You are on page 1of 10

This article has been accepted for publication in a future issue of this journal, but has not been

fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2728718, IEEE
Transactions on Energy Conversion

VSC Based Active Synchronizer for Generators


Shahil Shah, Student Member, IEEE, Hongbo Sun, Senior Member, IEEE, Daniel Nikovski, Member, IEEE, and
Jinyun Zhang, Fellow, IEEE

AbstractFast synchronization of generators and microgrids the generator and power system [2, 3]. This makes the intercon-
will be a critical technology in future power systems with high nection time highly variable and dependent on the initial phase
penetration of non-dispatchable power resources. Existing
error and frequency offset. Higher frequency offset can reduce the
synchronization methods rely on generator controls and their
performance is limited by the generator characteristics. Speed of phase-locking time [2], but results in a larger disturbances during
microgrid synchronization is further limited by the communi- interconnection. Active phase synchronization has been proposed
cation link among generation units. These factors lead to a slow in [5] by adding a term depending on the phase error to the
and sometimes faulty synchronization, predominantly because of generator frequency control loop. However, it is necessary to
the phase mismatch during interconnection. This paper frames
design the phase control much slower than the frequency control
the generator synchronization problem as a phase-locked loop
(PLL) design problem and introduces a voltage-source converter to avoid unstable interaction between them. The frequency control
(VSC) based synchronizer for implementing the PLL based active of generators is already very slow and the above requirement
synchronization method. The VSC based synchronizer is results in even slower phase synchronization. Hence, active phase
connected at the point of common coupling and it relies only on synchronization based on the generator controls gives little
local measurements for control. It ensures zero phase error
advantage over the passive phase synchronization approach.
during interconnection by taking the advantage of the fact that
the phase is not regulated in the generator controls. Relation Phase synchronization is more critical than the voltage and
between the synchronizer rating, control design, and synchroni- frequency synchronization for reducing the inrush currents [1].
zation speed is developed using describing function analysis of Unreliable phase synchronization and indeterminate breaker
frequency and phase control loop gains. The operation and operation time may lead to an out-of-phase synchronization and
performance of the VSC-based synchronizer is demonstrated
generator damage [6].
using simulations for a 555 MVA, 24 kV synchronous generator.
Synchronization of microgrids is achieved in a similar manner
Index TermsSynchronization, microgrid control, distributed as synchronous generators and suffers the same problems.
generators, automatic synchronizer. Additionally, as the synchronization parameters at the PCC of a
microgrid depend on several distributed generators, the synchroni-
I. INTRODUCTION
zation function is implemented in the secondary control [7, 8].
With the increasing penetration of non-dispatchable renewable Hence, the microgrid synchronization speed is further limited by
energy resources in power systems, it is becoming important to be the communication system of the secondary control [9-12]. Same
able to quickly dispatch generation units whenever demanded by as synchronous generators, the phase synchronization in
the load dispatch centers. Before a generator can be connected to a microgrids is achieved either passively [13] or by introducing a
power system, the frequency, phase, and amplitude of the voltages correction term, depending on the phase error, in the microgrid
at its bus need to be matched with those of the power system at the frequency control loop [14-17]. However, phase being an ac
point of common coupling (PCC) [1, 2]. Hence, fast synchroni- variable unlike the voltage and frequency magnitudes, phase
zation is critical to reduce the interconnection time. synchronization performance is particularly limited by the
Synchronization of conventional generators is achieved communication speed when achieved by distributed generator
through generator controls, including the frequency and voltage controls.
control [2-4]. The generator controls are structured into hierar- The above discussion highlights two problems: 1) control
chical levels including primary, secondary, and tertiary level design framework to avoid interaction between the frequency and
controls. Secondary control is implemented at a central location phase synchronization of generators and microgrids is not studied
and it communicates references to the primary control of (this is important because of the discontinuous nature of the phase
geographically distributed generators. Generator synchronization error); and 2) achieving fast synchronization, particularly the
is achieved locally in the primary control [2-4]. Fast synchroni- phase synchronization, is challenging when implemented through
zation, however, is difficult using the existing method as the generator controls. This paper addresses the above problems by
primary control bandwidth is limited by the generator character- framing the generator and microgrid synchronization problem as a
istics, e.g. mechanical inertia. Moreover, the phase synchroni- phase-locked loop (PLL) design problem and introducing a VSC-
zation is usually achieved passively by a frequency offset between based synchronizer at the PCC of the generator or microgrid to be
synchronized. The proposed VSC-based synchronizer relies only
S. Shah is with Rensselaer Polytechnic Institute, Troy, NY 12180 USA (email:
shahs12@rpi.edu). on local measurements and actively regulates the phase angle of
H. Sun, D. Nikovski, and J. Zhang are with Mitsubishi Electric Research the incoming generator or microgrid. Hence, zero phase error can
Laboratories, Cambridge, MA 02139, USA (e-mail: hongbosun@merl.com; be maintained during the breaker operation. Control system of the
nikovski@merl.com; jzhang@merl.com) synchronizer is implemented using a phase-locked-loop (PLL)

0885-8969 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2728718, IEEE
Transactions on Energy Conversion

structure [18, 19], in which the generator or microgrid to be input power Pm to the generator to eliminate the frequency error.
synchronized is treated as an oscillator. The PLL structure The voltage amplitude is similarly synchronized by modulating
provides a design framework for avoiding interaction between the the input voltage to the field windings of the generator (Efd). The
frequency and phase control loops. Relation between the synchro- phase synchronization is achieved by a frequency offset between
nizer rating, control design, and synchronization speed is the generator and grid frequencies. Because of the frequency
presented using describing function analysis. It is shown that the difference, the phase error keeps on changing with time. Once the
proposed synchronizer can reduce the synchronization time by an frequency, phase, and voltage errors come within stipulated limits,
order of magnitude, even when it is rated at less than one percent usually referred as synchronization window [2], the generator
of the generator rating. Operation and design principles of the breaker is closed.
VSC-based synchronizer are demonstrated using detailed simula- This paper focusses on the frequency and phase synchroni-
tions of a 555 MVA, 24 kV synchronous generator. zation and assumes that the voltage levels are always synchro-
The rest of the paper is organized as follows: Section II reviews nized because of the following reasons: i) voltage control can be
the existing synchronization method using generator controls. easily achieved by field current (generators) or reactive power
Section III frames the generator synchronization problem as a (microgrids) control, ii) voltage control does not involve conflict
PLL design problem and introduces a VSC-based synchronizer as in the frequency and phase control, and iii) the voltage
for achieving fast synchronization. Control design, sizing, and matching requirement is much less important for a smooth
performance evaluation of the synchronizer are presented in synchronization than the frequency and phase matching require-
Section IV. Section V concludes this paper. ments [1, 2].
The above discussed synchronization process is demonstrated
II. SYNCHRONIZATION USING GENERATOR CONTROLS in Fig. 2 for a 555 MVA, 24 kV generator. Generator parameters
Fig. 1 illustrates existing method of synchronization using are taken from example 3.1 and 3.2 in [20]. Major parameters are
generator controls [3-8]. In this method, the frequency and also provided in the appendix. Fig. 2a) and b) respectively show
amplitude of the generator output voltages are slowly brought to the frequency and phase synchronization. Fig. 2c) shows inrush
the grid frequency and voltage levels using the primary control of currents after closing of the generator breaker. It is to be noted that
the generator. When the synchronization process is initiated, the because of the synchronization process before the breaker
error between the generator and grid frequencies is processed operation, the peak inrush current is much lower than the
by a synchronization controller, as shown in Fig. 1c). Based on the generator peak rating current of 18.67 kA. The generator breaker
controller output, the primary control modulates the mechanical is closed when the frequency and phase errors are within the
following limits [2]:

Pm o
f  0.05 Hz ,   0.5 (1)
Generator
Controls Because of the slow bandwidth of the synchronization control
Efd loop with the time constant of 120s, the synchronization process
Generator 3- Grid takes around 300s.
Synchronous
Generator
Breaker Microgrid synchronization is achieved in a similar manner,
a) except for the fact that the synchronization controller implemented
at a remote location in the secondary control.
Pe, ref
Pe III. VSC-BASED ACTIVE SYNCHRONIZER
_
In steady-state A. PLL Based Active Synchronization
 =  pri + R p  P e, ref – P e 
Rp Generator or microgrid and main power system can be
considered as two self-sustained oscillators that need to be
pri Pm synchronized. Hence, methods for the synchronization of oscil-
_ Servo Hydraulic
Hpri(s) lators [21] can be applied for generator synchronization. With
Motor Turbine
Gate Opening generator treated as an oscillator, its synchronization problem can

b) Limit be formulated as a phase-locked loop (PLL) design problem. The
PLL structure allows simultaneous control of frequency and phase
without conflict.
sec A PLL consists of three components: phase detector, loop
ref  pri filter, and internal oscillator [18], as shown in Fig. 3. Phase
_ Hsyn(s) 
detector estimates error between the phases of an external signal
c)  and internal oscillator. The output of the phase detector is passed
Fig. 1. Synchronization using generator controls. a) generator to be connected through a loop filter to remove high frequency components. The
with the grid, b) primary control and c) synchronization control of the generator.

0885-8969 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2728718, IEEE
Transactions on Energy Conversion

60.6 can be similarly controlled for implementing the PLL based


synchronization. Any PLL structure [18, 19] and frequency
control mechanism can be used to implement the PLL based
60.4 f active synchronization method.
f (Hz)

B. VSC-based Synchronizer
60.2
The PLL based synchronization is realized using a two-level
voltage source converter (VSC) based synchronizer. The VSC-
60.0 based synchronizer is connected at the PCC of a generator or
a) microgrid to be synchronized. Synchronizer operation and design
0 50 100 150 200 250 300 350 are demonstrated for a synchronous generator. Synchronizer will
t (s)
have similar performance for microgrids with high penetration of
4
synchronous machine based generators. Possible issues that may
arise in microgrids with high penetration of converter based gener-
2 ators are discussed in the following section.
 (rad.)

Fig. 4 shows the previously discussed 555 MVA generator to


0 be connected to the grid via transmission line. It also shows VSC-
based synchronizer connected at the PCC. The VSC is supplied by
2 a dc voltage source of magnitude vdc. The dc side can be supplied
by batteries or fuel cells. It can also be realized by a power
b) converter interfacing with the main power system, resulting in a
4
160 200 240 280 320 back-to-back converter configuration. Back-to-back converter
t (s) configuration at the front-end of a synchronous machine has been
1.5 used in applications requiring variable-speed operation of the
generator, such as pumped-hydro energy storage [22] and type-IV
1.0
Inrush Current (kA)

wind turbines [18]. These applications, however, require full-scale


0.5 power converters as the power is always processed through the
converters. The VSC-based synchronizer, on the other hand, is
 operated only during the synchronization process. It will also be
0.5 shown that the synchronizer rating is required only to be a small
fraction of the generator rating.
1.0
The synchronizer regulates the frequency and phase at the PCC
c) 1.5 by controlling the active power output from the VSC.
301 302 303 Synchronous reference frame (SRF) based three-phase PLLs [18],
t (s) shown in Fig. 4c), are used for obtaining the phase angle,
Fig. 2. Synchronization using generator controls. a) frequency in Hz; solid line is frequency, and amplitude of three-phase voltages. Hence, two
the generator frequency, dashed line is the power system frequency, and dotted line
is the primary control frequency reference, pri/2, b) phase error , and c) inrush PLLs are used, one each for the generator and power system. Both
currents during the generator breaker operation. PLLs are designed with 30 Hz bandwidth. They implement the
phase detector function by obtaining the phase error:
loop filter output serves as frequency reference for an internal
oscillator, which is usually implemented using an analog or digital  =  ref –  (2)
circuit. For a properly designed PLL, the phase error between the
external signal and internal oscillator goes to zero after any distur- where ref and are respectively the phase angles of the power
bance. For generator or microgrid synchronization using the PLL system and generator output voltages. Fig. 4b) shows cascade
structure, an additional frequency control mechanism is required implementation of the frequency and phase control loops to
to track the frequency reference from the loop filter. The generator implement the PLL structure shown in Fig. 3. The phase error 
frequency can be easily controlled by modulating either its input is passed through a phase-control compensator H(s), which acts
power using the generator controls or its output power using a as the loop filter of Fig. 3. As shown in Fig. 4b), H(s) gives
power converter at the generator terminals. Microgrid frequency frequency reference for the oscillator, which in this case is the
generator to be synchronized. To eliminate initial transients, the
power system frequency ref is added to the output of H(s).
External
Phase Phase Loop Freq. PLL Based on the frequency error  the frequency-control
Signal Oscillator
Detector Error Filter Ref. O/P compensator H(s) generates reference for the active power
output Psyn from the VSC-based synchronizer. Finite synchronizer
rating Pc is represented by a saturation block at the output of
Fig. 3. PLL structure. H(s). Active power output from the VSC is regulated by

0885-8969 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2728718, IEEE
Transactions on Energy Conversion

Lline va vga
Pm
Generator vb vgb
Controls vc vgc
Efd
Generator Main Grid
Synchronous Local PLL PLL
Breaker
Generator Loads ib ic
ia
  vd ref ref vd, ref

L
 va vd 1
abc
idr vb  
Psyn
Pbase 23
ma
dq-Current mb
vc dq v HPLL(s)
q
 
PWM
Control mc
0 c)
iqr
vd
vdc idr md
_ Hi(s)
_

_
+
a)
id
ia 1L ma
abc dq
ref ib mb
ref Psyn dq abc
  ic 1L mc
_ H(s) _ H(s) q i
_ 
VSC Rating Pc
  iqr  Hi(s)  m
q
b) d)
Fig. 4. Active synchronization of generator. a) Synchronous generator with VSC-based synchronizer, b) frequency and phase synchronization control implementation, c)
phase-locked loop (PLL), and d) VSC ac current control in the dq-domain.

controlling the output current iabc using dq-domain current control Under such scenario, the generator controls may counteract the
shown in Fig. 4d). It is to be noted that overline indicates per unit synchronizer action because of the mismatch in their operation
(p.u.) values. Unless stated otherwise, parameters from appendix speeds. For example, when the synchronizer tries to increase the
are used for the synchronizer. generator frequency by injecting power at the PCC, as in Fig. 5a),
the generator controls will try to maintain the frequency by
C. Operation in the Absence of Generator Controls
reducing the power input Pm to the generator. Hence, after initial
To avoid conflict between the generator controls and the VSC buildup in the frequency because of the synchronizer, it will return
based synchronizer, the generator controls are disabled during the to the trajectory that is followed when synchronization is achieved
synchronization process. This is realized by freezing Pm and Efd only by the generator controls. Nonetheless, difference between
(ref. Fig. 4) during the synchronization process. Fig. 5 demon- the speeds of the VSC-based synchronizer and generator controls
strates the operation of the VSC-based synchronizer. After initi- can be leveraged to reduce the synchronization time.
ating synchronization at 10s, frequency locking occurs at around Fig. 6 demonstrates synchronizer performance in the presence
17s depending on the power supplied by the synchronizer. To of the generator controls. Initially, the generator controls are
distinctly demonstrate the operation of the frequency and phase allowed to execute the synchronization, as demonstrated in Fig. 2.
controls, the phase control is activated at 20s. Once the frequency When the frequency error is low enough, the VSC based synchro-
and phase errors are reduced below the offsets defined in (1), the nizer is activated to quickly synchronize the frequency and phase.
generator breaker is closed. Fig. 5c) shows power output from the If the converter based synchronizer is activated when the
VSC in per unit during the synchronization process. It is to be frequency error is too high, the generator controls will start acting
noted that the VSC rating is kept just one percent of the generator before the synchronization is complete and will nullify the
rating. The inrush currents in Fig. 5d) are smaller than those in synchronizer action. Higher rating of the converter based synchro-
Fig. 2c) because of the active phase synchronization. nizer permits higher frequency error at which the synchronizer can
D. Operation in the Presence of Generator Controls be activated.
If the VSC-based synchronizer is used for a microgrid or if the Under both scenarios, synchronization in the presence or
generator is located far from the PCC, it may not be possible to absence of the generator controls, the rating of the VSC based
disable the generator controls during the synchronization process. synchronizer influences the synchronization speed. Relation

0885-8969 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2728718, IEEE
Transactions on Energy Conversion

60.8 60.8
60.6 60.6

60.4 60.4
f (Hz)

f (Hz)
60.2 60.2

60.0 60.0
a) 59.8 a) 59.8
0 5 10 15 20 25 30 35 40 0 20 40 60 80 100 120 140
t (s) t (s)
4 4

2 2
 (rad.)

 (rad.)
0 0

2 2
b) 4 b)
0 5 10 15 20 25 30 35 40 4
100 110 120 130 140
t (s) t (s)
 Fig. 6. Synchronization using VSC-based synchronizer in the presence of gen-
erator controls. a) frequency in Hz; dashed line is the grid frequency and solid
line is the generator frequency, b) phase error in radians. VSC-based synchro-
0.005 nizer is activated when the frequency error becomes less than 0.2 Hz.
Psyn (p.u.)


2
0.005
1
va, vga (kV)

c) 0.010 0
0 5 10 15 20 25 30 35 40 -1
t (s)
-2
1.0
Inrush Current (kA)

10.25 10.3 10.35 10.4 10.45 10.5 10.55


0.5 Offset=0 t (s)
Fig. 7. Synchronization in the presence of harmonics in grid voltages (10% 7th
 harmonic and 5% 13th harmonic). Solid line: grid voltage and dashed line: gener-
ator voltage.

0.5 phase jumps. Fig. 7 shows synchronization in the presence of 10%


7th harmonic and 5% 13th harmonic in grid voltages. It is evident
d) 1.0 that the synchronizer operation is unaffected by the harmonics.
34.5 35.0 35.5 36.0 36.5 37.0 This can be attributed to low bandwidths of the frequency and
t (s) phase control loops of the synchronizer. The grid disturbances
Fig. 5. Synchronization using VSC-based synchronizer. a) frequency in Hz; enter the synchronizer control system through SRF-PLLs used to
dashed line is the grid frequency and solid line is the generator frequency, b)
phase error in radians, c) VSC power output, and d) inrush currents during the
implement the phase detector function in Fig. 4. Hence, effects of
breaker operation. Generator controls are disabled during synchronization. grid disturbances on the synchronizer performance can be
mitigated by an appropriate PLL design [18].
between the synchronizer rating and synchronization speed is
developed in the following section. IV. CONTROL DESIGN AND SIZING

E. Operation in the Presence of Grid Disturbances A. Frequency Control Design


It is important to evaluate the synchronizer performance in Bandwidth of the VSC current control in Fig. 4 is limited by
presence of grid disturbances such as harmonics, voltage sags, and the converter switching frequency. In the simulation examples, the

0885-8969 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2728718, IEEE
Transactions on Energy Conversion

Magnitude (dB) 0 4


4
0
0 2
2
0.06 Hz 20 Hz

 (rad.)
0
0
0
50
100
90 2
-2
Phase (DEG.)

4
-4
135 10
10 20
20 30
30 40 50
50 60
60 70
70 80
80
t (s)
Fig. 9. Phase error response for different phase-control bandwidths demonstrating
180 limitation on the bandwidth imposed by the synchronizer rating. Bandwidth: 0.03
0.02 0.1 1 10 50 Hz (solid lines), 0.06 Hz (dashed lines), 0.12 Hz (dashed-dotted lines), and 0.15 Hz
Frequency (Hz) (dotted lines).
Fig. 8. Bode plot of frequency and phase control loop-gains for an ideal VSC-
based synchronizer (infinite rating). Solid lines: frequency control loop-gain;
dashed lines: phase control loop-gain. It is to be noted that the rate-of-change-of-frequency (ROCOF)
during generator synchronization may be limited to avoid
switching frequency is kept 2 kHz and the current control excessive torsional stresses. In microgrid synchronization, a high
compensator Hi(s) is designed for 200 Hz bandwidth. ROCOF may also trigger protection functions such as islanding
detection [23] and under-frequency load-shedding (UFLS) relays
For designing the frequency control compensator H(s), we
[24]. ROCOF limits are not considered in this paper; however,
need to obtain the frequency control loop-gain:
they can be easily incorporated in the synchronizer controls.
s B. Phase Control Design
L   s  = H   s   ----------------- (3)
P syn  s  For designing the phase control compensator H(s), the
frequency control dynamics can be ignored if the phase control
where the second term on the right-hand side represents transfer bandwidth is much lower than the frequency control bandwidth.
function from the synchronizer power reference Psyn to generator Under this condition, the phase control loop-gain is
frequency in rad/s. As the frequency control bandwidth is
designed much lower than the VSC current control bandwidth, the 1
active power injected by the VSC-based synchronizer can be L   s  = H   s   ------ (7)
s
considered equal to the reference Psyn.
Generator frequency (speed) dynamics can be described as where the integrator represents conversion of the frequency output
from the frequency control loop to the phase angle. Base
d 1 frequency  converts the frequency control output from p.u. to
------- = -------  P m – P e  (4)
dt 2H absolute value.
With the frequency control bandwidth of 20 Hz, the phase
where Pm and Pe are respectively the mechanical power input and
control bandwidth can be easily designed to be around 2 Hz.
the electrical power output in p.u., and H is the inertia constant in
However, Fig. 9 shows that the phase control becomes unstable
seconds. Injection of power by synchronizer is equivalent to
for bandwidths above 0.12 Hz. This is because of the finite rating
reducing the generator output power Pe by the same amount.
of the converter based synchronizer, as explained in the following
Hence, they are related in the small-signal sense as:
subsection. Hence, the phase control bandwidth is designed to be
P syn  s  = – P e  s  (5) 0.06 Hz, as shown in Fig. 8.
C. Synchronizer Rating: Effects and Control Design
Depending on the generator controls, Pm will react to any change
in the generator frequency . Hence, the loop-gain in (3) will also Cost considerations require that the VSC-based synchronizer
depend on the generator controls. If the generator controls are rating is as small as possible. However, a finite synchronizer
disabled during the synchronization process, Pm remains constant rating limits the maximum permissible bandwidth of the phase
and the following relationship is obtained using (4) and (5): control loop. Rating of the synchronizer, denoted by Pc, manifests
as saturation, as shown in Fig. 4b). Conditional integration based
s 1 anti-windup scheme is employed in the PI compensator H(s) to
----------------- = ---------- (6) avoid integration windup because of the saturation block. The
P syn  s  2Hs
anti-windup scheme stops integration whenever the output of
Frequency control compensator is designed to give bandwidth H(s) hits either of the saturation limits ±Pc and the polarity of the
of 20 Hz. Response of L(s) is shown in Fig. 8. compensator input  is the same as that of the violated limit [25].
For control design, the saturation block in Fig. 4b) can be repre-

0885-8969 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2728718, IEEE
Transactions on Energy Conversion

0 can be determined by noting that it is the same as the maximum


Magnitude (dB) 0
possible value of A. We know that the maximum phase error,
which is the input to H(s), is . Hence, A for the worst case
Pc = 1%
0 scenario can be obtained by solving the following nonlinear
2% 5% 20 Hz implicit equation:
0
0.5%
50 A H  s   H s 
--- = ---------------------------------------------------------------
- (9)
90
 
s
Phase (DEG.)

1 + H   s   N  A   -----------------
P syn  s 
3KDVH GHJ

135

The right-hand-side of (9) represents the absolute gain from  to
the output of H(s) in Fig. 4.
a) 180

0.02 0.1
 1
 10
 50 We can obtain responses of the frequency and phase control
Frequency (Hz) loop gains for different synchronizer ratings by solving (9) at each
frequency for A and using it in (8). Solid lines in Fig. 10a) and b)
20 respectively compare the frequency and phase control loop gains,
0.06 Hz
Magnitude (dB)

0 L(s) and L(s), for different synchronizer ratings. Synchronizer


ratings in Fig. 10 are represented as percentage of the total
20
generator rating. Fig. 11 validates the analytical response of the
40 Pc = 1%
2% phase control loop gain, obtained using (6), (8), and (9), against
60 5% point-by-point simulations for the synchronizer of rating of 5%.
80 0.5%
0
As the frequency control can easily track slow varying refer-
ences without the error  becoming too large to saturate the
Phase (DEG.)

90 synchronizer, the frequency and phase control loop-gain responses


180 Pc = 1% remain unaffected by the synchronizer rating at low frequencies.
2% 5%
270 0.5% In other words, the saturation effect is manifested only above a
certain critical frequency for a particular synchronizer rating (ref.
b) 360
0.02 0.1 1 10 50 Fig. 10a). It is evident from Fig. 10a) that as the VSC based
Frequency (Hz) synchronizer rating is reduced, the effective frequency control
Fig. 10. Bode plot of a) frequency-control and b) phase-control loop gains. Solid
bandwidth also gets reduced. Detailed discussion on the effects of
lines show responses for different VSC-based synchronizer ratings, represented as a saturation block on the loop-gain response can be found in [27].
the percentage of the generator rating. Dashed lines show response for the ideal To avoid instability observed in Fig. 9, the phase control
synchronizer (infinite rating).
bandwidth must be kept below the frequency at which the
frequency control loop gain L(s) starts decreasing at a fast rate
sented by its describing function [26]. Describing function of a
because of the saturation effect. This frequency, denoted by c, is
nonlinearity is its large-signal gain from a single-sinusoidal input
approximately the same as the frequency at which amplitude A of
signal to the nonlinearity output component at the input frequency.
the input signal to the saturation block becomes equal to the
Describing function of the saturation block in Fig. 4b) is [26]:
converter rating Pc. Gain of the saturation block N(A) at this point
is unity. Hence, (9) at c can be written as
1 for A  P c
 P
NA =  2 Pc 2 (8) H   j c   H   j c 
Pc Pc -----c = -------------------------------------------------------
 --- asin  ----- + ----- 1 –  ----- for A  P c . (10)
 1
 A A A 1 + H   j c   --------------------
2H  j c
where A is the amplitude of the input signal to the saturation block.
It is evident from (8) that the saturation block gain is unity Rearranging the terms in (10), we get:
whenever the output of H(s) is less than Pc. The gain starts 1
decreasing as A increases beyond Pc. This reduces the frequency H   j c   --------------------
P H   j c  2H  j c
control bandwidth. Consequently, it also requires reduction in the -----c = --------------------  ------------------------------------------------------- (11)
 1 1
phase control bandwidth to avoid interaction between the -------------------- 1 + H   j c   --------------------
2H  j c 2H  j c
frequency and phase control loops.
Even after knowing the amplitude dependent gain of the
The term in the second set of brackets in (11) represents the
saturation block, it is not possible to obtain responses of the
frequency-control closed loop gain without considering the
frequency and phase control loop-gains. This is because the
saturation effects. As c is well below the designed frequency-
amplitude A is unknown. However, the worst case amplitude A
control bandwidth, which is 20 Hz in the case studies presented

0885-8969 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2728718, IEEE
Transactions on Energy Conversion

20 bandwidth must be limited to 0.06 Hz. However, Fig. 10a) shows


Phase (DEG.) Magnitude (dB) 0 that the phase control bandwidth must be below 0.12 Hz for
20 stability under the same conditions, which is also verified by
simulations in Fig. 9. The discrepancy is because we assumed that
40
the loop gain starts decreasing rapidly right after the amplitude A
60
hits the synchronizer rating Pc. However, the loop gain initially
80
0 decreases only gradually before decreasing rapidly to a low value
90 (refer Fig. 10a). Nonetheless, the condition in (15) can be used as a
thumb rule, leading only to a slightly conservative design.
180
270 D. Synchronizer Performance and Rating
360 This subsection relates the time required for synchronization
0.02 0.1 1 10 50 with the synchronizer rating. If the frequency difference between
Frequency (Hz) the generator and grid is f, the energy that needs to be exchanged
Fig. 11. Verification of the phase-control loop gain model. Solid lines show model with the generator to eliminate the frequency error is
response for synchronizer rating of 5%, circles show response obtained by point-
by-point simulations, and dashed lines show response for the ideal synchronizer. 1 2 2 2
E = --- J    2  f ref  –  2  f    4 J  f 1  f . (16)
2
here, the term in the second set of brackets is approximately equal where J is generator mechanical inertia in kg·m2. It is related with
to unity at c. Hence, (11) simplifies to the inertia constant H as:
P 2H  P base
-----c = 2H  j c  H   j c  . (12) J = -----------------------
- (17)
 2
1
Assuming that H(s) is realized by a PI compensator with the
zero located at the phase control bandwidth  for achieving 45o Time required for synchronizer of rating Pc to exchange energy
phase margin, using (7), we get: E from (16) is given by

s - E
 1 + ----- T  = ------------------------ . (18)

2
    P c  P base
H   s  =  ------------------  ---------------- (13)
  1  2  s  Time required for phase locking depends on the phase control
 
bandwidth . The phase-control loop forms a second-order
Gain in (13) ensures that the magnitude of the phase control loop system with the damping ratio  of 0.42 for the designed phase-
gain L(s) is unity at . margin of 45o. Moreover, its natural frequency is approximately
Using (12) and (13), the critical frequency c can be deter- the same as the bandwidth . Hence, the settling time of the
mined as: phase-control loop is given by:

4 4 H
2 f 1  P c 2 T   ----------  --- -------------- . (19)
c = ---------   -------------
- – 2 (14)    f  P c
2  H  1

Sum of the frequency and phase locking times from (18) and
As phase of the loop-gain Ls decreases rapidly above c (19) gives the total synchronization time. It is evident that a lower
(ref. Fig. 10b), the phase-control bandwidth must be kept lower rating of the synchronizer increases the time required for the
than the critical frequency c to ensure sufficient phase margin. synchronization process. Hence, there is a trade-off between the
Using (14), this condition simplifies to: synchronizer rating and speed of the synchronization process.
The PLL structure avoids unstable interaction between the
f1  Pc frequency and phase control loops. It is not necessary to achieve
  (in rad./s)  -------------
- (15)
H the frequency and phase locking sequentially as required in the
existing methods [12]. Simultaneous frequency and phase
It is interesting to note that the limit on the phase control
synchronization results in total synchronization time to be lower
bandwidth is directly related to the synchronizer rating. Moreover,
than that predicted by (18) and (19). For f of 0.5 Hz and param-
it is independent of the frequency control bandwidth. This is
eters from Appendix, the frequency and phase locking times from
expected, as the frequency control bandwidth is usually much
(18) and (19) are respectively 6.16s and 23.65s, predicting the
higher than the frequency range at which the saturation effect is
total synchronization time of around 30s. Fig. 12 shows that the
manifested (refer Fig. 10).
synchronization is achieved in 22s after the frequency and phase
For H = 3.7s and P c = 1% , using (15), the phase control

0885-8969 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2728718, IEEE
Transactions on Energy Conversion

60.8 TABLE I GENERATOR PARAMETERS


60.6 Parameter Value
60.4
f (Hz)

Rating, Pbase 550 MVA


60.2 Rated output voltage (rms), Vl-l 24 kV
Nominal frequency, f1 60 Hz
60.0
Stator resistance, Rs 3.1 m
a) 59.8 Stator leakage inductance, Ll 0.413 mH
0 5 10 15 20 25 30 35
t (s) d-axis magnetizing inductance, Lmd 4.569 mH
4 q-axis magnetizing inductance, Lmq 4.432 mH
2 Field winding resistance, Rf 0.0715 
 (rad.)

Field winding self inductance, Lffd 576.92 mH


0 Inertia constant, H 3.7 s
Number of poles 2
2
Transmission line inductance, Lline 0 to 1.1 mH
b) 4 0 5 10 15 20 25 30 35 Synchronization compensator, Hsyn(s) 0.01 + 0.008/s
t (s)
Fig. 12.Simultaneous operation of the frequency and phase control loops. Syn-
chronization is achieved in 22s. This paper reviewed existing methods for the synchronization
of generators and microgrids with an electric power system. It
control loops are activated together at t = 10s. showed that the existing methods rely on generator controls and
the phase synchronization is usually achieved in a passive manner.
E. Microgrid Synchronization This results in slow synchronization and long interconnection
Fundamental to the operation of the VSC-based synchronizer is time. It may also lead to a faulty synchronization, as a zero phase
that the frequency at the PCC of the generator or microgrid to be error cannot be ensured during the generator breaker operation.
synchronized is sensitive to the active power output of the Another problem is the lack of design framework to avoid inter-
synchronizer. This is given for a synchronous generator and the action between the frequency and phase synchronization, when
sensitivity is captured in (4). Such sensitivity is also present in the latter is achieved in an active manner. To address these
microgrids with high penetration of synchronous machine based problems, this paper framed the generator and microgrid synchro-
distributed generators. In such scenario, the transfer function from nization problem as a PLL design problem. A VSC-based active
the synchronizer power reference Psyn to frequency  at the PCC synchronizer is introduced to implement the PLL based synchro-
is dependent on the aggregated inertia in the microgrid. For nization method. Using detailed simulations for a synchronous
microgrids with high penetration of converter based generators, generator, it is shown that the proposed synchronizer can reduce
however, the sensitivity of frequency towards active power flow is the synchronization time by an order of magnitude, even when it is
required to be emulated by controls. Most converter based rated less than one percent of the generator rating.
microgrids use droop control for power sharing and hence the
microgrid frequency is dependent on the active power flow. It is APPENDIX
important to obtain the frequency response of the transfer function
from Psyn to  using measurements or modeling for designing the Parameters from Table I and II are used respectively for the
VSC-based synchronizer controls for such microgrids. synchronous generator and the VSC-based synchronizer.
Additional dynamic present in microgrids is the line imped-
REFERENCES
ances between the distributed generators and between the
microgrid and synchronizer. The frequency and phase synchroni- [1] R. D. Evans, F. H. Gullisken, and C. B. Myhre, “Synchronizing transients
zation dynamics are much slower than the electromagnetic and synchronizers for large machines” AIEEE, vol. 59, no. 12, pp. 965-
972, 1940.
dynamics introduced by transmission lines. Hence, they can be
[2] D. L. Ransom, “Get in step with synchronization,” IEEE Trans. Ind.
ignored in the synchronizer design. It is verified that even for a Appl., vol. 50, no. 6, pp. 4210-4215, Nov./Dec. 2014.
large variation in the transmission line inductance Lline between [3] J. C. Maters, “Method of synchronizing a turbomachine generator to an
the generator and PCC in Fig. 4, the phase and frequency response electric grid,” US Patent 7 915 868 B1, Mar. 29, 2011.
during synchronization remains unaffected. The variation of the [4] R. Hug and R. Luthi, “Method for synchronising a generator with a grid,”
EP Patent 2 651 000 A2, Oct. 16 2013 (in German).
transmission line inductance considered in simulations is given in
[5] Y Han, S. G. Cai, and F. Y. Jie, “A fast following synchronizer of gener-
Table I; the maximum value of Lline corresponds to grid short- ators,” IEEE Trans. Energy Conv., vol. 3, no. 4, pp. 765-769, Dec. 1988.
circuit ratio of as low as 2.5. [6] B. M. Pasternack, J. H. Provanzana, and L. B. Wagenaar, “Analysis of a
generator step-up transformer failure following faulty synchronization,”
V. CONCLUSIONS IEEE Trans. Power Del., vol. 3, no. 3, pp. 1051-1058, July 1988.

0885-8969 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2728718, IEEE
Transactions on Energy Conversion

TABLE II VSC-BASED SYNCHRONIZER PARAMETERS tional islanding based on remote sensing of voltage and frequency
signals,” IEEE Trans. Smart Grid, vol. 3, no. 4, pp. 1877-1884, Dec.
Parameter Value 2012.
[14] Y. Li, D. M. Vilathgamuwa, and P. C. Loh, “Design, analysis, and real-
VSC rating, Pc 0.01 p.u. (5.5 MVA) time testing of a controller for multibus microgrid system,” IEEE Trans.
Rated output voltage (rms), Vl-l 24 kV Power Electron., vol. 19, no. 5, pp. 1195-1204, Sep. 2004.
DC-bus Voltage, Vdc [15] S. D’Arco and J. A. Suul, “A synchronization controller for grid recon-
48 kV
nection of islanded virtual synchronous machines,” in 2015 IEEE 6th Int.
Phase reactor inductance, Lph 45.0 mH Symp. Power Electron. Distributed Generation Syst. (PEDG), June 2015.
Phase reactor resistance, Rph 2.3  [16] T. L. Vandoorn, B. Meersman, J. D. M. D. Kooning, and L. Vandevelde,
“Transition from islanded to grid-connected mode of microgrids with
Current control compensator, Hi(s) (2/Vdc)·(40 + 50x104/s) voltage-based droop control,” IEEE Trans. Power Syst., vol. 28, no. 3, pp.
Decoupling gain, kd (2/Vdc)·2f1Lph 2545-2553, Aug. 2013.
[17] A. Miscallef, M. Apap, C. S. Staines, J. M. Guerrero, “Single-phase
Frequency control compensator, H(s) 657.5 + 8.26x104/s
microgrid with seamless transition capabilities between modes of
Phase control bandwidth,  2·0.06 rad/s operation,” IEEE Trans. Smart Grid, vol. 6, no. 6, pp. 2736-2745, Nov.
Phase control compensator, H(s) (7.07+ 2.66/s)x104 2015.
[18] R. Teodorescu, M. Liserre, and P. Rodriguez, Grid Converters for Photo-
Switching frequency, fsw 2 kHz
voltaic and Wind Power Systems. Chichester, UK: Wiley, 2011.
[19] R. E. Best, Phase-Locked Loops: Design, Simulation, and Applications.
[7] J. M. Guerrero, J. C. Vasquez, J. Matas, L. G. de Vicuna, and M. Castilla, 6th Ed., McGraw-Hill, 2007.
“Hierarchical control of droop-controlled ac and dc microgrids – a [20] P. Kundur, Power System Stability and Control. New York: McGraw-Hill,
general approach toward standardization,” IEEE Trans. Ind. Electron., 1994.
vol. 58, no. 1, pp. 158-172, Jan. 2011. [21] A. Pikovsky, M. Rosenblum, and J. Kurths, Synchronization: A universal
[8] A. Bidram and A. Davoudi, “Hierarchical structure of microgrids control concept in nonlinear science. Cambridge Uni. Press, 2001.
system,” IEEE Trans. Smart Grid, vol. 3, no. 4, pp. 1963-1976, Dec. [22] G. Cavazzini and J. I. Perez-Diaz, “Technological developments for
2012. pumped-hydro energy storage,” Technical Report, European Energy
[9] A. Bellini, S. Bifaretti, and F. Giannini, “A robust synchronization Research Alliance, May 2014.
method in centralized microgrids” IEEE Trans. Ind. Appl., vol. 51, no. 2, [23] P. Gupta, R. S. Bhatia, and D. K. Jain, “Active ROCOF relay for
pp. 1602-1609, Mar./April 2015. islanding detection,” IEEE Trans. Power Del., vol. 32, no. 1, pp. 420-429,
[10] R. J. Best, J. Morrow, D. M. Laverty, and P. A. Crossley, “Synchrophasor Feb. 2017.
broadcast over internet protocol for distributed generator synchroni- [24] L. Sigrist, “A UFLS scheme for small isolated power systems using rate-
zation,” IEEE Trans. Power Del., vol. 25, no. 4, pp. 2835-2841, Oct. of-change of frequency,” IEEE Trans. Power Del., vol. 30, no. 4, pp.
2010. 2192-2193, July 2015.
[11] C. Ahumada, R. Cardenas, D. Saez, and J. M. Guerrero, “Secondary [25] K. J. Astrom and T. Hagglund, Advanced PID Control. ISA - Instrumen-
control strategies for frequency restoration in islanded microgrids with tation, Syst., and Appl. Soc., 2006.
consideration of communication delays,” IEEE Trans. Smart Grid, vol. 7, [26] A. Gelb and W. E. Vander Velde, Multiple-input Describing Functions
no. 3, May 2016. and Nonlinear System Design. New York, NY: McGraw-Hill, 1968.
[12] C. Cho, J-H. Jeon, J-Y. Kim, S. Kwon, K. Park, and S. Kim, “Active [27] A. S. McAllister, “A graphical method for finding the frequency response
synchronization control of a microgrid,” IEEE Trans. Power Electron., of nonlinear closed-loop systems,” AIEEE Trans. Part II: Appl. and Ind.,
vol. 26, no. 12, pp. 3707-3719, Dec. 2011. vol. 80, no. 55, pp. 268-277, 1961.
[13] T. M. L. Assis and G. N. Taranto, “Automatic reconnection from inten-

0885-8969 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.

You might also like