You are on page 1of 9

Downloaded from http://iranpaper.

ir

Electric Power Systems Research, 15 (1988) 31 - 39 31

Synchronous Generator Stability due to Multiple Faults on Unbalanced


Power Systems

ELHAM B. MAKRAM and V. OMAR ZAMBRANO


Electrical and Computer Engineering Department, Clemson University, Clemson, SC 29634-0915 (U.S.A.)
RONALD G. HARLEY
Department of Electrical Engineering, University of Natal, King George V Ave., Durban 4001 (Republic of
South Africa)
(Received February 22, 1988)

ABSTRACT single line to ground faults, line to line faults,


three-phase faults, and open conductors, was
This paper investigates the dynamic behav- one of the first to be solved by the symmet-
ior o f a synchronous generator connected to rical c o m p o n e n t s m e t h o d [4, 5].
an unbalanced three-phase p o w e r system In pow er systems, multiple shunt faults
which is subjected to a shunt fault at one occasionally occur simultaneously at differ-
location and blown fuses or open conductors ent locations, particularly in systems with
at another location. The m e t h o d involves an ungrounded neutral. As is known, a ground
phase frame representation o f the line. The fault in an ungrounded system results in an
imbalance created by large single-phase loads, increase in the unfaulted phase voltages and
untransposed lines, conductor bundles, etc., an increase in the arc overvoltages, which
is reflected in polyphase impedance matrices. may cause faults to ground at o t h e r locations
Consequently, line removals, additions, impe- with weak insulation [5]. On the o t h e r hand,
dance changes, conductor and faulted phase even if no faults occur, the system can be in
openings can be simulated based on the an unbalanced voltage condition which can
boundary conditions. Thus, the proposed be represented as multiple asymmetrical
m e t h o d makes it possible to study the syn- shunt faults.
chronous generator stability due to any com- A multiple fault occurs, for example, when
bination o f single or multiple asymmetrical a ground or interphase fault results in the
series and shunt faults occurring anywhere faulted c o n d u c t o r being opened and the
in the system and the results o f several case single-pole circuit breakers on each side o f
studies are presented. A significant finding the faulted c o n d u c t o r do not o p e n simul-
is that certain faults cause the generator to taneously, or one of t hem never opens at all,
lose synchronism only after several cycles o f or only one fuse in the line opens. Multiple
the rotor angle swing curve. In such cases it is faults can also occur when these two tripped
therefore no longer correct to judge the circuit breakers do n o t reclose simultaneous-
system's stability only on the 'first swing ly o n t o an asymmetrical short-circuit. Similar
cycle' o f the rotor angle. multiple faults also occur when one line is
open for some reason, giving rise to unbal-
anced voltage conditions leading to another
INTRODUCTION fault on either one or b o t h o f the ot her
two lines [6].
Unbalanced currents can cause serious Although synchronous machines have been
problems, and significant current imbalances widely used since the end o f the previous
have been shown t o exist during normal century, their_ transient operat i on has n o t
operation o f distribution systems [ 1 - 3 ] . y e t been fully evaluated under conditions
The problem o f determining current and of power system imbalance. Transient stabil-
voltage in unbalanced short-circuits, such as ity calculations for a large power system con-

0378-7796/88/$3.50 © Elsevier Sequoia/Printed in The Netherlands


Downloaded from http://iranpaper.ir

32

© ® THEORY

The synchronous machine is simulated by


INFINITE ~ Ia ~----~ ~ m Q its positive-, negative- and zero-sequence AC
BUS ~ ib
equivalent circuits, and these are transformed
Ic by the Fortesque sequence transformation
at the machine terminals into ABC phase
V abcl
~ i STATIC variables as explained in Appendix A. The
I~
I~ X -I" ~ LOAD
induced voltage inside the machine is assumed
L - X
to be balanced under all network conditions
Fig. 1. Network containing synchronous machine
and shunt load. and thus contains only a positive-sequence
voltage component E " , the so-called 'voltage
behind the subtransient reactance'; the
taining many lines, loads and generators negative- and zero-sequence equivalent cir-
are cumbersome and time consuming. Con- cuits therefore have no voltage sources.
sequently, the number of differential equa- During the simulation of any disturbance, E "
tions per generator is kept to a minimum; is updated as a function of flux linkages at
moreover, the network equations can be each step of the step-by-step integration
simplified if the generator is represented by process; electric transient effects in both the
an AC voltage phasor and an impedance. stator and the network are neglected.
Most, if not all, present day stability pro- The line is simulated by a 3 X 3 impedance
grams for power systems assume balanced matrix containing off-diagonal terms to rep-
network conditions in order to keep the resent mutual coupling between phases. The
number of equations to a manageable size shunt fault and shunt load are also simulated
and because network asymmetry or imbal- by 3 X 3 impedance matrices with suitable
ance has always been assumed to have a elements according to the boundary condi-
negligible effect on synchronous generator tions. Details of the network equations are
stability studies. in Appendix B.
This paper extends a previous study [7]
and evaluates the transient response of the
synchronous generator in Fig. 1 when a
multiple fault occurs such as a single line to
ground fault on one phase followed by a RESULTS
blowing fuse or one pole of a circuit breaker
opening, or a complete outage on the same In order to further evaluate the effects of
phase. asymmetrical multiple faults the system in
The results of several case studies lead to Fig. 1 was subjected to various combinations
the important findings that the multiple fault of a single line to ground fault on phase A
is a more severe test of machine stability than followed by a line outage of a faulted phase
the traditionally used three-phase to line (phase A) for different system initial condi-
ground fault and, furthermore, that for this tions. The machine parameters used are in
type of fault a stable first swing of the rotor Appendix C. Two types of line configuration
angle does not guarantee ultimate state stabil- were considered: firstly, a balanced triangular
ity. spacing of 5.333 ft between phases; and,
secondly, a fiat configuration with dimensions
Dab = 2 ft, Db~ = 6 ft and Dac -- 8 ft, as shown
in Fig. 2. This yielded a line Zab c matrix
, Dab ~I. Obc ~[
in p.u. for the unbalanced line:
V "F -I
0a ©--~b
b g ©
c Zabc --

-0.171 + j1.091 0.076 + j0.703 0.076 + j0.568-


g 0.076 + j0.073 0.171 + jl.091 0.076 + j0.596
Fig. 2. Unbalanced feeder configuration. 0.076 + j0.568 0.076 + j0.596 0.171 + j1.091
Downloaded from http://iranpaper.ir

33

For the balanced line, only the off-diagonal power flow from the generator, so that the
terms in Zab c change and all of them become generator's accelerating power is relatively
equal to 0.076 + j0.608 p.u. large.
For each of the transient tests, the prefault If the generator's neutral is grounded
initial conditions were taken to be a balanced t h r o u g h some finite reactance, the resultant
three-phase infinite bus voltage of 1 p.u. on swing curve D1 lies between curves D3 and
each phase on Fig. 1. All the shunt faults D4 (for the shunt load concentrated on phase
were applied to the line at a point close to A) and curve D2 lies below D4 for the shunt
the generator terminals. A t t e n t i o n was paid load concentrated on phase B.
to the effect of grounding and ungrounding
the generator's neutral. Temporary SLGF followed by temporary
The static shunt load at the generator line outage
terminals consisted of an unbalanced (21 + In order to evaluate further the effect of
j13)% admittance concentrated on only one asymmetrical shunt and series faults, the pre-
phase which varied from one case study to vious single line to ground fault (SLGF) is
the next. In some cases this load was balanced again assumed to last for 100 ms on phase A
at (7 + j4.3)% on each phase. as before, but instead of simply removing
Before evaluating the effect of a multiple the fault, the faulted phase A is now taken to
fault on the generator's transient stability, be switched out by a circuit breaker, thereby
the effects of the individual faults are con- leaving the generator running on a two-phase
sidered first, one at a time. supply w i t h o u t shunt faults for a further
100 ms before the A phase is reconnected
Temporary single line to ground fault (SLGF) after the fault has been cleared. The outage
The SLGF occurs by far the most often of of the phase A is classified as a series fault.
all fault types and ref. 8 states that it makes For comparative purposes, the SLGF on
up 70% of all faults on lines and feeders. The phase A is replaced by a symmetrical three-
swing curves in Fig. 3 show the generator's phase line to ground fault (3LGF) at the same
transient response for a temporary SLGF location but w i t h o u t a subsequent line
on phase A of the line (lasting for only 100 outage. The resultant swing curves appear in
ms) at its terminals in Fig. 1. It is clear from Fig. 4. Curves D6, D7 and D8 in Fig. 4 are
these swing curves that case D3 (ungrounded the resultant SLGF swing curves and curve
neutral and all shunt load concentrated on D5 applies to the 3LGF case. It is clear that
the A phase) has the worst effect upon the the traditional test of transient stability, the
stability; this happens since the fault short- 3LGF fault with the largest first-peak swing
circuits the shunt load and the increased line curve, still constitutes the most severe shock
voltage drop creates a severe reduction in
110
90
~~<z907050D S ~
8O
70

60 30.
50 0.'0 0,'3 0.6 0.'9 1.'2 1.r5
TIME, SEC
O
' .O ~
0.3 0/6 0.9' r
t.2 T--
1.5 Fig. 4. Rotor angle following a temporary 3LGF or
TIME,SEe temporary SLGF and temporary line outage for
Fig. 3. Rotor angle following a temporary SLGF for grounded and ungrounded neutrals: D5, balanced
ungrounded and grounded neutrals: D1, unbalanced feeder, balanced shunt load, grounded neutral,
line, shunt load on A, grounded neutral; D3, un- 3LGF; D6, unbalanced feeder, shunt load on A,
balanced line, shunt toad on A, ungrounded neutral; ungrounded neutral, SLGF on A; D7, unbalanced
D2, unbalanced line, shunt load on B, grounded feeder, shunt load on A, grounded neutral, SLGF on
neutral; D4, unbalanced line, shunt load on B, un- A; D8, repeat D6 but line outage increased from 100
grounded neutral. ms to 200 ms.
Downloaded from http://iranpaper.ir

34

to the system. Increasing the outage time of 140 -

phase A after an SLGF on phase A impairs ,~ 120-


the stability by changing curve D6 to D8.
100-
If this SLGF had caused a fuse to blow,
then the o p e n e d phase A could n o t have "< 80-
reclosed after 100 or 200 ms, but would have o
~ 60-
remained open permanently; the effect o f DI~I.

such a p er man en t line outage is studied in 40- o~J


01 , i ' I ' 3/ ' I ' I ' ~ , i ' I ' I r I
the n ex t few case studies. I 2 4- 5 6 7 8 9 10
(a) TIME. SEC

Permanent line outage only


Before evaluating multiple faults, at t ent i on
4.01
120 I D12
is first paid to understanding the synchronous
generator behavior when one phase c o n d u c t o r 100 1

is permanently switched out, no ot her shunt ": 80 4 A _


/ \ / \ j, , / ,j" . - \ - ~1 1 D
or series fault having occurred. Will the o 60 ]/I ,~\'J "V' ",U ~" "~ -
machine remain stable or n o t when running • ,'~ ~', "-~, ---- ....................................... D10
4.0 ,~ ~,..,'/~ ~-- ~ ~ ~ - ~ . . . . . . D9
on two phases only, or will it perhaps depend
i ' I ' 2 L ' i ' i ' E ' ~ , i , i ' I ' I
on the prefault system conditions? 0 1 3 4 5 6 7 8 9 10
The swing curves in Fig. 5 have been com- (b) TIME, SEO

p u t ed for different values of prefault power Fig. 5. Rotor angle following a permanent line outage
P0 arriving at the infinite bus. T hey show that of phase A. (a) Ungrounded generator neutral: D13,
repeat D10; D14, repeat D l l ; D15 repeat D12.
an ungrounded neutral generator is more (b) Grounded generator neutral: D9, P0 = 0.2, no
severely affected, and t hat in some cases the shunt load; D10, P0 =0.2, balanced shunt load;
generator may settle to a new steady larger Dll, repeat D10, but P0 = 0.4; D12, repeat D10,
r o t o r angle on a two-phase supply. However, but P0 = 0.6.
curves D12 and D15 for larger values of P0
show clear signs o f instability after 10 s, 1.0
even after their first peaks suggested a stable
system. F o r this t y p e of fault, therefore, the
system's ultimate stability cannot be judged
by considering only the first peak of the
CL
0.8

0.6

,~ 0.4.
~
~ / " ~ / /\-j, ,
}'],-, "~
TE12

swing curve, as is done in traditional pow e r 0.2-


system stability studies using the t e m p o r a r y
0.0-
3 L G F as a disturbance. Moreover, the first
peak of curve D12 (generator neutral un- ; 2' 3' ; 5' ; 7' 8' 4
grounded) is even higher than that of curve TIME, (SEC)

D5 (for the 3 LGF) in Fig. 4, illustrating t hat Fig. 6. Generator electric t o r q u e following a per-
the asymmetrical single line outage series m a n e n t line o u t a g e o f p h a s e A o n a n unbalanced line
fault is an even more severe disturbance to w i t h g e n e r a t o r n e u t r a l g r o u n d e d : TE9, P0 = 0.2, n o
s h u n t l o a d ( T E l l , P0 = 0.4); T E l 0 , P0 = 0.2, bal-
t h e system than the traditional 3LGF. Figure a n c e d s h u n t load ( T E l 2 , P0 = 0.4).
6 shows the generator t o r q u e variation cor-
responding to the r o t o r angle in Fig. 5(b).
Each t o r q u e curve exhibits a sharp drop in
t o r q u e at the m o m e n t the line is switched the auto-reclosing operation of a single-pole
out, but the to r que then rises and falls in circuit breaker, then some or all of these
h a r m o n y with the r o t o r angle. four unstable cases may well turn o u t to be
Whether or n o t cases D12 and D15 go un- stable, and each case would have to be studied
stable depends n o t only on the initial condi- on its own merits.
tions, such as the value of P0, but also on the The importance of these results can be
duration o f the line outage (which in these summarized by saying that at low pow er
cases was taken to be a p e r m a n e n t outage). levels a synchronous generator will remain
If the outage time were to be reduced t o a in synchronism after a line outage. However,
finite time o f a few hundred ms, representing at higher power levels it will drift o u t of
Downloaded from http://iranpaper.ir

35

,125]01 °7. = / /
I10 -

lO0-
~
j~90-
o
< 80-
I---

~ 70-

60- 5O
[ I ' I ' I I ' I ' i , t , i , i ' %

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5
TIME, SEC
lIME, SEC
Fig. 7. R o t o r angle m e a s u r e d o n a m i c r o a l t e r n a t o r
Fig. 9. Rotor angle after a permanent SLGF on phase
a f t e r o n e o f t h e p h a s e lines has b e e n p e r m a n e n t l y
A followed by a permanent line outage on an unbal-
removed.
anced line: D20, grounded neutral, shunt load on A,
P0 = 0.6; D21, grounded neutral, shunt load on B,
110 • P0--0.6; D22, repeat D20 but with ungrounded
neutral; D23, repeat D21 but with ungrounded neu-
100 -
em tral.
90. D17
,..,/
80. 160

j
I
N 7o.
°~.~ ~ i : / I , ' ~ " " ~ ' Y : . . . . "~''--~--' 140
I !:, .' "
60-
50-

OI ' i
1
,
2
i , i
3
,
4
i ,
5
i , 6/ ,
7
i , i
8
, i
9
, i
10
'= 120

1oo

~ 80
o !5 92°
TIME, SEC 6O F o~7
Fig. 8. Rotor angle following a temporary SLGF on
phase A cleared by a permanent line outage on an
unbalanced line: D16, grounded neutral, shunt load 0' 2' ,' 6' ; 1'0 1'2 1', ;6
on A, P0 = 0.4 (D18, ungrounded neutral); D17, TIME, (SEC)
grounded neutral, shunt load on B, P0 = 0.4 (D19, Fig. 10. R o t o r angle a f t e r a p e r m a n e n t S L G F o n
ungrounded neutral). p h a s e A f o l l o w e d b y a p e r m a n e n t line o u t a g e o n a n
u n b a l a n c e d line: D24, r e p e a t D 2 0 b u t P0 = 0.4; D25,
r e p e a t D 2 1 b u t P0 = 0.4; D26, r e p e a t D 2 4 b u t
stability several swing cycles a f t e r t h e first n e u t r a l u n g r o u n d e d ; D27, r e p e a t D 2 5 b u t n e u t r a l un-
o s t e n s i b l y stable swing c y c l e [ 9 ] ; this has grounded.
actually been confirmed by practical mea-
surements on a microalternator and the u n g r o u n d e d n e u t r a l and c o n c e n t r a t i o n o f t h e
results a p p e a r in Fig. 7. s h u n t l o a d o n p h a s e B.
All f o u r cases c o n s i d e r e d in Fig. 8 clearly
Temporary SLGF followed by a permanent r e a c h a stable s t a t e c o n d i t i o n .
line outage (multiple fault)
The fault conditions of a t e m p o r a r y S L G F Permanent SLGF followed by a permanent
o n l y (results in Fig. 3) a n d o f a p e r m a n e n t line outage
line o u t a g e o n l y (results in Fig. 5) are n o w This case s t u d y is a direct e x t e n s i o n o f t h e
c o m b i n e d t o r e p r e s e n t t h e case w h e r e t h e o n e a b o v e b y s i m u l a t i n g t h e case w h e r e an
S L G F causes t h e f a u l t e d line t o be o p e n e d , S L G F o n t h e line, b u t close t o t h e g e n e r a t o r
b u t , f o r s o m e r e a s o n or o t h e r , it is n o t t e r m i n a l s , causes t h e infinite bus end circuit
s w i t c h e d b a c k in again. As b e f o r e , t h e S L G F b r e a k e r in t h e f a u l t e d line t o trip, b u t n o t t h e
o n p h a s e A lasts f o r o n l y 1 0 0 m s , f o l l o w e d o n e at t h e g e n e r a t o r end. This results in t h e
b y its r e m o v a l a n d a p e r m a n e n t o u t a g e o f SLGF remaining permanently connected,
p h a s e A. This is classified as a m u l t i p l e fault. even a f t e r t h e line is s w i t c h e d o u t , a n d in
F o u r swing curves are p r e s e n t e d in Fig. 8 a d d i t i o n it is a s s u m e d t h a t t h e line r e m a i n s
to illustrate t h e e f f e c t o f g e n e r a t o r n e u t r a l p e r m a n e n t l y s w i t c h e d o u t , giving rise t o
g r o u n d i n g a n d t h e p o s i t i o n o f a single-phase a n o t h e r t y p e o f m u l t i p l e fault.
s h u n t load; t h e w o r s t case ( o n first swing T h e swing curves in Fig. 9 clearly s h o w all
e v a l u a t i o n ) is clearly t h e c o m b i n a t i o n o f an f o u r cases t o be u n s t a b l e , and again D 2 2 and
Downloaded from http://iranpaper.ir

36

160 - ] sity o f Natal) f o r o b t a i n i n g the actual mea-


14e I surements on a microalternator.
ow /
120
,.; /
z 100- / REFERENCES
o= 80. 2~,
= 60 • / F ~ f ~ -~--~
1 W. H. Kertsing and S. A. Seeker, A program to
40 ~ 1 study the effects of mutual coupling and unbal-
anced loading on a distribution system, IEEE
O' 4' 8' 1'2 1'6 Trans., PAS-101 (1974) 804 - 811.
TIME, (SEC)
2 M. A. Wortman, D. L. Allen and L. L. Grigsby,
Fig. 11. Rotor angle after a permanent SLGF on Techniques for the steady state representation of
phase A followed by a permanent line outage on an unbalanced power systems: Part I. A systematic
unbalanced line: D28, repeat D20 but P0=0,3; building block approach to network modeling,
D29, repeat D21 but P0 = 0.3; D30, repeat D28 but IEEE Trans., PAS-104 (1985) 2807 - 2814.
neutral ungrounded; D31, repeat D29 but neutral 3 R. W. Fisher, Voltage unbalance on three-phase
ungrounded. distribution system, Southeastern Electric Ex-
change 1977 Annu. Conf., Engineering and
D23 illustrate t h a t a stable first peak does Operation Division, New Orleans, April, 1977.
n o t guarantee stability. R e d u c i n g t h e p r e f a u l t 4 E. L. Harder, Sequence network connections,
p o w e r level P0 f r o m 0.6 t o 0.4 p.u. results Electr. Energ. Res. J., 34 (1937) 481 - 488.
in curves D 2 4 t o D 2 7 in Fig. 10, w h i c h are 5 K. Amchin and T. B. Gross, Analysis of subse-
quent faults, Trans. AIEE, 70 (1951) 1817-
still eventually unstable, a l t h o u g h their 1823.
shape l o o k s a lot d i f f e r e n t f r o m t h o s e in 6 E. B. Makram and A. Girgis, Multiple faults in-
Fig. 9. Finally, reducing P0 to 0.3 yields the volving open conductors and shunt faults on un-
resultant curves D 2 8 to D31 in Fig. 11, and balanced distribution systems, 19th Southeastern
this t h e r e f o r e shows t h a t , u n d e r certain con- Symp. on System Theory, Clemson, SC, March
1987, pp. 350 - 354.
ditions such as low p r e f a u l t p o w e r , the 7 V. O. Zambrano, E. B. Makram and R. G. Harley,
g e n e r a t o r can m a i n t a i n s y n c h r o n i s m t h r o u g h Stability of a synchronous machine due to an
o n l y t w o lines instead o f three, even w i t h unsymmetrical fault in unbalanced power sys-
an S L G F close t o its terminals o n t h e o p e n e d tems, 20th Southeastern Symp. on System
Theory, Charlotte, NC, March 1988, pp. 231-
line.
235.
8 P. Anderson, Analysis of Faulted Power Systems,
CONCLUSIONS Iowa State Univ. Press, Ames, IA, 1981.
9 S. M. Shuck, Subsynchronous resonance of the
This p a p e r r e c o n s i d e r e d t h e transient Koeberg turbo-generators and a laboratory
micro-alternator system, Trans. S. Aft. Inst.
stability o f a s y n c h r o n o u s g e n e r a t o r with Electr. Eng., 70 (1979) 278 - 297.
a s h u n t load c o n n e c t e d t o an infinite bus 10 B. Adkins and R. G. Harley, Theory of Alternat-
t h r o u g h an u n b a l a n c e d line. Several asym- ing Current Machines, Chapman and Hall, Lon-
metrical multiple faults have been studied don, 1975.
w h e n a single line to g r o u n d fault gives rise
to One o f the three-phase lines being s w i t c h e d
o u t , s o m e t i m e s t e m p o r a r i l y and s o m e t i m e s APPENDIX A
p e r m a n e n t l y . T h e results o f various case
studies reveal the i m p o r t a n t findings t h a t the Machine e q u a t i o n s
multiple fault is a m o r e severe test o f m a c h i n e F o r the p u r p o s e o f this investigation,
stability t h a n t h e t r a d i t i o n a l l y used three- electrical t r a n s i e n t effects in the m a c h i n e ' s
phase line t o g r o u n d fault, and f o r this t y p e s t a t o r have been neglected a n d all s t a t o r
o f fault a stable first swing o f the r o t o r angle voltages and c u r r e n t s are RMS quantities.
does n o t guarantee u l t i m a t e steady-state T h e s e q u e n c e c o m p o n e n t voltages are ob-
stability. tained f r o m the n o d e 2 phase voltages Vabc2
in Fig. 1 as follows:
ACKNOWLEDGEMENT Vt0pn = AVabc2
The a u t h o r s wish t o t h a n k Dr. J. C. Balda w h e r e A is the w e l l - k n o w n F o r t e s q u e se-
(Electrical Engineering D e p a r t m e n t , Univer- q u e n c e c o m p o n e n t m a t r i x t r a n s f o r m a t i o n and
Downloaded from http://iranpaper.ir

37

Vt0pnT are the sequence component voltages where Zab¢2 represents the feeder impedance
at the terminals of the machine. matrix for the line length L - - X , Iabc2 rep-
The positive-sequence generator current Igp resents the current in it and Vfabc the voltages
is given by at the fault location. Iab¢2 in turn is related
to the motor and shunt load currents by
Igp = (E" -- Vtp)/(Ra + jX~') (A-l)
and the positive-sequence power developed by labc2 = Iabeg + l a b e l (B-l)
the generator by Similarly,
Pgp -- R e a l { E " I g p * } (A-2) Vfabc -- Vabc I -- Zabe l/abe I (B-2)
The torque associated with the developed where Zabol and label apply to line length X,
power is and
Tgp = Pgpcoz/°-)n (A-3) /abel = labc2 +/fabc (B-3)
where coz is the synchronous speed in rad s-1, where
and COnthe instantaneous speed in rad s-1.
Similarly, the following expressions apply Ifabc = YfabcVfabc (B-4)
to the negative- and zero-sequence circuits: N o w labcg and label Can, in turn, be defined
in terms of the generator and the shunt load
Ign = - - Y t n l ( R a + R2n + jXn) (A-4)
admittances and their terminal voltages as
Igo = - - V t o / ( R o + jX0) (A-5) follows:
Tg. = Ilgnl:/R2n (A-6) l a b e l = YabcLVabc2 (B-5)
Tgo = Ilgol2/Ro (A-7) and
The equation for the motion of the rotor is labcg = Yabcg[ V a b c 2 - Vabcg] (B-6)
given by
Thus,
PCOm = (Tpm - - Tgp - - Tgn - - Tgo)/(2H/coz)
labc2 = label +/abcg (B-7)
(A-8)
Combination of eqns. (B-7) yields the voltage
where H is the inertia constant in seconds, Vfab¢ at the fault location:
and Tpm the prime mover driving torque.
For the purpose of this investigation, the [ U + Mlf] Vfabe -- Vabc I + Mlg Vabcg
prime mover o u t p u t power Ppm is assumed to -- KVabc2 (B-8)
remain constant at its pre<listurbance value
during disturbances, hence The final equation of Vfabe is

Tp~n = Ppm coz/ (.Om (A-9) Vfabc -- J[ Vabcl "t" MlgVabcg - - KVabc2] (B-9)

Finally, the load angle 5 is found from in- where


tegrating M l f = ZabclYfabc
p5 = (-~m - - (-Oz (A-IO) Mlg = ZabelYabcg
Equations (A-l) -(A-IO) can be solved by U = identity matrix
a numerical step-by-step integration process.
J = [U + Z a b c l Y f a b c ] -1

K = Zabcl[Yabcg + YabcL]
APPENDIX B By combining eqns. (B-3), (B-4) and (B-9)
and eliminating the voltage Vfabc ,
Network equations Vabc2 = J{[U + J] [Mlg + M1L] + M2g + M 2 L } - l
The abc voltage vector at node 2 in Fig. 1 X [ V a b c l "l- M l g V a b c g ]
is given by
or

Vabc 2 -- Vfab c - - Zabc2labc 2 Vabc2 = JN[ Vabcl -i-MlgVabcg] (B-10)


Downloaded from http://iranpaper.ir

38

® ® example, no longer affects the feeder cur-


rents. Its place is taken by a new voltage
V'al on the feeder side of S1. The equations
that describe the series fault can be obtained
I c Rfa Ifc
Vabc, Vobcz as follows:
t I
Vabc2 = Vabcl -- Zabclab c (B-12)
I I I
I~ x =i ~ L-x =I
Substitution of eqns. (B-l), (B-3), (B-5)
Fig. B-1. Representation of shunt faults to ground. and (B-7) in eqn. (B-12) yields
Vabc2 = [Yabcg + YabcL] -1 [Iabc + YabcgVabcg]
where (B-13)
M2g = Zabc2Yabcg /abc represents the current vector through
the feeder after the shunt fault is cleared and
M2L = Zabc2YabcL
the open conductor occurs (Fig. I).
N = {[U + J] [Mlg + M m ] + M2g + M 2 L ) -1 From eqns. (B-12) and (B-13), labc Can be
obtained:
Imbalance in the shunt load can be repre-
sented by substituting suitable values of Y~aL, /abc = [Yabcg + YabcL] -1 Vabcl
YbbL and Y~¢L in eqn. (B-5). For a balanced
load these three admittances are equal and
-- ([Yabcg + YabcL] -1 + Zabc) -1
for no shunt load whatsoever they are all > [Yabcg + Y~bcL]-'Y~bcgV~bcg (B-14)
three equal to zero.
Equation (B-14) can be written in matrix
S h u n t fault equations form as
Consider the case where the fault network
in Fig. 1 consists of three shunt fault resistors [icl ]-YII Y12 Y131 [Val 1
Rf representing a fault to ground, as shown
in Fig. B-1. Lr:,, r3d |V,,lj
In this case the fault admittance matrix is
rYll Y~2 Y~31 ~V,~l
ii -0 01
given by

- iY;, ,,;q l,, d


YFabc = 0 llRm 0 (B-11) LYe1 Y]2 Y]3J LV,,d
0 0 1/Rf¢ (B-15)
Suitably high or low values for Rfa, Rfb When line A opens, the voltage of phase A
and Rf¢ represent faults ranging from single at S1 in Fig. 1 becomes V'I and Ia becomes
line to ground (SLGF) on phases A, B or C zero. Thus, I b and I e can be obtained after
respectively. applying Kron's reduction to eqn. (B-15):
Ib = ( Y 2 2 - Y122/Yll)Vbl
Series fault equations
Open conductor or series faults may occur + ( Y 2 a - Y12Yla/YI1)Vcl
when a conductor is being opened, or when
+ (Y~]Y]2/Yll -- Y~I)V~
single-pole circuit breakers on each side of
t ?
the line do not open simultaneously, or + ( Y 1 2 Y 1 2 / Y 1 1 - Y22)Vbg
when one of them never opens at all, or when
+ ( Y ~ a Y 2 1 / Y 1 ] - Y~a)V¢g (B-16)
only one fuse in the line opens. Series faults
may also occur when the two tripped circuit Ic = ( Y 3 2 - Y31Y12/Yll)Vbl
breakers do not reclose simultaneously
during a short-circuit. + ( Y a a - Yla2/Y]I)Vcl
I t
When a fault on phase A, for example, is + ( Y 1 ] Y I a / Y I I - Yat)Vag
cleared (by opening S1 and/or $2 in Fig. 1) t ?
+ (Y12YIa/Y]l -- Ya2)Vbg
so that the current in it is forced to zero, the
voltage Vat on the bus 1 side of $1, for + ( Y~aYla/Y1 ] -- Yaa) Vcg (B-17)
Downloaded from http://iranpaper.ir

39

T h e n Ib a n d Ic are used in eqn. (B-12) X~' = 0.295 Xq = 0.295


t o find the values o f Vabc2. Xkd = 0.13 Xkq = 0.077
Rkd = 0.015 Rkq = 0.015

APPENDIX C = 0.395 T~o = 6.658


X~d = 0.19 T'~o = 0.054
Generator parameters Xo = 0.1475 Tqo 0.43
Based o n the per-unit s y s t e m o f ref. 10,
the g e n e r a t o r p a r a m e t e r s are as f o l o w s :
Ra = 0.0 R2, = 0.06
Xd = 2.5 Xq = 2.5 Rf = 0.000984 R0 = 0.0
Xmd = 2.28 Xmu = 2.28 f = 6 0 . 0 Hz H = 4.0 s

You might also like