You are on page 1of 13

Engineering Structures 36 (2012) 14–26

Contents lists available at SciVerse ScienceDirect

Engineering Structures
journal homepage: www.elsevier.com/locate/engstruct

Modal identification of Shanghai World Financial Center both from free


and ambient vibration response
Weixing Shi ⇑, Jiazeng Shan, Xilin Lu
Research Institute of Structural Engineering and Disaster Reduction, Tongji University, No. 1239 Siping Road, Shanghai 200092, China

a r t i c l e i n f o a b s t r a c t

Article history: The Shanghai World Financial Center (SWFC), a currently built super high-rise building, is located in
Received 22 July 2010 Lujiazui area. The height of this 101-storey building is 492 m above ground. A set of dynamic field tests
Revised 17 November 2011 were conducted on the building from April to May 2008. To identify the dynamic properties of the build-
Accepted 18 November 2011
ing, three output-only modal identification techniques are applied to the ambient and forced vibration
Available online 26 December 2011
measurements. These methods consist of: the Peak-Picking method (PP) combined with the half-power
bandwidth method, the Random Decrement based method (RDT) combined with curve-fitting method,
Keywords:
and the Hilbert–Huang transform method (HHT). The fundamental frequencies and damping ratios in
Field tests
Modal identification
two translational directions are identified from the free decays of forced vibration tests. The estimated
High-rise building eleven modal frequencies and damping ratios under microtremors from the Peaking-Picking method
Random decrement and the Hilbert–Huang transform method are compared to each other with favorable correlation. The
Hilbert–Huang transform modal frequencies from the finite element analysis and the shaking table test are further studied with
the results of field test. The effect of the installed Active Tuned Mass Damper (ATMD) on the damping
characteristics of the building is presented. Based on the identified results, accuracy and efficiency of
these methods are investigated with the length of Fast-Fourier Transform and the effect of RDT. The
modal properties of the SWFC presented in this paper can be used as baseline in future health monitoring.
Ó 2011 Elsevier Ltd. All rights reserved.

1. Introduction Recently there are many operational modal identification meth-


ods for the measured data analysis including frequency domain,
Performance of a super high-rise building subjected to seismic, time domain and time-frequency domain approaches. Traditional
wind and other dynamic loads depends upon its structural proper- modal identification methods are developed in frequency domain,
ties such as mass, stiffness, damping and their distribution. Besides such as Peak-Picking (PP) [2], Frequency Domain Decomposition
the safety during the disasters, the structures should be engineered (FDD) [3,4], and Enhanced Frequency Domain Decomposition
with sufficient damping to withstand the demand of habitability. (EFDD) [5]. The time domain parametric approaches can be divided
Though these structural properties can be determined through into Random Decrement based methods (RDT) [6], Natural Excita-
the analytical finite element models, the real behaviors of the tion Technique (NExT) [7,8], Eigensystem Realization Algorithm
high-rise building remain to be studied from the full-scale dynamic (ERA) [8], Autoregressive Moving Average model (ARMA) [9],
field test. The modal parameter set can be identified through the Bayesian statistical approach [10] and so on. The time-frequency
dynamic field test, and this valuable information is not just for domain approaches are mainly wavelet-type method [11,12] and
the analytical model but also for other applications, such as the Hilbert–Huang transform (HHT) method [13,14]. The evaluation
evaluation of prototypes, model updating, structural health moni- of damping has become more important these years due to the
toring, and structural control. Various vibration testing techniques higher demand on the precise prediction of the response of
are utilized to measure the dynamic properties of the existing high-rise buildings. Traditional damping evaluation methods are
structures, which can be divided into two groups. One group referred to half-power bandwidth method in PP [2], logarithmic-
named artificial excitation uses mechanical shakers, drop weights, decrement method with RDT [6] and Empirical Mode Decomposi-
human walking, control devices and so on. The other group named tion-Hilbert Transform (EMD-HT) method [13]. Besides them,
natural excitation uses ambient vibration, wind and earthquake there are also some developments in damping estimation these
[1]. days. A new approach is proposed to identify modal damping ratios
from free vibration response [15]. A structural damping identifica-
⇑ Corresponding author. Tel./fax: +86 021 65986103. tion procedure is presented based on the sensitivity of acceleration
E-mail address: swxtgk@tongji.edu.cn (W. Shi). response of the model with model updating technique using the

0141-0296/$ - see front matter Ó 2011 Elsevier Ltd. All rights reserved.
doi:10.1016/j.engstruct.2011.11.025
W. Shi et al. / Engineering Structures 36 (2012) 14–26 15

measured acceleration records [16]. The average inverse power ra-


tio method is discussed and proposed for the damping estimation
from a frequency response function [17,18].
Detailed system identification tests (for more than ten order
modal information) have been successfully applied to a number
of bridges such as the Hakucho suspension bridge [8], the Alfred
Zampa Memorial Bridge [19], the Gi–Lu bridge [20], and the Qingz-
hou cable-stayed bridge [21]. Many dynamic field tests on high-
rise buildings are performed for the purpose of wind-induced
vibration monitoring [22–25] or fundamental modal damping
evaluation [26]. These sensor locations, mostly near the roof level
among these studies, are not sufficient considering that not all
the information of modes is significant in the vibration responses
measured from locations near the roof level.
In this study, three representative modal identification tech-
niques were applied to the dynamic field test data collected from
the Shanghai World Financial Center (SWFC), a currently built
super high-rise building in Shanghai. These methods consist of:
(1) Peak-Picking method with half-power bandwidth method in
frequency domain; (2) Random Decrement method with logarith-
mic-decrement method in time domain; and (3) Empirical Mode
Decomposition-Hilbert Transform method in time-frequency do-
main. The measurements on the different floors of the building
were analyzed individually by these three methods to identify
the modal parameters. There is a discussion about the identified
results under ambient vibration between PP method and HHT
method. The identified natural frequencies are compared with
the analytical finite element model and shaking table test results.
The damping characteristics of the building with ATMD action on
and off are presented. Recommended lengths of FFT are proposed
corresponding to respective selected frequency ranges for the
FFT-based methods. Finally, the effect of RDT on the decaying
Fig. 1. Perspective view of Shanghai World Financial Center.
amplitude lines are shown to suggest the importance of RDT in
the HHT based method.

2. Field Test of Shanghai World Financial Center

2.1. Introduction of Shanghai World Financial Center

Shanghai World Financial Center (SWFC) is an extraordinary


building with a museum at the base, a hotel at the top, and office
spaces in between (see Fig. 1). The height of 101-storey building
is 492 m above ground. It is located in Lujiazui Financial and Trade
district, Shanghai, China. The structure is diagonally symmetrical
with a square base plan of 57.95 m  57.95 m, and the aspect ratio
of height to width is 8.49 [27]. Three parallel structural systems
including mega-frame structure, reinforced concrete and braced
steel services core, and outrigger trusses, are combined to resist
vertical and lateral loads, as shown in Fig. 2 [28].
In order to mitigate wind-induced vibration, two identical ac-
tive tuned mass dampers (ATMDs) are installed on the ninetieth
floor (90F), which is illustrated in Fig. 3. The active control feature
of the ATMDs is enabled under wind loading. The mass of the Fig. 2. Three parallel structural systems of Shanghai World Financial Center [23].
damping device is hoisted by the multi-sectional steel cables.
The damping devices consist of two parts: multi-section vibration
body and drive device. The control force of vibration body is 2.2. Experimental setup and response data
obtained by the feedback motion state variables. These state vari-
ables include the acceleration of the floor on which the damping A set of dynamic field tests were performed on the SWFC from
devices are set up, as well as displacement and speed of the vibra- April to May 2008. Fig. 1 also shows the construction stage of SWFC
tion body. The active control feature becomes disabled under during the dynamic field tests. These tests included ambient vibra-
earthquake excitation and the damping devices perform as pas- tion tests and forced vibration tests based on the actions of the
sive tuned mass dampers. The devices are locked when the vibra- ATMDs. In order to record the accurate low frequency behaviors
tion amplitude of vibration body exceeds 110 cm in the passive of the structure, the acceleration responses at various floors were
control state. sampled at a rate of 20 Hz. The resulting Nyquist frequency of
16 W. Shi et al. / Engineering Structures 36 (2012) 14–26

Fig. 3. Floor plan of the ninetieth floor (90F) and the installation of the two active tuned mass dampers.

10 Hz was much higher than the frequencies of interest (<2 Hz). A recorded. The ambient vibration test data used in this study were
dynamic response range of piezoelectric accelerometers used in collected in 30–40 min segments.
this test is from 0.05 Hz to 500 Hz, the measurement capacity Two types of forced vibration tests were performed on the
range is 0.1 g (1 g = 9.8 m/s2), and the sensibility is 105 g. Fig. 4 SWFC by the ATMDs. The first type is that the structure was forced
illustrates the typical accelerometers and data acquisition equip- to vibrate by an ATMD in one horizontal direction at an amplitude
ment used in this test. During the test, densely distributed acceler- of 5 cm/s2. Then the actuating ATMD was turned off to get the free
ometers were placed at different locations in two experimental decay response in this direction. The inherent fundamental damp-
steps, as shown in Fig. 5. For the first step, the accelerometers were ing ratio of the structure with ATMD off is estimated through this
located at tenth floor (10F), fiftieth floor (50F), sixtieth floor (60F), forced vibration test. The difference of the second type is that while
seventieth floor (70F), eightieth floor (80F), and ninetieth floor one actuating ATMD off, the other ATMD was turned on to reduce
(90F). Then at the second step, the accelerometers were moved the vibration in this direction. Figs. 6 and 7 show the acceleration
to fifteenth floor (15F), twenty-fifth floor (25F), fifty-fifth floor responses of the ninetieth floor (90F) during the two types of
(55F), sixty-fifth floor (65F), seventy-fifth floor (75F), and eighty- forced vibration tests, respectively. The ambient vibrations in the
fifth floor (85F). In these steps, both the ambient and forced two horizontal directions are also illustrated in Fig. 8.
vibration responses in two translational directions (X, Y) have been
3. Brief review of modal identification methods used

3.1. Peak-Picking method

The Peak-Picking (PP) method is a traditional frequency domain


method using output-only data and already applied to the modal
identification of engineering structures. It stems from the fact that
the frequency response function (FRF) of a given system will peak
at the modal frequencies of the system. With the broadband white
noise assumption, the Fourier power spectrum of the response data
can be considered as equal to the FRF of the structure at that sensor
location. The modal frequencies are identified through the power
spectrums from every experimental measurement. The corre-
sponding damping ratios can be estimated with half-power band-
width method, defined as:

Bi
ni ¼ ð1Þ
2f i

Fig. 4. The sensor placement and data acquisition equipment on the twenty-fifth where Bi is the half-power bandwidth of the spectral peak corre-
floor (25F). sponding to ith-order modal frequency fi.
W. Shi et al. / Engineering Structures 36 (2012) 14–26 17

where y(t) is a random time history sampled from ti to ti + s, s is the


equal time length of segments, and N is the number of segments in
the ensemble average.
If a stationary Gaussian random process excites a linear Single-
Degree-of-Freedom (SDOF) system, the RD-generated random sig-
nature of that response will have similar characteristics as a free
vibration response of the linear system under a specified initial
condition. The Random Decrement functions are curve-fitted to
obtain the logarithmic-decrement functions. Assuming that the
logarithmic-decrement function is in the form of Eq. (3), the modal
frequencies and damping ratios can be obtained utilizing the linear
least-square method:
xðtÞ ¼ A0 cos ðxd tÞ  expðnx0 tÞ ð3Þ
where A0 is the initial displacement, xd is the damped natural cir-
cular frequency, n is the damping ratio and x0 is the natural circular
frequency.
In this study, the modified RDT method is utilized for analysis,
which is to apply the triggering condition in the negative part of
the response and then average the extracted time segments for a
change in the sign with the extracted positive part of the response
time series. The number of the averaged time segments N is signif-
icant increased by the modified RDT method to derive better
Random Decrement signature.

3.3. Hilbert–Huang transform

The Hilbert–Huang transform method is a two-step data-analy-


sis method [29]. The first step is the empirical mode decomposition
(EMD) by which a complicated time history can be turned into a
series of intrinsic mode functions (IMFs) that admit well-behaved
Hilbert transforms. The second step of the HHT method is imple-
mented by performing the Hilbert transform (HT) to each IMF com-
ponent [13]. With Hilbert transform, an analytic signal z(t) for a
real-valued function y(t) can be defined as:
~ðtÞ ¼ AðtÞ  expðihðtÞÞ
zðtÞ ¼ yðtÞ þ iy ð4Þ
Z 1
yðuÞ
~ðtÞ ¼ H½yðtÞ ¼
y du ð5Þ
1 pðt  uÞ

where y ~ðtÞ is the Hilbert transform of y(t), i is the imaginary unit,


A(t) and h(t) are the amplitude and instantaneous phase angle of
y(t), respectively. The instantaneous frequency x(t) is thus the time
derivative of h(t). The definition equations of A(t), h(t), and x(t) are
shown below:

AðtÞ ¼ ½y2 ðtÞ þ y ~2 ðtÞ1=2 ð6Þ


 
~ðtÞ
y
Fig. 5. The elevation of Shanghai World Financial Center and the accelerometer
hðtÞ ¼ tan1 ð7Þ
yðtÞ
distribution of the field test.
dhðtÞ
xðtÞ ¼ ð8Þ
dt
3.2. Random Decrement based method For a linear Single-Degree-of-Freedom (SDOF) system under
impulsive loading, the free vibration response function of the sys-
The Random Decrement technique (RDT) is based on the tem is:
assumption that the dynamic response of a system is a superposi-
tion of the responses due to the initial displacement and velocity v ðtÞ ¼ A0 sin ðxd tÞ  expðnx0 tÞ; t P 0 ð9Þ
conditions, and the random vibration response due to random where x0 is the natural circular frequency, n is the damping ratio,
excitation [6,8]. The RD procedure starts by selecting an appropri- xd is the damped natural circular frequency and A0 is a constant
ate threshold value of the response, from which the equally-spaced depending on the intensity of impulsive loading and the mass and
segments of ht0, t + t0i time histories are extracted. These segments frequency of the system. By applying the Hilbert transform method,
are then averaged in order to eliminate the random parts and to the signal z(t) for v(t) can thus be obtained using Eq. (4):
retain only the deterministic part of the response. The Random
Decrement signature x(s) is expressed as: zðtÞ ¼ v ðtÞ þ iv~ ðtÞ ¼ AðtÞ  expðihðtÞÞ ð10Þ

1X N For a special case in which n is small and x0 is large, the amplitude


xðsÞ ¼ yðt i þ sÞ ð2Þ A(t) and the phase angle h(t) for the SDOF system can be obtained as
N i¼1
follows [30]:
18 W. Shi et al. / Engineering Structures 36 (2012) 14–26

Fig. 6. Acceleration response measured on the ninetieth floor in two horizontal directions during the first type of forced vibration test (ATMD off for the free decays): (a) X
direction; (b) Y direction.

Fig. 7. Acceleration response measured on the ninetieth floor in two horizontal directions during the second type of forced vibration test (ATMD on for the free decays): (a) X
direction; (b) Y direction.

Fig. 8. Ambient vibration measurement on the ninetieth floor in two horizontal directions: (a) X direction; (b) Y direction.
W. Shi et al. / Engineering Structures 36 (2012) 14–26 19

Table 1
Identified natural frequencies and damping ratios of the SWFC based on free decays with ATMD off.

Direction X Y
Method RDT-curve fitting method
Mode information Frequency (Hz) Damping ratio Frequency (Hz) Damping ratio
Value 0.1562 0.00509 0.1567 0.00423
Method Hilbert–Huang transform method
Mode information Frequency (Hz) Damping ratio Frequency (Hz) Damping ratio
Value 0.1563 0.00525 0.1570 0.00439

Fig. 9. Instantaneous functions of the first modal response by Hilbert transform method: (a) phase angle and linear least-squares fit; (b) amplitude and linear least-squares
fit.

AðtÞ ¼ A0  expðnx0 tÞ ð11Þ ln AðtÞ ¼ nx0 t þ ln A0 ð13Þ


p dhðtÞ
hðtÞ ¼ xd t  ð12Þ xðtÞ ¼ ¼ xd ð14Þ
2 dt
By introducing the logarithmic and differential operators to Eqs.
(11) and (12), respectively, one obtains: Therefore, the damped natural circular frequency xd can be identi-
fied from instantaneous frequency x(t) by Eq. (14). With the iden-
tified xd and the slope nx0 of the straight line of the decaying

Fig. 10. Instantaneous functions of the second modal response by Hilbert transform method: (a) phase angle and linear least-squares fit; (b) amplitude and linear least-
squares fit.
20 W. Shi et al. / Engineering Structures 36 (2012) 14–26

Fig. 11. Power spectrums in two translational directions from the response to ambient excitations: (a) X direction on the eightieth floor; (b) X direction on the sixty-fifth
floor; (c) X direction on the fifteenth floor; (d) Y direction on the eightieth floor; (e) Y direction on the sixty-fifth floor; (f) Y direction on the fifteenth floor.

amplitude A(t) in a semi-logarithmic scale, the damping ratio n can


be identified from the function xd = x0(1  n2)1/2. It should be Table 2
Identified modal information of the SWFC based on two methods under
noted that the Random Decrement technique is performed on the
microtremors.
target IMF to derive the free vibration response v(t) before the Hil-
bert transform. Method Pick-Peaking method Hilbert–Huang transform
method
Mode Data Frequency Damping Frequency Damping
4. Modal identification results
location (Hz) ratio (Hz) ratio
1 90F 0.1550 0.0059 0.1554 0.0063
This section presents the identified natural frequencies and
2 90F 0.1575 0.0046 0.1579 0.0048
damping ratios both from free decays and ambient vibration mea- 3 85F 0.4858 0.0066 0.4878 0.0049
surements. In purpose of comparison of the results from the free 4 15F 0.5371 0.0074 0.5496 0.0070
decay and ambient vibration, the free and ambient vibration data 5 25F 0.5737 0.0073 0.5730 0.0069
used in this section were all measured with the ATMD action off, 6 65F 0.9375 0.0050 0.9419 0.0049
7 55F 0.9717 0.0066 0.9747 0.0054
for example as shown in Figs. 6 and 8. 8 80F 1.0254 0.0085 1.0270 0.0032
9 25F 1.3965 0.0124 1.3872 0.0102
4.1. Results based on free vibration data 10 65F 1.4697 0.0078 1.4665 0.0107
11 85F 1.5283 0.0054 1.5279 0.0053
The modal identification techniques, RDT-curve fitting and
Hilbert–Huang transform method Eq. (9)–(14), were applied to
estimate the fundamental modal parameters based on free vibra-
two modes partially verify the necessity of the installation of the
tion test data. Due to the fact that the free vibration data are of
ATMDs on the high-rise building.
shorter duration than the ambient data, the Peak-Picking method
is not preferred here. The estimated fundamental frequencies and
damping ratios in the two translational directions are listed in Ta- 4.2. Results based on ambient vibration data
ble 1. The instantaneous functions of the first two modal responses
derived from the Hilbert transform are illustrated in Figs. 9 and 10. According to the practical engineering experience, accurate esti-
The damping ratios identified from the RDT-curve fitting method mation values of mode frequencies and damping ratios cannot be
are further considered as reference values to evaluate the accuracy obtained through the PP method only by limited test locations.
of the results from ambient vibration in the following section. It is Fig. 11 shows the power spectrums in two translational directions
noted that the fundamental frequencies in the two directions are from different test locations, which are fifteenth floor, sixty-fifth
close to each other, and the identified damping ratios of the struc- floor, and eightieth floor. It is understood that some higher mode
ture are around 0.5%. The low damping characteristics of the first frequency peaks may be not significant in the power spectrum
W. Shi et al. / Engineering Structures 36 (2012) 14–26 21

Fig. 12. The original ambient measurement on the ninetieth floor and its IMF components by EMD method.
22 W. Shi et al. / Engineering Structures 36 (2012) 14–26

Fig. 13. First and eleventh modal free modal response derived by the EMD and RDT method: (a) first modal response; (b) eleventh modal response.

Fig. 14. Instantaneous functions of the first modal response by Hilbert transform: (a) phase angle and linear least-squares fit; (b) amplitude and linear least-squares fit.

from the locations near the anti-node of the mode. For example, The HHT method is applied to each selected time series of struc-
the peak corresponding to 1.4697 Hz is significant in Fig. 11b but tural acceleration response to obtain the Hilbert spectrum in the
not apparent in Fig. 11a. Additionally, the fundamental frequency time-frequency domain. The first step is empirical mode decompo-
of 0.1575 Hz in the Y direction is not as clearly shown in Fig. 11e sition to obtain the intrinsic mode functions (IMFs). A series of
as in Fig. 11d and f. By analysis of all the significant peaks of the IMFs obtained from the measured data in the X direction at the
power spectrums from the twelve floors, the first eleven modal fre- ninetieth floor by empirical mode decomposition are plotted in
quencies are identified. The corresponding damping ratios are ob- Fig. 12. Since there are still some random components in the target
tained by applying the half-power bandwidth method. The relative IMF that would affect the accuracy of the identification, the RDT is
levels and the curve shapes of the modal frequency peaks in the then applied to the obtained IMF to extract the free modal re-
power spectrum are the two main reasons to select the data among sponses, which is then analyzed by the HT method [13,14,31].
the twelve floors for damping evaluation. The relatively higher and The triggering level was chosen as 1.0  r, where r is the root-
steeper peak is preferred which indicates more prominent vibra- mean-square of the time history. The optimal duration of segment
tion component in the measurement and less energy leak of this used in this study ranged from 40 s (eleventh-order mode) to 200 s
mode in the frequency domain. Different lengths of FFT were uti- (first-order mode) in the purpose that the RDT function is fully de-
lized ranging from 2048 to 16384 for the identification of the ele- cayed and the vibration is not becoming too small. Fig. 13 shows
ven modes. Both the natural frequencies and damping ratios are the first and eleventh-order free modal response time series result-
listed in Table 2 with the corresponding location information of ing from the seventh IMF of the measured data at the ninetieth
the used measurement data. floor in the X direction and the third IMF of the measured data at
W. Shi et al. / Engineering Structures 36 (2012) 14–26 23

Fig. 15. Instantaneous functions of the eleventh modal response by Hilbert transform: (a) phase angle and linear least-squares fit; (b) amplitude and linear least-squares fit.

Fig. 16. Comparison of the identified modal information of SWFC by Peak-Picking method and Hilbert–Huang Transform method using ambient vibration data: (a) modal
frequency; (b) modal damping ratio.

Table 3
The identified damping ratios and the rates of the identified values to reference values.

Method Reference value (free decay) PP method HHT method


Mode Damping ratio Damping ratio Rate Damping ratio Rate
1 0.00509 0.0059 1.159 0.0063 1.238
2 0.00423 0.0046 1.087 0.0048 1.135

the eighty-fifth floor in the X direction, respectively. The last step is 4.3. Comparison
to apply the Hilbert transform to every free modal response time
series to yield the instantaneous phase angle and amplitude func- Fig. 16 plots the identified natural frequencies and correspond-
tions. Both the instantaneous phase angle and amplitude functions ing damping ratios by Peak-Picking method and the Hilbert–Huang
from the first and eleventh-order free modal response time series Transform method. It is seen from Table 2 and Fig. 16 that the esti-
are shown in Figs. 14 and 15 with their linear least-squares fits. mated first eleven modal frequencies are approximately identical
The identified modal frequencies and damping ratios of SWFC by to each other between these two methods. Although the identified
the HHT method are also listed in Table 2. damping ratios do not show the same agreement as the modal
24 W. Shi et al. / Engineering Structures 36 (2012) 14–26

Fig. 17. The first five vibration mode shapes of the Shanghai World Financial Center computed from the finite element model.

Table 4 from the identified modal frequencies of the experimental struc-


The identified modal frequencies from three research areas. ture of the shaking table test. The first three modal frequencies
Method Field dynamic test Finite element analysis Shaking table test
of the building identified from the field test by PP method are com-
Mode Frequency (Hz) Frequency (Hz) Frequency (Hz) pared with their analytical counterparts obtained from the finite
1 0.1550 0.1561 0.176
element model and the shaking table test, which is listed in Table
2 0.1575 0.1837 0.176 4. It is noted that the identified modal frequencies have similar
3 0.4858 0.3598 0.411 values when compared between these research areas.
Note: The structure used in the finite element model is with ATMD and the
experimental structure used in the shaking table test is without ATMD. 5. Discussion

Besides the modal identification of the structure under microt-


Table 5 remors, the effect of the installed ATMDs on the damping proper-
Comparison of the damping ratios from two types of the forced vibration tests. ties were also evaluated through the analysis on the two types of
the forced vibration tests. The measurements are shown above in
Direction Frequency (Hz) ATMD action Damping rate (%)
Figs. 6 and 7. The intuitive difference between these two figures
X 0.1562 Off 0.509
is the significant different duration time of free decays to low
On 3.404
vibration levels (<0.01 m/s2), which is nearly 400 and 50 s in Figs.
Y 0.1567 Off 0.423
6 and 7, respectively. The comparison of the identified damping
On 3.865
ratios by the curve-fitting method on the free decays are listed in
Table 5. It is noted that the fundamental damping in the two trans-
lational directions are increased approximately seven-fold and
frequencies, the results are still applicable in practical engineering, nine-fold, respectively, when the ATMDs are turned on.
when considering the inherent uncertainty in damping prediction There is a general accepted opinion that the FFT-based method
and estimation [6]. It is suggested that the accuracy of 5–10% seems to overestimate the damping ratio compared to other meth-
would be appropriate for damping evaluation based on steady- ods because of the request for the length and stationary of data.
state forced vibration testing [32]. In this paper, the reference There must be at least four spectral lines in the half-power band-
values were assumed to be the damping ratios estimated from free width of each mode for limit bias errors [32]. In practical modal
decays by curve-fitting method. The rates of damping ratio be- identification, it is not convenient to check the contained spectral
tween the values identified from ambient vibration to the refer- line number. As a alternative, the length of FFT is proposed here
ence values are listed in Table 3. It is seen that the rates of to study the accuracy. A convergence study of the effect of the
different method in the X direction are 1.159 and 1.238, while frequency resolution Df on the damping ratio identification was
1.087 and 1.135 in the Y direction. The accuracy between the free performed as illustrated in Fig. 18. The dashed lines show the
decays and the ambient vibration is acceptable in damping damping estimations from the free decays with ATMD action off,
evaluation. as reference values acting in the two horizontal directions. It is
Besides the field measurement, a three-dimensional numerical seen that the estimations of damping shown by solid line converge
model of the SWFC was developed in the finite element analysis to the reference value while the frequency resolution decreases
software ANSYS. The first five natural frequencies and mode shapes from 0.0195 Hz to 0.0012 Hz. Note that the frequency resolution
obtained by the analytical finite element model are illustrated in value 0.0195 Hz corresponds to the length of FFT of 1024, while
Fig. 17. It shows that the first three modes of vibration are the lat- 0.0012 Hz relates to 16384. The frequency resolution here is
eral bending in the X direction, the lateral bending in the Y direc- directly determined by the length of FFT. Depending on the identi-
tion, and the torsion mode. According to the designed similarity fied results from field test, a series of recommended length of FFT
ratio, the modal frequencies of the prototype can also be calculated to utilize is proposed to meet the requirement of frequency
W. Shi et al. / Engineering Structures 36 (2012) 14–26 25

Fig. 18. Convergence study of the effect of frequency resolution on the accuracy of damping estimation by half-power bandwidth method: (a) the first mode damping ratio;
(b) the second mode damping ratio.

Fig. 19. Decaying amplitude lines calculated from ambient measurement: (a) with RDT; (b) without RDT.

resolution. If the interested modal frequency is in the range of hfnst/ estimation. It illustrates that the free vibration modal response
2n+1  fnst/2ni, the recommended length of FFT should be from the Random Decrement technique ensures the accuracy of
1024  2n, where fnst is the Nyquist frequency of the test. the Hilbert transform for modal identification of structural
The Hilbert–Huang transform method is utilized to analyze systems.
nonlinear and nonstationary time series in the frequency-time do-
main. If the HHT method is applied to the stationary ambient
vibration measured data, the Random Decrement technique is nec- 6. Conclusions and remarks
essary to obtain the free vibration modal response. Two compara-
tive cases were performed. One case used the RDT method on the This study has presented a data analysis with three modal iden-
target IMF before the Hilbert transform. The other case performed tification procedures to obtain dynamic properties of the Shanghai
the Hilbert transform directly on the target IMF without RDT. Two World Financial Center both from the free decays and ambient
decaying amplitude lines from both cases are plotted in Fig. 19. The vibration response. Three representative modal identification tech-
decaying amplitude line, derived without RDT as shown in Fig. 19b, niques are applied to the measured vibration data from a set of dy-
becomes unstable with large amplitude oscillation, which makes it namic field tests. These tests provided a unique opportunity to
unsuitable for use of linear least-squares fit technique for damping obtain the modal information of the super high-rise building from
26 W. Shi et al. / Engineering Structures 36 (2012) 14–26

artificial excitation and natural excitation, respectively. The long- [8] Siringoringo DM, Fujino Y. System identification of suspension bridge from
ambient vibration response. Eng Struct 2008;30:462–77.
period and inherent low-damping characteristics of the super
[9] Pi YL. Modal identification of vibrating structures using ARMA model. J Eng
high-rise building are identified from the field test. Because of Mech 1989;115(10):2232–50.
the twelve test locations distributed along the elevation in differ- [10] Beck J. System identification methods applied to measured seismic response.
ent floors, the identified natural frequencies and damping ratios In: Proceedings of the 11th world conference on earthquake engineering,
Acapulco, Mexico; 1996.
are given out with good confidence. The accuracy of the methods [11] Kijewski T, Kareem A. Wavelet transforms for system identification in civil
has been further investigated. There are some conclusions drawn engineering. Comput Aided Civil Infrast Eng 2003;18:339–55.
from the study: (1) the identified natural frequencies from the dif- [12] Ulker-Kaustell M, Karoumi R. Application of the continuous wavelet transform
on the free vibrations of a steel-concrete composite railway bridge. Eng Struct
ferent methods in different domains are in excellent agreement for 2011;33:911–9.
the eleven modes; (2) the discrepancy of the estimated damping [13] Xu Y, Chen S, Zhang R. Modal identification of Di Wang Building under
ratios under ambient vibration is relatively larger than that of Typhoon York using the Hilbert–Huang transform method. Struct Des Tall
Special Build 2003;12:21–47.
the natural frequencies, but still shows promise for use in practical [14] Yang JN, Lei Y, Lin S, Huang N. Identification of natural frequencies and
engineering; (3) the optimal test locations for different modes are dampings of in situ tall buildings using ambient wind vibration data. J Eng
distributed from twenty-fifth floor (25F) to ninetieth floor (90F); Mech 2004;130(5):570–7.
[15] Huang FL, Wang XM, Chen ZQ, He XH, Ni YQ. A new approach to identification
(4) the identified natural frequencies of the prototype agree with of structural damping ratios. J Sound Vib 2007;303:144–53.
the results of finite element model and shaking table test; (5) the [16] Li X, Law S. Identification of structural damping in time domain. J Sound Vib
fundamental damping ratios in two directions have been increased 2009;328:71–84.
[17] Yin H. A new theoretical basis for the bandwidth method and optimal power
significantly with the actions of the ATMDs; (6) a series of recom-
ratios for the damping estimation. Mech Syst Signal Process 2008;22:1869–81.
mended length of FFT is proposed to meet the requirement of fre- [18] Yin H. An average inverse power ratio method for the damping estimation
quency resolution in practice; and (7) the RDT should be applied from a frequency response function. Mech Syst Signal Process
between the EMD and HT method when facing the ambient vibra- 2010;24:617–22.
[19] He X, Moaveni B, Conte JP, Elgamal A, Masri SF. System identification of Alfred
tion response records. Zampa Memorial Bridge using dynamic field test data. J Struct Eng
The modal identification results from this study provide the ele- 2009;135(1):54–66.
ven modal properties of the Shanghai World Financial Center, [20] Weng JH, Loh CH, Lynch JP, Lu KC, Lin PY, Wang Y. Output-only modal
identification of a cable-stayed bridge using wireless monitoring systems. Eng
which can be in the application of the structural health monitoring Struct 2008;30:1820–30.
and structural damage detection to the super high-rise building [21] Ren WX, Peng XL, Lin YQ. Experimental and analytical studies on dynamic
under ambient vibration. characteristics of a large span cable-stayed bridge. Eng Struct
2005;27:535–48.
[22] Li Q, Xiao Y, Wong C, Jeary A. Field measurements of typhoon effects on a super
Acknowledgements tall building. Eng Struct 2004;26:233–44.
[23] Li Q, Xiao Y, Wu J, Fu J, Li Z. Typhoon effects on super-tall buildings. J Sound Vib
2008;313:581–602.
The authors are thankful for the assistances provided by Dr. [24] Xu Y, Zhan S. Field measurements of Di Wang Tower during Typhoon York. J
Xianqun Guo during the field test on the Shanghai World Financial Wind Eng Ind Aerodynam 2001;89:73–93.
[25] Snaebjornsson J, Reed D. Wind-induced accelerations of a building: a case
Center. study. Eng Struct 1991;13:268–80.
[26] Glanville M, Kwok K, Denoon R. Full-scale damping measurements of
structures in Australia. J Wind Eng Ind Aerodynam 1996;59:349–64.
References [27] Lu X, Zou Y, Lu W, Zhao B. Shaking table model test on Shanghai World
Financial Center Tower. Earthquake Eng Struct Dyn 2007;36:439–57.
[1] Suda K, Satake N, Ono J, Sasaki A. Damping properties of buildings in Japan. J [28] Leslie E. Robertson, SawTeen See. The Shanghai World Financial Center:
Wind Eng Ind Aerodynam 1996;59:383–92. welding brilliant architecture to imaginative engineering. Structure Magazine,
[2] Clough RW, Penzien J. Dynamics of structures. Computers & Structures Inc.; June 2007.
1995. [29] Huang NE, Shen Z, Long SR, Wu MC, Shih HH, Zheng Q, et al. The empirical
[3] Brincker R, Zhang L, Andersen P. Modal identification of output-only systems mode decomposition and the Hilbert spectrum for nonlinear and non-
using frequency domain decomposition. Smart Mater Struct 2001;10:441–5. stationary time series analysis. Proc R Soc Lond Ser A: Math Phys Eng Sci
[4] Magalhães F, Cunha Á, Caetano E. Dynamic monitoring of a long span arch 1998;454:903–95.
bridge. Eng Struct 2008;30:3034–44. [30] Yang J, Lei Y. Identification of natural frequencies and damping ratios of linear
[5] Brincker R, Ventura C, Andersen P. Damping estimation by frequency domain structures via Hilbert transform and empirical mode decomposition. In:
decomposition. Kissimmee, USA: IMAC; 2001. p. 698–703. Proceedings of the international conference on intelligent systems and
[6] Kareem A, Gurley K. Damping in structures: its evaluation and treatment of control. Anaheim, CA: IASTED/Acta Press; 1999. p. 310–5.
uncertainty. J Wind Eng Ind Aerodynam 1996;59:131–57. [31] Li Q, Wu J. Time-frequency analysis of typhoon effects on a 79-storey tall
[7] Brownjohn J, Magalhaes F, Caetano E, Cunha A. Ambient vibration re-testing building. J Wind Eng Ind Aerodynam 2007;95:1648–66.
and operational modal analysis of the Humber Bridge. Eng Struct [32] Littler J. An assessment of some of the different methods for estimating
2010;32:2003–18. damping from full-scale testing. J Wind Eng Ind Aerodynam 1995;57:179–89.

You might also like