Professional Documents
Culture Documents
fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2728718, IEEE
Transactions on Energy Conversion
AbstractFast synchronization of generators and microgrids the generator and power system [2, 3]. This makes the intercon-
will be a critical technology in future power systems with high nection time highly variable and dependent on the initial phase
penetration of non-dispatchable power resources. Existing
error and frequency offset. Higher frequency offset can reduce the
synchronization methods rely on generator controls and their
performance is limited by the generator characteristics. Speed of phase-locking time [2], but results in a larger disturbances during
microgrid synchronization is further limited by the communi- interconnection. Active phase synchronization has been proposed
cation link among generation units. These factors lead to a slow in [5] by adding a term depending on the phase error to the
and sometimes faulty synchronization, predominantly because of generator frequency control loop. However, it is necessary to
the phase mismatch during interconnection. This paper frames
design the phase control much slower than the frequency control
the generator synchronization problem as a phase-locked loop
(PLL) design problem and introduces a voltage-source converter to avoid unstable interaction between them. The frequency control
(VSC) based synchronizer for implementing the PLL based active of generators is already very slow and the above requirement
synchronization method. The VSC based synchronizer is results in even slower phase synchronization. Hence, active phase
connected at the point of common coupling and it relies only on synchronization based on the generator controls gives little
local measurements for control. It ensures zero phase error
advantage over the passive phase synchronization approach.
during interconnection by taking the advantage of the fact that
the phase is not regulated in the generator controls. Relation Phase synchronization is more critical than the voltage and
between the synchronizer rating, control design, and synchroni- frequency synchronization for reducing the inrush currents [1].
zation speed is developed using describing function analysis of Unreliable phase synchronization and indeterminate breaker
frequency and phase control loop gains. The operation and operation time may lead to an out-of-phase synchronization and
performance of the VSC-based synchronizer is demonstrated
generator damage [6].
using simulations for a 555 MVA, 24 kV synchronous generator.
Synchronization of microgrids is achieved in a similar manner
Index TermsSynchronization, microgrid control, distributed as synchronous generators and suffers the same problems.
generators, automatic synchronizer. Additionally, as the synchronization parameters at the PCC of a
microgrid depend on several distributed generators, the synchroni-
I. INTRODUCTION
zation function is implemented in the secondary control [7, 8].
With the increasing penetration of non-dispatchable renewable Hence, the microgrid synchronization speed is further limited by
energy resources in power systems, it is becoming important to be the communication system of the secondary control [9-12]. Same
able to quickly dispatch generation units whenever demanded by as synchronous generators, the phase synchronization in
the load dispatch centers. Before a generator can be connected to a microgrids is achieved either passively [13] or by introducing a
power system, the frequency, phase, and amplitude of the voltages correction term, depending on the phase error, in the microgrid
at its bus need to be matched with those of the power system at the frequency control loop [14-17]. However, phase being an ac
point of common coupling (PCC) [1, 2]. Hence, fast synchroni- variable unlike the voltage and frequency magnitudes, phase
zation is critical to reduce the interconnection time. synchronization performance is particularly limited by the
Synchronization of conventional generators is achieved communication speed when achieved by distributed generator
through generator controls, including the frequency and voltage controls.
control [2-4]. The generator controls are structured into hierar- The above discussion highlights two problems: 1) control
chical levels including primary, secondary, and tertiary level design framework to avoid interaction between the frequency and
controls. Secondary control is implemented at a central location phase synchronization of generators and microgrids is not studied
and it communicates references to the primary control of (this is important because of the discontinuous nature of the phase
geographically distributed generators. Generator synchronization error); and 2) achieving fast synchronization, particularly the
is achieved locally in the primary control [2-4]. Fast synchroni- phase synchronization, is challenging when implemented through
zation, however, is difficult using the existing method as the generator controls. This paper addresses the above problems by
primary control bandwidth is limited by the generator character- framing the generator and microgrid synchronization problem as a
istics, e.g. mechanical inertia. Moreover, the phase synchroni- phase-locked loop (PLL) design problem and introducing a VSC-
zation is usually achieved passively by a frequency offset between based synchronizer at the PCC of the generator or microgrid to be
synchronized. The proposed VSC-based synchronizer relies only
S. Shah is with Rensselaer Polytechnic Institute, Troy, NY 12180 USA (email:
shahs12@rpi.edu). on local measurements and actively regulates the phase angle of
H. Sun, D. Nikovski, and J. Zhang are with Mitsubishi Electric Research the incoming generator or microgrid. Hence, zero phase error can
Laboratories, Cambridge, MA 02139, USA (e-mail: hongbosun@merl.com; be maintained during the breaker operation. Control system of the
nikovski@merl.com; jzhang@merl.com) synchronizer is implemented using a phase-locked-loop (PLL)
0885-8969 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2728718, IEEE
Transactions on Energy Conversion
structure [18, 19], in which the generator or microgrid to be input power Pm to the generator to eliminate the frequency error.
synchronized is treated as an oscillator. The PLL structure The voltage amplitude is similarly synchronized by modulating
provides a design framework for avoiding interaction between the the input voltage to the field windings of the generator (Efd). The
frequency and phase control loops. Relation between the synchro- phase synchronization is achieved by a frequency offset between
nizer rating, control design, and synchronization speed is the generator and grid frequencies. Because of the frequency
presented using describing function analysis. It is shown that the difference, the phase error keeps on changing with time. Once the
proposed synchronizer can reduce the synchronization time by an frequency, phase, and voltage errors come within stipulated limits,
order of magnitude, even when it is rated at less than one percent usually referred as synchronization window [2], the generator
of the generator rating. Operation and design principles of the breaker is closed.
VSC-based synchronizer are demonstrated using detailed simula- This paper focusses on the frequency and phase synchroni-
tions of a 555 MVA, 24 kV synchronous generator. zation and assumes that the voltage levels are always synchro-
The rest of the paper is organized as follows: Section II reviews nized because of the following reasons: i) voltage control can be
the existing synchronization method using generator controls. easily achieved by field current (generators) or reactive power
Section III frames the generator synchronization problem as a (microgrids) control, ii) voltage control does not involve conflict
PLL design problem and introduces a VSC-based synchronizer as in the frequency and phase control, and iii) the voltage
for achieving fast synchronization. Control design, sizing, and matching requirement is much less important for a smooth
performance evaluation of the synchronizer are presented in synchronization than the frequency and phase matching require-
Section IV. Section V concludes this paper. ments [1, 2].
The above discussed synchronization process is demonstrated
II. SYNCHRONIZATION USING GENERATOR CONTROLS in Fig. 2 for a 555 MVA, 24 kV generator. Generator parameters
Fig. 1 illustrates existing method of synchronization using are taken from example 3.1 and 3.2 in [20]. Major parameters are
generator controls [3-8]. In this method, the frequency and also provided in the appendix. Fig. 2a) and b) respectively show
amplitude of the generator output voltages are slowly brought to the frequency and phase synchronization. Fig. 2c) shows inrush
the grid frequency and voltage levels using the primary control of currents after closing of the generator breaker. It is to be noted that
the generator. When the synchronization process is initiated, the because of the synchronization process before the breaker
error between the generator and grid frequencies is processed operation, the peak inrush current is much lower than the
by a synchronization controller, as shown in Fig. 1c). Based on the generator peak rating current of 18.67 kA. The generator breaker
controller output, the primary control modulates the mechanical is closed when the frequency and phase errors are within the
following limits [2]:
Pm o
f 0.05 Hz , 0.5 (1)
Generator
Controls Because of the slow bandwidth of the synchronization control
Efd loop with the time constant of 120s, the synchronization process
Generator 3- Grid takes around 300s.
Synchronous
Generator
Breaker Microgrid synchronization is achieved in a similar manner,
a) except for the fact that the synchronization controller implemented
at a remote location in the secondary control.
Pe, ref
Pe III. VSC-BASED ACTIVE SYNCHRONIZER
_
In steady-state A. PLL Based Active Synchronization
= pri + R p P e, ref – P e
Rp Generator or microgrid and main power system can be
considered as two self-sustained oscillators that need to be
pri Pm synchronized. Hence, methods for the synchronization of oscil-
_ Servo Hydraulic
Hpri(s) lators [21] can be applied for generator synchronization. With
Motor Turbine
Gate Opening generator treated as an oscillator, its synchronization problem can
b) Limit be formulated as a phase-locked loop (PLL) design problem. The
PLL structure allows simultaneous control of frequency and phase
without conflict.
sec A PLL consists of three components: phase detector, loop
ref pri filter, and internal oscillator [18], as shown in Fig. 3. Phase
_ Hsyn(s)
detector estimates error between the phases of an external signal
c) and internal oscillator. The output of the phase detector is passed
Fig. 1. Synchronization using generator controls. a) generator to be connected through a loop filter to remove high frequency components. The
with the grid, b) primary control and c) synchronization control of the generator.
0885-8969 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2728718, IEEE
Transactions on Energy Conversion
B. VSC-based Synchronizer
60.2
The PLL based synchronization is realized using a two-level
voltage source converter (VSC) based synchronizer. The VSC-
60.0 based synchronizer is connected at the PCC of a generator or
a) microgrid to be synchronized. Synchronizer operation and design
0 50 100 150 200 250 300 350 are demonstrated for a synchronous generator. Synchronizer will
t (s)
have similar performance for microgrids with high penetration of
4
synchronous machine based generators. Possible issues that may
arise in microgrids with high penetration of converter based gener-
2 ators are discussed in the following section.
(rad.)
0885-8969 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2728718, IEEE
Transactions on Energy Conversion
Lline va vga
Pm
Generator vb vgb
Controls vc vgc
Efd
Generator Main Grid
Synchronous Local PLL PLL
Breaker
Generator Loads ib ic
ia
vd ref ref vd, ref
L
va vd 1
abc
idr vb
Psyn
Pbase 23
ma
dq-Current mb
vc dq v HPLL(s)
q
PWM
Control mc
0 c)
iqr
vd
vdc idr md
_ Hi(s)
_
_
+
a)
id
ia 1L ma
abc dq
ref ib mb
ref Psyn dq abc
ic 1L mc
_ H(s) _ H(s) q i
_
VSC Rating Pc
iqr Hi(s) m
q
b) d)
Fig. 4. Active synchronization of generator. a) Synchronous generator with VSC-based synchronizer, b) frequency and phase synchronization control implementation, c)
phase-locked loop (PLL), and d) VSC ac current control in the dq-domain.
controlling the output current iabc using dq-domain current control Under such scenario, the generator controls may counteract the
shown in Fig. 4d). It is to be noted that overline indicates per unit synchronizer action because of the mismatch in their operation
(p.u.) values. Unless stated otherwise, parameters from appendix speeds. For example, when the synchronizer tries to increase the
are used for the synchronizer. generator frequency by injecting power at the PCC, as in Fig. 5a),
the generator controls will try to maintain the frequency by
C. Operation in the Absence of Generator Controls
reducing the power input Pm to the generator. Hence, after initial
To avoid conflict between the generator controls and the VSC buildup in the frequency because of the synchronizer, it will return
based synchronizer, the generator controls are disabled during the to the trajectory that is followed when synchronization is achieved
synchronization process. This is realized by freezing Pm and Efd only by the generator controls. Nonetheless, difference between
(ref. Fig. 4) during the synchronization process. Fig. 5 demon- the speeds of the VSC-based synchronizer and generator controls
strates the operation of the VSC-based synchronizer. After initi- can be leveraged to reduce the synchronization time.
ating synchronization at 10s, frequency locking occurs at around Fig. 6 demonstrates synchronizer performance in the presence
17s depending on the power supplied by the synchronizer. To of the generator controls. Initially, the generator controls are
distinctly demonstrate the operation of the frequency and phase allowed to execute the synchronization, as demonstrated in Fig. 2.
controls, the phase control is activated at 20s. Once the frequency When the frequency error is low enough, the VSC based synchro-
and phase errors are reduced below the offsets defined in (1), the nizer is activated to quickly synchronize the frequency and phase.
generator breaker is closed. Fig. 5c) shows power output from the If the converter based synchronizer is activated when the
VSC in per unit during the synchronization process. It is to be frequency error is too high, the generator controls will start acting
noted that the VSC rating is kept just one percent of the generator before the synchronization is complete and will nullify the
rating. The inrush currents in Fig. 5d) are smaller than those in synchronizer action. Higher rating of the converter based synchro-
Fig. 2c) because of the active phase synchronization. nizer permits higher frequency error at which the synchronizer can
D. Operation in the Presence of Generator Controls be activated.
If the VSC-based synchronizer is used for a microgrid or if the Under both scenarios, synchronization in the presence or
generator is located far from the PCC, it may not be possible to absence of the generator controls, the rating of the VSC based
disable the generator controls during the synchronization process. synchronizer influences the synchronization speed. Relation
0885-8969 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2728718, IEEE
Transactions on Energy Conversion
60.8 60.8
60.6 60.6
60.4 60.4
f (Hz)
f (Hz)
60.2 60.2
60.0 60.0
a) 59.8 a) 59.8
0 5 10 15 20 25 30 35 40 0 20 40 60 80 100 120 140
t (s) t (s)
4 4
2 2
(rad.)
(rad.)
0 0
2 2
b) 4 b)
0 5 10 15 20 25 30 35 40 4
100 110 120 130 140
t (s) t (s)
Fig. 6. Synchronization using VSC-based synchronizer in the presence of gen-
erator controls. a) frequency in Hz; dashed line is the grid frequency and solid
line is the generator frequency, b) phase error in radians. VSC-based synchro-
0.005 nizer is activated when the frequency error becomes less than 0.2 Hz.
Psyn (p.u.)
2
0.005
1
va, vga (kV)
c) 0.010 0
0 5 10 15 20 25 30 35 40 -1
t (s)
-2
1.0
Inrush Current (kA)
0885-8969 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2728718, IEEE
Transactions on Energy Conversion
(rad.)
0
0
0
50
100
90 2
-2
Phase (DEG.)
4
-4
135 10
10 20
20 30
30 40 50
50 60
60 70
70 80
80
t (s)
Fig. 9. Phase error response for different phase-control bandwidths demonstrating
180 limitation on the bandwidth imposed by the synchronizer rating. Bandwidth: 0.03
0.02 0.1 1 10 50 Hz (solid lines), 0.06 Hz (dashed lines), 0.12 Hz (dashed-dotted lines), and 0.15 Hz
Frequency (Hz) (dotted lines).
Fig. 8. Bode plot of frequency and phase control loop-gains for an ideal VSC-
based synchronizer (infinite rating). Solid lines: frequency control loop-gain;
dashed lines: phase control loop-gain. It is to be noted that the rate-of-change-of-frequency (ROCOF)
during generator synchronization may be limited to avoid
switching frequency is kept 2 kHz and the current control excessive torsional stresses. In microgrid synchronization, a high
compensator Hi(s) is designed for 200 Hz bandwidth. ROCOF may also trigger protection functions such as islanding
detection [23] and under-frequency load-shedding (UFLS) relays
For designing the frequency control compensator H(s), we
[24]. ROCOF limits are not considered in this paper; however,
need to obtain the frequency control loop-gain:
they can be easily incorporated in the synchronizer controls.
s B. Phase Control Design
L s = H s ----------------- (3)
P syn s For designing the phase control compensator H(s), the
frequency control dynamics can be ignored if the phase control
where the second term on the right-hand side represents transfer bandwidth is much lower than the frequency control bandwidth.
function from the synchronizer power reference Psyn to generator Under this condition, the phase control loop-gain is
frequency in rad/s. As the frequency control bandwidth is
designed much lower than the VSC current control bandwidth, the 1
active power injected by the VSC-based synchronizer can be L s = H s ------ (7)
s
considered equal to the reference Psyn.
Generator frequency (speed) dynamics can be described as where the integrator represents conversion of the frequency output
from the frequency control loop to the phase angle. Base
d 1 frequency converts the frequency control output from p.u. to
------- = ------- P m – P e (4)
dt 2H absolute value.
With the frequency control bandwidth of 20 Hz, the phase
where Pm and Pe are respectively the mechanical power input and
control bandwidth can be easily designed to be around 2 Hz.
the electrical power output in p.u., and H is the inertia constant in
However, Fig. 9 shows that the phase control becomes unstable
seconds. Injection of power by synchronizer is equivalent to
for bandwidths above 0.12 Hz. This is because of the finite rating
reducing the generator output power Pe by the same amount.
of the converter based synchronizer, as explained in the following
Hence, they are related in the small-signal sense as:
subsection. Hence, the phase control bandwidth is designed to be
P syn s = – P e s (5) 0.06 Hz, as shown in Fig. 8.
C. Synchronizer Rating: Effects and Control Design
Depending on the generator controls, Pm will react to any change
in the generator frequency . Hence, the loop-gain in (3) will also Cost considerations require that the VSC-based synchronizer
depend on the generator controls. If the generator controls are rating is as small as possible. However, a finite synchronizer
disabled during the synchronization process, Pm remains constant rating limits the maximum permissible bandwidth of the phase
and the following relationship is obtained using (4) and (5): control loop. Rating of the synchronizer, denoted by Pc, manifests
as saturation, as shown in Fig. 4b). Conditional integration based
s 1 anti-windup scheme is employed in the PI compensator H(s) to
----------------- = ---------- (6) avoid integration windup because of the saturation block. The
P syn s 2Hs
anti-windup scheme stops integration whenever the output of
Frequency control compensator is designed to give bandwidth H(s) hits either of the saturation limits ±Pc and the polarity of the
of 20 Hz. Response of L(s) is shown in Fig. 8. compensator input is the same as that of the violated limit [25].
For control design, the saturation block in Fig. 4b) can be repre-
0885-8969 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2728718, IEEE
Transactions on Energy Conversion
1 + H s N A -----------------
P syn s
3KDVHGHJ
135
The right-hand-side of (9) represents the absolute gain from to
the output of H(s) in Fig. 4.
a) 180
0.02 0.1
1
10
50 We can obtain responses of the frequency and phase control
Frequency (Hz) loop gains for different synchronizer ratings by solving (9) at each
frequency for A and using it in (8). Solid lines in Fig. 10a) and b)
20 respectively compare the frequency and phase control loop gains,
0.06 Hz
Magnitude (dB)
0885-8969 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2728718, IEEE
Transactions on Energy Conversion
s - E
1 + ----- T = ------------------------ . (18)
2
P c P base
H s = ------------------ ---------------- (13)
1 2 s Time required for phase locking depends on the phase control
bandwidth . The phase-control loop forms a second-order
Gain in (13) ensures that the magnitude of the phase control loop system with the damping ratio of 0.42 for the designed phase-
gain L(s) is unity at . margin of 45o. Moreover, its natural frequency is approximately
Using (12) and (13), the critical frequency c can be deter- the same as the bandwidth . Hence, the settling time of the
mined as: phase-control loop is given by:
4 4 H
2 f 1 P c 2 T ---------- --- -------------- . (19)
c = --------- -------------
- – 2 (14) f P c
2 H 1
Sum of the frequency and phase locking times from (18) and
As phase of the loop-gain Ls decreases rapidly above c (19) gives the total synchronization time. It is evident that a lower
(ref. Fig. 10b), the phase-control bandwidth must be kept lower rating of the synchronizer increases the time required for the
than the critical frequency c to ensure sufficient phase margin. synchronization process. Hence, there is a trade-off between the
Using (14), this condition simplifies to: synchronizer rating and speed of the synchronization process.
The PLL structure avoids unstable interaction between the
f1 Pc frequency and phase control loops. It is not necessary to achieve
(in rad./s) -------------
- (15)
H the frequency and phase locking sequentially as required in the
existing methods [12]. Simultaneous frequency and phase
It is interesting to note that the limit on the phase control
synchronization results in total synchronization time to be lower
bandwidth is directly related to the synchronizer rating. Moreover,
than that predicted by (18) and (19). For f of 0.5 Hz and param-
it is independent of the frequency control bandwidth. This is
eters from Appendix, the frequency and phase locking times from
expected, as the frequency control bandwidth is usually much
(18) and (19) are respectively 6.16s and 23.65s, predicting the
higher than the frequency range at which the saturation effect is
total synchronization time of around 30s. Fig. 12 shows that the
manifested (refer Fig. 10).
synchronization is achieved in 22s after the frequency and phase
For H = 3.7s and P c = 1% , using (15), the phase control
0885-8969 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2728718, IEEE
Transactions on Energy Conversion
0885-8969 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2728718, IEEE
Transactions on Energy Conversion
TABLE II VSC-BASED SYNCHRONIZER PARAMETERS tional islanding based on remote sensing of voltage and frequency
signals,” IEEE Trans. Smart Grid, vol. 3, no. 4, pp. 1877-1884, Dec.
Parameter Value 2012.
[14] Y. Li, D. M. Vilathgamuwa, and P. C. Loh, “Design, analysis, and real-
VSC rating, Pc 0.01 p.u. (5.5 MVA) time testing of a controller for multibus microgrid system,” IEEE Trans.
Rated output voltage (rms), Vl-l 24 kV Power Electron., vol. 19, no. 5, pp. 1195-1204, Sep. 2004.
DC-bus Voltage, Vdc [15] S. D’Arco and J. A. Suul, “A synchronization controller for grid recon-
48 kV
nection of islanded virtual synchronous machines,” in 2015 IEEE 6th Int.
Phase reactor inductance, Lph 45.0 mH Symp. Power Electron. Distributed Generation Syst. (PEDG), June 2015.
Phase reactor resistance, Rph 2.3 [16] T. L. Vandoorn, B. Meersman, J. D. M. D. Kooning, and L. Vandevelde,
“Transition from islanded to grid-connected mode of microgrids with
Current control compensator, Hi(s) (2/Vdc)·(40 + 50x104/s) voltage-based droop control,” IEEE Trans. Power Syst., vol. 28, no. 3, pp.
Decoupling gain, kd (2/Vdc)·2f1Lph 2545-2553, Aug. 2013.
[17] A. Miscallef, M. Apap, C. S. Staines, J. M. Guerrero, “Single-phase
Frequency control compensator, H(s) 657.5 + 8.26x104/s
microgrid with seamless transition capabilities between modes of
Phase control bandwidth, 2·0.06 rad/s operation,” IEEE Trans. Smart Grid, vol. 6, no. 6, pp. 2736-2745, Nov.
Phase control compensator, H(s) (7.07+ 2.66/s)x104 2015.
[18] R. Teodorescu, M. Liserre, and P. Rodriguez, Grid Converters for Photo-
Switching frequency, fsw 2 kHz
voltaic and Wind Power Systems. Chichester, UK: Wiley, 2011.
[19] R. E. Best, Phase-Locked Loops: Design, Simulation, and Applications.
[7] J. M. Guerrero, J. C. Vasquez, J. Matas, L. G. de Vicuna, and M. Castilla, 6th Ed., McGraw-Hill, 2007.
“Hierarchical control of droop-controlled ac and dc microgrids – a [20] P. Kundur, Power System Stability and Control. New York: McGraw-Hill,
general approach toward standardization,” IEEE Trans. Ind. Electron., 1994.
vol. 58, no. 1, pp. 158-172, Jan. 2011. [21] A. Pikovsky, M. Rosenblum, and J. Kurths, Synchronization: A universal
[8] A. Bidram and A. Davoudi, “Hierarchical structure of microgrids control concept in nonlinear science. Cambridge Uni. Press, 2001.
system,” IEEE Trans. Smart Grid, vol. 3, no. 4, pp. 1963-1976, Dec. [22] G. Cavazzini and J. I. Perez-Diaz, “Technological developments for
2012. pumped-hydro energy storage,” Technical Report, European Energy
[9] A. Bellini, S. Bifaretti, and F. Giannini, “A robust synchronization Research Alliance, May 2014.
method in centralized microgrids” IEEE Trans. Ind. Appl., vol. 51, no. 2, [23] P. Gupta, R. S. Bhatia, and D. K. Jain, “Active ROCOF relay for
pp. 1602-1609, Mar./April 2015. islanding detection,” IEEE Trans. Power Del., vol. 32, no. 1, pp. 420-429,
[10] R. J. Best, J. Morrow, D. M. Laverty, and P. A. Crossley, “Synchrophasor Feb. 2017.
broadcast over internet protocol for distributed generator synchroni- [24] L. Sigrist, “A UFLS scheme for small isolated power systems using rate-
zation,” IEEE Trans. Power Del., vol. 25, no. 4, pp. 2835-2841, Oct. of-change of frequency,” IEEE Trans. Power Del., vol. 30, no. 4, pp.
2010. 2192-2193, July 2015.
[11] C. Ahumada, R. Cardenas, D. Saez, and J. M. Guerrero, “Secondary [25] K. J. Astrom and T. Hagglund, Advanced PID Control. ISA - Instrumen-
control strategies for frequency restoration in islanded microgrids with tation, Syst., and Appl. Soc., 2006.
consideration of communication delays,” IEEE Trans. Smart Grid, vol. 7, [26] A. Gelb and W. E. Vander Velde, Multiple-input Describing Functions
no. 3, May 2016. and Nonlinear System Design. New York, NY: McGraw-Hill, 1968.
[12] C. Cho, J-H. Jeon, J-Y. Kim, S. Kwon, K. Park, and S. Kim, “Active [27] A. S. McAllister, “A graphical method for finding the frequency response
synchronization control of a microgrid,” IEEE Trans. Power Electron., of nonlinear closed-loop systems,” AIEEE Trans. Part II: Appl. and Ind.,
vol. 26, no. 12, pp. 3707-3719, Dec. 2011. vol. 80, no. 55, pp. 268-277, 1961.
[13] T. M. L. Assis and G. N. Taranto, “Automatic reconnection from inten-
0885-8969 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.