RESIDENTIAL LOADS : Form 2

Transformer No. 01

No. & Type of Maximum


Pole Number Number of SPAN kVA SPAN
Customers Demand
P-1 A+C+3F+SL 17.246 2 34.492
P-2 A+D+3E+SL 18.208 1 18.208
P-3 3B+E+F+SL 19.825 1 19.825
P-4 C+3D+F+SL 15.524 1 15.524
P-5 A+2C+2D+SL 20.644 2 41.288

Total Maximum Demand of Transformer : 91.447 KW


USE: 167 KVA

Selection of Transformer Location

P-1 P-2 P-3 P-4 P-5

T-01

Transformer No. 01 Is installed at Pole No. 3

Left Side
Pole Number kVA/Pole No. of SPAN kVA SPAN
P-1 17.246 2 34.492
P-2 18.208 1 18.208
P-3 19.825 1 19.825

Total 35.454 52.7

Right Side
Pole Number kVA/Pole No. of SPAN kVA SPAN
P-4 15.524 1 15.524
P-5 20.644 2 41.288

Total 36.168 56.812

RESIDENTIAL LOADS : Form 2

Transformer No. 02
No. & Type of Maximum
Pole Number Number of SPAN kVA SPAN
Customers Demand
P-6 3B+2F+SL 19.292 2 38.584
P-7 B+C+2F+SL 13.269 1 13.269
P-8 3B+C+F+SL 20.85 1 20.85
P-9 A+C+3F+SL 17.246 1 17.246
P-10 C+D+3E+SL 15.286 2 30.572

Total Maximum Demand of Transformer : 85.943 KW


USE: 167 KVA

Selection of Transformer Location

P-6 P-7 P-8 P-9 P-10

T-02

Transformer No. 02 Is installed at Pole No. 8

Left Side
Pole Number kVA/Pole No. of SPAN kVA SPAN
P-6 19.292 2 38.584
P-7 13.269 1 13.269
P-8 20.85 1 20.85

Total 32.561 51.853

Right Side
Pole Number kVA/Pole No. of SPAN kVA SPAN
P-9 17.246 1 17.246
P-10 15.286 2 30.572

Total 32.532 47.818


RESIDENTIAL LOADS: Form 3

For T - 01

Use 167 KVA, 34.5kV, 230V, 115V, grounded, 60 Hz distribution transformer with 5% impedance.

% Loading = Total Maximum Demand of Transformer


x 100%
KVA Rating of Transformer

= 91.447 x 100%
167
= 54.76 %

1) I (Full Load) = KVA rating of transformer / (34.5 kV)


= 167 /34.5
= 4.841 Amps

2) The maximum setting of the over-current protection device in the primary.


Im = 3 x IFL = 3 x 4.841
Im = 14.522 Amps

3) The KVA short circuit in the primary.


= KVA of the transformer / ( % impedance)
= 167 / 0.05
= 3340 KVA

4) The symmetrical short circuit in the primary.


I (s.c. sym = KVA of Transformer
(% impedance x kV)
= 167 /(34.5 x 0.05)
= 96.812 amps

5) The asymmetrical short circuit in the primary is:


I (s.c. as = 1.6 x Isym = 154.899 Amps

The rating of the transformer shall be 167 KVA, 34.5kV, 230V, 115V, 60 Hz, single
phase distribution transformer with 5% impedance,the total expected load is
54.76 %, the
the rating of the fus 20 ampere fuse link. The maximum setting is
14.522 amps;
the L.A. shall be line type rated 27 kV.

RESIDENTIAL LOADS: Form 3

For T - 01
Use 167 KVA, 34.5kV, 230V, 115V, grounded, 60 Hz distribution transformer with 5% impedanc
kVA SPAN

38.584
13.269 % Loading = Total Maximum Demand of Transformer
x 100%
20.85 KVA Rating of Transformer
17.246
30.572 = 85.943 x 100%
167
= 51.46 %

1) I (Full Load) = KVA rating of transformer / (34.5 kV)


= 167 /34.5
= 4.841 Amps

2) The maximum setting of the over-current protection device in the primary.


Im = 3 x IFL = 3 x 4.841
Im = 14.522 Amps

3) The KVA short circuit in the primary.


= KVA of the transformer / ( % impedance)
= 167 / 0.05
= 3340 KVA

4) The symmetrical short circuit in the primary.


I (s.c. sym = KVA of Transformer
(% impedance x kV)
= 167 /(34.5 x 0.05)
= 96.812 amps

5) The asymmetrical short circuit in the primary is:


I (s.c. as = 1.6 x Isym = 154.899 Amps

The rating of the transformer shall be 167 KVA, 34.5kV, 230V, 115V, 60 Hz, single
phase distribution transformer with 5% impedance,the total expected load is
51.46
the rating of the fus 20 ampere fuse link. The maximum setting is
14.522
the L.A. shall be line type rated 27 kV.
with 5% impedance.

0 Hz, single
nsformer with 5% impedance.

x 100%

in the primary.

impedance)

V, 115V, 60 Hz, single


%, the
amps;