Professional Documents
Culture Documents
ir
Paper accepted for presentation at 2009 IEEE Bucharest Power Tech Conference, June 28th - July 2nd, Bucharest, Romania
http://www.itrans24.com/landing1.html
I N recent years, many distributed generators (DG) have been The test system used in this paper is part of a real power
installed in power systems worldwide, and many more units system sited at the North region of Brazil, and is
are expected to be installed in the near future because of their interconnected with the main transmission Brazilian system.
advantages over conventional generation. The European Its one-line diagram in presented in Fig. 1.
Union goal is a 22% production from renewable energy The main system is composed by 230kV and 138kV
sources in 2010 [1]. This scenario is motivated by the transmission lines and has two hydroelectric: TUC, the main
increasing concern over environment impact and the need for generation with total capacity of 8.1 GW, and CUNA, a
eliminating the unnecessary transmission and distribution distributed generation with total capacity of 30MW. The main
costs. load points, which are indicated in the figure and represent
Examples of renewable energy sources are wind turbines, small cities, are: TUC, ALT, RUR, ITA, TAP and STA. The
photovoltaic systems, biomass, fuel cells and small hydro system was divided in three different areas for clarity
power plants. In particular, small hydro power plants have purposes, as shows Fig. 1.
obtained increasing interest due to their acceptable prices for Table 1 presents system active power demand to each area
generating electrical power without producing harmful for different load pattern. Since the more pessimist situation is
pollution and green-house gases and their relatively low the high load, the studies presented in this paper were
environmental impact compared to large hydro power plants. conducted to the high load pattern.
However, the connection of the DG has both benefits and
drawbacks of the technical, economical and environmental TABLE I
SYSTEM DEMAND (MW)
aspects [2]. A high DG penetration level may influence the Area Area 1 Area 2 Area 3
whole system operation and control, leading to technical Light load 19.0 28.2 89.0
impacts that must be identified [3, 4]. Then, such aspects must Medium load 27.1 40.7 92.4
be analyzed to prevent instability problems and assure High Load 29.0 43.6 100.4
adequate system voltage and frequency levels, regarding
customers and utility interests.
In this context, this paper presents a complete investigation
Fig.1. Single-line diagram representing part of the northern region of the Brazilian system.
as suggests the ONS (Brazilian System National Operator) B. Voltage Stability Analysis
[10]. Two protections schemes were considered in the The voltage stability margin measures the distance from the
simulations, as shows Table 2. The undervoltage protection initial operation point to the maximum loading point in the PV
acts when voltage becomes lower than 0.9 pu. This circuit curve, and can be expressed in MW or in percentage [5].
breaker is indicated in Fig. 1 as CB. In order to study the impact of DG on the voltage stability,
TABLE II
three scenarios with different DG penetration levels are
PROTECTION SCHEMES
protection type clearing time (s) investigated: case 1, case 2 and case 3. Fig. 6 shows the
distance protection 80 ms voltage stability PV curve at bus 5210 (138kV) for different
undervoltage protection 60 ms DG penetration levels to high demand, considering constant
power loads. Although the active and reactive power supplied
III. SIMULATION RESULTS by the DG was kept constant during the simulations, what
means that only the main generation assumes the increase in
A. Steady-State Analysis system demand, the results show that the presence of the DG
In this section, both voltage drop and active power loss are improves the system voltage stability margin. It can be
analyzed. Fig. 4 shows system voltage profile to high load for explained because the DG provides active and reactive power
the main buses in the corridor between the main generator to local loads, decreasing system losses and increasing system
(bus 6420) and the DG (bus 5170). The results show that as voltage stability limit.
the DG penetration level increases, system voltage profile also 0,984
1.12 PL = 15.6%
0,826 PL = 12.1%
1.1 PL=15.6%
PL = 8.6%
PL=12.1%
0,787
1.08 PL=8.6%
PL=0%
1.06 0,748
169,9 189, 208,1 227,3 246,4
System Loading (MW)
Voltage (pu)
1.04
Fig.6. PV curves for different DG penetration levels considering constant
1.02
power load.
1
Simulations were also performed considering the others ZIP
0.98 load models: constant impedance (Z), constant current (I) and
0.96 constant power (P) [5]. The constant power load model is the
most pessimist situation for static loads, with lower voltage
0.94
stability margin as shows Table III. Another simulation was
6420 6510 6530 6540 6550 5150 5165 5170
Buses conducted replacing 60% of the static loads modeled as constant
Fig.4. Steady-state voltage profile for different DG penetration levels. power with dynamic loads (induction motors). This brings the
system to a voltage stability margin even worst, of 39.6%.
12 However, for all cases, simulations results considering
High Load
11 Medium Load
different DG penetration levels show that the presence of the
Light Load DG always increased the voltage stability margin.
10
TABLE III
9 LOAD MODEL AND SYSTEM VOLTAGE STABILITY MARGIN
System Losses (MW)
3 C. Transient Analysis
2
Although many simulations were analyzed, this paper
0 2 4 6 8 10
DG penetration level (%)
12 14 16
presents only the results analyzed for two faults, which are
indicated in Figure 1.
Fig.5. Active power losses for different DG penetration levels.
Fig. 7 presents the voltage sag at bus 751 close to the DG, 60.2 PL = 12.1%
Frequency (Hz)
PL = 15.6%
occasioned by this fault for different DG penetration levels.
60.1
The results show that the increase in the DG penetration level
results only in a slightly increase in voltage sag magnitude 60
during the transient, which is not significant. The DG slightly
increases the current in the branch 5170–751, as shows Fig. 8. 59.9
0 2 4 6 8 10 12 14 16 18
Time (s)
1.08
(b)Transient Details
PL = 8.6% 60.2
1.05 PL = 8.6%
PL = 12.1%
PL = 15.6% 60.15 PL = 12.1%
Frequency (Hz)
PL = 15.6%
Nodal voltage at bus 751 (pu)
60.1
1
0.85 60.05
0.845
0.95 60
0.835 59.95
0.9 1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8
0.9 Time (s)
0.825
Fig.9. Frequency behavior during fault 1 for different DG penetration levels.
34
0.85 0.815
31 PL = 8.6%
0.1 165
PL = 15.6%
PL = 8.6%
Active Power (MW)
PL = 15.6%
0.06 145
0.04 135
0 1 2 3 4 5 6 7
125
Time (s)
(b)Transient Details 115
0.14 0 1 2 3 4 5 6 7 8
PL = 8.6% Time (s)
0.12 PL = 12.1%
Fig.10. Active power during fault 1 for different DG penetration levels.
PL = 15.6%
Current (pu)
0.1
0.08
1.2 (a)Simulation
60.7
PL = 8.6%
PL = 8.6%
1.1 PL = 12.1%
Frequency (Hz)
60.5 PL = 12.1%
PL = 15.6%
PL = 15.6%
1 60.3
Nodal voltage at bus 751 (pu)
0.9 60.1
0.41
0.8 0.405
59.9
0 2 4 6 8 10 12 14 16 18
Time (s)
0.4
0.7 (b)Transient Details
0.395
60.7
0.6 PL = 8.6%
Frequency (Hz)
0.39 60.5 PL = 12.1%
0.5 PL = 15.6%
0.385 60.3
0.4 0.38
0.99 1 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 60.1
0.5 1 1.5 2 2.5 3
Time (s) 59.9
0.9 1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8
Fig.11. Nodal voltage at bus 751 for different DG penetration levels. Time (s)
(a)Simulation
0.25 30
PL = 8.6%
0.2 PL = 12.1%
Current (pu)
20 15MW
PL = 15.6%
0.15 21MW
10 27MW
0.1
0 1 2 3 4 5 6 7 8
0.05
Time (s)
0
0 1 2 3 4 5 6 7
TUC Active Power (MW)
Time (s)
160 PL = 8.6%
(b)Transient Details PL = 12.1%
0.275
PL = 15.6%
0.27 140
0.265
Current (pu)
120
0.26
0.255 0 1 2 3 4 5 6 7 8
PL = 8.6% Time (s)
0.25
PL = 12.1%
0.245 PL = 15.6% Fig.14. Active power during fault 2 for different DG penetration levels.
200
150
Brazilian National Operator for 138kV transmission lines.
Also, only faults in lines next to the DG will cause the
100
generator disconnection by severe voltage sags. Based on the
50
results and discussion, it can be concluded that DG can
0 improve the steady-state and stability performance of power
-50 system.
-100
V. REFERENCES
-150
0 2 4 6 8 10 12 14 16 18 20
Time (s)
[1] EU Directive 2001/77/EC on the promotion of the electricity produced
from renewable energy source in the internal electricity market.
Fig.15. DG rotor angle for a three-phase short circuit. [Online]. Available:
http://europa.eu.int/comm/energy/res/legislation/electricity_en.htm
The ONS establishes a voltage sag tolerance curve for [2] N. Jenkins, R. Allan, P. Crossley, D. Kirschen, and G. Strbac,
generators (ride through capability) as shows Fig. 16 [12]. "Embedded. Generation", 1st ed. London, U.K.: Inst. Elect. Eng., 2000.
Generators which do not meet this tolerance curve must be [3] V. V. Thong, J. Driesen, R. Belmans, "Benefits and Impact of Using
disconnected and pay fine. The results show that these voltage Small Generators for Network Support", in Proc. 2007 IEEE Power
sags does not imply in generator disconnection. Only faults in Engineering Society General Meeting, pp 1-7.
lines 5150-5165 and 5165-5170 will cause the generator [4] A. M. Azmy, I. Erlich, "Impact of distributed generation on the stability
disconnection. of electrical power system", in Proc. 2005 IEEE Power Engineering
Society General Meeting, Vol. 2, pp. 1056-1063.
1.2 [5] P. Kundur, "Power System Stability and Control". New York: McGraw-
1.1
Hill, 1994.
[6] IEEE Working Group on Prime Mover and Energy Supply Models for
1 System Dynamic Performance Studies. IEEE Transactions on Power
0.9 Systems. Vol.7 No.1. Feb. 1992.
[7] CEPEL, Centro de Pesquisas de Energia Elétrica, "ANAREDE:
DG terminal voltage (pu)
0.8
Programa de Análise de Redes", Manual Guide, 07-08 Version. Manual
0.7
do Usuário, August 1999.
0.6 [8] CEPEL, Centro de Pesquisas de Energia Elétrica, "ANATEM: Análise
0.5 de Transitórios Eletromecânicos", Manual Guide, 09 Version, December
2002.
0.4
[9] T. Van Cutsem, "Voltage Instability: Phenomena, Countermeasures and
0.3 Analysis Methods", in Proc. 2000 IEEE, vol.88, No. 2, pp. 208 – 227.
Fault 2
0.2 Fault 1
[10] ONS Network Procedures 2008, “Guidelines and Criteria for Electrical
ONS curve Studies – item 23.3” [Online]. Available: www.ons.org.br
0.1
[11] ONS Network Procedures 2008, "Minimum Requirements for protection
0
0.8 1 1.2 1.4 1.6 1.8 2
systems – item 2.6". [Online]. Available: www.ons.org.br
Time (s) [12] ONS Network Procedures 2008, "Minimum Technical Requirements for
the connection to the basic network – item 3.6". [Online]. Available:
Fig.16. DG terminal voltage during fault 1 and fault 2. www.ons.org.br