ENVA Parameter Setting

A. Setting at Configuration Management


 Start NE Management
 Configuration Management
 Modify Area
 Equipment
 Rack

Find alarm code description setting

 Fault
 Setting
 Alarm code description setting
Modify alarm label
 199083860 until 199083866 (for RNC)
 199087787 until 199087793 (for BSC)
Fiil that code into Gate Control’s Alarm Code in Configuration management

BSC

RNC
B. Independent Board Configuration Online
 Independent Board Configuration Online

 Shelf 3
 Modify
 Environment Monitoring Board Information
 Enable The Management and alarm shield flag of room humidity and temperatur
(ZTE High Temp Sensor)

 Setting 35 for The Maximal check value of the room temperature (centigrade thermometer)
 Route of the Management and alarm shield flag of the power (referering shelf source power A and
Source power B in Cabinet BSC/RNC)
One = Source A shelf 1
Two = Source A shelf 2
Three = Source A shelf 3
Four = Source B shelf 1
Five = Source B shelf 2
Six = Source B shelf 3

Example BSC/RNC use two Shelf, you should enable 1;3;4;6

 Find Alarm flag of the door for ENVA (BSC/RNC are same)

Enva Cable only have 6pcs with B1 until B6 as Cable Label, it 4 cable are use (B3 until B6)
That cable proposed as:
B3 = Main Fail
B4 = Rectifier Fail
B5 = Low Battery
B6 = Genset Running
For High Temp alarm using other cable and konek to high temp sensor