ADDITIONAL NOTES GENERAL NOTES


DIMENSIONS:
1. ALL MDB SHALL BE SUPPLIED BY DUAL TRANSFORMER TO
PROVIDE POWER REDUNDANCY. -All dimensions to Gridline unless otherwise indicated.
-Grid is set out to a Local Plane Grid (Revit Project Point) established by the Architect
2. TRANSFORMER SUPPLYING HOSPITAL FACILITY SHALL BE -All SURVEY Points are given to Universal Transverse Mercator (UTM)
LOADED UPTO 70% CAPACITY ONLY. -Setting out of Building Origin (Intersection of Gridlines 32, R23 & 113)
IN THE EVENT OF MAINS FAILURE, SECONDARY -Refer to Dwg No:MI-AA-03-A2-B01.00-A0-10-001 for Grid Setting Out
-UTM Datum: N: 2 755 098.815m / E: 654 766.407m
TRANSFORMER WILL OPERATE IN AF MODE WITH -There can be no deviation from these coordinates without prior agreement with
140% OF ITS RATED CAPACITY TO SUPPORT TWO MDBs the Architect.
OPERATING IN FULL LOAD. -Wall setting out and o/a thickness subject to detail design by Structural Engineer.
-Setting out of curved walls to coordinates as indicated on drawing, (coordinates given to
3. THESE DETAILS MAYBE SUBJECT TO ADJUSTMENT DURING TECHNICAL UTM Datum).
DESIGN AND CONSTRUCTION STAGES. -Center point of curved walls to Building Origin (as above).
-Dimensions along arc indicated by 'ARC LENGTH'.
LEVEL 10 4. REFER TO CALCULATION REPORT B01.00-E011 TOWER BLOCK 7 & 8 -Dimensions between points on curved wall indicated by 'CHORD LENGTH'
FOR VOLTAGE DROP AND FAULT VALUES.
5. CABLE LENGTHS TO BE REVISITED PRIOR TO PROCUREMENT.
SHEET NOTES
MAIN EQUIPMENT REFERENCE
(E) MDB - B01.00 - SS1 - 01 ELECTRICAL NOTES:
EQUIPMENT NO. 1. REFER TO DRAWING MI-RS-A2-B01.00-E0-00-001-04 AND MI-RS-A2-B01.00-
E0-00-002-04 FOR LEGENDS, SYMBOLS AND GENERAL NOTES.
SUBSTATION
BUILDING CODE
EQUIPMENT TYPE
MDB - MAINDISTRIBUTION BOARD
MVSG - MV SWITCHGEAR
PFC - POWER FACTOR CORRECTION BANK
TX - TRANSFORMER
OPTIONAL
E - ESSENTIAL SUPPLY
PANEL BOARD REFERENCE U - SUPPLY VIA UPS
(E) DB - B01.00 - 4a - GL - P1

LOAD TYPE & PANEL NO.


P# - POWER PANEL
L# - LIGHTING PANEL
# - COMBINED POWER & LIGHTING
FLOOR LEVEL
ZONE ID
BUILDING CODE
PANEL TYPE
SMDB - SUBMAIN DISTRIBUTION BOARD
MCC - MOTOR CONTROL CENTRE
CABLE SCHEDULE : CMDB-B01.00-9b-L9-1 CABLE SCHEDULE : CMDB-B01.00-9a-L9-1 DB - DISTRIBUTION BOARD
IPP - ISOLATED POWER PANEL
ATS - AUTOMATIC TRANSFER SWITCH
CIRCUIT NO. DESCRIPTION LENGTH (m) CIRCUIT NO. DESCRIPTION LENGTH (m)
UPS - UNINTERRUPTIBLE POWER SUPPLY
FPCP - FIRE PUMP CONTROL PANEL
1 4C-70mm² FIRE RATED LS0H + 1C-35mm² Cu/PVC (E) 35 1 4C-70mm² FIRE RATED LS0H + 1C-35mm² Cu/PVC (E) 99
JPCP - JOCKEY PUMP CONTROL PANEL
LCP - LIGHTING CONTROL PANEL
2 4C-70mm² FIRE RATED LS0H + 1C-35mm² Cu/PVC (E) 41 2 4C-70mm² FIRE RATED LS0H + 1C-35mm² Cu/PVC (E) 105
OPTIONAL
3 4C-70mm² FIRE RATED LS0H + 1C-35mm² Cu/PVC (E) 47 3 4C-70mm² FIRE RATED LS0H + 1C-35mm² Cu/PVC (E) 111 E - ESSENTIAL SUPPLY
C - SUPPLY VIA UPS
4 4C-70mm² FIRE RATED LS0H + 1C-35mm² Cu/PVC (E) 53 4 4C-70mm² FIRE RATED LS0H + 1C-35mm² Cu/PVC (E) 117 T - ICT LOADS
SPARE SPARE SPARE SPARE SPARE SPARE I - SUPPLY VIA UPS TO ISOLATION TRANSFORMER
5 4C-70mm² FIRE RATED LS0H + 1C-35mm² Cu/PVC (E) 59 5 4C-70mm² FIRE RATED LS0H + 1C-35mm² Cu/PVC (E) 123
1 2 3 4 5 1 2 3 4 5

TO SCADA/BMS
EMU EMU EMU EMU EMU EMU EMU EMU EMU EMU

160 AT 160 AT 160 AT 160 AT 160 AT 160 AT 160 AT 160 AT 160 AT 160 AT 160 AT 160 AT 160 AT 160 AT 160 AT 160 AT
400 AF 400 AF 400 AF 400 AF 400 AF 400 AF 400 AF 400 AF 400 AF 400 AF 400 AF 400 AF 400 AF 400 AF 400 AF 400 AF 400 AF
TP&N TP&N TP&N TP&N TP&N TP&N TP&N TP&N 800A, TP&N, TP&N TP&N TP&N TP&N TP&N TP&N TP&N TP&N
ACB , N/O

1000A, TPN+E, 400V, 60Hz, 35kA @ 3 SEC. 1000A, TPN+E, 400V, 35Hz, 60kA @ 3 SEC.
A A A 800:5A 800:5A A A A

B B G B B G

OC SC EF U/V 800:5A 800:5A U/V EF SC OC

V SS SS V

CMDB-B01.00-9b-L9-1 CMDB-B01.00-9a-L9-1
TCL= 122.28 kW 800A 800A TCL= 119.31 kW
MD = 92.07 kW TP&N, ACB TP&N, ACB MD = 90.09 kW
@ 75% D.F M M @ 76% D.F
N/C N/C
NEUTRAL BAR ELECTRO NEUTRAL BAR
MECHANICAL
EARTH BAR EARTH BAR
IP42 FORM 4b TYPE 6 INTERLOCK IP42 FORM 4b TYPE 6

STS-B01.00-9b-L9-1 STS STS STS-B01.00-9a-L9-1

CUPS-B01.00-9b-L9-1 CUPS-B01.00-9a-L9-1
350kW 3:3 350kW 3:3
ON-LINE ON-LINE
MODULAR MODULAR
UPS UPS

800A 800A
ATS-B01.00-9b-L9-4 ATS-B01.00-9a-L9-5
4P 4P 02A 26-11-2017 ISSUED FOR M-T APPROVAL

CUPS ROOM 01 20-11-2016 ISSUED FOR M-T APPROVAL

00 31-07-2016 DESIGN DEVELOPMENT


Rev # Rev Date Revision Description
FROM GMDB-B01.00-SS6-01 via CORE 9a RISER FROM GMDB-B01.00-SS6-02 via CORE 9b RISER
02A 26-11-2017 RS GE ISSUED FOR M-T APPROVAL

Current Rev # and Date Orig. Signature ABV Approval Signature


FROM EMDB-B01.00-SS6-01 via CORE 9b RISER FROM EMDB-B01.00-SS6-02 via CORE 9a RISER General Notes :
THE CONSULTANT RETAINS COPYRIGHT OF ALL DOCUMENTS PREPARED BY HIM.
ALL RELEVANT DETAILS, LEVELS AND DIMENSIONS ARE TO BE CHECKED ON SITE
PRIOR TO COMMENCEMENT OF WORK.
ANY DISCREPANCIES ARE TO BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT. THE ARCHITECT ACCEPTS NO RESPONSIBILITY FOR ERRORS
RESULTING FROM MISINTERPRETATION OF THE DRAWINGS.
ALL WORK TO BE CARRIED OUT STRICTLY IN ACCORDANCE WITH NATIONAL
BUILDING
REGULATIONS AND LOCAL AUTHORITY REGULATIONS. ALL DIMENSIONS ARE IN
MILLIMETRES U.N.O.
DO NOT SCALE THIS DRAWING.
USE FIGURED DIMENSIONS ONLY.

KeyPlan : Zone : /

LEVEL 9 LEVEL 9

CSMDB-B01.00-9b-L8-1 CSMDB-B01.00-9a-L8-1
5 TCL= 16.41 kW TCL= 17.64 kW 5
MD = 12.35 kW
682 @75% D.F.
MD = 13.34 kW 681
@76% D.F.

Owner :
LEVEL 8 LEVEL 8 Kingdom of Saudi Arabia
Ministry of Interior

CSMDB-B01.00-9b-L7-1 CSMDB-B01.00-9a-L7-1
4 TCL= 23.16 kW TCL= 19.05 kW 4
MD = 17.44 kW
682 @75% D.F.
MD = 14.34 kW 681
@75% D.F. SECURITY FORCES MEDICAL CENTER PROJECT AT RIYADH AND JEDDAH

Engineer / Owners Representative :


LEVEL 7 LEVEL 7

CSMDB-B01.00-9b-L6-1 CSMDB-B01.00-9a-L6-1
3 TCL= 23.16 kW TCL= 19.05 kW 3
MD = 17.44 kW
682 @75% D.F.
MD = 14.34 kW 681
@75% D.F. Contractor : ABV Rock Group Co. Ltd.

LEVEL 6 LEVEL 6

CSMDB-B01.00-9b-L5-1 CSMDB-B01.00-9a-L5-1
TCL= 27.21 kW ABV ROCK Group Co. Ltd. Lead Designer / Consultant :
2 TCL= 32.48 kW 2
MD = 20.49 kW
682 @73% D.F.
MD = 24.65 kW 681 P&T Architects and Engineers Ltd.
@76% D.F. Al Hudaiba Awards Bldg., 5/F, Unit 510 Block B,
Mina Rashid/ Jumeirah 1 Road
P O Box 112025 Block B
Tel 971 4 350 3800/ 358 6803, Fax 971 4 358 6800
LEVEL 5 LEVEL 5 E-mail: pt.dubai@p-t-group.com,Website:www.p-t-group.com

ABV ROCK Group Co. Ltd. Structural,Infrastructure and MEPF Consultant:

CSMDB-B01.00-9b-L4-1 HYDER & SOLAIMAN ELKHEREIJI CONSULTING COMPANY


CSMDB-B01.00-9a-L4-1 P.O Box 1655
1 TCL= 32.34 kW TCL= 31.09 kW 1
MD = 24.35 kW Jeddah 21441
682 @76% D.F.
MD = 23.42 kW 681 Kingdom of Saudi Arabia
@75% D.F. Tel: +966 126044700
Fax: +966 126044701
Sub Consultant:
LEVEL 4 LEVEL 4
11/24/2017 1:48:31 PM

CORE-9b 1 SCHEMATIC CORE-9a


(RISER / EE ROOM) - NTS (RISER / EE ROOM) CAD/BIM Filename : Floor : Scale :

CMDB-B01.00-9b-L9-1 MI - RS - A2 - B01.00 - E0 - RS - 680 - 05 - 02A NTS


CMDB-B01.00-9a-L9-1 Drawing Title :
HOSPITAL BUILDING
TOWER BLOCK 7
PRINTED/EXPORTED ON:

SUBSTATION 6 SUB MAIN DISTRIBUTION SCHEMATIC


DIAGRAM (CRITICAL - UPS) - SHEET 1
DWG No.

MI RS A2 B01.00 E0 RS 680 05 02A