ENVA Parameter Setting
ENVA Parameter Setting
Fault
Setting
Alarm code description setting
Modify alarm label
199083860 until 199083866 (for RNC)
199087787 until 199087793 (for BSC)
Fiil that code into Gate Control’s Alarm Code in Configuration management
BSC
RNC
B. Independent Board Configuration Online
Independent Board Configuration Online
Shelf 3
Modify
Environment Monitoring Board Information
Enable The Management and alarm shield flag of room humidity and temperatur
(ZTE High Temp Sensor)
Setting 35 for The Maximal check value of the room temperature (centigrade thermometer)
Route of the Management and alarm shield flag of the power (referering shelf source power A and
Source power B in Cabinet BSC/RNC)
One = Source A shelf 1
Two = Source A shelf 2
Three = Source A shelf 3
Four = Source B shelf 1
Five = Source B shelf 2
Six = Source B shelf 3
Find Alarm flag of the door for ENVA (BSC/RNC are same)
Enva Cable only have 6pcs with B1 until B6 as Cable Label, it 4 cable are use (B3 until B6)
That cable proposed as:
B3 = Main Fail
B4 = Rectifier Fail
B5 = Low Battery
B6 = Genset Running
For High Temp alarm using other cable and konek to high temp sensor