TITLE: WellServices CMTSkidLite OPC to Profibus Interface

WellServices CMTSkidLite OPC to Profibus Interface

Schlumberger Private
PN: 100742751AA

Written by Deyne Carrasco Date 22/10/09


Revised Irene Ang Date 30/11/09
Verified by Deyne Carrasco Date 22/03/10
Approved by
Number of pages: 22
Printed
PDM # 100742751
Revision: AE
GUIDELINES Date: 22/03/10
Page: 2 of 22

TITLE: WellServices CMTSkidLite OPC to Profibus Interface

Table of Contents

1.  REQUIREMENTS 4 

2.  INTERFACE NETWORK 5 

3.  HARDWARE SETUP (ANYBUS) 6 

4.  SOFTWARE SETUP 8 

ANYBUS I/O CONFIGURATION 8 

ANYBUS IP CONFIGURATION 13 

Schlumberger Private
4.  CMTSKIDLITE OPC SERVER SETTINGS 17  

5.  XFERCIPPROFI SOFTWARE CONFIGURATION 18 

6.  PROFIBUS DATA MAPPING 21 


PDM # 100742751
Revision: AE
GUIDELINES Date: 22/03/10
Page: 3 of 22

TITLE: WellServices CMTSkidLite OPC to Profibus Interface

List of Figures

Figure 1: Interface network ........................................................................................................................................... 5 


Figure 2: Top Mounted Interface .................................................................................................................................. 6 
Figure 3: Bottom Mounted Interface............................................................................................................................ 6 
Figure 5: Top view of the OLM-Location of the Switches ........................................................................................ 7 
Figure 4: Interface between the Profibus Port on the AnyBus and that on the OLM .......................................... 7 
Figure 6: New Connection Name.................................................................................................................................. 8 
Figure 7: Com Port Selection ......................................................................................................................................... 9 
Figure 8: Port Settings .................................................................................................................................................. 10 

Schlumberger Private
Figure 9: Anybus X-gateway main menu................................................................................................................... 11 
Figure 10: Change Configuration ................................................................................................................................ 12 
Figure 11: Anybus IPconfig Setup Wizard................................................................................................................ 13 
Figure 12: Select installation Folder for Anybus IPconfig ...................................................................................... 13 
Figure 13: Confirm Installation of Anybus IPconfig ................................................................................................. 14 
Figure 14: Complete Installation of Anybus IPconfig .............................................................................................. 14 
Figure 15: Windows Security Alert............................................................................................................................. 15 
Figure 16: Anybus IPconfig .......................................................................................................................................... 15 
Figure 17: Ethernet Configuration ............................................................................................................................... 16 
Figure 18: cmt_skid_lit.ini. ........................................................................................................................................... 17 
Figure 19: XferCIPprofi Wix.msi .................................................................................................................................. 18 
Figure 20: WinZip Caution ............................................................................................................................................ 18 
Figure 21: Window Explorer - C:\Program Files\XferCIPprofi\data ....................................................................... 19 
Figure 22: XferCIPprofi ................................................................................................................................................. 20
Figure 23: Network Configuration Sheet………………………………………………………………...23
PDM # 100742751
Revision: AE
GUIDELINES Date: 22/03/10
Page: 4 of 22

TITLE: WellServices CMTSkidLite OPC to Profibus Interface

1. Requirements
To successfully complete this procedure the following items will be required:

a) Null modem Serial Cable

b) Ethernet Cable

c) Laptop

d) Screw Drivers

e) Configuration files, confi1.xml, XferCIPprofi Wix.zip and the HMS_1013.GSD (the GSD file
must be handle over the Rig to properly identify the Anybus via Profibus)

Schlumberger Private
f) External USB memory device.

g) CMTSkidLite version 1.2 or higher


PDM # 100742751
Revision: AE
GUIDELINES Date: 22/03/10
Page: 5 of 22

TITLE: WellServices CMTSkidLite OPC to Profibus Interface

2. Interface Network

PC ETHERNET CAN
(CMTSkidLite) DCU
CEG

IP 192.168.2.3 IP 192.168.2.2

ETHERNET
Profibus Slave
Add: 57
Profibus
Anybus
Network

Schlumberger Private
IP 192.168.2.16

Figure 1: Interface network

Figure 1 shows the network interface from the CMTSkidLite to the Profibus network. By connecting an
Anybus gateway module between the CEG and the profibus network, information such as Slurry density,
Slurry volume, Slurry flow rate and Treating Pressure can be extracted from a cement pump (e.g CPS763)
to the client’s network.

The IP address of the PC must be set to 192.168.2.3. To check the IP address of the PC,
• Right-click the My Network Places icon on the desktop and go to Properties
• Right-click on the Local Area Connection that is connected using the Broadcom NetXtreme 57xx
Gigabit C and go to Properties
• Scroll down to Internet Protocol (TCP/IP) and click on it
• Click the Properties button and check the IP address

The configuration of the Anybus IP address will be illustrated in Section 3 (Software setup).
PDM # 100742751
Revision: AE
GUIDELINES Date: 22/03/10
Page: 6 of 22

TITLE: WellServices CMTSkidLite OPC to Profibus Interface

3. Hardware Setup (Anybus)


1. IP address configuration
The entire Ethernet configuration Switches must be set up to off. IP address will be configured
later on this document. Connect an Ethernet cable between the LAN port on the Anybus and
that on the CEG.

Schlumberger Private
Figure 2: Top Mounted Interface

2. Profibus Slave Address Rotary Switches


The two profibus node address switches provide an address range of 1-99. In our application,
the profibus node address switches must be set up to 12 (1 X10) + (2 X1).

1. Profibus Port
2. Node Address
4. Serial Port DB9

Figure 3: Bottom Mounted Interface


PDM # 100742751
Revision: AE
GUIDELINES Date: 22/03/10
Page: 7 of 22

TITLE: WellServices CMTSkidLite OPC to Profibus Interface

3. Connect the AnyBus Profibus cable directly to the OLM, bypassing the DP/DP coupler.

Schlumberger Private
Figure 4: Interface between the Profibus Port on the AnyBus and that on the OLM

4 The OLM Switches must have the settings as depicted in Table 1.

Figure 5: Top view of the OLM-Location of the Switches


PDM # 100742751
Revision: AE
GUIDELINES Date: 22/03/10
Page: 8 of 22

TITLE: WellServices CMTSkidLite OPC to Profibus Interface

Table 1: Switches Settings


Switches S7 S6 S5 S4 S3 S2 S1 S0 S8

Position 0 1 1 1 1 1 1 1 0

4. Software Setup

AnyBus I/O Configuration

1. Connect the Laptop RS232 port to the RS232 port Gateway Configuration using the Null
modem cable.

Schlumberger Private
2. Follow the below mentioned steps on the Laptop
2.1.1 Start the Windows HyperTerminal (Start -> Programs -> Accessories ->
Communications -> HyperTerminal)
2.1.2 HyperTerminal will prompt for a name to use for the new connection.
Name the connection ‘AnyBus-X’, and click ok (Figure 6).

Figure 6: New Connection Name


PDM # 100742751
Revision: AE
GUIDELINES Date: 22/03/10
Page: 9 of 22

TITLE: WellServices CMTSkidLite OPC to Profibus Interface

2.1.3 Specify which interface to use for the connection (select the COM port
that is connected to the gateway, in this particular case COM8), and click
‘OK’ (Figure 7).

Schlumberger Private
Figure 7: Com Port Selection
2.1.4 HyperTerminal will now prompt for the communication properties for the
interface. Ensure that the settings match that of the Gateway Config
Interface and click ‘Apply’ then ‘OK’ (Figure 8).
PDM # 100742751
Revision: AE
GUIDELINES Date: 22/03/10
Page: 10 of 22

TITLE: WellServices CMTSkidLite OPC to Profibus Interface

Schlumberger Private
Figure 8: Port Settings

2.1.5 Power up the gateway. The gateway displays several diagnostic


messages during startup. To enter the main menu (Figure 9), press <Esc>.
PDM # 100742751
Revision: AE
GUIDELINES Date: 22/03/10
Page: 11 of 22

TITLE: WellServices CMTSkidLite OPC to Profibus Interface

Schlumberger Private
Figure 9: Anybus X-gateway main menu
PDM # 100742751
Revision: AE
GUIDELINES Date: 22/03/10
Page: 12 of 22

TITLE: WellServices CMTSkidLite OPC to Profibus Interface

3. Type 6 to change the configuration as shown in Figure 10


It’s important to:
• Disable “Live list” and “Modbus Address Mode”
• Enable “Control/Status word”
• Disable “Run/Idle header (+/-)”
• All the other setting must be as showed below.

Schlumberger Private

Figure 10: Change Configuration


PDM # 100742751
Revision: AE
GUIDELINES Date: 22/03/10
Page: 13 of 22

TITLE: WellServices CMTSkidLite OPC to Profibus Interface

AnyBus IP Configuration
1. Install the Anybus Configuration tool (anybus ipconfig setup 1.3.1.1.msi) and click on “Next”.

Schlumberger Private
Figure 11: Anybus IPconfig Setup Wizard

2. Accept the default installation path.

Figure 12: Select installation Folder for Anybus IPconfig

3. Confirm the installation.


PDM # 100742751
Revision: AE
GUIDELINES Date: 22/03/10
Page: 14 of 22

TITLE: WellServices CMTSkidLite OPC to Profibus Interface

Schlumberger Private
Figure 13: Confirm Installation of Anybus IPconfig

4. Close the installation window to complete the installation.

Figure 14: Complete Installation of Anybus IPconfig

5. Go to the following path, “C:\Program Files\HMS\Anybus IPconfig” and double click on Anybus
IPconfig.exe
6. If Windows Security alerts pops up, click on the Unblock button.
PDM # 100742751
Revision: AE
GUIDELINES Date: 22/03/10
Page: 15 of 22

TITLE: WellServices CMTSkidLite OPC to Profibus Interface

Schlumberger Private
Figure 15: Windows Security Alert

7. Flip the IP Switch number 8 to ON position; it will assign the following IP to the Gateway
192.168.0.1, as is highlighted on the Network Installation Sheet (Page 22, figure 23).
8. Changed the IP address on CMTSkidLite PC to 192.168.0.2
9. Once the Software opens click on Scan to search the Anybus device as shown in Figure 16.

Figure 16: Anybus IPconfig

10. Double click on the IP address number to display the configuration settings.
PDM # 100742751
Revision: AE
GUIDELINES Date: 22/03/10
Page: 16 of 22

TITLE: WellServices CMTSkidLite OPC to Profibus Interface

11. Change the Ethernet Configuration Settings as showed below and click on the Set button.

Schlumberger Private
Figure 17: Ethernet Configuration

12. Reset the IP Switch number 8 to off position, it will enable the IP address previously set up on the
last step.
13. Change the PC CMTSkidLite IP address back to 192.168.2.3
14. Disconnect and Reconnect the power to the Anybus device to restart the device.
15. Re-open the AnyBus IPconfig software, scan for the Anybus interface and confirm that it sees the
Anybus Interface.
PDM # 100742751
Revision: AE
GUIDELINES Date: 22/03/10
Page: 17 of 22

TITLE: WellServices CMTSkidLite OPC to Profibus Interface

5. CMTSkidLite OPC Server Settings


1. On the SkidLite computer go to “C:\Program Files\Schlumberger\CMTSkidLite1.2\ncdata”
2. Open the file cmt_skid_lite.ini.
3. Go the line [CommSource] and make sure that “selection=1” (Figure 18), it indicates OPC enable
for data transfer.

Schlumberger Private
Figure 18: cmt_skid_lit.ini.

4. Save changes
5. Open CMTSkidLite Software
Note: The CMTSkidLite version must be 1.2 build 15 or higher.
PDM # 100742751
Revision: AE
GUIDELINES Date: 22/03/10
Page: 18 of 22

TITLE: WellServices CMTSkidLite OPC to Profibus Interface

6. XferCIPprofi Software Configuration


The following instructions describe the necessary steps to install and configure the XferCIPprofi
software to allow data transfer between CMTSkidLite OPC server and the profibus network.

If the XferCIPprofi software is not installed precede with the following steps otherwise go to step
number 4.

1. Double click on the XferCIPprofi Wix.zip file and subsequently on XferCIPprofi Wix.msi to
begin with the installation.

Schlumberger Private
Figure 19: XferCIPprofi Wix.msi

2. Select “Yes” to ignore the warning.

Figure 20: WinZip Caution


PDM # 100742751
Revision: AE
GUIDELINES Date: 22/03/10
Page: 19 of 22

TITLE: WellServices CMTSkidLite OPC to Profibus Interface

3. Verify the existence of the following icon on the computer desktop.

XferCIPprofi.lnk

4. Replace the file Config1.xml to the following path” C:\Program Files\XferCIPprofi\data”

Schlumberger Private
Figure 21: Window Explorer - C:\Program Files\XferCIPprofi\data

5. Replace the existing file by clicking on yes.