You are on page 1of 4

YORK® MODEL YK

HEAT-RECOVERY

Optimize your
CHILLER

facility’s energy
utilization with free heat
Reduce energy consumption
with sustainable technology
Take a step forward to reducing your The double-bundle condenser of a heat-recovery chiller
facility’s environmental footprint contains the heating condenser and the tower condenser,
Identifying technologies that can reduce the environmental as shown in Figure 1. The warm refrigerant gas from the
impact of your building at a reasonable cost is one of the compressor flows over both tube bundles.
biggest challenges facing commercial, institutional, and
industrial facilities today. The flow of heat in the double-bundle condenser is controlled
by a cooling-tower bypass valve (see Figure 2 on page 4).
As a major user of energy, heating and cooling systems hold The valve receives signals from a temperature sensor in
a key to resolving this challenge. That’s why Johnson Controls the heating circuit.
offers a solution that addresses today’s pressing environmental
and energy issues—the YORK® heat-recovery chiller. When heating is required, the tower-bypass valve directs the
water in the tower-condenser circuit to bypass the cooling
Substantial heat energy is available tower. Because the circuit cannot exhaust its heat, it gets
Your chillers not only remove heat from your building’s warmer and warmer, until it is the same temperature as the
conditioned space, the compressors add up to 25% more refrigerant leaving the compressor, at which point it can no
thermal energy that must also be removed. This heat is longer absorb any more heat, effectively becoming inactive.
rejected by the cooling towers, which emit a tremendous
amount of heat energy into the atmosphere. In fact, ASHRAE The refrigerant heat now passes into the water flowing
Standard 90.1 6.5.6.2 estimates that a facility with a year- through the heating condenser, which carries the heat to the
round cooling load will reject a minimum of 6,000 MBH heating load or to a booster boiler.
(1,800 kW) into the ambient air.
When less heat is required, the tower-bypass valve begins
To take advantage of that vast amount of free heat energy, to open, which causes more of the condenser heat to flow
Johnson Controls offers heat-recovery technology on the into the tower-condenser circuit, and less heat flows into the
YORK Model YK centrifugal chillers ranging from 250 to 2,800 heating circuit.
tons of refrigeration (900–9,800 kW), which can provide from
1,200 to 40,000 MBH (400–11,700 kW) heating capacity.
Compressor
Heating condenser
Heat-recovery Chiller Specification
Evaporated
Tower refrigerant gas
Cooling Capacity Range 250–2,800 Tons (900–9,800 kW) condenser
Heating Capacity Range 1,200–40,000 MBH (400–11,700 kW)
Max. Hot Water Temperature 110°F (43°C) Evaporator
Refrigerant R-134a

Understanding heat-recovery chiller technology


A YORK Model YK heat-recovery chiller puts your facility’s
heat byproduct to work. Consequently, it saves energy by
decreasing the load on, and the fuel consumption of, your
facility’s boilers.

In a typical multiple-chiller plant employing heat recovery,


Condensed Expansion orifice
one chiller will be designed for heat recovery. It will usually refrigerant liquid
be the first chiller activated when cooling is required.

Figure 1: Refrigerant flow in a heat-recovery chiller.

2
Heat-recovery benefits

Facility Types Heat-Recovery Uses Facility Types Heat-Recovery Uses


Hospitals/Medical Centers The recovered heat can be Manufacturing Manufacturing facilities can
used to control humidity take advantage of process
in sensitive sites, like heat supplied by a heat-
laboratories and hospital recovery chiller for their
operating rooms. process operations.

Hotels/Resorts The recovered heat can be Educational Education facilities—


used to reheat the air in dormitories, athletic
a hotel in a cooler climate. complexes, and food
Hotels can also utilize the services—can utilize heat
waste heat to preheat recovery to preheat
domestic hot water for domestic hot-water
pools, hot tubs, showers, needs for laundry, showers,
and laundry. cooking, and dishwashing.

Numerous applications
Practically any chiller plant that has simultaneous heating and date. HFC-134a also has favorable thermodynamic properties
cooling needs, can utilize a heat-recovery chiller. Common and specific volumes that are ideal for heat-recovery duty.
applications include hospitals and medical centers, hotels and
resorts, manufacturing facilities, and educational facilities. High heating COPs
The coefficient of performance (COP) of a heat-recovery
Assured equipment selection chiller in heating mode is outstanding. For example, with
The expertise of Johnson Controls in understanding your chilled-water temperatures of 54°–44°F (12°–7°C)
building environment, combined with YORK chiller-applications and tower water of 85°–95°F (29–35°C), the cooling COP
experience, provides the best assurance of a proper heat- could be 6.3. With hot water from 95°–105°F (35°–41°C),
recovery chiller selection. To produce the greatest energy the combined cooling and heating COP could be 11.4.
savings, we analyze the chilled-water plant to take full advantage
of your load profiles. The result is a solution that fits your Low sound levels
budget while reducing your facility's energy-use profile. Patented YORK OptiSound™ control technology is standard
on YORK heat-recovery chillers. This technology handles
Energy use and cost savings the sound generated by chillers operating with high-
A YORK heat-recovery chiller uses less total energy than head pressures and reduced loads, which are commonly
separate cooling and heating equipment by taking advantage encountered in the heat-recovery operation. With the
of “free” condenser heat that would otherwise be lost through OptiSound control, part-load sound levels do not exceed
the cooling towers. In effect, a heat-recovery chiller lets full-load sound levels.
you do “double-duty”—cooling and heating with the
same piece of equipment. This is more economically and Complies with ASHRAE 90.1
environmentally friendly than burning fossil fuels or using ASHRAE 90.1, 6.3.6.2—Heat Recovery for Service Water
electric-resistance heaters. Heating covers the efficient use of heat-recovery technology
in buildings. Application of a YORK heat-recovery chiller will
Environmentally friendly refrigerant meet and exceed these exacting requirements to ensure
YORK heat-recovery chillers utilize HFC-134a refrigerant, you’re getting maximum energy savings.
which has zero ozone-depletion potential and no phase-out

3
Case study:
Global medical manufacturer
140°F
(60°C)
Heat
Exchanger
115°F
(46°C)
TC
Boiler
BWP

130°F 105°F TE
Cooling Tower
(54°C) (41°C)

Tower
Heating Condenser Bypass valve
TCV
95°F 105°F
(35°C) (41°C)

HWP Tower Condenser


Heating Load
105°F
(41°C)

Compressor
CWP

TXV Hot
Gas
Motor

42°F
(6°C)

Evaporator

52°F
(11°C)
ChWP

Figure 2: Heat-recovery chiller integrated with boiler loop. Cooling Load

Fully utilizing recovered heat using 105°F (41°C) water from the chiller, enabling energy-cost
A medical manufacturing facility with simultaneous cooling reductions year-round.
and heating requirements demonstrates the substantial energy
savings available with a YORK heat-recovery chiller. In this case, the chiller is running in heat-recovery mode
year-round. When operating in heat-recovery mode (cooling
In the configuration shown in Figure 2, heat that would otherwise and heating simultaneously), the cooling capacity is 405 tons
be lost is recovered in the heating condenser, to produce (1,424 kW). The combined cooling and heating COP value
105°F (41°C) water. In the winter, as the water flows through is 10.2. If the chiller would operate in cooling-only mode,
the heat exchanger, the booster boiler adds enough heat it would have a capacity of 425 tons (1,491 kW) with a 5.7 COP.
to raise its temperature to 130°F (54°C). The hot water is
distributed through the building to meet the comfort-heating For more information on YORK Model YK heat-recovery
needs of the facility. During the summer, the boiler is not chillers, contact your nearest Johnson Controls office.
required. The building’s heating needs can be satisfied Or visit us on the Internet at www.johnsoncontrols.com.

Printed on recycled paper.

PUBL-6317 (510)
© 2010 Johnson Controls, Inc.  P.O. Box 423, Milwaukee, WI 53201  Printed in USA
www.johnsoncontrols.com

You might also like