Professional Documents
Culture Documents
fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2021.3061434, IEEE
Transactions on Power Systems 1
Abstract—Large-scale integration of renewable generation, usu- to different types of grid-forming and grid-following converter
ally interfaced to the network through power electronics, has control schemes. While providing valuable insights into the
led to drastic changes in power system dynamics. This paper operation of individual converter-interfaced generation units, all
presents novel insights into stability properties of such systems.
For that purpose, a high-fidelity dynamic model of a generic low- aforementioned studies consider single-generator models and a
inertia power system has been developed. The full-order, state-of- stiff grid equivalent, which oversimplifies the problem.
the-art control schemes of both synchronous and converter-based Multi-inverter configurations have also been thoroughly in-
generators are included, with the latter differentiating between
grid-forming and grid-following mode of operation. Furthermore, vestigated in the literature. Studies in [11]–[13] propose var-
the dynamics of transmission lines and loads are captured in ious state-space models for small systems comprised of two
the model. Using modal analysis techniques such as participation or three inverters connected through constant impedance lines,
factors and parameter sensitivity, the most vulnerable segments followed by stability analyses such as droop gain parameter
of the system are determined and the adverse effects of timescale sweeps and the impact of R/X ratio of the interconnecting
coupling and control interference are investigated. More precisely,
this work characterizes the maximum permissible penetration levels cables. However, the authors use simplified inverter models
of inverter-based generation as well as the nature of the associated comprising only droop control and LCL filter dynamics, thus
unstable modes and the underlying dynamics. Finally, potential neglecting device-level control and line dynamics in the process.
directions for improving the system stability margin under different Moreover, they only consider grid-forming operation and do not
generation portfolios are proposed for several benchmark systems. take into account a potentially adverse impact of Phase-Locked
Loops (PLLs) on system stability. Alternatively, [14] focuses
Index Terms—differential-algebraic equations, voltage source on interactions between a virtual synchronous generator and a
converter, synchronous generator, small-signal stability, low-inertia converter-interfaced load by considering small-signal stability
systems
under different operating conditions. While the authors include
a dynamic model of the load and the interconnecting line, they
I. I NTRODUCTION analyze stability solely via parameter sweeps of the virtual inertia
to convergence of economic and policy drivers, large-
UE constant and load impedance, which does not provide enough
D scale electric power grids are hosting rapidly increasing
amounts of wind and solar generation as well as battery stor-
insight into the nature of potential instabilities. A more general
and rigorous approach towards synchronization and stability
age. These sources often interface with the grid via Voltage analysis of droop-based microgrids is taken in [15]–[17], where
Source Converters (VSCs), whose interaction with the grid is the appropriate conditions for synchronization, power sharing
substantially different from synchronous machines and poses and voltage stability of droop-controlled inverters in islanded
many challenges for power system modeling, analysis and con- microgrids have been derived. Nevertheless, the aforementioned
trol [1]. Moreover, a high penetration of fast-acting VSCs may simplifications in terms of model complexity are still present.
create unexpected couplings and existing control approaches may In contrast, the studies in [19]–[22] focus on detailed system
become less valid, thus adversely affecting frequency and voltage models which include both low and high inverter frequency
stability. With the aim of providing solutions to the underlying dynamics as well as the network and load dynamics, and propose
problems, detailed and accurate models of low-inertia systems accurate small-signal representation of real-size microgrids. The
in the form of Ordinary Differential Equation (ODE) are needed work in [22] provides analysis in terms of system eigenvalues
for the purpose of small-signal analysis. and their sensitivity to different states. It was observed that the
The field of small-signal analysis is well established for con- dominant low-frequency modes are highly sensitive to network
ventional power systems [2]–[4]. With the increasing integration configuration and the parameters of the power sharing controller,
of renewables, a number of publications addressing modeling and whereas the high frequency modes are largely sensitive to the
stability of 100 % inverter-based microgrids has emerged, vary- inverter inner loop controllers, network dynamics, and load dy-
ing from the analysis of individual converter operation modes in namics. However, only grid-forming mode of operation has been
a single-machine infinite-bus equivalent [5]–[10] to operation of taken into consideration. Alternatively, the authors in [19] present
small and real-size distribution grids [11]–[21]. The former stud- a new methodology for forming, augmenting, and modifying
ies mostly emphasize the validation of the proposed small-signal the state-space matrices of large microgrids comprising both
models and provide insights into the stability characteristics and grid-forming and grid-following inverter control schemes, and
modes of individual inverter control schemes by analyzing their investigate a 100 % inverter-based 69-bus distribution system.
sensitivities with respect to system parameters. In particular, The emphasis is however on model validation, state matrix par-
[5] and [6] investigate stability properties of grid-supporting titioning and optimal control tuning for improving the oscillatory
inverters operating as virtual synchronous machines, [7] com- modes in the system, but not on the stability analysis. Further-
pares dynamic characteristics of droop-based grid-feeding and more, [20] sets a particular focus on inner cascade loops and the
grid-supporting VSCs, whereas [8]–[10] extend these analyses differences in small-signal stability of a three-inverter microgrid
0885-8950 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Universidad de chile. Downloaded on March 06,2021 at 21:50:42 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2021.3061434, IEEE
Transactions on Power Systems 2
utilizing conventional PI-based and internal model-based control tions and phenomena. On the other hand, [37] and [38] employ
approaches. Eigenvalue sensitivity analysis with respect to power systematic nonlinear simulations and off-the-shelf small-signal
droop gains and filter inductance again reveals that the low- analysis tools to assess the impact of increased penetration of
frequency modes are highly sensitive to the parameters of the wind and photovoltaic generation on stability of the Kundur two-
power sharing controllers for both methods. area and the western North American power system, respectively.
On the other hand, [21] proposes an approximation method Both studies are however restricted solely to the investigation of
based on critical clusters for assessing the droop gain stability inter-area oscillations and the nature of underlying oscillatory
margins of medium-scale islanded microgrids that takes ad- modes.
vantage of the fact that the contribution of inverters to the Alternatively, a two-bus system comprising a grid-following
small-signal stability may depend on their location and the VSC and a synchronous generator was investigated in [39] and
interactions with each other. Both [20] and [21] are however [40] through eigenvalue analysis. Both studies point out that the
solely restricted to grid-forming VSCs and do not investigate the PLL can be a source of oscillatory modes and instability. The
adverse interactions between different converter control schemes. work in [39] incorporates relatively detailed control structures of
The latter aspect is partially tackled in [23] by analyzing stability both units, but mostly focuses on model validation and sensitivity
issues between a grid-feeding VSC and an inverter operating as analysis to determine the optimal ranges of relevant control
a virtual synchronous generator, with a focus on virtual inertia parameters. On the other hand, the authors in [40] provide
characteristics and interaction between power converters and the insightful remarks regarding the permissible penetration levels
AC grid. Moreover, [23]–[25] highlight some conceptual differ- of grid-following inverters, as well as the relevance of different
ences between a traditional and an inverter-based power system controllers on small-signal stability. However, they employ an
in terms of associated control timescales. Nonetheless, they all inverter scaling method that complicates model implementation
confine the analysis only to 100 % inverter-based microgrids. on a larger system and omit the Power System Stabilizer (PSS)
While the aforementioned studies provide various perspectives and important flux dynamics from the SG model. Furthermore,
on stability of microgrids and zero-inertia systems, less em- neither of the aforementioned studies explore the deeper causes
phasis has been placed on performance of large-scale systems of instability, nor consider the impact of different converter
with a mixture of synchronous machines and VSCs. Having operation modes. Finally, the focus is primarily on distribution
in mind that operators in Ireland [26], Texas [27] and South networks and microgrids, thus neglecting the potential impact of
Australia [28] are already facing obstacles regarding high wind transmission line dynamics.
penetration during certain periods of the day, the fundamental The work presented in this paper improves on the existing
understanding of low-inertia systems and their stability properties literature in several ways. In contrast to [19]–[25], we include
is of crucial importance. Nevertheless, simulation and analysis of several converter operation modes and investigate their interac-
large power systems with a mix of synchronous and converter- tions in a 100 % inverter-dominated transmission network. The
based generation involves a significant computational burden. analysis is also extended to low-inertia systems and the adverse
To this end, commercial software packages such as PSLF [29], interference between different components of synchronous and
DSATools [30] and PSS/E [31] are widely employed, both for converter-based generation. However, unlike the work in [33]–
industrial and academic purposes. While these software tools [40], we employ a more detailed representation of a generic,
incorporate detailed dynamic models of different generator types low-inertia system that captures all relevant physical properties
and provide means for large-scale time-domain simulations, they and associated dynamics, including various generation models
are restricted in terms of analytical capabilities and flexibility. and control schemes as well as line and load dynamics. More-
This mostly stems from underlying modeling assumptions valid over, unlike most of the existing studies, we are not primarily
for traditional Synchronous Generator (SG)-based power net- concerned with parameter sensitivity but rather with investigating
works, which are not applicable to inverter-dominated systems. maximum permissible penetrations of PE-interfaced generation
For instance, the widely employed dynamic models for wind and under various system configurations. In particular, the critical
photovoltaic plants, originally proposed by WECC renewable levels of installed inverter-based generation and the key modes
energy modeling task force [32], do not consider dynamics of of arising instability are identified and mapped back to the
high-frequency converter controls and PLLs, which can have a respective controller dynamics.
detrimental impact on stability. Furthermore, transmission line Our findings suggest that the root cause of instability cannot
dynamics are typically neglected in power system studies due to be associated solely with the aggregate power injection of VSC
drastically shorter timescales compared to SG dynamics. With units, as it varies depending on the installed capacity and operat-
the introduction of fast-acting Power Electronic (PE) devices, ing setpoints of renewable generation. Additionally, the problems
such assumptions are not valid anymore [1]. arising from underlying timescale coupling of converter and
In turn, the existing literature on stability of large-scale trans- transmission line dynamics, as well as the timescale separation
mission systems with high share of inverter-based generation between the respective VSC and SG controllers regulating the
tends to neglect important aspects of system dynamics and same system quantities have been observed. As a result, new
confine the analytical analysis to simplified mathematical models insights into the overall stability of low- and no-inertia systems
and state-space formulations. More precisely, [33]–[36] study the are presented, together with potential directions for improving
impact of large-scale wind power generation on power system the system stability margin under different generation portfolios
oscillation, transient and small-signal stability. However, the and the analytical expressions for necessary control criteria
authors either use oversimplified synchronous generator models pertaining to the impact of line dynamics. Furthermore, some
(i.e., not equipped with governors and exciters) [33], neglect of the widely common premises in terms of stability and overall
inner control loops of inverter-interfaced wind generation [34], system dynamics have been debunked solely as an artifact of
[35] or focus on high-level probabilistic frameworks [36], which inadequate modeling and system representation, which justifies
obstructs them from capturing some important dynamic interac- the importance of the proposed ODE formulation and the level
0885-8950 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Universidad de chile. Downloaded on March 06,2021 at 21:50:42 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2021.3061434, IEEE
Transactions on Power Systems 3
?
vdc xm = (if , vf , ig , vdc )
i?dc rd Device rs System us
Level Level u
Control Control ?
rd = (θr , ωr , vsw , i?dc ) Power ym = (if , vf , ig , vdc )
?
vsw ∠θc yd ys Converter
Model
idc isw if ig
+ if Rf Lf ig Rt Lt
vdc Gdc Cdc
Fig. 2. Simplified MIMO structure of the device model.
− + + +
vsw Cf vf vt
Power Converter (Device) Model − − −
A. Converter Control Scheme
The prevalent control architecture for power converters is the
- power ctrl. - reference tracking - DC-link capacitor
- AC voltage ctrl. - DC voltage ctrl. - lossless switching two-level VSC shown in Fig. 1. In this setup, an outer system-
- frequency ctrl. - operating in SRF - output filter level control provides a reference for the converter’s terminal
voltage that is subsequently tracked by a cascaded device-level
setpoint
System
output
Device
device
Power
system controller. We first present the model of a two-level voltage
Level Level Converter
input Control references Control references Model output source converter and subsequently discuss the individual control
measurements
blocks depicted in Fig. 1.
1) Power Converter Model: The three-phase power converter
Fig. 1. Representation of the VSC model: two-level VSC connected through a
transformer to the grid (top); general input-output block structure of the power model (i.e., the device model in Fig. 1) used in this study
converter model and its control scheme (bottom). consists of a DC-link capacitor, a lossless switching block which
modulates the DC-capacitor voltage vdc ∈ R>0 into a three-
abc
phase AC voltage vsw ∈ R3 , and an output filter. Throughout
of detail included in this study. this work, we assume that the DC-source current idc ∈ R>0
The remainder of the paper is structured as follows. In is supplied by a controllable source (e.g., an energy storage or
Section II, detailed dynamical models and control schemes a curtailed renewable generation) and can be used as a control
of synchronous and converter-based generators are presented, input. Averaging the dynamics over one switching period and
together with the general ODE formulation of an arbitrary low- expressing them in per-unit yields:
inertia power system. Subsequently, the underlying timescales cdc
and the potential adverse dynamical interactions are discussed v̇dc = −gdc vdc − isw + idc , (2a)
ωb
in Section III. The numerical results from different case studies
`f abc
and the respective small-signal stability margins are illustrated i̇ = −rf iabc abc
f + vsw − vf ,
abc
(2b)
in Sections IV and V, whereas Section VI draws the main ωb f
cf abc
conclusions and discusses the key findings and outlook of the v̇ = +iabc abc
f − ig , (2c)
study. ωb f
addition, the dynamics of network elements such as impedance vfabc ∈ R3 , and iabc g ∈ R3 to denote the three-phase filter
loads, shunt capacitors and transmission lines are also taken into current, three-phase converter voltage and three-phase current
consideration. injection into the system. As this work deals strictly with per-
We use R to denote the set of real and natural numbers and, unit formulation of converter models and controls, the explicit
e.g., R≥a := {x ∈ R|x ≥ a}. Given an angle θ ∈ [−π, π), the per-unit declaration of system variables in (2) and the rest of the
2-D rotation matrix is given by paper will be omitted for brevity.
We assume that the three-phase signals are balanced and, given
cos θ − sin θ a reference angle θr ∈ [−π, π), the converter variables can be
R(θ) := ∈ R2×2 . (1) defined in a rotating dq-reference frame by applying the power-
sin θ cos θ
variant dq-transform (see e.g., [41])
Moreover, we define the 90◦ rotation matrix j := R(π/2) that
can be 2 cos θr cos(θr − 2π 2π
3 ) cos(θr + 3 )
√ interpreted as an embedding of the complex imaginary T (θr ) := (3)
unit −1 into R2 . For column vectors x ∈ Rn and y ∈ Rm 3 sin θr sin(θr − 2π 3 ) sin(θr + 2π
3 )
we use (x, y) = [xT , y T ]T ∈ Rn+m to denote a stacked vector.
Furthermore, In denotes the identity matrix of dimension n, ⊗ to the three-phase converter signals (e.g., vfdq = T (θr )vfabc ). For
denotes the Kronecker product, and kxk denotes the Euclidean reasons similar to the ones pertaining to per-unit notation, the dq
norm. Matrices of zeros of dimension n × m are denoted by superscript will not be used in the remainder of the paper, i.e.,
0n×m , and 0n and 1n denote column vectors of zeros and ones the presented converter model will be described in dq-vector
of length n. form x := xdq := (xd , xq ) and per-unit. Therefore, guided
0885-8950 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Universidad de chile. Downloaded on March 06,2021 at 21:50:42 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2021.3061434, IEEE
Transactions on Power Systems 4
by the practice commonly employed in power electronics (see xfollow
s = θs , ε, p̃c , q̃c
Appendix A), we rewrite filter dynamics in (2b)-(2c) as
ωb rf ys = (vf , pc , qc ) System rs = i?f
i̇f = (vsw − vf ) − ωb + jωb ωr if , (4a) Level
`f `f us = (p?c , qc? , ωc? , Vc? ) r̂s = (θs , ωs )
Control
ωb
v̇f = (if − ig ) − jωb ωr vf . (4b)
cf
xform
s = θc , ω̃c , ṽc
The converter is usually interfaced to the grid through a trans-
former, with the dynamics of transformer current (i.e., current
injected into the grid) described by ys = (vf , ig , vdc ) System rs = θc , ωc , vf?
Level
ωb rt us = (p?c /vdc
?
, qc? , ωc? , Vc? ) Control
i̇g = (vf − vt ) − ωb + jωb ωr ig , (4c)
`t `t Fig. 3. Simplified MIMO structure of the system-level control: grid-following
operation mode (top) and grid-forming operation mode (bottom).
where rt ∈ R>0 and `t ∈ R>0 denote the transformer’s per-
unit resistance and inductance, vt ∈ R2 is the voltage at the
connection terminal, and ωr ∈ R>0 is the normalized reference
for the angular velocity of the dq-frame. for simplicity. Therefore, the remainder of this paper will focus
Expressions in (4) represent the AC-side dynamics of the only on droop control as a mean of system-level regulation.
power converter and, together with DC-side dynamics in Grid-Following Control: The two converter modes are fun-
(2a), complete the 7th -order power converter model described damentally different. In the context of grid-following control,
by xm = (if , vf , ig , vdc ) ∈ R7 and depicted in Fig. 2. the measurements ys = (vf , pc , qc ) ∈ R4 are commonly the
The input vector comprises device-level references1 rd = output voltage and the active and reactive power. Moreover, (6)
?
(θr , ωr , vsw , i?dc ) ∈ R5 and the measurement output ym encom- models a synchronization device - usually a PLL - that estimates
passes full state feedback for system- and device-level control the phase angle θs ∈ [−π, π) of the voltage vf as well as the
(i.e., xm ⊂ ym ), as well as the converter’s AC-voltage magnitude synchronous (grid) frequency ωs ∈ R>0 at the Point of Common
Vc ∈ R>0 and instantaneous active and reactive power injection Coupling (PCC), and provides them as reference r̂s = (θs , ωs )
(pc , qc ) ∈ R2 given by to the device-level control (see Fig. 3). Additionally, the so-
called outer control loop is used to calculate the current reference
Vc := kvf k, pc := vfT ig , qc := vfT j T ig . (5) i?f ∈ R2 based on the mismatch between measured signals ys
and prescribed setpoints us . Hence, the system-level controller
The latter three measurements are directly obtained from con-
is described by xfollow
s = (θs , ε, p̃c , q̃c ) ∈ R4 , where p̃c ∈ R
verter’s output voltage vf and current ig and are therefore not
and q̃c ∈ R are the internal states corresponding to active and
explicitly included in ym := xm for brevity. However, these
reactive power, respectively. Since the angle (θs ) and frequency
measurements will be considered available to the system-level
(ωs ) references are measured and passed through to device-level
control. In fact, this control layer often includes processing of
control (i.e., they are not regulated by an appropriate control
vf and ig such that the quantities in (5) are internally obtained.
? law), we do not include them into the main output reference
Moreover, note that we assume vsw := vsw , i.e., the modulation
? vector r.
voltage reference vsw is perfectly transformed to the AC side.
Due to high modeling complexity and very fast underlying The most common PLL implementation is a so-called type-2
dynamics [42], the converter switching is not included in the SRF PLL [51], which achieves synchronization by diminishing
model nor will it be considered throughout this study. the q-component vfq ∈ R of the voltage via PI control, thus
2) System-Level Control: The desired dynamic behavior of aligning the d-axis of the Synchronously-rotating Reference
the power converter as seen from the system point of view is Frame (SRF) with the output voltage vector vf [7], [9], [10]:
commonly prescribed by a dynamic controller of the form
ẋs = κ(xs , ys , us ), (6a) ε̇ = vfq , (7a)
rs = h(xs , ys , us ), (6b) ωs = ω0 + KPs vfq + KIs ε, (7b)
where xs ∈ Rn is a vector of internal controller states, ys ∈ Rm θ̇s = ωb ωs . (7c)
are the measured converter outputs, us ∈ Rp are the prescribed
control setpoints, and rs ∈ Rq is a vector of computed references Here, (KPs , KIs ) are the proportional and integral control gains
sent to the device-level control. A simplified representation of of the synchronization unit, ω0 = 1 p.u. is the nominal angular
the general MIMO structure for both grid-forming and grid- frequency, and ε ∈ R is the integrator state. Note that the grid-
following operation mode is illustrated in Fig. 3, with the former following converters require an established three-phase voltage at
mode potentially differentiating between several representative the connection terminal in order to obtain a reasonable frequency
classes of control such as droop control [43], [44], Virtual (i.e., angle) signal. Therefore, they do not posses standalone nor
Synchronous Machine (VSM) control [45], [46], Virtual Oscil- black start capabilities.
lator Control (VOC) [47], [48] and matching control [49], [50].
Having determined the synchronous angle and frequency
However, under certain trivial conditions, all aforementioned
(θs , ωs ), the outer control loop subsequently computes the cur-
control strategies showcase a small-signal equivalence (see e.g.,
rent reference i?f ∈ R2 . By employing frequency and voltage
[48]), and can be subsumed under a single droop-based controller
droop control (Rcω ∈ R≥0 , Rcv ∈ R≥0 ) in combination with
d q
1 We assume perfect tracking of the DC-current reference, i.e., i ?
dc = idc in
integral controllers KI,f ∈ R>0 and KI,f ∈ R>0 , the outer
(2a). control loop, described by internal states variables (p̃c , q̃c ), regu-
0885-8950 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Universidad de chile. Downloaded on March 06,2021 at 21:50:42 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2021.3061434, IEEE
Transactions on Power Systems 5
lates the power output (pc , qc ) to its respective setpoint (p?c , qc? ), in dq-coordinates defined by (θc , ωc ), the device-level control
as follows: is described by a cascade of voltage and current controllers
(also called inner control loops) computing a switching voltage
p̃˙c = KI,f
d
(p?c − pc − Rcω (ωs − ωc? )) , (8a) ?
reference vsw ∈ R2 [5], [46]. More precisely, it encompasses a
q
˙q̃c = K (qc? − qc − Rcv (kvf k − Vc? )) .
I,f (8b) PI voltage controller
Due to the P − f and Q − V droop characteristics, the active ξ˙ = vf? − vf , (12a)
power reference is adjusted in response to a deviation of the i?f = KPv (vf? − vf ) + KIv ξ + KFv ig + jωc cf vf , (12b)
measured frequency ωs with respect to the frequency setpoint ωc? ,
whereas the reactive power reference is modified according to the that provides an internal current reference i?f for a current PI
mismatch between the magnitude of the output voltage kvf k and controller
the converter voltage setpoint Vc? . Hence, the internal state vector
γ̇ = i?f − if , (13a)
of the system-level controller is xfollow
s = (θs , ωs , p̃c , q̃c ) ∈ R4 ,
?
with p̃c and q̃c representing the power (i.e., dq-current) refer- vsw = KPi (i?f − if ) + KIi γ + KFi vf + jωc `f if , (13b)
ences. It should be pointed out that the controller (8) can take
where (KPv , KPi ) ∈ R2>0 , (KIv , KIi ) ∈ R2≥0 and (KFv , KFi ) ∈
different forms, varying from a traditional frequency/AC-voltage
droop control [14] and droop control with a low-pass filter [10] Z2{0,1} are the respective proportional, integral, and feed-forward
to DC-energy/reactive power droop control [52]. gains, ξ ∈ R2 and γ ∈ R2 represent the integrator states,
The computed power references are then transformed into and superscripts v and i denote the voltage and current con-
the corresponding current reference signal rs = i?f , with two trollers [9], [22], [56]. Note that the angular velocity ωc of an
commonly used implementations for balanced systems: a con- SRF is reflected in the last terms of (12b) and (13b).
stant current and a constant power mode. The first approach Finally, the DC voltage is controlled through the DC-current
directly feeds the power references to the device-level control source and a PI controller, as follows:
i?f = (p̃c , q̃c ), while the second mode adjusts them based on ?
χ̇ = vdc − vdc , (14a)
output voltage measurement such that the converter’s power
output is kept constant: idc = KPdc (vdc
?
− vdc ) + KIdc χ + KFdc i?dc , (14b)
?
vfd p̃c + vfq q̃c vfq p̃c − vfd q̃c with DC-voltage setpoint ud = ∈ R>0 being an external
vdc
i?f d = , i?f q = . (9) control input, χ ∈ R the internal state variable, and proportional,
kvf k kvf k integral, and feed-forward gains denoted by KPdc ∈ R>0 , KIdc ∈
Grid-Forming Control: Droop control is the prevalent con- R≥0 , and KFdc ∈ {0, 1}, respectively. The DC current reference
trol scheme for parallel grid-forming converters [53]–[55]. It i?dc ∈ R>0 is determined by the operating point (Vc? , p?c , qc? )
?
achieves synchronization through measuring power imbalance and the converter losses, which indicates that for vdc = vdc the
?
and is inspired by the traditional primary frequency control of DC-side current will be idc = idc .
a synchronous machine. In particular, by appropriately adjust- Having computed the AC current and voltage (i?f , vsw ?
) and DC
ing the individual droop factors, it enables self-synchronization ?
current (idc ) reference signals, the device-level control output
?
through the power grid and power sharing in proportion to the rd = (θr , ωr , vsw , i?dc ) is sent to the power converter, with
converter rating, while using only local measurements. Droop (θr , ωr ) = (θc , ωc ) being the angular reference adopted from
control is given by the system-level control. The state vector of the controller is
described by xd = (ξ, γ, χ) ∈ R5 . In contrast, the system-level
ωc = ωc? + Rcp λz (s) (p?c − pc ) (10a)
| {z } controller of a grid-following converter provides filter current
ω̃c reference. Therefore, the device-level control only comprises
vcd = Vc? + Rcq λz (s) (qc? − qc ), (10b) AC and DC current computation given by (13)-(14) (i.e., xd =
| {z } (γ, χ) ∈ R3 ), thus bypassing the inner voltage controller. The
ṽc ?
output reference vector rd = (θs , ωs , vsw , i?dc ) is provided to
with Rcp ∈ R>0 and Rcq ∈ R≥0 being the droop gains, the power converter model, with (θr , ωr ) = (θs , ωs ) being
λz θ(s) = ωωz +s
z
representing the low-pass filter applied to the the measured angle and frequency references obtained by a
power measurements, ωz ∈ R>0 denoting its cut-off frequency, synchronization unit within the system-level control.
θ̇c = ωb ωc and vcq = 0. We emphasize that, unlike for the grid- 4) Uniform Converter Model: In order to facilitate an ODE
following operation mode, in this case the angle θc , frequency form of an arbitrary, generic low-inertia system, we propose
ω̃c ∈ R, and voltage ṽc ∈ R are internal states of the control. In a uniform converter model that comprises both grid-forming
contrast, the active active and reactive power injections pc and and grid-following mode of operation within a single control
qc are measured, i.e., ys = (pc , qc ) ∈ R2 . Therefore, the control structure. More precisely, we modify the latter control design
state vector can be defined as xform
s = (θc , ω̃c , ṽc ), where (both in terms of system- and device-level control) such that it
ω̃˙ c = −ωz ω̃c + Rcp ωz (p?c − pc ), (11a) fits the input-output characteristic of a grid-forming VSC while
ṽ˙ c = −ωz ṽc + Rcq ωz (qc? − qc ). (11b)
3) Device-Level Control: We start off by analyzing the xd = (ξ, γ, χ)
device-level control of grid-forming converters, with a general
structure presented in Fig. 4. This control layer provides both AC ?
yd = (if , vf , ig , vdc ) Device rd = θr , ωr , vsw , i?dc
and DC-side reference signals for the VSC device. The AC-side Level
controller operates in a synchronously-rotating dq-frame, with rs = vf? /i?f , ud = vdc
?
Control
the reference angle θc and velocity ωc provided by the system-
level control (6). In particular, given a voltage reference vf? ∈ R2 Fig. 4. Simplified MIMO structure of the device-level control.
0885-8950 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Universidad de chile. Downloaded on March 06,2021 at 21:50:42 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2021.3061434, IEEE
Transactions on Power Systems 6
Device model Rt L t it
System-level control Grid
ig iabc
g vt
Power dq
dq
Calculation vf vfabc
Unit abc
abc
pc qc Cf
ωc?
ωc? /ωs Rf
(vf , ig )
θc vsw i idc
θc sw
0885-8950 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Universidad de chile. Downloaded on March 06,2021 at 21:50:42 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2021.3061434, IEEE
Transactions on Power Systems 7
vg∗ edq
AVR s
vt 1 v1 + vfd Rt Lt it
k·k2 Ke Grid
1 + sTe − +
norm transducer vs exciter saturation vt
PSS
ψ dq dq
a , is
sTw v2 1 + sT1 v3 1 + sT3 pe ←[ τe
Ks ψad iqs − ψaq ids ψfd , ψD1 , ψQ1 , ψQ2
1 + sTw 1 + sT2 1 + sT4
stab. gain washout phase compensation electrical torque internal rotor dynamics
Fig. 6. Block diagram of a synchronous generator equipped with a prime mover, a governor and a voltage excitation system. The internal state variables are denoted
by red color.
Mg ∆ω̇r = ∆pe − Dg ∆ωr , (18) with the subtransient, saturated, mutual reactances x̂da,s ∈ R>0
0885-8950 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Universidad de chile. Downloaded on March 06,2021 at 21:50:42 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2021.3061434, IEEE
Transactions on Power Systems 8
Finally, the inclusion of stator’s circuit balance completes the ilj icj ick ilk
vtj vtk
internal generator model: Zlj Cj Ck Zlk
eds = −ra ids + xl iqs − ψaq , (21a)
eqs = −ra iqs + xl ids − ψad . (21b)
Fig. 7. Generic network model with line dynamics and respective dq-frame
In (21), stator voltage and current vectors are denoted by es ∈ R2 alignment.
and is ∈ R2 , while ra ∈ R>0 and xl ∈ R>0 represent the arma-
ture resistance and leakage reactance respectively. Expressions
(18)-(21) yield a 6th -order dynamical model described by the SRF rotates at constant nominal angular velocity, as pointed out
state vector xintg := θs , ωs , ψfd , ψD1 , ψQ1 , ψD2 ∈ R6 , where in [19].
θ̇s = ωb ωs . For more details regarding the generator modeling Let us introduce a transformation fn : Z>0 7→ Z>0 that maps
and internal parameter computation we refer the reader to [2]. the set of generator indices g ∈ G ⊂ Z>0 to the subset of nodal
2) Control Design and Electrical Interface: The proposed indices of the network with generator connection j ∈ Ng ⊂ N ,
control scheme comprises two independent loops for frequency with N ⊂ Z>0 being the index set of network nodes. Hence,
and voltage regulation [58]. The former one consists of droop the terminal currents3 itg ∈ R2 and voltages vtg ∈ R2 of each
control and governor and turbine dynamics (see Fig. 6), de- generator unit g ∈ G are mapped to vectors itj ∈ R2 and vtj ∈
scribed respectively by state variables pg ∈ R and pm ∈ R R2 corresponding to the terminal currents and voltages of the
(i.e., a state vector xfreq g = (pg , pm ) ∈ R2 ). On the other network nodes j ∈ Ng , where j = fn (g). The nodal vectors
hand, voltage control includes an AVR with a transducer and are subsequently aligned to the SRF of an arbitrary synchronous
a saturated exciter, and a PSS combining a washout filter and a generator or a grid-forming converter r ∈ G, rotating at angular
lead-lag phase compensation, with vectors xAVR g := v1 ∈ R and speed ω ? := ωsr , i.e., ω ? := ωcr , as follows:
xPSS
g := (v , v
2 3 s, v ) ∈ R 3
describing the underlying controller
states respectively. For brevity, we will omit a detailed derivation xnj = R (θ? − θj ) xtj , ∀j ∈ N . (23)
of the control dynamics pertaining to frequency control, AVR and
PSS, as it can be easily deduced from the control block diagram Here, xnj ∈ {inj , vnj } denotes the “nodal” metrics described in
in Fig. 6. Note that all state variables are denoted by red color the nominal reference frame, the uniform SRF angle is computed
in Fig. 6. as θ̇? = ωb ω ? , and θj ∈ [−π, π) corresponds to the internal SRF
As mentioned previously, a synchronous generator is inter- angle of the respective unit, i.e., θj := θsj for the synchronous
faced to the grid through a transformer modeled as a series and θj := θcj for the converter-based generator. According to
impedance rt ∈ R>0 and `t ∈ R>0 . The dynamics of the current [59], [61], such approach provides a good trade-off between the
it ∈ R2 flowing through a transformer can be expressed in an computational complexity and model accuracy.
SRF defined by (θs , ωs ) as The nodal voltage and current dynamics can now be expressed
∀j ∈ N as
ωb rt
i̇t = (es − vt ) − ωb + jωb ωs is , (22)
`t `t ωb
v̇nj = ic − jωb ω ? vnj , (24a)
where vt ∈ R2 denotes the terminal voltage and terminal clj j
current corresponds to stator current (i.e., is := it ). Finally, by ωb rlj ?
i̇lj = vn − ωb + jωb ω ilj , (24b)
combining (18)-(22) with the dynamics of frequency and voltage `lj j `lj
control loops, we obtain a 14th -order SG model described by the
state vector xg = xint
g , xfreq
g , xAVR
g , xPSS
g , it ∈ R14
. thus capturing the load and shunt phenomena at each node,
with rlj ∈ R>0 and `lj ∈ R>0 being the load’s resistance
and inductance, and cj ∈ R>0 reflecting the aggregate shunt
C. Network and System Modeling
capacitance. Finally, the line dynamics are represented using a
1) Transmission Network Dynamics: Modeling of the trans- conventional RL circuit formulation
mission network is described for a generic system depicted in
rjk
Fig. 7, composed of generators supplying local RL loads and the i̇jk = `ωjkb (vnj − vnk ) − `jk ωb + jωb ω ? ijk , ∀j ∈ N , k ∈ Kj ,
interconnecting transmission lines modeled as π-sections; long (25)
transmission lines with lengths above 250 km are represented with ijk ∈ R2 being the current and (rjk , `jk ) ∈ R2>0 the
by distributed line parameters. In order to establish a consistent respective parameters of a transmission line connecting nodes
mathematical formulation, all variables have to be defined within j ∈ N and k ∈ Kj , and Kj ⊂ N denoting the subset of
a single SRF, including the reference frame of the network. nodes adjacent to node j. Combining (23)-(25) with the algebraic
Neglecting grid dynamics has been a general assumption for expressions for current balance at each node j ∈ N in the system
SG-dominated power systems, based on the premise of grid and concludes the network model.
and generator’s armature dynamics being much faster than those
of the excitation and governor systems [59], [60]. Alternatively, 3 Note that the terminal currents correspond to stator currents i of SGs (see
s
studies often oversimplify the problem and assume that the grid’s Fig. 6) or to grid injection currents ig of VSCs (see Fig. 5).
0885-8950 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Universidad de chile. Downloaded on March 06,2021 at 21:50:42 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2021.3061434, IEEE
Transactions on Power Systems 9
0885-8950 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Universidad de chile. Downloaded on March 06,2021 at 21:50:42 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2021.3061434, IEEE
Transactions on Power Systems 10
current
VSCf PWM Harmonics DC SRF inner voltage
control PLL APC & RPC
< 1 ms 1 ms 10 ms 100 ms 1s 10 s T
Fig. 9. Characteristic timescales of different physical and control dynamics in a low-inertia system.
We also note that the impact of network line dynamics observe information through the network. Hence, larger time
becomes more profound in inertialess systems. Its effect on constants require a lower feedback gain, which implies that
frequency stability can be illustrated by analyzing a uniform reducing transmission line impedance ratio or increasing network
frequency control loop of an individual grid-forming inverter connectivity can make a low-inertia system unstable. Similar
connected to k ∈ Kj adjacent inverter units as follows: remarks have been pointed out for microgrids comprising solely
inverters based on droop [64] and dispatchable virtual oscillator
τz θ̈cj + 1 − ωb Rcp Bj0 θ̇cj + ωb Rcp Bj θcj + Cj = 0, (28) control [65]. While we only focus on frequency dynamics in this
with (ωc , θc ) denoting the converter frequency and phase angle, example, it should be noted that the voltage dynamics could also
Rcp being the active power droop, ωb representing the base be assessed using the proposed approach, as indicated in [64]–
frequency, Cj = ωb ωc?j + ωb Rcp p?cj , and [66].
X ω0 `jk 0
X 2rjk `2jk IV. S TABILITY P ROPERTIES OF A S MALL S YSTEM
Bj = 2 , Bj = 2 .
2
k∈Kj ωb rjk + ω02 `2jk k∈Kj 2
ωb rjk + ω02 `2jk A. Unit Interactions in a 2-bus Test System
For the first case study, we consider a simple 2-bus system
Here, ω0 is the nominal per-unit frequency and (rjk , `jk ) denote
with two generators connected over a transmission line and
the resistance and inductance of the transmission line between
an RL load supplied at one node. The goal is to incorporate
nodes j and k. The analytical derivation is omitted for brevity.
different units into the system and investigate their dynamic
We also note that the impact of network line dynamics
interactions and the respective stability margins. In order to
becomes more profound in inertialess systems. Its effect on
confine the observed phenomena solely to the generators under
frequency stability can be illustrated by analyzing a general
study, the transmission line dynamics are neglected at this point,
frequency control loop of an individual grid-forming inverter
i.e., line connections are represented only by algebraic equations.
j ∈ Ng connected to |Kj | VSC units k ∈ Kj adjacent to inverter
We investigate three different scenarios based on the generator
j, as follows:
type configuration: (i) a synchronous generator and a grid-
τz θ̈cj + 1 − ωb Rcp Bj0 θ̇cj + ωb Rcp Bj θcj + Cj = 0, (29) following VSC; (ii) a synchronous generator and a grid-forming
VSC; and (iii) a grid-forming and a grid-following VSC. Fur-
with Cj = ωb ωc?j + ωb Rcp p?cj and thermore, we introduce a penetration ratio η, which describes the
P P 2rjk `2jk
installed penetration level of inverter-based units. In the first two
ω0 `jk
Bj = k∈Kj ω (r 2 +ω 2 `2 )2 , Bj0 = k∈Kj ω (r 2 +ω 2 `2 )2 . cases this corresponds to η = pc /(pg + pc ), whereas in the last
b jk 0 jk b jk 0 jk
scenario this factor denotes the penetration of the grid-following
The derivation of underlying expressions is provided in Ap- generation, i.e., η = pcf /(pcF + pcf ), with subscripts F and
pendix B. f representing the grid-forming and grid-following converters
In order to preserve system synchronization, the natural nega- respectively. Note that all generators operate at 50 % of the
tive feedback terms for θcj and θ̇cj must be positive, indicating installed capacity, i.e., p? = 0.5 p.u.
an upper limit on the active power droop gain Rcp < (ωb Bj0 )−1 . The small-signal stability margins of different system config-
Such threshold is even more restrictive for distribution networks, urations are illustrated in Fig. 10, where the stability is assessed
due to shorter node distances and a lower `jk /rjk line impedance through real-part movement of the most critical eigenvalue λ̂.
ratio. Furthermore, the impact of the power network also pertains Understandably, the system comprising both synchronous gen-
to inverter synchronization through θcj term, since very high erators and grid-forming inverters can withstand higher levels
feedback control gains κj = ωb Rcp Bj might lead to inverter of PE-based devices (≈ 79%), as the voltage phasors at both
frequency oscillations exciting the oscillatory modes of the trans- nodes are fully established and controlled by the local generators.
mission lines. In other words, the inverters achieve synchroniza- Additionally, the synchronization and power sharing properties
tion by inferring information about the phase angle differences are inherently provided by both units. On the other hand, the
through local measurements of currents and voltages. Therefore, penetration of grid-following generation adversely affects the
the time constant of transmission lines can be interpreted as system balance, and significantly reduces the maximum admis-
a propagation delay of the information on the phase angles, sible ratio to ηmax ≈ 60 % and ηmax ≈ 59 % for Scenarios I and
and the controllers cannot act faster than the time needed to III, respectively. Scenario III also has a steeper progression of λ̂,
0885-8950 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Universidad de chile. Downloaded on March 06,2021 at 21:50:42 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2021.3061434, IEEE
Transactions on Power Systems 11
5
providing fast and accurate voltage and power reference tracking,
<(λ̂)
5
0 Scenario III
<(λ̂)
10 20 30 40 50 60 70 80 90
10 η [%]
20
Fig. 10. Impact of inverter penetration on system stability for different unit
30 40 50 60
Fig. 12. Stability maps in Ks −η and Dg −η planes indicating the effect of PSS
70
stabilization gain and SG damping on admissible penetration of grid-following
configuration. inverter units in Scenario I.
η [%]
0885-8950 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Universidad de chile. Downloaded on March 06,2021 at 21:50:42 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2021.3061434, IEEE
Transactions on Power Systems 12
factor η), with the results presented in Fig. 14. The main
distinction of this scenario is the elimination of voltage control
issues in the presence of SGs and inverters, as both VSCs
regulate voltage on the same timescale. In spite of improving the
voltage dynamics in the system, the synchronization problems
are aggravated due to an exclusion of a synchronous generator.
In other words, the dedicated “forming” capability of a grid-
forming converter is inferior to the one of a traditional generator.
As a result, for penetration levels above ≈ 59 % the PLL units
of grid-following inverters cannot accurately estimate the fre-
quency signal, leading to failure in the active power control and
preventing system-level synchronization. Similar properties are
also reflected when analyzing η as a function of the proportional
PLL gain, with a more responsive PLL potentially facilitating a
higher penetration factor (see Fig. 15). However, this approach
does not solve the fundamental problem at hand, and provides
only a marginal improvement of a few percent. It should be
noted that the integral gain of the respective PI controller does
not affect the system stability margin, indicating that the original
PLL time constant could be maintained in the process.
Fig. 13. Impact of different controllers on system stability under high grid-
forming inverter penetration in Scenario II.
B. Inclusion of Transmission Line Dynamics
We broaden the scope of our analysis by including the
transmission line dynamics. The same three scenarios are re-
evaluated and compared against the previous case study, with the
respective results illustrated in Fig. 16. A noticeable difference
in the stability margin of a 100 % inverter-based system can
be observed, where the inclusion of line dynamics significantly
increases the maximum penetration ratio η. This can be explained
by the inductive and capacitive components of the lines acting as
energy buffers and augmenting the synchronization between the
two units. More precisely, the frequency issues associated with a
large proportion of PLL-based generation are alleviated through
interactions with the LC segments of the transmission lines,
which slows down the frequency dynamics and enables the grid-
following VSCs to more accurately detect the weak frequency
signal. Similar conclusions have been drawn for autonomous
microgrids [67] and networks comprised of a specific class of
grid-forming inverters [65], as well as in [3] using a mechanical
analogue of swings in a multi-machine system.
On the other hand, the scenarios experiencing instability
related to voltage dynamics are for the most part unaffected by
Fig. 14. Impact of different controllers on system stability under high grid-
following inverter penetration in Scenario III.
the transmission line dynamics. The voltage control interaction
between the synchronous and PE-based generation is somewhat
mitigated, due to the time constants of the line dynamics and the
3) Scenario III: We tackle the 100 % PE-based scenario by SRF inner control loops being of the same order of magnitude.
increasing the share of grid-following units (i.e., by increasing
Fig. 15. Stability map in the Kppll − η plane indicating the effect of propor- Fig. 16. Impact of inverter penetration on system stability for different unit
tional PLL gain on admissible penetration of grid-following inverter units in configuration, with inclusion of transmission line dynamics. Transparent dashed
Scenario III. lines indicate results for scenarios without line dynamics from Fig. 10.
0885-8950 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Universidad de chile. Downloaded on March 06,2021 at 21:50:42 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2021.3061434, IEEE
Transactions on Power Systems 13
However, the line dynamics do not have any impact on the slower mode becoming unstable for increased installed VSC capac-
modes associated with the synchronous machines. Therefore, ity, previously pointed out in Section IV-A. However, when
the stability in Scenario I cannot be preserved for the grid- increasing the converter dispatch point p?c , the aforementioned
following penetration above 70 %, as it is associated solely with mode moves to the left-hand side (indicated by the blue arrow),
the AVR and PSS control design. The predominant impact of whereas another mode (denoted by red-edged diamonds) shifts
SGs on system stability is even higher in Scenario II, with grid- to the right-hand side (indicated by the red arrow) and eventually
forming inverters only marginally affecting the critical modes becomes unstable for p?c > 0.7 p.u. An interesting observation is
within a narrow range of η ∈ [78, 79] %. Hence, the maximum that the instability arises from synchronization issues, i.e., it is a
admissible VSC penetration after the inclusion of transmission consequence of adverse interactions between the two frequency
line dynamics remains the same in this case. controllers. Such finding confirms a very complex nature of
As a mean of model validation, we investigate the same 2- potentially unstable modes in a PE-dominated power system,
bus test case comprised only of synchronous generators or grid- and implies that a single metric of inverter penetration might
forming converters. Understandably, networks with such homo- not be sufficient to prescribe reliable stability margins. Another
geneous configurations of generators with standalone capabilities insightful remark can be made regarding the nature of the most
face no stability problems under any ratio of installed powers critical modes, as they all have zero imaginary part. This implies
between the two units. Therefore, these results are not included that the underlying instability is not oscillatory, and one should
in Fig. 16 for simplicity, nor will the respective scenarios be not be thinking of “fast” and “slow” second-order dynamics but
discussed in the remainder of the study. rather of just first-order dynamics when referring to these modes.
0 p?c = 0.5
p?c = 0.6
p?c = 0.7 3 6 7 8 2
−10 p?c = 0.8
0
voltage ctrl. λ (squares)
−1
−0.1 −0.08 −0.06 −0.04 −0.02 0 0.02 4
<(λ)
1
Fig. 17. Root loci spectrum of interest for different system operating points:
general mode movement (top) and the most critical modes (bottom). In the
bottom figure, the edge color of the mode corresponds to the color of the
respective arrow indicating the direction of the movement. The size of the symbol Fig. 18. Network diagram of the IEEE 9-bus system. The blue and red lines
scales down with the increase in converter power setpoint p?c . indicate the additionally incorporated transmission lines.
0885-8950 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Universidad de chile. Downloaded on March 06,2021 at 21:50:42 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2021.3061434, IEEE
Transactions on Power Systems 14
100
εg = 40 % 86 88 86 88
82
ηmax [%]
80 εg = 60 % 75
εg = 80 %
60 53 52
44
40
P0 Pf PF
Fig. 19. Stability mapping for the IEEE 9-bus test case under different levels of less accentuated voltage instability compared to the Pf sce-
network connectivity. Colored arrows indicate the appropriate reading direction nario. However, increasing network connectivity balances these
on the respective axes. penetration ratios out, as direct transmission line connections
resolve the timescale separation between the voltage controllers
of synchronous and converter-based generators (see Fig. 9). As
εg = 2Nb /(Nn2 − Nn ), from 40 % in the original model to 60 % a result, the system can facilitate up to ηmax = 88 % of PE-
and 80 % in the modified system. interfaced units; an increase of approximately 70 % compared to
Fig. 19 suggests that, for the generator configuration in this test the original portfolio P0 .
case, system stability cannot be maintained with less than 47 % Alternatively, a different configuration with a less heteroge-
synchronous generation. Reducing connectivity (in particular by neous portfolio comprised of two grid-forming and one grid-
removing network connections between generator buses) makes following inverter is investigated. For higher levels of network
the system even more reliant on synchronous generation. It connectivity the system faces no stability issues under any share
is clear that stability erodes at high VSC penetration levels of installed powers, whereas in case of εg = 40 % the maximum
independent of the grid-forming share, which is consistent with permissible penetration of grid-following generation is 93 %.
our previous findings in Section IV-A. Interestingly, the permis- This highlights the fact that the small-signal stability of low-
sible converter installation margin significantly reduces when inertia systems is drastically more vulnerable compared to the
the ηF /ηf ratio diverges from 1, as the maximum value of one of 100 % PE-based systems.
η = ηF + ηf drops from 44 % to 27 % in case of ηF ≈ 0 % or
ηf ≈ 0 %. This is due to different instabilities occurring between
various unit types, specifically voltage issues for a system com- B. Stability Characteristics of South-East Australian Network
prised of synchronous and inverter-based generators (Scenarios I Having gained fundamental understanding of dynamic inter-
and II) and synchronization obstacles related to a 100 % PE- actions between different types of generators in a simplistic test
based system (Scenario III), as described in Section IV-A. For a environment, we extend the analysis to a 14-generator, 59-bus
rather balanced portfolio, all of these problems are somewhat South-East Australian system [68], [69] shown in Fig. 21. This
confined within reasonable limits, while an imbalance in the network represents a long, linear system as opposed to the more
ηF /ηf ratio tends to emphasize the voltage dynamics issues and tightly meshed networks found in Europe and the United States.
endanger the whole network. Another valid point can be made For convenience, it has been divided into 5 areas, with areas 1
regarding the beneficial impact of transmission line dynamics. and 2 being closely electrically coupled. Therefore, there are
As previously indicated in Section IV-B, a direct connection in essence 4 main regions, namely South Australia (area 5),
between units experiencing frequency instability mitigates the Queensland (area 4), Victoria (area 3) and New South Wales
synchronization issues, thus facilitating a higher share of PE- (subsuming areas 1 and 2), and hence 3 inter-area modes are
based devices. Nonetheless, this is not the case for transmission present. Beside its string topology, the system is characterized
lines between the load nodes, as increasing connectivity from by the weak coupling between South Australia and the rest of
60 % to 80 % has a negligible impact on the stability margin. the system. The model employed in this work considers the light
We extend this analysis by differentiating between three loading scenario provided in [69], [70].
different generation portfolios: (i) P0 - a mix of all three unit Moreover, for the purpose of this work, the model presented in
types, as previously discussed; (ii) Pf - a system comprised [70] was modified to obtain a low-inertia case study by replacing
only of synchronous generators and grid-following VSCs; and synchronous generators located at buses 101, 202, 301, 302,
(iii) PF - a system comprised only of synchronous generators 501, 502 and 503 by grid-following VSCs of identical power
and grid-forming VSCs; in the latter two cases the portfolio rating. In addition, we install 4 more grid-following units, two
consists of two synchronous and one inverter-based generator, in each of the area 2 and 3, at nodes 212 and 214, i.e., 308 and
i.e., one of the VSCs from the original portfolio P0 is replaced 314 respectively. This yields a total of 11 converter-interfaced
by SG, whereas the total inverter penetration ratio is equal to generators operating in grid-following mode and 7 conventional
either ηf or ηF . The results for the IEEE 9-bus system presented SGs, representing the default test case for our analysis. Such
in Fig. 20 suggest that more homogeneous portfolios, such as modeling choice is based on the high penetration of renewable
Pf and PF , can withstand drastically higher penetrations of generation in the real-world system, particularly in area 5, that
renewables, with ηmax reaching up to 75 % and 82 % respectively. does not provide standalone frequency support [71], [72]. Note
Understandably, portfolio PF has a higher η margin due to that the default test case comprises all-inverter-based areas 5,
0885-8950 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Universidad de chile. Downloaded on March 06,2021 at 21:50:42 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2021.3061434, IEEE
Transactions on Power Systems 15
315 309
101 wide areas affected by their “forming” property and facilitating
311 310
308 307 305 a high grid-following inverter penetration. By replacing the
grid-forming unit at node 404 with a grid-following one, the
VSC
VSC
304 303 301 electrical distance between this converter and the grid-forming
306
VSC in South Australia becomes too large and the system cannot
preserve small-signal stability. We can therefore conclude that
VSC
VSC
0885-8950 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Universidad de chile. Downloaded on March 06,2021 at 21:50:42 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2021.3061434, IEEE
Transactions on Power Systems 16
Fig. 22. Scenario configuration and stability analysis of South-East Australian grid based on the generation portfolio in the system.
depending on the generation portfolio; (iii) Contrary to popular [4] D. Mondal, A. Chakrabarti, and A. Sengupta, Power System Small Signal
belief, low inertia on its own does not have a major impact Stability Analysis and Control. Elsevier - Academic Press, 2014.
[5] S. D’Arco, J. A. Suul, and O. B. Fosso, “Small-signal modelling and
on the small-signal stability of power systems with high shares parametric sensitivity of a virtual synchronous machine,” in Power Systems
of PE-interfaced generation. It does however affect frequency Computation Conference, Aug 2014.
dynamics and associated fast transients, which in turn can [6] O. Mo, S. D’Arco, and J. A. Suul, “Evaluation of virtual synchronous
machines with dynamic or quasi-stationary machine models,” IEEE Trans.
adversely trigger numerous protection schemes based on Rate-of- Ind. Electron., vol. 64, no. 7, pp. 5952–5962, July 2017.
Change-of-Frequency (RoCoF) measurements; (iv) Controllers [7] G. S. Misyris, J. A. Mermet-Guyennet, S. Chatzivasileiadis, and
of synchronous and inverter-based generators can interact in a T. Weckesser, “Grid supporting vscs in power systems with varying inertia
and short-circuit capacity,” in 2019 IEEE Milan PowerTech, June 2019.
way that leads to frequency and voltage instabilities under high [8] R. Ofir, U. Markovic, P. Aristidou, and G.Hug, “Droop vs. virtual inertia:
penetration of renewables. This can only be observed under Comparison from the perspective of converter operation mode,” in IEEE
sufficiently detailed modeling of underlying control schemes; International Energy Conference (ENERGYCON), June 2018.
(v) In addition to installed inverter capacity, the operating points [9] U. Markovic, J. Vorwerk, P. Aristidou, and G. Hug, “Stability analysis of
converter control modes in low-inertia power systems,” in IEEE Innovative
have a crucial impact on overall stability and can drastically Smart Grid Technologies Conference Europe, Oct 2018.
change the nature of unstable modes and underlying dynamics, [10] U. Markovic, O. Stanojev, P. Aristidou, and G. Hug, “Partial grid forming
which in turn could affect the optimal power flow dispatch. concept for 100% inverter-based transmission systems,” in IEEE PES
General Meeting, Aug 2018.
Future research could include, among other things, a compre- [11] E. A. A. Coelho, P. C. Cortizo, and P. F. D. Garcia, “Small-signal stability
hensive analysis of potentially adverse effects of incompatible for parallel-connected inverters in stand-alone ac supply systems,” IEEE
converter control strategies, impact of unit placement on transient Trans. Ind. Appl., vol. 38, no. 2, pp. 533–542, March 2002.
[12] S. V. Iyer, M. N. Belur, and M. C. Chandorkar, “A generalized computa-
and small-signal stability, as well as the overall system capability tional method to determine stability of a multi-inverter microgrid,” IEEE
for frequency regulation (e.g., limiting nadir and RoCoF) under Trans. Power Electron., vol. 25, no. 9, pp. 2420–2432, Sep. 2010.
high inverter penetration. Furthermore, the aspects of large-signal [13] X. Guo, Z. Lu, B. Wang, X. Sun, L. Wang, and J. M. Guerrero, “Dynamic
phasors-based modeling and stability analysis of droop-controlled inverters
stability and the impact of HVDC and MTDC grids should be for microgrid applications,” IEEE Trans. Smart Grid, vol. 5, no. 6, pp.
thoroughly investigated. 2980–2987, Nov 2014.
[14] S. D’Arco and J. A. Suul, “Small-signal analysis of an isolated power
R EFERENCES system controlled by a virtual synchronous machine,” in IEEE International
Power Electronics and Motion Control Conference, Sep. 2016.
[1] F. Milano, F. Dörfler, G. Hug, D. J. Hill, and G. Verbič, “Foundations [15] J. W. Simpson-Porco, F. Drfler, and F. Bullo, “Synchronization and power
and challenges of low-inertia systems,” in Power Systems Computation sharing for droop-controlled inverters in islanded microgrids,” Automatica,
Conference (PSCC), Jun 2018. vol. 49, no. 9, pp. 2603 – 2611, 2013.
[2] P. Kundur, Power System Stability and Control. McGraw-Hill, 1994. [16] J. W. Simpson-Porco, F. Dörfler, and F. Bullo, “Voltage stabilization
[3] J. Machowski, J. W. Bialek, and J. R. Bumby, Power System Dynamics: in microgrids via quadratic droop control,” 52nd IEEE Conference on
Stability and Control. Wiley, 2008. Decision and Control, 2013.
0885-8950 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Universidad de chile. Downloaded on March 06,2021 at 21:50:42 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2021.3061434, IEEE
Transactions on Power Systems 17
[17] J. Schiffer, R. Ortega, A. Astolfi, J. Raisch, and T. Sezi, “Conditions [44] J. W. Simpson-Porco, F. Dörfler, and F. Bullo, “Synchronization and power
for stability of droop-controlled inverter-based microgrids,” Automatica, sharing for droop-controlled inverters in islanded microgrids,” Automatica,
vol. 50, no. 10, pp. 2457 – 2469, 2014. vol. 49, no. 9, pp. 2603–2611, 2013.
[18] N. Pogaku, M. Prodanovic, and T. C. Green, “Modeling, analysis and [45] H. P. Beck and R. Hesse, “Virtual synchronous machine,” in 2007 9th
testing of autonomous operation of an inverter-based microgrid,” IEEE International Conference on Electrical Power Quality and Utilisation, Oct
Trans. Power Electron., vol. 22, no. 2, pp. 613–625, 2007. 2007.
[19] G. Diaz, C. Gonzalez-Moran, J. Gomez-Aleixandre, and A. Diez, [46] S. D’Arco, J. A. Suul, and O. B. Fosso, “Virtual synchronous machines
“Complex-valued state matrices for simple representation of large au- - classification of implementations and analysis of equivalence to droop
tonomous microgrids supplied by pq and vf generation,” IEEE Trans. controllers for microgrids,” in 2013 IEEE Grenoble Conference, June 2013.
Power Syst., vol. 24, no. 4, pp. 1720–1730, Nov 2009. [47] M. Colombino, D. Groß, J.-S. Brouillon, and F. Dörfler, “Global phase and
[20] S. Leitner, M. Yazdanian, A. Mehrizi-Sani, and A. Muetze, “Small-signal magnitude synchronization of coupled oscillators with application to the
stability analysis of an inverter-based microgrid with internal model-based control of grid-forming power inverters,” 2019.
controllers,” IEEE Trans. Smart Grid, vol. 9, no. 5, pp. 5393–5402, Sep. [48] D. Groß, M. Colombino, J.-S. Brouillon, and F. Dörfler, “The effect of
2018. transmission-line dynamics on grid-forming dispatchable virtual oscillator
[21] I. P. Nikolakakos, H. H. Zeineldin, M. S. El-Moursi, and N. D. Hatziar- control,” 2019.
gyriou, “Stability evaluation of interconnected multi-inverter microgrids [49] T. Jouini, C. Arghir, and F. Dörfler, “Grid-friendly matching of synchronous
through critical clusters,” IEEE Trans. Power Syst., vol. 31, no. 4, pp. machines by tapping into the DC storage,” in IFAC Workshop on Distributed
3060–3072, July 2016. Estimation and Control in Networked Systems (NecSys, 2016, pp. 192–197.
[22] N. Pogaku, M. Prodanovic, and T. C. Green, “Modeling, analysis and
[50] C. Arghir, T. Jouini, and F. Dörfler, “Grid-forming control for power
testing of autonomous operation of an inverter-based microgrid,” IEEE
converters based on matching of synchronous machines,” Automatica,
Trans. Power Electron., vol. 22, no. 2, pp. 613–625, March 2007.
vol. 95, pp. 273 – 282, 2018.
[23] Q. Peng, Q. Jiang, Y. Yang, T. Liu, H. Wang, and F. Blaabjerg, “On the
stability of power electronics-dominated systems: Challenges and potential [51] S.-K. Chung, “A phase tracking system for three phase utility interface
solutions,” IEEE Trans. Ind. Appl., pp. 1–1, 2019. inverters,” IEEE Trans. Power Electron., vol. 15, no. 3, pp. 431–438, May
[24] M. Zhao, X. Yuan, J. Hu, and Y. Yan, “Voltage dynamics of current control 2000.
time-scale in a vsc-connected weak grid,” IEEE Trans. Power Syst., vol. 31, [52] S. F. Zarei, H. Mokhtari, M. A. Ghasemi, S. Peyghami, P. Davari, and
no. 4, pp. 2925–2937, July 2016. F. Blaabjerg, “Control of grid-following inverters under unbalanced grid
[25] H. Yuan, X. Yuan, and J. Hu, “Modeling of grid-connected vscs for power conditions,” IEEE Trans. Energy Convers., pp. 1–1, 2019.
system small-signal stability analysis in dc-link voltage control timescale,” [53] M. C. Chandorkar, D. M. Divan, and R. Adapa, “Control of parallel
IEEE Trans. Power Syst., vol. 32, no. 5, pp. 3981–3991, Sep. 2017. connected inverters in standalone ac supply systems,” IEEE Trans. Ind.
[26] EirGrid and SONI, “DS3: System services review TSO recommendations,” Appl., vol. 29, no. 1, pp. 136–143, Jan. 1993.
EirGrid, Tech. Rep., May 2013. [54] V. Mariani, F. Vasca, J. C. Vsquez, and J. M. Guerrero, “Model order
[27] J. Matevosyan and P. Du, “Wind integration in ERCOT,” in Integration of reductions for stability analysis of islanded microgrids with droop control,”
Large-Scale Renewable Energy into Bulk Power Systems. Springer, 2017. IEEE Trans. Ind. Electron., vol. 62, no. 7, pp. 4344–4354, July 2015.
[28] Australian Energy Market Operator, “Black System South Australia 28 [55] J. W. Simpson-Porco, F. Drfler, and F. Bullo, “Voltage stabilization in
September 2016 - Final Report,” Tech. Rep., March 2017. microgrids via quadratic droop control,” IEEE Trans. Autom. Control,
[29] “PSLF”, GE Energy Consulting. [Online]. Available: vol. 62, no. 3, pp. 1239–1253, March 2017.
http://www.geenergyconsulting.com/practice-area/software-products/pslf [56] T. Qoria, F. Gruson, F. Colas, X. Guillaud, M. Debry, and T. Prevost,
[30] “TSAT”, Powertech Labs Inc. [Online]. Available: “Tuning of cascaded controllers for robust grid-forming voltage source
https://www.dsatools.com/tsat/ converter,” in Power Systems Computation Conference, 2018.
R
[31] “PSS E”, Siemens PTI. [Online]. Available: [57] T. Qoria, U. Markovic, T. Jouini, D. Groß, G. Denis, and T. Prevost, “Data
https://new.siemens.com/global/en/products/energy/services/transmission- underlying the research of a 3 bus model for full inverter system - Migrate
distribution-smart-grid/consulting-and-planning/pss-software/pss-e.html WP3,” 2018. [Online]. Available: https://doi.org/10.4121/uuid:e5497fd2-
[32] P. Pourbeik, J. J. Sanchez-Gasca, J. Senthil, J. D. Weber, P. S. Zadehkhost, f617-4573-b6d5-1202ebae411d
Y. Kazachkov, S. Tacke, J. Wen, and A. Ellis, “Generic dynamic models [58] ENTSO-E, “Documentation on controller tests in test grid configurations,”
for modeling wind power plants and other renewable technologies in large- Tech. Rep., November 2013.
scale power system studies,” IEEE Trans. Energy Convers., vol. 32, no. 3, [59] J. M. Uudrill, “Dynamic stability calculations for an arbitrary number of
pp. 1108–1116, Sep. 2017. interconnected synchronous machines,” IEEE Trans. Power Apparatus and
[33] J. Slootweg and W. Kling, “The impact of large scale wind power Systems, vol. PAS-87, no. 3, pp. 835–844, March 1968.
generation on power system oscillations,” Electric Power Systems Research, [60] C. Spanias and I. Lestas, “A system reference frame approach for stability
vol. 67, no. 1, pp. 9 – 20, 2003. analysis and control of power grids,” ArXiv e-prints, Sep. 2018.
[34] A. Mendonca and J. A. P. Lopes, “Impact of large scale wind power [61] P. M. Anderson and A. A. Fouad, Power system control and stability. John
integration on small signal stability,” in 2005 International Conference on Wiley & Sons, 2008.
Future Power Systems, Nov 2005. [62] E. Ekomwenrenren, H. Alharbi, T. Elgorashi, J. Elmirghani, and P. Aristi-
[35] D. Gautam, V. Vittal, and T. Harbour, “Impact of increased penetration of dou, “Stabilising control strategy for cyber-physical power systems,” IET
dfig-based wind turbine generators on transient and small signal stability of Cyber-Physical Systems: Theory Applications, vol. 4, no. 3, pp. 265–275,
power systems,” IEEE Trans. Power Syst., vol. 24, no. 3, pp. 1426–1434, 2019.
Aug 2009.
[63] P. Kundur, J. Paserba, V. Ajjarapu, G. Andersson, A. Bose, C. Canizares,
[36] P. N. Papadopoulos and J. V. Milanovi, “Probabilistic framework for N. Hatziargyriou, D. Hill, A. Stankovic, C. Taylor, T. Van Cutsem,
transient stability assessment of power systems with high penetration of and V. Vittal, “Definition and classification of power system stability
renewable generation,” IEEE Trans. Power Syst., vol. 32, no. 4, pp. 3078– IEEE/CIGRE joint task force on stability terms and definitions,” IEEE
3088, July 2017. Trans. Power Syst., vol. 19, no. 3, pp. 1387–1401, Aug 2004.
[37] X. Xi, H. Geng, and G. Yang, “Small signal stability of weak power
system integrated with inertia tuned large scale wind farm,” in 2014 IEEE [64] P. Vorobev, P. Huang, M. A. Hosani, J. L. Kirtley, and K. Turitsyn, “A
Innovative Smart Grid Technologies - Asia (ISGT ASIA), May 2014. framework for development of universal rules for microgrids stability and
control,” in IEEE 56th Conference on Decision and Control, Dec 2017.
[38] R. Elliott, R. Byrne, A. Ellis, and L. Grant, “Impact of increased photo-
voltaic generation on inter-area oscillations in the western north american [65] D. Groß, M. Colombino, J.-S. Brouillon, and F. Dörfler, “The effect of
power system,” in 2014 IEEE PES General Meeting, July 2014. transmission-line dynamics on grid-forming dispatchable virtual oscillator
[39] F. Katiraei, M. R. Iravani, and P. W. Lehn, “Small-signal dynamic model of control,” ArXiv e-prints, Feb. 2018.
a micro-grid including conventional and electronically interfaced distributed [66] P. Vorobev, P. Huang, M. A. Hosani, J. L. Kirtley, and K. Turitsyn, “High-
resources,” IET Generation, Transmission Distribution, vol. 1, no. 3, pp. fidelity model order reduction for microgrids stability assessment,” IEEE
369–378, May 2007. Trans. Power Syst., vol. 33, no. 1, pp. 874–887, Jan 2018.
[40] Y. Lin, B. Johnson, V. Gevorgian, V. Purba, and S. Dhople, “Stability [67] W. Du, R. H. Lasseter, and A. S. Khalsa, “Survivability of autonomous
assessment of a system comprising a single machine and inverter with microgrid during overload events,” IEEE Trans. Smart Grid, Apr 2018.
scalable ratings,” in North American Power Symposium, Sep. 2017. [68] A. S. Ahmadyar, S. Riaz, G. Verbi, A. Chapman, and D. J. Hill, “A
[41] P. W. Sauer and M. A. Pai, Power system dynamics and stability. Prentice framework for assessing renewable integration limits with respect to
Hall, 1997. frequency performance,” IEEE Trans. Power Syst., vol. 33, no. 4, 2018.
[42] G. Pinares, “Analysis of the dc dynamics of vsc-hvdc systems connected to [69] M. J. Gibbard and D. J. Vowles, “Simplified 14-generator model of the se
weak ac grids using a frequency domain approach,” in 2014 Power Systems australian power system,” 2010.
Computation Conference, Aug 2014. [70] A. Moeini, I. Kamwa, P. Brunelle, and G. Sybille, “Open data ieee test
[43] M. C. Chandorkar, D. M. Divan, and R. Adapa, “Control of parallel systems implemented in simpowersystems for education and research in
connected inverters in standalone AC supply systems,” vol. 29, no. 1, pp. power grid dynamics and control,” in 2015 50th International Universities
136–143, 1993. Power Engineering Conference (UPEC), Sep. 2015.
0885-8950 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Universidad de chile. Downloaded on March 06,2021 at 21:50:42 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2021.3061434, IEEE
Transactions on Power Systems 18
[71] S. Püschel-Løvengreen and P. Mancarella, “Frequency response constrained current flowing through the line between converters j and k,
economic dispatch with consideration of generation contingency size,” in and θjk := θcj − θck Furthermore, considering line parameters
2018 Power Systems Computation Conference (PSCC), June 2018.
[72] B. Kameshwar Poolla, D. Groß, and F. Dörfler, “Placement and imple- of the form (rjk , `jk ) ∈ R>0 , we express the electromagnetic
mentation of grid-forming and grid-following virtual inertia,” IEEE Trans. dynamics of the line current in a dq-frame by (see Appendix A)
Power Syst., vol. 34, no. 4, pp. 3035–3046, 2019.
[73] D. Groß, S. Bolognani, B. Poolla, and F. Dörfler, “Increasing the resilience ωb rjk
of low-inertia power systems by virtual inertia and damping,” in IREP Bulk i̇jk = (vc − vck ) − ωb + jωb ω0 ijk , (37)
Power System Dynamics & Control Symposium, Aug 2017. `jk j `jk
[74] A. Venkatraman, U. Markovic, D. Shchetinin, E. Vrettos, P. Aristidou, and which is subsequently transformed into frequency (Laplace)
G. Hug, “Improving Dynamic Properties of Low-Inertia Systems through
Eigensensitivity Optimization,” IEEE Trans. Power Syst., vol. 36, no. 3, domain as
pp. 1–14, 2021.
vcj − vck
ijk = . (38)
rjk + jω0 `jk + s`jk /ωb
A PPENDIX Let us define i0jk ∈ R2 as the nominal current flowing through
A. Vector Formulation of Circuit Dynamics the line (rjk , `jk ) with the end voltages vcj ∈ R2 and vck ∈ R2 ,
We derive the dq-vector formulation for a general RL circuit i.e.,
vcj − vck
described by the per-unit series resistance r ∈ R>0 and induc- i0jk = . (39)
rjk + jω0 `jk
tance ` ∈ R>0 . Let us consider such series impedance, with
three-phase voltages v1abc ∈ R3 and v2abc ∈ R3 at the respective Substituting (39) into (38) yields
ends and the three-phase current iabc ∈ R3 flowing through
i0jk
it. Assuming a base angular velocity ωb ∈ R>0 , the current ijk = . (40)
dynamics are described in per-unit by 1 + s`jk / (rjk + jω0 `jk ) ωb
| {z }
d abc ωb abc r σl
dt i =− v1 − v2abc − ωb iabc , (30)
` ` Note that σl can be expressed using SI terms as
Moreover, let us denote by X(θr ) = T (θr )−1 the inverse of the s`jk sLjk sTjk
power-variant dq-transform in (3). Assuming a balanced three- σl = = = ,
(rjk + jω0 `jk ) ωb Rjk + jω0 Ljk 1 + jω0 Tjk
phase system and, given a reference angle θr ∈ [−π, π) of the (41)
dq-frame, expression (30) can be rewritten as with Tjk = Rjk
L
being the transmission line time constant.
ωb dq r jk
d
Xi dq
= − X v − v dq
− ωb Xidq . (31) Considering that RXjkl ≈ 10, we can assume Tjk ≈ 0.03 s.
dt 1 2
` ` Therefore, it is reasonable to assume that σl 1 holds for modes
d
Considering that dt θr = ωb ωr and that j := R(π/2) can √ be
evolving on the timescales shorter than the line time constant
interpreted as an embedding of the complex imaginary unit −1 Tjk [66]. By performing a first-order Taylor series expansion
into R2 , the term on the left-hand side of (31) can be further (1 + σl )−1 ≈ 1 − σl , we can rewrite (40) as
expressed as s`jk
ijk ≈ i0jk − i0 , (42)
d
dt Xi
dq d
= dt (X) idq + X dtd dq
i = jωb ωr idq + X dt d
idq . ωb (rjk + jω0 `jk ) jk
(32) and transform it back into the time-domain form
Substituting (32) into (31) and conducting a set of trivial math-
`jk
ematical operations yields ijk ≈ i0jk − 2 v̇cj − v̇ck . (43)
d dq ωb dq dq
r ωb (rjk + jω0 `jk )
dt i = v1 − v2 − ωb + jω b ω r idq . (33)
` ` Assuming nominal voltage magnitudes and small angle devia-
tions between the nodes, i.e., kvcj k ≈ 1 p.u. and θjk ≈ 0, ∀j ∈
B. Frequency Control Loop of a Grid-Forming Converter in a Ng , ∀k ∈ Kj , we can compute the time derivatives of voltage
Multi-Machine System vectors and subsequently the total active power injection as
Let us consider an index set Ng representing all interconnected
grid-forming converters with the droop-based active power con- X ω0 `jk 2
2rjk `jk
pcj = 2 θcj + 2 θ̇cj
trol (10) described by 2 2 2 2 2 2
k∈Kj ωb rjk + ω0 `jk ωb rjk + ω0 `jk
τz ω̇cj = ωc?j − ωcj + Rcp p?cj − pcj , ∀j ∈ Ng , (34)
= Bj θcj + Bj0 θ̇cj .
where τz = ωz−1 is the time constant of the low-pass filter. (44)
Having in mind that θ̇cj = ωb ωcj , one can transform (34) into Substituting (44) into (34) yields the frequency dynamics of an
individual inverter of the form
τz θ̈cj = −θ̇cj + ωb ωc?j + ωb Rcp p?ck − pck . (35)
τz θ̈cj + 1 − ωb Rcp Bj0 θ̇cj + ωb Rcp Bj θcj + Cj = 0, (45)
The converter’s output power pcj can be described as the sum
of all powers flowing across the transmission lines connecting with Cj = ωb ωc?j + ωb Rcp p?cj .
VSC j to the adjacent converter units k ∈ Kj :
X X
pcj = pjk = vcTj ijk , (36)
k∈Kj k∈Kj
0885-8950 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Universidad de chile. Downloaded on March 06,2021 at 21:50:42 UTC from IEEE Xplore. Restrictions apply.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2021.3061434, IEEE
Transactions on Power Systems 19
Uros Markovic (S’16-M’20) was born in Belgrade, Gabriela Hug (S’05-M’08-SM’14) was born in Baden,
Serbia. He received the Dipl.-Eng. degree in Electrical Switzerland. She received the M.Sc. degree in electrical
Engineering from the University of Belgrade, Serbia, engineering in 2004 and the Ph.D. degree in 2008,
in 2013, with a major in power systems. He obtained both from the Swiss Federal Institute of Technology
the M.Sc. and Ph.D. degrees in Electrical Engineer- (ETH), Zurich, Switzerland. After the Ph.D. degree,
ing and Information Technology in 2016 and 2020, she worked in the Special Studies Group of Hydro
respectively, both from the Swiss Federal Institute of One, Toronto, ON, Canada, and from 2009 to 2015,
Technology (ETH), Zurich, Switzerland. He is currently she was an Assistant Professor in Carnegie Mellon
a joint Postdoctoral researcher with the Power Systems University, Pittsburgh, PA, USA. She is currently an
Laboratory and the Automatic Control Laboratory of Associate Professor in the Power Systems Laboratory,
ETH Zurich, Switzerland, and an affiliated researcher ETH Zurich. Her research is dedicated to control and
at the Grid Integration Group (GIG) of Lawrence Berkeley National Laboratory optimization of electric power systems.
(LBNL), California, USA.
His research interests include power system dynamics, control and optimiza-
tion, with a focus on stability and operation of inverter-dominated power systems
with low rotational inertia.
0885-8950 (c) 2021 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Authorized licensed use limited to: Universidad de chile. Downloaded on March 06,2021 at 21:50:42 UTC from IEEE Xplore. Restrictions apply.