Professional Documents
Culture Documents
ir
32
© ® THEORY
33
For the balanced line, only the off-diagonal power flow from the generator, so that the
terms in Zab c change and all of them become generator's accelerating power is relatively
equal to 0.076 + j0.608 p.u. large.
For each of the transient tests, the prefault If the generator's neutral is grounded
initial conditions were taken to be a balanced t h r o u g h some finite reactance, the resultant
three-phase infinite bus voltage of 1 p.u. on swing curve D1 lies between curves D3 and
each phase on Fig. 1. All the shunt faults D4 (for the shunt load concentrated on phase
were applied to the line at a point close to A) and curve D2 lies below D4 for the shunt
the generator terminals. A t t e n t i o n was paid load concentrated on phase B.
to the effect of grounding and ungrounding
the generator's neutral. Temporary SLGF followed by temporary
The static shunt load at the generator line outage
terminals consisted of an unbalanced (21 + In order to evaluate further the effect of
j13)% admittance concentrated on only one asymmetrical shunt and series faults, the pre-
phase which varied from one case study to vious single line to ground fault (SLGF) is
the next. In some cases this load was balanced again assumed to last for 100 ms on phase A
at (7 + j4.3)% on each phase. as before, but instead of simply removing
Before evaluating the effect of a multiple the fault, the faulted phase A is now taken to
fault on the generator's transient stability, be switched out by a circuit breaker, thereby
the effects of the individual faults are con- leaving the generator running on a two-phase
sidered first, one at a time. supply w i t h o u t shunt faults for a further
100 ms before the A phase is reconnected
Temporary single line to ground fault (SLGF) after the fault has been cleared. The outage
The SLGF occurs by far the most often of of the phase A is classified as a series fault.
all fault types and ref. 8 states that it makes For comparative purposes, the SLGF on
up 70% of all faults on lines and feeders. The phase A is replaced by a symmetrical three-
swing curves in Fig. 3 show the generator's phase line to ground fault (3LGF) at the same
transient response for a temporary SLGF location but w i t h o u t a subsequent line
on phase A of the line (lasting for only 100 outage. The resultant swing curves appear in
ms) at its terminals in Fig. 1. It is clear from Fig. 4. Curves D6, D7 and D8 in Fig. 4 are
these swing curves that case D3 (ungrounded the resultant SLGF swing curves and curve
neutral and all shunt load concentrated on D5 applies to the 3LGF case. It is clear that
the A phase) has the worst effect upon the the traditional test of transient stability, the
stability; this happens since the fault short- 3LGF fault with the largest first-peak swing
circuits the shunt load and the increased line curve, still constitutes the most severe shock
voltage drop creates a severe reduction in
110
90
~~<z907050D S ~
8O
70
60 30.
50 0.'0 0,'3 0.6 0.'9 1.'2 1.r5
TIME, SEC
O
' .O ~
0.3 0/6 0.9' r
t.2 T--
1.5 Fig. 4. Rotor angle following a temporary 3LGF or
TIME,SEe temporary SLGF and temporary line outage for
Fig. 3. Rotor angle following a temporary SLGF for grounded and ungrounded neutrals: D5, balanced
ungrounded and grounded neutrals: D1, unbalanced feeder, balanced shunt load, grounded neutral,
line, shunt load on A, grounded neutral; D3, un- 3LGF; D6, unbalanced feeder, shunt load on A,
balanced line, shunt toad on A, ungrounded neutral; ungrounded neutral, SLGF on A; D7, unbalanced
D2, unbalanced line, shunt load on B, grounded feeder, shunt load on A, grounded neutral, SLGF on
neutral; D4, unbalanced line, shunt load on B, un- A; D8, repeat D6 but line outage increased from 100
grounded neutral. ms to 200 ms.
Downloaded from http://iranpaper.ir
34
p u t ed for different values of prefault power Fig. 5. Rotor angle following a permanent line outage
P0 arriving at the infinite bus. T hey show that of phase A. (a) Ungrounded generator neutral: D13,
repeat D10; D14, repeat D l l ; D15 repeat D12.
an ungrounded neutral generator is more (b) Grounded generator neutral: D9, P0 = 0.2, no
severely affected, and t hat in some cases the shunt load; D10, P0 =0.2, balanced shunt load;
generator may settle to a new steady larger Dll, repeat D10, but P0 = 0.4; D12, repeat D10,
r o t o r angle on a two-phase supply. However, but P0 = 0.6.
curves D12 and D15 for larger values of P0
show clear signs o f instability after 10 s, 1.0
even after their first peaks suggested a stable
system. F o r this t y p e of fault, therefore, the
system's ultimate stability cannot be judged
by considering only the first peak of the
CL
0.8
0.6
,~ 0.4.
~
~ / " ~ / /\-j, ,
}'],-, "~
TE12
D5 (for the 3 LGF) in Fig. 4, illustrating t hat Fig. 6. Generator electric t o r q u e following a per-
the asymmetrical single line outage series m a n e n t line o u t a g e o f p h a s e A o n a n unbalanced line
fault is an even more severe disturbance to w i t h g e n e r a t o r n e u t r a l g r o u n d e d : TE9, P0 = 0.2, n o
s h u n t l o a d ( T E l l , P0 = 0.4); T E l 0 , P0 = 0.2, bal-
t h e system than the traditional 3LGF. Figure a n c e d s h u n t load ( T E l 2 , P0 = 0.4).
6 shows the generator t o r q u e variation cor-
responding to the r o t o r angle in Fig. 5(b).
Each t o r q u e curve exhibits a sharp drop in
t o r q u e at the m o m e n t the line is switched the auto-reclosing operation of a single-pole
out, but the to r que then rises and falls in circuit breaker, then some or all of these
h a r m o n y with the r o t o r angle. four unstable cases may well turn o u t to be
Whether or n o t cases D12 and D15 go un- stable, and each case would have to be studied
stable depends n o t only on the initial condi- on its own merits.
tions, such as the value of P0, but also on the The importance of these results can be
duration o f the line outage (which in these summarized by saying that at low pow er
cases was taken to be a p e r m a n e n t outage). levels a synchronous generator will remain
If the outage time were to be reduced t o a in synchronism after a line outage. However,
finite time o f a few hundred ms, representing at higher power levels it will drift o u t of
Downloaded from http://iranpaper.ir
35
,125]01 °7. = / /
I10 -
lO0-
~
j~90-
o
< 80-
I---
~ 70-
60- 5O
[ I ' I ' I I ' I ' i , t , i , i ' %
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5
TIME, SEC
lIME, SEC
Fig. 7. R o t o r angle m e a s u r e d o n a m i c r o a l t e r n a t o r
Fig. 9. Rotor angle after a permanent SLGF on phase
a f t e r o n e o f t h e p h a s e lines has b e e n p e r m a n e n t l y
A followed by a permanent line outage on an unbal-
removed.
anced line: D20, grounded neutral, shunt load on A,
P0 = 0.6; D21, grounded neutral, shunt load on B,
110 • P0--0.6; D22, repeat D20 but with ungrounded
neutral; D23, repeat D21 but with ungrounded neu-
100 -
em tral.
90. D17
,..,/
80. 160
j
I
N 7o.
°~.~ ~ i : / I , ' ~ " " ~ ' Y : . . . . "~''--~--' 140
I !:, .' "
60-
50-
OI ' i
1
,
2
i , i
3
,
4
i ,
5
i , 6/ ,
7
i , i
8
, i
9
, i
10
'= 120
1oo
~ 80
o !5 92°
TIME, SEC 6O F o~7
Fig. 8. Rotor angle following a temporary SLGF on
phase A cleared by a permanent line outage on an
unbalanced line: D16, grounded neutral, shunt load 0' 2' ,' 6' ; 1'0 1'2 1', ;6
on A, P0 = 0.4 (D18, ungrounded neutral); D17, TIME, (SEC)
grounded neutral, shunt load on B, P0 = 0.4 (D19, Fig. 10. R o t o r angle a f t e r a p e r m a n e n t S L G F o n
ungrounded neutral). p h a s e A f o l l o w e d b y a p e r m a n e n t line o u t a g e o n a n
u n b a l a n c e d line: D24, r e p e a t D 2 0 b u t P0 = 0.4; D25,
r e p e a t D 2 1 b u t P0 = 0.4; D26, r e p e a t D 2 4 b u t
stability several swing cycles a f t e r t h e first n e u t r a l u n g r o u n d e d ; D27, r e p e a t D 2 5 b u t n e u t r a l un-
o s t e n s i b l y stable swing c y c l e [ 9 ] ; this has grounded.
actually been confirmed by practical mea-
surements on a microalternator and the u n g r o u n d e d n e u t r a l and c o n c e n t r a t i o n o f t h e
results a p p e a r in Fig. 7. s h u n t l o a d o n p h a s e B.
All f o u r cases c o n s i d e r e d in Fig. 8 clearly
Temporary SLGF followed by a permanent r e a c h a stable s t a t e c o n d i t i o n .
line outage (multiple fault)
The fault conditions of a t e m p o r a r y S L G F Permanent SLGF followed by a permanent
o n l y (results in Fig. 3) a n d o f a p e r m a n e n t line outage
line o u t a g e o n l y (results in Fig. 5) are n o w This case s t u d y is a direct e x t e n s i o n o f t h e
c o m b i n e d t o r e p r e s e n t t h e case w h e r e t h e o n e a b o v e b y s i m u l a t i n g t h e case w h e r e an
S L G F causes t h e f a u l t e d line t o be o p e n e d , S L G F o n t h e line, b u t close t o t h e g e n e r a t o r
b u t , f o r s o m e r e a s o n or o t h e r , it is n o t t e r m i n a l s , causes t h e infinite bus end circuit
s w i t c h e d b a c k in again. As b e f o r e , t h e S L G F b r e a k e r in t h e f a u l t e d line t o trip, b u t n o t t h e
o n p h a s e A lasts f o r o n l y 1 0 0 m s , f o l l o w e d o n e at t h e g e n e r a t o r end. This results in t h e
b y its r e m o v a l a n d a p e r m a n e n t o u t a g e o f SLGF remaining permanently connected,
p h a s e A. This is classified as a m u l t i p l e fault. even a f t e r t h e line is s w i t c h e d o u t , a n d in
F o u r swing curves are p r e s e n t e d in Fig. 8 a d d i t i o n it is a s s u m e d t h a t t h e line r e m a i n s
to illustrate t h e e f f e c t o f g e n e r a t o r n e u t r a l p e r m a n e n t l y s w i t c h e d o u t , giving rise t o
g r o u n d i n g a n d t h e p o s i t i o n o f a single-phase a n o t h e r t y p e o f m u l t i p l e fault.
s h u n t load; t h e w o r s t case ( o n first swing T h e swing curves in Fig. 9 clearly s h o w all
e v a l u a t i o n ) is clearly t h e c o m b i n a t i o n o f an f o u r cases t o be u n s t a b l e , and again D 2 2 and
Downloaded from http://iranpaper.ir
36
37
Vt0pnT are the sequence component voltages where Zab¢2 represents the feeder impedance
at the terminals of the machine. matrix for the line length L - - X , Iabc2 rep-
The positive-sequence generator current Igp resents the current in it and Vfabc the voltages
is given by at the fault location. Iab¢2 in turn is related
to the motor and shunt load currents by
Igp = (E" -- Vtp)/(Ra + jX~') (A-l)
and the positive-sequence power developed by labc2 = Iabeg + l a b e l (B-l)
the generator by Similarly,
Pgp -- R e a l { E " I g p * } (A-2) Vfabc -- Vabc I -- Zabe l/abe I (B-2)
The torque associated with the developed where Zabol and label apply to line length X,
power is and
Tgp = Pgpcoz/°-)n (A-3) /abel = labc2 +/fabc (B-3)
where coz is the synchronous speed in rad s-1, where
and COnthe instantaneous speed in rad s-1.
Similarly, the following expressions apply Ifabc = YfabcVfabc (B-4)
to the negative- and zero-sequence circuits: N o w labcg and label Can, in turn, be defined
in terms of the generator and the shunt load
Ign = - - Y t n l ( R a + R2n + jXn) (A-4)
admittances and their terminal voltages as
Igo = - - V t o / ( R o + jX0) (A-5) follows:
Tg. = Ilgnl:/R2n (A-6) l a b e l = YabcLVabc2 (B-5)
Tgo = Ilgol2/Ro (A-7) and
The equation for the motion of the rotor is labcg = Yabcg[ V a b c 2 - Vabcg] (B-6)
given by
Thus,
PCOm = (Tpm - - Tgp - - Tgn - - Tgo)/(2H/coz)
labc2 = label +/abcg (B-7)
(A-8)
Combination of eqns. (B-7) yields the voltage
where H is the inertia constant in seconds, Vfab¢ at the fault location:
and Tpm the prime mover driving torque.
For the purpose of this investigation, the [ U + Mlf] Vfabe -- Vabc I + Mlg Vabcg
prime mover o u t p u t power Ppm is assumed to -- KVabc2 (B-8)
remain constant at its pre<listurbance value
during disturbances, hence The final equation of Vfabe is
Tp~n = Ppm coz/ (.Om (A-9) Vfabc -- J[ Vabcl "t" MlgVabcg - - KVabc2] (B-9)
K = Zabcl[Yabcg + YabcL]
APPENDIX B By combining eqns. (B-3), (B-4) and (B-9)
and eliminating the voltage Vfabc ,
Network equations Vabc2 = J{[U + J] [Mlg + M1L] + M2g + M 2 L } - l
The abc voltage vector at node 2 in Fig. 1 X [ V a b c l "l- M l g V a b c g ]
is given by
or
38
39