNet: 1
F: [Hardware Type]
5. Use The <NEXT> and <PREV> keys to scroll through
the following choices and then press <ENTER>. 3. Press <ENTER>. A prompt similar to the following
appears, allowing you to set the Hardware Type.
• Edit- change the characteristics of an existing
IDNet device: IDNet: 1
• Add- add a new IDNet device at an unused address. [ADRPUL]
• Delete- remove a configured IDNet device from the
system. 4. Use the <NEXT> and <PREV> keys to scroll through
the list of available Hardware Types. See the descrip-
Select the operation you want to perform and see the appro- tions in Table 4-1and Table 4-2 for more information.
priate section in this chapter.
Press <ENTER> when the applicable Hardware Type is
displayed. A prompt similar to the following appears,
Adding an IDNet Device asking you to confirm the operation.
Follow the steps outlined in “Accessing IDNet Program- <ENTER>= Confirm
ming Menus.” Select “Add” and then press <ENTER>. The [ADRPUL]
display appears similar to the following.
5. <ENTER> will select the hardware type shown, while
<ENTER>=Accept <EXIT/CLEAR> will return to the previous screen
IDNet: 2 without making any changes
Use the <NEXT> and <PREV> keys to scroll through the
list of device addresses. When the appropriate address is dis-
played, press <ENTER>.

4-2
Chapter 4. Manually Programming IDNet Points

. Table 4-1 Hardware Types for Sensors/Bases


Table 4-1 Hardware Types for Sensors/Bases
Use this
Sensor Base
Use this Hardware
Sensor Base Models Models
Hardware Type
Models Models
Type
4098-9754 4098-9795
4098-9755 4098- 4098-9795C SPHOTO &
4098-9755C 9754C Multi-detector sounder base SHEAT
Two-wire duct base w/o relay See Note 1 and Note 2 below.
Combina-
4098-9792 tion Photo
4098-9792C PHOTO Electric 4098-9796
Detector base w/o remote LED Smoke 4098-9796C PHOTO &
Detector Multi-detector base with LED HEAT
4098-9789 and Heat See Note 2 below.
4098-9714 4098-9789C Detector
4098- Detector base with remote LED
9714C
4098-9756 Note 1. The operation of sounder bases is controlled by
4098-9756C RPHOTO the Single Station system option. See Chapter 7
Photo-
Four-wire duct base with relay of this manual for additional information.
Electric
Smoke 4098-9791
Detector 4098-9791C RPHOTO
Note 2. A multi-detector base, coupled with a combina-
Sensor Detector base with relay tion photo/heat sensor, uses two addresses. Make
sure to set the address on the base to an even
4098-9793
4098-9793C IPHOTO number, and do not set any other device to the
Isolator base address that you set plus one. The even number
represents the Photo portion of the combination
4098-9794
4098-9794C sensor. The address plus one represents the heat
SPHOTO
Sounder base portion of the sensor.
See Note1 below
Note 3. The HEAT, RHEAT, IHEAT, and SHEAT func-
4098-9792
4098-9792C tion types set the heat detector to a fixed sensitiv-
Detector base w/o remote LED
HEAT
ity of 135°F. An alarm is initiated when the
OHEAT temperature rises beyond this temperature.
4098-9789
4098-9789C
4098-9733 Detector base with remote LED The OHEAT, ROHEAT, IOHEAT, and SOHEAT
4098-
4098-9791
function types set the heat detector for rate-of-rise
9733C RHEAT operation. With this hardware type, if the temper-
4098-9791C
ROHEAT
Detector base with relay ature rises beyond 135°F or if the temperature
Heat
Detector 4098-9793 rises at a rate of 15°F per minute, an alarm is ini-
Sensor IHEAT
4098-9793C tiated.
IOHEAT
Isolator base
Table 4-2 Hardware Types, IDNet Modules
4098-9794
4098-9794C SHEAT
Use this
Sounder base SOHEAT
Module Hardware
See Note 1 below.
Type

4090-9007
Zone Individual Addressable Module (IAM) for SIGNAL
Class A or B Signal Circuits

4090-9001
IAM
Supervised Individual Addressable Module (IAM)

4090-9002
RIAM
Indiv. Addressable Module with Relay

4-3
Chapter 4. Manually Programming IDNet Points

Table 4-2 Hardware Types, IDNet Modules IDNet: 1


F: [Hardware Type]
Use this
Module Hardware 3. Use the <NEXT> and <PREV> keys to scroll through
Type the options until [Function] is displayed and then press
4090-9116
ENTER. A prompt similar to the following appears,
ISOL allowing you to select the applicable function.
Addressable Isolator

4090-9101 IDNet: 1
Class B Zone Addressable Module for monitor MBZAM [PULL]
devices

4090-9106 4. Use the <NEXT> and <PREV> keys to scroll through


Class A Zone Addressable Module (ZAM) for MAZAM the list of available function types. The list of displayed
monitor devices function types depends on the hardware type assigned to
4099-9010 Single action pull station
the point.
ADRPUL 5. Press <ENTER> when the appropriate function type is
4099-9012 Dual Action (Push/Pull)
Addressable Pull Stations shown. The system prompts you to confirm the selec-
tion.
Edit IDNet Function Type
<ENTER>= Confirm
The panel’s addressable channel supports the following [PULL]
function types.
6. <ENTER> will select the function in the display, while
• Input function types are used with monitor points. <EXIT/CLEAR> will return to the previous screen
The function type determines the way in which the without making any changes
panel responds to a change in a point’s electrical state.
For example, when you assign the SMOKE function Note: Refer to table at top of Page 4-1 for UL 864 compliant
type to a smoke detector, the system interprets an open options.
on the device as a trouble and a short/abnormal state as
a fire. Refer to Table 4-3 for a list of input function Table 4-3 Input Function Types
types and states.
• Output Function Types are used with notification Function
Device State = Status
Type
appliances and relays (connected via a 4090-9007 Sig-
nal IAM). An output point’s function type determines Normal = NORMAL
the operation of the NAC or relay (e.g., on til silence; on Current-Limited = FIRE
til reset, etc.) Refer to Table 4-4 for a list of output func- Short = FIRE
SMOKE
tion types. Notification appliances and relays controlled Open = TROUBLE
via a 4090-9007 Signal IAM or 4090-9002 Relay IAM Use with smoke detectors.
activate with a steady output; coding of notification
appliances and relays attached to IAMs is not allowed. Normal = NORMAL
Current-Limited = FIRE
Program the input and output function types as follows: Short = FIRE
HEAT
Open = TROUBLE
1. Follow the steps outlined in “Accessing IDNet Pro-
gramming Menus” earlier in this chapter. Select “Edit” Use with heat detectors.
and then press <ENTER>. The display shows the first Normal = NORMAL
point in the list. For example: Current-Limited = FIRE
Short = FIRE
PULL
IDNet: 1 Open = TROUBLE
Pull Lobby Door
Use with pull stations.
2. Use the <NEXT> and <PREV> keys to scroll through
the list of points until the appropriate point is displayed.
Press <ENTER>. A prompt similar to the following
appears.

4-4
Chapter 4. Manually Programming IDNet Points

Table 4-3 Input Function Types Table 4-3 Input Function Types

Function Function
Device State = Status Device State = Status
Type Type

Normal = NORMAL Normal = NORMAL


Current-Limited = FIRE Current-Limited = FIRE
Short = FIRE Short = TROUBLE
DUCT
Open = TROUBLE Open = TROUBLE
STYLEC
Use with Duct detectors. Style-C Fire Alarm Monitor. Used when only cur-
rent limited devices are connected to the zone. A
Normal = NORMAL short circuit is reported as a Trouble.
Current-Limited = VERIFY
Short = FIRE Normal = NORMAL
Open = TROUBLE Current-Limited = SUPERVISORY
Short = SUPERVISORY
If a smoke detector with the function type SUPV Open = TROUBLE
VSMOKE enters a current-limited state, the
panel’s alarm verification cycle begins. The panel Used to monitor any supervisory type device
starts a delay timer of 30 seconds. When the where operator acknowledgment is required.
timer expires, the zone containing the activated
detector is reset. Following the reset, another 10 Normal = NORMAL
second timer starts. When the 10 second timer Current-Limited = SUPERVISORY
expires, the system checks the device for an Short = SUPERVISORY
alarm. If a current-limited condition exists on the LATSUPV Open = TROUBLE
device, the panel initiates a fire alarm. If no cur-
VSMOKE Generic supervisory monitor - latches until a sys-
rent-limited condition exists, the panel starts a 2
minute timer. While the timer is counting down, tem reset occurs.
any current-limited condition on any other device
Normal = NORMAL
will trigger a fire alarm.
Current-Limited = SUPERVISORY
Short = SUPERVISORY
A short from a pull-station always triggers an
Open = TROUBLE
alarm condition, regardless of the alarm verifica-
SO
tion cycle.
Used to indicate abnormal sprinkler conditions,
such as the opening of a PIV or OS&Y tamper-
At any stage of the alarm verification cycle, the
switch. Must be used with normally open contacts
presence of two devices in alarm triggers an
only.
alarm condition.
Normal = NORMAL
Note: The VSMOKE function type shall not be
Current-Limited = SUPERVISORY
enabled for Canadian applications. Short = FIRE (water flow)
Open = TROUBLE
Normal = NORMAL
Current-Limited = FIRE
Combination Waterflow/Sprinkler Monitor (NO).
Short = FIRE WSO
Where permitted by the AHJ, this circuit
Open = TROUBLE
monitors both waterflow sensors and PIV/OS&Y
tampers on the same circuit. All tamper switches
This is a generic fire alarm point type. A typical
(N.O. contacts) must be connected with a listed
FIRE application for this point type is a fire alarm
current limiting resistor. A short condition indi-
zone containing more than one type of device.
cates waterflow alarms.
For example, when a combination of smoke
detectors, pull stations, waterflow monitors, and Normal = NORMAL
heat detectors is connected to an IAM or Current-Limited = FIRE (water flow)
ZAM, this point type allows alarms to report as
Short = FIRE (water flow)
originating from a zone. WATER
Open = TROUBLE

Use with normally open waterflow monitors.

4-5
Chapter 4. Manually Programming IDNet Points

Table 4-3 Input Function Types Table 4-4 Output Function Types

Function Function
Device State = Status Description
Type Type

Normal = NORMAL Relay typically provides 24V power to larger door


Current-Limited = TROUBLE holder relay with separate power source. Relay
Short = TROUBLE DHOLDER activates on general alarm and signals door holder
TROUBLE
Open = TROUBLE relay to cut power to door holder magnets.

Generic trouble monitor.


NAC Function Types
Normal = OFF Use for 4090-9007 Signal Individual Addressable Module (IAM).
Current-Limited = ON Note: Notification appliances attached to a Signal IAM cannot be
Short = ON coded. Output is always steady.
Open = TROUBLE
QALERT Not Applicable - cannot be used with IDNet output.
A utility initiating device requires the following
General Alarm (on til-silence). Use for NAC circuits
programming:
UTIL containing only audible devices.
• IDC must be in same alarm group as utility
NAC. SSIG Compatible audible-only devices include:
• IDC must be assigned a Utility function type.
Typically used for process monitoring function. • 4901-9820, wall-mount, red, horn only.
For example, a relay on a machine is tied to the
IDC. When the relay activates, the utility IDC acti-
vates and triggers the utility NAC. General Alarm (on steady-til-reset). Use for NAC
circuits containing visual-only devices.

Compatible devices include the following:


Table 4-4 Output Function Types
RSIG
• 4906-9101, wall-mount, visual-only, red
Function • 4906-9102, ceiling-mount, visual-only, red
Description
Type • 4906-9103, wall-mount, visual-only, white
• 4906-9104, ceiling-mount, visual-only, white
Relay Function Types
(Use for 4090-9002 Indiv. Addressable Module with Relay)
NAC activates when there is a supervisory condi-
Relay activates steady on general alarm; turns off SUPV tion active in the system. NAC is on until supervi-
SRELAY
when alarm silence occurs. sory condition is acknowledged.

Relay activates steady on general alarm; turns off NAC activates when there is a trouble condition
RRELAY
when system reset occurs. TRBL active in the system. NAC is on until trouble condi-
tion is acknowledged.
Relay activates steady when there is a supervisory
SUPV condition active in the system. Relay is on until AUXPWR Not Applicable - cannot be used with IDNet output.
supervisory condition is acknowledged.
AVS44 Not Applicable - cannot be used with IDNet output.
Relay activates steady when there is a trouble
TRBL condition active in the system. Relay is on until MDL Not Applicable - cannot be used with IDNet output.
trouble condition is acknowledged.

AUXPWR Not Applicable - cannot be used with IDNet output.


Note: Elevator recall requires the following:
• The relay must have a function type of Primary or Alter-
Relay activates on general alarm. Relay is tied to
PRIMARY nate and must be wired to the appropriate elevator con-
Primary Elevator Recall contacts. See Note below.
trol contact.
Relay activates on general alarm. Relay is tied to • The initiating devices used to trigger elevator recall
ALTERN Alternate Elevator Recall contacts. See Note
below.
must be associated with the following alarm groups.
- Alarm Group 98. Associate all zones used to recall
Relay provides 24V power to four wire detectors.
the elevator to the primary floor in this alarm
DRESET Relay turns off for 5 secs on system reset)
group.

4-6
Chapter 4. Manually Programming IDNet Points

- Alarm Group 99. Associate all zones used to recall The following is a list of all words in the library.
the elevator to the alternate floor in this alarm
group. Table 4-5 Word Library

Editing Point Labels


1. Follow the steps in “Accessing Menus”. Make sure to Default of blanks 5th Floor
choose IDNet as the type of device to program.
North Flr_1 Garage
<ENTER>=Accept
South Flr_2 Hallway
Prg: [IDNet]
East Flr_3 HVAC_Room
2. Press <ENTER>. The top line shows the custom label
assigned to the first IDNet point. Use the <NEXT> and West Flr_4 Kitchen
<PREV> keys to scroll through the list of points.
Front Flr_5 Lobby
3. Press <ENTER> when the appropriate point is dis-
Centr RM __ Office
played. A prompt appears, asking you to specify the
function type. Use the <NEXT> and <PREV> keys to rear Basement Patient
scroll through the choices until <Edit Label> appears.
upper Boiler_RM Restroom
IDNet1
lower Classroom Room
Fn: [Edit Label]
main Closet__ Stairway
4. Press <ENTER>. A cursor appears beneath the leftmost
letter of the currently assigned custom label. Use the left first Corridor Storeroom
and right arrow keys to move the cursor between letters.
2nd Elect_RM Wing

You can edit a label in one of three ways: 3rd Elevator Zone
• Using the Keypad. Press the alphanumeric key cor- 4th Entrance
responding to the letter you want. For example, for
the letter “C”, press the “2” key on the keypad three
times. Use the left and right arrow keys to move to 5. Pressing <ENTER> saves the current label. Pressing
the next letter in the label. <EXIT/CLEAR> will quit label editing without saving.
• Use the <NEXT> and <PREV> keys. Each time Clear Point Label
you press the <NEXT> key, the display advances to
the next character. Likewise, each press of the The "Clear Point Label" menu performs the same function as
<PREV> key moves backward one character. Use "Edit Point Label" described above except that it clears the
the left and right arrow keys to move to the next let- point's currently assigned label first.
ter in the label.
• Use the Word Library, which is a stored list of com- Alarm Group
mon words sorted alphabetically. Press the
The Alarm Group programming choice allows you to per-
<FUNCTION> key on the front panel. A prompt
form input-output (selective signaling) programming in a
similar to the following appears.
fast, flexible manner. The Alarm Group concept allows the
IDNet1 activation of a particular input to control a specific set of
<FUNC> = Word Library outputs. An IDC can be in up to three different Alarm
Groups. For additional details on Alarm Groups and their
To jump to a word, press the alphanumeric key cor- operation, refer to “Programming Overview” in Chapter 1.
responding to the first letter in the word. For exam-
ple, to use the word Floor, press the “3” key When the Alarm Group choice is selected the following
repeatedly until Floor appears. screen showing the point's custom label and the currently
assigned Alarm Groups is displayed:

IDNet:1
ALM GRP: [00] 00 00

4-7
Chapter 4. Manually Programming IDNet Points

The right and left arrow keys allow you to move the focus
brackets to a different alarm group, while the <NEXT> and
<PREV> keys allow you to select the desired group number.
Pressing <ENTER> will accept any changes made and exit,
and the <EXIT/CLEAR> key will quit the alarm group edit
without saving.

Deleting an IDNet Point


This menu selection allows you to manually delete a specific
IDNet device from the job configuration. All programming
associated with that point (e.g. Annunciator programming)
will also be deleted.

4-8
Chapter 5. Manually Programming NACs,
Relays, and DACT

NOTICE TO INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES

This product incorporates field-programmable software. In order for the product to comply with the requirements in the Stan-
dard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be
limited to specific values or not used at all as indicated below.

Program Feature or Option Permitted in UL 864? (Y/N) Possible Settings Settings Permitted in UL 864

SSIG, RSIG, SUPV, TRBL, SSIG, RSIG, SUPV, TRBL


NAC Function Type Y
UTILITY

SRELAY, RRELAY, SUPV, SRELAY, RRELAY, SUPV,


TRBL, UTILITY, PRIMARY, TRBL, PRIMARY, ALTERN,
Relay Function Type Y
ALTERN, DRESET, DRESET, DHOLDER
DHOLDER

Manually programming NAC, programmable relay, and DACT points In This Chapter
allows you to set the attributes of the point to the specific values
required for the job. You can create a custom label for each point,
change the way in which the NACs, programmable relays, and DACT Accessing Menus . . . . . . . . . . . . . . . . . . . . . . 5-2
operate, or add a NAC or relay to an alarm group for selective signaling. Programming NACs . . . . . . . . . . . . . . . . . . . . 5-2
Programming AUX Relays . . . . . . . . . . . . . . . 5-4
It is recommended that you use the panel’s auto programming feature Programming DACT. . . . . . . . . . . . . . . . . . . . 5-6
Accessing DACT Menu . . . . . . . . . . . . . . . . . 5-6
(see Chapter 3) when initially programming the panel, or when adding
Programming DACT Options . . . . . . . . . . . . . 5-7
devices to an existing job. Auto programming automatically programs
Programming Contact ID (CID) Points . . . . . . 5-9
the NACs, Relays, and DACT with default values. You can then use the Programming Event Codes . . . . . . . . . . . . . 5-10
manual programming procedures described in this chapter to adjust the Saving Changes. . . . . . . . . . . . . . . . . . . . . . 5-11
following values.

• Hardware Type. Identifies the specific type of device.


• Function Type. Determines the operation of the point. For a NAC or
relay, you can set whether the device turns off on silence or reset,
etc.
• Label. Up to 20 characters can be used to create a custom label for
the point.
• Alarm Group. Applies to NACs and Relays. Allows you to define
selective signalling groups. Each NAC or Relay point can be asso-
ciated with up to three alarm groups, allowing you to specify which
initiating devices are allowed to activate the device.

To manually add, edit, or delete a point, you must first login at Access
Level 4. Refer to Chapter 1 for information on doing this.
If an Expansion Power Supply Module is installed in the system, you
must first set the Expansion Power Supply system option to ON before

5-1
Chapter 5. Manually Programming NACs, Relays, and DACT

programming NACs. Refer to Chapter 7 - “Manually Pro- • Alarm Group


gramming System Options” for information on doing this.
Setting NAC Function Type and Coding Pattern
Accessing Menus The Function Type determines the way in which the NAC
operates (whether it is an audible, visual, relay, etc.) and its
Use the following steps to gain access to the NAC and relay output method (steady, etc.)
menus.
1. Follow the steps in “Accessing Menus”. Make sure to
1. Press the <MENU> key. Press <NEXT> or <PREV> choose NAC as the type of device to program.
until the [Programming] option is displayed. Press
<ENTER>. The following displays: <ENTER>=Accept
Prg: [NAC]
FIRE ALARM
SUSPENDED 2. Press <ENTER>, and then use <NEXT> and <PREV>
keys to choose the circuit (NAC1, NAC2, NAC3, or
<ENTER> to Program NAC4) to program.
<EXIT> to resume
NAC1
2. Press <ENTER>. The Programming menu appears. Signal 1/4
[Points] is the default selection, which allows you to
make changes to a specific point’s programming. 3. Press <ENTER> when the appropriate NAC is dis-
played. A prompt appears, asking you to specify the
<ENTER>=Accept NAC function type.
Prg:[Points]
NAC1
3. Press <ENTER>. A prompt appears, allowing you to Fn: [Function]
select the type of point to manually edit. By default,
[IDNet] is the first choice. 4. Press <ENTER>. As shown in the example below, the
NAC function type is comprised of two parts -- the
<ENTER>=Accept function (On Till Silence, On Till Reset, etc.) and the
Prg:[IDNet] coding pattern (temporal, 120 BPM, etc.)

4. Possible choices for this prompt are listed below. Use NAC1
the <NEXT> and <PREV> keys to scroll to the appro- [SSIG] TEMPRL
priate choice and then press <ENTER>.
• NAC 5. Use the <NEXT> and <PREV> keys to select the
appropriate Function. Use the right and left arrow keys
• RELAY (Use for panel’s on-board AUX relays)
to move the cursor between the function type and the
Select the operation you want to perform and see the appro- coding pattern. Use the <NEXT> and <PREV> keys to
priate section in this chapter. set the pattern to the appropriate choice.
6. Pressing <ENTER> will accept any changes made and
Programming NACs exit, and the <EXIT/CLEAR> key quits editing without
saving
Use the following procedure to edit the programming of the
Note: Refer to the table located at the top of Page 5-1 for UL
two Notification Appliance Circuits (NACs) on the base
864 compliant options.
panel, or the two optional NACs on the expansion power
supply. NACs cannot be added or deleted, only edited.

NAC editing provides the following options:


• Edit Function, which defines the following for a NAC:
- When the NAC activates and deactivates
- The "output method" used by the NAC when it acti-
vates (coded, steady, etc.)
• Edit Point Label

5-2
Chapter 5. Manually Programming NACs, Relays, and DACT

. Table 5-1 NAC Function Types

Table 5-1 NAC Function Types Function


Description
Type
Function
Description NAC activates when an initiating device with the
Type
following attributes activates:
General Alarm Horn/Strobe (horn on-til-silence;
strobe on-til-reset). Use for NAC circuits containing • IDC must be in same alarm group as utility NAC.
both horns and strobes. • IDC must be assigned a Utility function type.
UTILITY

Compatible visual-only devices include: Typically used for process monitoring function. For
• 4906-9101, wall-mount, visual-only, red example, a relay on a machine is tied to the IDC.
• 4906-9102, ceiling-mount, visual-only, red When the relay activates, the utility IDC activates
• 4906-9103, wall-mount, visual-only, white and triggers the utility NAC.
• 4906-9104, ceiling-mount, visual-only, white
Table 5-2 NAC Operation Settings
Compatible A/V devices include:
QALERT
• 4906-9127, wall-mount, red
• 4906-9128, ceiling-mount, red Operation Description
• 4906-9129, wall-mount, white
Standard Temporal coded pattern. A three pulse
• 4906-9130, wall-mount, red
coding pattern consisting of three ½ second
Temporal pulses, each separated by ½ second silence. Each
Compatible audible-only devices include:
group of three pulses is separated by 1.5 seconds
of silence.
• 4901-9820, wall-mount, red, horn only. Horn
must be selected for two-wire horn strobe con-
Generates synchronization pulse for visual-only
trol. See Horn Instruction manual.
NAC circuits that use the following visual-only
devices.
General Alarm (on til-silence). Use for NAC circuits Synch
containing only audible devices. • 4906-9101, wall-mount, visual-only, red
• 4906-9102, ceiling-mount, visual-only, red
• 4906-9103, wall-mount, visual-only, white
SSIG Compatible audible-only devices include:
• 4906-9104, ceiling-mount, visual-only, white
• 4901-9820, wall-mount, red, horn only.
Steady Steady On

20 BPM Slow March Time - 20 beats per minute


General Alarm (on steady-til-reset). Use for NAC
circuits containing visual-only devices.
Editing Point Label
Compatible devices include:
RSIG This option allows you to assign a 40-character custom label
• 4906-9101, wall-mount, visual-only, red to each NAC point.
• 4906-9102, ceiling-mount, visual-only, red
• 4906-9103, wall-mount, visual-only, white 1. Follow the steps in “Accessing NAC and Relay
• 4906-9104, ceiling-mount, visual-only, white Menus”. Make sure to choose NAC as the type of
device to program.
NAC activates when there is a supervisory condi-
SUPV tion active in the system. NAC is on until supervi- <ENTER>=Accept
sory condition is cleared. Prg: [NAC]
NAC activates when there is a trouble condition
TRBL active in the system. NAC is on until trouble condi-
2. Press <ENTER>, and then use <NEXT> and <PREV>
tion is acknowledged. keys to choose the circuit (NAC1, NAC2, NAC3, or
NAC4) to program.

NAC1
Signa1 1/4

3. Press <ENTER> when the appropriate NAC is dis-


played. A prompt appears, asking you to specify the
NAC function type.

5-3
Chapter 5. Manually Programming NACs, Relays, and DACT

NAC1 NAC1
FN: [Function Type] Fn: [Alarm Groups]

4. Use the <NEXT> and <PREV> keys until <Edit Label> 5. Press <ENTER>. A prompt similar to the following
is displayed. For example: appears.

NAC1 ALARM GROUPS


Fn: [Edit Label] [99] 00 00

5. Press <ENTER>. The current custom label for the point 6. Use the <NEXT> and <PREV> keys to scroll the num-
is displayed on the top line of the display. A cursor is ber in the brackets. Use the right and left arrow keys to
shown below the selected character in the label. Use the move between the alarm groups. Press <ENTER> when
right and left arrow keys to move the cursor to a differ- all the values are set correctly.
ent character to edit; use the <NEXT> and <PREV>
keys to scroll through the characters. Programming AUX Relays
6. Pressing the <ENTER> key will save the current label,
and <EXIT/CLEAR> will quit label editing without Aux Relay programming allows you to define the following
saving. options:
• Function, defines the following for a relay.
Clear Point Label - When the Relay activates and deactivates.
The "Clear Point Label" menu performs the same function as - The "output method" that defines how the Relay
"Edit Point Label" described above except that it clears the activates (coded, steady, etc.)
point’s currently assigned label first. • Edit or Clear Point Label. Allows you to set a 40 char-
acter label for the relay point.
Editing Alarm Groups • Alarm Group. Allows you to associate the relay with up
Alarm groups allow you to program selective signaling. to 99 groups of initiating devices, providing the ability
Assign the NAC an alarm group number from 1 to 99. to perform selective activation of the relay.
Assign the same alarm group number to the initiating
1. Follow the steps in “Accessing Menus.” Make sure to
device(s) that you want to control the NAC. Each NAC can
choose Relay as the type of device to program.
be in up to three groups.
1. Follow the steps in “Accessing Menus”. Make sure to <ENTER>=Accept
choose NAC as the type of device to program Prg: [Relay]

<ENTER>=Accept 2. Press <ENTER>, and then use <NEXT> and <PREV>


Prg: [NAC] to choose the relay to program.

2. Press <ENTER>, and then use <NEXT> and <PREV> AUX1


keys to choose the circuit (NAC1, NAC2, NAC3, or Alarm 1/2
NAC4) to program.
3. Press <ENTER> when the appropriate relay is dis-
NAC1 played. A prompt appears, asking you to specify the
Signal 1/4 relay function type.

3. Press <ENTER> when the appropriate NAC is dis- AUX1


played. A prompt appears, asking you to specify the FN: [Function]
NAC function type.
4. Press <ENTER>. The display appears similar to the fol-
NAC1 lowing. As shown in the example below, the function
FN: [Function Type] type is comprised of two parts -- the function (On Till
Trouble Relay, On Till Reset, etc.) and the coding pat-
4. Use the <NEXT> and <PREV> keys until [Alarm tern (Steady, 120 BPM, etc.)
Groups] is displayed. For example:
AUX1
[OTR] STEADY

5-4
Chapter 5. Manually Programming NACs, Relays, and DACT

5. Use the <NEXT> and <PREV> keys to select the


appropriate Function. Use the right arrow key to move Table 5-4 Relay Operation Settings
the cursor to the coding pattern, and then use the
<NEXT> and <PREV> keys to set the pattern. Operation Description

6. Pressing <ENTER> will accept any changes made and Standard Temporal coded pattern. A
exit. <EXIT/CLEAR> key will quit the alarm group edit three pulse coding pattern consisting
without saving. of three ½ second pulses, each sepa-
Temporal rated by ½ second silence. Each
Note: Refer to the table located at the top of Page 5-1 for UL group of three pulses is separated by
864 compliant options. 1.5 seconds of
silence.
Table 5-3 Relay Function Types Steady Steady On

Function SYNCH N/A - Do not use


Description
Type
Slow March Time - 20 beats per
20 Bpm
Relay activates on general alarm; minute.
SRELAY
remains on-til-silence.

Relay activates on general alarm;


Note: Elevator recall requires the following:
RRELAY
remains on-til-reset. • The relay must have a function type of Primary or Alter-
nate and must be wired to the appropriate elevator con-
Relay activates when a Supervisory
SUPV condition occurs; remains on-til- trol contact.
cleared. • The initiating devices used to trigger elevator recall
Relay activates when a Trouble con-
must be associated with the following alarm groups.
TRBL dition occurs; remains on-til-acknowl- - Alarm Group 98. Associate all zones used to recall
edge. the elevator to the primary floor with this alarm
Relay activates when a utility IDC in group.
Utility
the same alarm group activates. - Alarm Group 97. Associate all zones used to recall
PRIMARY Relay activates on general alarm.
the elevator to the alternate floor with this alarm
See Note Relay is tied to Primary Elevator group.
Below Recall contacts.
Editing Point Label
ALTERN Relay activates on general alarm.
See Note Relay is tied to Alternate Elevator This option allows you to assign a 40-character custom label
Below Recall contacts.
to each relay point.
Relay provides 24V power to four
DRESET wire detectors. Relay turns off for 5
1. Follow the steps in “Accessing Menus”. Make sure to
secs on system reset. choose Relay as the type of device to program.

Relay typically provides 24V power to <ENTER>=Accept


larger door holder relay with separate Prg: [RELAY]
power source. Relay activates on
DHOLDER
general alarm and signals door
holder relay to cut power to door
2. Press <ENTER>, and then use <NEXT> and <PREV>
holder magnets. keys to choose the relay (AUX1, AUX2, etc.) to pro-
gram.

AUX1
Alarm 1/2

3. Press <ENTER> when the appropriate relay is dis-


played. A prompt appears, asking you to specify the
relay’s hardware type.

AUX1
FN: [Hardware Type]

5-5
Chapter 5. Manually Programming NACs, Relays, and DACT

4. Use the <NEXT> and <PREV> keys until <Edit Label> 2. Press <ENTER>. The Programming menu appears.
is displayed. For example:
<ENTER>=Accept
AUX1 Prg:[Points]
Fn: [Edit Label]
3. Press <NEXT> or <PREV> until DACT is shown.
5. Press <ENTER>. The current custom label for the point
<ENTER>=Accept
is displayed on the top line of the display. A cursor is
Prg: [DACT]
shown below the selected character in the label. Use the
right and left arrow keys to move the cursor to a differ- 4. Press <ENTER>. The following prompt appears.
ent character to edit; use the <NEXT> and <PREV>
keys to scroll through the characters. <ENTER>=Accept
DACT: [Options]
Pressing the <ENTER> key will save the current label, and
5. Use the <NEXT> and <PREV> keys to select one of the
<EXIT/CLEAR> will quit label editing without saving.
following choices.
Clear Point Label • Options. This choice allows you to program a wide
range of DACT parameters. (supervising station
The "Clear Point Label" menu performs the same function as
phone numbers and account codes, dialing mode,
"Edit Point Label" described above except that it clears the
communications format, etc.). Refer to “Program-
point’s currently assigned label first.
ming DACT Options” below for specific informa-
tion.
Programming DACT
Note: If no DACT is installed, use this option to
The panel’s DACT (Digital Alarm Communicator Transmit-
disable the DACT. See “Programming DACT
ter) allows the panel to use one or two telephone lines to call
Options,” below for more information.
a supervising station and report a local alarm, trouble, or
supervisory condition. • Event Codes. The 3/1, 4/2, BFSK, and SIA com-
munication formats support per-event reporting of
This section describes programming the DACT options to fire alarms, trouble conditions, etc. With these for-
specify the characteristics of the DACT’s phone connection, mats, the supervising station receives a general
communication format, and the format of the event or CID code for an event type that does not specify the
codes used by the supervising station. activated point.

Login at Level 4 before starting DACT programming. See Use this choice to verify and edit the codes for each
Chapter 1 for information on doing this. event type. Refer to “Programming Event Codes,”
below for more information.
Note: The <Exit/Clear> key is used to back out of menus or
displays and return to the top-level menu structure. Where Note: Only the 3/1 and 4/2 formats allow editing of
possible, the <Exit/Clear> key backs out one level at a time. event codes.
There are cases, however, that the Exit/Clear key will return
• CID Points. The Contact ID communication for-
the operator directly to the top-level menu.
mat supports per-point reporting of system events.
The supervising station receives a code identifying
Accessing DACT Menu the point and the event type (alarm, trouble, etc.).
With this format, the DACT can also send a resto-
1. Press the <MENU> key. Press <NEXT> or <PREV> ral code to the supervising station after the device
until the [Programming] option is displayed. Press experiencing the alarm, trouble, or supervisory
<ENTER>. The following displays: condition is restored to a normal state. Use this
choice to verify and edit the activation and restoral
FIRE ALARM
codes for each point. Refer to “Programming Con-
SUSPENDED
tact ID (CID) Event Codes,” below for more infor-
<ENTER> to Program mation.
<EXIT> to resume

5-6
Chapter 5. Manually Programming NACs, Relays, and DACT

Programming DACT Options use when setting the primary and secondary phone num-
bers.
1. Follow the steps in “Accessing DACT Menu”. Make • B -- Use if it is necessary to input a DTMF (touch-
sure to choose Options as the type of device to program. tone) asterisk (*) into the phone number.
<ENTER>=Accept • C -- Use if it is necessary to input a DTMF pound
DACT: [Options] sign (#) into the phone number.
• D -- Inserting this character into the phone number
Enabling/Disabling DACT causes a 3 second delay at the point at which the D
1. Press <ENTER> at the DACT: [Options] prompt. The appears.
following prompt appears, allowing you to enable or - E -- This character causes the DACT to wait two
disable the DACT. seconds for a secondary (outside line) dial tone. It
may be necessary to use this character if you must
<ENTER>=Accept dial a specific number (9, for example) to get an
Opt: [Enable DACT] outside line on the phone system. For example, 9E
would cause the DACT to request an outside line
2. Press <ENTER>. The following appears.
and then wait 2 seconds for the secondary dial tone
Enable DACT before proceeding with the rest of the phone num-
[OFF] ber. If you use the “E” special character, make sure
to set the Dial Mode to Tone; do not use Tone
3. Use the <NEXT> or <PREV> keys to change the set- else Pulse.
ting to ON.
3. Press <ENTER>. The prompt shown in Step 1 reap-
By default, the DACT is enabled, but unconfigured. The pears.
DACT will report a configuration trouble until the 4. Press the <NEXT> key. The prompt for the primary
phone numbers and account numbers are programmed, account number appears.
or until it is disabled if it will not be used.
4. Press <ENTER>. A prompt appears, asking you to con- Setting Primary Account Number
firm the choice. The primary account number is a unique identifier assigned
and used by the supervising station.
5. Press <ENTER> to confirm the selection. The prompt
shown in Step 1 reappears. Use the <NEXT> key to Pri Account #
move to the prompt for primary phone number. [0] 000
Setting Primary Phone Number 1. Use the arrow keys to move the cursor from one number
The next prompt allows you to set the Primary Phone Num- to another. Use the NEXT and PREV keys or the key-
ber of the supervising station. This is the number that the pad to enter each number.
DACT dials first.
2. Press <ENTER> when the number is correctly entered.
<ENTER>=Accept A prompt appears asking you to confirm the number
Opt: [Pri Phone #] that you entered.

1. Press <ENTER>. The following prompt appears. 3. Press <ENTER>. The prompt shown above Step 1 reap-
pears.
Pri Phone # 4. Press the <NEXT> key. The prompt for the Secondary
[X] XXXXXXXXXXXXXXXX Phone Number appears.
2. Use the arrow keys to move the cursor from one digit to
Setting Secondary Phone Number
another. Use the keypad numbers, or use the NEXT and
PREV keys to enter each number. Press <ENTER> The Secondary Phone Number specifies the alternate phone
when the number is correctly entered. A prompt appears number that the DACT can use if attempts to dial the pri-
asking you to confirm the number that you entered. mary phone number fail.

Note: The following special characters are available for Note: You can also use the special characters B, C, D, and E
when specifying the Secondary Phone Number. See the

5-7
Chapter 5. Manually Programming NACs, Relays, and DACT

description of these characters in the section “Setting Pri- and tone else pulse (attempt to dial with a touchtone for-
mary Phone Number” above. mat and if that fails, use a pulse format).

<ENTER>=Accept 3. Press <ENTER> to accept the choice. A prompt appears


Opt: [Sec Phone #] asking you to confirm the choice.

1. Press <ENTER>. The following prompt appears. 4. Press <ENTER>. The prompt shown above Step 1 reap-
pears.
Sec Phone # 5. Press the <NEXT> key. The prompt for the Pulse Rate
[X] XXXXXXXXXXXXXXXX appears.
2. Use the arrow keys to move the cursor from one digit to
another. Use the keypad numbers, or use the NEXT and Setting Pulse Rate
PREV keys to enter each number. Press <ENTER> The Pulse Rate option specifies the pulse rate used with
when the number is correctly entered. A prompt appears either the 3/1 or 4/2 pulse format. This option does not apply
asking you to confirm the number that you entered. to other formats.
3. Press <ENTER> again. The prompt shown above Step 1 <ENTER> = Accept
reappears. Pulse Rate
4. Press the <NEXT> key. The prompt for the Secondary
Account Number appears. 1. Press <ENTER>.

Setting Secondary Account Number Pulse Rate


[20 PPS]
The secondary account number is a unique identifier
assigned and used by the supervising station. 2. Use the NEXT and PREV keys to move from one
choice to another. Choices are 20 pulses per second
Sec Account # (PPS), which is the default, and 10 PPS.
[0] 000
3. Press <ENTER> to accept the choice. A prompt appears
1. Use the arrow keys to move the cursor from one number asking you to confirm the choice.
to another. Use the NEXT and PREV keys or the key-
4. Press <ENTER>. The prompt shown above Step 1 reap-
pad to enter each number.
pears.
2. Press <ENTER> when the number is correctly entered.
5. Press the <NEXT> key. The prompt for the Pulse Fre-
A prompt appears asking you to confirm the number
quency appears.
that you entered.
3. Press <ENTER>. The prompt shown above Step 1 reap- Setting Pulse Frequency
pears. The pulse frequency specifies the frequency (in KHz) of the
4. Press the <NEXT> key. The prompt for setting the dial- pulses used by the DACT.
ing mode appears.
<ENTER> = Accept
Setting Dialing Mode Opt: [Pulse Freq]

The dialing mode specifies the type of phone line being used 1. Press <ENTER>.
by the DACT.
Pulse Freq
<ENTER> = Accept [1.9KHz Data]
Dialing Mode
2. Use the NEXT and PREV keys to move from one
1. Press <ENTER>. choice to another. Choices are

Dialing Mode 1.9 KHz


[Tone else Pulse] 1.8 KHz

2. Use the NEXT and PREV keys to move from one 3. Press <ENTER> to accept the choice. A prompt appears
choice to another. Choices are tone (touchtone), pulse, asking you to confirm the choice.

5-8
Chapter 5. Manually Programming NACs, Relays, and DACT

4. Press <ENTER>. The prompt shown above Step 1 reap- AC Fail Delay
pears. The AC Fail Delay allows you to specify the interval
5. Press the <NEXT> key. The prompt for the Reporting between power loss at the panel and when the DACT noti-
Format appears. fies the supervising station of the power loss. AC fail delay
is selectable from 0-24 hours.
Reporting Format
Before you select the Communications Format Code, deter-
AC Fail Delay
mine, from an authorized person at the supervising station,
[06] Hrs
the required reporting format.
1. Use the NEXT and PREV keys to move from one
<ENTER> = Accept
choice to another ( 0-24 hours).
Opt: [Report Format]
2. Press <ENTER> to accept the choice. A prompt appears
1. Press <ENTER>. The following prompt appears. asking you to confirm the choice.

Report Format 3. Press <ENTER>. The prompt shown above Step 1 reap-
[Contact ID] pears.
4. Press the <NEXT> key. The prompt for the Test Report
The DACT can report in any of the following communi-
Time appears.
cation formats.
• 3/1 pulse = Three-digit account code followed by Test Report Time
one-digit reporting code, double round at 20 pulses
This option specifies the time at which the Test Report Event
per second (PPS). Allows programmable reporting
is sent to the supervising station. Time is set in 24 hour, mil-
codes. Refer to “Programming Event Codes” later
itary, format.
in this chapter.
• 4/2 pulse = Four-digit account code followed by <ENTER> = Accept
two-digit reporting code, double round at 20 PPS. Opt: [Test Rpt Time]
Allows programmable reporting codes. Refer to
“Programming Event Codes” later in this chapter. 1. Press <ENTER>.
• BFSK = Three-digit account code followed by
Test Rpt Time
two-digit reporting code, single transmission of
[02] : 00
constant tones. Features built-in error checking and
fixed reporting codes. 2. Use the NEXT and PREV keys to increment or decre-
• SIA = Level 1 compatibility. Four-digit account ment the hour setting (two digits on left). Use the right
code features tonal acknowledge, basic reports, and arrow key to move the cursor to the minutes (two digits
fixed reporting codes. on right). Use the NEXT and PREV keys to increment
• Contact ID (Default). Uses a four digit account or decrement the minutes setting.
code, followed by a two- digit group number and 3. Press <ENTER> to accept the choice. A prompt appears
three digit contact number. asking you to confirm the choice.
2. Use the NEXT and PREV keys to move from one 4. Press <ENTER>. The prompt shown above Step 1 reap-
choice to another. pears.
3. Press <ENTER> to accept the choice. A prompt appears 5. Press the <EXIT/CLEAR> key. The prompt for setting
asking you to confirm the choice. DACT options reappears. Press the <NEXT> key to
4. Press <ENTER>. The prompt shown above Step 1 reap- access either the CID Points or Event Codes menus.
pears.
5. Press the <NEXT> key. The prompt for the AC Fail Programming Contact ID (CID)
Delay appears. Points
Follow the procedure below only if the DACT is using the
Contact ID (CID) reporting format. CID reporting format
requires you to specify the group and Contact ID for each

5-9
Chapter 5. Manually Programming NACs, Relays, and DACT

point, but there is no need to specify the type of event with <ENTER>=Accept
the CID format. This information is automatically derived DACT: [Event Codes]
from the point’s function type.
2. Press <ENTER>. A prompt similar to the following
Note: Default CID point values are provided in the panel. appears.
Before changing these values, please contact an authorized
[FIRE ALARM]
representative at the supervising station. Refer to Table 3-4
Code: A1
for information on the default CID codes.
3. For each code, use the right arrow key to move between
1. Follow the steps in “Accessing DACT Menu,” earlier in
the letter/digit of the Code field. Use the <NEXT> and
this chapter. Use the <NEXT> or <PREV> keys to
<PREV> keys to increment or decrement the value of a
choose CID Points.
letter or digit. See Table 5-5 for a list of Event types and
<ENTER>=Accept their corresponding codes.
DACT: [CID Points] 4. To choose another code to edit or verify, press the right
2. Press <ENTER>. A prompt similar to the following arrow key until the cursor is on the top line of the
appears. prompt. Use the <NEXT> and <PREV> keys to scroll
to another code and then repeat Step 3.
[Garage IDC1]
GRP: 01 ID: 001 5. When all points have been configured, press the
<ENTER> key. A prompt similar to the following
This prompt consists of the following fields. appears, asking you to confirm the changes you made.
• Point Custom Label. The top line of the prompt dis-
plays the custom label assigned to the point. <ENTER>=Confirm
Code: A1
• Grp. A 2-digit number used to group associated
devices together. 6. Press <ENTER>. The prompt shown in Step 1 appears.
• ID (Contact ID). a 3-digit number used to identify a
Table 5-5 Event Categories and Codes
specific point/device.
3. For each point, use the right arrow key to move between Event 3/1 BFSK 4/2 SIA
the digits of the GRP and ID fields. Use the <NEXT>
Fire Alarm 1 11 A1 FA1
and <PREV> keys to increment or decrement the value
of a digit. Supervisory 3 33 A3 SS3

4. To choose another point, press the right arrow key until Trouble 4 F4 A4 FT4
the cursor is on the top line (custom label) of the
Fire Restoral E E1 71 FR1
prompt. Use the <NEXT> and <PREV> keys to scroll
to another point and then repeat Step 3. Supervisory E E3 73 SJ3
Restoral
5. When all points have been configured, press the
<ENTER> key. A prompt similar to the following Trouble Restoral E E4 74 FJ4
appears, asking you to confirm the changes you made.
Phone Line 1 F FB 31 LT1
Trouble
<ENTER>=Confirm
GRP: [01] ID:001 Phone Line 1 E EB 35 LR1
Restoral
6. Press <ENTER>. The prompt shown in Step 1 appears.
Phone Line 2 F FC 32 LT2
Trouble
Programming Event Codes
Phone Line 2 E EC 36 LR2
Follow the procedure below only if the DACT is using the Restoral
3/1 or 4/2 reporting format. AC Failure F FA 6A AT0
1. Follow the steps in “Accessing DACT Menu,” earlier in AC Restoral E EA 7A AR0
this chapter. Use the <NEXT> or <PREV> keys to
choose Event Codes. Auto Test Report E EE 3A RP0

5-10
Chapter 5. Manually Programming NACs, Relays, and DACT

Table 5-5 Event Categories and Codes

Event 3/1 BFSK 4/2 SIA

Manual Test E EE 3A RX0


Report

Off-normal at F F8 33 YX0
test

Note: Event codes for SIA and BFSK are non-editable.

Saving Changes
When DACT programming is complete, press the EXIT/
CLEAR key until the following prompt is shown.

[Cont] Dscrd Save

Use the right arrow key to move the cursor to one of the fol-
lowing options and press <ENTER>.

• Cont - continues the edit session.


• Dscrd - exits the edit session without saving your
changes (keeps the job that was loaded before you
started editing).
• Save - saves your edit changes

Note: Both discard and save restart the panel.

5-11
Chapter 6. Manually Programming
Annunciators

This chapter describes In This Chapter


• Programming LEDs on the Local Zone LED annunciator, which
is a door-mounted annunciator containing 10 Red and 14 Yellow
Adding an Annunciator. . . . . . . . . . . . . . . . . . .6-2
LEDs, providing a red alarm and yellow trouble LED for each of 10
Accessing Annunciator Menus. . . . . . . . . . . . .6-2
initiating device circuits. This module also provides 4 Yellow Programming LEDs Located on Zone Annunciator
LEDs, one for each of 4 NACs. The LEDs are programmable, and and Remote LED/Switch Modules . . . . . . . . . .6-3
can be used for other functions as appropriate per application. Programming Panel and LCD LEDs . . . . . . . .6-6
• Programming LEDs on the Remote LED/Switch Annunciator. Programming LCD Annunciator Attributes . . . .6-7
Saving Changes to the Job . . . . . . . . . . . . . . .6-9
- 10 programmable red LEDs
- 6 programmable yellow LEDs (no default operation)
- Green “power on” LED (not programmable)
- Yellow “Alarm Silenced” LED (not programmable)
- Yellow “Trouble” (not programmable)
- Yellow “Comm Loss” LED (not programmable)
- Tone-Alert (not programmable).
- Switches for ACK, Alarm Silence, System Reset, and Lamp
Test. Note: These switches are not programmable.
- Key switch to enable switch functions.
For Canadian applications, one red LED and one yellow LED must
be programmed for each Alarm Group and each NAC. Yellow
LEDs must be programmed for indicating Earth Detect, City/
DACT disconnect, and Signal Silence Inhibit enabled. If the total
number of Alarm Groups plus NACs exceeds 10, an additional
remote annunciator shall be mounted adjacent to the panel.
• Programming the three panel LEDs. Typical applications for these
LEDs include waterflow indicator and Earth fault indicator.
• Programming the LCD Annunciator. Programming consists of
identifying which groups of events are sent to the LCD annunciator,
and determining whether the keyswitch must be turned on before
using the system reset, alarm silence, and acknowledge keys.
For Canadian applications, the LCD annunciator is only suit-
able for supplementary applications.

Note: The <Exit/Clear> key is used to back out of menus or displays


and return to the top-level menu structure. Where possible, the <Exit/
Clear> key backs out one level at a time. There are cases, however, that
the Exit/Clear key will return the operator directly to the top-level
menu.

6-1
Chapter 6. Manually Programming Annunciators

Adding an Annunciator 4. Press <ENTER>. Use the <NEXT> and <PREV> keys
to scroll through the choices until “Add” is displayed.
Automatically Adding Annunciator Cards
<ENTER>=Accept
Use the Automatic Programming option to automatically Annuns: [Add]
add annunciator modules to the job. (This option will also
detect and add an Expansion Power Supply and City Card, if 5. Press <ENTER>. A prompt appears, asking you to iden-
installed.) tify the specific type of annunciator.
1. Press the <MENU> key. Press <NEXT> or <PREV> <ENTER>=Accept
until the [Automatic Programming] option is displayed. Add: [LCD]
Press <ENTER>. The following displays:
6. Use the <NEXT> and <PREV> keys to select one of the
FIRE ALARM
following:
SUSPENDED
• Zone Ann
<ENTER> to Program • Remote LED/SW
<EXIT> to resume • LCD. Option not applicable to this panel.
2. Press <ENTER>. The following prompt appears. 7. Press <ENTER>. A prompt appears, asking you to set
the card address for the annunciator. The address you
<ENTER>=Accept specify must match the address set via dip switch on the
AP: [Reconfig All] annunciator. The address must be in the range of 4
through 7.
3. Use the <NEXT> key to select [Detect New]. The fol-
lowing prompt appears. 8. Use the <NEXT> and <PREV> keys to select the
appropriate address and press ENTER.
<ENTER> to Continue
9. A prompt appears asking you to confirm the addition of
*May CHANGE Setting*
the annunciator. Pressing <ENTER> will accept any
4. Press <ENTER> to detect and add annunciators to the changes made and exit. Use the <EXIT/CLEAR> key to
job. quit without saving.

Manually Adding an Annunciator Module Accessing Annunciator Menus


Use the following procedure to manually add the annuncia-
1. Press the <MENU> key. Press <NEXT> or <PREV>
tor module to the job.
until the [Programming] option is displayed. Press
1. Press the <MENU> key. Press <NEXT> or <PREV> <ENTER>. The following displays:
until the [Programming] option is displayed. Press
<ENTER>. The following displays: FIRE ALARM
SUSPENDED
FIRE ALARM
SUSPENDED <ENTER> to Program
<EXIT> to resume
<ENTER> to Program
<EXIT> to resume 2. Press <ENTER>. The Programming menu appears.
[Points] is the default selection, which allows you to
2. Press Enter. The Programming menu appears: make changes to a specific point’s programming.

<ENTER>=Accept <ENTER>=Accept
Prg:[Points] Prg:[Points]

3. Use the <NEXT> and <PREV> keys to scroll through 3. Press <ENTER>. A prompt appears, allowing you to
the choices until “Annuns” is displayed. select the type of point to manually edit. By default,
[IDC] is the first choice.
<ENTER>=Accept
Prg: [Annuns]

6-2
Chapter 6. Manually Programming Annunciators

<ENTER>=Accept
Prg:[IDC

4. Use The <NEXT> and <PREV> keys to scroll to the


Point 17 Point 9 Point 3
appropriate choice and then press <ENTER>.
Point 20 Point 10 Point 18
• LED. Use this selection for programming the fol- Point 22 Point 11 Point 19
lowing: Point 4 Point 12 Point 1
- LEDs on 4610-9111 Remote LED/Switch Point 5 Point 13 Point 21
Annunciator. Point 6 Point 14 Point 2
- LEDs on Local Zone LED Annunciator (door- Point 7 Point 15 Point 23
mounted annunciator). Point 8 Point 16 Point 24

• INPUT. Option not applicable to this panel.


• USER SWITCH/LED (Panel LEDs). Use this
option to program the panel’s three LEDs and the
LCD Annunciator. Fire Alarm Annunciator
Alarm
Point 17 Point 9 Alarm Silenced
Silence
Point 20 Point 10
Programming LEDs Located on Point 22
Point 4
Point 11
Point 12
ACK
Comm Lost

CONTROL

Zone Annunciator and Remote LED/ Point 5


Point 6
Point 7
Point 13
Point 14
Point 15
Reset
Trouble ENABLE

Lamp Power

Switch Modules Point 8 Point 16 Test

Use the procedures outlined in this section to program any of


the following:
Figure 6-1 Mapping LEDs to Software Points
• LEDs on Local Zone Annunciator
• LEDs on Remote LED/Switch Module Programming Overview
Note: The three LEDs on the front of the display are pro- Programming an LED consists of performing the following
grammed in a different manner. Refer to ”Programming tasks
Panel LEDs” at the end of this chapter for information. • Identify which point is being monitored by the LED
(called the reference point).
Mapping LEDs to Software Points
• Identify which point state (fire alarm, trouble, etc.) trig-
Figure 6-1 identifies the way in which the software points gers the LED to turn on. This is called the mode.
map to the LEDs on the annunciators. For example, to con-
trol the LED in the upper left corner of the Local Zone LED See “Programming the LED’s Mode and Reference Point”
Annunciator, you need to program Point 17. later in this chapter.

For example, you can associate an LED with a smoke detec-


tor point and have the LED turn on only when the point
enters a trouble state.

Default Programming
The LEDs on the Local Zone LED and Remote LED/Switch
annunciators have the pre-defined operations listed in Table
6-1 and Table 6-2.

In both tables, a default function of FIRE means the LED


illuminates if a current-limited condition occurs on the cor-
responding reference point. A default function of TROU-
BLE means the LED illuminates if a short occurs on the
corresponding reference point.

6-3
Chapter 6. Manually Programming Annunciators

Table 6-2 Default LED Assignments, Remote LED/


Table 6-1 Default LED Assignments, Switch Module
Local Zone LED Module
Default
Default Reference Default
LED/Color Default Function Point Type Reference
Point Function
Point
1 TROUBLE Alarm Group 9
Alarm
2 TROUBLE NAC2 7 Red LED FIRE
Group 6
3 FIRE Alarm Group 8
Alarm
4 TROUBLE Alarm Group 1 8 Red LED FIRE
Group 7
5 FIRE Alarm Group 2
Alarm
6 TROUBLE Alarm Group 2 9 Red LED FIRE
Group 8
7 FIRE Alarm Group 3
Alarm
8 TROUBLE Alarm Group 3 10 Red LED FIRE
Group 9
9 FIRE Alarm Group 4
Alarm
10 TROUBLE Alarm Group 11 Yellow LED TROUBLE.
Group 99
11 FIRE Alarm Group 5
Alarm
12 TROUBLE Alarm Group 5 12 Yellow LED TROUBLE
Group 1
13 FIRE Alarm Group 6
Alarm
14 TROUBLE Alarm Group 6 13 Yellow LED TROUBLE
Group 2
15 FIRE Alarm Group 7
Alarm
16 TROUBLE Alarm Group 7 14 Yellow LED TROUBLE
Group 3
17 FIRE Alarm Group 99
Alarm
18 TROUBLE Alarm Group 8 15 Yellow LED - TROUBLE
Group 4
19 FIRE Alarm Group 9
Alarm
20 TROUBLE Alarm Group 99 16 Yellow LED - TROUBLE
Group 5
21 TROUBLE NAC 1
Alarm
22 FIRE Alarm Group 1 17 Red LED - FIRE
Group 99
23 TRBL NAC 3
18 Yellow LED - none none
24 TRBL NAC 4
Alarm
20 Red LED - FIRE
Table 6-2 Default LED Assignments, Remote LED/ Group 1
Switch Module Alarm
22 Red LED - FIRE
Group 2
Default
Default
Point Type Reference
Function
Point
Note: Do not program Point 2 (Common Trouble LED
or Point 18 (Comm Loss) on the LED/Switch Annuncia-
PIEZO (tracks state tor.
1 Tone-Alert none
of main piezo)
Programming the LED’s Mode and Reference Point
General Trouble (illu-
2 Yellow LED minates on any trou- none An LED’s mode allows you to specify which point is being
ble). monitored by the LED (called the reference point) and what
Alarm
point state triggers the LED to turn on. For example, you can
4 Red LED FIRE associate an LED with a smoke detector point and have the
Group 3
LED turn on only when the point enters a trouble state.
Alarm
5 Red LED FIRE
Group 4 1. Follow the steps in “Accessing Annunciator Menus”
earlier in this chapter. Choose LED as the type of
Alarm
6 Red LED FIRE
Group 5
device to program.

6-4
Chapter 6. Manually Programming Annunciators

<ENTER>=Accept Table 6-3 LED Modes


Prg: [LED]
Mode Description
2. Press <ENTER>. A scrollable list of points appears.
Use the <NEXT> and <PREV> keys to scroll to the Output activates when referenced
SUPV
LED point you want to edit. The display appears similar point is in a Supervisory condition.
to the following.
Output activates when referenced
TRBL
LED Card 5, Pt 1 point is in a Trouble condition.
LED 1/24
Output activates when the refer-
DISA
3. Press <ENTER>. The next prompt appears similar to enced point is Disabled.
the following: Output activates when the state of the
ON
reference point is ON.
LED Card 5, Pt 1
Fn: [Edit Mode] Output activates when the state of the
OFF
reference point is OFF.
4. Press <ENTER>. A prompt similar to the following
Output activates when any point is in an
appears. LF
alarm condition.
Mode Prg - Output Output activates when any point is in a
[TRBL] 15-10 LS
supervisory condition.

5. Use the <NEXT> and <PREV> keys to scroll through Output activates when any point is in a
LT
the available modes. As you scroll through the modes, trouble condition.
the default reference address for the mode appears to the
right of the mode. Refer to Table 6-3 for a list of the
available modes. Table 6-4 Common LED Reference Points
6. When the appropriate mode is selected, use the right
Reference
arrow key to move the cursor brackets over to the refer- Description
Point
ence point. Press the <FUNCTION> key. This changes
the numerical designation of the reference point to a Separate reference point for each
text-based description. Refer to Table 6-4 for a list of IDNet initiating device. State moni-
common reference points. For example: IDNet 1-200
tored determined by selected LED
mode.
Type: BZONE Fire
IDC10 Aux Relays 1 Separate reference point for each
and 2 relay. State monitored determined
7. Use the <NEXT> and <PREV> keys to scroll through by selected LED mode.
the list of available reference points.
City/DACT Separate reference point (18-14) for dis-
8. Press <ENTER> when the appropriate reference point is Disconnect
displayed. The prompt shown in Step 4 reappears. connect and trouble. Typical use is to
City Trouble monitor the ON state of either point.
9. Press <ENTER>. A prompt appears, asking you to con-
firm the changes. Control
Bypass
10. Press <ENTER> to confirm the changes. Separate reference point for each type
Elevator of bypass.Typical use is to monitor the
Table 6-3 LED Modes Bypass ON state of any of the points.

Mode Description Door Bypass

Output activates when referenced


FIRE
point is in an Alarm condition.

6-5
Chapter 6. Manually Programming Annunciators

Table 6-4 Common LED Reference Points <ENTER>=Accept


Prg: [User SW/LED]
Reference
Description 2. Press <ENTER>. A scrollable list of points appears.
Point
Use the <NEXT> and <PREV> keys to scroll to the
List contains all zones with FIRE, VERIF, point you want to edit. The display appears similar to
or STYLEC function type. Monitoring the the following.
Fire or Trouble state of this list allows
List - General
you to illuminate an LED when any zone User LED 1
Alarm Points
in the list enters an alarm or trouble Y LED 1/5
state. Select either FIRE or TRBL as the
mode. 3. Press <ENTER>. Use the <NEXT> and <PREV> keys
List contains all zones with WATER or to scroll through the options until [FUNCTION] is
WSO function type. Monitoring the Fire shown.
or Trouble state of this list allows you to
List - Water- User LED 1
illuminate an LED when any zone in the
flow Zones Fn: [Function]
list enters an alarm or trouble state. Use
output mode to select which state (Fire,
Trouble) is monitored. 4. Press <ENTER>. A prompt similar to the following
appears, allowing you to set the LED color.
List contains all zones with SO or WSO
function type. Monitoring the Fire, Trou- User LED 1
ble, or Supervisory state of this list [Y LED]
List - Sprinkler allows you to illuminate an LED when
Zones any zone in the list enters an alarm, 5. Use the <NEXT> and <PREV> keys to toggle between
trouble, or supervisory state. Select the following LED colors
either FIRE, TRBL, or SUPV as the
mode. • Y - Programs LED as a yellow LED.
• RG - Programs LED as a Red / Green LED. If you
Separate list for each alarm group. Mon-
assign this type to LED1 (top LED), its color will
itoring the Fire, Supervisory, Trouble, or
be red. If you assign this type to the LED2 (middle)
ON state of an alarm group list allows
Alarm Group or LED3 (bottom), its color will be green.
you to illuminate an LED if any point in
1 -99
the group enters the fire, trouble, super- 6. Press <ENTER> to choose a color. A prompt appears
visory, or ON state. Use output mode to asking you to press <ENTER> to confirm the choice.
select state monitored.
For Canadian applications, LED colors must comply with
Separate list for each NAC. Monitoring Table 6-5.
the ON or trouble state of a NAC allows
you to illuminate an LED if the NAC
NACs 1 - 4
enters trouble state or turns on. Use out- Table 6-5 ULC LED Color Requirements
put mode to select state (on or trouble)
monitored. Function Color

Alarm Inputs Red

Programming Panel and LCD LEDs Alarm Signal Red with unique identifier
Signal Circuit Fault Yellow
This section describes programming the built-in LEDs on
Inhibit Yellow
the front panel and on the LCD annunciator. Programming
Supervisory Inputs Yellow with unique identi-
involves setting the reference point, mode (the point and
fier
point state that triggers the LED to illuminate), and the color
Power - ON Green
of the LED.
Trouble Signal Yellow
Setting LED Color Alarm Signal Silence Yellow

1. Follow Steps 1 through 4 in “Accessing Annunciator


Menus” earlier in this chapter. Choose User SW/LED
as the type of device to program.

6-6
Chapter 6. Manually Programming Annunciators

Setting LED Mode and Reference Point Common LED Applications


An LED’s mode allows you to specify which point is being
Common applications for programmable LEDs are:
monitored by the LED (called the reference point) and what
point state triggers the LED to turn on. • Earth Fault Detect LED. This LED tracks whether the
panel’s Earth fault system point is active or not. If the
1. Follow Steps 1 through 4 in “Accessing Annunciator point enters a trouble state (i.e., there is an Earth fault),
Menus” earlier in this chapter. Choose User SW/LED the yellow LED illuminates. Program the LED as fol-
as the type of device to program. lows:
<ENTER>=Accept - Make sure the color is yellow
Prg: [User SW/LED] - Select the "TRBL" mode
- Select 17-06 as the reference point
2. Press <ENTER>. A scrollable list of points appears.
Use the <NEXT> and <PREV> keys to scroll to the • Waterflow LED, which illuminates if a device with the
point you want to edit. The display appears similar to function type WATER or WSO activates. Program the
the following. LED as follows:
- Make sure the LED color is red
User LED 1 - Select the "FIRE" mode
Y LED 1/5
- Select 22-101 as the reference point
3. Press <ENTER>. Use the <NEXT> and <PREV> keys • City/DACT Disconnect (required for Canadian panels).
to scroll through the options until [Edit Mode] is shown. This LED tracks whether the City/DACT Disconnect
system point is active or not. If the point turns ON (i.e.,
User LED 1 either the city circuit or DACT has been disconnected),
Fn: [Mode] the yellow LED illuminates. Program the LED as fol-
lows:
4. Press <ENTER>. The next prompt appears similar to
- Make sure the color is yellow
the following:
- Select the "ON" mode
Mode Prg - LED - Select 18-14 as the reference point
[NONE] --
• Signal Silence Inhibit Enabled (required for Canadian
5. Use the <NEXT> and <PREV> keys to scroll through panels). This LED tracks whether the Signal Silence
the available modes. As you scroll through the modes, Inhibit Enabled system point is active or not. If the point
the default reference address for the mode appears to the turns ON (i.e., Signal Silence Inhibit system option is
right of the mode. Refer to Table 6-3 for a list of the set to ON), the yellow LED illuminates. Program the
available modes. LED as follows:
- Make sure the color is yellow
6. When the appropriate mode is selected, use the right
arrow key to move the cursor brackets over to the refer- - Select the "ON" mode
ence point. Press the <FUNCTION> key. This changes - Select 18-35 as the reference point
the numerical designation of the reference point to a
text-based description. For example: Programming LCD Annunciator
Type: BZONE Fire Attributes
IDC10
The following LCD annunciator attributes can be modified.
7. Use the <NEXT> and <PREV> keys to scroll through • The type of events annunciated at the LCD. You can
the list of available reference points. choose whether to view Fire, Supervisory, or Trouble
events at the annunciator.
8. Press <ENTER> when the appropriate reference point is
displayed. The prompt shown in Step 4 reappears. • Whether the key-switch must be activated to use the
LCD annunciator’s Acknowledge, Signal Silence, and
9. Press <ENTER>. A prompt appears, asking you to con- System Reset keys.
firm the changes.
10. Press <ENTER> to confirm the changes.

6-7
Chapter 6. Manually Programming Annunciators

1. Press the <MENU> key. Press <NEXT> or <PREV> Choosing Event Groups to Annunciate
until the [Programming] option is displayed. Press After selecting <NEXT>, as described in Step 6 of the previ-
<ENTER>. The following displays: ous section, you are prompted to specify whether you want
to annunciate Fire events on the LCD.
FIRE ALARM
SUSPENDED <ENTER>=Accept
Send FIRE Events: [Yes]
<ENTER> to Program
<EXIT> to resume 1. Use the <NEXT> and <PREV> keys to toggle between
Yes and No. Press <ENTER> when the correct value
2. Press <ENTER>. The Programming menu appears.
appears. The next prompt asks whether you want to
[Points] is the default selection, which allows you to
annunciate Supervisory Events on the LCD.
make changes to a specific point’s programming.
<ENTER>=Accept
<ENTER>=Accept
Send SUPV Events: [Yes]
Prg:[Points]
2. Use the <NEXT> and <PREV> keys to toggle between
3. Press <ENTER>. A prompt appears, allowing you to
Yes and No. Press <ENTER> when the correct value
select the type of point to manually edit. By default,
appears. The next prompt asks whether you want to
[IDC] is the first choice.
annunciate Trouble Events on the LCD.
<ENTER>=Accept
<ENTER>=Accept
Prg:[Cards]
Send TBL Events: [Yes]
4. Press <ENTER>. The display prompts you for the type
3. Use the <NEXT> and <PREV> keys to toggle between
of operation you want to perform.
Yes and No. Press <ENTER> when the correct value
<ENTER>=Accept appears. The next prompt asks whether you want to
Cards:[Add] annunciate signal silence and system reset messages on
the LCD.
5. Use the <NEXT> and <PREV> keys to scroll through
the choices until Modify is shown. Press <ENTER>. <ENTER>=Accept
The display prompts you to specify the address of the Send Reset/Silence: [Yes]
card you want to modify.
4. Use the <NEXT> and <PREV> keys to toggle between
Card=[11] Yes and No. Press <ENTER> when the correct value
LCD appears. See “Setting Key-Switch Operation” below for
information on the next prompt that appears.
6. Use the <NEXT> and <PREV> keys to scroll to the
address of the LCD annunciator. Press <ENTER> when Setting Key-Switch Operation
the appropriate address is shown. A prompt similar to The key-switch operation selection allows you to select
the following appears. whether or not the LCD's key-switch is required to be
inserted and activated in order for the keypad's operation to
<ENTER>=ALL Events take effect. The first prompt appears as follows.
<NEXT> = Select Events
<ENTER> = Default Key
• Press <ENTER> to annunciate all events generated <NEXT> = Select Key
by the panel and attached devices to the LCD. The
next prompt asks you to specify the operation of the 1. Press <ENTER> to require the use of the key for all
key-switch. See “Setting Key-Switch Operation” LCD operations (system reset, ACK, signal silence).
below for information. Press <NEXT> to see the following prompt, which asks
• Press <NEXT> to select which groups of events are if you want to require the key to use the Fire Ack key.
forwarded to the annunciator. A series of prompts
<ENTER>=Accept
appears, telling you to press ENTER to send a
FIRE ACK: [Yes]
group of events to the annunciator. See “Choosing
Event Groups to Annunciate” below.

6-8
Chapter 6. Manually Programming Annunciators

2. Use the <NEXT> and <PREV> keys to toggle between


Yes and No. Press <ENTER> when the correct value • Cont - continues the edit session.
appears. Press <NEXT> to see the following prompt,
• Dscrd - exits the edit session without saving your
which asks if you want to require the key to use the
changes (keeps the job that was loaded before you
Supv Ack key.
started editing).
<ENTER>=Accept • Save - saves your edit changes
SUPV ACK: [Yes]
Note: Both discard and save restart the panel.
3. Use the <NEXT> and <PREV> keys to toggle between
Yes and No. Press <ENTER> when the correct value
appears. Press <NEXT> to see the following prompt,
which asks if you want to require the key to use the Tbl
Ack key.

<ENTER>=Accept
TROUBLE ACK: [Yes]

4. Use the <NEXT> and <PREV> keys to toggle between


Yes and No. Press <ENTER> when the correct value
appears. Press <NEXT> to see the following prompt,
which asks if you want to require the key to use the Sys-
tem Reset key.

<ENTER>=Accept
SYSTEM RESET: [Yes]

5. Use the <NEXT> and <PREV> keys to toggle between


Yes and No. Press <ENTER> when the correct value
appears. Press <NEXT> to see the following prompt,
which asks if you want to require the key to use the
Alarm Silence key.

<ENTER>=Accept
ALARM SILENCE: [Yes]

6. Use the <NEXT> and <PREV> keys to toggle between


Yes and No. Press <ENTER> when the correct value
appears. When you press <NEXT>, a prompt appears
asking you to press <ENTER> to save the changes.

<ENTER>=Save

Press <ENTER> to save the changes. Press <EXIT/


CLEAR> to abandon the changes.

Saving Changes to the Job


When all annunciator programming is complete, press the
EXIT/CLEAR key until the following prompt is shown.

[Cont] Dscrd Save

Use the right arrow key to move the cursor to one of the fol-
lowing options and press <ENTER>.

6-9
Chapter 7. Manually Programming System
Options

System options are pre-defined modes of operation with a range of set- In This Chapter
tings from which to choose. System Options define global operations
such as the time and date format, door drop timers, and whether the city
circuit is enabled, etc. System options can be set during either the auto- Accessing System Options Menu . . . . . . . . . .7-1
matic (Chapter 3) or manual programming process. Programming Options . . . . . . . . . . . . . . . . . . .7-1

Accessing System Options Menu


1. Login at Access Level 4.
2. Press the <MENU> key. Press <NEXT> or <PREV> until the [Pro-
gramming] option is displayed. Press <ENTER>. The following
displays:

FIRE ALARM
SUSPENDED

<ENTER> to Program
<EXIT> to resume

3. Press <ENTER>. The Programming menu appears. Press the


<NEXT> or <PREV> keys until <OPTIONS> appears.

<ENTER>=Accept
Prg: [OPTIONS]

4. Press <ENTER>. The first prompt appears as follows:

<ENTER>=Accept
Opt: [Time/Date]

5. Use the <NEXT> key to scroll through the list of options.

Programming Options
Refer to the appropriate section in the table below for details on each
option. In each case, programming the option involves using the
<NEXT> and <PREV> keys to scroll through the choices and using the
<ENTER> key to set the option to the value you choose.

To back out of an option without setting it, use the <EXIT/CLEAR>


key.

7-1
Chapter 7. Manually Programming System Options

Option Settings
Option Settings
The Door Holder Drop on AC Failure allows
Choose 12 (am/pm) or 24-hour (military) for- the 4008 to hold doors open for a set duration
Time/Date during an AC power loss condition. After that
mat. Use <NEXT> and <PREV> to scroll
Format timer has expired, the 4008 turns off the door
between options and <ENTER> to set.
holder relays (all DHOLDER point types). The
The Active Status Reminder option allows AC Doors range for the timer is 0-60 minutes with a
you to set an interval and duration during default setting of 5 minutes. To have the door
which the panel reminds operators that a holders drop the doors immediately upon AC
FIRE, SUPV, or TBL condition still exists. This power loss, set the timer to 0. This option
is accomplished by sounding the front panel applies to all DHOLDER relay function types
tone-alert. regardless of their Alarm Group setting.
• Choose: ON or OFF (default = OFF).
• Set reminder interval This option selects the operation of the 4008 if
Reminder (1-12 hours) an alarm occurs during an AC power loss
• Signal duration. This option sets the while a depleted battery trouble exists. If this
duration of the acknowledge signal. (0- option is selected, the system does the fol-
60 seconds; 0=on until ack; default=5) lowing:
• WILL NOT initiate an alarm if the first
The default for this option is 0, meaning alarm occurs after the depleted battery
an acknowledge is required to silence Depleted Bat- state has been detected. If the hardware
the reminder. tery Cutout jumper for depleted battery cutout has
been clipped, the system will shut down
60 seconds after the depleted battery
While the timer is counting down, the Alarm condition is detected
Silence/Reset Inhibit Timer prevents a sys- • WILL continue sounding the alarm if the
tem operator from using either the Alarm depleted battery state is reached after
Silence or System Reset functions. When the the system is already in the alarm state.
Inhibit inhibit timer expires, the 4008 may be reset/
silenced.
Display 1st When this option is selected, the 4008 will
Choose a timer range from 0-60 minutes Alarm automatically display the first (oldest) alarm
(default=0 - no inhibit) instead of the Alarm Tally abnormal screen.
This allows the first responder to determine
The Alarm Signal Cutout timer allows you to the location of the first alarm in the system
set a duration for how long notification appli- without having to open the door and press the
ances sound after an alarm. In other words, acknowledge key.
when an alarm condition exists, the signals
sound until silenced. With this option set at If an unacknowledged alarm exists, the sys-
Alarm Cutout two minutes, building signals sound on alarm tem displays that alarm. When that alarm is
for two minutes and then stop sounding. acknowledged, the system shall revert to dis-
However, the alarm condition remains active. playing the oldest alarm.

Choose a timer range from 0-60 minutes If no fire alarms exist in the system, the first
(default=0 - no cutout) supervisory event is shown on the display. If
no supervisories exist, the first trouble is
Allows the 4008 to hold doors open for a set shown on the display. If there are no fire
duration during an alarm condition. After that alarms, supervisories, or troubles, the SYS-
duration has expired, the 4008 shuts off the TEM NORMAL screen is displayed.
door holder relays (all DHOLDER point
Alarm Doors types). Choose a timer range from 0-60 min- Enable City Cir- This option activates the 4008 Circuit Module.
utes (default=0 - immediate door drop). This cuit If a city circuit is used in the system this
option applies to all DHOLDER relay function option must be selected or a trouble will be
types, regardless of their Alarm Group set- reported. If this option is selected and the city
ting. module is not connected, the trouble will also
report. There is no other programming
required for the city module. The city type is
configured with jumpers on the city circuit
board.

7-2
Chapter 7. Manually Programming System Options

Option Settings

This option activates the 4008 Expansion


Power Supply Module and its associated
NACs. If the expansion power is used in the
system this option must be selected or a trou-
ble will be reported. If this option is selected
Enable Expan- and the EPS is not connected, the trouble will
sion Power also report.

Activation of this module allows the two


expansion NACs to be edited in the Point pro-
gramming menu.

7-3
Chapter 8. Operating

Normal Operation In This Chapter


The 4008 operator interface shows the following under normal condi-
tions: Normal Operation. . . . . . . . . . . . . . . . . . . . . . .8-1
LAMP Test . . . . . . . . . . . . . . . . . . . . . . . . . . . .8-1
• Green AC power LED is on steady
Abnormal Conditions . . . . . . . . . . . . . . . . . . . .8-1
• All other panel indicator LEDs are off Silencing Alarms . . . . . . . . . . . . . . . . . . . . . . .8-2
• Front panel LCD shows the following: System Reset. . . . . . . . . . . . . . . . . . . . . . . . . .8-2
Historical Logs . . . . . . . . . . . . . . . . . . . . . . . . .8-2
Viewing and Controlling Points. . . . . . . . . . . . .8-3
SYSTEM NORMAL Enabling or Disabling Points . . . . . . . . . . . . . .8-4
Control Functions . . . . . . . . . . . . . . . . . . . . . . .8-4
1:45:07 pm 3/10/03 Setting the Time and Date . . . . . . . . . . . . . . . .8-5
Reports. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8-5

LAMP Test
Lamp Test is accomplished during normal monitoring (Access Level 1)
by pressing the Function key, then pressing ENTER. All LEDs energize
and all LED segments are written to.

Abnormal Conditions
Abnormal conditions are indicated on the 4008 by flashing the alarm,
supervisory, or trouble LED and sounding the tone-alert. The tone-alert
pulses for an alarm condition, and is on steady for a trouble or supervi-
sory. If the "Display First Alarm" option is selected, the display pro-
vides information about the first, highest-priority alarm in the system
without operator intervention. If "Display First Alarm" is not selected, a
screen showing the overall system status is shown:

FIRE | SUPV | TRBL

02 | 00 | 00

When the appropriate Acknowledge key is pressed, the tone-alert turns


off and the indicator LED illuminate steady, indicating that the operator
has acknowledged all events in that category. The first abnormal point
in that category is then shown on the display:

CORE 1 MEZZANINE

FIRE 1/2

8-1
Chapter 8. Operating

Historical Logs
The 4008 is a Global Acknowledge system meaning that one
press of an Acknowledge key acknowledges every abnormal The 4008 has three separate, non-volatile historical logs:
point in the system within that category. Pressing the Ack Alarm, Supervisory, and Trouble. These logs can be viewed
key allows the operator to scroll through all the abnormal separately, or they can be viewed in chronological order as a
points in that category. The additional information listed single combined log. Each log records information about the
below can be obtained by pressing the <ENTER> key. event and the time the event occurred. The following table
describes the different logs and their stored events.
• The electrical state of the point (open, short circuit, nor-
Table 8-1 Log Events
mal, abnormal)
• Enable/Disable state of the point Historical
Stored Events
• Manual override state (if output) Log
• Assigned Alarm Groups
Alarms
ALOG Alarm Acknowledge
Silencing Alarms Alarm Log Log Cleared
100 Entries Alarm Silence
The "Alarm Silence" key allows the operator to silence System Reset
active Notification Appliance Circuits that are programmed
for "on-til-silence" operation. SLOG Supervisory Conditions
Supervisory Supervisory Acknowledge
Log Log Cleared
Caution: Pressing the Alarm Silence key causes fire alarm
100 Entries
evacuation signals to turn OFF. Follow local procedures to
silence alarm evacuation signals. Trouble Events
TLOG
Login/Logout for Level 2 or higher
Trouble Log
To silence an alarm, press the <ALARM SILENCE> key. Log Cleared
300 Entries
WALKTEST Events
• All "on-til-silence" notification appliance circuits will
turn OFF CLOG All Events in Chronological Order
• The Alarm Silenced indicator LED will turn on Combined Log

If a subsequent alarm occurs, the notification appliance cir- Viewing Logs


cuits resound.
1. Press <MENU>.

System Reset 2. Press <NEXT> and <PREV> until the following


prompt appears.
The <SYSTEM RESET> key is used to attempt to restore
the system to its normal state after an alarm condition has <ENTER>=Accept
been cleared. When the <SYSTEM RESET> key is pressed, Menu: [History Logs]
it causes all latched circuits to reset automatically. The sys-
tem will display the “RESET IN PROGRESS” message 3. Press <ENTER>. A prompt similar to the following
when the key is pressed. After a short delay and if all alarms appears.
are cleared, the system is restored to its normal, non-alarm
<ENTER>=Accept
state (e.g. all alarm notification, relays, etc. are turned off).
Rep: [ALOG]
The alarm points are removed from the alarm list and the
alarm LED will turn off. 4. Use the <NEXT> or <PREV> key to select one of the
logs described in Table 8-4
If a device remains in alarm during the reset period, the sys-
tem reset is aborted, and the system remains in the alarm 5. Press <ENTER> to access the contents of the log. Use
state. The display will continue to show the device(s) that <NEXT> and <PREV> to scroll through each log entry.
remain in alarm.
Clearing Logs
The logs may be viewed at Access Level 1, however they
may not be cleared unless you are at Access Level 2 or

8-2
Chapter 8. Operating

higher. To clear the log you are currently viewing, press 7. Press <ENTER> when the point whose status you want
<ENTER> while viewing any log entry. The following to view is displayed. The Hardware Type and Function
screen will be displayed: Type for the point are shown. For example:

<ENTER>= Clear Log IDNet1


<EXIT> to cancel PHOTO SMOKE

Press <ENTER> to clear the current log. An entry is added 8. Additional information and control options are available
to the log to indicate that it was cleared. as described in the following table.

Viewing and Controlling Points Table 8-2 Additional Point Information


The 4008 allows you to view each point in the system to
obtain additional information, or to control or disable/enable a. Press <ENTER> to view the point’s
it. Points may be viewed at Access Level 1, but control and hardware type and assigned function
disable/enable operations are protected at Level 2 or higher. type. For example:

IDNet1
Viewing Point Information
PHOTO SMOKE
1. Press <MENU>.
a. Press the <NEXT> key to view the
2. Press <NEXT> and <PREV> until the following following information for the device.
IDNet
prompt appears.
• Enable/Disable status
<ENTER>=Accept • Alarm Verification Tally
Menu: [Control/View] • Electrical state (normal, short, open,
abnormal)
3. Press <ENTER>. A prompt similar to the following
appears. • CID Group and ID
• Assigned Alarm Groups
<ENTER>=Accept
Ctrl/View: [IDNet]
a. Press <ENTER> to view the point’s
4. Use the <NEXT> or <PREV> key to select one of the hardware type and assigned function
following. type. For example:

NAC1
- IDNet
NAC
- Relay
- NAC a. Press the <NEXT> key to view the
- Input (Not Applicable) following information for the IDC.
Relay or
- Output (LED) NAC
• Electrical State (open/short/normal)
- System Point - these are logical system points used • Enable/Disable status
for on/off control of system functions. Control of • Output state (on/off/coding)
these points is not allowed. • Automatic/Manual control status. See
5. Press <ENTER> when the appropriate point category “Manually Controlling a NAC/Relay”
(i.e., Relay, NAC) is selected. A display similar to the below for additional information.
following appears. • Function type and output method
• Assigned Alarm Groups
IDNet1
Input N/A
Fire NORMAL

6. Use the <NEXT> or <PREV> key to scroll through the


list of points for the selected category.

8-3
Chapter 8. Operating

Table 8-2 Additional Point Information 2. Press <NEXT> until Control/View is shown.

Output a. Press <ENTER> to view a descrip- 3. Press <ENTER>. Use the <NEXT> or <PREV> key to
(LED) select IDC, NAC, or Relay.
tion of the first system point in the
list. Press NEXT to scroll through the 4. Press <ENTER>. Use the <NEXT> or <PREV> key to
list of points. scroll through the list of points.
5. Press <DISABLE/ENABLE> when the point you want
System to turn enable/disable is displayed. A prompt similar to
a. Press <ENTER> to view a descrip-
Point the following appears.
tion of the first system point in the
list. Press NEXT to scroll through the
IDNet1
list of points.
FN: [Enable]

6. Use NEXT to toggle between Enable and Disable. Press


Manually Activating a NAC/Relay <ENTER>. A prompt appears asking you to confirm the
operation. Press <ENTER>. Keep the following in mind
Follow these steps to manually turn a NAC or Relay on or when enabling/disabling points.
off, or set it to automatic operation.
• When a monitor point is disabled, any status
1. Press <MENU>. changes occurring on the point are ignored by the
panel. If a control point is disabled, any automatic
2. Press <NEXT> until Control/View is shown.
functions are inhibited. A disable trouble will exist
3. Press <ENTER>. Use the <NEXT> or <PREV> key to for each disabled point in the system.
select NAC or Relay. • When a monitor point is enabled, a 30-second
4. Press <ENTER>. Use the <NEXT> or <PREV> key to countdown will start to prevent an operator from
scroll through the list of points for NAC or Relay. accidentally enabling a point that will alarm the
system. The point may be enabled immediately by
5. Press <ENTER> when the point you want to turn on or pressing <ENTER>, or the enable can be aborted
off is displayed. by pressing <EXIT>.
6. Press <NEXT> until a prompt similar to the following is
shown. Control Functions
ENTER = Control AUX User control functions, such as Drill, City Disconnect, Con-
TROUBLE STEADY trol Point Bypass, and Elevator Recall Bypass are available
by pressing the <FUNCTION> key.
7. Press <ENTER>. The following prompt appears.
The table below shows the operations available in the Func-
ENTER = Accept tion menu.
FN: ON
Table 8-3 Control Functions
8. Use <NEXT> to select one of the following:
• ON. Use this option to turn the relay or NAC on. To Function Description
return the NAC/Relay to automatic operation, first
set it to OFF, and then reselect the point and set it to Drill Activates the drill operation (all notifica-
AUTO. tion appliances)
• OFF. Turns the relay or NAC off. Manual Evacu- Activates manual evacuation (general
• AUTO. Use this option to return the NAC or Relay ation alarm)
to automatic operation. City/DACT Disconnects the city circuit or DACT
Disconnect (causes a trouble)
Enabling or Disabling Points
Use the following steps to enable or disable points.
1. Press <MENU>.

8-4
Chapter 8. Operating

Table 8-3 Control Functions a. Connect a 733-794 download cable between the
Service Port on the panel and a serial communica-
Function Description tion port on the PC.
a. Create a connection profile for the serial port. Set
Control Point Bypasses the following control points the serial communication parameters to 9600 baud,
Bypass (causes a trouble): 8 bits, no parity, 1 stop bit, and no flow control.
• On-til-Silence NACs a. Configure the application to capture the informa-
• On-til-Reset NACs/relays tion coming in on the serial port. (Choose Capture
Text in the Hyperterminal Transfer menu.)
Elevator Bypasses Elevator Recall operation
Bypass (causes a trouble)
To generate a report, do the following.
Doorholder Bypasses the door holder operation
Bypass (causes a trouble) 1. Press <MENU>.
2. Press <NEXT> and <PREV> until the following
Lamp Test Illuminates all LEDs and LCD segments
on the operator interface. prompt appears.

Earth Fault Latches intermittent Earth troubles in the <ENTER>=Accept


Latch panel, preventing them from automati- Menu: [Reports]
cally clearing.
3. Press <ENTER>. A prompt similar to the following
Display Time Shows the current time and date. appears.
Send DACT Sends the DACT test event to the sta-
Test tionary station. <ENTER>=Accept
Rep: [ALOG]

Setting the Time and Date 4. Use the <NEXT> or <PREV> key to select one of the
options described in Table 8-4.
Selecting the "Set Time/Date" option from the main menu
allows you to change the system time and date. This opera- Table 8-4 Reports
tion is protected at Access Level 2.
Report Description
<ENTER>=Accept ALOG Displays contents of alarm log.

[11]:23 pm 11/12/03 SLOG Displays contents of supervisory log.

TLOG Displays contents of trouble log.


The Right/Left arrow keys allow you to move the focus from CLOG Combined alarm, supervisory, and trou-
field-to-field for editing. The <NEXT/PREV> keys allow ble logs.
you to change the currently selected fields. The am/pm field
and the day-of-week field are not editable. CONFIG Text description - including custom label,
function type

Reports
5. Press <ENTER>. The panel displays a message noting
Reports, which are either text-based archives of system that the report has been sent to the printer.
activity or a text-based description of the panel configura-
tion, can be archived and printed in the following manner. Diagnostics
• The panel supports an unsupervised, 80-column serial
printer that can be used to record events, or to print his- Use the following procedure to run the panel’s diagnostic
tory log reports. options.

• Use Windows Hyperterminal (or similar application), as 1. Press <MENU>.


follows:
2. Press <NEXT> and <PREV> until the following
prompt appears.

8-5
Chapter 8. Operating

<ENTER>=Accept - If the WalkTest signaling option is set to SIG, the


Menu: [Diagnostics] panel pulses the device’s zone number on the
panel’s NACs. After 15 seconds the panel drops
3. Press <ENTER>. A prompt similar to the following power to the zone, resetting the activated device.
appears. Subsequently activating another initiating device
on the same zone sounds a double pulse on the
<ENTER>=Accept NAC.
Diag: [BAT CHGR METR]
- If the WalkTest signaling option is set to SIL, the
4. Use the <NEXT> or <PREV> key to select one of the panel logs the alarm activation to the ALOG (alarm
options described in Table 8-5. log). Use the History Logs menu option to view the
ALOG. Use the Reports menu option to print a
copy of the ALOG.
Table 8-5 Diagnostic Options • Initiating Device Trouble Sensing. To test the panel’s
ability to sense a trouble condition for each initiating
Option Description device, disconnect one of the IDC wires at the detector.
If the panel senses the trouble condition correctly, one
BAT CHGR View battery charger incoming voltage,
of two things happen:
METER and output current.
- If the WalkTest signaling option is set to SIG, the
Battery Meter View battery voltage and battery load panel activates the panel’s NACs for four seconds.
HW Reset The Hardware Reset is context sen- - If the WalkTest signaling option is set to SIL, the
sitive. If the reset is performed with panel logs the trouble in the TLOG (trouble log).
an alarm in the system, the alarms Use the History Logs menu option to view the
are allowed to reset. If there are no TLOG. Use the Reports menu option to print a copy
alarms present, a HW reset (power of the TLOG.
is dropped to all zones for 15 sec- • Earth Ground Sensing. To test the panel’s ability to
onds) is performed. The hardware detect an Earth Ground, short one of the panel’s circuits
reset will attempt to clear any to Earth. If the panel senses the trouble condition cor-
latched troubles. rectly, one of two things happen:
CLR Tally/TBL - If the WalkTest signaling option is set to SIG, the
This option clears the alarm verifica-
panel activates the panel’s NACs for four seconds.
tion tallies for all IDCs in the system.
Typically this is only done when an - If the WalkTest signaling option is set to SIL, the
Alarm Verification Tally Limit trouble panel logs the trouble in the TLOG (trouble log).
occurs. The Alarm Verification Tally Use the History Logs menu option to view the
Limit trouble occurs if an IDC pro- TLOG. Use the Reports menu option to print a copy
grammed for alarm verification starts of the TLOG.
the verification cycle, but does not • NAC Trouble Sensing. To test the panel’s ability to
verify 10 times. sense a trouble condition for each NAC, disconnect one
of the NAC wires at the panel. If the panel senses the
5. Press <ENTER>. The function you chose in Step 4 exe- trouble condition correctly, one of two things happen:
cutes. - If the WalkTest signaling option is set to SIG, the
panel activates the panel’s NACs for four seconds.
WalkTest - If the WalkTest signaling option is set to SIL, the
panel logs the trouble in the TLOG (trouble log).
WalkTest allows one person to test the functionality of the Use the History Logs menu option to view the
panel’s devices. Once the panel is placed into WalkTest TLOG. Use the Reports menu option to print a copy
mode, you can test the following: of the TLOG.
• Initiating Device Alarm Sensing. To test each detector’s
alarm capability, use a pole magnet or canned smoke to Setting WalkTest Options
activate the initiating device. If the device is functioning WalkTest options are set via the WalkTest entry at the main
correctly, one of two things happen: menu. You must be logged in at either Access Level 3 or 4 to
set the WalkTest options.

8-6
Chapter 8. Operating

1. Press the <MENU> key. Press <NEXT> or <PREV> Restarting the CPU
until the [Walktest] option is displayed. Press This option is used to clear an Access Level 4 Trouble (i.e., a
<ENTER>. The following displays: “Service Mode Trouble”).
<ENTER>=Accept 1. Press <MENU>.
[Off] Lg Sil NoPr
2. Press <NEXT> and <PREV> and choose one of the fol-
2. For each option, use the <NEXT> and <PREV> keys to lowing options.
scroll through the option’s choices. Use the right and • Warm. Clears the Access Level 4 trouble, restarts
left arrow keys to move from one option to another. the panel, but preserves the panel’s non-volatile
Available options include memory, including time/date information, historical
• ON/OFF. Used to enable and disable WalkTest. logs, and all currently disabled points
When set to ON, a WalkTest Enabled trouble is dis- • Cold. Clears the Access Level 4 trouble and re-ini-
played on the panel. tializes the panel’s non-volatile memory, clearing
• LG/NL. Controls whether alarms and troubles gen- all time/date information, historical logs, and dis-
erated by WalkTest are sent to the alarm or trouble abled points.
log. Lg enables logging; NL disables logging. 3. Choose an option and press <ENTER>. System startup
• SIG/SIL. Controls whether the NACs are used to prompts appear on the screen, followed by the system
signal activation of an alarm or trouble condition. status message.
SIG enables NACs for Walktest; SIL disables
NACs for WalkTest. Viewing Software Revision Number and Job Info
• PR/NoPR. Enables (PR) or disables (NoPR) 1. Press <MENU>.
whether WalkTest alarms and troubles are sent to
2. Press <NEXT> or <PREV> until Software Rev is
the locally attached printer.
shown. Press <ENTER>. A message similar to the fol-
3. When the options are set, press the <ENTER> key. The lowing appears, displaying the revision level of the
system prompts you to confirm the settings. Press panel’s software.
<ENTER> again to confirm.

Rev 1.00.11
Advanced Operations <NEXT> = View Job Info
Upload/Download 3. Press <NEXT> to see the job revision number (i.e., the
Uploading and downloading files allows you to transfer the number of times the job has been edited and saved), and
panel’s job file between a service PC and the panel. The term the date on which the panel was edited.
Uploading refers to transferring a job file from the panel to a
PC; whereas, the term Downloading refers to moving a job JOB REV:1
file from the PC to the panel. 12:00:00 am 04/09/04

Note: The UPLD/DWNLD menu option enables the panel


for an upload or download operation. This option does not,
however, perform the transfer operation. A service PC, run-
ning the panel’s PC programmer tool, is required.
1. Press <MENU>.
2. Use the <NEXT> or <PREV> keys to scroll to the
UPLD/DWNLD menu choice.
3. Press <ENTER>. A prompt similar to the following
appears.

<ENTER>=Accept
XFER: [Start XFER]

8-7
Appendix A. Battery Standby Calculations

Current Draw for System Components


Each component of the 4008 system has a specified alarm and standby current rating. To calculate the current draw for the sys-
tem, add the specified standby current for each module and device to obtain an alarm and a standby current rating for your sys-
tem.

Note: Auxiliary power from the system’s AUX 24 V taps must also be included in the calculation, unless that power is
switched off during battery standby. For example, door holders operated from 24 V need not be included if they are discon-
nected via a relay during a battery standby condition. Notification Appliance load must be included in the alarm current total.

Module Standby Current Alarm Current

Main System Board (50 IDNet Devices) 175mA 200 mA

Each Additional IDNet Device 1 mA 1 mA

Expansion Power Supply 50 mA 60 mA

Remote LCD Annunciator 100 mA 150 mA

Remote LED Annunciator 100 mA 100 mA

City Connect Module or Relay Module 30 mA 60 mA

Aux 24V (excluding LCD/LED


Annunciators)

Notification Appliance Load 0 mA

Total Standby Current:____________ Total Alarm Current:____________


1. Identify Standby Time (C), in hours. C = ______ (typically 4, 24, 48, or 60 hr)

2. From previous calculations, locate total Alarm Current (B) in amperes. B = ______

3. Identify Alarm Time (D) in minutes. D = ______ (typically 5, 10, or 15 min)


4. Using the values in Steps 1-4, perform an Initial Battery Calculation per the following:

5. (A x C) + (0.0167 x B x D) = _______ Ah (Ah = ampere hours)

6. Select a battery size LARGER than the number from the Initial Battery Calculation from the following list of batteries
using the 20 Hour Rating value:

A-1
20 Hour Rating C/20 (Amps) 20 Hour Rating C/20 (Amps)

1.3 Ah 0.065 6.2 Ah 0.31

2.2 Ah 0.11 7.0 Ah 0.35

3.0 Ah 0.15 7.2 Ah 0.36

3.4 Ah 0.17 10 Ah 0.50

4.0 Ah 0.20 12 Ah 0.60

4.5 Ah 0.225 12.7 Ah 0.635

5.0 Ah 0.25 18 Ah 0.90

7. If either the Standby Current or the Alarm Current is greater than the C/20 current for the initial battery size selected, a
Discharge Factor (DF) must be applied. For example, 1 A load on a 10 Ah battery requires a Discharge Factor of 1.08 (10
Ah / 1 A gives discharge time of 10 hours; DF = 1.08). Use the following table to determine Discharge Factor (use the 20
hr value for 24 hr standby):

Discharge Discharge Discharge Discharge Discharge Discharge Discharge


Time Factor Time Factor Time Factor Factor

0.083 hr 5 min 3.85 2 hr 1.43 8 hr 1.10 14 hr 1.03

0.166 hr 10 min 2.78 3 hr 1.30 9 hr 1.09 16 hr 1.02

0.249 hr 15 min 2.27 4 hr 1.22 10 hr 1.08 18 hr 1.01

0.332 hr 20 min 2.08 5 hr 1.18 11 hr 1.06 20 hr 1.00

0.5 hr 30 min 1.96 6 hr 1.14 12 hr 1.05 48 hr 1.00

1 hr 60 min 1.67 7 hr 1.11 13 hr 1.04 60 hr 1.00

8. Standby Discharge Factor (SDF) = _________ Alarm Discharge Factor (ADF) = _________

9. Minimum Required Battery Capacity Calculation. (to account for battery aging, a 1.17 multiplier is included)

Minimum battery capacity in Ah =

1.17 x [(A x C x SDF) + (0.0167 x B x D x ADF)] = _______

10. If the battery size initially selected is smaller than the result of step 9 above, repeat the calculations using a larger battery
size.

A-2

You might also like